ULNRC-05484, Responses to Requests for Additional Information Regarding Proposed Revision to Technical Specification 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air

From kanterella
Jump to navigation Jump to search

Responses to Requests for Additional Information Regarding Proposed Revision to Technical Specification 3.8.3, Diesel Fuel Oil, Lube Oil, and Starting Air
ML080800458
Person / Time
Site: Callaway Ameren icon.png
Issue date: 03/12/2008
From: Mclachlan M
AmerenUE
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
ULNRC-05484
Download: ML080800458 (10)


Text

AmerenUE P0 Box 620 Cal/away Plant Fulton, MO 65251 March 12, 2008 U.S. Nuclear Regulatory Commission Attn: Document Control Desk Mail Stop P1-137 Washington, DC 20555-0001 Ladies and Gentlemen: ULNRC-05484 DOCKET NUMBER 50-483 CALLAWAY PLANT UNIT 1 UNION ELECTRIC CO.

v"Amere RESPONSES TO REQUESTS FOR ADDITIONAL INFORMATION UE REGARDING PROPOSED REVISION TO TECHNICAL SPECIFICATION 3.8.3, "DIESEL FUEL OIL, LUBE OIL, AND STARTING AIR" Reference 1: AmerenUE Letter ULNRC-05379, "Proposed Revision to Technical Specification 3.8.3,

'Diesel Fuel Oil, Lube Oil, and Starting Air',"

dated August 20, 2007 By letter dated August 20, 2007 (Reference 1) and pursuant to 10 CFR 50.90 AmerenUE (Union Electric Company) submitted a license amendment request (LAR) to incorporate proposed changes to Technical Specification (TS) 3.8.3, "Diesel Fuel Oil, Lube Oil, and Starting Air," which specifies requirements for the diesel fuel oil storage tanks associated with the standby emergency diesel generators (EDGs) at Callaway Plant. Specifically, AmerenUE proposed an increase in the minimum fuel oil volume required to be maintained in the EDG storage tanks during applicable operating conditions. Supporting information was provided in accordance with 10 CFR 50.90.

From its ongoing review of this proposed revision to TS 3.8.3, the NRC staff has transmitted a request for additional information (RAI) containing several individual questions/requests for which responses from AmerenUE are needed in order to support completion of the NRC's review. Accordingly, this letter provides AmerenUE's response to the NRC's RAI in Attachment 1. Within the attachment, each of the individual questions/requests contained in the associated RAI is stated and immediately followed with AmerenUE's response. Text from the NRC's RAI is shown in italics.

Responding to the NRC's RAI requires no changes to be made to the proposed changes for TS 3.8.3. Further, the response to the NRC's RAI does not change the evaluations provided in the license amendment request, including the determination of no significant hazards consideration.

a subsidiary of Ameren Corporation

ULNRC-05484 March 12, 2008 Page 2 AmerenUE appreciates the NRC staffs continued review of the proposed revision to TS 3.8.3. For any questions regarding the attached information, please contact Scott A. Maglio at 573-676-8719 or Tom Elwood at (573) 676-6479.

I declare under penalty of perjury that the foregoing and attached are true and correct.

Sincerely, ,

Executed on: March 12, 2008 Mark A. McLachlan Manager Engineering Services KRG/nls Attachments: 1) Responses to NRC RAI Questions Regarding License Amendment Request OL-1271

ULNRC-05484 March 12, 2008 Page 3 cc: Mr. Elmo E. Collins, Jr.

Regional Administrator U.S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-4005 Senior Resident Inspector Callaway Resident Office U.S. Nuclear Regulatory Commission 8201 NRC Road Steedman, MO 65077 Mr. Jack N. Donohew Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop O-8B1 Washington, DC 20555-2738 Mr. Mohan C. Thadani (2 copies)

Licensing Project Manager, Callaway Plant Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory Commission Mail Stop O-8G14 Washington, DC 20555-2738

ULNRC-05484 March 12, 2008 Page 4 Index and send hardcopy to QA File A160.0761 Hardcopy:

Certrec Corporation 4200 South Hulen, Suite 422 Fort Worth, TX 76109 (Certrec receives ALL attachments as long as they are non-safeguards and may be publicly disclosed.)

