{{#Wiki_filter:EOP: P-TURB.1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 1 of 12 ROCHESTER GAS AND ELECTRIC ORPORATION GINNA STAT ON CONTROLLED COPY BER TECHNICAL REVIEW PORC VIEW DATE P T SUPERINTENDENT EFF TIVE DATE CAT G RY 1.0 REVIEWED BY: 9306040i5i 930524 PDR ADQCK 05000244 P PDR L  
{{#Wiki_filter:EOP:         TITLE:
\~EOP: P-TURB.'1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 2 of 12 A.PURPOSE-This procedure provides the necessary instructions to control the plant following a turbine trip without a reactor trip required.B.ENTRY CONDITIONS/SYMPTOMS 1.ENTRY CONDITIONS
REV: 7 P-TURB.1           TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 1 of 12 ROCHESTER GAS AND ELECTRIC   ORPORATION GINNA STAT ON CONTROLLED COPY     BER TECHNICAL REVIEW PORC   VIEW DATE P   T SUPERINTENDENT EFF TIVE DATE CAT G RY 1.0 REVIEWED BY:
-This procedure is entered from: a.AP-CW.1, LOSS OF A CIRC WATER PUMP, or, b.AP-ELEC.l, LOSS OF 12A AND/OR 12B TRANSFORMER, or, c~AP FW 1 g PART I AL OR COMPLETE LOSS OF MA I N FEE DWATER g or, d.AP-TURB.2, AUTOMATIC TURBINE RUNBACK, or, e.AP-TURB.3, TURBINE VIBRATIONS, or, f.AP-TURB.4, LOSS OF CONDENSER VACUUM, when power is less than P-9 and the turbine trips without a Rx trip.2.SYMPTOMS-The symptoms of TURBINE TRIP WITHOUT RX TRIP REQUIRED are: a~b.c~d.e.gi Annunciator K-l, THRUST BEARING FAILURE, lit, or Annunciator K-9, TURBINE BEARING OIL LO PRESS TRIP 6 psi, lit, or Annunciator K-17, TURBINE LOW VACUUM TRIP 20" HG, lit, or Annunciator K-18, MAIN FEEDWATER PUMPS TRIPPED, lit, or Annunciator K-26, GENERATOR LOCKOUT RELAY, lit, or Annunciator K-25, TURBINE OVERSPEED ALERT 1980 RPM, lit, or Annunciator F-21, COND HI PRESS 20" HG OR LOSS OF BOTH CIRC WTR PMPS, lit, or h.Annunciator K-3, AMSAC ACTUATED, lit.
9306040i5i 930524 PDR     ADQCK 05000244 P                   PDR     L
~l T EOP: P-TURB;1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 3 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED***************.**************************CAUTION IF, AT ANY TIME DURING THIS PROCEDURE, A REACTOR TRIP OR SI OCCURS, E-O, REACTOR TRIP OR SAFETY INJECTION, SHALL BE PERFORMED.
1 Verify Turbine Stop Valves-CLOSED Manually trip turbine.IF turbine stop valves can NOT be closed, THEN close both MSIVs.IF reactor power greater than 8%with both MSIVs closed, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.


