Form APF-05-003-01, Rev. 2 ASSIGNED DISCIPLINE:
Form APF-05-003-01, Rev. 2 ASSIGNED DISCIPLINE:
FP DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER E-1F9910 OTHER DOCUMENTS AFFECTED BY THIS CHANGE: NONE OTHER DDCN'S REQUIRED TO IMPLEMENT CHANGE: NONE REASON FOR CHANGE: AP 05-010 Document Correction as identified by CR 98049. Reference to GDHS0011A deleted consistent with E-1F9915, E-1F9443, other sections ofE-1F9910, and OFN RP-017 per CP 13800. DigsigOrg 4.5 PREPARED BY: DATE: 1131117 Verifier Qualification will be to the same requirement as the parent document DigsigVer 4.5 VERIFIED BY: DATE: 1131117 DigsigApp 4.5 0.5 02/06/2017 APPROVEDBY:
FP DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER E-1F9910 OTHER DOCUMENTS AFFECTED BY THIS CHANGE: NONE OTHER DDCN'S REQUIRED TO IMPLEMENT CHANGE: NONE REASON FOR CHANGE: AP 05-010 Document Correction as identified by CR 98049. Reference to GDHS0011A deleted consistent with E-1F9915, E-1F9443, other sections ofE-1F9910, and OFN RP-017 per CP 13800. DigsigOrg 4.5 PREPARED BY: DATE: 1131117 Verifier Qualification will be to the same requirement as the parent document DigsigVer 4.5 VERIFIED BY: DATE: 1131117 DigsigApp 4.5 0.5 02/06/2017 APPROVEDBY:
DATE: DigsigDSR 4.5 0.65 DC RELEASE:
DATE: DigsigDSR 4.5 0.65 DC RELEASE: DC4 DATE: 02/06/2017 DESCRIPTION OF CHANGE: See page 2 and 3. INITIATING DOC. TYPE: CR NO. 98049 DCP/CCP NO N/ A REV. REV. 14 SEQ. NO. 01 PAGE 1 OF 3 DigsigCert 1.75 3.49 RPE Certification For ASME Section III design specifications, refer to AP 05-004 for qualification requirements Post Fire Safe Shutdown Area Analysis e 1 F9910, Rev. 1S Fire Area C-1 0 Sheet C 10 16 of C 10 S3 Relay# Description 86XRP7 Train B MDAFP (PAL01 B) The relays identified in the above table are used in OFN RP-017 to isolate the control room from the listed components in the event of a fire in the control room. The lockout relays (LOR) are actuated by operators placing hand switches RPHIS0001, RPHIS0002 and RPHIS0003 in isolate position.
DC4 DATE: 02/06/2017 DESCRIPTION OF CHANGE: See page 2 and 3. INITIATING DOC. TYPE: CR NO. 98049 DCP/CCP NO N/ A REV. REV. 14 SEQ. NO. 01 PAGE 1 OF 3 DigsigCert 1.75 3.49 RPE Certification For ASME Section III design specifications, refer to AP 05-004 for qualification requirements Post Fire Safe Shutdown Area Analysis e 1 F9910, Rev. 1S Fire Area C-1 0 Sheet C 10 16 of C 10 S3 Relay# Description 86XRP7 Train B MDAFP (PAL01 B) The relays identified in the above table are used in OFN RP-017 to isolate the control room from the listed components in the event of a fire in the control room. The lockout relays (LOR) are actuated by operators placing hand switches RPHIS0001, RPHIS0002 and RPHIS0003 in isolate position.
Damage to the relays and/or associated cables due to a fire in area C-10 could prevent operation of the listed equipment.
Damage to the relays and/or associated cables due to a fire in area C-10 could prevent operation of the listed equipment.
If this occurs, Train A equipment, located in a separate fire area, is available and is unaffected by the fire. Cable 12RPK09BA provides Class 1 E 125 VDC power from NK4201 to panel RP334. Damage to this cable could disrupt power to the TDAFP loads served by panel RP334, which could prevent operation of the TDAFP. Cable 14RPK09NA provides Class 1 E 125 VDC power from NK4419 to panel RP335. Damage to this cable could disrupt power to the loads served by panel RP335, which could prevent operation of the associated equipment.
If this occurs, Train A equipment, located in a separate fire area, is available and is unaffected by the fire. Cable 12RPK09BA provides Class 1 E 125 VDC power from NK4201 to panel RP334. Damage to this cable could disrupt power to the TDAFP loads served by panel RP334, which could prevent operation of the TDAFP. Cable 14RPK09NA provides Class 1 E 125 VDC power from NK4419 to panel RP335. Damage to this cable could disrupt power to the loads served by panel RP335, which could prevent operation of the associated equipment.
Line 32: Line 31:
The s*.vitch is used to isolate the damper from the control room and allow it to fail open. The switch is used in OFN RP 017 when aligning Train B ESIJV in response to a control room fire. Cables 14GDG01BE, 14GDG01BF, 14GDG01BH and 14GDY01BB, associated with the Train B ESW pump room supply fan, is run in area C-1 0. Damage to these cables, or the associated hand switches, could prevent operation of the supply fan. Cable 14GDI04BF provides ESW Broom temperature from temperature element GDTE0011 to temperature controller GDTC0011.