Electronic distribution for the following can be made via Other Situations ULNRC Distribution:

C. D. Naslund A. C. Heflin L. H. Graessle K. A. Mills M. A. McLachlan G. A. Hughes S. A. Maglio S. L. Gallagher L. M. Belsky (NSRB)

T. B. Elwood Ms. Diane M. Hooper (WCNOC)

Mr. Dennis Buschbaum (TXU)

Mr. Scott Bauer (Palo Verde)

Mr. Stan Ketelsen (PG&E)

Mr. Scott Head (STP)

Mr. John O'Neill (Pillsbury Winthrop Shaw Pittman LLP)

Missouri Public Service Commission to ULNRC-05484 RESPONSES TO NRC RAI QUESTIONS REGARDING LICENSE AMENDMENT REQUEST OL-1271

Attachment 1 to ULNRC-05484 RESPONSES TO NRC RAI QUESTIONS REGARDING LICENSE AMENDMENT REOUEST OL-1271 In its letter dated August 20, 2007, Union Electric Company (the licensee) submitted a request to incorporate proposed changes to Technical Specification (TS) 3.8.3, "Diesel Fuel Oil, Lube Oil, and Starting Air," which specifies requirements for the diesel fuel oil

.storage tanks associated with the standby emergency diesel generators (EDGs) at the facility. As noted in the letter, the proposed changes are to Condition A of.TS 3.8.3 and associated Surveillance Requirement (SR) 3.8.3.1 in order to incorporate new values for the minimum fuel oil volume required to be contained in the EDG fuel oil storage tanks.

The minimum required fuel oil volume is being revised (increased) to provide

'conservative margin against potential vortex effects that could otherwise occur during fuel oil transfer pump operation. AmerenUE's request is currently under review by the NRC staff.

To continue the review ofAmerenUE's LAR OL-12 71, the NRC staff requests the following additionalinformation.

1. As stated in the applicationdated August 20, 2007 (ULNRC-05379), for each emergency diesel generator (EDG),fuel oil is transferredfrom the storage tank to the EDG's day tank by a can-type transferpump that is submerged in thefuel storage tank. The operatingexperience report identified a design control issue wherein vortex prevention was not taken into account in the calculationfor determining the usable volume in the dieselfuel oil storage tank. The revised calculation identified an additionalunusablefuel oil volume of approximately 0. 6% to preclude vortex problems. Describe the hydraulic calculation of the vortex problems and explain how the 0. 6% unusablefuel oil volume was determined.

Response

The equations in ASME JPGC2001/PWR- 19010 were used to determine the required fuel oil transfer pump submergence. The ASME JPGC2001/PWR-19010 paper was commissioned by D.C. Cook Nuclear Plant due to discovery of a scenario where their suction line from the Refueling Water Storage Tank (RWST) could become uncovered.

The goal of the ASME investigations was to determine the amount of air ingestion that would be expected due to vortexing (when the suction is still submerged) and when the suction is partially uncovered under several different flow conditions. Since the available data at the time of the study were notapplicable to these situations, hydraulic testing was conducted using a 1:4 geometric scale modelof the RWST and associated pump suction piping. Several water levels and flow rates were tested with the water level both above and below the top of the suction pipe.

Page 1 of 5 to ULNRC-05484 During the ASME testing, it was observed that at model flow rates greater than 120 gpm, air entrainment occurred with the water level above the top of the horizontal suction pipe due to the formation of free vortices in the tank. At this flow rate, the Reynolds number and the Weber number exceeded 3 x 104 and 120, respectively.

Founded on previously developed generalized techniques for evaluating scale effects on vortex formation, the study concluded that the viscous and surface tension forces were negligible.1 Based on this, the study concluded that the governing dimensionless parameter is the Froude number.