EOP: P-'TURB;1 T!TLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 4 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED*****************************************CAUTION PRZR PRESSURE LOW PRESSURE TRIP IS RATE SENSITIVE, THEREFORE, MONITOR PRESSURE WHEN REDUCING RCS TEMPERATURE.
\~
*****************************************NOTE: Automatic rod control is desired, if available.
EOP:         TITLE:
2 Check Reactor, Power: a.NIS intermediate ranges-ABOVE THE POINT OF ADDING HEAT (APPROXIMATELY 2.5xlO 6 AMPS)a.Go to Step 3.b.Verify control rods driving in to reduce reactor power in AUTO b.Perform the following:
REV  7 P-TURB.'1          TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 2  of 12 A. PURPOSE    - This procedure provides the necessary    instructions to control the plant following      a turbine  trip  without a reactor trip required.
l)Ensure ROD CONTROL BANK SELECTOR switch to MANUAL 2)Insert rods as necessary to reduce reactor power.c.Borate as necessary to maintain control rods above rod insertion limits EOP: P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 5 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 3 Monitor S/G Levels: a.Levels-GREATER THAN 30%OR INCREASING a.IF MFW regulating and bypass valves NOT controlling in AUTO, THEN place controllers in MANUAL and restore narrow range level to program.IF S/G level can NOT be restored, THEN trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
B. ENTRY CONDITIONS/SYMPTOMS
b.Levels-TRENDING TO PROGRAM b.IF S/G level above program and increasing uncontrolled, THEN place controller(s) in MANUAL and decrease flow as necessary.
: 1. ENTRY CONDITIONS  This    procedure  is entered from:
IF flow can NOT be controlled, THEN perform the following:
: a. AP-CW.1, LOSS OF A CIRC WATER PUMP,  or,
l)Trip the reactor.2)Stop the running MFW pump.3)Close MFW pump discharge valves.4)Go to E-O, REACTOR TRIP OR SAFETY INJECTION.
: b. AP-ELEC.l,  LOSS OF 12A AND/OR 12B TRANSFORMER,    or, c ~                I                          I AP FW 1 g PART AL OR COMPLETE LOSS OF MA N FEE DWATER g or,
EOP: P.~TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 6 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 4 Verify Proper Operation Of Steam Dump: a.Verify annunciator G-15, STEAM DUMP ARMED-LIT a.Place steam dump mode selector switch to MANUAL.b.Condenser steam dump operating in AUTO b.IF steam dump NOT available, THEN perform the following:
: d. AP-TURB.2, AUTOMATIC TURBINE RUNBACK,    or,
1)Adjust S/G ARV setpoints to 1005 psig and verify proper operation.
: e. AP-TURB.3, TURBINE VIBRATIONS,  or,
2)IF power is greater than 8%, THEN ensure reactor trip and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
: f. AP-TURB.4, LOSS OF CONDENSER VACUUM, when power is less than P-9 and the turbine trips without a Rx trip.
c.Tavg-TRENDING TO PROGRAM c.IF Tavg can NOT be controlled, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
: 2. SYMPTOMS    The symptoms of TURBINE TRIP WITHOUT RX TRIP REQUIRED  are:
5 Check PRZR Pressure-TRENDING TO 2235 PSIG IF PRZR pressure can NOT be controlled, THEN refer to AP-PRZR.1, ABNORMAL PRESSURIZER PRESSURE.
a ~  Annunciator K-l,  THRUST BEARING FAILURE,    lit, or
EOP: P-TURB;1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 7 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 6 Check PRZR Level: a.Level-GREATER THAN 13%a.Perform the following:
: b. Annunciator K-9,  TURBINE BEARING OIL LO PRESS TRIP 6 psi,  lit, or c    Annunciator K-17,  TURBINE LOW VACUUM TRIP 20" HG,
1)Place loop B cold leg isolation valve to REGEN Hx (AOV-427)switch to CLOSE.2)Place letdown orifice valve switches to CLOSE (AOV-200A, AOV-200B, and AOV-202).3)Verify excess letdown isolation valve (AOV-310)closed.4)Ensure PRZR heaters off.5)Control charging to restore PRZR level greater than 13%.6)WHEN PRZR level greater than 13%, THEN restore letdown.b.Level-TRENDING TO PROGRAM'b.Increase charging flow as necessary to restore PRZR level to program.  
                      ~
lit, or
: d. Annunciator  K-18, MAIN FEEDWATER PUMPS TRIPPED, lit, or
: e. Annunciator K-26,  GENERATOR LOCKOUT RELAY,    lit, or Annunciator K-25,  TURBINE OVERSPEED ALERT 1980 RPM, lit, or gi    Annunciator F-21,                20" CIRC WTR PMPS,  lit, or HI PRESS COND                HG OR LOSS OF BOTH
: h. Annunciator K-3,  AMSAC ACTUATED,  lit.
 
~l T
 
EOP:            TITLE:
REV  7 P-TURB;1               TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 3  of 12 STEP      ACTION/EXPECTED RESPONSE          RESPONSE NOT OBTAINED CAUTION IF,  AT ANY TIME DURING THIS PROCEDURE, A REACTOR TRIP OR  SI OCCURS,  E-O, REACTOR  TRIP OR SAFETY INJECTION, SHALL BE PERFORMED.
1  Verify Turbine Stop Valves            Manually  trip turbine.
CLOSED IF turbine stop valves can NOT be closed, THEN close both MSIVs.
IF reactor power greater than  8%
with both MSIVs closed, THEN manually trip the reactor and  go to E-O, REACTOR TRIP  OR SAFETY INJECTION.
 
