BWX Technologies, Inc.

February 19, 2021 21-012 A TIN: Document Control Desk Director, Office of Nuclear Material Safety & Safeguards U. S. Nuclear Regulatory Commission Washington, DC 20555-0001

Reference:

License No. SNM-42, Docket 70-27

Subject:

Semi-Annual-Effluent Monitoring Report

Dear Sir or Madam:

The Semi-Annual Effluent Report for the BWXT Nuclear Operations Group, Inc., Lynchburg (NOG-L) facility covering the second semi-annual effluent monitoring period for 2020 is enclosed. This report is being submitted in accordance wtth the requirements of 1 O CFR 70.59.

If you have questions or require additional infonnation, please contact Chris Terry, Manager of Licensing and Safety Analysis, at ctterry@bwxt.com or 434-522-5202.

Sincerely,

~/,~~

Manager, Environment, Safety, Health & Safeguards BWXT Nuclear Operations Group, Inc. - Lynchburg Enclosure cc:

NRC, Region II NRC, Resident Inspector BWXT Nuclear Operattons Group, Inc PO Box 785 Lynchburg, VA 24505 USA t + 1 434 522 !5000 www,bw,lj com People Strong INNDVATIDN DRIVEN >

BWXT Nuclear O~atlO/lS Group, Inc PO Box 785 Lynchburg, VA 24505 USA I + 1 434 522 6000 WWW bwxl com ENCLOSURE 7 pages People Strong INNOVATION DRIVEN>

I. GASEOUS EFFLUENTS (Continuously Sampled Stacks)

Reporting Period: 6/29/20 to 1/3/21 (Weeks Ending 6/28/20 to 1/3/21)

Stack: WASTE MGMT CENTER (# 39)

Average Flow Rate:

1.37 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCu'ml)

(µCi/ml)

(µCi/ml)

(µCi)

(=)

U-234 (S)

<l.0E-14

<1.0E-14

<l.0E-14 5.0E-03 2.7E--06 Stack: MFP LOAD (# 19)

Average Flow Rate:

1.20 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCu'ml)

(µCi/ml)

(µCi/ml)

(µCi)

(=)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 5.0E-03 2.7E-06 Stack: 2A STACK (# 23)

Average Flow Rate:

1.07 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCu'ml)

(µCi)

(mrem)

U-234 (S) l.0E-14 l.0E-14 2.0E-14 l.6E-01 8.7E-05 Stack: 2A PRODUCTION SUPPORT (# 44)

Average Flow Rate:

1.15 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(=)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 l.0E-02 5.4E-06 Stack: IA MAINTENANCE (# 43)

Average Flow Rate:

5.35 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCu'ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 2.0E-02 l.lE-05

I. GASEOUS EFFLUENTS (Continuously Sampled Stacks)

Reporting Period: 6/29/20 to 1/3/21 (Weeks Ending 6/28/20 to 1/3/21)

Stack: 3A PHARMACY (# 24)

Average Flow Rate:

1.28 cubic meters/second Quantity Off-Site Concentration ErrorEstunate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<1.0E-14

<l.0E-14 2.0E-02 l.lE-05 Stack: NMC STORAGE (# 42) or Bay 17 Average Flow Rate:

0.78 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 2.0E-02 9.6E-06 Stack: MET LAB (# 26)

Average Flow Rate:

4.80 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 2.7E-01 l.4E-04 Stack: U-MOL (# 45)

Average Flow Rate:

5.73 cubic meters/second Quantity Off-Site Concentrat:J.on Error Estimate MOC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 4.0E-02 l.9E-05

I. GASEOUS EFFLUENTS (Continuously Sampled Stacks)

Reporting Period: 6/29/20 to 1/3/21 (Weeks Ending 6/28/20 to 1/3/21)

Stack: RTRT (# 16)

Average Flow Rate:

6.33 cubic meters/second Quantity Off-Srte Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 4.2E-Ol 2.0E-04 Stack: SPF (# 11)

Average Flow Rate:

9.63 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µClim!)