This conclusion becomes very important when the formulations developed in this paper are applied to Callaway's EDG fuel oil transfer pumps. Clearly, disparities in physical properties exist between the fluid studied in the ASME model (fresh water) and in the fluid pumped by the EDG fuel oil transfer pumps (#2 diesel). The primary differences are in the densities, viscosities, and surface tension. Recalling the conclusion that the viscous and surface tension forces were negligible (i.e., the Reynolds and Weber numbers are not the governing dimensionless parameters), it is reasonable to assume that the results of the study may be utilized for applications using diesel fuel oil as the pumped fluid.

Because geometry is an important consideration when utilizing scale models to analyze fluid flow characteristics, another difference between the ASME JPCG2001/PWR-19010 model and Callaway's fuel oil transfer pump installation needed to be reconciled. The ASME model consisted of a suction line connected to the side of a tank. Callaway's fuel oil transfer pumps' suction is horizontal; however, it is located in an open portion of its tank.

A flush penetration (inside) side suction configuration like that of the ASME model tends to be beneficial in the breakup of free vortices. The vertical portion of the tank wall above the suction line acts like a vortex breaker. When a vortex collides with the side of the tank, it gets disrupted and may break up prior to being pulled into the suction line.

Callaway's fuel oil transfer pumps take suction through a weld neck flange connected directly to the pump inlet. (There are no connections to the flange.) The hub surrounding the inlet of the flange will act in a manner similar to the tank wall described previously.

Another consideration for applying the ASME model to some tank configurations (such as at Callaway) is that for small suction inlet diameters and relatively high flowrates (at runout conditions), the Froude number is higher than the Froude number range studied in ASME JPCG2001/PWR-19010 (0 < Fr < 1.40). For example, Brunswick Nuclear Power Plant applied the results of ASME JPCG2001/PWR- 19010 For Reynolds numbers greater than 3 x 104, viscous forces are negligible, and for Weber numbers greater than 120, surface tension forces are negligible. [ASME JPCG2001/PWR-19010]

Page 2 of 5

C_

-Attachment 1 to ULNRC-05484 to a vortex issue associated with their Condensate Storage Tank. For the Condensate Storage Tank vortexing evaluations performed at Brunswick, it was determined that the Froude number range was outside the range specified in the ASME paper.

Brunswick's solution was to perform their own scale model testing. The purpose of the testing was not to establish new equations, but instead to validate the existing equations published in the ASME paper for the original range of Froude numbers and to determine their behavior for an expanded range of Froude numbers (Fr > 1.40).

Brunswick's testing concluded that the required submergence predicted by the ASME formulations was conservative (i.e., the ASME equations required the suction inlet to be deeper). This conclusion was found to be true for the entire tested range of Froude numbers.

The Brunswick results supported use of the ASME JPGC2001/PWR-1 9010 methodology in the calculations performedfor Callaway's EDG fuel oil storage tanks. Accordingly, Callaway's calculation used pump suction inlet diameter and runout flowrate to calculate the fluid velocity and subsequently the Froude number.

The Froude number was then input into the equations developed in ASME JPGC2001/PWR-19010 to determine the required submergence, a dimensionless parameter used to ensure the depth of the suction pipe entrance is sufficient to preclude free vortex formation and ingestion. Using the calculated submergence and the pipe inner diameter, the required fluid depth was determined which, after subtracting the pipe inner diameter, yielded the liquid height required to maintain the new unusable fuel oil volume. This value was then rounded up to 2 inches to incorporate additional conservatism.

Because the Callaway EDG Fuel Oil Storage Tanks are installed at a slight angle, a model was developed wherein incremental cross-sectional volume slices were added to get the total fluid volume of the tanks. (Cross-sectional volumes were determined using fluid level, tank radius, and slice thickness.) In the model the fluid level was increased in 1/ 1 0 th inch increments until the computed transfer pump submergence was at least two inches. The volume at this fluid level represents the new unusable volume of approximately 500 gallons. The increase of the required 7-day fuel oil volume from 80,400 gallons to 80,900 gallons corresponds to an increase of approximately 0.6%.