EOP:            T!TLE:
REV: 7 P-'TURB; 1            TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 4   of 12 STEP       ACTION/EXPECTED RESPONSE             RESPONSE NOT OBTAINED CAUTION PRZR PRESSURE LOW PRESSURE TRIP IS RATE   SENSITIVE, THEREFORE, MONITOR PRESSURE WHEN REDUCING RCS TEMPERATURE.
NOTE:   Automatic rod control is desired,   if available.
2 Check Reactor, Power:
: a. NIS intermediate ranges   - ABOVE       a. Go to Step 3.
THE POINT OF ADDING HEAT (APPROXIMATELY 2.5xlO 6 AMPS)
: b. Verify control rods driving in         b. Perform the following:
to reduce reactor power in AUTO l) Ensure ROD CONTROL BANK SELECTOR switch to MANUAL
: 2) Insert rods as necessary   to reduce reactor power.
: c. Borate as necessary   to maintain control rods   above rod insertion limits
 
EOP:
REV: 7 P-TURB;1           TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 5   of 12 STEP     ACTION/EXPECTED RESPONSE       RESPONSE   NOT OBTAINED 3 Monitor S/G Levels:
: a. Levels - GREATER THAN 30% OR     a. IF   MFW regulating and bypass INCREASING                          valves   NOT controlling in AUTO, THEN place controllers in     MANUAL and restore narrow range level to program.
IF S/G level can NOT be restored, THEN trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
: b. Levels - TRENDING TO PROGRAM     b. IF S/G level above program and increasing uncontrolled,     THEN place controller(s) in MANUAL and decrease flow as necessary.
IF flow can NOT be controlled, THEN   perform the following:
l) Trip the reactor.
: 2) Stop the running     MFW pump.
: 3) Close   MFW pump discharge valves.
: 4) Go to E-O, REACTOR TRIP OR SAFETY INJECTION.
 
EOP:
REV: 7 P.~TURB; 1           TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 6     of 12 STEP       ACTION/EXPECTED RESPONSE       RESPONSE NOT OBTAINED 4 Verify Proper Operation       Of Steam Dump:
: a. Verify annunciator G-15, STEAM a. Place steam   dump mode   selector DUMP ARMED  - LIT                    switch to   MANUAL.
: b. Condenser steam   dump operating b. IF steam dump NOT available, in AUTO                              THEN perform the following:
: 1) Adjust S/G ARV setpoints to 1005 psig and verify proper operation.
: 2) IF power is greater than 8%,
THEN   ensure reactor trip and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
: c. Tavg - TRENDING TO PROGRAM       c. IF Tavg can NOT be controlled, THEN manually trip the reactor and go to E-O, REACTOR   TRIP OR SAFETY INJECTION.
5 Check PRZR Pressure                 IF PRZR pressure can NOT be TRENDING TO 2235 PSIG                controlled,   THEN refer to AP-PRZR.1,   ABNORMAL PRESSURIZER PRESSURE.
 
EOP:             TITLE:
REV: 7 P-TURB;1               TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 7   of 12 STEP     ACTION/EXPECTED RESPONSE           RESPONSE NOT OBTAINED 6   Check PRZR Level:
: a. Level - GREATER THAN 13%         a. Perform the   following:
: 1) Place loop   B cold leg isolation valve to     REGEN Hx (AOV-427) switch to CLOSE.
: 2) Place letdown   orifice valve switches to   CLOSE (AOV-200A, AOV-200B, and AOV-202).
: 3) Verify excess letdown isolation valve (AOV-310) closed.
: 4) Ensure PRZR   heaters   off.
: 5) Control charging to restore PRZR level greater than     13%.
: 6) WHEN PRZR level greater than 13%, THEN restore letdown.
: b. Level -   TRENDING TO PROGRAM     'b. Increase charging flow as necessary to restore PRZR level to program.
 
