Foundation Investigation WPPSS Hanford 2 Nuclear Power Plant,Central Plant Facilities,Benton County,Washington
ML20210B314
Person / Time
Site: Columbia 
Issue date: 08/05/1971
From:
BURNS & ROE CO.
To:
Shared Package
ML19306D139 List:
References
NUDOCS 8702090129
Download: ML20210B314 (55)


Text

.

. i.

e.

g 4

6 WNP-2 in f

-Q i

APPENDIX 2.5E L /-.

FOUNDATION INVESTIGATION, WASHINGTON PUBLIC POWER SUPPLY, SYSTEM, HANFORD NO. 2 NUCLEAR PLANT, CENTRAL PLANT FACILITIES s

BENTON COUNTY, WASHINGTON, DATED MAY 28, 1971.

1 g.

0702090129 870115 PDR ADOCK 05000397 p

PDR

f C

FOUNDATION INVESTIGATION WASHINGTON PUBLIC POWER SUPPLY SYSTEM HANFORD NO. 2 NUCLEAR POWER PLANT CENTRAL PLANT FACILITIES BENTON COUNTY, WASHINGTON r

FOR BURNS and ROE, INC.

ENGINEERS AND CONSTRUCTORS i

1 MAY 28,1971

~ Revised as noted 8/5/71 SHANNON & WILSON, INC.

SOIL MECHANICS AND FOUNDATION ENGINEERS SEATTLE. WASHINGTON l

2.5E-i

s

SUMMARY

This report summarizes the results of a comprehensive foundation investigation at the site of the proposed Hanford No. 2 Nuclear Poser Plant near Richland, Washington.

In general, the rcccm=cndations and conclusions presented are based on detailed cngineering cvaluation of subsurface scils dcta chtnined frem eleven borings and two test pits accomplished during the field exploration phase of these studies.

It should be noted that this is not a cc=plete site evaluation in that certain aspects (i. e.,

geology, geophysical exploration, site seismicity evaluation, groundwater hydrology, etc.) are being accomplished and reported on by others.

The field explorations indicate that the Hanford No. 2 site is underlain by dense granular soils to at least a depth of 250 feet, 'which corresponds to the depth of the deepest boring.

The enti a cite is mantled with a 2 to 3-foot layer.of fine, eolian LAND.

This thin blanket is immediately underlain by about

(

a 100-foot thick deposit of fine to coarse SAND, which varies in consistency.from slightly gravelly to.,that of a sand and gravel mixture.

In th.e upper 40 feet, these sands increase in density with depth from medium dense to very dense.

Below a depth of about 40 feet, all soils were found to be very dense, as indicated by penetration test values which were with a single exception greater than 100 blows per foot.

Below an average depth of 107 feet'," the borings encountered the extremely dense Ringold con-l glomerates (sand-gravel mixtures), which are underlain at about 217 feet by the lower unit of the Ringold Formation consisting l

primarily of very dense or hard, interbedded sand, silt, clay and gravel.

The water table was measured to be at an average l

depth of 62 feet and the estimated top of basalt bedrock is l

approximately 420 feet below the ground surface as determined by geophysical methods.

i Based on our field inspection and evaluation of samples, on data from our laboratory test program and preliminary plant ii

Rcvised 8/5/71 1

i design information furnished by Burns and Roe, Inc., we have con-s ducted various engineering studies to determine foundation design criteria..From our studies, we conclude that for the dense eranular soils and the three buildines with mat foundation conficurations described herein, the ultimate soil bearinc capacity is in excess cf 50 tens per square foot.

Thus, the allcwable bearine pressure fcr these structures will be coverned bv the differential settle-ments that may be tolerated.

Based on the present design loads, the proposed depth of excavation, and averace clastic moduli (2) of 25,000 psi, 60,000 psi and 90,000 psi for the major soil ecnes, the maximum elastic settlement that will occur during construction is computed to be slightly more than 2 inches, while the maximum differential settlement should be in the order of 1 inch.

Maximum post-construction differential settlements should not exceed about 0.25 inch.

The strip footing foundations for the diesel cenerator building and the truck lock, and the spread footings for the service building will need to be designed for somewhat lower bearing pres-sures than the broader mat foundations.

Because of the dense nature of the ' foundation soils, there is no possibility for the occurrence of soil liquefaction beneath l

the major structures.

Due to the possibility of a future groundwater rise, the reactor building will require waterproofing to resist f

hydrostatic pressures or 'the use of a dewatering and drainage system.

No additional settlements are anticipated as a result of changes l

in groundwater level.

Criteria have been developed and presented regarding the l

l placement and compaction of structural fills as well as the lateral pressures such fills, backfills and adjacent foundations will exert on subsurface, exterior walls, In general, we recommend that these walls be designed for coefficients of earth pressure at rest which vary from K

= 0.5 to 0.8.

Where applicable, active and passive g

pressure coefficients may be used as given.

We have concluded that the soil conditions at the proposed.

I site are suitable for the design and construction of the central

[-

facilities presently planned.

However, it is recognized that

!s I

t I

iii l:

l c

I 9

additional explorations will be required for some of the major (such as cool- (_.

central plant structures, other major plant structures ing towers) and various minor structures associated with the plant.

In general, such explorations would be confirmatory in nature to verify that th'e anticipated conditions at other site locations are consistent with the conclusions reported herein.

s i

(

l l

l iv n n

m u

Raviced 8/5/71 TABLE OF CONTENTS 1

PAGE I.

INTRODUCTION 1

1.1 Purpose and Scope

1 1.2 Authorization 2

1.3 Limitations 3

1.4 Centributors 3

II.

GENERAL INFORMATION 4

2.1 Site and Regional Description 4

2.2 Geology 8

2.3 Description of Proposed Plant Structures 11 2.4 Field Exploration 14 2.5 Laboratory Testing 15 III.

SUBSURFACE CONDITIONS 16 3.1 Surface Sand 18 3.2 Sand and Gravel Deposits 18 3.3 Conglomerate Deposit 22 3.4 Average Soil Conditions 24 C.

3.5 Groundwater 29 IV.

FOUNDATION AND CONSTRUCTION CONSIDERATIONS 33 4.1 Foundation Types and Bearing Pressu es 33 4.2 Settlements 37 4.3 Positioning of Facilities 38' 4.4 Excavation 40 4.5 Drainage 40 4.6 Material Resources 41 4.7 Structural Fill and Compaction 42 4.8 Lateral Earth Pressures 43 4.9 Additional Explorations and Studies 45 I-k v

l

RGvi' cd 8/s/71 4

I 5

(

LIST OF TABLES Page Table No.

