ML070430563: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(StriderTol Bot change)
 
(One intermediate revision by the same user not shown)
Line 16: Line 16:


=Text=
=Text=
{{#Wiki_filter:AmerGen, AmerGen Energy Company www.exeloncorp.com An Exelon Company Oyster Creek US Route 9 South, P.O. Box 388 ASME Code, Section Xl Forked River, NJ 08731-0388 1 OCFR50.55a FRM 9 20 2130-07-20462 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Oyster Creek Generating Station Facility License No. DPR-16 Docket No. 50-219  
{{#Wiki_filter:AmerGen Energy Company             www.exeloncorp.com AmerGen,  An Exelon Company Oyster Creek US Route 9 South, P.O. Box 388                                         ASME Code, Section Xl Forked River, NJ 08731-0388                                                       1 OCFR50.55a FRM 9 20 2130-07-20462 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Oyster Creek Generating Station Facility License No. DPR-16 Docket No. 50-219


==Subject:==
==Subject:==
Oyster Creek Generating Station Refueling Outage 21 (1 R21) Inservice Inspection (ISI) Summary Report Submittal of the Owner's Data Reports for Inservice Inspections is required by the American Society of Mechanical Engineers (ASME) Code, Section XI. Attachment 1, "NIS-1 Owner's Data Report for Inservice Inspections," covers the Oyster Creek Generating Station Refueling Outage 21 (1R21) examinations conducted between November 23, 2004 and November 12, 2006. The report includes the second period of the Fourth Inservice Inspection (ISI) interval examinations performed in accordance with the ASME Code, Section XI, 1995 Edition with 1996 Addenda.Attachment 2, "Form NIS-1 for Containment ISI Program -IWE," includes the NIS-1 Form covering OCGS Data Report for Containment Inservice Inspections where documentation was completed between November 23, 2004 and November 12, 2006. The report includes the third period of the First Inservice Inspection (ISI) interval examinations performed in accordance with the ASME Code, Section Xl, 1992 Edition with 1992 Addenda.Attachment 3, "Form NIS-2 Owner's Report for Repairs or Replacements," includes the NIS-2 Forms covering repairs or replacements where documentation was completed between November 23, 2004 and February 8, 2007.If you should have any questions, please contact the Oyster Creek ISI Coordinator, Mr. Greg Harttraft at 609-971-2287.
Oyster Creek Generating Station Refueling Outage 21 (1 R21) Inservice Inspection (ISI) Summary Report Submittal of the Owner's Data Reports for Inservice Inspections is required by the American Society of Mechanical Engineers (ASME) Code, Section XI. Attachment 1, "NIS-1 Owner's Data Report for Inservice Inspections," covers the Oyster Creek Generating Station Refueling Outage 21 (1R21) examinations conducted between November 23, 2004 and November 12, 2006. The report includes the second period of the Fourth Inservice Inspection (ISI) interval examinations performed in accordance with the ASME Code, Section XI, 1995 Edition with 1996 Addenda.
Sincerely, 6 T thy S. Rausch ice Pres~ident, Oyster Creek Generating Station A04-f7  
Attachment 2, "Form NIS-1 for Containment ISI Program - IWE," includes the NIS-1 Form covering OCGS Data Report for Containment Inservice Inspections where documentation was completed between November 23, 2004 and November 12, 2006. The report includes the third period of the First Inservice Inspection (ISI) interval examinations performed in accordance with the ASME Code, Section Xl, 1992 Edition with 1992 Addenda.
Attachment 3, "Form NIS-2 Owner's Report for Repairs or Replacements," includes the NIS-2 Forms covering repairs or replacements where documentation was completed between November 23, 2004 and February 8, 2007.
If you should have any questions, please contact the Oyster Creek ISI Coordinator, Mr. Greg Harttraft at 609-971-2287.
Sincerely, 6 T       thy S. Rausch ice Pres~ident, Oyster Creek Generating Station A04-f7


==Enclosure:==
==Enclosure:==
OCGS ISI Post 1R21 Outage Summary Report cc: S. J. Collins, USNRC, Regional Administrator, Region I G.E. Miller, USNRC, Senior Project Manager, OCGS M. Ferdas, USNRC, Senior NRC Resident Inspector, TMI Scott Laley, Hartford Steam Boiler I&l Co. of CT File No. 07037


OCGS ISI Post 1R21 Outage Summary Report cc: S. J. Collins, USNRC, Regional Administrator, Region I G.E. Miller, USNRC, Senior Project Manager, OCGS M. Ferdas, USNRC, Senior NRC Resident Inspector, TMI Scott Laley, Hartford Steam Boiler I&l Co. of CT File No. 07037 Attachment 1 Oyster Creek Generating Station ISI Post 1R21 Outage Summary Report I lZz/FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules 1. Owner AmerGen Enerev Co. L.L.C.. 200 Exelon Way. Kennett Square, PA 19348 (Name and Address of Owner)2. Plant Oyster Creek Generating Station, Route 9 South, Forked River
Attachment 1 Oyster Creek Generating Station ISI Post 1R21 Outage Summary Report
 
IlZz/
FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules
: 1. Owner    AmerGen Enerev Co. L.L.C.. 200 Exelon Way. Kennett Square, PA 19348 (Name and Address of Owner)
: 2. Plant  Oyster Creek Generating Station, Route 9 South, Forked River, NJ 08731 (Name and Address of Plant)
: 3. Unit      I                4. Owner Certificate of Authorization (if required)        N/A S. Commercial Service Date 12/23/69          6. National Board Number for Unit Reactor Vessel 14895
: 7. Components Inspected ISI Program (See attached Table 1)
Manufacturer Component or              Manufacturer                  or Installer        State or          National Appurtenance                or Installer                  Serial No. Providence No.        Board No.
Reactor Vessel    Combustion Engineering                                                          14895 Class 1 & 2 Piping and Supports Note: Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 8 1/2 in. x II in., (2) information in items 1 through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets recorded at the top of this form.
 
Si~21 FORM NIS-1 (back)
: 8. Examination Dates 11/23/04 to 11/12/06
: 9. Inspection Period Identification: Second Period
: 10. Inspection Interval Identification: Fourth Inspection Interval
: 11. Applicable Editions for Section XI        1995      Addenda  1996
: 12. Date / Revision of Inspection Plan:      ER-OC-330-1001 Rev. 2 dated 6/7/06
: 13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See attached
: 14. Abstract of Results of Examinations and Tests. See attached
: 15. Abstract of Corrective Measures. See attached We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan

Latest revision as of 19:14, 13 March 2020

Refueling Outage 21 (1R21) Inservice Inspection (ISI) Summary Report
ML070430563
Person / Time
Site: Oyster Creek
Issue date: 02/09/2007
From: Rausch T
AmerGen Energy Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
2130-07-20462
Download: ML070430563 (50)


Text

AmerGen Energy Company www.exeloncorp.com AmerGen, An Exelon Company Oyster Creek US Route 9 South, P.O. Box 388 ASME Code, Section Xl Forked River, NJ 08731-0388 1 OCFR50.55a FRM 9 20 2130-07-20462 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Oyster Creek Generating Station Facility License No. DPR-16 Docket No. 50-219

Subject:

Oyster Creek Generating Station Refueling Outage 21 (1 R21) Inservice Inspection (ISI) Summary Report Submittal of the Owner's Data Reports for Inservice Inspections is required by the American Society of Mechanical Engineers (ASME) Code,Section XI. Attachment 1, "NIS-1 Owner's Data Report for Inservice Inspections," covers the Oyster Creek Generating Station Refueling Outage 21 (1R21) examinations conducted between November 23, 2004 and November 12, 2006. The report includes the second period of the Fourth Inservice Inspection (ISI) interval examinations performed in accordance with the ASME Code,Section XI, 1995 Edition with 1996 Addenda.

