* VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261
VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 April 23, 1996 United States Nuclear Regulatory Commission                      Serial No.      96-138 Attention: Document Control Desk                                  NL&OS/EJW Washington, D.C. *20555                                            Docket No. 50-280 License No. DPR-32 Gentlemen:
* April 23, 1996 United States Nuclear Regulatory Commission                      Serial No.      96-138 Attention: Document Control Desk                                  NL&OS/EJW Washington, D.C. *20555                                            Docket No. 50-280 License No. DPR-32 Gentlemen:
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT 1 INSERVICE INSPECTION PROGRAM RELIEF REQUESTS During the recent refueling outage, Surry Power Station Unit 1 completed examinations in the first period of its third ten year inservice inspection (ISi) interval. The component examination program is conducted in accordance with ASME Section XI 1989 Edition.
VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT 1 INSERVICE INSPECTION PROGRAM RELIEF REQUESTS During the recent refueling outage, Surry Power Station Unit 1 completed examinations in the first period of its third ten year inservice inspection (ISi) interval. The component examination program is conducted in accordance with ASME Section XI 1989 Edition.
Pursuant to 10 CFR 50.55a(g)(5)(iii), relief is requested from certain requirements of the ASME Section XI Code associated with partial examinations conducted during the 1995 Surry Unit 1 refueling outage. Relief Requests SR-009 through SR-017 (attached) provide the basis for the requested relief.
Pursuant to 10 CFR 50.55a(g)(5)(iii), relief is requested from certain requirements of the ASME Section XI Code associated with partial examinations conducted during the 1995 Surry Unit 1 refueling outage. Relief Requests SR-009 through SR-017 (attached) provide the basis for the requested relief.
These relief requests have been approved by the Surry Station Nuclear Safety and Operating Committee.
These relief requests have been approved by the Surry Station Nuclear Safety and Operating Committee.
If you have any questions concerning these requests, please contact us.
If you have any questions concerning these requests, please contact us.
Very truly yours, James P. O'Hanlon Senior Vice President - Nuclear Attachments
Very truly yours, James P. O'Hanlon Senior Vice President - Nuclear Attachments 9604250440 9604-23 PDR ADOCK 05000280
          -    -
9604250440 9604-23 PDR ADOCK 05000280
       ~                      PDR
       ~                      PDR


                                                       \ ..
                                                       \ ..
'
       *J cc:    United States Nuclear Regulatory Commission Region II 101 Marietta Street, N.W.
       *J
                        *
* cc:    United States Nuclear Regulatory Commission Region II 101 Marietta Street, N.W.
Suite 2900 Atlanta, GA 30323 Mr. M. W. Branch NRC Senior Resident Inspector Surry Power Station
Suite 2900 Atlanta, GA 30323 Mr. M. W. Branch NRC Senior Resident Inspector Surry Power Station


                    *
RELIEF REQUEST SR-009 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                          Drawing#                      Class Weld 1-12        27 1/2"-RC-9-2501 R            11448-WMKS-0102AZ-1            1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-J, item number 89.11 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
* RELIEF REQUEST SR-009 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                          Drawing#                      Class Weld 1-12        27 1/2"-RC-9-2501 R            11448-WMKS-0102AZ-1            1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-J, item number 89.11 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full volumetric coverage could not be achieved due* to the configuration of the weld (pipe to reactor coolant pump) and a 1" x 5" identification tag.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full volumetric coverage could not be achieved due* to the configuration of the weld (pipe to reactor coolant pump) and a 1" x 5" identification tag.
Coverage of the volumetric examinations are detailed in Table SR-009-1. Figure SR-009-1 is provided as graphic detail of the limitations experienced. This weld is a terminal end weld and, as such, all welds of this type are scheduled for examination.
Coverage of the volumetric examinations are detailed in Table SR-009-1. Figure SR-009-1 is provided as graphic detail of the limitations experienced. This weld is a terminal end weld and, as such, all welds of this type are scheduled for examination.
Line 44: Line 37:
IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.
IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.


Table SR-009-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WMKS-0102AZ-1 Category B-J, Item B9.11 UT Scan Coverage
Table SR-009-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WMKS-0102AZ-1 Category B-J, Item B9.11 UT Scan Coverage Surface Weld No.                                  1        .8.        Coverage%              Reason For Partial 1-12                  96.2      0        100      100            100                Pipe to reactor coolant pump configuration prevented scanning from the 5 side. A l" x 5" welded tag prevented full coverage, (76% coverage obtained) for the 5" of weld circumference on the 2 side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yz node examinations were possible.
* Surface Weld No.                                  1        .8.        Coverage%              Reason For Partial 1-12                  96.2      0        100      100            100                Pipe to reactor coolant pump configuration prevented scanning from the 5 side. A l" x 5" welded tag prevented full coverage, (76% coverage obtained) for the 5" of weld circumference on the 2 side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yz node examinations were possible.
UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow
UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction
* 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow


Figure SR-009-1 Search Unit
Figure SR-009-1 Search Unit 5 Side A
* 5 Side A
               ~1 Exam. Volume                                  Exam. Volume Hatched area (in examination volume) shows extent of coverage due to the I.D. Tag.
               ~1 Exam. Volume                                  Exam. Volume
* Hatched area (in examination volume) shows extent of coverage due to the I.D. Tag.
Seventy-six (76) percent of the volume was not examined for five (5) inches.
Seventy-six (76) percent of the volume was not examined for five (5) inches.


Line 59: Line 48:
REACTOR COOLANT                                                          I    I PUMP                        GE~OR                          I    I
REACTOR COOLANT                                                          I    I PUMP                        GE~OR                          I    I
                                                       ....*r*1tc.......                                                    I    I
                                                       ....*r*1tc.......                                                    I    I
: . ..... P-u£ . .>                            l*RC-                  I    I
: . ..... P-u£ . .>                            l*RC-                  I    I I    I INOTE 'II
* I    I INOTE 'II
                                                                                               .....E*IC ...              I    I INOTE 111              I    I COLD      HOT LEG      l~G
                                                                                               .....E*IC ...              I    I INOTE 111              I    I COLD      HOT LEG      l~G
                                                                                                                                     ~ E DETAIL 'O"OH
                                                                                                                                     ~ E DETAIL 'O"OH
                                                                                                                                    '
                                                                                                                                                         'J L_4411-1tHKS*lllll2Alj JI'* 2'1'
                                                                                                                                                         'J L_4411-1tHKS*lllll2Alj JI'* 2'1'
                                                                                                                                         'Ill" RED Ell
                                                                                                                                         'Ill" RED Ell
                                                                         ,-* ...x
                                                                         ,-* ...x
                                                                                                                                                            *
{ EL. II'* 'I 15/16" ------V/
{ EL. II'* 'I 15/16" ------V/
                         ;
                         ;
Line 76: Line 62:
                                                                                                                   'J INOTE 71
                                                                                                                   'J INOTE 71


                      *
RELIEF REQUEST SR-010 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                        Drawing#                      Class Weld 1-11        31 "-RC-8-2501 R              11448-WMKS-0102AZ-1            1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-J, item number B9.11 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
* RELIEF REQUEST SR-010 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                        Drawing#                      Class Weld 1-11        31 "-RC-8-2501 R              11448-WMKS-0102AZ-1            1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-J, item number B9.11 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full coverage could not be achieved due to the configuration of the weld (pipe to reactor coolant pump) and a support. Coverage of the examinations are detailed in Table SR-010-1. Figure SR-010-1 is provided as graphic detail of the limitations experienced, where the weld could be examined. Figure SR-010-2 is provided to show the closeness of the support in relation to weld 1-11. The support is a massive welded and bolted structure that supports the reactor coolant pump and, as such, cannot be removed to allow access to weld 1-11. This weld is a terminal end and, as such, all welds of this type are scheduled for examination. Therefore, substitution with another weld is not feasible.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full coverage could not be achieved due to the configuration of the weld (pipe to reactor coolant pump) and a support. Coverage of the examinations are detailed in Table SR-010-1. Figure SR-010-1 is provided as graphic detail of the limitations experienced, where the weld could be examined. Figure SR-010-2 is provided to show the closeness of the support in relation to weld 1-11. The support is a massive welded and bolted structure that supports the reactor coolant pump and, as such, cannot be removed to allow access to weld 1-11. This weld is a terminal end and, as such, all welds of this type are scheduled for examination. Therefore, substitution with another weld is not feasible.
IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.
IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.
Line 90: Line 75:
* examinations were possible.
* examinations were possible.
UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow
UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow
                                                                                                                                                            *
 
