{{#Wiki_filter:EOP:P-TURB.1TITLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE1of12ROCHESTER GASANDELECTRICORPORATION GINNASTATONCONTROLLED COPYBERTECHNICAL REVIEWPORCVIEWDATEPTSUPERINTENDENT EFFTIVEDATECATGRY1.0REVIEWEDBY:9306040i5i 930524PDRADQCK05000244PPDRL
{{#Wiki_filter:EOP: P-TURB.1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 1 of 12 ROCHESTER GAS AND ELECTRIC ORPORATION GINNA STAT ON CONTROLLED COPY BER TECHNICAL REVIEW PORC VIEW DATE P T SUPERINTENDENT EFF TIVE DATE CAT G RY 1.0 REVIEWED BY: 9306040i5i 930524 PDR ADQCK 05000244 P PDR L
\~EOP:P-TURB.'1 TITLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV7PAGE2of12A.PURPOSE-Thisprocedure providesthenecessary instructions tocontroltheplantfollowing aturbinetripwithoutareactortriprequired.
\~EOP: P-TURB.'1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 2 of 12 A.PURPOSE-This procedure provides the necessary instructions to control the plant following a turbine trip without a reactor trip required.B.ENTRY CONDITIONS/SYMPTOMS 1.ENTRY CONDITIONS
B.ENTRYCONDITIONS/SYMPTOMS 1.ENTRYCONDITIONS
-This procedure is entered from: a.AP-CW.1, LOSS OF A CIRC WATER PUMP, or, b.AP-ELEC.l, LOSS OF 12A AND/OR 12B TRANSFORMER, or, c~AP FW 1 g PART I AL OR COMPLETE LOSS OF MA I N FEE DWATER g or, d.AP-TURB.2, AUTOMATIC TURBINE RUNBACK, or, e.AP-TURB.3, TURBINE VIBRATIONS, or, f.AP-TURB.4, LOSS OF CONDENSER VACUUM, when power is less than P-9 and the turbine trips without a Rx trip.2.SYMPTOMS-The symptoms of TURBINE TRIP WITHOUT RX TRIP REQUIRED are: a~b.c~d.e.gi Annunciator K-l, THRUST BEARING FAILURE, lit, or Annunciator K-9, TURBINE BEARING OIL LO PRESS TRIP 6 psi, lit, or Annunciator K-17, TURBINE LOW VACUUM TRIP 20" HG, lit, or Annunciator K-18, MAIN FEEDWATER PUMPS TRIPPED, lit, or Annunciator K-26, GENERATOR LOCKOUT RELAY, lit, or Annunciator K-25, TURBINE OVERSPEED ALERT 1980 RPM, lit, or Annunciator F-21, COND HI PRESS 20" HG OR LOSS OF BOTH CIRC WTR PMPS, lit, or h.Annunciator K-3, AMSAC ACTUATED, lit.  
-Thisprocedure isenteredfrom:a.AP-CW.1,LOSSOFACIRCWATERPUMP,or,b.AP-ELEC.l, LOSSOF12AAND/OR12BTRANSFORMER, or,c~APFW1gPARTIALORCOMPLETELOSSOFMAINFEEDWATERgor,d.AP-TURB.2, AUTOMATIC TURBINERUNBACK,or,e.AP-TURB.3, TURBINEVIBRATIONS, or,f.AP-TURB.4, LOSSOFCONDENSER VACUUM,whenpowerislessthanP-9andtheturbinetripswithoutaRxtrip.2.SYMPTOMS-ThesymptomsofTURBINETRIPWITHOUTRXTRIPREQUIREDare:a~b.c~d.e.giAnnunciator K-l,THRUSTBEARINGFAILURE,lit,orAnnunciator K-9,TURBINEBEARINGOILLOPRESSTRIP6psi,lit,orAnnunciator K-17,TURBINELOWVACUUMTRIP20"HG,lit,orAnnunciator K-18,MAINFEEDWATER PUMPSTRIPPED,lit,orAnnunciator K-26,GENERATOR LOCKOUTRELAY,lit,orAnnunciator K-25,TURBINEOVERSPEED ALERT1980RPM,lit,orAnnunciator F-21,CONDHIPRESS20"HGORLOSSOFBOTHCIRCWTRPMPS,lit,orh.Annunciator K-3,AMSACACTUATED, lit.  
~l T EOP: P-TURB;1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 3 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED***************.**************************CAUTION IF, AT ANY TIME DURING THIS PROCEDURE, A REACTOR TRIP OR SI OCCURS, E-O, REACTOR TRIP OR SAFETY INJECTION, SHALL BE PERFORMED.
~lT EOP:P-TURB;1TITLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV7PAGE3of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED***************.**************************CAUTIONIF,ATANYTIMEDURINGTHISPROCEDURE, AREACTORTRIPORSIOCCURS,E-O,REACTORTRIPORSAFETYINJECTION, SHALLBEPERFORMED.
1 Verify Turbine Stop Valves-CLOSED Manually trip turbine.IF turbine stop valves can NOT be closed, THEN close both MSIVs.IF reactor power greater than 8%with both MSIVs closed, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.  
1VerifyTurbineStopValves-CLOSEDManuallytripturbine.IFturbinestopvalvescanNOTbeclosed,THENclosebothMSIVs.IFreactorpowergreaterthan8%withbothMSIVsclosed,THENmanuallytripthereactorandgotoE-O,REACTORTRIPORSAFETYINJECTION.  