1 Average Soil Properties - Sand and 22 Gravel Deposits 2

Groundwater Observations 31 3

Summary of Building Loads and 34 Foundation Criteria 4

Summary of Elastic Moduli Values 37

~39 5

Summary of Building Settlements LIST OF FIGURES Page Pi'g. No.

5 1

Vicinity Map

(

6 2

P'lan of Proposed Nuclear Plant 12' 3-Preliminary Central Plant Layout 17 4

Subsurface Profiles 5

Penetration Resistance vs. Depth 20 (2-inch split-spoon sampler) 6 Penetration Resistance vs. Depth 21 (4.5-inch thick wall sampler) 25 7

Generalized Soil Profile 27 8

Summary of Elastic Modulus Data.

28 9

Summary of Shear Modulus Data 10 Summary of Damping Ratios for San'5h 30 44 11 Lateral Earth Pressures vi i

a e

i APPENDICES APPENDIX A DRILLING PROCEDURES AND SUBSURFACE INSTALLATIONS A-1 Drilling and Sampling A-2 Groundwater Observation and Installations A-3 Near-Surface Explorations A-4 Borings for Geophysical Explorations APPENDIX B EVALUATION OF PENETRATION TEST PEOCEDURES FOR DETERMINING PILATIVE DENSITY APPENDIX C LABORATORY TEST PROCEDUPIS AND PISULTS C-1 Classification Tests C-2 Compaction Tests C-3 Repeated Loading Triaxial Cor.pression T:sts C-4 Permeability Tests C-5 Resonant Column Tests APPENDIX D BIBLIOGRAPHY D-1 Geology and Soil Conditions D-2 Tectonics and Seismology D-3, Groundwater Conditions

(~_

D-4 Foundation Experience

\\.

D-5 Miscellaneous Reports APPENDIX E PRELIMINARY FOUNDATION INVESTIGATION - PUMP STATION E-1 Site Description E-2 Subsurface Explorations E-3 Subsurface Conditions E-4 Preliminary Conclusions O

4 9

vii c

i LIST OF TABLES IN APPENDICES Table No.

[

A-1 Drive Sample Criteria C-1 Visual Classification and Water Content of Samples C-2 Summary - Maximum and Minimum Density Determinations C-3 Summary - Permeability Measurements C-4 Summary of Damping Ratio Measurenents LIST OF FIGURES IN APPENDICES Fic. No.

A-1 Log of Boring B-1 A-2 Log of Borings B-2 and B-3 A-3 Log of Borings B-4 and B-5 A-4 Log of Borings B-6 and B-7

(

A-5 Log of Boring B-8 X-6 Log of Boreng B-9 A-7 Log of Boring B-10 A-8 Log of Test Pits B-1 Comparison of Penetration Methods C-1 Grain Size Classification, Surface Sand, Dep th O ' to 3' C-2 Grain Size Classification, Sand, Depth 3' to 20' C-3 Grain Size Classification, Sand, Dept 20' to 40' C-4 Grain Size Classification, Sand and Gravel, Dep th 4 0 ' to 100' C-5 Grain Size Classification, Sand and Gravel, Depth 100'

'C-6 Compaction Test viii

~-

5 a

LIST OF FIGURES IN APPENDICES (Continued)

Fig. No.

C-7

. Repeats 5 Loading Triaxial Tests, Dept 25' to 27' C-8 Repeated Loading Triaxial Tests, Depd140' to 42' C-9 Repeated Loading Triaxial Tests, Depth 55' to 55.5'

.C-10 Repeated Loading Triaxial Test, Hysterctic Damping C-ll Resonant Column Test, Depda20' to 22' C-12 Resonant Column Test, Dep th 64 ' to 65.5' C-13 Resonant Column Test, Depth 75' to 77' C-14 Resonant Column Test, Depth 108 ' to 108.6' C-15 Resonant Column Test, Depth 205' to 207' C-16 Resonant Column Test, Typical Amplitude-Decay Record E-1 Boring Location Plan k

.E-2 Log of Boring P-1 Pump Station m

l l

l S

I ix L

=. - -

e ~

I I

e FOUNDATION INVESTIGATION WASHINGTON PUBLIC POWER SUPPLY SYSTEM HANFORD NO. 2 NUCLEAR POWER PLANT CENTPAL PLANT FACILITIES BENTON COUNTY, WASHINGTON I.

INTRODUCTION 1.1 P'URPOSE AND SCOPE This report presents the results of our foundation investigation for the central plant facilities of the proposed Hanford No. 2 Nuclear Power Plant.

The purpose of this investi-gation was to determine the subsurface conditions at the proposed site and to make detailed recommendations for design and con-struction of the foundations for the major buildings within

~

this ar,ea.

Emphasis in this study was placed on establishing foundation requirements imposed by normal, static load' conditions f

as well as determining the static and dynamic, engineering soil l

properties.

It is our understanding that the seismic design l

criteria and response analyses will be evaluated by others.

I l

Included in the field explorations at the proposed central plant site were eleven subsurface borings and two test pits.

This report contains a description of the general site

~

.and proposed facilities, geologic setting, boring explorations, laboratory testing, interpretation of sub' surface conditions, and our detailed recommendations and conclusions.

The engineering studies and conclusions based on these data include recommend-

. ations for foundation types of the various buildings, bearing pressures, estimated settlements, together with recommended excavation slopes, waterproofing and drainage, backfill and compaction requirements, and earth pressures for design of perm-anent subsurface exterior v'lls.

In general, we have concluded that the proposed Hanford No. 2 site is suitable with respect to i

~

Rsvised 8/9/71 t

soil conditions for plant construction and operation.

To further supplement the main text of this report, a list of references and five appendices are included.

Appendix A presents a discussion of the various field exploration techniques used to obtain subsurface data during this investigation.

Because some aspect's of the penetration tests deviated slightly frem that designated as " standard", an evaluation of penetration test pre-cedures was prepared and is presented in Appendix 3 A detailed su==2ry of laboratory test methods and results is presented in Appendix C.

Appendix D is a bibliography of various reports, papers and books, which include information on the Hanford area with respect' to the following general subjects:

geology, seismo-logy, groundwater, foundation design and general informatien.

Appendix E presents preliminary data obtained from drilling one out of the three planned borings at the site of the proposed pump station along the Columbia River.

It is presently anticipated that the foundation studies for this structure will be accomplished once the river level recedes to a point where the other two boring loca-tions are ace,essible to tiuck-mounted drilling equipment.

