| number = ML14139A100
| number = ML14139A100
| issue date = 05/19/2014
| issue date = 05/19/2014
| title = LAR Ultimate Heat Sink (TAC No. MF1780)
| title = LAR Ultimate Heat Sink
| author name = Thadani M C
| author name = Thadani M
| author affiliation = NRC/NRR/DORL/LPLI-1
| author affiliation = NRC/NRR/DORL/LPLI-1
| addressee name = Craft W D
| addressee name = Craft W
| addressee affiliation = Dominion Nuclear Connecticut, Inc
| addressee affiliation = Dominion Nuclear Connecticut, Inc
| docket = 05000423
| docket = 05000423
| license number = NPF-049
| license number = NPF-049
| contact person = Thadani M C, NRR/DORL/LPLI-1
| contact person = Thadani M, NRR/DORL/LPLI-1
| case reference number = TAC MF1780
| case reference number = TAC MF1780
| document type = E-Mail, Request for Additional Information (RAI)
| document type = E-Mail, Request for Additional Information (RAI)
| page count = 1
| page count = 1
| project = TAC:MF1780
| project = TAC:MF1780
| stage = Other
}}
}}


=Text=
=Text=
{{#Wiki_filter:From: Thadani, Mohan Sent: Monday, May 19, 2014 9:59 AM To: Wanda D Craft (Generation - 6) (wanda.d.craft@dom.com) Cc: Purciarello, Gerard Subject: LAR RE: Ultimate Heat Sink. Wanda:  By letter dated May 3, 2013, Dominion Nuclear Connecticut, Inc. requested an amendment to revise the Millstone Power Station, Unit 3 Technical Specification 3/4 .7.5, "Ultimate Heat Sink,"
{{#Wiki_filter:From:                     Thadani, Mohan Sent:                     Monday, May 19, 2014 9:59 AM To:                       Wanda D Craft (Generation - 6) (wanda.d.craft@dom.com)
to increase the current ultimate heat sink (UHS) water temperature limit from 75 °F to 80°F.
Cc:                       Purciarello, Gerard


The NRC staff has reviewed the request and identified that the license's request for change to Surveillance Requirement SR 4.7.5 does not include the most current revision to SR 4.7.5.
==Subject:==
The NRC staff requests that the licensee provide a response to the following RAI within 30 days from the date of this request.  
LAR RE: Ultimate Heat Sink.
Wanda:
By letter dated May 3, 2013, Dominion Nuclear Connecticut, Inc. requested an amendment to revise the Millstone Power Station, Unit 3 Technical Specification 3/4 .7.5, Ultimate Heat Sink, to increase the current ultimate heat sink (UHS) water temperature limit from 75 °F to 80°F.
The NRC staff has reviewed the request and identified that the licenses request for change to Surveillance Requirement SR 4.7.5 does not include the most current revision to SR 4.7.5.
The NRC staff requests that the licensee provide a response to the following RAI within 30 days from the date of this request.
Best regards, Mohan C Thadani Senior Project Manager Millstone, Ginna, and Constellation Fleet Plant Licensing Branch I-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation (301) 415-1476 Mohan.Thadani@nrc.gov MILLSTONE POWER STATION, UNIT 3 LICENSE AMENDMENT REQUEST PROPOSED TECHNICAL SPECIFICATIONS AMENDMENT SURVEILLANCE REQUIREMENT 3/4.7.5, ULTIMATE HEAT SINK DOCKET NOS. 50-423


Best regards,  Mohan C Thadani Senior Project Manager Millstone, Ginna, and Constellation Fleet Plant Licensing Branch I-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation (301) 415-1476      Mohan.Thadani@nrc.gov    ____________________________________________________________________________
===RAI 1===
________________________________________
The license amendment request (LAR) of May 3, 2013 requests a change to Surveillance Requirement (SR) 4.7.5, which does not now include the most current revision of SR 4.7.5 The licensee is requested to provide the proposed change to SR 4.7.5 using the current revision.
MILLSTONE POWER STATION, UNIT 3 LICENSE AMENDMENT REQUEST  PROPOSED TECHNICAL SPECIFICATIONS AMENDMENT SURVEILLANCE REQUIREMENT 3/4.7.5, ULTIMATE HEAT SINK  DOCKET NOS. 50-423  RAI 1 The license amendment request (LAR) of May 3, 2013 requests a change to Surveillance Requirement (SR) 4.7.5, which does not now include the most current revision of SR 4.7.5  


The licensee is requested to provide the proposed change to SR 4.7.5 using the current revision.
===RAI 2===
In the LAR for LCO 3.7.5 and SR 4.7.5, the licensee changed the parameter to be monitored from average water temperature to water temperature.
The licensee is requested to explain the technical reasons and justify changing the parameter to be monitored as explained above.


RAI 2 In the LAR for LCO 3.7.5 and SR 4.7.5, the licensee changed the parameter to be monitored from "average water temperature" to "water temperature."
===RAI 3===
The licensee is requested to explain the technical reasons and justify changing the parameter to be monitored as explained above. 
In the licensees letter, dated January 15, 2014, as a response to request for additional information (RAI) 4, regarding the ESF air conditioning unit (3HVQ ACUS1A, 1B, 2A, and 2B) condensers, the licensee explained the seemingly low service water flow rate of 25 gpm and 33.2 gpm by allowing the service water (SW) T across the heat exchangers to increase to transfer the heat for condensing the R-22 Freon. With a SW inlet temperature of 80°F, the vendor data sheet has a T of 15.7°F, while the licensees calculated Ts are 29.5°F and 24.4°F. The licensee justified the seemingly low SW flow rate by allowing higher SW Ts. The licensee did not address the effect of the corresponding higher SW temperatures across the condensers on the condensing effects of the R-22, but called the results reasonable.
 