References:

ASME JPGC2001/PWR-19010 Calculation JE-13 Rev. 0 Page 3 of 5 to ULNRC-05484

2. The formation of surface andsubsurface Vortices can cause numerous hydraulic problems. If the disturbancecontinues, thefluidflow will carry the,submergedpart of the vortex down toward the suction and ultimately into the pump. 'However, the vortex disturbancemay also carrythe submergedsludge, water and bio-film from bottom of the tank toward the pump suction. Discuss how fuel oil contamination caused by vortex disturbanceis prevented.

Response

The required minimum fuel oil storage volumes contain an unusable volume that provides sufficient submergence of the transfer pump suction nozzle to preclude the formation of surface and subsurface vortices. Therefore, fuel oil contamination due to Vortex disturbance is not credible.

Furthermore, several system features are present to protect the EDGs from contaminated fuel oil:

The oil fill connection to the underground storage tank is located above grade and includes a strainer.

  • Duplex basket strainers and duplex oil filters are installed in series on the fuel oil lines from the day tank to the engine.

The storage tanks have integral sumps. Each tank is sloped to the sump. Sample lines extend from the sumps to the vaults for periodic.bottom sampling and water draw-off.

References:

Calculation JE-13 Rev. 0 FSAR SP Sections 9.5.4.2.1 & 9.5.4.2.2

3. As stated in the application,the originalcalculationfor the fuel oil storage tank has accountedfor net positive suction head with respect to the fuel oil transferpumps.

Address whether thefuel oil storage tank useablefuel volume calculation has considered transferpump minimum submergence includingfuel Oil at bottom of the tank that is not draw-able.

Response

The required minimum fuel oil storage volumes contain an unusable volume that accounts for the location of the pump suction nozzle location (9-1/2" above tank bottom), includes an allowance for vortex prevention, and ensures the fluid height necessary to provide the required net positive, suction head is available.

Reference:

Calculation JE- 13 Rev. 0 Page 4 of 5 to ULNRC-05484

4. The applicationdid not address whether outdoor temperature changes were taken into account in the originalcalculations. Forcold weather operation,both pour point and viscosity may affect the capabilityof the fuel oil transferfrom the storage tank to the EDG. Provide information on pourpoint, cloudpoint, and viscosity characteristicsfor the fuel oil transfer calculationduring extreme cold ambient temperatureconditions.

Response

FSAR SP Table 9.5.4-3 describes Callaway's compliance with Regulatory Guide 1.137, Fuel-Oil Systems for Standby Diesel Generators. As noted therein, Callaway complies with Section 7.3 of ANSI N195-1976 which states that adequate heating shall be provided for the fuel oil system. Further, assurance is provided that fuel oil can be supplied and ignited at all times under the most severe environmental conditions expected at the facility. This is accomplished by maintenance of the onsite fuel oil above the "Cloud Point" temperature per Callaway Chemistry departmental procedure, CSP-ZZ-07350, Diesel Fuel Oil Testing Program. In addition, prior to addition to the supply tanks, new fuel oil is tested for viscosity (in lieu of cloud point), as stated in FSAR SP Table 9.5.4-3, and per CSP-ZZ-07350, Diesel Fuel Oil Testing Program.

In addition, as described in FSAR SP Section 9.5.4.3, maintenance of the fuel oil temperature is achieved for portions of the system that are above ground by enclosing the equipment in heated buildings and by burial below the frostline for underground portions of the system.

Regardless of the above, however, and as noted in the response to Question 1, the ASME study concluded that the viscous and surface tension forces are negligible in the determination of required submergence for precluding vortex formation.

Viscosity was therefore not an input to Callaway's calculation. See the response to Question 1 for a discussion of the ASME study and Callaway's EDG fuel oil storage tank and day tank volume requirements calculation.

Reference:

FSAR SP Table 9.5.4-3 and Section 9.5.4.3 ANSI N195-1976 CSP-ZZ-07350, Diesel Fuel Oil Testing Program ASME JPGC2001/PWR-19010 Calculation JE-13 Rev. 0 Page 5 of .5