EOP:P-'TURB;1T!TLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE4of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED*****************************************CAUTIONPRZRPRESSURELOWPRESSURETRIPISRATESENSITIVE, THEREFORE, MONITORPRESSUREWHENREDUCINGRCSTEMPERATURE.
EOP: P-'TURB;1 T!TLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 4 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED*****************************************CAUTION PRZR PRESSURE LOW PRESSURE TRIP IS RATE SENSITIVE, THEREFORE, MONITOR PRESSURE WHEN REDUCING RCS TEMPERATURE.
*****************************************NOTE:Automatic rodcontrolisdesired,ifavailable.
*****************************************NOTE: Automatic rod control is desired, if available.
2CheckReactor,Power:a.NISintermediate ranges-ABOVETHEPOINTOFADDINGHEAT(APPROXIMATELY 2.5xlO6AMPS)a.GotoStep3.b.VerifycontrolrodsdrivingintoreducereactorpowerinAUTOb.Performthefollowing:
2 Check Reactor, Power: a.NIS intermediate ranges-ABOVE THE POINT OF ADDING HEAT (APPROXIMATELY 2.5xlO 6 AMPS)a.Go to Step 3.b.Verify control rods driving in to reduce reactor power in AUTO b.Perform the following:
l)EnsureRODCONTROLBANKSELECTORswitchtoMANUAL2)Insertrodsasnecessary toreducereactorpower.c.Borateasnecessary tomaintaincontrolrodsaboverodinsertion limits EOP:P-TURB;1TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE5of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED3MonitorS/GLevels:a.Levels-GREATERTHAN30%ORINCREASING a.IFMFWregulating andbypassvalvesNOTcontrolling inAUTO,THENplacecontrollers inMANUALandrestorenarrowrangeleveltoprogram.IFS/GlevelcanNOTberestored, THENtripthereactorandgotoE-O,REACTORTRIPORSAFETYINJECTION.
l)Ensure ROD CONTROL BANK SELECTOR switch to MANUAL 2)Insert rods as necessary to reduce reactor power.c.Borate as necessary to maintain control rods above rod insertion limits EOP: P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 5 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 3 Monitor S/G Levels: a.Levels-GREATER THAN 30%OR INCREASING a.IF MFW regulating and bypass valves NOT controlling in AUTO, THEN place controllers in MANUAL and restore narrow range level to program.IF S/G level can NOT be restored, THEN trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
b.Levels-TRENDINGTOPROGRAMb.IFS/Glevelaboveprogramandincreasing uncontrolled, THENplacecontroller(s) inMANUALanddecreaseflowasnecessary.
b.Levels-TRENDING TO PROGRAM b.IF S/G level above program and increasing uncontrolled, THEN place controller(s) in MANUAL and decrease flow as necessary.
IFflowcanNOTbecontrolled, THENperformthefollowing:
IF flow can NOT be controlled, THEN perform the following:
l)Tripthereactor.2)StoptherunningMFWpump.3)CloseMFWpumpdischarge valves.4)GotoE-O,REACTORTRIPORSAFETYINJECTION.