* Figure SR-010-1 Search Unit                            Search Unit
Figure SR-010-1 Search Unit                            Search Unit 5 Side                                                                                2 Side I
* 5 Side                                                                                2 Side I
V
V
                                                                       ~I
                                                                       ~I Exam. Volume Hatched area (in examination volume) shows lack of coverage due to configuration, i.e., six (6) percent of the examination volume was not examined.
* Exam. Volume Hatched area (in examination volume) shows lack of coverage due to configuration, i.e., six (6) percent of the examination volume was not examined.


Figure SR-010-2 Reactor coolant Pump
Figure SR-010-2 Reactor coolant Pump
                   ~--+-Weld 1-11 Component Su art
                   ~--+-Weld 1-11 Component Su art 31"-RC-8-2501R at \.leld 1-11 Pipe support--.
* 31"-RC-8-2501R at \.leld 1-11 Pipe support--.
Top View Side View
Top View
* Side View


11448-WMKS-0102AZ-l (MH....
11448-WMKS-0102AZ-l (MH....
Line 109: Line 90:
I I
I I
                                               \ .... P-1c* ... >
                                               \ .... P-1c* ... >
* I    I IIIOTE 'II
I    I IIIOTE 'II
                                                                                         .... E-IC....                                I    I INIJJE II                                I    I CIJ..D    HOT LEG      LEG
                                                                                         .... E-IC....                                I    I INIJJE II                                I    I CIJ..D    HOT LEG      LEG
                                                                                                                                               ~ E DETAIL 'D'CIN  j
                                                                                                                                               ~ E DETAIL 'D'CIN  j
Line 116: Line 97:
TD 11441
TD 11441
                                               *Wl<<S*IUl3A7
                                               *Wl<<S*IUl3A7
                                                                                                                                                                      *
                     ' REACTOR                                    *.........~                                  SEE llETAIL '&'ON j ll4411*WHKS*Bll2AZj
                     ' REACTOR                                    *.........~                                  SEE llETAIL '&'ON j ll4411*WHKS*Bll2AZj
                                                                               'rl""&"&deg;*.~RC~-~:"-l*-15_0_2_*_1 VESSEL I-RC- .
                                                                               'rl""&"&deg;*.~RC~-~:"-l*-15_0_2_*_1 VESSEL I-RC- .
Line 123: Line 103:
                                                                     \
                                                                     \


                    *                                    **
RELIEF REQUEST SR-011 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                        Drawing#                        Class Weld 1-20        31 "-RC-8-2501 R              11448-WMKS-0102AZ-1              1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category 8-J, item number 89.12 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent. Code Case N524 (b), (1) modifies Table IWB-2500-1, Note (4) and only requires that examination requirements shall be met for both transverse and parallel flaws at the intersection of the welds and for that length of longitudinal weld within the circumferential examination volume.
RELIEF REQUEST SR-011 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                        Drawing#                        Class Weld 1-20        31 "-RC-8-2501 R              11448-WMKS-0102AZ-1              1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category 8-J, item number 89.12 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent. Code Case N524 (b), (1) modifies Table IWB-2500-1, Note (4) and only requires that examination requirements shall be met for both transverse and parallel flaws at the intersection of the welds and for that length of longitudinal weld within the circumferential examination volume.
Ill. BASIS FOR RELIEF The component listed above is inaccessible for both surface and volumetric examination. Examination could not be achieved due to the configuration of the support. A reactor coolant pump support/pipe support completely covers this longitudinal weld. The circumferential weld (1-11) that intersects with this longitudinal weld is a terminal end and, as such, all welds of this type are scheduled for examination. Therefore, substitution with another weld is not feasible. The adjacent longitudinal weld 1-21 (shown on drawing 11448-WMKS-0102AZ-1 and Figure SR-011-
Ill. BASIS FOR RELIEF The component listed above is inaccessible for both surface and volumetric examination. Examination could not be achieved due to the configuration of the support. A reactor coolant pump support/pipe support completely covers this longitudinal weld. The circumferential weld (1-11) that intersects with this longitudinal weld is a terminal end and, as such, all welds of this type are scheduled for examination. Therefore, substitution with another weld is not feasible. The adjacent longitudinal weld 1-21 (shown on drawing 11448-WMKS-0102AZ-1 and Figure SR-011-
Line 130: Line 109:
_J
_J


                                                                                            #
Figure SR-011-1                            !.
Figure SR-011-1                            !.
Reactor coolant Pump
Reactor coolant Pump
                                                                                            *
                                   ~ Weld 1-11 (circumferential weld)
                                   ~ Weld 1-11 (circumferential weld)
Weld 1-20 ....                    ~ Weld 1-21 (longitudinal weld)    Component (longitudinal weld)                                                  Su ort is under component support.
Weld 1-20 ....                    ~ Weld 1-21 (longitudinal weld)    Component (longitudinal weld)                                                  Su ort is under component support.
31"-RC-8-2501R at Weld 1-11 Pipe support ....
31"-RC-8-2501R at Weld 1-11 Pipe support ....
Top View
Top View Side View
* Side View


                                                                                                                                                              !.
11448-lrl4KS-0102AZ-1 REACTOR COOLANT
11448-lrl4KS-0102AZ-1 REACTOR COOLANT
                                                                                                                           ,~....
                                                                                                                           ,~....
Line 147: Line 122:
I POMP                      GE~OR                                  I      I
I POMP                      GE~OR                                  I      I
                                                   .,..*r1tc***.. .                                                        I      I
                                                   .,..*r1tc***.. .                                                        I      I
                                                 \ .... P*IC-... >                        l*RC-                            I      I
                                                 \ .... P*IC-... >                        l*RC-                            I      I I      I
* I      I
                                                                                       .....E*IC.....                      I      I INOTE 'II                                                          I      I
                                                                                       .....E*IC.....                      I      I INOTE 'II                                                          I      I
                                                                                           !NOTE Ill CDl.0
                                                                                           !NOTE Ill CDl.0
Line 155: Line 129:
                                                                                                                                       ' L44ll*WHICS*1112AZ:J ll'X 2<r
                                                                                                                                       ' L44ll*WHICS*1112AZ:J ll'X 2<r
                                                                                                                                             'II' RED ELL l EL, II'* 'I 15/16' y/
                                                                                                                                             'II' RED ELL l EL, II'* 'I 15/16' y/
                                                                                                                                                              *
                       ' REACTOR
                       ' REACTOR
(_ ......\_          ..          SEE DETAIL '8' ON -::1 114411*WHKS*lllll2AZj VESSEL                                                I &'*RC*:'1-15112* I I-RC-
(_ ......\_          ..          SEE DETAIL '8' ON -::1 114411*WHKS*lllll2AZj VESSEL                                                I &'*RC*:'1-15112* I I-RC-
Line 161: Line 134:
                                                                     \
                                                                     \