EOP:            T1jLE:
REV    7 P-TURB;1                TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 8  of 12 STEP      ACTION/EXPECTED RESPONSE            RESPONSE  NOT OBTAINED 7  Check  MFW    System:
: a. Verify MFW regulating      and bypass a. Place  MFW  regulating  and bypass valves    - OPERATING IN AUTO              valve controllers in    MANUAL and restore S/G level.
: b. MFW  pumps - BOTH RUNNING              b. Perform the following:
: 1) Verify  one  MFW pump  running.
IF NOT, THEN  verify both MDAFW  pumps  running.
: 2) Go  to Step 8.
: c. Close one    MFW pump  discharge valve
: d. Stop selected    MFW  pump 8  Establish Stable Plant Conditions:
: a. Place rod control bank selector in  MANUAL
: b. NIS intermediate ranges      - BELOW  b. Return to Step 2.
THE POINT OF ADDING HEAT (APPROXIMATELY 2.5x10        AMPS)
: c. PRZR  pressure    - BETWEEN            c. Control PRZR heaters and spray 2220 PSIG AND 2260 PSIG                    as necessary.
: d. PRZR  level    - TRENDING TO PROGRAM  d. Control charging as necessary.
: e. S/G  levels    - TRENDING TO PROGRAM  e. Control S/G feed flow as necessary.
: f. RCS  Tavg -    GREATER THAN  540'F    f. Control dumping steam as necessary. IF cooldown continues, THEN close both MSIVs.
 
  ~ ~
A
 
EOP:            T1TLE:
REV    7 P-WRB:1                TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 9    of 12 STEP      ACTION/EXPECTED RESPONSE                  RESPONSE  NOT OBTAINED CAUTION IF ANY S/G LEVEL ABOVE PROGRAM, THEN AFW FLOW MAY BE THROTTLED IMMEDIATELYTO PREVENT S/G ISOLATION.
NOTE:  Maintain Reactor power less than        2%. This is within the capacity of MDAFW  pumps.
9  Check S/G Feed Flow          Status:
: a. Manually    start both  MDAFW pumps
: b. Verify AFW flow -      ESTABLISHED        b. Perform the following:
: 1) Establish MFW flow using    MFW regulating valve bypass valves.
IF MFW NOT  available,  THEN manually  start TDAFW pump and establish flow  as necessary.
: 2) Go  to Step 10.
: c. Verify MFW flow control valves              c. Place  A and B MFW regulating and CLOSED                                        bypass valve controllers in manual at 0% demand.
            ~ MFW  regulating valves
            ~ MFW  bypass valves
: d. Close  MFW pump    discharge valves
            ~ MOV-3977, A    MFW  pump
            ~ MOV~976,      B MFW pump
: e. Stop any running      MFW  pump and place  in  PULL STOP
: f. Check S/G    level  - TRENDING TO 39%      f. Adjust  MDAFW pump  flow as necessary  to restore S/G level.
4
 
EOP:              TITLE:
REV: 7 P~ TURB." 1            TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 10  of 12 STEP      ACTION/EXPECTED RESPONSE                  RESPONSE  NOT OBTAINED CAUTION WHEN FEEDING BOTH      S/G(S) USING  ONE MDAFW PUMP,  THEN THE SUM OF THE FLOWS TO BOTH  S/G(S)  MUST BE LESS THAN 230 GPM.
10  Establish Normal          AFW Pump Shutdown Alignment:
: a. Place    AFW  bypass switches to    DEF
: b. Verify the following:                      b. Continue with Step  ll. WHEN conditions met,  THEN do Steps o  Both S/G levels -      STABLE OR          10c through  f.
INCREASING o  Total    AFW  flow  - LESS THAN 200  GPM
: c. Close    MDAFW pump    discharge valves
            ~ MOV-4007
            ~ MOV-4008
: d. Stop  all  but  one  MDAFW pump
: e. Open  AFW  discharge crossover valves
            ~ MOV-4000A
            ~ MOV-4000B
: f. Open AFW bypass      valves as necessary    to control S/G levels
            ~ AOV-4480
            ~ AOV-4481
 
EOP:            TITLE:
REV: 7 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 11  of 12 STEP      ACTION/EXPECTED RESPONSE              RESPONSE NOT OBTAINED 11  Establish Normal Shutdown Alignment:
: a. Check condenser    - AVAILABLE        a. Dispatch AO to perform Attachment SD-2.
: b. Perform the following as necessary:
o  Open  generator disconnects
              ~  1G13A71
              ~  9X13A73 o  Place voltage regulator to    OFF o  Open    turbine drain valves o  Rotate reheater steam supply controller cern to close valves o  Place reheater dump valve switches to HAND o  Stop  all  but one condensate pump
: c. Verify Bus llA and Bus llB            c. IF either bus NOT energized, energized - BOTH BUSSES GREATER            THEN refer to 0-6.9.2, THAN 4 KV                                  ESTABLISHING AND/OR TRANSFERRING OFFSITE POWER TO BUS 12A/
BUS 12B.
: d. Dispatch    AO to perform Attachment SD-1