l)Trip the reactor.2)Stop the running MFW pump.3)Close MFW pump discharge valves.4)Go to E-O, REACTOR TRIP OR SAFETY INJECTION.
EOP:P.~TURB;1TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE6of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED4VerifyProperOperation OfSteamDump:a.Verifyannunciator G-15,STEAMDUMPARMED-LITa.PlacesteamdumpmodeselectorswitchtoMANUAL.b.Condenser steamdumpoperating inAUTOb.IFsteamdumpNOTavailable, THENperformthefollowing:
EOP: P.~TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 6 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 4 Verify Proper Operation Of Steam Dump: a.Verify annunciator G-15, STEAM DUMP ARMED-LIT a.Place steam dump mode selector switch to MANUAL.b.Condenser steam dump operating in AUTO b.IF steam dump NOT available, THEN perform the following:
1)AdjustS/GARVsetpoints to1005psigandverifyproperoperation.
1)Adjust S/G ARV setpoints to 1005 psig and verify proper operation.
2)IFpowerisgreaterthan8%,THENensurereactortripandgotoE-O,REACTORTRIPORSAFETYINJECTION.
2)IF power is greater than 8%, THEN ensure reactor trip and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
c.Tavg-TRENDINGTOPROGRAMc.IFTavgcanNOTbecontrolled, THENmanuallytripthereactorandgotoE-O,REACTORTRIPORSAFETYINJECTION.
c.Tavg-TRENDING TO PROGRAM c.IF Tavg can NOT be controlled, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.
5CheckPRZRPressure-TRENDINGTO2235PSIGIFPRZRpressurecanNOTbecontrolled, THENrefertoAP-PRZR.1, ABNORMALPRESSURIZER PRESSURE.
5 Check PRZR Pressure-TRENDING TO 2235 PSIG IF PRZR pressure can NOT be controlled, THEN refer to AP-PRZR.1, ABNORMAL PRESSURIZER PRESSURE.
EOP:P-TURB;1TITLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE7of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED6CheckPRZRLevel:a.Level-GREATERTHAN13%a.Performthefollowing:
EOP: P-TURB;1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 7 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 6 Check PRZR Level: a.Level-GREATER THAN 13%a.Perform the following:
1)PlaceloopBcoldlegisolation valvetoREGENHx(AOV-427) switchtoCLOSE.2)PlaceletdownorificevalveswitchestoCLOSE(AOV-200A, AOV-200B, andAOV-202).
1)Place loop B cold leg isolation valve to REGEN Hx (AOV-427)switch to CLOSE.2)Place letdown orifice valve switches to CLOSE (AOV-200A, AOV-200B, and AOV-202).3)Verify excess letdown isolation valve (AOV-310)closed.4)Ensure PRZR heaters off.5)Control charging to restore PRZR level greater than 13%.6)WHEN PRZR level greater than 13%, THEN restore letdown.b.Level-TRENDING TO PROGRAM'b.Increase charging flow as necessary to restore PRZR level to program.  
3)Verifyexcessletdownisolation valve(AOV-310) closed.4)EnsurePRZRheatersoff.5)ControlchargingtorestorePRZRlevelgreaterthan13%.6)WHENPRZRlevelgreaterthan13%,THENrestoreletdown.b.Level-TRENDINGTOPROGRAM'b.Increasechargingflowasnecessary torestorePRZRleveltoprogram.  