(

Following completion of our report on May 28, 1971, sub-sequent changes in building grades and dimensions, pnd the general re-orientation and positioning of the various facilities, have re-quired that revisions be made in the engineering studies and con-i clusions contained in the original report.

These changes have been ' incorporated in the following pages of the original text.

Where revisions on a ' specific page were made, that page is appro-priately identified and dated in the top right hand corner as noted above.

1.2 AUTHORIZATION This investigation was authorized verbally on February 24, 1971, by Mr. A.

M. Capobianco, General Purchasing Agent for Burns and Roe, Inc._and subsequentl'y verified by Purchase Order No.

BR-2808-3 (also dated February 24, 1971).

The scope of work as originally detailed in our proposal of January 26, 1971, was revised to exclude both the administration of drilling subcontracts and e

u Raviced 8/5/71 the conduct of geophysical explorations.

Subcontracting of these latter two items was administered directly by Burns and Roe, Inc.

The investigation was subsequently expanded to include a preliminary study for the proposed pumping station to be located en the Columbia River, and the drilling of two extra borings at the plant site for in the geophysical explorations.

7.11 work in conjunction with use unis investigation was generally accceplished as described in Eurns and Roe Purchase Requisition No. 2 80 8-3 dated February 18, 1971.

The revised study contained herein was authorized ver-bally by Mr. Gus Satir of Burns and Roe, Inc. en July 21, 1971, and confirmed by change order dated July 26, 1971.

1.3 LIMITATIONS The analyses, conclusions and recommendations contained in this report are based on site conditions as they presently exist and further assume that the exploratory borings and test pits are representative of the subsurface conditions throughout the site, (s

the ' subsurface conditions everywhere are not significantly i.e.,

different from those disclosed by the investigation.

Though the foundation soil conditions underlying this site *are considered to be very good, certain additional explorations will be necessary at various facilities to confirm that the soil conditions at those i

locations are consistent with the conclusions contained herein.

1.4 CONTRIBUTORS j

For Shannon & Wilson, Inc., the field inspection of drill-ing was accomplished primarily by Mr. Rohn Abbott and Mr. Fred Nygren.

Mr. Fred Brown and Mr. E. D.

Schwantes jo'intly compiled the data, j

supervised laboratory testing, performed most of the engineering studies and largely prepared the main text and subsequent revisions of the report.

The overall project was under the direction of Dr.

R.

P. Miller, who supervised all phases of the project.

l

{

t 3_

R2visad'8/5/71 II.

GENERAL INFORMATION 2.1 SITE AND REGIONAL DESCRIPTION a.

Site Description The proposed Hanford No. 2 Nuclear Power Plant site is located in the 575 square mile U. S. Atomic' Energy Commissicn Han-ferd Reservation, in the south central part of Washington.

The main plant area lies in Section 5 (T 11 N, R 28 E), approximately 3-1/2 miles west of the Columbia River and 14 miles north of the city of Richland, Washington.

The Vicinity Map, Fig.

1, shows the location of both the proposed plant site and pump station.

Fig. 2 presents a more detailed site plan of the main plant, and also identifies the other major plant facilities and their tenta-tive positions.

The central plant location, approximately 400 feet by 400 feet in dimension, is situated near the middle of a relatively flat, esse.itially featureless plain extending in all directions for k-several miles..

Maximum relief across the central plant site, as shown in Fig.

2, is approximately 10 feet or less.

In general, the terrain s' lopes slightly to the northeast toward the. columbia River.

The aver ~ age ground surface elevation at the site is about 440 feet (MSL Datum).

Access to the plant area is presently provided by gravel l

~

and dirt roads which connect with a major four-lane roadway, which cuts 4 cross the Reservation in a NW-SE direction as shown in the Vicinity Map (Fig. 1).

The flat terrain is such that most vehicles can easily drive onto and around the site.

The only recognizable, nearby landmarks visible from the site are:

the AEC railroad trac,ks running in a NW and SE direction about 700 feet east of the j

site, the telephone lines running in the same general direction about 800 feet west of the site, and the WYE burial ground located approximately 1800 feet northwest of the site.

Vegetation over the plant area is minimal and consists j

of young plants found typically in arid regions.

Larger plants

(

such as sagebrush once covered this entire area; however, a i

_4 i

. -.......a

R2 vised 8/5/71 i

l I

s LEGEND HANFORD WORKS BOUNDARY-f."{

(

:::: RAILROAD PAVED ROAD EXISTlHG I

I FACILITIES 100 N' 100 9

C-CR 100 N d"

\\

I c3 f>-C k

lOL[

s

%s,,/N u<

'a p/

N, e

..i 200 200

{

EAST g

WEST HANFORD W U.S. ATOMIC ENERGY COMMISSION

\\*

2A0 RESERVATION

/

PROPOSED HAl' FORD No.

.[

HUCLEAR POWER PLANT rrir PRCPOSED y

1 ruur sTAtiow 1

EEN r ANK N DAW 300 AREA-g i

f,

['_

WASHINGTON g

s b

(

W.P.P.S.S.

HAWF0P.D KO. 2 KUCLEAR PLANT

(

0 s

1,0 VICINITY MAP C

A T s, E T-2 M SCALE IN WILES S H A N N O N f WI L.S O N soa L. ma t cn n e.e 6 6 r c. N A: sos E N G.*.t t si s l

l R

.g

Ma2.swd 8/5/n

~

a e

o

=

J 8

2 2

E e

FUTURE SttTCHING f-i

(.

STATION Hanford grid coordinate e

+

Y

~

u12.sco r,

u l2,1;;l r_--______,

7 : ring i,4 2

l l

I na u en

?

f'*,

Existing Wye l

B lG

[,9 9B3 Eurial Grcunds

,g,

%-)\\

l I

E-H s.gg? $gg.5&m h', g kh?/h

_________a

(

i C ENT R A L P L A N T <.c,Y,E -)@,,f E[3._

FA lLITIES/ {;.

(See fig. 2) k I

s,/,

I N11,5CO f

Nil.100 1

l l

/

(

f_

\\

COOLINGTOWER)) -

\\

no N_

ato wio.sco

,g M

Hio,5co

=

e2 E

l l

o 200 400 e00 80c loco

[)

l l

SCALE IN FEET COOLING TOWER t.P.P.S.S.

HANFORD NO. 2 NUCLEI.R PLANT u t.co NOTE PLAN OF THE PLANT LAYOUT WAS PROYl0E0 PROPOSED NUCLEAR PLANT BT EURNS 1. ROE, INC. THis Lif-OUT IS TENTATIVE AND SUBJECT AL' GUST 5,1971 T-2139-01 ssAssos a mos TO REYlSION.