EOP: P-TURB;1 T1jLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 8 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 7 Check MFW System: a.Verify MFW regulating and bypass valves-OPERATING IN AUTO b.MFW pumps-BOTH RUNNING c.Close one MFW pump discharge valve a.Place MFW regulating and bypass valve controllers in MANUAL and restore S/G level.b.Perform the following:
1)Verify one MFW pump running.IF NOT, THEN verify both MDAFW pumps running.2)Go to Step 8.d.Stop selected MFW pump 8 Establish Stable Plant Conditions:
a.Place rod control bank selector in MANUAL b.NIS intermediate ranges-BELOW THE POINT OF ADDING HEAT (APPROXIMATELY 2.5x10 AMPS)b.Return to Step 2.c.PRZR pressure-BETWEEN 2220 PSIG AND 2260 PSIG d.PRZR level-TRENDING TO PROGRAM e.S/G levels-TRENDING TO PROGRAM f.RCS Tavg-GREATER THAN 540'F c.Control PRZR heaters and spray as necessary.
d.Control charging as necessary.
e.Control S/G feed flow as necessary.
f.Control dumping steam as necessary.
IF cooldown continues, THEN close both MSIVs.
A~~
EOP: P-WRB:1 T1TLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 9 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED****************************************CAUTION IF ANY S/G LEVEL ABOVE PROGRAM, THEN AFW FLOW MAY BE THROTTLED IMMEDIATELY TO PREVENT S/G ISOLATION.
NOTE: Maintain Reactor power less than 2%.This is within the capacity of MDAFW pumps.4 9 Check S/G Feed Flow Status: a.Manually start both MDAFW pumps b.Verify AFW flow-ESTABLISHED c.Verify MFW flow control valves CLOSED~MFW regulating valves~MFW bypass valves d.Close MFW pump discharge valves~MOV-3977, A MFW pump~MOV~976, B MFW pump e.Stop any running MFW pump and place in PULL STOP f.Check S/G level-TRENDING TO 39%b.Perform the following:
1)Establish MFW flow using MFW regulating valve bypass valves.IF MFW NOT available, THEN manually start TDAFW pump and establish flow as necessary.
2)Go to Step 10.c.Place A and B MFW regulating and bypass valve controllers in manual at 0%demand.f.Adjust MDAFW pump flow as necessary to restore S/G level.
EOP: P~TURB." 1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 10 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED*****************************************CAUTION WHEN FEEDING BOTH S/G(S)USING ONE MDAFW PUMP, THEN THE SUM OF THE FLOWS TO BOTH S/G(S)MUST BE LESS THAN 230 GPM.10 Establish Normal AFW Pump Shutdown Alignment:
a.Place AFW bypass switches to DEF b.Verify the following:
o Both S/G levels-STABLE OR INCREASING b.Continue with Step ll.WHEN conditions met, THEN do Steps 10c through f.o Total AFW flow-LESS THAN 200 GPM c.Close MDAFW pump discharge valves~MOV-4007~MOV-4008 d.Stop all but one MDAFW pump e.Open AFW discharge crossover valves~MOV-4000A~MOV-4000B f.Open AFW bypass valves as necessary to control S/G levels~AOV-4480~AOV-4481 EOP: TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 11 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 11 Establish Normal Shutdown Alignment:
a.Check condenser-AVAILABLE a.Dispatch AO to perform Attachment SD-2.b.Perform the following as necessary:
o Open generator disconnects
~1G13A71~9X13A73 o Place voltage regulator to OFF o Open turbine drain valves o Rotate reheater steam supply controller cern to close valves o Place reheater dump valve switches to HAND o Stop all but one condensate pump c.Verify Bus llA and Bus llB energized-BOTH BUSSES GREATER THAN 4 KV c.IF either bus NOT energized, THEN refer to 0-6.9.2, ESTABLISHING AND/OR TRANSFERRING OFFSITE POWER TO BUS 12A/BUS 12B.d.Dispatch AO to perform Attachment SD-1
('
('
EOP: II PERTURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 12 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: Refer to 0-9.3, NRC IMMEDIATE NOTIFICATION, for reporting requirements.
EOP:
12 Notify Higher Supervision 13 Establish Desired Plant Conditions:
II                                                                           REV  7 PERTURB;1         TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 12   of 12 STEP     ACTION/EXPECTED RESPONSE             RESPONSE   NOT OBTAINED NOTE:   Refer to 0-9.3, NRC IMMEDIATE NOTIFICATION,   for reporting requirements.
a.Reactor shutdown-DESIRED a.IF turbine is to be restored to service, THEN maintain reactor critical and refer to 0-1.2, PLANT FROM HOT SHUTDOWN TO STEADY LOAD.b.Refer to 0-2.1, NORMAL SHUTDOWN TO HOT SHUTDOWN-END-0~J 0 EOP: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 1 of 1 AP-TURB.1 APPENDIX LIST TITLE PAGES 1)2)ATTACHMENT SD-1 ATTACHMENT SD-2}}
12   Notify Higher Supervision 13   Establish Desired Plant Conditions:
: a. Reactor shutdown - DESIRED           a. IF turbine   is to be restored to service,   THEN maintain reactor critical   and refer to 0-1.2, PLANT FROM HOT SHUTDOWN TO STEADY LOAD.
: b. Refer to 0-2.1, NORMAL SHUTDOWN TO HOT SHUTDOWN
                                            -END-
 
