c'-

, Entergy Operations, Inc.

River Bend Station 5485 U.S Highway 61 4 == ENTERGY'  ; 4 S e. u zo775 1 Tel 504 336 6226 Fax 504 635 5068 James J. Fisicaro Director

!" Nuclear Safety May 12,1995 U.S. Nuclear Regulatory Commission Attn: Document Control Desk M/S PI-37 Washington, DC 20555

Subject:

River Bend Station - Unit 1 Docket No. 50-458 l Monthly Operating Report File No.: G9.5, G4.25 RBG-41500 RBF1-95-0120 Gentlemen:

In accordance with River Bend Station (RBS) Technical Specification 6.9.1.6, enclosed is the April,1995 Monthly Operating Report for RBS - Unit 1.

Sincerely, RMM/kym enclosure 2CG012 l

' , v, 9505220146 9!50430 I .'

PDR ADDCK 05000458 R PDR

  • z.

April 1995 Monthly Operating Report

- May 12,1995 RBG-41500 RBF1-95-0120 Page 2 of 2 4

cc: U. S. Nuclear Regulatory Commission

! Region IV 611 Ryan Plaza Drive, Suite 400

, Arlington, TX 76011 s

i- NRC Senior Resident Inspector 4

P.O. Box 1051 St. Francisville, LA 70775

INPO Records Center 1100 Circle 75 Parkway Atlanta, GA 30339 Chester R. Oberg PUCT 7800 Shoal Creek Blvd., Suite 400N Austin, TX 78757 Dottle Shennan American Nuclear Insurers 29 South Main Street West Hartford, CN 06107 Cajun Electric Power Co-op, Inc.

9 l

1 DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO. R-95-04 DATE May 11.1995 COMPLETED BY T. J. Bolke TITLE Engineer III TELEPHONE 504-346-8651 ext. 2940 MONTil April,1995 .

DAY AVERAGE DAILY DAY AVERAGE DAILY i POWER LEVEL POWER LEVEL (MWe-Net) (MWe-Net)

1. 940.I 17. 928.3
2. 938.8 18. 926.5
3. 936.7 19. 925.0
4. 933.6 20. 923.0
5. 934.3 21. 927.8
6. 934.5 22. 925.6
7. 932.8 23, 931.4
8. 679.6 24. 937.7
9. 857.I 25, 937.1
10. 929.3 26. 907.9
11. 932.7 27. 847'.2
12. 937.0 28. 932.0
13. 936.7 29. 930.5
14. 936.7 30. 929.0
15. 933.6 31. N/A
16. 930.7

I l

DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO. R-95-04 DATE May 11.1995 COMPLETED BY T. .I. Bolke TITLE Engineer Ill TELEPIIONE 504-346-8651 ext. 2940 PAGE 1 OF 2 OPEPATING STATUS

1. REPORTING PERIOD: APRIL.1995 GROSS IIOURS IN REPORTING PERIOD: 719
2. CURRENTLY AUTilORIZED POWER LEVEL (Mwt): 2894 MAX. DEPEND CAPACITY (MWe-Net): 9J36 .

DESIGN ELECTRICAL RATING (MWe-Net): 3 9_3[6

3. POWER LEVEL TO WIIICil RESTRICTED (IF ANY)(MWe-Net): N/A
4. REASONS FOR RESTRICTION (IF ANY): N/A Tills YR TO CUMU-MONTII DATE LATIVE l
5. NUMBER OF llOURS REACTOR WAS CRITICAL 719.0 2879.0 59375.2
6. REACTOR RESERVE SIIUTDOWN IIOURS 0 0 0
7. IlOURS GENERATOR ON LINE 719.0 2879.0 56318.1 i
8. UNIT RESERVE SIIUTDOWN llOURS 0 0 0
9. GROSS TilERMAL ENERGY GENERATED (MWil) 2.050.928 8.283.464 151.356.477
10. GROSS ELECTRICAL ENERGY GENERATED (MWil) 704.407 2.856.231 51.238.286
11. NET ELECTRICAL ENERGY GENERATED (MWil) 659.852 2.680.035 47.955.767  ;

I

n '.

DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO. R-95-04 DATE May 11.1995 COMPLETED BY T. J. Bolke -

TITLE Engineer III TELEPIIONE 504-346-8651 ext. 2940 PAGE 2 OF 2 OPERATING STATUS ,

Tills YR TO CUMU-MONTil DATE LATIVE

12. REACTOR SERVICE FACTOR 100.0 100.0 71.8 13 REACTOR AVAILABILITY FACTOR 100.0 100.0 71,8
14. UNIT SERVICE FACTOR 100.0 100.0 69.5
15. UNIT AVAILABILITY FACTOR 100.0 100.0 69.6
16. UNIT CAPACITY FACTOR (USING MDC) 98.1 99.5 64.5
17. UNIT CAPACITY FACTOR (USING DESIGN MWe) 98.1 99.5 64.5  !

1

18. UNIT FORCED OUTAGE RATE 0.0 0.0 13.5
19. SIIUTDOWNS SCIIEDULED OVER NEXT SIX MONTilS (TYPE, DATE, AND DURATION OF EACII):

NO SIIUTDOWNS SCIIEDULED OVER NEXT SIX MONTIIS

20. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):

N/A 1

~.

UNIT SHUTDOWNS AND POWER REDUCTIONS - -

TIhE TIAE START RECOVER OF FROM DURATION TYPE REASON AETHOD CORRECTIVE ACTION /

NO. DATE OCCURRENCE OCCURRENCE (HOURS) NOTE (1) NOTE (2) NOTE (3) COMhENTS 95-01 950408 0009 950409 28.6 S B 1 POWER REDUCED TO PERFORM 0442 CON'IROL ROD, MSIV, CIV, AND COIiTROL VALVE TESTING

SUMMARY

NOTE (1) TYPE OF OCCURRENCE: EN'IT.R CODE DOCKET NO. 50/458 F: FORCED RIVER BEND STATION UNIT I S: SCIEDULED NOTE (2) REASON FOR OCCURRENCE: ENTER CODE REPORT NO. R-95-04 A: EQUIPhENT FAILURE (EXPLAIN IN CORRECTIVE ACTIONS /COMhENTS)

B: MAINTENANCE OR TEST REPORTMONTH April.1995 C: REFUEL'NG D: REGULATORY RESTRICTION E: OPERATOR TRAINING AND LICENSE EXAMINATION DATE May 10.1995 F: ADMINISTRATIVE G: OPERATIONAL ERROR (EXPLAIN IN CORRECTIVE ACTIONS /COMhENTS) T. J. Bolke H: OTTER (EXPLAIN IN CORRECTIVE ACTIONS /COMAENTS) COMPLETED BY NOTE (3) METHOD OF SHUTTING DOWN REACTOR OR REDUCING POWER- ENTER ONE

1. MANUAL
2. MANUAL SCRAM Engineer III
3. AUTOMATIC SCRAM TITLE
4. OTHER (EXPLAIN IN CORRECTIVE ACTION /COMhENTS)

TELEPHONE: 504-346-8651 ext. 2940

._