EOP:P-TURB;1T1jLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV7PAGE8of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED7CheckMFWSystem:a.VerifyMFWregulating andbypassvalves-OPERATING INAUTOb.MFWpumps-BOTHRUNNINGc.CloseoneMFWpumpdischarge valvea.PlaceMFWregulating andbypassvalvecontrollers inMANUALandrestoreS/Glevel.b.Performthefollowing:
EOP: P-TURB;1 T1jLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 8 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 7 Check MFW System: a.Verify MFW regulating and bypass valves-OPERATING IN AUTO b.MFW pumps-BOTH RUNNING c.Close one MFW pump discharge valve a.Place MFW regulating and bypass valve controllers in MANUAL and restore S/G level.b.Perform the following:
1)VerifyoneMFWpumprunning.IFNOT,THENverifybothMDAFWpumpsrunning.2)GotoStep8.d.StopselectedMFWpump8Establish StablePlantConditions:
1)Verify one MFW pump running.IF NOT, THEN verify both MDAFW pumps running.2)Go to Step 8.d.Stop selected MFW pump 8 Establish Stable Plant Conditions:
a.PlacerodcontrolbankselectorinMANUALb.NISintermediate ranges-BELOWTHEPOINTOFADDINGHEAT(APPROXIMATELY 2.5x10AMPS)b.ReturntoStep2.c.PRZRpressure-BETWEEN2220PSIGAND2260PSIGd.PRZRlevel-TRENDINGTOPROGRAMe.S/Glevels-TRENDINGTOPROGRAMf.RCSTavg-GREATERTHAN540'Fc.ControlPRZRheatersandsprayasnecessary.
a.Place rod control bank selector in MANUAL b.NIS intermediate ranges-BELOW THE POINT OF ADDING HEAT (APPROXIMATELY 2.5x10 AMPS)b.Return to Step 2.c.PRZR pressure-BETWEEN 2220 PSIG AND 2260 PSIG d.PRZR level-TRENDING TO PROGRAM e.S/G levels-TRENDING TO PROGRAM f.RCS Tavg-GREATER THAN 540'F c.Control PRZR heaters and spray as necessary.
d.Controlchargingasnecessary.
d.Control charging as necessary.
e.ControlS/Gfeedflowasnecessary.
e.Control S/G feed flow as necessary.
f.Controldumpingsteamasnecessary.
f.Control dumping steam as necessary.
IFcooldowncontinues, THENclosebothMSIVs.
IF cooldown continues, THEN close both MSIVs.
A~~
A~~
EOP:P-WRB:1T1TLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV7PAGE9of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED****************************************CAUTIONIFANYS/GLEVELABOVEPROGRAM,THENAFWFLOWMAYBETHROTTLED IMMEDIATELY TOPREVENTS/GISOLATION.
EOP: P-WRB:1 T1TLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 9 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED****************************************CAUTION IF ANY S/G LEVEL ABOVE PROGRAM, THEN AFW FLOW MAY BE THROTTLED IMMEDIATELY TO PREVENT S/G ISOLATION.
NOTE:MaintainReactorpowerlessthan2%.ThisiswithinthecapacityofMDAFWpumps.49CheckS/GFeedFlowStatus:a.ManuallystartbothMDAFWpumpsb.VerifyAFWflow-ESTABLISHED c.VerifyMFWflowcontrolvalvesCLOSED~MFWregulating valves~MFWbypassvalvesd.CloseMFWpumpdischarge valves~MOV-3977, AMFWpump~MOV~976,BMFWpumpe.StopanyrunningMFWpumpandplaceinPULLSTOPf.CheckS/Glevel-TRENDINGTO39%b.Performthefollowing:
NOTE: Maintain Reactor power less than 2%.This is within the capacity of MDAFW pumps.4 9 Check S/G Feed Flow Status: a.Manually start both MDAFW pumps b.Verify AFW flow-ESTABLISHED c.Verify MFW flow control valves CLOSED~MFW regulating valves~MFW bypass valves d.Close MFW pump discharge valves~MOV-3977, A MFW pump~MOV~976, B MFW pump e.Stop any running MFW pump and place in PULL STOP f.Check S/G level-TRENDING TO 39%b.Perform the following:
1)Establish MFWflowusingMFWregulating valvebypassvalves.IFMFWNOTavailable, THENmanuallystartTDAFWpumpandestablish flowasnecessary.
1)Establish MFW flow using MFW regulating valve bypass valves.IF MFW NOT available, THEN manually start TDAFW pump and establish flow as necessary.
2)GotoStep10.c.PlaceAandBMFWregulating andbypassvalvecontrollers inmanualat0%demand.f.AdjustMDAFWpumpflowasnecessary torestoreS/Glevel.
2)Go to Step 10.c.Place A and B MFW regulating and bypass valve controllers in manual at 0%demand.f.Adjust MDAFW pump flow as necessary to restore S/G level.