0 ~J 0
 
EOP:
REV: 7 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 1 of 1 AP-TURB.1 APPENDIX LIST TITLE                                 PAGES
: 1) ATTACHMENT SD-1
: 2) ATTACHMENT SD-2}}

Latest revision as of 10:36, 4 February 2020

Rev 7 to AP-TURB.1, Turbine Trip W/O Rx Trip Required.
ML17263A304
Person / Time
Site: Ginna Constellation icon.png
Issue date: 05/07/1993
From: Marlow T
ROCHESTER GAS & ELECTRIC CORP.
To:
Shared Package
ML17263A305 List:
References
AP-TURB.1, NUDOCS 9306040151
Download: ML17263A304 (19)


Text

EOP: TITLE:

REV: 7 P-TURB.1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 1 of 12 ROCHESTER GAS AND ELECTRIC ORPORATION GINNA STAT ON CONTROLLED COPY BER TECHNICAL REVIEW PORC VIEW DATE P T SUPERINTENDENT EFF TIVE DATE CAT G RY 1.0 REVIEWED BY:

9306040i5i 930524 PDR ADQCK 05000244 P PDR L

\~

EOP: TITLE:

REV 7 P-TURB.'1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 2 of 12 A. PURPOSE - This procedure provides the necessary instructions to control the plant following a turbine trip without a reactor trip required.

B. ENTRY CONDITIONS/SYMPTOMS

1. ENTRY CONDITIONS This procedure is entered from:
a. AP-CW.1, LOSS OF A CIRC WATER PUMP, or,
b. AP-ELEC.l, LOSS OF 12A AND/OR 12B TRANSFORMER, or, c ~ I I AP FW 1 g PART AL OR COMPLETE LOSS OF MA N FEE DWATER g or,
d. AP-TURB.2, AUTOMATIC TURBINE RUNBACK, or,
e. AP-TURB.3, TURBINE VIBRATIONS, or,
f. AP-TURB.4, LOSS OF CONDENSER VACUUM, when power is less than P-9 and the turbine trips without a Rx trip.
2. SYMPTOMS The symptoms of TURBINE TRIP WITHOUT RX TRIP REQUIRED are:

a ~ Annunciator K-l, THRUST BEARING FAILURE, lit, or

b. Annunciator K-9, TURBINE BEARING OIL LO PRESS TRIP 6 psi, lit, or c Annunciator K-17, TURBINE LOW VACUUM TRIP 20" HG,

~

lit, or

d. Annunciator K-18, MAIN FEEDWATER PUMPS TRIPPED, lit, or
e. Annunciator K-26, GENERATOR LOCKOUT RELAY, lit, or Annunciator K-25, TURBINE OVERSPEED ALERT 1980 RPM, lit, or gi Annunciator F-21, 20" CIRC WTR PMPS, lit, or HI PRESS COND HG OR LOSS OF BOTH
h. Annunciator K-3, AMSAC ACTUATED, lit.