The s*.vitch is used to isolate the damper from the control room and allow it to fail open. The switch is used in OFN RP 017 when aligning Train B ESIJV in response to a control room fire. Cables 14GDG01BE, 14GDG01BF, 14GDG01BH and 14GDY01BB, associated with the Train B ESW pump room supply fan, is run in area C-1 0. Damage to these cables, or the associated hand switches, could prevent operation of the supply fan. Cable 14GDI04BF provides ESW Broom temperature from temperature element GDTE0011 to temperature controller GDTC0011.
Cable 14GDI04BG provides signals from GDTC0011 to outside air intake damper GDTZ0011A.
Cable 14GDI04BG provides signals from GDTC0011 to outside air intake damper GDTZ0011A.
Cable 14GDI04BH provides signals from GDTC0011 to recirculation damper GDTZ0011 B. Damage to these cables could prevent operation of the dampers.
Cable 14GDI04BH provides signals from GDTC0011 to recirculation damper GDTZ0011 B. Damage to these cables could prevent operation of the dampers. Temperature controls for Train A ESW pump room are unaffected by a fire in area C-10. Cable 14GDY01 BB is associated with the automatic start on the Train B ESW pump room supply fan control circuit. Upon start of the Train B ESW pump, the contacts on this circuit close and energize the ARC relay, which closes a contact to start the supply fan. Cable 14GDY01 BD is associated with low temperature switch GDTSL0011 that prevents the fan from starting if the room temperature is below a pre-determined set point. Damage to these cables due to a fire could spuriously start the fan or prevent it from starting.
Temperature controls for Train A ESW pump room are unaffected by a fire in area C-10. Cable 14GDY01 BB is associated with the automatic start on the Train B ESW pump room supply fan control circuit.
Upon start of the Train B ESW pump, the contacts on this circuit close and energize the ARC relay, which closes a contact to start the supply fan. Cable 14GDY01 BD is associated with low temperature switch GDTSL0011 that prevents the fan from starting if the room temperature is below a pre-determined set point. Damage to these cables due to a fire could spuriously start the fan or prevent it from starting.
In either case, the Train A ESW pump room ventilation system is unaffected by a fire in area C-10. DDCN E-1 F991 0-014-01 page 2 of 3 Post Fire Safe Shutdown Area Analysis E 1F9910, Rev.15 Fire Area C-17 Sheet C 17 36 of C 17 41 5.2.23 Lockout Relay Panel RP335 Cable 14RPK09NA provides Class 1 E 125 VDC power from NK4419 to panel RP335. Damage to this cable could disrupt power to the loads served by panel RP335, which could prevent operation of the associated equipment.
In either case, the Train A ESW pump room ventilation system is unaffected by a fire in area C-10. DDCN E-1 F991 0-014-01 page 2 of 3 Post Fire Safe Shutdown Area Analysis E 1F9910, Rev.15 Fire Area C-17 Sheet C 17 36 of C 17 41 5.2.23 Lockout Relay Panel RP335 Cable 14RPK09NA provides Class 1 E 125 VDC power from NK4419 to panel RP335. Damage to this cable could disrupt power to the loads served by panel RP335, which could prevent operation of the associated equipment.
The following table identifies the PFSSD equipment powered by this cable. Panel RP335 PFSSD Relays Relay# Description 86XRP5 Train B MDAFP from CST and ESW Supply Valves (ALHV0034 and ALHV0030) 86XRP6 ESW to TDAFP Supply Valve (ALHV0033) 86XRP7 Train B MDAFP (PAL01 B) As discussed in Section 5.2.4, Train A auxiliary feedwater is available and is unaffected by a fire in area C-17. Therefore, damage to cable 14RPK09NA will have no adverse impact on PFSSD. Other cables associated with control room lockout relays are run in area C-17. Damage to these cables could prevent operation of associated equipment.
The following table identifies the PFSSD equipment powered by this cable. Panel RP335 PFSSD Relays Relay# Description 86XRP5 Train B MDAFP from CST and ESW Supply Valves (ALHV0034 and ALHV0030) 86XRP6 ESW to TDAFP Supply Valve (ALHV0033) 86XRP7 Train B MDAFP (PAL01 B) As discussed in Section 5.2.4, Train A auxiliary feedwater is available and is unaffected by a fire in area C-17. Therefore, damage to cable 14RPK09NA will have no adverse impact on PFSSD. Other cables associated with control room lockout relays are run in area C-17. Damage to these cables could prevent operation of associated equipment.
Line 41: Line 38:
==References:==
==References:==