Attachment 2, "Form NIS-1 for Containment ISI Program - IWE," includes the NIS-1 Form covering OCGS Data Report for Containment Inservice Inspections where documentation was completed between November 23, 2004 and November 12, 2006. The report includes the third period of the First Inservice Inspection (ISI) interval examinations performed in accordance with the ASME Code, Section Xl, 1992 Edition with 1992 Addenda.

Attachment 3, "Form NIS-2 Owner's Report for Repairs or Replacements," includes the NIS-2 Forms covering repairs or replacements where documentation was completed between November 23, 2004 and February 8, 2007.

If you should have any questions, please contact the Oyster Creek ISI Coordinator, Mr. Greg Harttraft at 609-971-2287.

Sincerely, 6 T thy S. Rausch ice Pres~ident, Oyster Creek Generating Station A04-f7

Enclosure:

OCGS ISI Post 1R21 Outage Summary Report cc: S. J. Collins, USNRC, Regional Administrator, Region I G.E. Miller, USNRC, Senior Project Manager, OCGS M. Ferdas, USNRC, Senior NRC Resident Inspector, TMI Scott Laley, Hartford Steam Boiler I&l Co. of CT File No. 07037

Attachment 1 Oyster Creek Generating Station ISI Post 1R21 Outage Summary Report

IlZz/

FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules

1. Owner AmerGen Enerev Co. L.L.C.. 200 Exelon Way. Kennett Square, PA 19348 (Name and Address of Owner)
2. Plant Oyster Creek Generating Station, Route 9 South, Forked River, NJ 08731 (Name and Address of Plant)
3. Unit I 4. Owner Certificate of Authorization (if required) N/A S. Commercial Service Date 12/23/69 6. National Board Number for Unit Reactor Vessel 14895
7. Components Inspected ISI Program (See attached Table 1)

Manufacturer Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Providence No. Board No.

Reactor Vessel Combustion Engineering 14895 Class 1 & 2 Piping and Supports Note: Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 8 1/2 in. x II in., (2) information in items 1 through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets recorded at the top of this form.

Si~21 FORM NIS-1 (back)

8. Examination Dates 11/23/04 to 11/12/06
9. Inspection Period Identification: Second Period
10. Inspection Interval Identification: Fourth Inspection Interval
11. Applicable Editions for Section XI 1995 Addenda 1996
12. Date / Revision of Inspection Plan: ER-OC-330-1001 Rev. 2 dated 6/7/06
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See attached
14. Abstract of Results of Examinations and Tests. See attached
15. Abstract of Corrective Measures. See attached We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable) None Expiration Date N/A Date 2 g 07 Signed AmerGen Energy Co., L.L.C. B /r/f i7iji1J2*I(4*O6.-LA/C.

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and/or the State or Province of New Jersey a d pmployel by jSB.ofCT have inspected the components described in this Owners' Data Report during the period/f 1 a to /3gand state that to the best of my knowledge and belief, the Owner has performed examinations and taken correctivt measures described in this Owners' Data Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Date Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising fr onected this--inspection.

Commissions NB 9364 (1) (N) NJ766 Inspector's Siture ( National Board, State, Province and No.

Date 2--//2007.

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS Form NIS-1 for ISI Program

13. Abstract of Examinations and Tests This submittal is for the ISI examinations performed during the Oyster Creek Generating Station 1R21 refuel outage. This is Oyster Creek's second submittal for the fourth inspection interval. The exams were completed in accordance with the 1995 Edition of the ASME Code with 1996 Addenda. A total of one hundred twenty six (126) exams were completed on Class 1 and 2 systems for ASME Section XI requirements. Refer to Table 5 for system pressure test results.
14. Abstract of Results of Examinations and Tests Welds categorized as B-J, C-F-1 and C-F-2 were examined to the requirements of PDI, in compliance with the amended requirements of 10CFR50.55a for implementation of Appendix VIII of the ASME Section XI, 1995 Edition with 1996 Addenda. The reactor pressure test of the reactor coolant pressure boundary was completed at the end of the outage. Leakage at bolted flange connections was observed on some control rod drives (CRDs) and this was evaluated in accordance with Code Case N-566-1. The alternative pressure test requirements of Code Case N-416-3 were utilized for welded repairs or installation of replacement items by welding.

There were challenges identified during this inspection on the Main Steam, Isolation Condenser and Reactor Building Closed Cooling Water system piping supports in the Drywell. Scope expansion was required due to unacceptable as-found conditions on pipe supports.

15. Abstract of Corrective Measures See Table 2 for ISI and in-vessel visual inspection (IVVI) corrective measures. For ISI components not associated with IWI no indications were detected by the examinations, and there was no through-wall leakage identified at the pressure boundary. Table 3 provides the statistics for ISI examinations completed during the 1R21 outage and includes a correction from the last submittal for Category B-K. Refer to Table 4 for the ISI examinations that were completed that did not meet ASME code coverage requirements. The limitations were due to nozzle geometry, restricted access, and one-sided examinations due to attached nozzle or valve. A relief request will be submitted near the end of the interval for approval of these limited coverage examinations.

TABLE I ISI PROGRAM CODE SYSTEM ... EXAM RESULTS CAT. ITEM NO METHOD- COMPONENT ID- - . .. CLASS' WONUMBER PROGRAM -NUMBER... :.,DATE: __... r _

B-A B1.22 UT NR02 3-574A WELD 1 C2012450 ISI 221 10-21-06 NRI B-A B1.22 UT NR02 3-574B WELD 1 C2012450 ISI 221 10-21-06 NRI B-A B1.22 UT NR02 3-574C WELD 1 C2012450 ISI 221 10-21-06 NRI B-A B1.22 UT NR02 3-574D WELD 1 C2012450 ISI 221 10-21-06 NRI B-A B1.22 UT NR02 3-574E WELD 1 C2012450 ISI 221 10-22-06 NRI B-A B1.22 UT NR02 3-574F WELD 1 C2012450 ISt 221 10-22-06 NRI B-A B1.22 UT NR02 3-574G WELD 1 C2012450 ISI 221 10-22-06 NRI B-A B1.22 UT NR02 3-574H WELD 1 C2012450 ISI 221 10-22-06 NRI B-D B3.100 UT NR02 3-565E WELD 1 C2012461 ISI 221 10-25-06 NRI B-D B3.100 UT NR02 6-566A WELD 1 C2012409 ISI 221 10-27-06 NRI B-D B3.100 UT NR02 6-566B WELD 1 C2012306 ISI 221 10-27-06 NRI B-D B3.100 UT NR02 5-576 WELD 1 C2012402 ISI 221 10-23-06 NRI B-F B5.10 UT/SUR NR02 4-565E WELD