EOP:P~TURB."1TITLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE10of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED*****************************************CAUTIONWHENFEEDINGBOTHS/G(S)USINGONEMDAFWPUMP,THENTHESUMOFTHEFLOWSTOBOTHS/G(S)MUSTBELESSTHAN230GPM.10Establish NormalAFWPumpShutdownAlignment:
EOP: P~TURB." 1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 10 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED*****************************************CAUTION WHEN FEEDING BOTH S/G(S)USING ONE MDAFW PUMP, THEN THE SUM OF THE FLOWS TO BOTH S/G(S)MUST BE LESS THAN 230 GPM.10 Establish Normal AFW Pump Shutdown Alignment:
a.PlaceAFWbypassswitchestoDEFb.Verifythefollowing:
a.Place AFW bypass switches to DEF b.Verify the following:
oBothS/Glevels-STABLEORINCREASING b.ContinuewithStepll.WHENconditions met,THENdoSteps10cthroughf.oTotalAFWflow-LESSTHAN200GPMc.CloseMDAFWpumpdischarge valves~MOV-4007~MOV-4008d.StopallbutoneMDAFWpumpe.OpenAFWdischarge crossover valves~MOV-4000A
o Both S/G levels-STABLE OR INCREASING b.Continue with Step ll.WHEN conditions met, THEN do Steps 10c through f.o Total AFW flow-LESS THAN 200 GPM c.Close MDAFW pump discharge valves~MOV-4007~MOV-4008 d.Stop all but one MDAFW pump e.Open AFW discharge crossover valves~MOV-4000A~MOV-4000B f.Open AFW bypass valves as necessary to control S/G levels~AOV-4480~AOV-4481 EOP: TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 11 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 11 Establish Normal Shutdown Alignment:
~MOV-4000B f.OpenAFWbypassvalvesasnecessary tocontrolS/Glevels~AOV-4480~AOV-4481 EOP:TITLE:TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE11of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINED11Establish NormalShutdownAlignment:
a.Check condenser-AVAILABLE a.Dispatch AO to perform Attachment SD-2.b.Perform the following as necessary:
a.Checkcondenser
o Open generator disconnects
-AVAILABLE a.DispatchAOtoperformAttachment SD-2.b.Performthefollowing asnecessary:
~1G13A71~9X13A73 o Place voltage regulator to OFF o Open turbine drain valves o Rotate reheater steam supply controller cern to close valves o Place reheater dump valve switches to HAND o Stop all but one condensate pump c.Verify Bus llA and Bus llB energized-BOTH BUSSES GREATER THAN 4 KV c.IF either bus NOT energized, THEN refer to 0-6.9.2, ESTABLISHING AND/OR TRANSFERRING OFFSITE POWER TO BUS 12A/BUS 12B.d.Dispatch AO to perform Attachment SD-1  
oOpengenerator disconnects
~1G13A71~9X13A73oPlacevoltageregulator toOFFoOpenturbinedrainvalvesoRotatereheatersteamsupplycontroller cerntoclosevalvesoPlacereheaterdumpvalveswitchestoHANDoStopallbutonecondensate pumpc.VerifyBusllAandBusllBenergized
-BOTHBUSSESGREATERTHAN4KVc.IFeitherbusNOTenergized, THENreferto0-6.9.2,ESTABLISHING AND/ORTRANSFERRING OFFSITEPOWERTOBUS12A/BUS12B.d.DispatchAOtoperformAttachment SD-1  
('
('
EOP:IIPERTURB;1 TURBINETRIPWITHOUTRXTRIPREQUIREDREV7PAGE12of12STEPACTION/EXPECTED RESPONSERESPONSENOTOBTAINEDNOTE:Referto0-9.3,NRCIMMEDIATE NOTIFICATION, forreporting requirements.
EOP: II PERTURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 12 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: Refer to 0-9.3, NRC IMMEDIATE NOTIFICATION, for reporting requirements.
12NotifyHigherSupervision 13Establish DesiredPlantConditions:
12 Notify Higher Supervision 13 Establish Desired Plant Conditions:
a.Reactorshutdown-DESIREDa.IFturbineistoberestoredtoservice,THENmaintainreactorcriticalandreferto0-1.2,PLANTFROMHOTSHUTDOWNTOSTEADYLOAD.b.Referto0-2.1,NORMALSHUTDOWNTOHOTSHUTDOWN-END-0~J0 EOP:TURBINETRIPWITHOUTRXTRIPREQUIREDREV:7PAGE1of1AP-TURB.1 APPENDIXLISTTITLEPAGES1)2)ATTACHMENT SD-1ATTACHMENT SD-2}}
a.Reactor shutdown-DESIRED a.IF turbine is to be restored to service, THEN maintain reactor critical and refer to 0-1.2, PLANT FROM HOT SHUTDOWN TO STEADY LOAD.b.Refer to 0-2.1, NORMAL SHUTDOWN TO HOT SHUTDOWN-END-0~J 0 EOP: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 1 of 1 AP-TURB.1 APPENDIX LIST TITLE PAGES 1)2)ATTACHMENT SD-1 ATTACHMENT SD-2}}