.oic w ec~

.,ie s rev ~ o. vie ~ r,4 ci~ c i s l

q W

.- rit. Z a

6

(

1970 brush fire destroyed most of this growth.

Beneath the sparse vegetation, the ground surface is mantled with a light brown to tan, dry, fine, eolian sand.

These sands were transported and deposited over the site by strong winds which, during the field explorations, generally prevailed from a southwesterly or northwesterly direction.

Since the fire, the absence of vegetation has allowed the winds to reach, crode, and transport more retdily

'these unprotected deposits.

Severe dust or scnd ct'cres are not uncommon.

b.

Regional Description The regional topography is that of a broad, relatively flat basin (Pasco Basin) with the plant site being located in one of the lower areas.

The maximum variation in elevation within a 7-mile radius of the site is about 200 feet on the north, south and west sides (between elevations 400 and 600 feet).

However, 3-1/2 miles to the east of the site, steep, river-cut bluffs rise to form the east bank of the Columbia River.

Beyond the' river for at least 10 miles, the flat basin continues;'however, it is terraced and elevated approximately 300 to 500 feet above the

~

plant elevation.

On the west and southwest horizons, 8 to 10 miles away, the basin slopes upward forming the* edge of the Rattle-snake Hills.

The peaks of the Rattlesnake Hills rise a maximum of 3200 feet above the plant site.

To the north about 8 miles, Gable Mountain rises above the floor of the basin to an elevation l

.some 670 feet above the plant site.

The Columbia River has cut a channel through the center j

of the basin, about 3-1/2 miles east of the plant site.

The river in this vicinity is over a half mile wide, however, some of l

this width consists of small sand bar isiands.

Based on published literature, the average flow past this location is on the order of 120,000 cfs with a maximum and minimum range of about 695,000 and 40,000 cfs, respectively.

Most of this flow results from runoff of snow melt in areas far to the north, more than half coming from Canada.

q The precipitation in the Hanford area is very low,

l with a mean annual rainfall of approximately 7 inches.

The 4 -

e temperatures are moderate, with a mean of 54 degrees and an average

{"

range between 24 and 92 degrees F.

Low precipitation and moderate temperatures contribute to the semi-arid desert environment within the Reservation,. which allows only desert vegetation to survive.

In areas where vegetation is minimal, sand dunes develop and~ migrate locally with the prevailing winds.

South of the project site are the tri-cities of Ri ch l and, Pasco and Kennewick, which constitute the icjor center of population in the region.

These cities are mere er less dependent on the Hanford operation as their major incustry However, there is some farming and cattle rcising, especially on the cast side of the Columbia.

2.2 GEOLOGY The geology of the Hanford area is the subject of a detailed report for Douglas United Nuclear Inc. by Fred O. Jones and Robert J. Deacon, titled " Geology and Tectonic History of the Hanford Area", June 15, 1966.

The following are excerpts from that report.to provide the general geologic setting for the subsurface conditions existing at the plant site.

"The surficial geology of the Hanford area is probably better known than any other area of Washington.

R. E. Brown, Battelle Institute geologist,-has written extensively about the geology and hydrology of the basin.

Others who have written important papers include R.

C.

,Newcomb, U.S.G.S.,

Donald J. Brown, M. W. McConiga, and a host of other scientists who have been associated with research projects in the Hanford area.

The geology of the basin has been compiled using information from over 700 wells that total more than 150,000 feet of exploratory drilling.

The Pasco Basin is one of the principal physiographic and structural features of the Columbia Plateau in south central Washington.

The basin is a moderately deformed late Tertiary-carly Quaternary structural feature which is bounded on the north by Saddle Mountain Anticline, on the south by Rattlesnake Hills and Horse Heaven Hills Anticline, on the.

.{ **

west by east-plunging Yakima Ridge and Umtanum Ridge Anticlines, and on the east by Jackass Mountain Monocline.

The Hanford Reservation comprises the southwestern part of the Pasco Basin.

The basin is separated into the Wahluke Syncline, the Cold Creek Syncline, and the Pasco Syncline.

It reaches its deepest point 200 feet below sea level in the Wahluke Syncline.

The rocks consist of five major stratigraphic units.

In ascending order these are the Yakima Basalt Formation with interbeds of the Ellensburg Formation in its upper part, the Ringold Formation, Palouse Soil, and unconsolidated glacio-fluvial sards and gravels.

Touchet beds are a phase of the glacio-fluvial sediments.

A major unconformity is present between the Ringold and glacio-fluvial sediments.

a.

Yakima Basalt Formation Basaltic lavas of the Yakima Basalt Formation form the bedrock of the Pasco Basin and are. part of a regional l

sequence of the Columbia River Group of lavas which cover abo'ut 200,000 square miles in Washington, Oregon, and Idaho.

The basalts are exposed in the nearby anticlinal ridges on

.the flanks of the basin and in or>e antic 1'ine ridge, Gable But'te - Gable Mountain, near the center of the basin.

The basalt sequence consists of dense, relatively unweathered, conformably layered flows, with occasional interbeds of flow j

breccias, pyroclastics, and sedimentary rocks.

The lava

, sequence is believed to be in excess of 10,000 feet thick (Standard Oil Co., Rattlesnake Hills Oil and Gas Test, T.D.

10,655,).

b.

Rincold Formation Lacustrine and fluvial sediments of the Ringold Forma-tion conformably overlie the lava sequence in the basin and are exposed in the " White Bluffs" along the Columbia River near the eastern edge of the Reservation.

The Ringold Forma-tion consists of semi-consolidated and locally cemented sand, semi-coherent gravel or conglomerate with very stiff to hard I

(indurated) silt and clay. E m

m

The Ringold Formation locally contains fossilized bones of many types of vertebrate animals and is considered

(

to be early to middle Pleistocene in age.

The formation is highly variable both vertically and laterally but generally can be divided into three members described as follows:

Upper Member.

This member consists largely of light buf f to cream and tannish brown, sandy silt-and fine sand.

It is exposed in the bluf fs along the lef t bank of the Columbia River.

Middle Member.

This member consists of brc.-:n and gray,' locally consolidated to semi-consolidated silt, sand and gravel and is referred to as the "congicmerate"- zone.

Lower Member.

This member is characteristically a blue green, clayey silt and is known as the " blue clay" zone.

Locally, however, the zone is composed largely of sand and cobble gravel with subordinate amounts of silt beds.