. .. 1 02012461 221 10-23-06 NRI B-F B5.10 UT/SUR NR02 5-566A WELD 1 C2012409 ISI 221 10-23-06 NRI B-F B5.10 UT/SUR NR02 5-566B WELD 1 C2012306 ISI 221 10-23-06 NRI B-F B5.10 SUR NR02 6-576 WELD 1 C2012402 ISI 221 10-22-06 NRI B-G-2 B7.50 VR-I 11-BG-0001 BOLT 1 C2012464 ISI 411 10-20-06 NRI B-G-2 B7.50 VT-1 411-BG-0002 BOLT 1 C2012464 ISI 411 10-20-06 NRI B-G-2 B7.50 VT-1 411-BG-0003 BOLT 1 C2012464 ISI 411 10-20-06 NRI B-G-2 B7.50 VT-1 411-BG-0004 BOLT 1 C2012467 ISI 411 10-20-06 NRI B-J B9.40 SUR MS-9-0031 WELD 1 C2012327 ISI 411 10-21-06 NRI B-J B9.40 SUR MS-9-0033 WELD 1 C2012327 ISI 411 10-21-06 NRI B-J 89.40 SUR MV-5-0011 WELD 1 C2012642 ISI 411 10-20-06 NRI B-J B9.40 SUR NG-A-0035 WELD 1 C2012481 ISI 223 10-26-06 NRI B-J B9.40 SUR NG-B-0033 WELD 1 02012493 ISI 223 10-25-06 NRI B-J B9.40 SUR NG-B-0034 WELD 1 C2012493 ISI 223 10-25-06 NRI B-J B9.40 SUR NG-B-0032 WELD 1 C2012469 ISI 223 10-26-06 NRI

...- CODE ISYSTEM EXAM RESULTS CAT. ITEM NO METHOD COMPONENT ID CLASS WO NUMBER PROGRAM NUMBER: - DATE -

B-J 89.40 SUR NG-C-0033 WELD I C2012469 ISI 223 10-26-06 NRI B-J B9.11 UT MS-1-0001A WELD 1 C2012306 ISI 411 10-23-06 NRI B-J B9.11 UT MS-1-0081 WELD 1 C2012286 ISt 411 10-21-06 NRI B-J B9.11 UT ND-1-0003 WELD 1 C2012509 ISI 215 10-20-06 NRI B-J B9.11 UT ND-1-0210 WELD 1 C2012521 ISI 215 10-25-06 NRI B-J B9.11 UT NE-2-0054A WELD 1 C2012202 ISI 211 10-25-06 NRI B-J B9.11 UT NE-2-0118 1 C2012200 ISI 211 10-25-06 NRI B-J B9.11 UT NE-2-0116 1 C2012199 ISI 211 10-23-06 NRI B-J B9.11 UT NE-5-0008 1 C2012170 ISI 211 10-23-06 NRI B-J B9.11 UT NE-5-0024 1 C2012194 ISI 211 10-25-06 NRI B-J B9.11 UT NG-B-0004 WELD 1 C2012667 ISI 223 10-25-06 NRI B-J B9.11 UT NU-1-0003 WELD 1 C2012530 ISI 214 10-26-06 NRI C-B C2.21 PT CD-14-001A 211-C-6 WELD 2 C2012159 ISI 211 10-22-06 NRI C-B C2.21 PT CD-14-001A 211-S-6 WELD 2 C2012161 ISI 211 10-22-06 NRI C-F-1 C5.11 UT/PT NE-1-203WELD 2 C2012222 ISI 211 10-17-06 NRI C-F-1 C5.11 UT NE-1-219 WELD 2 C2012561 ISI 211 10-21-06 NRI C-F-1 C5.11 UT NE-1-220 WELD 2 C2012158 ISI 211 10-19-06 NRI C-F-1 C5.11 UT NE-1-236 WELD 2 C2012670 ISI 211 10-19-06 NRI C-F-1 C5.11 UT NE-2-250 WELD 2 C2012556 ISI 211 10-27-06 NRI C-F-2 C5.90 SUR CC-3-0003 WELD 2 C2012400 ISI 541 10-23-06 NRI C-F-2 C5.90 SUR CC-3-0004 WELD 2 C2012400 ISI 541 10-23-06 NRI C-F-2 C5.51 UT/SUR MS-1-0039 WELD 2 C2012281 ISI 411 10-27-06 NRI C-F-2 C5.51 UT/SUR MS-1-0092 WELD 2 C2012325 ISI 411 10-18-06 NRI C-F-2 C5.51 UT/SUR MS-1-0101 WELD 2 C2012326 ISI 411 10-21-06 NRI C-F-2 C5.51 UT/SUR MS-1-0102WELD 2 C2012326 ISI 411 10-21-06 NRI C-F-2 C5.51 UT/SUR MS-1-0111 WELD 2 C2012663 ISI 411 10-21-06 NRI C-F-2 C5.51 UT/SUR NQ-2-0021 WELD 2 C2012634 ISI 241 10-27-06 NRI C-F-2 C5.51 UT/SUR NQ-2-0162 WELD 2 C2012653 ISI 241 10-27-06 NRI C-F-2 C5.51 UT/SUR NQZ-1-0020 WELD 2 C2012649 ISI 241 10-29-06 NRI C-F-2 C5.51 UT/SUR NZ-1-0013 WELD 2 C2012346 ISI 212 10-28-06 NRI C-F-2 C5.51 UT/SUR NZ-1-0018 WELD 2 C2012347 ISI 212 10-28-06 NRI C-F-2 C5.90 UT/SUR NZ-2-0004 WELD 2 C2012353 ISI 212 10-28-06 NRI C-F-2 C5.51 UT/SUR RF-2-0078 WELD 2 C2012621 ISI 422 10-22-06 NRI C-F-2 C5.51 UT/SUR RF-2-0103 WELD 2 C2012618 ISI 422 10-22-06 NRI

CODE SYSTEM EXAM RESULTS CAT. ITEM NO METHOD COMPONENT ID CLASS WO NUMBER PROGRAM NUMBER. DATE F-A F1.20 VT-3 211-BP-633-R4-0066 2 C2012171 ISI 211 10-26-06 NRI SUPPORT F-A F1.20 VT-3 211-BP-634-R9-0028 2 C2012230 ISI 211 10-19-06 NRI SUPPORT F-A F1.20 VT-3 211-BP-NE-1-H6-0063 2 C2012162 ISI 211 10-18-06 NRI SUPPORT F-A F1.10 VT-3 211-BP-NE-5-H1-0057 1 C2012170 ISl 211 11-4-06 NRI SUPPORT F-A F1.20 VT-3 212-BP-411-R1O-0078 2 C2012366 ISI 212 10-16-06 NRI SUPPORT F-A F1.20 VT-3 212-BP-411-R11-0065 2 C2012364 ISI 212 11-4-06 NRI SUPPORT F-A F1.10 VT-3 212-BP-NZ-2-HI1-0006 1 C2012328 ISl 212 10-21-06 NRI SUPPORT F-A F1.20 VT-3 212-BP-NZ-2-H2-0026 2 C2012357 ISI 212 10-17-06 NRI SUPPORT F-A F1.20 VT-3 212-BP-NZ-2-H3-0024 2 C2012354 ISI 212 10-17-06 NRI SUPPORT F-A F1.20 VT-3 212-BP-NZ-2-H43-0080 2 C2012365 ISI 212 10-20-06 NRI SUPPORT F-A F1.20 VT-3 212-BP-NZ-2-H5-0019 2 C2012358 ISl 212 10-22-06 NRI SUPPORT F-A F1.10 VT-3 212-BP-NZ-2-RI-0084 1 C2012366 ISl 212 10-15-06 NRI SUPPORT F-A F1.20 VT-3 212-BR-NZ-2-H6-0018 2 C2012363 ISI 212 10-19-06 NRI SUPPORT F-A F1.10 VT-3 213-BP-NP-2-R8B-0005 1 C2012584 ISI 213 10-26-06 NRI SUPPORT F-A F1.10 VT-3 213-BR-NP-1-R5-0014 1 C2012584 ISI 213 10-16-06 NRI SUPPORT F-A F1.10 VT-3 214-BP-NU-1-HI-0001 1 C2012530 ISI 214 11-3-06 NRI SUPPORT F-A F1.10 VT-3 214-BP-NU-1-H8-0016 1 C2012537 ISI 214 10-17-06 NRI SUPPORT F-A F1.10 VT-3 223-GR-H6(C)-0029 1 C2012469 ISI 223 10-24-06 NRI SUPPORT F-A F1.10 VT-3 225-BP-NC-4-R5-0013 1 C2012608 ISI 225 10-19-06 NRI SUPPORT F-A F1.20 VT-3 241-BP-NQ-2-H18-0022 2 C2012604 ISI 241 11-4-06 NRI SUPPORT