XX-E-013, E-15000, E-13AL01B, E-13AL02B, E-13AL04B, E-13RP09, E-13RP15, E-093-00095, E-093-00096, E-1 F9202, E-1 F9204 5.2.24 Miscellaneous Control Room Panels Cables 14RPY09BA and 14RPY09CA provide 120 VAC power to control room panels RP053BA, RP053BB and RP053BC.
XX-E-013, E-15000, E-13AL01B, E-13AL02B, E-13AL04B, E-13RP09, E-13RP15, E-093-00095, E-093-00096, E-1 F9202, E-1 F9204 5.2.24 Miscellaneous Control Room Panels Cables 14RPY09BA and 14RPY09CA provide 120 VAC power to control room panels RP053BA, RP053BB and RP053BC. Cable 14RPY09GA provides 120 VAC power to panel RP147B. Cable 14RPY10BA provides 120 VAC power to panel RP068. The following table identifies the PFSSD components that could be affected by a loss of Train B 120 VAC power to these panels. Cable Power Supply Affected Components ABHS0004, ABPIC0004A, ALFT0007, ALFY0007B, ALHK0005A, ALHK0007A, ALHK0010A, ALHK0012A, ALHS0007, 14RPY09BA NN0416 ALHS0012, ALHV0012, ALPI0024A, EFFI0054, EFFT0054, EFPI0002, EFPT0002, JELSL0021 C, JEL T0021, RP118B ALHY0012,ALPT0039,ALPY0039A, 14RPY09CA NN0418 EGFT0129, EGPSL0078, EGPT0078, GDHS0011A, GDTE0011, GDTSL0011, GDTZ0011A ABHS0004, ABPIC0004B, ABPT0004, ABPY0004, ALFT0001, ALFY0005B, 14RPY09GA NN0404 ALHK0005A, ALHK0005B, ALHK001 OA, ALHK0010B, ALHS0005, ALHS0010, ALHV0010, ALHY0010, ALP10024B, ALPT0024, RP118B 14RPY10BA NG02ACR136 GDHIS0011A (CGD01 B) Loss of power to these components will not adversely impact PFSSD. Redundant Train A components are unaffected by the fire or the component fails in the desired PFSSD position.
Cable 14RPY09GA provides 120 VAC power to panel RP147B. Cable 14RPY10BA provides 120 VAC power to panel RP068. The following table identifies the PFSSD components that could be affected by a loss of Train B 120 VAC power to these panels. Cable Power Supply Affected Components  
: ABHS0004, ABPIC0004A,  
: ALFT0007, ALFY0007B, ALHK0005A, ALHK0007A, ALHK0010A, ALHK0012A,  
: ALHS0007, 14RPY09BA NN0416 ALHS0012,  
: ALHV0012, ALPI0024A,  
: EFFI0054, EFFT0054,  
: EFPI0002, EFPT0002, JELSL0021 C, JEL T0021, RP118B ALHY0012,ALPT0039,ALPY0039A, 14RPY09CA NN0418 EGFT0129, EGPSL0078,  
: EGPT0078, GDHS0011A,  
: GDTE0011, GDTSL0011, GDTZ0011A  
: ABHS0004, ABPIC0004B,  
: ABPT0004, ABPY0004,  
: ALFT0001, ALFY0005B, 14RPY09GA NN0404 ALHK0005A, ALHK0005B, ALHK001 OA, ALHK0010B,  
: ALHS0005, ALHS0010,  
: ALHV0010, ALHY0010, ALP10024B,  
: ALPT0024, RP118B 14RPY10BA NG02ACR136 GDHIS0011A (CGD01 B) Loss of power to these components will not adversely impact PFSSD. Redundant Train A components are unaffected by the fire or the component fails in the desired PFSSD position.
DDCN E-1 F991 0-014-01 page 3 of 3}}
DDCN E-1 F991 0-014-01 page 3 of 3}}