                    *
RELIEF REQUEST SR-012 I. IDENTIFICATION OF COMPONENT Weld No.        Line #                          D.rawing #                  Class Weld 1-05DM      29 11 -RC-1-2501 R              11448-WMKS-O 1OOAZ-1          1 Weld 1-06DM      31"-RC-2-2501R                  11448-WMKS-01 OOAZ-1          1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-F, item number 85.70 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
* RELIEF REQUEST SR-012 I. IDENTIFICATION OF COMPONENT Weld No.        Line #                          D.rawing #                  Class Weld 1-05DM      29 11 -RC-1-2501 R              11448-WMKS-O 1OOAZ-1          1 Weld 1-06DM      31"-RC-2-2501R                  11448-WMKS-01 OOAZ-1          1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-F, item number 85.70 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
Ill. BASIS FOR RELIEF The components listed above have been examined to the extent practical as required by the Code. However, due to the configuration of the weld (pipe to steam generator nozzle to safe end butt weld) full volumetric coverage could not be achieved. Coverage of the volumetric examinations are detailed in Table SR-012-1. Figure SR-012-1 is provided as graphic detail of the limitations experienced. All welds of this type are scheduled for examination. Therefore, substitution with other welds is not feasible.
Ill. BASIS FOR RELIEF The components listed above have been examined to the extent practical as required by the Code. However, due to the configuration of the weld (pipe to steam generator nozzle to safe end butt weld) full volumetric coverage could not be achieved. Coverage of the volumetric examinations are detailed in Table SR-012-1. Figure SR-012-1 is provided as graphic detail of the limitations experienced. All welds of this type are scheduled for examination. Therefore, substitution with other welds is not feasible.
IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code*requirements.
IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code*requirements.


Table SR-012-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WMKS-01 OOAZ-1 Category B-F, Item BS.70 UT Scan Coverage
Table SR-012-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WMKS-01 OOAZ-1 Category B-F, Item BS.70 UT Scan Coverage Surface Weld No.                                  1        .8.        Coverage%              Reason For Partial l-05DM                0        80      50      50              100                Pipe to steam generator nozzle to safe-end configuration prevented scanning from the nozzle side, and also prevented full scanning from the elbow side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yi node examinations were possible.
* Surface Weld No.                                  1        .8.        Coverage%              Reason For Partial l-05DM                0        80      50      50              100                Pipe to steam generator nozzle to safe-end configuration prevented scanning from the nozzle side, and also prevented full scanning from the elbow side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yi node examinations were possible.
l-06DM                80        0        50      50              100                Pipe to steam generator nozzle to safe-end configuration prevented scanning from the nozzle side, and also prevented full scanning from the elbow side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yi node examinations were possible UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow
l-06DM                80        0        50      50              100                Pipe to steam generator nozzle to safe-end configuration prevented scanning from the nozzle side, and also prevented full scanning from the elbow side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yi node examinations were possible
* UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow


Figure SR-012-1 Search Unit
Figure SR-012-1 Search Unit Nozzle Side Elbow Side
* Nozzle Side Elbow Side
                                                                             ..... 43&deg; Beam Angle
                                                                             ..... 43&deg; Beam Angle
                                                                       .,_  Exam. Volume t
                                                                       .,_  Exam. Volume t
* Hatched area (in examination volume) shows extent of coverage due to configuration, i.e., 20% of the examination volllne was not examined.
Hatched area (in examination volume) shows extent of coverage due to configuration, i.e., 20% of the examination volllne was not examined.


                                                                                                                ,....*..
I
I
                                                                                                                         ,I I        I REACTOR COOLANf                                      I        I I        I PJMP                                CE~OR      I        I I        I
                                                                                                                         ,I I        I REACTOR COOLANf                                      I        I I        I PJMP                                CE~OR      I        I I        I
Line 183: Line 151:
                                 ~                              r*IA                                  E*IA
                                 ~                              r*IA                                  E*IA
[,;,"    ..".,..,. I I
[,;,"    ..".,..,. I I
  *.    .... .,
   . .:, 'CO'o"    ,'*,**,
   . .:, 'CO'o"    ,'*,**,
:,*;:  ~
:,*;:  ~
Line 191: Line 158:
:.**,*-(,
:.**,*-(,
       ~                                                                                                Ll<lLl              ***'- !:*. .':*-* .*.:*                                      ..  .,;,
       ~                                                                                                Ll<lLl              ***'- !:*. .':*-* .*.:*                                      ..  .,;,
                                                                                                                                                                                                        *-*-:.
                                                                                                                                                                                         .:,:;,,,:*"*
                                                                                                                                                                                         .:,:;,,,:*"*
       ~
       ~
Line 198: Line 164:
                                                                                                                               ~.r.: .. ' . .;      ~  . . . ., .....
                                                                                                                               ~.r.: .. ' . .;      ~  . . . ., .....
l . . . . ; < ',*'.l i :~ '' .:.:- *              **,,
l . . . . ; < ',*'.l i :~ '' .:.:- *              **,,
                                                                                                                                                                                        . *****.:**.
II
II
                                                                                                                                                                                           *"* ,*: *,' ~  I
                                                                                                                                                                                           *"* ,*: *,' ~  I
Line 211: Line 176:
                                                                                                                                                                       !f~_;/:~t}ff:r,*;~,~.i1H t~~              ....; ~
                                                                                                                                                                       !f~_;/:~t}ff:r,*;~,~.i1H t~~              ....; ~
IIUd f'!!I                                ,:r:*.-;: .......1 IIH,111',.:",.)                          ~:P;*,,; ~1 .-..;*,G t  ll,11'*'1 I'.:<:.' ;/
IIUd f'!!I                                ,:r:*.-;: .......1 IIH,111',.:",.)                          ~:P;*,,; ~1 .-..;*,G t  ll,11'*'1 I'.:<:.' ;/
                                                                                                                                                                                                                *
                                                                                                                                 ~~~                VIRGINIA POWER
                                                                                                                                 ~~~                VIRGINIA POWER
                                                                                                                                 ~\~ NORTH CAROLI NA POWER NUCLEAA EMH~[RINO SERVICES RICitHO~.O.VIRCil,.IA INSERVICE INSPECTION ISOMETRIC RC SYS: LOOP A REACTOR COOLANT PIPE SURRY POWER STATION Ut,,!T I VIRGINIA POWER
                                                                                                                                 ~\~ NORTH CAROLI NA POWER NUCLEAA EMH~[RINO SERVICES RICitHO~.O.VIRCil,.IA INSERVICE INSPECTION ISOMETRIC RC SYS: LOOP A REACTOR COOLANT PIPE SURRY POWER STATION Ut,,!T I VIRGINIA POWER


                    *                                      **
RELIEF REQUEST SR-013 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                        Drawing#                      Class Weld 0-07        3"-CH-113-1503                11448-WMKS-1105B3              2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category C-F-1, item number C5.21 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less thari 10 percent.
RELIEF REQUEST SR-013 I. IDENTIFICATION OF COMPONENT Weld No.          Line#                        Drawing#                      Class Weld 0-07        3"-CH-113-1503                11448-WMKS-1105B3              2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category C-F-1, item number C5.21 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less thari 10 percent.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full volumetric coverage could not be achieved due to the configuration of the weld (pipe to valve) and a welded pipe support. Coverage of the volumetric examinations are detailed in Table SR-013-1. Figure SR-013-1 is provided as graphic detail of the limitations experienced. Substitution with another weld of the same size would not necessarily improve the examination coverage since similar.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full volumetric coverage could not be achieved due to the configuration of the weld (pipe to valve) and a welded pipe support. Coverage of the volumetric examinations are detailed in Table SR-013-1. Figure SR-013-1 is provided as graphic detail of the limitations experienced. Substitution with another weld of the same size would not necessarily improve the examination coverage since similar.
Line 226: Line 189:
accessible.
accessible.
* UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow
* UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow
* Figure SR-013-1 lleld 0-07 l
 