~l T

EOP: TITLE:

REV 7 P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 3 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION IF, AT ANY TIME DURING THIS PROCEDURE, A REACTOR TRIP OR SI OCCURS, E-O, REACTOR TRIP OR SAFETY INJECTION, SHALL BE PERFORMED.

1 Verify Turbine Stop Valves Manually trip turbine.

CLOSED IF turbine stop valves can NOT be closed, THEN close both MSIVs.

IF reactor power greater than 8%

with both MSIVs closed, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

EOP: T!TLE:

REV: 7 P-'TURB; 1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 4 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION PRZR PRESSURE LOW PRESSURE TRIP IS RATE SENSITIVE, THEREFORE, MONITOR PRESSURE WHEN REDUCING RCS TEMPERATURE.

NOTE: Automatic rod control is desired, if available.

2 Check Reactor, Power:

a. NIS intermediate ranges - ABOVE a. Go to Step 3.

THE POINT OF ADDING HEAT (APPROXIMATELY 2.5xlO 6 AMPS)

b. Verify control rods driving in b. Perform the following:

to reduce reactor power in AUTO l) Ensure ROD CONTROL BANK SELECTOR switch to MANUAL

2) Insert rods as necessary to reduce reactor power.
c. Borate as necessary to maintain control rods above rod insertion limits

EOP:

REV: 7 P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 5 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 3 Monitor S/G Levels:

a. Levels - GREATER THAN 30% OR a. IF MFW regulating and bypass INCREASING valves NOT controlling in AUTO, THEN place controllers in MANUAL and restore narrow range level to program.

IF S/G level can NOT be restored, THEN trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

b. Levels - TRENDING TO PROGRAM b. IF S/G level above program and increasing uncontrolled, THEN place controller(s) in MANUAL and decrease flow as necessary.

IF flow can NOT be controlled, THEN perform the following:

l) Trip the reactor.

2) Stop the running MFW pump.
3) Close MFW pump discharge valves.
4) Go to E-O, REACTOR TRIP OR SAFETY INJECTION.

EOP:

REV: 7 P.~TURB; 1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 6 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 4 Verify Proper Operation Of Steam Dump:

a. Verify annunciator G-15, STEAM a. Place steam dump mode selector DUMP ARMED - LIT switch to MANUAL.
b. Condenser steam dump operating b. IF steam dump NOT available, in AUTO THEN perform the following:
1) Adjust S/G ARV setpoints to 1005 psig and verify proper operation.
2) IF power is greater than 8%,

THEN ensure reactor trip and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

c. Tavg - TRENDING TO PROGRAM c. IF Tavg can NOT be controlled, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

5 Check PRZR Pressure IF PRZR pressure can NOT be TRENDING TO 2235 PSIG controlled, THEN refer to AP-PRZR.1, ABNORMAL PRESSURIZER PRESSURE.

EOP: TITLE:

REV: 7 P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 7 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 6 Check PRZR Level:

a. Level - GREATER THAN 13% a. Perform the following:
1) Place loop B cold leg isolation valve to REGEN Hx (AOV-427) switch to CLOSE.
2) Place letdown orifice valve switches to CLOSE (AOV-200A, AOV-200B, and AOV-202).
3) Verify excess letdown isolation valve (AOV-310) closed.
4) Ensure PRZR heaters off.
5) Control charging to restore PRZR level greater than 13%.
6) WHEN PRZR level greater than 13%, THEN restore letdown.
b. Level - TRENDING TO PROGRAM 'b. Increase charging flow as necessary to restore PRZR level to program.

EOP: T1jLE:

REV 7 P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 8 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 7 Check MFW System:

a. Verify MFW regulating and bypass a. Place MFW regulating and bypass valves - OPERATING IN AUTO valve controllers in MANUAL and restore S/G level.
b. MFW pumps - BOTH RUNNING b. Perform the following:
1) Verify one MFW pump running.

IF NOT, THEN verify both MDAFW pumps running.

2) Go to Step 8.
c. Close one MFW pump discharge valve
d. Stop selected MFW pump 8 Establish Stable Plant Conditions:
a. Place rod control bank selector in MANUAL
b. NIS intermediate ranges - BELOW b. Return to Step 2.

