ML091490473: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
Line 2: Line 2:
| number = ML091490473
| number = ML091490473
| issue date = 05/29/2009
| issue date = 05/29/2009
| title = Susquehanna Units 1 and 2, ME0933 & ME0934, RAIs from Srxb Amendment Request for Changes in TS Table 3.3.5.1-1 and TS 3.10.8.f
| title = ME0933 & ME0934, RAIs from Srxb Amendment Request for Changes in TS Table 3.3.5.1-1 and TS 3.10.8.f
| author name = Vaidya B K
| author name = Vaidya B K
| author affiliation = NRC/NRR/DORL/LPLI-1
| author affiliation = NRC/NRR/DORL/LPLI-1
Line 14: Line 14:
| page count = 2
| page count = 2
| project = TAC:ME0933, TAC:ME0934
| project = TAC:ME0933, TAC:ME0934
| stage = RAI
| stage = Other
}}
}}



Revision as of 18:33, 9 February 2019

ME0933 & ME0934, RAIs from Srxb Amendment Request for Changes in TS Table 3.3.5.1-1 and TS 3.10.8.f
ML091490473
Person / Time
Site: Susquehanna  Talen Energy icon.png
Issue date: 05/29/2009
From: Bhalchandra Vaidya
Plant Licensing Branch 1
To: Filchner D L
Susquehanna
vaidya B K, NRR/Dorl/lpl1-1, 415-3308
References
TAC ME0933, TAC ME0934
Download: ML091490473 (2)


Text

From: Bhalchandra Vaidya Sent: Friday, May 29, 2009 1:20 PM To: 'dlfilchner@pplweb.com'; 'Coddington, Cornelius T'; 'ckhoffman@pplweb.com' Cc: Douglas Pickett; John Boska; Richard Guzman; Kulin Desai; Gregory Cranston

Subject:

Susquehanna, Units 1 and 2, TAC Nos. ME0933 & ME0934, RAIs(SRXB) for Amd Request Re: Changes to TS Table 3.3.5.1-1 & TS 3.10.8.f

SUBJECT:

PPL Susquehanna, Units 1 and 2. - Request for Additional Information RE: Amendment Request for Changes in TS Table 3.3.5.1-1 (CST) and TS 3.10.8.f (TAC NOS. ME0933 and ME0934)

By letter dated March 24, 2009, as supplemented by Letter dated April 24, 2009, you submitted a license amendment request to revise high pressure coolant injection system automatic suction transfer allowable value in TS Table 3.3.5.1-1 and changes to TS 3.10.8.f .

Reactor Systems Branch (SRXB) has identified the areas in which the reviewer requests additional information in order to complete the review of your application, as follows: . 1. Please provide the flow analysis as documented in EC-052-1055 to determine the new TS allowable value of 40.5 inches for the CST low level.

2. Please clarify whether the float type level switches are safety-related or not ? If they are not safety-related then justify its operability during transient and accident conditions.
3. Provide operating history of these float type level switches.

Please contact me, if you have any questions and/or need clarifications.

Bhalchandra K. Vaidya Licensing Project Manager NRC/NRR/DORL/LPL1-1 (301)-415-3308 (O) bhalchandra.vaidya@nrc.gov E-mail Properties Mail Envelope Properties ()

Subject:

Susquehanna, Units 1 and 2, TAC Nos. ME0933 & ME0934, RAIs(SRXB)

for Amd Request Re: Changes to TS Table 3.3.5.1-1 & TS 3.10.8.f Sent Date: 05/29/2009 12:54:28 PM Received Date: 05/29/2009 1:20:00 PM From: Bhalchandra Vaidya

Created By: Bhalchandra.Vaidya@nrc.gov

Recipients:

dlfilchner@pplweb.com ('dlfilchner@pplweb.com') Tracking Status: None ctcoddington@pplweb.com ('Coddington, Cornelius T')

Tracking Status: None ckhoffman@pplweb.com ('ckhoffman@pplweb.com')

Tracking Status: None Douglas.Pickett@nrc.gov (Douglas Pickett)

Tracking Status: None John.Boska@nrc.gov (John Boska)

Tracking Status: None Richard.Guzman@nrc.gov (Richard Guzman)

Tracking Status: None Kulin.Desai@nrc.gov (Kulin Desai)

Tracking Status: None Gregory.Cranston@nrc.gov (Gregory Cranston)

Tracking Status: None

Post Office:

Files Size Date & Time

MESSAGE 13955 05/29/2009

Options Expiration Date:

Priority: olImportanceNormal ReplyRequested: False Return Notification: False

Sensitivity: olNormal Recipients received: