- ML20081B377 + (13:21:57, 14 December 2024)
- 05000361/LER-1983-123-03, /03L-0:on 830913,w/Unit 2 in Mode 1 & Unit 3 in Mode 3,insp of Electrical Penetrations Revealed Two Holes in Penetration Seals in Auxiliary Bldg Control Area.Caused by Procedural Deficiencies During Const + (13:21:59, 14 December 2024)
- ML20081B366 + (13:22:00, 14 December 2024)
- 05000362/LER-1983-065-03, /03L-0:on 830905 & 12,w/unit in Mode 2 at Zero Power,High Range in-containment Radiation Monitor 3RI-7820-1 Found in Failed Low Condition & Declared Inoperable.Caused by Faulty Electrical Cable Penetration Path + (13:22:02, 14 December 2024)
- ML20081B359 + (13:22:03, 14 December 2024)
- 05000373/LER-1983-116-03, /03L-0:on 830926,control Rod Drive (CRD) at Core Location 30-19 Indicated Overtravel When Withdrawn to Full Out Position.Caused by Inner Filter Retainer Spring Damage Due to Excessive Crud Buildup + (13:22:04, 14 December 2024)
- ML20081B348 + (13:22:05, 14 December 2024)
- HL-4771, Forwards Rev 13B to FSAR for Ei Hatch Nuclear Plant & Rev 10B to Fire Hazards Analysis & Fire Protection Programs for Plant Hatch Units 1 & 2 + (13:22:06, 14 December 2024)
- 05000249/LER-1983-032-03, /03L-0:on 830921,valve LPCI 1501-11B Closed During Installation of Terminal Jumper.Caused by Technician Inadvertently Placing Terminal Jumper on 903-3 Panel Instead of 903-10 Panel + (13:22:08, 14 December 2024)
- ML20081B340 + (13:22:09, 14 December 2024)
- 05000361/LER-1983-124-03, /03L-0:on 830917 & 23,control Element Assembly Calculator Declared Inoperable Due to Spurious Position from Control Element Assembly 20.Caused by Defective Board & Connector.Equipment Replaced + (13:22:10, 14 December 2024)
- ML20081B333 + (13:22:11, 14 December 2024)
- NG-83-3408, Discusses Scram Discharge Vol short-term Mods in Response to IE Bulletin 80-17.Water Added to Scram Discharge Vol & Vent Procedures & Drain Valve Operability & Closure Time Test Changed from Quarterly to Monthly + (13:22:12, 14 December 2024)
- ML20081B328 + (13:22:16, 14 December 2024)
- ML20081B330 + (13:22:16, 14 December 2024)
- ML20081B323 + (13:22:17, 14 December 2024)
- ML20081B325 + (13:22:17, 14 December 2024)
- 05000362/LER-1983-076-03, /03L-0:on 830907,during Shift Surveillance, Control Element Assembly Calculator 2 Declared Inoperable. Caused by Poorly Seated Circuit Board.Circuit Boards Resealed + (13:22:19, 14 December 2024)
- ML20081B314 + (13:22:20, 14 December 2024)
- ML20081B318 + (13:22:20, 14 December 2024)
- 05000362/LER-1983-073-01, /01T-0:on 830929,charging & Letdown Flows Isolated by Closing Manual Isolation Valves S31208MU084 & S31208MU091 in Violation of Limiting Conditions of Operation.Caused by Personnel Error.Valves Opened on 830930 + (13:22:28, 14 December 2024)
- AECM-83-0668, Final Deficiency Rept PRD-83/12 for Unit 1 & Interim Rept for Unit 2 Re Failure of Agastat GP Series Relays to Switch. Initially Reported on 830902.Deficiency Reportable Per Part 21 for Unit 1.Investigation Ongoing for Unit 2 + (13:22:30, 14 December 2024)
- ML20081B281 + (13:22:30, 14 December 2024)
- ML20081B278 + (13:22:31, 14 December 2024)
- ML20081B277 + (13:22:31, 14 December 2024)
- ML20081B276 + (13:22:32, 14 December 2024)
- 05000362/LER-1983-064-03, W/Unit in Mode 2,ex-core Logarithmic Power Safety Channel C Declared Inoperable & on 830918,channel B Declared Inoperable.Caused by Failed Cable Connectors.Connectors Replaced + (13:22:33, 14 December 2024)
- ML20081B274 + (13:22:34, 14 December 2024)
- 05000249/LER-1983-034-03, /03L-0:on 830923,during Normal Operation,Mobile Crane Hit Wet Pipe Sprinkler Drain Valve,Breaking Valve & Spraying Water on Trackway.Caused by Personnel Error.Valve Repaired.Personnel Counseled + (13:22:36, 14 December 2024)
- ML20081B263 + (13:22:37, 14 December 2024)
- ML20081B265 + (13:22:37, 14 December 2024)
- 05000265/LER-1983-017-03, /03L-0:on 830924,during RCIC Turbine Area High Temp Switch Calibr QIS-28,temp Switches TS 2-1360-15B,16B & 14D Tripped Above Tech Spec Limit.Caused by Setpoint Drift. Switches Replaced + (13:22:39, 14 December 2024)
- ML20081B257 + (13:22:40, 14 December 2024)
- 05000362/LER-1983-069-03, /03L-0:on 830917,w/unit in Mode 3,condenser Air Ejector wide-range Gas Monitor 3RI-3870 Declared Inoperable. Caused by Loss of Communication Between RM80 Microprocessor & RM23 Control Room Readout.Data Base Reloaded + (13:22:42, 14 December 2024)
- ML20081B252 + (13:22:43, 14 December 2024)
- ML20081B253 + (13:22:43, 14 December 2024)
- ML20081B251 + (13:22:44, 14 December 2024)
- 05000254/LER-1983-037-03, /03L-0:on 830923,while Inerting Primary Containment,Containment Oxygen Not Reduced to Tech Spec Requirement.Caused by Sample Response Time & Probable Source of Air in-leakage Through Compressor + (13:22:45, 14 December 2024)
- 05000254/LER-1983-036-03, /03L-0:on 830920,discovered Ripped Ventilation & Fire Stop Boot.Caused by Extended Exposure of Boot to Heat & Normal Wear.Urethane Foam Matl Installed & Boot Replaced + (13:22:47, 14 December 2024)
- ML20081B247 + (13:22:49, 14 December 2024)
- ML20081B244 + (13:22:51, 14 December 2024)
- ML20081B240 + (13:22:52, 14 December 2024)
- ML20081B237 + (13:22:53, 14 December 2024)
- ML20081B232 + (13:22:56, 14 December 2024)
- 05000373/LER-1995-006-01, :on 950210,recirculation Flow Units Rod Block Function Was Inoperable Due to Procedure to Test Flow Unit Inadequate.Procedure Revised + (13:22:58, 14 December 2024)
- ML20081B225 + (13:22:59, 14 December 2024)
- 05000275/LER-1983-019-03, Welding Performed on Additive Tank W/O First Draining Tank of Sodium Hydroxide Solution.Caused by Lack of Communication to Field.No Evidence of Cracks or Corrosion Observed + (13:23:01, 14 December 2024)
- ML20081B218 + (13:23:02, 14 December 2024)
- ML20081B217 + (13:23:02, 14 December 2024)
- ML20081B216 + (13:23:03, 14 December 2024)
- ML20081B214 + (13:23:04, 14 December 2024)