* 1-CH-MOV-1373
Figure SR-013-1 lleld 0-07 l
\ _____                            _,,      t 0.40011 distance from trunion to
1-CH-MOV-1373
* toe of weld. Trunion diameter is 3.2 11
\ _____                            _,,      t 0.40011 distance from trunion to toe of weld. Trunion diameter is 3.2 11


e 7 6 5 4 3          l
e 7 6 5 4 3          l
                                                                                           )-
                                                                                           )-
                                                                             \\            I
                                                                             \\            I NOTES, L~1!\~~~?[~~.~:1:::(gw~~~-i z.*1LL*1*r,c1,mtLII\SZA 11f:[C) ... f[II:._ !NIC..,US'/7 l'll[C,ll""-"IIAC""'"'I*
                                                                                          '->
NOTES, L~1!\~~~?[~~.~:1:::(gw~~~-i z.*1LL*1*r,c1,mtLII\SZA 11f:[C) ... f[II:._ !NIC..,US'/7 l'll[C,ll""-"IIAC""'"'I*
REFERENCE ORAWti-lGS1 11**1*,.S*Ur..lJ                  Pl'lllGSTll';Ho;.i,(Tt14 IIUl*CII' le!l*J5"..Z            Ill Q.olSiifJCAIIO'I BC,.~\* c,u11,a,G 11u1*"*au                        Pl*IJroGCJ1*111:11G 11,.,.,,.z,~                      l'IP'l>G CJl**l"IC
REFERENCE ORAWti-lGS1 11**1*,.S*Ur..lJ                  Pl'lllGSTll';Ho;.i,(Tt14 IIUl*CII' le!l*J5"..Z            Ill Q.olSiifJCAIIO'I BC,.~\* c,u11,a,G 11u1*"*au                        Pl*IJroGCJ1*111:11G 11,.,.,,.z,~                      l'IP'l>G CJl**l"IC
                                                                                        *
* VIRGINIA POWER NORTH CAROLI NA POWER kJCLEAR E~lf.EERlhO SER'IICES RICH<<Jf<<JoYIRulHI" INSERVICE INSPECTION ISOMETRIC CHEMICAL ANO VOLUME CDNTfiJL SURRY POWER STATION UNIT I VIRGINIA POWER CAO"'* 1c.,,,,.,,.a1111121~q11.1so ll44IS*WMl(S*IIB'!1Bl
* VIRGINIA POWER NORTH CAROLI NA POWER kJCLEAR E~lf.EERlhO SER'IICES RICH<<Jf<<JoYIRulHI" INSERVICE INSPECTION ISOMETRIC CHEMICAL ANO VOLUME CDNTfiJL SURRY POWER STATION UNIT I VIRGINIA POWER CAO"'* 1c.,,,,.,,.a1111121~q11.1so ll44IS*WMl(S*IIB'!1Bl
                                                                                                ....


                    *
RELIEF REQUEST SR-014 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                          Drawing#                      Class Weld 1-01        1 1/2"-CH-97-1502              11448-WMKS-01 OOA 1Z          1 Weld 1-01        1 1/2"-CH-95-1502              11448-WMKS-0101 A 1Z          1 Weld 1-01        1 1/2"-CH-93-1502              11448-WMKS-0102A 1Z            1 II. IMPRACTICABLE CODE REQUIREMENTS For Surry Unit 1, Relief Request SR-008 was used for weld selection of Class 1 pressure retaining welds in piping in lieu of ASME Section XI, 1989 Edition, Table IWB-2500-1, Notes 1 (b) and 2 of Category B-J. Relief Request SR-008 was approved by NRC letter 95-404, dated 7-19-95. The relief request requires that all terminal ends of piping runs connected to vessels and pumps be examined.
* RELIEF REQUEST SR-014 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                          Drawing#                      Class Weld 1-01        1 1/2"-CH-97-1502              11448-WMKS-01 OOA 1Z          1 Weld 1-01        1 1/2"-CH-95-1502              11448-WMKS-0101 A 1Z          1 Weld 1-01        1 1/2"-CH-93-1502              11448-WMKS-0102A 1Z            1 II. IMPRACTICABLE CODE REQUIREMENTS For Surry Unit 1, Relief Request SR-008 was used for weld selection of Class 1 pressure retaining welds in piping in lieu of ASME Section XI, 1989 Edition, Table IWB-2500-1, Notes 1 (b) and 2 of Category B-J. Relief Request SR-008 was approved by NRC letter 95-404, dated 7-19-95. The relief request requires that all terminal ends of piping runs connected to vessels and pumps be examined.
Ill. BASIS FOR RELIEF The components listed above are terminal ends on seal injection piping connected to the reactor coolant pumps. The welds are completely inaccessible due to their closeness to the pump flange, i.e., they are underneath the flange. The attached picture shows the configuration on the "A" loop. However, when the reactor coolant pump main flange is disassembled, the weld is accessible for examination. All terminal end welds are scheduled for examination. Therefore, substitution with another weld is not feasible. However, another weld will be selected for examination in order to ensure that 25% of examination Category B-J welds will be examined.
Ill. BASIS FOR RELIEF The components listed above are terminal ends on seal injection piping connected to the reactor coolant pumps. The welds are completely inaccessible due to their closeness to the pump flange, i.e., they are underneath the flange. The attached picture shows the configuration on the "A" loop. However, when the reactor coolant pump main flange is disassembled, the weld is accessible for examination. All terminal end welds are scheduled for examination. Therefore, substitution with another weld is not feasible. However, another weld will be selected for examination in order to ensure that 25% of examination Category B-J welds will be examined.
IV. ALTERNATE PROVISIONS It is proposed that the system leakage test and the primary loop leakage monitoring performed by the station be substituted for the Code surface examination. If a reactor coolant pump main flange is disassembled, thereby making the weld accessible for examination, the weld will be examined consistent with Code requirements.           *
IV. ALTERNATE PROVISIONS It is proposed that the system leakage test and the primary loop leakage monitoring performed by the station be substituted for the Code surface examination. If a reactor coolant pump main flange is disassembled, thereby making the weld accessible for examination, the weld will be examined consistent with Code requirements.
 
*
* SR-014-PICTURE
* SR-014-PICTURE
* 11448-WMKS-OlOOAlZ
* 11448-WMKS-OlOOAlZ CEEJ" EL.16'-e* --..
* CEEJ" EL.16'-e* --..
               ""'- ..........    \
               ""'- ..........    \
CEtr.:                      CTE]
CEtr.:                      CTE]
Line 257: Line 212:
RED
RED


  *.,.
11448~WMKS-0101A1Z i.
11448~WMKS-0101A1Z
REACT~R ~OOLANT u p 2" X 1 112" RED /    /
                                                                                                  ---
i.
REACT~R ~OOLANT u p
                            ,,,..'.
2" X 1 112" RED /    /
                               /
                               /
[IE]
[IE]
                                                                                  *,
                                                                                   \ .OJI]
                                                                                   \ .OJI]
                                                                               *,    '* 'l0" SW ELL
                                                                               *,    '* 'l0" SW ELL
Line 279: Line 228:


I "-J
I "-J
* 11448-WMKS-0102A1Z
* 11448-WMKS-0102A1Z REACTOR COOLANT
* REACTOR COOLANT
[IE]
[IE]
               '!0" SW ELL""*      /        (--l--,CH--"'35,..,,0""')                  Eill:1e
               '!0" SW ELL""*      /        (--l--,CH--"'35,..,,0""')                  Eill:1e
                                           /                                  .... ***1-RC- **..
                                           /                                  .... ***1-RC- **..
[J]D
[J]D
                                '
                                         / / mo                        /***.......e::.lC..... /
                                         / / mo                        /***.......e::.lC..... /
                                                           /"/
                                                           /"/
Line 299: Line 246:
                                                 .I "f    z*-CH-'i2-!503-  j ISi CLASS 28 151 CLASS IA 2" X 3/4' RED.
                                                 .I "f    z*-CH-'i2-!503-  j ISi CLASS 28 151 CLASS IA 2" X 3/4' RED.
ORIENTATION LOOKING NORTHWEST
ORIENTATION LOOKING NORTHWEST
* RELIEF REQUEST SR-015 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                            Drawing#                    Class Weld 2-05        1-RS-P-2A                        11448-WMKS-RS-P-2A          2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category C-G, item number C6.10 does not allow any limitations to the required surface examinations.
 