CODE SYSTEM ýEXAM RESULTS, CAT. ITEM NO -METHOD COMPONENT1)IDCAS W-NME-PORM NUMBER- DATE F-A F1.20 VT-3 241-BP-NQ-2-H51-0090 2 C2012603 ISI 241 10-17-06 NRI SUPPORT F-A F1.20 VT-3 241-BP-NQZ-1-R5-0098 A 2 C2012602 ISI 241 10-19-06 NRI SUPPORT F-A F1.20 VT-3 241-BP-NQZ-1-R5-0098 B 2 C2012602 ISI 241 10-19-06 NRI SUPPORT F-A F1.20 VT-3 241-BP-NQZ-T-Hl(E-0099 2 C2012602 ISI 241 10-19-06 NRI SUPPORT F-A F1.40 VT-3 411-BP-MSH-4-0030 V-1-9 1 C2012567 ISI 411 10-19-06 NRI SUPPORT F-A F1.40 VT-3 411-BP-MSH-8-0036 V-1-10 1 C2012567 ISI 411 10-19-06 NRI SUPPORT F-A FI.10 VT-3 411-BP-MS-R4-0026 SUPPORT 1 C2012564 ISI 411 11-2-06 NRI F-A F1.10 VT-3 411-BP-MS-R4A-0006 1 C2012563 ISI 411 11-5-06 NRI SUPPORT F-A F1.20 VT-3 422-1004 SUPPORT 2 C2012622 ISI 422 10-23-06 NRI F-A F1.10 VT-3 422-BP-RF-R5A-0010 SUPPORT 1 C2012656 ISI 422 10-19-06 NRI F-A F1.10 VT-3 422-BP-RF-R6A-0009 SUPPORT 1 C2012656 ISI 422 10-19-06 NRI F-A F1.10 VT-3 422-BP-RF-R-Hll-0011 1 C2012656 ISI 422 10-20-06 NRI SUPPORT F-A F1.10 VT-3 422-BP-X-4B-SS-1-0012 B 1 C2012658 ISI 422 10-23-06 NRI SUPPORT F-A F1.40 VT-3 P-20-001A H-1 2 C2012605 ISI 212 10-17-06 NRI SUPPORT F-A F1.40 VT-3 P-20-001B H-1 2 C2012606 ISI 212 10-18-06 NRI SUPPORT F-A F1.40 VT-3 TORUS (CLASS MC) SUPPORT MC C2012683A01 ISI 187 10-28-06 NRI Downcomer Brace (Below Water)

F-A F1.40 VT-3 TORUS (CLASS MC) SUPPORT MC C2012683A02 ISI 187 10-27-06 NRI Monorail Support (Above Water)

F-A F1.40 VT-3 TORUS (CLASS MC) SUPPORT MC C2012683A03 ISI 187 10-28-06 NRI Inside Torus Vent Header (Below Water)

F-A F1.40 VT-3 TORUS (CLASS MC) SUPPORT MC C2012683A04 ISI 187 10-28-06 NRI Catwalk Support Structure (Below Water)

F-A F1.40 VT-3 TORUS (CLASS MC) SUPPORT MC C2012684 ISI 187 11-3-06 NRI Vent Jet Deflector Plate and Gusset Support (Below Water)

F-A F1.40 VT-3 TORUS - VENT HEADER MC C2012717 ISI 187 10-30-06 NRI SUPPORT COLUMNS

.CODE SYSTEM: EXAM RESULTS CAT. ITEM NO METHOD COMPONENT ID CLASS WO NUMBER PROGRAM NUMBER DATE ________

F-A F1.40 VT-3 CATWALK STRUCTURAL MC C2012717 ISI 187 11-3-06 NRI ELEMENTS AND SUPPORTS (Above Water)

B-J B9.11 UT/MT NU-2-18-X 1 C2012002 PSI 214 11-1-06 NRI B-J B9.11 UT/MT NU-2-17-X 1 C2012002 PSI 214 11-1-06 NRI F-A F1.10 VT-3 216-1007 1 C2013783 PSI 216 11-9-06 NRI

TABLE 2 OYSTER CREEK GENERATING STATION ISI / IVVI CORRECTIVE MEASURES Component., - ' Deficiency. - - '- - References Disposition , -I Steam Dryer Visual Inspection identified WO C2012802 Repair was completed utilizing stop Repair indications in lower dryer banks ECR 04-00955 drilling prior to reassembly IR 547245 SRM / IRM Dry Replaced 3 IRM and 1 SRM Dry WO C2011967 Replaced Dry Tubes with previously Tubes Tubes due to normal aging identified deficiencies.

Top Guide Visual Inspection of Indications IR 547961 Condition still bounded by flaw Reported Larger Size than Previous AR 547961-02 evaluation. Top Guide is very flaw Inspection tolerant.

Shroud Vertical Visual Inspection of Indications IR 547617 Current condition acceptable with a Weld V9 Reported back in 1996 showed little AR 547617-02 reinspection interval not to exceed 10 change years per BWRVIP-76 Main Steam Mechanical Snubber Cracked IR 547847 Replaced Mechanical Snubber Support 411-0026 Spherical Bearing Main Steam Mechanical Snubber Lack of Thread IR 547286 Support was Repaired Support 411-0006 Engagement and Loose Locknut RBCCW System Spring Can Support Setting is IR 548963 Reset Spring Can Support to Proper Support 541-1018 Improper Setting Main Steam Mechanical Snubber Lack of Thread IR 550574 Support was Repaired Support 411-0007 Engagement and Loose Locknut Isolation Spring Can Support Setting is IR 548961 Reset Spring Can Support to Proper Condenser Improper Setting System Support 211-0057 1R21 Nuclear During the 1R21 NSSS Leak Test A2108628-05 Technical Evaluation Steam Supply Recordable Indications of leakage IR 553700 addressed the Bolted Flange leakage System (NSSS) were identified during VT-2 on CRD in accordance with N-566-1 Leak Results inspection I _I

TABLE 3 STATISTICS FOR ISI EXAMINATIONS Number of Components Examined Period I Period 2 CATEGORY TOTAL 1R20 1R21 1R22 B-A 40 3 8 B-D 48 12 4 B-F 49 11 4 B-G-1 22 3 0 B-G-2 13 6 4 B-J 199 34 42 B-K 29 5 0 B-N-1 3 1 0 B-N-2 32 11 0 C-B 8 2 2 C-C 26 5 0 C-F-1 29 5 5 C-F-2 81 28 15 F-A 160 40 42 Total 739 166 (22%) 126