Provide definitive statements, as appropriate, regarding the operability of the ESF air conditioning units to perform their safety functions and remove design heat loads under accident conditions with an 80°F SW inlet temperature and the high SW Ts and low flow rates described in your RAI response. Describe any adverse effect on the R-22 condensing function with the higher SW T and the ability of the ESF units to perform their safety functions.}}
RAI 3 In the licensee's letter, dated January 15, 2014, as a response to request for additional information (RAI) 4, regarding the ESF air conditioning unit (3HVQ ACUS1A, 1B, 2A, and 2B) condensers, the licensee explained the seemingly low service water flow rate of 25 gpm and 33.2 gpm by allowing the service water (SW) T across the heat exchangers to increase to transfer the heat for condensing the R-22 Freon. With a SW inlet temperature of 80°F, the vendor data sheet has a T of 15.7°F, while the licensee's calculated T's are 29.5°F and 24.4°F. The licensee justified the seemingly low SW flow rate by allowing higher SW Ts. The licensee did not address the effect of the corresponding higher SW temperatures across the condensers on the condensing effects of the R-22, but called the results "reasonable."    Provide definitive statements, as appropriate, regarding the operability of the ESF air conditioning units to perform their safety functions and remove design heat loads under accident conditions with an 80°F SW inlet temperature and the high SW Ts and low flow rates described in your RAI response. Describe any adverse effect on the R-22 condensing function with the higher SW T and the ability of the ESF units to perform their safety functions.    
 
}}

Latest revision as of 21:03, 5 February 2020

LAR Ultimate Heat Sink
ML14139A100
Person / Time
Site: Millstone Dominion icon.png
Issue date: 05/19/2014
From: Thadani M
Plant Licensing Branch 1
To: Craft W
Dominion Nuclear Connecticut
Thadani M, NRR/DORL/LPLI-1
References
TAC MF1780
Download: ML14139A100 (1)


Text

From: Thadani, Mohan Sent: Monday, May 19, 2014 9:59 AM To: Wanda D Craft (Generation - 6) (wanda.d.craft@dom.com)

Cc: Purciarello, Gerard

Subject:

LAR RE: Ultimate Heat Sink.

Wanda:

By letter dated May 3, 2013, Dominion Nuclear Connecticut, Inc. requested an amendment to revise the Millstone Power Station, Unit 3 Technical Specification 3/4 .7.5, Ultimate Heat Sink, to increase the current ultimate heat sink (UHS) water temperature limit from 75 °F to 80°F.

The NRC staff has reviewed the request and identified that the licenses request for change to Surveillance Requirement SR 4.7.5 does not include the most current revision to SR 4.7.5.

The NRC staff requests that the licensee provide a response to the following RAI within 30 days from the date of this request.

Best regards, Mohan C Thadani Senior Project Manager Millstone, Ginna, and Constellation Fleet Plant Licensing Branch I-1 Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation (301) 415-1476 Mohan.Thadani@nrc.gov MILLSTONE POWER STATION, UNIT 3 LICENSE AMENDMENT REQUEST PROPOSED TECHNICAL SPECIFICATIONS AMENDMENT SURVEILLANCE REQUIREMENT 3/4.7.5, ULTIMATE HEAT SINK DOCKET NOS. 50-423

RAI 1

The license amendment request (LAR) of May 3, 2013 requests a change to Surveillance Requirement (SR) 4.7.5, which does not now include the most current revision of SR 4.7.5 The licensee is requested to provide the proposed change to SR 4.7.5 using the current revision.

RAI 2

In the LAR for LCO 3.7.5 and SR 4.7.5, the licensee changed the parameter to be monitored from average water temperature to water temperature.

The licensee is requested to explain the technical reasons and justify changing the parameter to be monitored as explained above.

RAI 3

In the licensees letter, dated January 15, 2014, as a response to request for additional information (RAI) 4, regarding the ESF air conditioning unit (3HVQ ACUS1A, 1B, 2A, and 2B) condensers, the licensee explained the seemingly low service water flow rate of 25 gpm and 33.2 gpm by allowing the service water (SW) T across the heat exchangers to increase to transfer the heat for condensing the R-22 Freon. With a SW inlet temperature of 80°F, the vendor data sheet has a T of 15.7°F, while the licensees calculated Ts are 29.5°F and 24.4°F. The licensee justified the seemingly low SW flow rate by allowing higher SW Ts. The licensee did not address the effect of the corresponding higher SW temperatures across the condensers on the condensing effects of the R-22, but called the results reasonable.

Provide definitive statements, as appropriate, regarding the operability of the ESF air conditioning units to perform their safety functions and remove design heat loads under accident conditions with an 80°F SW inlet temperature and the high SW Ts and low flow rates described in your RAI response. Describe any adverse effect on the R-22 condensing function with the higher SW T and the ability of the ESF units to perform their safety functions.