The base of the formation has been moderately deformed f'

but the middle and upper portions are only'slightly deformed.

The upper surface of the formation beneath the Reservation has been deeply channeled.

The aggregate thickness of the Ringold Formation is approximately 1,200 feet, but because of erosion only a maximum of about 600 feet remain within the Pasco Basin.

c.

Glacio-Fluvial Sediments Coarse grained deposits that lie above a channeled surface of the Ringold Formation are referred to as Glacio-Fluvial Sediments.

Part of the sediments were deposited by the ancestral Columbia River and part by glacial melt water.

The glacio-fluvial deposits cover most of the surface of the Pasco Basin and consist of fine gravel, sand and pebble gravel, and cobble and boulder gravel with occa-sional interbeds of fine sand and silt.

The sediments locally contain highly erratic torrential cross-bedding, I

slump structures, and clastic dikes.

The glacio-fluvial -.

+

L

^

~

Rsvisid'~8/5/71 sequence is considered to be late Pleistocene to early Recent.

Radiocarbon dating of Touchet Beds (a fine grained phase) indicates that the sequence is about 13,000 years old.

  • d.

Palouse Soil Palouse soil locally overlies the Ringold Formation in the Pasco Basin and consists of fine sand and silt with a maximum thickness of about 60 feet.

The ur.it is believed to be of eolian origin and is locally called "Palouse Soil" because of its similarity to the Palouse soil of eastern Washington and western Idaho.

e.

Touchet Beds Touchet Beds are fine grained, lacustrine deposits i

i' I

laid down on the bottom of pro-glacial Lake Lewis.

They are equivalent to the upper portion of the glacio-fluvial sequence but are lake deposits rather than' fluvial deposits.

The Touchet Beds lie between altitudes of about 400 and 1,150 feet.

They are present at the lower altitudes in the southwest and northern part of the Pasc.o Basin."

The Touchet Beds apparently are not present at either the pla2'or pump station sites.

For more detailed information on the geology of the Hanford area, a bibliography of references pertinent to this sub-ject is contained in Appendix D-1, 2._3 DESCRIPTION OF PROPOSED PLANT STRUCTURES Within the central plant area, preliminary plans show six major structures:

reactor building, turbine generator build-ing, radwaste building, service building, diesel generator build-ing and truck lock.

The positioning of these central plant facili-ties, as furnished to us by Burns and Roe, Inc., is shown in Fig. 3.

It is our understanding that this layout is tentative and subject to revision, as more detailed design information is developed.

The following describes each structure based on presently avail-able information:

N1

~

=

TP-2

=

E B

=

(

B-1 B-2 B-3 A

.A b

d B-llg g gh g

B-4 g

B-5 B-6 B-10 N12,000 TURDINE GENERATOR BUILDlHG SERVICE B

B BUILDlHG L

h h

.B-7 B-8 B-9 REACTOR BUILDING

/

RADWASTE Dull. DING ETP-1 l

DIESEL GEN.

DUILDING l

0 IOD 200 TRUCK LOCK l

SCALE IN FEET LEGEND h

BORING LOCATION h

TEST PIT LOCATION B

W.P.P.S.S.

J SUBSURFACE PROFILE HANFORD HO. 2 HUCLEAR PLANT (See fig. 4)

NOTE PRELIMINARY CENTRAL PLANT LAYOUT I

EUILDING OUTLINES WERE PROYl0E0 BY AUGUST 5,1971 T-2139-01 BURNS & ROE, INC. THIS LAYOUT IS

,ggngog 3 w,tson TENTATIVE AND SUBJECT TO REYislCN.

.on. w reatu c. a reu~oanow raci~rcas

, FIG. 3

^

[

Rsviced 8/5/71

(

a.

Reactor Building The Reactor Building is to be 130 by 140 feet in plan and extend approximately 31 feet below present grade (approximate bearing elevation 409 feet).

The total weight of the structure including equipment (dead load plus live load), is roughly estimated to be 82,000 tons.

This load will produce a unit pressure at the fcundation level of approximately 9,000 pcundr per square foot (psf), over the projected plan area of this structure, b.

Turbine Generater Buildina This 304-foot by 184-foot building is the largest of the plant facilities in floor area.

The turbine, generator and sub-cidiary equipment along with the dead load of the struc.ture are expected to apply an average unit pressure of about 4,000' psf over the entire building area.

The foundation grade is presently de-signed to be about 7.5 feet below the ground surface (elevation 432.5 feet).

c.

Radwaste Building

(

This structure.is the second largest building in the central pla'nt complex, with rectangular plan dimensions of about 218 by 184 feet.

The total foundation load of this structure is expecte'd to be,about 110,000 tons.

This load wiIl produce an avarage unit pressure of 5,500 psf over the projected plan area of the build-ing.

The foundation grade is to be at elevation 429, which is about 11 feet below the existing ground surface.

d.

Service Building This structure is to be located in the eastern part of l

the central plant area.

As designed it will cover a floor area of 1

some 20,000 square feet, as shown in Fig. 3, and will be supported l

by isolated column footingsspaced approximately 20 foot on centers.

Unit pressures on these footings are estimated to be in the order of about 6,000 psf.

This building, as planned, will extend about 3.5 feet below the present ground surface to bear at elevation 436.5 l

feet.

l e.

Diesel Generator Building

(,

The Diesel Generator Building is one of the smaller of the major structures in the central plant area.

This building will !

I

.a m

.m -

(

be designed to transmit loads (dead and live) of about 5,000 pounds per lineal foot onto continuous wall footings running around the perimeter of the building.

The building itself is 60 by 124 feet in plan.

Since considerable excavation will be required for the adjacent Reactor Building, it is very likely that the Diesel Genera-tor Building vill be founded entirely in ecmpacted, structural back-fill af ter the subsurface work for the Reactor is compl'ete, f.

Truck Lock This facility will be located adjacent to the radwaste building on the south sid.

It will be some 32 by 166 feet in plan e

and will be founded very near the existing ground surface.

The foundation, as planned, will consist of a continuous wall' footing around the perimater that will impose an average unit pressure of 5,000 psf on the supporting soil.

The footings will be loaded about 3.5 feet below the ground surface at approximately elevation 436.5.

Other major plant structures (shown in Fig. 2) and a f

number of minor structures, presumably one or two story buildings

(

with relatively light loads, are also anticipated.

The actual location, size and description of these buildings, as well as roads, railroads, embankments or other structures within the over-all plant complex have only been tentatively established.

How-ever, the apparently uniform subsurface conditions in the general area should allow recommendations to,be formulated which could apply, to a majority of these structures with certain additional subsurface explorations necessary only to verify these conditions.