RELIEF REQUEST SR-015 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                            Drawing#                    Class Weld 2-05        1-RS-P-2A                        11448-WMKS-RS-P-2A          2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category C-G, item number C6.10 does not allow any limitations to the required surface examinations.
Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full surface coverage could not be achieved due to interferences from a pump casing support. The reduction in coverage is forty (40) percent. Figure SR-015-1 is provided as graphic detail of the limitations experienced. Substitution with another weld is not feasible because the 11 8 11 pump has the same limitation.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full surface coverage could not be achieved due to interferences from a pump casing support. The reduction in coverage is forty (40) percent. Figure SR-015-1 is provided as graphic detail of the limitations experienced. Substitution with another weld is not feasible because the 11 8 11 pump has the same limitation.
Line 310: Line 258:
                                                                                                           *I 3 11 x3 11 xV, 11 THK Angle Iron
                                                                                                           *I 3 11 x3 11 xV, 11 THK Angle Iron
               <-- Weld 2-05 Top View
               <-- Weld 2-05 Top View
                     ... 211 x1h11 Ring  Wall
                     ... 211 x1h11 Ring  Wall Welded To Casing Inaccessible (Buried)
* Welded To Casing Inaccessible (Buried)
                  !
Wall Side View Circumference is 75 11
Wall Side View Circumference is 75 11
* Starting at 011 , going clockwise, support extends from 23" to 53 11 , and makes            this    area  inaccessible for      surface examination.
* Starting at 011 , going clockwise, support extends from 23" to 53 11 , and makes            this    area  inaccessible for      surface examination.
Line 321: Line 267:
                                                                     . t !0--Rs-q-15J3 ~
                                                                     . t !0--Rs-q-15J3 ~
                                                             --.Ji. _Q!SCH_~Q!;
                                                             --.Ji. _Q!SCH_~Q!;
GAUGE CONNECTION CAN DRAIN 1t'PIPE1
GAUGE CONNECTION CAN DRAIN 1t'PIPE1 VS LC
                                            .* '-,
VS LC
* DETAIL E
* DETAIL E
(&sect;I)
(&sect;I)
Line 333: Line 277:
* OET~IL C-...___,.
* OET~IL C-...___,.


''
RELIEF REQUEST SR-016 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                            Drawing#                Class Weld 2-05        1-SI-P-1A                        11448-WMKS-SI-P-1A        2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category C-G, item number C6.10 does not allow any limitations to the required surface examinations.
                        *
* RELIEF REQUEST SR-016 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                            Drawing#                Class Weld 2-05        1-SI-P-1A                        11448-WMKS-SI-P-1A        2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category C-G, item number C6.10 does not allow any limitations to the required surface examinations.
Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 1O percent.
Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 1O percent.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full surface coverage could not be achieved due to interferences from a pump casing support. The reduction in coverage is thirty-seven (37) percent.
Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full surface coverage could not be achieved due to interferences from a pump casing support. The reduction in coverage is thirty-seven (37) percent.
Line 347: Line 289:
Vibration Plate 0"
Vibration Plate 0"
                               .. Weld 2-05 Top View
                               .. Weld 2-05 Top View
                                     .. 211 xY, 11 Ring  Wall Welded To Casing
                                     .. 211 xY, 11 Ring  Wall Welded To Casing Inaccessible (Buried)
* Inaccessible (Buried)
                      ,-----'--------!
Wall        \
Wall        \
Side View Circumference is 75 11
Side View Circumference is 75 11
* Starting at 011 , going clockwise, support extends from 3 11 to 31", and makes            this    area  inaccessible    for  surface examination .
* Starting at 011 , going clockwise, support extends from 3 11 to 31", and makes            this    area  inaccessible    for  surface examination .
    ..,
   /
   /
',


''
  ".
           **                                                                      .  .*.      ~
           **                                                                      .  .*.      ~
11448-WMKS-SI-P-lA
11448-WMKS-SI-P-lA
Line 378: Line 314:
L--,,.--~SE---.ir-~-,
L--,,.--~SE---.ir-~-,
                                                                                 -.-1
                                                                                 -.-1
                                                            '**
                                                                 -i
                                                                 -i
                                                                 ~u 12'*SH*l5J- !                                  -~ SEE OETAIL A ITEi                                *---1:BLJ SEE DETAIL B SEE DETAIL  c ..___,'
                                                                 ~u 12'*SH*l5J- !                                  -~ SEE OETAIL A ITEi                                *---1:BLJ SEE DETAIL B SEE DETAIL  c ..___,'


...
RELIEF REQUEST SR-017 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                            Drawing#                Class.
    "
                          *
* RELIEF REQUEST SR-017 I. IDENTIFICATION OF COMPONENT Weld No.        Line#                            Drawing#                Class.
Weld 3-07BC      3"-RC-35-1502                    11448-WMKS-0124A1-1      1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category 8-J, item number 89.32 does not allow any limitations to the required surface examinations.
Weld 3-07BC      3"-RC-35-1502                    11448-WMKS-0124A1-1      1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category 8-J, item number 89.32 does not allow any limitations to the required surface examinations.
Code Case N:..460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 1O percent.
Code Case N:..460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 1O percent.
Line 391: Line 323:
Therefore, substitution with another weld is not feasible.
Therefore, substitution with another weld is not feasible.
IV. ALTERNATE PROVISIONS It is proposed that a surface examination performed on the fillet weld of the reinforcement pad, and the system leakage test be substituted for the Code surface examination.
IV. ALTERNATE PROVISIONS It is proposed that a surface examination performed on the fillet weld of the reinforcement pad, and the system leakage test be substituted for the Code surface examination.
* 11448-WMKS-0124Al-1
 
11448-WMKS-0124Al-1
     ~~
     ~~
( l*RC*IJJ)                3/4' 4'-RC*34*1592*
( l*RC*IJJ)                3/4' 4'-RC*34*1592*
SCH.129
SCH.129
                                                                                                                                              *
:~:r:~:
:~:r:~:
ISi CLASS IA NON CLASSED p                                          ISi CLASS IA NON CLASSED . PRESSURIZER I-RC-
ISi CLASS IA NON CLASSED p                                          ISi CLASS IA NON CLASSED . PRESSURIZER I-RC-Bill Tll<<i                                                                                  E-2      NON 6'*RC*l7*'51l2*
* Bill Tll<<i                                                                                  E-2      NON 6'*RC*l7*'51l2*
8 NJTS
8 NJTS
* 11                                                                                                                    SCH.128 CLASSED INOTE 41 i'*RC-42*682-                  PRESSURIZER SCH. 169                        l-RC-E-2 1&-*Rt-49*692* !
* 11                                                                                                                    SCH.128 CLASSED INOTE 41 i'*RC-42*682-                  PRESSURIZER SCH. 169                        l-RC-E-2 1&-*Rt-49*692* !
                                                                                                                             /    SCH.169 i
                                                                                                                             /    SCH.169 i
PRESSURIZER I-RC-E-2}}
PRESSURIZER I-RC-E-2}}

Revision as of 23:39, 2 February 2020

Forwards Relief Requests SR-009 Through SR-017 Re Inservice Insp Program
ML18152A268
Person / Time
Site: Surry Dominion icon.png
Issue date: 04/23/1996
From: Ohanlon J
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
96-138, NUDOCS 9604250440
Download: ML18152A268 (35)


Text

VIRGINIA ELECTRIC AND POWER COMPANY RICHMOND, VIRGINIA 23261 April 23, 1996 United States Nuclear Regulatory Commission Serial No.96-138 Attention: Document Control Desk NL&OS/EJW Washington, D.C. *20555 Docket No. 50-280 License No. DPR-32 Gentlemen:

VIRGINIA ELECTRIC AND POWER COMPANY SURRY POWER STATION UNIT 1 INSERVICE INSPECTION PROGRAM RELIEF REQUESTS During the recent refueling outage, Surry Power Station Unit 1 completed examinations in the first period of its third ten year inservice inspection (ISi) interval. The component examination program is conducted in accordance with ASME Section XI 1989 Edition.