TABLE 4 ISI LIMITED COVERAGE EXAMS

  • CODE* *:,;O;:'*PERCENT. ýSYSTEMK -'MM;;7 'RESULTS-CAT. NO ETHOD COMPONENT 101 DESCRIPIF COD WO ,' PERCENTUSYSEM EXAMT E SULT B-D B3.90 UT NR02 3-565E WELD 1 C2011461 47.9% 221 10-25-06 NRI NIE RECIRC OUTLET NOZZLE E-LOOP B-D 1B3.90 LUT NR02 5-576 WELD 1 C2012402 89% 221 10-23-06 . NRI N8 CLOSURE HEAD NOZZLE REACTOR HEAD VENT B-D 1B3.90 UT INR02 6-566A WELD 1 C2012409 . 52.9% 221 10-27-06 NRI IN3A MAIN STEAM NOZZLE ______

B-D B3.90! UT [NR02 6-566B WELD 1 ...C2012306f 52.9% 221 10-27-06 1 NRI

__I N3B MAIN STEAM NOZZLE _...._..... ..... .... .. .. _.....

B-J B9.11 LUT NE-2"0061WELD 1 C2012213 50% 211 10-22-06 NRI B-J 19.11 j UT NWELD 1 C2012152 50% 211 10-21-06 NRI B-J B9.11 1 UT

___VALVE N-2-255 WELD V-14-0036 TO PIPE 1 C2012213 50% 211 10-22-06 NRI B-J j"B9.11 UT NE-2-0257WELD 1 C2012152 50% 211 10-21-06 NRI B-J 1B9.11

_VALVE

... ... ... ... 1 .V UT V-1 4-0037 TO PIPE P IP E.................

A LV E T OWELD NE-2-220 "" I 0 ° 2 55 1.C2012153 50% % 22111 10-19-06 NRI B-J 1B9.11 jUT NE-2-240 WELD I C2012230 50% 211 10-19-06 NRI B-J B9.11 UT IVALVE TO PIPE NE-5-206 WELD 1 I

C2012221 I__

50% 211 10-24-06 NRI IVALVE TO PIPEIII.I B-J f B9.11 UT NE-5-214

,VALVE TOWELD PIPE 1 C2012160 50%

0 211 10-19-06 1"90 I1! NRI B-J 1B9.11 UT NU-1-0001 WELD I 1 C2012530 50% [ 214 10-20-06 NRI I VALVE TO PIPE ...... I 1.1 B-J 1B9.11 UT ND-10-0005 WELD PIPE TO VALVE V-16-0063 1 1 I

C2012505 1 50%

1 I

215 10-20-06 1 NRI

CAT

,______.____ ITEM METHOD

.,COMPONENT ID "-DESClrIP.T .... _ CLAASS.

ODE' _,NUMBER

-_*__ wO jPERCENT COMPLEIK SYSTEM NUMBER' EXAM E___ .DATE _NU RESULTS B-J B9.11 I UT ND-10-0009 WELD 1 C2012507 50% 215 10-25-06 NRI B-J 1II_______0_E 9.11 LUT PIPE TO VALVE P..PE.TO..VA L VE ING-A-0007 WELD Lw_................ ..................................

1I_________

02012485 I 50% I 223 ______________

10-24-06 _____________

NRI I IVALVE TO ELBOW .... .. I I I II B-J B9.11 UT NG-A-0018 WELD 1 C2012666 j 50% 223 10-24-06 NRI B-J B9.11 F

UT NG-A-0014 WELD ELBOW TO PUMPIVE 1 C2012478 50% . 223 10-25-06I NRI I PU MPTO ELBO W I. .. ..... .................

B-J B9.11 LUT NG-A-0018WELD 1 I C201248 50% 223 10-26-06 NRI B-J B9.11 UT NG-C-0006 WELD 1 C20124909 50% J 223 10-24-06 NRI VALVE TO ELBOW a I I B-J B 89.11 UT NG-B-0012 WELD 1 C2012492 50% 223 10-24-06 . NRI I B89.11 IELBOW TO VALVE PUMP TO ELBOW I I J223 I

I B-J UT I NG-C-0005 WELD 1 02012490 50% 10-24-06 NRI I ______ IPIPE, TO VALVE V-37-0020____I__________I_________I_____

B-J 29.11 LUT 6WELD E-L1-001 I C2012494 50% 223 10-25-06 NRI B-J B 89.11 L IDT NG-C-0005 WELD 1 C2012499 50% 223 10-26-06 NRI IVALVE TO ELBOW D 1 1 1 B-J 189.111 UIT N-012WELD 1 1020124961 50% 223 j10-28-061 NR

___ 189.111 UT N-016WELD 1 1020124951 50% 12231 10-25-061 ____

B-J 1B9.11 UT NG-C-0004 WELD 1 C2012499 f 50% 223 10-26-06 J NRI

_ __ _I _ _PIPE TO VALVE _ _I_ _ _ _ _ I _I_ _ _ _

C-B 02.21 UT CD-14-001A 21 1-C-6 WELD 2 C2012159 50% 1 211 10-28-06 NRI ISOLATION CONDENSER (CONDENSIER____ _________ ____

C-B 02.21

___SIDE)

LIUT NOZZLE WELD ICD-14-001A 211-S-6 WELD ISOLATION CONDENSER (STEAM SIDE)

III1 2

2f 02012161 50% } 211 10-28-06 NRI

___ ___ ____NOZZLE WELD I___ I____I I_ __ I________

TABLE 5 PRESSURE TESTING RESULTS The 1R21 class I pressure test was completed satisfactorily on 111512006 (R2060815). The following is a list of periodic pressure tests conducted since 1R20. All tests were satisfactory.

SYSTEM CLASS PM TASK WO# COMPLETE ISOL. CONDENSER 2 PMVT0008 R2013595 5/17/2005 CONT. SPRAY 2 2 PMVT0057 R2013592 4/21/2005 CONT. SPRAY 1 2 PMVT0002 R2013577 1017/2005 FEEDWATER 2 PMVT0009 R2026873 12/9/2006 MAIN STEAM 2 PMVTOO13 R2061149 11/22/2006 SD COOLING 2 PMVT0003 R2068286 10/23/2006

Attachment 2 Oyster Creek Generating Station Form NIS-1 for Containment ISI Program - IWE

FORM NIS-1 OWNER'S DATA REPORT FOR INSERVICE INSPECTIONS As required by the Provisions of the ASME Code Rules

1. Owner AmerGen Enerlv Co. L.L.C.. 200 Exelon Way. Kennett Square. PA 19348 (Name and Address of Owner)
2. Plant Oyster Creek Generating Station, Route 9 South, Forked River, NJ 08731 (Name and Address of Plant)
3. Unit Unit 1 4. Owner Certificate of Authorization (if required) N/A
5. Commercial Service Date 12/23/69 6. National Board Number for Unit Reactor Vessel 14895
7. Components Inspected Containment ISf Program - IWE (See attached Table 1)

Manufacturer Component or Manufacturer or Installer State or National Appurtenance or Installer Serial No. Providence No. Board No.