Revision as of 14:08, 7 July 2018

Rev 7 to AP-TURB.1, Turbine Trip W/O Rx Trip Required.
ML17263A304
Person / Time
Site: Ginna Constellation icon.png
Issue date: 05/07/1993
From: MARLOW T A
ROCHESTER GAS & ELECTRIC CORP.
To:
Shared Package
ML17263A305 List:
References
AP-TURB.1, NUDOCS 9306040151
Download: ML17263A304 (19)


Text

EOP: P-TURB.1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 1 of 12 ROCHESTER GAS AND ELECTRIC ORPORATION GINNA STAT ON CONTROLLED COPY BER TECHNICAL REVIEW PORC VIEW DATE P T SUPERINTENDENT EFF TIVE DATE CAT G RY 1.0 REVIEWED BY: 9306040i5i 930524 PDR ADQCK 05000244 P PDR L

\~EOP: P-TURB.'1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 2 of 12 A.PURPOSE-This procedure provides the necessary instructions to control the plant following a turbine trip without a reactor trip required.B.ENTRY CONDITIONS/SYMPTOMS 1.ENTRY CONDITIONS

-This procedure is entered from: a.AP-CW.1, LOSS OF A CIRC WATER PUMP, or, b.AP-ELEC.l, LOSS OF 12A AND/OR 12B TRANSFORMER, or, c~AP FW 1 g PART I AL OR COMPLETE LOSS OF MA I N FEE DWATER g or, d.AP-TURB.2, AUTOMATIC TURBINE RUNBACK, or, e.AP-TURB.3, TURBINE VIBRATIONS, or, f.AP-TURB.4, LOSS OF CONDENSER VACUUM, when power is less than P-9 and the turbine trips without a Rx trip.2.SYMPTOMS-The symptoms of TURBINE TRIP WITHOUT RX TRIP REQUIRED are: a~b.c~d.e.gi Annunciator K-l, THRUST BEARING FAILURE, lit, or Annunciator K-9, TURBINE BEARING OIL LO PRESS TRIP 6 psi, lit, or Annunciator K-17, TURBINE LOW VACUUM TRIP 20" HG, lit, or Annunciator K-18, MAIN FEEDWATER PUMPS TRIPPED, lit, or Annunciator K-26, GENERATOR LOCKOUT RELAY, lit, or Annunciator K-25, TURBINE OVERSPEED ALERT 1980 RPM, lit, or Annunciator F-21, COND HI PRESS 20" HG OR LOSS OF BOTH CIRC WTR PMPS, lit, or h.Annunciator K-3, AMSAC ACTUATED, lit.

~l T EOP: P-TURB;1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 3 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED***************.**************************CAUTION IF, AT ANY TIME DURING THIS PROCEDURE, A REACTOR TRIP OR SI OCCURS, E-O, REACTOR TRIP OR SAFETY INJECTION, SHALL BE PERFORMED.