Pursuant to 10 CFR 50.55a(g)(5)(iii), relief is requested from certain requirements of the ASME Section XI Code associated with partial examinations conducted during the 1995 Surry Unit 1 refueling outage. Relief Requests SR-009 through SR-017 (attached) provide the basis for the requested relief.

These relief requests have been approved by the Surry Station Nuclear Safety and Operating Committee.

If you have any questions concerning these requests, please contact us.

Very truly yours, James P. O'Hanlon Senior Vice President - Nuclear Attachments 9604250440 9604-23 PDR ADOCK 05000280

~ PDR

\ ..

  • J cc: United States Nuclear Regulatory Commission Region II 101 Marietta Street, N.W.

Suite 2900 Atlanta, GA 30323 Mr. M. W. Branch NRC Senior Resident Inspector Surry Power Station

RELIEF REQUEST SR-009 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 1-12 27 1/2"-RC-9-2501 R 11448-WMKS-0102AZ-1 1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-J, item number 89.11 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.

Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full volumetric coverage could not be achieved due* to the configuration of the weld (pipe to reactor coolant pump) and a 1" x 5" identification tag.

Coverage of the volumetric examinations are detailed in Table SR-009-1. Figure SR-009-1 is provided as graphic detail of the limitations experienced. This weld is a terminal end weld and, as such, all welds of this type are scheduled for examination.

Therefore, substitution with another weld is not feasible.

IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.

Table SR-009-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WMKS-0102AZ-1 Category B-J, Item B9.11 UT Scan Coverage Surface Weld No. 1 .8. Coverage% Reason For Partial 1-12 96.2 0 100 100 100 Pipe to reactor coolant pump configuration prevented scanning from the 5 side. A l" x 5" welded tag prevented full coverage, (76% coverage obtained) for the 5" of weld circumference on the 2 side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yz node examinations were possible.

UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow

Figure SR-009-1 Search Unit 5 Side A

~1 Exam. Volume Exam. Volume Hatched area (in examination volume) shows extent of coverage due to the I.D. Tag.

Seventy-six (76) percent of the volume was not examined for five (5) inches.

11448-WMKS-0102AZ-l

('""")

REACTOR COOLANT I I PUMP GE~OR I I

....*r*1tc....... I I

. ..... P-u£ . .> l*RC- I I I I INOTE 'II

.....E*IC ... I I INOTE 111 I I COLD HOT LEG l~G

~ E DETAIL 'O"OH

'J L_4411-1tHKS*lllll2Alj JI'* 2'1'

'Ill" RED Ell

,-* ...x

{ EL. II'* 'I 15/16" ------V/

REACTOR VESSEL

~ **"

    • .. \ * * * ~,=s*--R-c--:--,-.,-5-.,2---1 l*RC-

......R*l ..... SEE DE TAIL 'A' ON 448*WHk5*1llll2Alj

'J INOTE 71

RELIEF REQUEST SR-010 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 1-11 31 "-RC-8-2501 R 11448-WMKS-0102AZ-1 1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-J, item number B9.11 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.

Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full coverage could not be achieved due to the configuration of the weld (pipe to reactor coolant pump) and a support. Coverage of the examinations are detailed in Table SR-010-1. Figure SR-010-1 is provided as graphic detail of the limitations experienced, where the weld could be examined. Figure SR-010-2 is provided to show the closeness of the support in relation to weld 1-11. The support is a massive welded and bolted structure that supports the reactor coolant pump and, as such, cannot be removed to allow access to weld 1-11. This weld is a terminal end and, as such, all welds of this type are scheduled for examination. Therefore, substitution with another weld is not feasible.

IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.

Table SR-010-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WM KS-0102AZ-1 .;.

Category 8-J, Item 89.11 UT Scan Coverage Surface Weld No.

1-11 0 49 46.5 50 Coverage%

50 Reason For Partial Pipe to reactor coolant pump configuration prevented scanning from the 2 side. A pipe support covering the weld from 270° to 90°, (9 O'clock to 3.

O'clock) prevented examination, both volumetric and surface, in this area.

The use of alternate angles would not have improved volumetric coverage.

Because of the use of the longitudinal wave form only 1/2 node

  • examinations were possible.

UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow

Figure SR-010-1 Search Unit Search Unit 5 Side 2 Side I

V

~I Exam. Volume Hatched area (in examination volume) shows lack of coverage due to configuration, i.e., six (6) percent of the examination volume was not examined.

Figure SR-010-2 Reactor coolant Pump

~--+-Weld 1-11 Component Su art 31"-RC-8-2501R at \.leld 1-11 Pipe support--.

Top View Side View

11448-WMKS-0102AZ-l (MH....

REACTOR COOLANT I I fYB.P OE~OR I I

        • r1te**..... "'i-Rt*""

I I

I I

\ .... P-1c* ... >

I I IIIOTE 'II

.... E-IC.... I I INIJJE II I I CIJ..D HOT LEG LEG

~ E DETAIL 'D'CIN j

' L4411*11NCS*lll2AZ~r-ll'* zqo

'Ill' RED ELL i EL, II"* 'I l!lil&'y/

TD 11441

  • Wl<<S*IUl3A7

' REACTOR *.........~ SEE llETAIL '&'ON j ll4411*WHKS*Bll2AZj

'rl""&"°*.~RC~-~:"-l*-15_0_2_*_1 VESSEL I-RC- .

......R*l ..... SEE OET AIL 'A' ON "]

INOTE 71 448*WHk5*BIB2AZj

\

RELIEF REQUEST SR-011 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 1-20 31 "-RC-8-2501 R 11448-WMKS-0102AZ-1 1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category 8-J, item number 89.12 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent. Code Case N524 (b), (1) modifies Table IWB-2500-1, Note (4) and only requires that examination requirements shall be met for both transverse and parallel flaws at the intersection of the welds and for that length of longitudinal weld within the circumferential examination volume.

Ill. BASIS FOR RELIEF The component listed above is inaccessible for both surface and volumetric examination. Examination could not be achieved due to the configuration of the support. A reactor coolant pump support/pipe support completely covers this longitudinal weld. The circumferential weld (1-11) that intersects with this longitudinal weld is a terminal end and, as such, all welds of this type are scheduled for examination. Therefore, substitution with another weld is not feasible. The adjacent longitudinal weld 1-21 (shown on drawing 11448-WMKS-0102AZ-1 and Figure SR-011-

1) was examined 100%, at weld 1-11, per Code Case N-524, with no reportable indications (NRI).

IV. ALTERNATE PROVISIONS It is proposed that the system leakage test be substituted for the Code surface and volumetric examination.

_J

Figure SR-011-1  !.

Reactor coolant Pump

~ Weld 1-11 (circumferential weld)

Weld 1-20 .... ~ Weld 1-21 (longitudinal weld) Component (longitudinal weld) Su ort is under component support.

31"-RC-8-2501R at Weld 1-11 Pipe support ....

Top View Side View

11448-lrl4KS-0102AZ-1 REACTOR COOLANT

,~....