Primary Chicago Bridge & Iron Co. G-1276 2900 Containment Vessel -Drywell Primary Chicago Bridge & Iron Co. G-1277 3501 Containment Vessel - Torus 1~ t 4 1* t t t I I~

Note: Supplemental sheets in form of lists, sketches, or drawings may be used provided (1) size is 8 1/2 in. x II in., (2) information in items I through 6 on this data report is included on each sheet, and (3) each sheet is numbered and the number of sheets recorded at the top of this form.

FORM NIS-1 (back)

8. Examination Dates 11/23/04 to 11/12/06
9. Inspection Period Identification: Third Period
10. Inspection Interval Identification: First Inspection Interval
11. Applicable Editions for Section XI 1992 Addenda 1992
12. Date / Revision of Inspection Plan: ER-OC-330-1006 Rev. 3 dated 9/11/06
13. Abstract of Examinations and Tests. Include a list of examinations and tests and a statement concerning status of work required for the Inspection Plan. See attached
14. Abstract of Results of Examinations and Tests. See attached
15. Abstract of Corrective Measures. See attached We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. (if applicable) None Expiration Date N/A Date 2. ]01 Signed AmerGen Energv Co.. L.L.C. By &6/P.r PAO6.*MC.

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and/or the State or Province of New Jersey 4nd pmploye1 by, HSB.of CT have inspected the components described in this Owners' Data Report during the period//z g to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective' measures described in this Owners' Data Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Date Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising r connect d with this inspection.

Commissions NB 9364 (1) (N) NJ766 Inspector'sunature Y, National Board, State, Province and No.

I

FORM NIS-1 OWNER'S REPORT FOR INSERVICE INSPECTIONS Form NIS-1 for Containment ISI Program - IWE

13. Abstract of Examinations and Tests Visual and UT examinations were completed on the drywell and torus in accordance with ASME Section IWE (Containment Program). Oyster Creek is at the start of the third period of the first inspection internal for containment inspections. These examinations were performed to fulfill the requirements of ASME Section Xl, 1992 Edition with 1992 Addenda. Examinations were performed on all accessible areas of the interior of the drywell and torus suppression chamber, including underwater inspections of the torus.

An augmented examination of the drywell shell and exterior sand bed area was also performed.

A list identifying the components inspected has been attached as Table 1.

14. Abstract of Results of Examinations and Tests The results from the inspection of the drywell sand bed region confirmed that corrosion on the outside of the drywell shell has been arrested. UT measurements of the drywell at 19 monitoring locations for the sand bed region were satisfactory. The visual inspection of 100% of the epoxy coating in the sand bed region showed it to be in good condition. On the inside of the drywell, water was found in between the drywell concrete floor and the interior drywell shell. This water originated from typical drywell equipment leakage inside the drywell.

Inspection results for the inside of the Torus identified that the underwater coating is continuing to protect the shell from further degradation. No significant issues were identified on the Torus as result of the visual inspections completed above and below the water.

15. Abstract of Corrective Measures Due to identification of the water between the drywell concrete floor and the interior drywell shell, a new moisture barrier (caulk) was applied between the drywell interior floor and the drywell shell. A PSI inspection (VT-3) was performed of this new moisture barrier and it will be added to the Oyster Creek IWE program scope for future inspections.

Table I CONTAINMENT ISI PROGRAM - IWE CAT.. ITEM NO METHOD COMPONENT ID CODE CLASS WO NUMBER EXAM DATE E-A E1.12 VT-3 TORUS VESSEL - ID - Above and Below MC R2077340 10-28-06 Water Level C2012678 A02 E-A E1.12 VT-3 X-058A PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058B PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058C PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058D PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058E PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058F PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058G PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058H PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-0581 PENETRATION MC C2012678 10-25-06 E-A E1.12 VT-3 X-058J PENETRATION MC C2012678 10-25-06 E-A E1.20 VT-3 DOWNCOMERS SYSTEM - 120 - Above MC R2077340 11-3-06 and Below Water Level C2012678 E-A E1.20 VT-3 VENT LINES SYSTEM - 10 MC C2012678 11-3-06 E-C E4.11 VT-1 NR01 DRYWELL VESSEL - UT AREAS MC C2012677 10-23-06 FOR AUGMENTED EXAM E-D E5.30 VT-3 DRYWELL CONCRETE FLOOR TO MC (PSI) C2013727 11-4-06 SHELL SEAL - MOISTURE BARRIER E-D E5.30 VT-3 DRYWELL OD SANDBED AREA FLOOR MC R2088918 10-20-06 TO SHELL SEAL - MOISTURE BARRIER R2088924 E-G E8.10 VT-3 NR01 DRYWELL PERSONNEL AIRLOCK MC C2012677 11-4-06 BOLTING AND SEAL SURFACES E-G E8.10 VT-3 X-053A PENETRATION - TORUS MC C2012678 10-26-06 MANWAY S BOLTS E-G E8.10 VT-3 X-053B PENETRATION -TORUS MC C2012678 10-26-06 MANWAY N BOLTS

Attachment 3 FORM NIS-2 OWNER'S REPORT FOR REPAIRS AND REPLACEMENTS

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date February 10, 2005 Name 200 EXELON WAY, KENNEIT SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2008225 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY. KENNETr SQUARE. PA Expiration Date N/A Address
4. Identification of System Spent Fuel Pool Cooling System (25 1)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Manufacturer National Year Repaired, Code Name of Name of Serial No. Board Other Identification Replaced, or Stamped Component Manufacturer Replacement (Yes or No.

No)

Spent Fuel P-18-1A. Replaced No Pool Cooling Pump

7. Description of Work: Replaced Spent Fuel Pool Cooling system pump P-I 8-IA with a new pump due to internal wear.
8. Tests Conducted Hydrostatic _ Pneumatic _ Nominal Operating Pressure _X_

Other _ Pressure _psi Test Temp. °F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/2 x 11 in. (2) information in items 1 through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7th St. , New York, NY 10017 AG0527 (05101)

FORM NIS-2 (Back)

9. Remarks: Replaced Spent Fuel Pool Cooling system pump P-18-IA with a new pump due to internal wear and vibration.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period A/$V to '* and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Co mmissions NB 9364 (I) (N) NJ766 lnvctor'sSignaI National Board, State, Province, and Endorsements Date 2 / 2005 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date January 11, 2006 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet 1 of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2011271 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Service Water System (531)

I

5. (a) Applicable Construction Code ASME B31.1 1955 Edition, N/A Addenda, N-523-2 Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.
7. Description of Work: Installed repair clamp on 2 inch piping between V-3-34 and V-3-324 to repair thru wall leak.
8. Tests Conducted Hydrostatic__ Pneumatic _ Nominal Operating Pressure _X_

Other Pressure _psi Test Temp. - F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/22 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47"h St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Installed repair clamp on 2 inch piping between V-3-34 and V-3-324 to repair thru wall leak in accordance with code case N-523-2. An evaluation of the flaw causing the leakage was performed in accordance with code case N-513.

Repair clamp is planned to be removed and the piping replaced during the 11R21 refuel outage.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Rigedi 2d- ~r PMX~At1 QAG-5:

Owneror O*ner's Designee, Title Date VJANKAY 11 ,2006 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period/ .__., to _ 6 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 9364 (1) (N) NJ766 In or'sSignare National Board, State, Province, and Endorsements Date 2006 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI I.