THE POINT OF ADDING HEAT (APPROXIMATELY 2.5x10 AMPS)

c. PRZR pressure - BETWEEN c. Control PRZR heaters and spray 2220 PSIG AND 2260 PSIG as necessary.
d. PRZR level - TRENDING TO PROGRAM d. Control charging as necessary.
e. S/G levels - TRENDING TO PROGRAM e. Control S/G feed flow as necessary.
f. RCS Tavg - GREATER THAN 540'F f. Control dumping steam as necessary. IF cooldown continues, THEN close both MSIVs.

~ ~

A

EOP: T1TLE:

REV 7 P-WRB:1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 9 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION IF ANY S/G LEVEL ABOVE PROGRAM, THEN AFW FLOW MAY BE THROTTLED IMMEDIATELYTO PREVENT S/G ISOLATION.

NOTE: Maintain Reactor power less than 2%. This is within the capacity of MDAFW pumps.

9 Check S/G Feed Flow Status:

a. Manually start both MDAFW pumps
b. Verify AFW flow - ESTABLISHED b. Perform the following:
1) Establish MFW flow using MFW regulating valve bypass valves.

IF MFW NOT available, THEN manually start TDAFW pump and establish flow as necessary.

2) Go to Step 10.
c. Verify MFW flow control valves c. Place A and B MFW regulating and CLOSED bypass valve controllers in manual at 0% demand.

~ MFW regulating valves

~ MFW bypass valves

d. Close MFW pump discharge valves

~ MOV-3977, A MFW pump

~ MOV~976, B MFW pump

e. Stop any running MFW pump and place in PULL STOP
f. Check S/G level - TRENDING TO 39% f. Adjust MDAFW pump flow as necessary to restore S/G level.

4

EOP: TITLE:

REV: 7 P~ TURB." 1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 10 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED CAUTION WHEN FEEDING BOTH S/G(S) USING ONE MDAFW PUMP, THEN THE SUM OF THE FLOWS TO BOTH S/G(S) MUST BE LESS THAN 230 GPM.

10 Establish Normal AFW Pump Shutdown Alignment:

a. Place AFW bypass switches to DEF
b. Verify the following: b. Continue with Step ll. WHEN conditions met, THEN do Steps o Both S/G levels - STABLE OR 10c through f.

INCREASING o Total AFW flow - LESS THAN 200 GPM

c. Close MDAFW pump discharge valves

~ MOV-4007

~ MOV-4008

d. Stop all but one MDAFW pump
e. Open AFW discharge crossover valves

~ MOV-4000A

~ MOV-4000B

f. Open AFW bypass valves as necessary to control S/G levels

~ AOV-4480

~ AOV-4481

EOP: TITLE:

REV: 7 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 11 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 11 Establish Normal Shutdown Alignment:

a. Check condenser - AVAILABLE a. Dispatch AO to perform Attachment SD-2.
b. Perform the following as necessary:

o Open generator disconnects

~ 1G13A71

~ 9X13A73 o Place voltage regulator to OFF o Open turbine drain valves o Rotate reheater steam supply controller cern to close valves o Place reheater dump valve switches to HAND o Stop all but one condensate pump

c. Verify Bus llA and Bus llB c. IF either bus NOT energized, energized - BOTH BUSSES GREATER THEN refer to 0-6.9.2, THAN 4 KV ESTABLISHING AND/OR TRANSFERRING OFFSITE POWER TO BUS 12A/

BUS 12B.

d. Dispatch AO to perform Attachment SD-1

('

EOP:

II REV 7 PERTURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 12 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: Refer to 0-9.3, NRC IMMEDIATE NOTIFICATION, for reporting requirements.

12 Notify Higher Supervision 13 Establish Desired Plant Conditions:

a. Reactor shutdown - DESIRED a. IF turbine is to be restored to service, THEN maintain reactor critical and refer to 0-1.2, PLANT FROM HOT SHUTDOWN TO STEADY LOAD.
b. Refer to 0-2.1, NORMAL SHUTDOWN TO HOT SHUTDOWN

-END-

0 ~J 0

EOP:

REV: 7 TURBINE TRIP WITHOUT RX TRIP REQUIRED PAGE 1 of 1 AP-TURB.1 APPENDIX LIST TITLE PAGES

1) ATTACHMENT SD-1
2) ATTACHMENT SD-2