Revision as of 01:41, 6 July 2018

Wolf Creek Generating Station, Post Fire Safe Shutdown Area Analysis, E-IF9910, Rev. 14-01, Fire Area C-10
ML18093A999
Person / Time
Site: Wolf Creek Wolf Creek Nuclear Operating Corporation icon.png
Issue date: 02/06/2017
From:
Wolf Creek
To:
Office of Nuclear Reactor Regulation
Shared Package
ML18093A810 List: ... further results
References
WO 18-0011 E-IF9910, Rev. 14-01
Download: ML18093A999 (3)


Text


Form APF-05-003-01, Rev. 2 ASSIGNED DISCIPLINE:

FP DESIGN DOCUMENT CHANGE NOTICE DOCUMENT NUMBER E-1F9910 OTHER DOCUMENTS AFFECTED BY THIS CHANGE: NONE OTHER DDCN'S REQUIRED TO IMPLEMENT CHANGE: NONE REASON FOR CHANGE: AP 05-010 Document Correction as identified by CR 98049. Reference to GDHS0011A deleted consistent with E-1F9915, E-1F9443, other sections ofE-1F9910, and OFN RP-017 per CP 13800. DigsigOrg 4.5 PREPARED BY: DATE: 1131117 Verifier Qualification will be to the same requirement as the parent document DigsigVer 4.5 VERIFIED BY: DATE: 1131117 DigsigApp 4.5 0.5 02/06/2017 APPROVEDBY:

DATE: DigsigDSR 4.5 0.65 DC RELEASE: DC4 DATE: 02/06/2017 DESCRIPTION OF CHANGE: See page 2 and 3. INITIATING DOC. TYPE: CR NO. 98049 DCP/CCP NO N/ A REV. REV. 14 SEQ. NO. 01 PAGE 1 OF 3 DigsigCert 1.75 3.49 RPE Certification For ASME Section III design specifications, refer to AP 05-004 for qualification requirements Post Fire Safe Shutdown Area Analysis e 1 F9910, Rev. 1S Fire Area C-1 0 Sheet C 10 16 of C 10 S3 Relay# Description 86XRP7 Train B MDAFP (PAL01 B) The relays identified in the above table are used in OFN RP-017 to isolate the control room from the listed components in the event of a fire in the control room. The lockout relays (LOR) are actuated by operators placing hand switches RPHIS0001, RPHIS0002 and RPHIS0003 in isolate position.

Damage to the relays and/or associated cables due to a fire in area C-10 could prevent operation of the listed equipment.

If this occurs, Train A equipment, located in a separate fire area, is available and is unaffected by the fire. Cable 12RPK09BA provides Class 1 E 125 VDC power from NK4201 to panel RP334. Damage to this cable could disrupt power to the TDAFP loads served by panel RP334, which could prevent operation of the TDAFP. Cable 14RPK09NA provides Class 1 E 125 VDC power from NK4419 to panel RP335. Damage to this cable could disrupt power to the loads served by panel RP335, which could prevent operation of the associated equipment.

The Train A MDAFP is available and is unaffected by the fire. Based on the above discussion, a fire involving lockout relay panels RP334 and RP335 will not adversely impact PFSSD.

References:

XX-E-013, E-15000, E-13AB01, E-13AB01A, E-13AL02B, E-13AL04B, E-13BB24, E-13FC23, E-13RP09, E-13RP11, E-13RP12, E-13RP14, E-13RP15, OFN RP-017 5.1. 7 ESW Pump Room Ventilation Hand switch GDHS0011 is an isolation switch used to isolate Train B ESW pump room supply fan control circuit from the control room and manually start the fan. The switch is used in OFN RP-017 when aligning Train B ESW in response to a fire in the control room. Hand switch GDHS0011A is associate*1-with Train B ESW pump room supply damper GDTZ0011A.