2.4 FIELD EXPLORATION For this foundation investigation, field explorations consisted of excavating two test pits and drilling eleven explora-tory borings within the general area of the central plant f acili-ties.

The two test pits (TP-1 and 2), were dug as a minimal effort at the plant site to compare with information obtained from the borings and from other nearby investigations.

The eleven borings,

( -

~

Revised 8/5/71

{'{

designated B-1 through B-11, were advanced to depths ranging be-tween 77 and 250 feet.

The location of the various borings and test pits are shown on.the Prelkninary Central Plant Layout (Fig. 3).

As noted in this plan, the first nine borings are laid out on a rectangular grid pattern covering an area of approximately 400 by 400 ' feet.'

These original nine borings were located in anticipa-tion that they would provide reasonable cc.vcrage of the entire central plant area since the exact location and orientation of individual buildings had not been determined at that time.

Bor-ings B-10 and B-ll were drilled at locations required for geophy-sical cross-hole measurements, as requested by Burns and Roe, Inc.

Because of its close proximity to B-5 and B-10, no sampling was accomplished in boring B-ll.

The individual logs of borings and test pits are presented in Appendix A.

Also presented in Appendix A is a detailed description of drilling and sampling procedures, and groundwater observation installations.

For the purpose of measuring the depth to groundwater, the 6-inch I.D.

steel drill casing was slotted at appropriate depths and left in place in three borings (B-3, 7 and 9) follow-ing drilling.

In boring B-1, a piezometer tip was installed near the bo.ttom of the boring and subsequently sealed into the middle unit of the Ringold Formation with a bentonite layer.

As installed, this piezometer should measure any excess hydrostatic pressures existing within that portion of the Ringold Formation.

Results of groundwater readings from the o,bservation wells and piezometer are summarized in Section 3.5.

Additional field explorations consisting of geologic reconnaissance and mapping', and geophysical surveys were conducted I

by others.

1 2.5 LABORATORY TESTING Laboratory tests were performed on representative samples recovered from the borings to determine the applicable physical and engineering properties.

These tests, in addition to a detailed visual classification of each sample, included:

water content I

determinations, grain size analyses, maximum and minimum density - -

Ravingd s75/WE

~

determinations, permeability tests, compaction tests, resonant column tests, and repetitive triaxial tests.

The grain size analyses were conducted primarily to verify visual c.lassifications conducted both in the field and laboratory.

Maximum and minimum density determinations were made such that remolded specimens for other tests could be prepared and tested in the laboratory at controlled relative densities.

Per-n.cabllity tests were used to evaluate potential drainage require-ments for deep foundations; while ccmpaction tests, together with gradation and moisture content tests were used to establish the suitability of site materials for fill, its placement, and com-paction requirements.

Resonant column tests and repetitiv.e triaxial tests were conducted to provide laboratory data to be used in con-junction with field data from the geophysical explorations, for establishing design modulus and damping values for static and dynamic response calculations.

The results of the laboratory test program are contained in Appendix C, together with brief descrip-tions of each laboratory test performed.

III.

SUBSURFACE CONDITIONS l

The s'ubsurface conditions encountered beneath the plant site to a maximum depth of 250 feet are depicted in the Subsurface Profiles, Fig. 4.

In general, three basic soil types were encoun-tered in the borings.

In descending order, these soils consist of:

}

1) fine surface SAND, 2) relatively clean, uncemented SAND and GRA-VEL, and 3) sandy and gravelly CONGLOMERATE with silty and clayey zones.

The following three sections (3.1, 3.2 and 3.3) discuss in 1

detail each of these basic soil types and their physical charac-teri,stics based on:

visual classification of the samples, field penetration tests, and laboratory tests.

The fourth section (3.4) is devoted to a discussion of the average soil conditions at the plant site and presents certain engineering properties for possible use in site response calculations.

Incidded in the final section (3.5) is an evaluation of the groundwater conditions.

I.

+

nuviseu ej af n T-G BUILDING SERYlCE BUILDlHG 0-6 I.

B-4 B-10 B-5 0FFSET 30'50.

Loose.l, fine SAND s-

- 44o

.r.

L_

--?-

2 e- -.

-7 44o 2

,.. ~, : ;

~

,..i.ne.to coarse.

,$ AND with, scattered gravel Medium to ve r y. d.ense, f

4ao,_

,_ 4 a g gy-7 w.

-?-

y g

L

=

L 2

z

!3E0 Very dense, fine to ccarse SAND and GRAVEL

- sto52 o

-2

-?

2 e

? ' _- -P '.,T ','. o,,- Rh j.,;

& y..1 e

.:_/.,

~.

32o Yery $se, s, lightly silty, sindy'.

giat elly CONCLCMET ATE s o

.o.

rio 2so PROFILE W-A Loose, fine SAND l

-0U RA0 WASTE BUILDING l

0~0 REACTORBUILDINGlhthG 0-9 l

3 440

..?

44o

.. ".. [ l,,

L4 s _ :,,;

,,,f ;,,,,, _ ;,

-Q..

todense,finetocoarse{'ND with scattered fine]trayel' Redjm

'- i._.,-;..*,;.';.

.., -,,o 4o0

?-

1._.

7-.

~

T--

1

_sz_

Very, dense, fine to ccarse SAND and GRAVEL 360 sso O

C.

'?. - ' o.' lc.. < :.?. c>- G :..r:..,,,.:.".~o

  • 9 '

g :, *... a....?

7 --

320

,... q _. y-

. c> ;.. O :

y go 320 5

~

Very dense, slightly silty, sandy, gravelly CONGLOMERATE *; -Q 5

9 O,- rea E E 2r.o

=

=

.o w

' g..

140 s<a PROFILE B-B Yery dense.

silty cleYey,d GRAVEL--

goo ano SAND an LEGEND

- iso iso,-

I-d BUILDING FOUNDATION O

to iBo 5Z-GROUNDWATER LEVEL SCALE lH FEET 80TT0ll 0F BORING i

NOTES 1.

THE PROFILES ARE. GENERALIZED

,pp33 FROW THE LtATERIALS ENCOUNTERED HANFORDNb*2NUCLEARPLANT IN THE BORINGS AND VARIATIONS i

'(

BETWEEN THE FROFILES AND ACTUAL SUBSURFACE PROFILES e

CONDITIONS NAY EIIST.

2.

DATUM:

U.S.G.S. EEAN SEA LEVEL.