I

)

I POMP GE~OR I I

.,..*r1tc***.. . I I

\ .... P*IC-... > l*RC- I I I I

.....E*IC..... I I INOTE 'II I I

!NOTE Ill CDl.0

  • NOT LEG L!EG

~ E DETAIL 'O'ON ' ]

' L44ll*WHICS*1112AZ:J ll'X 2<r

'II' RED ELL l EL, II'* 'I 15/16' y/

' REACTOR

(_ ......\_ .. SEE DETAIL '8' ON -::1 114411*WHKS*lllll2AZj VESSEL I &'*RC*:'1-15112* I I-RC-

., ...... R*l ..... SEE DETAIL 'A' ON INOTE 71 448*WHKS*B1ll2AZj

\

RELIEF REQUEST SR-012 I. IDENTIFICATION OF COMPONENT Weld No. Line # D.rawing # Class Weld 1-05DM 29 11 -RC-1-2501 R 11448-WMKS-O 1OOAZ-1 1 Weld 1-06DM 31"-RC-2-2501R 11448-WMKS-01 OOAZ-1 1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category B-F, item number 85.70 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.

Ill. BASIS FOR RELIEF The components listed above have been examined to the extent practical as required by the Code. However, due to the configuration of the weld (pipe to steam generator nozzle to safe end butt weld) full volumetric coverage could not be achieved. Coverage of the volumetric examinations are detailed in Table SR-012-1. Figure SR-012-1 is provided as graphic detail of the limitations experienced. All welds of this type are scheduled for examination. Therefore, substitution with other welds is not feasible.

IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code*requirements.

Table SR-012-1 Surry Unit 1 Examination Coverage Estimates (Piping) 11448-WMKS-01 OOAZ-1 Category B-F, Item BS.70 UT Scan Coverage Surface Weld No. 1 .8. Coverage% Reason For Partial l-05DM 0 80 50 50 100 Pipe to steam generator nozzle to safe-end configuration prevented scanning from the nozzle side, and also prevented full scanning from the elbow side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yi node examinations were possible.

l-06DM 80 0 50 50 100 Pipe to steam generator nozzle to safe-end configuration prevented scanning from the nozzle side, and also prevented full scanning from the elbow side. The use of alternate angles would not have improved volumetric coverage. Because of the use of the longitudinal wave form only Yi node examinations were possible UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow

Figure SR-012-1 Search Unit Nozzle Side Elbow Side

..... 43° Beam Angle

.,_ Exam. Volume t

Hatched area (in examination volume) shows extent of coverage due to configuration, i.e., 20% of the examination volllne was not examined.

I

,I I I REACTOR COOLANf I I I I PJMP CE~OR I I I I

~ l*RC* l*RC* I I

~ r*IA E*IA

[,;," ..".,..,. I I

. .:, 'CO'o" ,'*,**,

,*;: ~

I CJ 11,~.J ..... ~ J.:,........ "

..:*',I _J cif;L I ~--; :- :~., I C-===:J 1...:,,., . . . ,I CJ 'til .-..-

e!

.**,*-(,

~ Ll<lLl ***'- !:*. .':*-* .*.:* .. .,;,

.:,:;,,,:*"*

~

  • -*!.Ul'..*,,.:**I'>**,*

1J ,II .'l '.'.. , i ,I ,;,, ' -l

~.r.: .. ' . .; ~ . . . ., .....

l . . . . ; < ',*'.l i :~ .:.:- * **,,

II

  • "* ,*: *,' ~ I
11!**"'*
-;**f,**

tlL,U 'I l'l*iC.' , ,

/

&£1:Ill!l /

~EJ;ill,

  • l*RC;