1 Verify Turbine Stop Valves-CLOSED Manually trip turbine.IF turbine stop valves can NOT be closed, THEN close both MSIVs.IF reactor power greater than 8%with both MSIVs closed, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

EOP: P-'TURB;1 T!TLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 4 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED*****************************************CAUTION PRZR PRESSURE LOW PRESSURE TRIP IS RATE SENSITIVE, THEREFORE, MONITOR PRESSURE WHEN REDUCING RCS TEMPERATURE.

                                                                                  • NOTE: Automatic rod control is desired, if available.

2 Check Reactor, Power: a.NIS intermediate ranges-ABOVE THE POINT OF ADDING HEAT (APPROXIMATELY 2.5xlO 6 AMPS)a.Go to Step 3.b.Verify control rods driving in to reduce reactor power in AUTO b.Perform the following:

l)Ensure ROD CONTROL BANK SELECTOR switch to MANUAL 2)Insert rods as necessary to reduce reactor power.c.Borate as necessary to maintain control rods above rod insertion limits EOP: P-TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 5 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 3 Monitor S/G Levels: a.Levels-GREATER THAN 30%OR INCREASING a.IF MFW regulating and bypass valves NOT controlling in AUTO, THEN place controllers in MANUAL and restore narrow range level to program.IF S/G level can NOT be restored, THEN trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

b.Levels-TRENDING TO PROGRAM b.IF S/G level above program and increasing uncontrolled, THEN place controller(s) in MANUAL and decrease flow as necessary.

IF flow can NOT be controlled, THEN perform the following:

l)Trip the reactor.2)Stop the running MFW pump.3)Close MFW pump discharge valves.4)Go to E-O, REACTOR TRIP OR SAFETY INJECTION.

EOP: P.~TURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 6 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 4 Verify Proper Operation Of Steam Dump: a.Verify annunciator G-15, STEAM DUMP ARMED-LIT a.Place steam dump mode selector switch to MANUAL.b.Condenser steam dump operating in AUTO b.IF steam dump NOT available, THEN perform the following:

1)Adjust S/G ARV setpoints to 1005 psig and verify proper operation.

2)IF power is greater than 8%, THEN ensure reactor trip and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

c.Tavg-TRENDING TO PROGRAM c.IF Tavg can NOT be controlled, THEN manually trip the reactor and go to E-O, REACTOR TRIP OR SAFETY INJECTION.

5 Check PRZR Pressure-TRENDING TO 2235 PSIG IF PRZR pressure can NOT be controlled, THEN refer to AP-PRZR.1, ABNORMAL PRESSURIZER PRESSURE.

EOP: P-TURB;1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 7 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 6 Check PRZR Level: a.Level-GREATER THAN 13%a.Perform the following:

1)Place loop B cold leg isolation valve to REGEN Hx (AOV-427)switch to CLOSE.2)Place letdown orifice valve switches to CLOSE (AOV-200A, AOV-200B, and AOV-202).3)Verify excess letdown isolation valve (AOV-310)closed.4)Ensure PRZR heaters off.5)Control charging to restore PRZR level greater than 13%.6)WHEN PRZR level greater than 13%, THEN restore letdown.b.Level-TRENDING TO PROGRAM'b.Increase charging flow as necessary to restore PRZR level to program.

EOP: P-TURB;1 T1jLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 8 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 7 Check MFW System: a.Verify MFW regulating and bypass valves-OPERATING IN AUTO b.MFW pumps-BOTH RUNNING c.Close one MFW pump discharge valve a.Place MFW regulating and bypass valve controllers in MANUAL and restore S/G level.b.Perform the following:

1)Verify one MFW pump running.IF NOT, THEN verify both MDAFW pumps running.2)Go to Step 8.d.Stop selected MFW pump 8 Establish Stable Plant Conditions:

a.Place rod control bank selector in MANUAL b.NIS intermediate ranges-BELOW THE POINT OF ADDING HEAT (APPROXIMATELY 2.5x10 AMPS)b.Return to Step 2.c.PRZR pressure-BETWEEN 2220 PSIG AND 2260 PSIG d.PRZR level-TRENDING TO PROGRAM e.S/G levels-TRENDING TO PROGRAM f.RCS Tavg-GREATER THAN 540'F c.Control PRZR heaters and spray as necessary.

d.Control charging as necessary.

e.Control S/G feed flow as necessary.

f.Control dumping steam as necessary.