1. Owner AmerGen Energy Co L.L.C. Date January 11, 2006 Name I

200 EXELON WAY. KENNETT SOUARE. PA Sheet 1 of 2 Address

2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH. FORKED RIVER. NJ 08731 WO# R2061656 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed bv AmerGen Enerev Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date_ N/A Address
4. Identification of System Emergency Service Water System (532) *. I. J x,
5. (a) Applicable Construction Code 'IASME B31.1 1955 Edikion, 14/A Addenda, 'NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Manufacturer National Year Repaired, Code Name of Name of Component Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped No. Replacement (Yes or No)

Check valve V-3-131 Replaced No

7. Description of Work: Replaced ESW keep fill check valve V-3-131 due to internal wear.
8. Tests Conducted Hydrostatic Pneumatic Nominal Operating PreSsure _X_

Other__ Pressure _psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 8 / x II in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47"h St. New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Replaced ESW keep fill check valve V-3-131 due to internal wear.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed f CO Date cJWA/kA!Yý (I/ ,2006 Owner or Owne s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by. HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period to I/Z4, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 9364 (1) (N) NJ766 Inspt 's signare National Board, State, Province, and Endorsements Date 2006 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date January 11,2006 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# R2063622 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Emergency Service Water System (532)

I 5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda

6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Manufacturer National Year Repaired, Code Name of Name of Component Manufacturer o.Built Board Serial No. No.al Other Identification Replaced,enor Relc Stamped (Yso No. Replacement (Yes or No)

Check valve V-3-133 Replaced No

7. Description of Work: Replaced ESW keep fill check valve V-3-133 due to internal wear.
8. Tests Conducted Hydrostatic _ Pneumatic _ Nominal Operating Pressure _X_

Other _ Pressure _psi Test Temp. 0T NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 2 x 1 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47"h St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Replaced ESW keep fill check valve V-3-133 due to internal wear.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration I)ate N/A Ricyned1 YAIAI ý4=lAi BES PO6,(NM r-A). nate *-AM ) Y/O I 2006 Owner or O~ner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period ____01 to ýý_1,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

.Commissions NB 9364 (1) (N) NJ766 National Board, State, Province, and Endorsements Date // 2 2006 AG0527 (05101)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date January 12, 2006 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet 1 of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2006266 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY. KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Service Water System (531)

I

5. (a) Applicable Construction Code ASME B31.1 1955 Edition, N/A Addenda, Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Name of Name of Manufacturer National Year Repaired, Code Component Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped No. Replacement (Yes or No)

Pipe 20 inch Service Replaced No Water Piping

7. Description of Work: Installed 20 inch service water bypass piping tie-in.
8. Tests Conducted Hydrostatic __ Pneumatic __ Nominal Operating Pressure X Other__ Pressure _psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 Y2 x I I in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7th St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Installed 20 inch service water bypass piping tie-in to service water system. Replaced flange bolting with new bolting (hot bolted).

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period 5._ to ./* and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures desci'ibed in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

  • /7,/* *, Commissions NB 9364 (I'i (N'* NJ766

.... ..... NB9... 6 1) (N J 766 N-In~~{or's Signat~'e National Board, State, Province, and Endorsements Date 2006 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date April 10, 2006 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# R2071905 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETIT SQUARE, PA Expiration Date N/A Address
4. Identification of System Emergency Service Water System (532)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A - Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Name of Name of Manufacturer National Year Repaired, Code Component Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped No. Replacement (Yes or No)

Check valve V-3-133 Replaced No

7. Description of Work: Replaced ESW keep fill check valve V-3-133 due to internal wear and broken spring.
8. Tests Conducted Hydrostatic _X_ Pneumatic _ Nominal Operating Pressure _X_

Other Pressure 59-'-" F, psi Test Temp. 0 F

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 V2 x II in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7 th St. , New York, NY 10017 AG0527 (05/0 1)

FORM NIS-2 (Back)

9. Remarks: Replaced ESW keep fill check valve V-3-133 dt ie to internal wear and broken spring. Also completed a bench hvdro test to 425 nsie on the valve body Drior to installation.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Dat e N/A Signed 151 MO6 6 Date_ APfLIL 10 ,2006 Owner or (vner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period /A L, to ý4r and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 9364 (1)(N) NJ766 Ilr ctor's Signture National Board, State, Province, and Endorsements Date 2006 AG0527 (05101)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date September 11, 2006 Name 200 EXELON WAY, KENNETT SQUARE. PA Sheet 1 of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH . FORKED RIVER. NJ 08731 WO# R2064076 US ROUTE 9 SOUTH FORKED RIVER NJ 08731 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Condensate Transfer System (424)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME National Year Repaired, Code Name of Name of Manufacturer Component Manufacturer Serial No. Board Other Identification Replaced, or Stamped No. Replacement (Yes or No)

Flow Meter FI-424-1714 Replaced No

7. Description of Work: Replaced Condensate Transfer System Flow Meter FI-424-1714 with a new one as a PM task.
8. Tests Conducted Hydrostatic _Pneumatic _ Nominal Operating Pressure _X_

Other Pressure VT-2 psi Test Temp. OF, NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/22 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet'is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47 h St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Replaced Condensate Transfer System Flow Meter FI-424-1714 with a new one as a PM task.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement conforms to the rules of the ASME Code, Section Xl.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A nntp -501F. /I I Owner oxwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period 0 to nd state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

<ý;i,,7v ý2ý,- 'ý I- - :

ss : ons 'STn 01" 1% IV 1,11*74f National Board, State, Province, and Endorsements lelctor T97n,4ure n~,tP t/ ý7 9flflI Date (I AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date October 13, 2006 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# R2088695 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE. PA Expiration Date N/A Address
4. Identification of System Emergency Service Water (532)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Name of Manufacturer National Year Repaired, Code Name of Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped Component No. Replacement (Yes or No)

Check Valve V-3-131 Replaced No

7. Description of Work: Replaced check valve V-3-131 with a new one as a PM task.
8. Tests Conducted Hydrostatic _Pneumatic I Nominal Operating Pressure _X__

Other Pressure VT-2 psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 V2 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7th St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Reolaced check valve V-3-131 with a new one as a PM task..

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed , ,

SOwner or Owvner's Designee, Title T Date m 06T 1 3, 2006 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period.507.O_ - to /_ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

_ _ _ _ _ __ Commissions NB 9364 (1) (N) NJ766 Inspector's ature National Board, State, Province, and Endorsements Date _ _ _ __ 2006_

/I --

AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date October 13, 2006 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH. FORKED RIVER, NJ 08731 WO# R2085230 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A TI A 200 EXELON WAY, KENNETT SQUARE, PA T7 A

F I" v"

n +

" v, Address

4. Identification of System, Emergency Service Water (532)
5. (a) Applicable Construction Code ASME B31.1 1955 Edition, N/A Addenda, NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Name of Name of Manufacturer National Year Repaired, Code Component Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped No. Replacement (Yes or No)

Check Valve V-3-133 Replaced No

7. Description of Work: Replaced check valve V-3-133 with a new one as a PM task.
8. Tests Conducted Hydrostatic _Pneumatic Nominal Operating Pressure _X_

Other Pressure VT-2 psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/2 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7th St., New York, NY 10017 AG0527 (05101)

FORM NIS-2 (Back)

