RBG-42478, Monthly Operating Rept for Jan 1996 for RBS

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Jan 1996 for RBS
ML20100G442
Person / Time
Site: River Bend Entergy icon.png
Issue date: 01/31/1996
From: Bolke T, James Fisicaro
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
RBF1-96-0054, RBF1-96-54, RBG-42478, NUDOCS 9602230184
Download: ML20100G442 (7)


Text

    • Entirgy Operati:ns, Inc.

River Bend Staton m 5485 U.S. Highway 61 t Francis le, LA 70775 Tel 504 336 6225 Fax 504 635 5068 James J. Fisicaro ar safety February 15,1996 U. S. Nuclear Regulatory Commission Document Control Desk Mail Stop PI-37 Washington, DC 20555

Subject:

River Bend Station - Unit 1 Docket No. 50-458 Monthly Operating Report File No. G9.5, G4.25

, RBG-42478 RBF1-96-0054 Gentlemen:

In accordance with River Bend Station (RBS) Technical Specification 5.6.4, enclosed is the January,1996, Monthly Operating Report for RBS.

Sincerely, tmh JJF/RMM/kym enclosure 230070 2230184 960131 ,

R ADOCK 05000458 PDR Ill/

... . . _ . . . . . ~ . . _ - .

- j l

Monthly Operating Report Febniary 15,1996 RBG-42478 RBF1-96-0054 Page 2 of 2 cc: U. S. Nuclear Regulatory Commission j Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011

NRC Senior Resident Inspector P.O. Box 1051 St. Francisville, LA 70775 INPO Records Center 700 Galleria Parkway Atlanta, GA 30339-3064-Chester R. Oberg PUCT 7800 Shoal Creek Blvd., Suite 400N -

Austin, TX 78757 Dottie Shennan American Nuclear Insurers 29 South Main Street West Hartford, CN 06107 Cajun Electric Power Co-op, Inc.

l l

i l

1 1

DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO. R-96-01 DATE February 13.1996 COMPLETED BY T. J. Bolke TITLE Engineer III TELEPHONE 504-346-8651 ext. 2940 MONTil January 1996 DAY AVERAGE DAILY DAY AVERAGE DAILY POWER LEVEL POWER LEVEL (MWe-Net) (MWe-Net)

1. 774.3 17. 0.0
2. 598.8 18. 0.0
3. 502.2 19. 0.0
4. 367.8 20. 0.0
5. 0.0 21. 0.0
6. 0.0 22. 0.0
7. 0.0 23. 0.0
8. 0.0 24. 0.0
9. 0.0 25. 0.0 10, 0.0 26. 0.0 ,

i 1. 0.0 27. 0.0 1

12. 0.0 28. 0.0
13. 0.0 29. 0.0
14. 0.0 30. 0.0
15. 0.0 31. 0.0
16. 0.0

DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO. R-96-01 DATE February 13,1996 COMPLETED BY T. J. Bolke TITLE Engineer III TELEPHONE 504-346-8651 ext. 2940 l PAGE 1 OF 2 OPERATING STATUS

1. REPORTING PERIOD: January.1996 GROSS HOURS IN REPORTING PERIOD: 744
2. CURRENTLY AUTHORIZED POWER LEVEL (Mwt): 2894 MAX. DEPEND CAPACITY (MWe-Net): 936 DESIGN ELECTRICAL RATING (MWe-Net): 93
3. POWER LEVEL TO WHICH RESTRICTED (IF ANY)(MWe-Net): N/A  !
4. REASONS FOR RESTRICTION (IF ANY): N/A THIS YR TO CUMU- '

MONTH DATE LATIVE

5. NUMBER OF HOURS REACTOR WAS CRITICAL 90.3 90.3 65310.9
6. REACTOR RESERVE SHUTDOWN HOURS 0 0 0
7. IIOURS GENERATOR ON LINE 90.3 90.3 62233.6
8. UNIT RESERVE SHUTDOWN HOURS 0 0 0
9. GROSS THERMAL ENERGY GENERATED (MWH) 171.494 171.494 167.887.435
10. GROSS ELECTRICAL ENERGY GENERATED (MWH) 58.551 58.551 56.912.321
11. NET ELECTRICAL ENERGY GENERATED (MWH) 53.831 53.831 53.260.670 1

l 1

l

4 -

DOCKET NO. 50/458 RIVER BEND STATION UNIT 1 REPORT NO. R-96-01 DATE February 13.1996

, COMPLETED BY T. J. Bolke TITLE Engineer III TELEPliONE 504-346-8651 ext. 2940 PAGE 2 OF 2 OPERATING STATilS THIS YR TO CUMU- l l MONTH DATE LATIVE