IF cooldown continues, THEN close both MSIVs.

A~~

EOP: P-WRB:1 T1TLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 9 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED****************************************CAUTION IF ANY S/G LEVEL ABOVE PROGRAM, THEN AFW FLOW MAY BE THROTTLED IMMEDIATELY TO PREVENT S/G ISOLATION.

NOTE: Maintain Reactor power less than 2%.This is within the capacity of MDAFW pumps.4 9 Check S/G Feed Flow Status: a.Manually start both MDAFW pumps b.Verify AFW flow-ESTABLISHED c.Verify MFW flow control valves CLOSED~MFW regulating valves~MFW bypass valves d.Close MFW pump discharge valves~MOV-3977, A MFW pump~MOV~976, B MFW pump e.Stop any running MFW pump and place in PULL STOP f.Check S/G level-TRENDING TO 39%b.Perform the following:

1)Establish MFW flow using MFW regulating valve bypass valves.IF MFW NOT available, THEN manually start TDAFW pump and establish flow as necessary.

2)Go to Step 10.c.Place A and B MFW regulating and bypass valve controllers in manual at 0%demand.f.Adjust MDAFW pump flow as necessary to restore S/G level.

EOP: P~TURB." 1 TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 10 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED*****************************************CAUTION WHEN FEEDING BOTH S/G(S)USING ONE MDAFW PUMP, THEN THE SUM OF THE FLOWS TO BOTH S/G(S)MUST BE LESS THAN 230 GPM.10 Establish Normal AFW Pump Shutdown Alignment:

a.Place AFW bypass switches to DEF b.Verify the following:

o Both S/G levels-STABLE OR INCREASING b.Continue with Step ll.WHEN conditions met, THEN do Steps 10c through f.o Total AFW flow-LESS THAN 200 GPM c.Close MDAFW pump discharge valves~MOV-4007~MOV-4008 d.Stop all but one MDAFW pump e.Open AFW discharge crossover valves~MOV-4000A~MOV-4000B f.Open AFW bypass valves as necessary to control S/G levels~AOV-4480~AOV-4481 EOP: TITLE: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 11 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED 11 Establish Normal Shutdown Alignment:

a.Check condenser-AVAILABLE a.Dispatch AO to perform Attachment SD-2.b.Perform the following as necessary:

o Open generator disconnects

~1G13A71~9X13A73 o Place voltage regulator to OFF o Open turbine drain valves o Rotate reheater steam supply controller cern to close valves o Place reheater dump valve switches to HAND o Stop all but one condensate pump c.Verify Bus llA and Bus llB energized-BOTH BUSSES GREATER THAN 4 KV c.IF either bus NOT energized, THEN refer to 0-6.9.2, ESTABLISHING AND/OR TRANSFERRING OFFSITE POWER TO BUS 12A/BUS 12B.d.Dispatch AO to perform Attachment SD-1

('

EOP: II PERTURB;1 TURBINE TRIP WITHOUT RX TRIP REQUIRED REV 7 PAGE 12 of 12 STEP ACTION/EXPECTED RESPONSE RESPONSE NOT OBTAINED NOTE: Refer to 0-9.3, NRC IMMEDIATE NOTIFICATION, for reporting requirements.

12 Notify Higher Supervision 13 Establish Desired Plant Conditions:

a.Reactor shutdown-DESIRED a.IF turbine is to be restored to service, THEN maintain reactor critical and refer to 0-1.2, PLANT FROM HOT SHUTDOWN TO STEADY LOAD.b.Refer to 0-2.1, NORMAL SHUTDOWN TO HOT SHUTDOWN-END-0~J 0 EOP: TURBINE TRIP WITHOUT RX TRIP REQUIRED REV: 7 PAGE 1 of 1 AP-TURB.1 APPENDIX LIST TITLE PAGES 1)2)ATTACHMENT SD-1 ATTACHMENT SD-2