9. Remarks: Replaced check valve V-3-133 with a new one as a PM task..

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Shined /;4 W tV4/- -r.le06(, 9W.* Date o90c-tr (3 2006 4 Owner orVbwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period- '/V/* to 11 and state that to the best of my knowledge and belief, the Owner 1_

has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 9364 (I) (N) NJ766 In tor's Sig ,6re National Board, State, Province, and Endorsements Date 2006 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date November 8, 2006 Name 200 EXELON WAY. KENNETT SOUARE. PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2013778 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A TIf A 200 EXELON WAY, KENNETT SQUARE. PA Vfl;rn*; nn ftl Ff .. USJ. Ca Address
4. Identification of System Control Rod Drive (225)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, N-416-3 Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME National Rpie, Cd Name of Manufacturer N Year Repaired, Code Name of Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped Component No. Replacement (Yes or No)

Pipe NC-2-2 weld Replaced No between V- 15-28 and V-15-29

7. Description of Work: Replaced 3" piping between valve V-15-28 and V-15-29 including weld NC-2-2.
8. Tests Conducted Hydrostatic _Pneumatic _ Nominal Operating Pressure _X_

Other Pressure VT-2 psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 /2x II in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7th St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Replaced 3" piping between valve V-15-28 and V-15-29 including weld NC-2-2.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD. CONNECTICUT have inspected the components described in this Owner's Report during the period /o1/906 to Itd./.o_, and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NBl 9364 (1) (N) NJ766 Inspat's Signat*¶e National Board, State, Province, and Endorsements Date ///,2 _ 2006 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co. L.L.C. Date December 8, 2006 Name 200 EXELON WAY. KENNETIT SOUARE. PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2012452 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Emergency Service Water (532)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, N-416-3 Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Manufacturer National Year Repaired, Code Name of Name of Replaced, or Stamped Component Manufacturer Serial No. N.Built Other Identification Board Rpaeen Yso (Yes or No. Replacement No) 10" Pipe 10" Pipe Elbow and Replaced No Elbow and spool piece spool piece

7. Description of Work: Replaced the 10 inch pipe elbow and pup piece downstream of ESW pump 1-3 discharge.
8. Tests Conducted Hydrostatic _Pneumatic - Nominal Operating Pressure _X_

0F Other Pressure VT-2 1)si Test Temp.

NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/2 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47th St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Replaced the 10 inch pipe elbow and pup piece downstream of ESW pump 1-3 discharge.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed Y g D/esigne IS[

T2006i Proeram EnOrineer Date d Owner or Ownerl Designee, TitleI CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period'/* &. to /[* and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 9364 (1) (N) NJ766 Inspecto gnature National Board, State, Province, and Endorsements Date /ZZ , 2006

(

AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co L.L.C. Date December 8, 2006 Name 200 EXELON WAY, KENNET7 SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2012497 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Emergency Service Water (532)
5. (a) Applicable Construction Code ASME B3 1.1 1955 Edition, N/A Addenda, Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.
7. Description of Work: Replaced the 10 inch pipe spool piece between V-3-65 and the 10 inch elbow.
8. Tests Conducted Hydrostatic _Pneumatic _ Nominal Operating Pressure _X_

Other Pressure VT-2 psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 V2 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 4 7th St., New York, NY 10017 AG0527 (05/0!)

FORM NIS-2 (Back)

9. Remarks: Replaced the 10 inch pipe spool piece between V-3-65 and the 10 inch elbow.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A Expiration Date N/A Signed ISI Proeram Engineer Date - 2--/* / ,2006 er or Owner's besignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD, CONNECTICUT have inspected the components described in this Owner's Report during the period $W .. to T 0i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

J4 Commissions NB 9364 (1) (N) NJ766 lnspect,,/Signatu;4" National Board, State, Province, and Endorsements Date 2006 AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co. L.L.C. Date February 8. 2007 Name 200 EXELON WAY. KENNETT SOUARE. PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit -OYSTER CREEK Name US ROUTE 9 SOUTH. FORKED RIVER. NJ 08731 WO# C2013729 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNETT SQUARE, PA Expiration Date N/A Address
4. Identification of System Drvwell and Torus (187)
5. (a) Applicable Construction Code ASME VIII 1962 Edition, N/A Addenda, 1270N-5, 1272N-5.1271N Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 w/ 1992 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Nameof Name of Manufacturer National Year Repaired, Code Component Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped CtNo. Replacement (Yes or No)

Floor to Liner Drywell Concrete Replaced No Joint Moisture Floor to Liner Joint Barrier Moisture Barrier

7. Description of Work: Replaced the moisture barrier between the drowell concrete floor and the metal liner at 10 ft.

elevation of drywell 360 deg. around.

8. Tests Conducted Hydrostatic Nominal Operating Pressure Other Visual VT-3 -psi Test Temp. OF NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 / x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 47th St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: Replaced the moisture barrier between the dr!well concrete floor and the metal liner at 10 ft. elevation of drywell 360 deg. around.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by _HSBOFQC of HARTFORD. CONNECTICUT have inspected the components described in this Owner's Report during the period/D/16/O to -0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 9364 (1) (N) NJ766

.. " nspectorvignature U National Board, State, Province, and Endorsements Date. . /;FA/2007

/

AG0527 (05/01)

FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As required by the Provisions of the ASME Code Section XI

1. Owner AmerGen Energy Co. L.L.C. Date February 8. 2007 Name 200 EXELON WAY, KENNETT SQUARE, PA Sheet I of 2 Address
2. Plant OYSTER CREEK GENERATING STATION Unit OYSTER CREEK Name US ROUTE 9 SOUTH, FORKED RIVER, NJ 08731 WO# C2012002 Address Repair Organization P.O. No., Job No., etc.
3. Work Performed by AmerGen Energy Co LLC Type Code Symbol Stamp N/A Name Authorization No. N/A 200 EXELON WAY, KENNEIT SQUARE, PA Expiration Date N/A Address
4. Identification of System Shutdown Cooling System (214)
5. (a) Applicable Construction Code ASME B31.1 1955 Edition, N/A Addenda, N-416-3 Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1995 w/ 1996 Addenda
6. Identification of Components Repaired or Replaced and Replacement Components.

ASME Manufacturer National Year Repaired, Code Name of Name of Component Manufacturer Serial No. Board Other Identification Built Replaced, or Stamped No. Replacement (Yes or

__________________________ No)

Valve V- 17-57 V-17-57 Replaced No

7. Description of Work: Replaced motor operated valve V-17-57.

'8. Tests Conducted Hydrostatic ___________ Nominal Operating Pressure X Other Visual VT-2 . -psi Test Temp. °F NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 Y2 x 11 in. (2) information in items I through 6 on this report is included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.

(12/82) This Form (E00030) may be obtained from the Order Dept., ASME, 345 E. 471 St., New York, NY 10017 AG0527 (05/01)

FORM NIS-2 (Back)

9. Remarks: -Replaced motor operated valve V-17-57.

Applicable Manufacturer's Data Reports to be attached CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this replacement (repair or replacement) conforms to the rules of the ASME Code,Section XI.

Type of Code Symbol Stamp N/A Certificate of Authorization No. N/A _________________Expiration Date N/A Signed') U ý ISI Prom'm Engineer Date " 8"A ,2007 Owner orlbwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NEW JERSEY and employed by HSB OF CT of HARTFORD. CONNECTICUT have inspected the components described in this Owner's Report during the period t 'd 2and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

.... Commissions NB 9364 (I) (N) NJ766 Inspector's SýOture ' National Board, State, Province, and Endorsements Date 2007 AG0527 (05101)