(µCi)

(rnrem)

U-234 (S)

<l.0E-14 l.0E-14 l.0E-14 7.2E-0l 4.3E-04 Stack: 13A/14A/15A DRY (# 38)

Average Flow Rate:

15.20 cubic meters/second Quantity Off-Site Concentration Error Estimate MOC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrcm)

U-234 (S) l.0E-14 l.0E-14 2.0E-14 l.4E+o0 8.5E-04 Stack: CHEM LAB SCRUBBER (# 37)

Average Flow Rate:

11.39 cubic meters/second Quantity Off-Srte Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µClim!)

(µCi)

(mrem)

U-234 (S) l.0E-14

<l.0E-14 l.0E-14 l.8E+o0 l.IE-03 Stack: 14A MAINTENANCE (# 35)

Average Flow Rate:

3.12 cubic meters/second Quantity Off-Site Concentra11on Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µClim!)

(µCi)

(mrem)

U-234 (S)

<l.0E-14 l.0E-14 2.0E-14 l.9E-01 l.IE-04

I. GASEOUS EFFLUENTS (Continuously Sampled Stacks)

Reporting Period: 6/29/20 to 1/3/21 (Weeks Ending 6/28/20 to 1/3/21)

Stack: RECOVERY (# 15)

Average Flow Rate:

10.34 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (F) 6.00E-14 2.00E-14 7.00E-14 9.48E+o0 6.20E-05 Stack: LAUNDRY STACK (# 30)

Average Flow Rate:

2.83 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCJ/ml)

(µCi)

(mrem)

U-234 (S) 2.0E-14 1.0E-14 2.0E-14 l.lE+o0 7.0E-04 Stack: COMPACTOR (# 32)

Average Flow Rate:

1.67 cubic meters/second Quantity Off-Site Concentra1ion Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCJ/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 3.0E-02 l.9E-05 Stack: RETENTION TANKS (# 36)

Average Flow Rate:

0.45 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCJ/ml)

(µCi/ml)

(µCi/ml)

(µCi)

(mrem)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 l.0E-02 6.SE-06 Stack: WT SCRUBBER(# 31)

Average Flow Rate:

1.43 cubic meters/second Quantity Off-Site Concentration Error Estimate MDC Released Dose Radionuclide

(µCi/ml)

(µCi/ml)

(µCJ/ml)

(µC1)

(mrern)

U-234 (S) 2.S0E-13 2.00E-14 2.00E-14 5.95E+o0 3.?0E-03

I. GASEOUS EFFLUENTS (Continuously Sampled Stacks)

Reporting Period: 6/29/20 to 1/3/21 (Weeks Ending 6/28/20 to 1/3/21)

Stack: DECON (# 33)

Average Flow Rate:

1.94 cubic meters/second Concentration Error Estimate MDC Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

U-234 (S)

<l.0E-14

<l.0E-14

<l.0E-14 Stack: LTC 50 METER STACK Average Flow Rate:

16.34 cubic meters/second Concentration Error Estimate MDC Radionuclide

(µCi/ml)

(µCi/ml)

(µCi/ml)

Ni-63 (S) l.00E-14

<l.00E-14

<l.00E-14 H-3 (F) l.56E-11 l.00E-14 4.08E-13 Quantity Released

(µCi) 6.0E-02 Quantity Released

(µCi) 3.28E-01 3.86E+o3

  • Note: Ni-63 & H-3 activity is included m the Comply Calculated Dose of I.OOE-07 mRem Stack: LTC ACL STACK Average Flow Rate:

1.35 cubic meters/second Quantity Concentration Error Estimate MDC Released Radionuchde

(µCi/ml)

(µCi/ml)

(µCJ/ml)

(µCi)

Am-241 l.00E-14

<l.00E-14

<l.OOE-14 l.65E-01 Cm-244 3.03E-14 l.00E-14 l.00E-14 6.43E-01

  • Note: Am-24 I & Cm-244 actiVIty is mcluded in the Comply Calculated Dose of I. I 0E-03 mRem Stack: LTC RCL ST ACK 1.52 cubic meters/second Average Flow Rate:

Quantity Concentration ErrorEstimate MDC Released Pu-239

<l.00E-14

<l.00E-14

<l.00E-14 2.73E-03 Pu-240

<l.00E-14

<l.OOE-14

<l.00E-14 2.73E-03 Pu-238

<l.00E-14

<l.00E-14

<l.00E-14 l.09E-02 Am-241

<l.00E-14

<l.00E-14

<l.OOE-14 3.64E-02 Cm-244

<l.00E-14

<l.00E-14 l.OOE-14 l.08E-01 Co-60 2.34E-14 l.51E-13 2.0SE-13 5.58E-01 Fe-55 2.llE-14 l.20E-13 l.24E-13 5.04E-01 Ni-63 l.00E-14 6.82E-14 7.61E-14 2.09E-01

  • Note. All listed RCL Stack actiVIty is mcluded in the Comply Calculated Dose of2.90E-04 mRem Off-Site Dose (mrem) 3.8E-05 Off-Site Dose (mrem) 1.SE-07 Note*

Off-Site Dose (mrem) l.l0E-03 Note*

Off-Site Dose 2.90E-04 Note*

I. GASEOUS EFFLUENTS (Continuously Sampled Stacks)

Reporting Period: 6/29/20 to 1/3/21 (Weeks Ending 6/28/20 to 1/3/21)

NOTES:

(1)

The total exposure from all stacks is 8.9E-3 mrem. Doses were determined using the EPA COMPLY code. Actual stack and building heights were used. A distance from source to receptor of540 meters was used, with wind blowing towards the receptor at a speed of2 meters/sec, 25% of the time. Other default parameters such as temperature were used if prompted. Comply itself is conservative.

(2)

All alpha activity is conservatively reported as U-234 for the NOG-L Stacks as this is the predominant uranium nuclide and has the most conservative dose conversion factor of the various uranium isotopes. No nuclides other than Uranium were found in the NOG-L Stack Semi-Annual Composite Samples. For the LTC Stacks each nuclide above MDC is reported.

(3)

Beta/Gamma nuclides are not reported unless they exceed the respective MDC based on isotopic analysis.

(4)

Average concentrations, errors and MDCs are quoted as IE-14 µCi/ml for stacks when these values are between 5E-15 µCi/ml and IE-14

µCi/ml, and they are quoted as <IE-14 µCi/ml when the values are less than 5E-15 µCi/ml.

(5)

Activities are quoted as IE-02 µCi when these values are between 5E-03 µCi and IE-02 µCi, and they are quoted as <IE-02 µCi when the values are less than 5E-03 µCi. 5E-03 µCi is conservatively used to calculate the offsite dose when the activity is <IE-02 µCi.

(6)

The error estimate is the daily error at the 95% confidence interval propagated over the six month period.

(7)

Quantity released (µCi) is the sum of the activities calculated daily based on the calculated daily concentration for all concentrations> 0.

(8)

Twenty three (23) stacks were monitored during this monitoring period.

(9)

Average concentrations, errors and MDCs are quoted to one significant digit except for the Recovery, Waste Treatment, and three LTC stacks.

II.

LIQUID EFFLUENT A Reportmg Penod 07/01/20 to 12/31/20 B. Location of Sample: Collection Prior to Discharge into the James River.

C. Total L1qmd Flow:

3.54E+-08 liters D. Sample Collection:

Batch composite sampler.

Quantity Radionuclide Concentration Error Estimate MDC Released Total Dose U-234 U-235 U-236 U-238 NOTES:

(1)

(2)

(pCi/1)

(+/-pCi/1)

(pCi/1)

(µC1)

(mrem) 3.67E+0l 7.12E+-OO l.60E-01 12,986.60 1 19E-Ol 8.S0E-01 6.20E-01 l.60E-01 312.77 2.69E-03 2.S0E-01 3.60E-Ol l.OOE-01 99.51 8.64E-04 3.00E-01 3.60E-Ol l.OOE-01 106.93 8.S0E-04 Total l.23E-0l The total dose calculated for liquid release uses a dilution factor of 18:1.

Regulatory Guide 1.109 was used as guidance, with conservative assumptions to estimate the exposure.

The semi-annual concentration reported above is a volume-weighted average for the six months and may be less than the averaged MDC for the same period.

(3)

Isotopic analysis is perfo=ed on the monthly composite samples for the most commonly utilized beta/gamma nuclides such as Sr-90, Tc-99 and Cs-137.

The analysis of these nuclides typically indicates results less than minimum detectable concentration (MDC).

Only one nuclide with a concentration above the respective MDC was reported.