AUGUST 5, 1971 1-2139-01 SH ANNON & WILSON

{

soit wtcw Ahics a r ouND ATeoN ENGINtras F!G. 4

3.1 SURFACE SAND Mantling the entire plant site is a relatively thin s

' layer of fine, slightly silty, eolian SAND (locally referred to as blow sand), which ranges from 1.5 to 3 feet in thickness.

Based on gradation curves of select samples, and visual classi-fication of all near-surface samples, these surface sands are clcscified as SP or SM according to the Unified Soil Classification system.

These sands are generally brown to light brown, or tan in color, and have a relative density varying from lcose to i.edium dense.

The measured water content of this material averages about 6 percent.

The laboratory permeability of the 'curf ace sands, recompacted in a loose to medium dense state was measured and

~4 computed to be 7.8 x 10 cm/sec.

Based on our experience with other nearby sites, we anticipate that. the average permeability of this material is slightly greater than this single laboratory c

test indicates.

3.2 SAND AND GRAVEL DEPOSITS Underl'ying the thin layer of surface sand is a

(

relatively thick deposit of uncemented granular soil, which extends to an average depth of about 107 feet below the ground surface.

These materials,' geologically, constitute portions of two for-mations, namely:

glacio-fluvial deposits, underlain by a sandy and gravelly unit of the Ringold Formation.

The distinction between the two formations is difficult to determine precisely at this site because the caliche and Palouse soils that mark the surface of the Ringold Formation throughout much of the Hanford area are missing.

However, based on the penetration resistance of these materiais, a comparison of average gradation curves (Appendix C), and local gradation changes noted in the boring logs, the interface between these two zones is estimated to be an average of 40 feet below the ground surface (approximately elevation 398+).

In the upper 40 feet of this deposit, the soils con-sist predominantly of SAND which is light brown to dark gray in

! t s-

Ravised 8/5/71 color.

This sand varies locally in gradation from fine to coarse, is relatively clean to slightly silty, and generally contains con-siderable fine gravel throughout.

Based on gradation tests, sum-4 marized in Appendix C, these soils generally correspond to either an SM o~r SW classification, or a combination of the two symbols, according to the Unified Soil Classification system.

Below 40 feet, the soils consist of a complex inter-bedded system of reasonably well graded sands and gravels.

Locally, as noted on the boring logs (Appendix A), either sandy GRAVEL :ones (GM-GW) or gravelly SAND zones (SM-SW) ray exist within any given depth interval.

Both the sands and gravels have particles which are generally rounded to subrounded.

Occasional ccbble =cnes are also present.

Although no boulders were encountered in the borings, they have been encountered in other borings, especially those drilled near the Columbia River.

Most of the existing major facilities on the Hanford Re-servation have' been founded within and supported by these sands and

(

gravels., Likewise, most of the proposed Han. ford No. 2 Plant struc-tures will be founded within the upper 40 feet of this deposit.

The relative density of the sand and _ gravel deposits, as indicated by the field penetration resistance tests summarized in Figs. 5 and 6, generally increases with depth from medium to dense or very dense in the upper 40 feet.

Below this depth, the penetration resistance indicates the presence of very dense soils in essentially all cases.

Exposure of similar materials on Gable

,Mountain, together with other geological considerations indicate that these sediments were once deposited to at least elevation 800 feet, which is about 360 feet above the-present ground surface at I

the Hanford No. 2 site.

Thus the soils beneath the plant site pro-

"bably have been preloaded by loads far in excess of those to be expected from the reactor and other buildings.

Other physica'l properties and permeability were deter-mined for selected ' specimens in the laboratory using standard test procedures.

The average properties from these tests are

(.

' i

... _. _. ~, _ _

llEASURED PENETRATION RESISTANCE, Nc Blows / foot (140 lb weight 30" drop) 0 20 40 60 80 100

> 100 0

... \\. '.

\\

3.\\

  • s..s..

,0

\\

\\

g.

j.

N

\\x.m 20 x \\.

a'dian N.

s o,

\\

+

\\

j,..

N4..

30 s

o 4

K g

o Mentite Line s

40 l

l 3a

^^^ ^^"""

60 NOTES 1.

Penetration Resistances obtained f rom Borings B-1 through B-10.

i l

2.

lielative density, Or, based on Gibbs and Holtz criteria.

3.

Mc values were obtained using cable f.P.P.S.S.

tcol drilling methods.

HAU ORD HO. 2 N AR N 4.

Penetration resistance, Nc, ras reduced 25: to obtain an ' equivalent' 2-lHCH SPLIT-SPOON SAMPLER Standard Penetration Resistance PENETRATION RESISTANCE VS DEPTH r

l (i.e. N = 0.75 Nc).

5.

Iet unit weight = 129 pcf.

MAY 28, IS71 T-2!39-01 SH ANNON er WILSON soit. M ECH ANICS & FOU N D ATION ENCfNCENS i

FIG.

5

~

MEASURED PENETRATION RESISTANCE, O

Blows / foot (1500 lb. weight,12" dicp)

)(

Blows / foot (1380 lb. weight,18" drop) 0 20 40 60 to 100

> 100 0

a i

X X

10

?

x 20

  1. 'dia 30 n

5b o

~

(

40 O

X so Per utite Lin y

X u

~

XO 50 l

60 XX i

NOTES r

1. Penetration Resistances obtained from Borings B-1 through 8-10,
2. All values measured using 4.5"

. 0.0.(3.5"I.0.) thick wall sampler,

f. P. P. S. S.

HANFORD NO. 2 NUOLEAR PLANT 4.5 - INCH THICK WALL SAMPLER PENETRATION RESISTANCE VS DEPTH u f 28, 1971 4-2135-01 SH ANNON & WILSON sonL ptcMa%4cm a F OU N O. TION EhGINttas

(

n EML k

cummarizrd in Tablo 1.

Aleo gpacializsd tests, consisting of resonant column and repeated loading triaxial tests, were per-formed to evaluate the moduli and damping factors.

The results from these tests are presented in Section 3.4. Laboratory test procedures and results are discussed and presented in Appendix C.

TABLE 1 AVERAGE SOIL PROPERTIES-SAND AND GRAVEL DEIOSITS I)

Approx. Average Water Content Above Water Table 61 Approx. Average Water Content Below Water Table 101 2)

Mean Grainsize Above 40' O.45 mm Mean Grainsize Below 40' l.90 mm Density Determinations

3) Maximum Dry Density Minimum Dry Density Depth Material 132.3 pcf 107.1 pcf 16 ft.

Sand 118.2 pcf 98.4 pcf 20 ft.