.. Rel ,r .. -1,:,*J

e ~~:~:*.i:.!)'" ll I

!f~_;/:~t}ff:r,*;~,~.i1H t~~ ....; ~

IIUd f'!!I ,:r:*.-;: .......1 IIH,111',.:",.) ~:P;*,,; ~1 .-..;*,G t ll,11'*'1 I'.:<:.' ;/

~~~ VIRGINIA POWER

~\~ NORTH CAROLI NA POWER NUCLEAA EMH~[RINO SERVICES RICitHO~.O.VIRCil,.IA INSERVICE INSPECTION ISOMETRIC RC SYS: LOOP A REACTOR COOLANT PIPE SURRY POWER STATION Ut,,!T I VIRGINIA POWER

RELIEF REQUEST SR-013 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 0-07 3"-CH-113-1503 11448-WMKS-1105B3 2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination category C-F-1, item number C5.21 does not allow any limitations to the required volumetric or surface examinations. Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less thari 10 percent.

Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full volumetric coverage could not be achieved due to the configuration of the weld (pipe to valve) and a welded pipe support. Coverage of the volumetric examinations are detailed in Table SR-013-1. Figure SR-013-1 is provided as graphic detail of the limitations experienced. Substitution with another weld of the same size would not necessarily improve the examination coverage since similar.

geometric conditions are expected.

IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.

Table SR-013-1 Surry Unit 1 .

Examination Coverage Estimates (Piping) 11448-WM KS-110583 Category C-F-1, Item CS.21 UT Scan Coverage Surface Weld No. z .a Coverage% Reason For Partial 0-07 59 59 100 100 100 Pipe to valve configuration prevented scanning from the 2 side (valve side).

Welded support prevented 100% coverage from the elbow side. A 4T calibration was used to scan from the elbow side of the weld, where.

accessible.

  • UT Scan Direction Definitions 2 - Axial scan, 180 degrees from Isometric flow direction 5 - Axial scan, the same direction as the isometric flow 7 - Circumferential scan, clockwise rotation when viewing in the direction of isometric flow 8 - Circumferential scan, counter-clockwise rotation when viewing in the direction of isometric flow

Figure SR-013-1 lleld 0-07 l

1-CH-MOV-1373

\ _____ _,, t 0.40011 distance from trunion to toe of weld. Trunion diameter is 3.2 11

e 7 6 5 4 3 l

)-

\\ I NOTES, L~1!\~~~?[~~.~:1:::(gw~~~-i z.*1LL*1*r,c1,mtLII\SZA 11f:[C) ... f[II:._ !NIC..,US'/7 l'll[C,ll""-"IIAC""'"'I*

REFERENCE ORAWti-lGS1 11**1*,.S*Ur..lJ Pl'lllGSTll';Ho;.i,(Tt14 IIUl*CII' le!l*J5"..Z Ill Q.olSiifJCAIIO'I BC,.~\* c,u11,a,G 11u1*"*au Pl*IJroGCJ1*111:11G 11,.,.,,.z,~ l'IP'l>G CJl**l"IC

  • VIRGINIA POWER NORTH CAROLI NA POWER kJCLEAR E~lf.EERlhO SER'IICES RICH<<Jf<<JoYIRulHI" INSERVICE INSPECTION ISOMETRIC CHEMICAL ANO VOLUME CDNTfiJL SURRY POWER STATION UNIT I VIRGINIA POWER CAO"'* 1c.,,,,.,,.a1111121~q11.1so ll44IS*WMl(S*IIB'!1Bl

RELIEF REQUEST SR-014 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 1-01 1 1/2"-CH-97-1502 11448-WMKS-01 OOA 1Z 1 Weld 1-01 1 1/2"-CH-95-1502 11448-WMKS-0101 A 1Z 1 Weld 1-01 1 1/2"-CH-93-1502 11448-WMKS-0102A 1Z 1 II. IMPRACTICABLE CODE REQUIREMENTS For Surry Unit 1, Relief Request SR-008 was used for weld selection of Class 1 pressure retaining welds in piping in lieu of ASME Section XI, 1989 Edition, Table IWB-2500-1, Notes 1 (b) and 2 of Category B-J. Relief Request SR-008 was approved by NRC letter 95-404, dated 7-19-95. The relief request requires that all terminal ends of piping runs connected to vessels and pumps be examined.

Ill. BASIS FOR RELIEF The components listed above are terminal ends on seal injection piping connected to the reactor coolant pumps. The welds are completely inaccessible due to their closeness to the pump flange, i.e., they are underneath the flange. The attached picture shows the configuration on the "A" loop. However, when the reactor coolant pump main flange is disassembled, the weld is accessible for examination. All terminal end welds are scheduled for examination. Therefore, substitution with another weld is not feasible. However, another weld will be selected for examination in order to ensure that 25% of examination Category B-J welds will be examined.

IV. ALTERNATE PROVISIONS It is proposed that the system leakage test and the primary loop leakage monitoring performed by the station be substituted for the Code surface examination. If a reactor coolant pump main flange is disassembled, thereby making the weld accessible for examination, the weld will be examined consistent with Code requirements.

  • SR-014-PICTURE
  • 11448-WMKS-OlOOAlZ CEEJ" EL.16'-e* --..

""'- .......... \

CEtr.: CTE]

I 1/2° X 3/4* /

REO

'le* LR ELL 2* JC J,4*

RED

11448~WMKS-0101A1Z i.

REACT~R ~OOLANT u p 2" X 1 112" RED / /

/

[IE]

\ .OJI]

  • , '* 'l0" SW ELL

'lJ:li]

'l0" SW ELL I

1 112" X JI~" r;rn/

'" [I]O

' SCH. 160 FLOOR SLEEVE FL ELl-13'-6"

/

'-.J 2"-CH-94-1503-  !

ISi CLAS~ 28 ISi CLASS IA ORIENTATION LOOKING EAST

I "-J

[IE]

'!0" SW ELL""* / (--l--,CH--"'35,..,,0""') Eill:1e

/ .... ***1-RC- **..

[J]D

/ / mo /***.......e::.lC..... /

/"/

JilD

/ / '!0" SW ELL OJI]

,FLANGE BOL

'.4 STUOS T!NJ /

I 9 NUT~

~OTE~

'!0" SW ELL I 1/2" X 3/4" RED./

2"-(H*<!J-1502-

[8D

.I "f z*-CH-'i2-!503- j ISi CLASS 28 151 CLASS IA 2" X 3/4' RED.

ORIENTATION LOOKING NORTHWEST

RELIEF REQUEST SR-015 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 2-05 1-RS-P-2A 11448-WMKS-RS-P-2A 2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category C-G, item number C6.10 does not allow any limitations to the required surface examinations.

Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 10 percent.

Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full surface coverage could not be achieved due to interferences from a pump casing support. The reduction in coverage is forty (40) percent. Figure SR-015-1 is provided as graphic detail of the limitations experienced. Substitution with another weld is not feasible because the 11 8 11 pump has the same limitation.

IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.

Figure SR-015-1 (

1-RS-P-2A 3V, 11 x3 11 xV, 11 THK Angle Iron

<- Support/

Vibration Plate

  • I 3 11 x3 11 xV, 11 THK Angle Iron

<-- Weld 2-05 Top View

... 211 x1h11 Ring Wall Welded To Casing Inaccessible (Buried)

Wall Side View Circumference is 75 11

  • Starting at 011 , going clockwise, support extends from 23" to 53 11 , and makes this area inaccessible for surface examination.

11448-WMKS-RS-P-2A D <~~.;)

OUTS I DE REC I RC SPRAY PUMP D D TO 11448

-WMKS-0123N1

. t !0--Rs-q-15J3 ~

--.Ji. _Q!SCH_~Q!;

GAUGE CONNECTION CAN DRAIN 1t'PIPE1 VS LC

  • DETAIL E

(§I)

---;o~~IJ~!~~~~v~~!T'fE6Ef~IL

,. 2'Xl/2'THK RING

-::,,2:'.:!=~~=~ ---- 'WELDED ro CASING ACCESS!BL~ **. ~~ 12'-0' INACCESSIBLE JETAIL D FROM I 1448

-WMKS-1101AS

. -..... DETAIL A 20 - 1 318' DETAIL B

  • OET~IL C-...___,.

RELIEF REQUEST SR-016 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class Weld 2-05 1-SI-P-1A 11448-WMKS-SI-P-1A 2 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category C-G, item number C6.10 does not allow any limitations to the required surface examinations.

Code Case N-460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 1O percent.

Ill. BASIS FOR RELIEF The component listed above has been examined to the extent practical as required by the Code. However, full surface coverage could not be achieved due to interferences from a pump casing support. The reduction in coverage is thirty-seven (37) percent.

Figure SR-016-1 is provided as graphic detail of the limitations experienced.

Substitution with another weld is not feasible because the 11 8 11 pump has the same limitation.

IV. ALTERNATE PROVISIONS It is proposed that the examination already completed at the reduced coverage be counted as meeting the Code requirements.

Figure SR-016-1 3'1,11 x3 11 x'l, 11 THK Angle Iron

  • 1-SI-P-1A

.. Support/

Vibration Plate 0"

.. Weld 2-05 Top View

.. 211 xY, 11 Ring Wall Welded To Casing Inaccessible (Buried)

Wall \

Side View Circumference is 75 11

  • Starting at 011 , going clockwise, support extends from 3 11 to 31", and makes this area inaccessible for surface examination .

/

    • . .*. ~

11448-WMKS-SI-P-lA

.<~:i~

LOWHEAD SAFETY

)

INJECTION PUMP

")TOR ITEi CSEE NOTE Jl TO 11448 COVER

-WM~S-0127CI 10'*51*84*152* ! mTI ISEE NOTE JI

'I

.__ SEE DETAIL E VS LC

  • SEE 11448*FV*5A CCET El

@D *FOR VIBRATION PLATE DETAJ..

. 2"Xll2'THK RING

.. .,WELDED TO CASINO ACCESSIBLE *. ~I, _12*~~-.

iNACCESSIBLE

.. - Jtll'W<>I I_ Ti11CKNESS STIFFENING RIB CTYP 41 . SEE DETAIL D

,-l~~=SE!"!!!!I."--'--,

L--,,.--~SE---.ir-~-,

-.-1

-i

~u 12'*SH*l5J- ! -~ SEE OETAIL A ITEi *---1:BLJ SEE DETAIL B SEE DETAIL c ..___,'

RELIEF REQUEST SR-017 I. IDENTIFICATION OF COMPONENT Weld No. Line# Drawing# Class.

Weld 3-07BC 3"-RC-35-1502 11448-WMKS-0124A1-1 1 II. IMPRACTICABLE CODE REQUIREMENTS The 1989 Edition of ASME Section XI Table IWB-2500-1, examination Category 8-J, item number 89.32 does not allow any limitations to the required surface examinations.

Code Case N:..460, Alternative Examination Coverage for Class 1 and Class 2 Welds, allows a reduction in coverage, if it is less than 1O percent.

Ill. BASIS FOR RELIEF The weld listed above is covered by a reinforcement pad/saddle weld, which totally covers the examination area described in the Code. Therefore, examination coverage cannot be achieved due to the configuration of the piping. This weld is a branch connection and, as such, all welds of this type are scheduled for examination.

Therefore, substitution with another weld is not feasible.

IV. ALTERNATE PROVISIONS It is proposed that a surface examination performed on the fillet weld of the reinforcement pad, and the system leakage test be substituted for the Code surface examination.

11448-WMKS-0124Al-1

~~

( l*RC*IJJ) 3/4' 4'-RC*34*1592*

SCH.129

~:r:~:

ISi CLASS IA NON CLASSED p ISi CLASS IA NON CLASSED . PRESSURIZER I-RC-Bill Tll<<i E-2 NON 6'*RC*l7*'51l2*

8 NJTS

  • 11 SCH.128 CLASSED INOTE 41 i'*RC-42*682- PRESSURIZER SCH. 169 l-RC-E-2 1&-*Rt-49*692* !

/ SCH.169 i

PRESSURIZER I-RC-E-2