The s*.vitch is used to isolate the damper from the control room and allow it to fail open. The switch is used in OFN RP 017 when aligning Train B ESIJV in response to a control room fire. Cables 14GDG01BE, 14GDG01BF, 14GDG01BH and 14GDY01BB, associated with the Train B ESW pump room supply fan, is run in area C-1 0. Damage to these cables, or the associated hand switches, could prevent operation of the supply fan. Cable 14GDI04BF provides ESW Broom temperature from temperature element GDTE0011 to temperature controller GDTC0011.

Cable 14GDI04BG provides signals from GDTC0011 to outside air intake damper GDTZ0011A.

Cable 14GDI04BH provides signals from GDTC0011 to recirculation damper GDTZ0011 B. Damage to these cables could prevent operation of the dampers. Temperature controls for Train A ESW pump room are unaffected by a fire in area C-10. Cable 14GDY01 BB is associated with the automatic start on the Train B ESW pump room supply fan control circuit. Upon start of the Train B ESW pump, the contacts on this circuit close and energize the ARC relay, which closes a contact to start the supply fan. Cable 14GDY01 BD is associated with low temperature switch GDTSL0011 that prevents the fan from starting if the room temperature is below a pre-determined set point. Damage to these cables due to a fire could spuriously start the fan or prevent it from starting.

In either case, the Train A ESW pump room ventilation system is unaffected by a fire in area C-10. DDCN E-1 F991 0-014-01 page 2 of 3 Post Fire Safe Shutdown Area Analysis E 1F9910, Rev.15 Fire Area C-17 Sheet C 17 36 of C 17 41 5.2.23 Lockout Relay Panel RP335 Cable 14RPK09NA provides Class 1 E 125 VDC power from NK4419 to panel RP335. Damage to this cable could disrupt power to the loads served by panel RP335, which could prevent operation of the associated equipment.

The following table identifies the PFSSD equipment powered by this cable. Panel RP335 PFSSD Relays Relay# Description 86XRP5 Train B MDAFP from CST and ESW Supply Valves (ALHV0034 and ALHV0030) 86XRP6 ESW to TDAFP Supply Valve (ALHV0033) 86XRP7 Train B MDAFP (PAL01 B) As discussed in Section 5.2.4, Train A auxiliary feedwater is available and is unaffected by a fire in area C-17. Therefore, damage to cable 14RPK09NA will have no adverse impact on PFSSD. Other cables associated with control room lockout relays are run in area C-17. Damage to these cables could prevent operation of associated equipment.

Train A equipment, located in a separate fire area, is available and is unaffected by the fire.

References:

XX-E-013, E-15000, E-13AL01B, E-13AL02B, E-13AL04B, E-13RP09, E-13RP15, E-093-00095, E-093-00096, E-1 F9202, E-1 F9204 5.2.24 Miscellaneous Control Room Panels Cables 14RPY09BA and 14RPY09CA provide 120 VAC power to control room panels RP053BA, RP053BB and RP053BC. Cable 14RPY09GA provides 120 VAC power to panel RP147B. Cable 14RPY10BA provides 120 VAC power to panel RP068. The following table identifies the PFSSD components that could be affected by a loss of Train B 120 VAC power to these panels. Cable Power Supply Affected Components ABHS0004, ABPIC0004A, ALFT0007, ALFY0007B, ALHK0005A, ALHK0007A, ALHK0010A, ALHK0012A, ALHS0007, 14RPY09BA NN0416 ALHS0012, ALHV0012, ALPI0024A, EFFI0054, EFFT0054, EFPI0002, EFPT0002, JELSL0021 C, JEL T0021, RP118B ALHY0012,ALPT0039,ALPY0039A, 14RPY09CA NN0418 EGFT0129, EGPSL0078, EGPT0078, GDHS0011A, GDTE0011, GDTSL0011, GDTZ0011A ABHS0004, ABPIC0004B, ABPT0004, ABPY0004, ALFT0001, ALFY0005B, 14RPY09GA NN0404 ALHK0005A, ALHK0005B, ALHK001 OA, ALHK0010B, ALHS0005, ALHS0010, ALHV0010, ALHY0010, ALP10024B, ALPT0024, RP118B 14RPY10BA NG02ACR136 GDHIS0011A (CGD01 B) Loss of power to these components will not adversely impact PFSSD. Redundant Train A components are unaffected by the fire or the component fails in the desired PFSSD position.

DDCN E-1 F991 0-014-01 page 3 of 3