12. REACTOR SERVICE FACTOR 12.1 12.1 73.2 4

13 REACTOR AVAILABILITY FACTOR 12.1 12.1 73.2

.i

14. UNIT SERVICE FACTOR 12.1 12.1 71.1 i
15. UNIT AVAILABILITY FACTOR 12.1 12.1 71.1 l
16. UNIT CAPACITY FACTOR (USING MDC) 7.7 7.7 66.2
17. UNIT CAPACITY FACTOR (USING DESIGN MWe) 7.7 7.7 66.2
18. UNIT FORCED OUTAGE RATE 0.0 0.0 12.4
19. SilUTDOWNS SCIIEDULED OVER NEXT SIX MONT11S (TYPE, DATE, AND DURATION OF EACII):

None i

20. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):

l N/A i

l s

It

. . -_ .. = .

UNIT SIIUTDOWNS AND POWER REDUCTIONS -

TlhE TlhE START RECOVER OF FROM DURATION TYPE REASON METHOD CORRECTIVE ACTION /

NO. DATE OCCURRENCE OCCURRENCE (HOURS) NOTE (1) NOTE (2) NOTE (3) COMhENTS 1/4/96 1817 S C 2 While reducing power for refueling outage operators manually scrammed the reactor due to high tiubine vibration. Entered scheduled refueling

SUMMARY

No SRV challenges occurred this month. Refer to following page for SRV Maintenance.

NOTE (1) TYPE OF OCCURRENCE: ENTER CODE DOCKET NO. 50/458 F: FORCED RIVER BEND STATION UNIT I S: SCHEDULED NOTE (2) REASON FOR OCCURRENCE: ENTER CODE REPORT NO. R-96-01 A: EQUIPhENT FAILURE (EXPLAIN IN CORRECTIVE ACTIONS / COMMENTS)

B: MAINTENANCE OR TEST REPORT MONTH January 19%

C: REFUELING D: REGULATORY RESTRICTION E: OPERATOR TRAINING AND LICENSE EXAMINATION DATE Febmary 13.1996 F: ADMINISTRATIVE G: OPERATIONAL ERROR (EXPLAIN IN CORRECTIVE ACTIONS /COMAENTS) T. J. Bolke H: OTIER (EXPLAIN IN CORRECTIVE ACTIONS / COMMENTS) COMPLETED NOTE (3) METHOD OF SHUTTING DOWN REACTOR OR REDUCING POWER- ENTER ONE

. IIIGNATURE

1. MANUAL
2. MANUAL SCRAM Engineer III
3. AUTOMATIC SCRAM TITLE
4. OTHER(EXPLAIN IN CORRECTIVE ACTION /COMhENTS)

TELEPHONE: 504-346-865I ext. 2940

. ~,

SRV Maintenance During the month of January, 1996,16 Safety Relief Valves were removed from the Main Steam System and replaced. This was a normal, planned replacement evolution during Refueling Outage #6.

SRV'S REMOVED SRV'S INSTALLED N63800-00-035 1B21-RVF041C N63800-00-109 1B21-RVF041C N63800-00-043 IB21-RVF047C N63800-00-098 IB21 RVF047C N63800 00-037 1B21-RVF041F N63800-00-039 1B21-RVF041F N638004)D4)45 IB21 RVF047F N63800-00-095 IB21-RVF047F N638004)0 Il5 IB21-RVF051C N63800 00-120 IB21-RVF051C N63800-00-046 1B21-RVF05iB N638004)0-123 1B21 RVF051B N63800-00-041 IB21 RVF047A N638004)0-097 IB21 RVF047A N63800-00-042 IB21-RVF047B N63800-00-100 IB21 RVF047B N63800-00-118 1B21-RVF05IG N63800-00-121 1B21-RVF051G N63800-00 Il7 IB21-RVF051D N638004)0-047 IB21-RVF051D N63800-00-033 1B21-RVF041 A N63800-00-040 1B21-RVF041 A .

N638004)0-036 1B21-RVF041D N63800-00-106 iB21-RVF041D N63800-004)34 iB21-RVF041B N63800-00-107 1B21-RVF04iB N63800-00-038 IB21 RVF041G N63800 00-Ill IB21 RVF041G N638004)0-044 IB21-RVF047D N63800-00-081 IB21-RVF047D N63800-00-110 1B21-RVF04iL N63800-00-112 iB21-RVF041L 4

l