Sand 110.2 pcf 99.6 pcf 25 ft.

Sand 115.1 pcf 104.7 pcf 35 ft.

Sand 136.6 pcf 115.0 pcf 40 ft.

Gravelly Sand 4)

Perme ability Depth Material 1.1x10_jcm/sec 4.2x10_

10 ft.

Sand cm/sec 35 ft.

Sand 4

2.1x10 cm/sec 65 ft.

Sand & Gravel 3.3 CONGLOMERATE DEPOSIT Beneath the sand and gravel deposits at an average depth of 107 feet, the borings encountered the middle unit of the Ringold Formation.

This readily identifiable CONGLOMERATE, consisting of a multicolored gravel in a slightly clayey to silty l

sand matrix (GM or SM), was partially penetrated by nine of the borings, two of"which (B-1 and B-9 extended completely through this unit and into the lower unit of the Ringold.

The middle unit has an approximate thickness of 110 feet.

l Borings were extended in.to this formation primarily to verify its competency as well as to establish the general

(.

~,,

(-

materials for use in site response calculations.

The very high classification and pertinent engineering properties of these penetration resistance, with blow counts per foot far in excess of 100 in 79' tests, establishes its very dense consistency.

In general, this formation is relatively uniforn with depth, though occasional sandy or cobbly zones were' penetrated.

In three borings (B-1, B-2 and B-3) a relatively thin (4 to 9 foot)

' layer of hard, tan, fine sandy SILT was encountered directly overlying the-Ringold CONGLOMERATE.

These zones are noted in the Boring Logs (Appendix A).

Because of the very high density of this material, only minimal specialized testing was accomplished or considered necessary.

The results of these tests are summarized in Section 3.4 and described in more detail in Appendix C.

The lower unit of the Ringold, penetrated in borings B-1 and B-9 at an average depth of 217 feet, was likewise found to be very competent, so much so that identification samples were difficult to obtain since these material's were difficult to penetrate with conventional soil sampling devices.

The lower unit is classified much the same as the middle unit.

The predominant distinguishing features are its darker color and a

~

slightly greater percentage of fines.

The complete penetration of this layer and into underlying rock with borings was not accomplished nor considered necessary as the available information including the results of the present investigation, demonstrate j

that these deep materials are ver'y competent rock-like materials.

Consequently, we believe that the sampling and testing of soils and rock below a 250-foot depth is not required for the prediction of the behavior of a power p1' ant founded at the proposed location.

To obtain the general classification of.

materials below the plant site borings, reference should be made f

to the brief geology section of this report or directly to the I

logs of deep borings made at nearby sites.

These logs are re-ported in a nearby site investigation report (referenced in Appendix D-4).

I' 1

23-l

.,,,-,,,-,_-,..,,._,,_,,,__m_,.

_y

,~,_ -. _..

..~~._m._n,.__,_-.,-._

w._.

Directly underlying the Ringold Formation is basalt bed-rock of the Yakima Formation.

Based on a seismic refraction 4

survey recently completed at the site, the depth to rock at the plant is indicated to be about 420 feet.

3.4 AVERAGE SOIL CONDITIONS In the investigation and evaluation of pctential nuclccr mc;.: plant sites, it is necessary to predict the site recpense n.lur earthquake loading for structural design.

For plants fcundcd in soil, this requires the determination of the average subsurface conditions, including:

groundwater, soil classifi-catien, average stratification and lateral distributien of the scil materials and the pertinent engineering properties of cach layer.

Also the depth to bedrock or dense, rock-like soils

~

must be assessed within reasonable limits.

Based on the data obtained from our field and laboratory investigations, together with other available data, we have evaluated the soil conditions and properties and present part of this information as a function,of depth in' the Generalized Soil Profile in Fig. 7.

(

This profile can be considered as representative for all of the central plant' structures since the soils throughout, the site appear to be relatively uniform, with the interface elevation of successi re major layers generally not varying more than about 5 feet between borings.

Although the data shown in Fig. 7 have bee *. projected to extend to bedrock, the upper soil materials are s'ufficiently dense or rock-like that input seismic bedrock motions, in our opinion,may be placed at the top of the sand and gravel conglomerate (107 feet).

However, this decision is lef t to those performing the site seismicity evaluations.

In addition to the above subsurface conditions and parameters, the dynamic soil properties, including moduli and

]

damping factors also must be assesced as a function of depth.

j These dynamic properties are essentially strain dependent and therefore their magnitudes vary according to the time history of the shear stresses applied by the design earthquake at the (P !

e DEPTH (feet)

DESCRIPTION UNIT WElGHT RELATIVE AVERAGE (wet)

DENSITY MOISTURE CONTENT g

2 7 Fine SAND y = 115 pc1 Dr = SOS l

w=6i f

.C Fine to coarse SAND y = 129 pcf Dr = ES:cin.

  • =E5 with gravel 40 U 62 Silty SAND and GRAVEL.

7 = 145 pcf Dr= 55

E 107 l

SAND and GRAVEL y = 145 pcf Dr = 100 w = 125 CONGLOMERATE 217 Silty, sandy GRAVEL 7 = 145 pcf lir = 1005

= 135 U *S** $ *L 5' W

~~~

~

250

-~~

j l

I i

I 7 = 145 pef I

Dr = 1005 l

l Interbedded SAND. SILT, CLAY l

l and GRAVEL

  • I I

I i

I i

i I

l I

i i

si I

D YJ

/ I i

l

/

lA 420il ______

J pproximate top o bedrcck

_ _l_ _ _ j f

LEGEND NOTE W.P.P.S.S.

V Water level Average surface

(~

.7 Unit weight elevation 440' (E:L)

GENERAllZED SDIL PROFILE Eased en data f rcm nearby si te (S&W, Inc. files)

EAV 28. 1571

@-2139-01 Dr Relative density sH ANNON & WILSON l

  • ' ' " ' * " " " " * ' " " ^ " " ' ' ' ' " " "

Vcisture centent

, __. - 2 5 - __ _

FIG. 7

appropriate depth interval being considered.

Shear and. elastic moduli values were obtained in this investigation by resonant column tests and by others using geophysical techniques.

The results of the geophysical tests were provided to us by Burns and Roe, Inc.

Elastic moduli values were also obtained by repeated loading triaxial compression tests rMer both drained and undrained ccnditions.

The moduli deter-ned under undrained conditions were obtained for use in dynamic analyses, while those determined under drained conditicns cre obtained for use in evaluating settlement estimates under sec. tic loads.

Those moduli values (E and G) obtained from

'ie s e tests dre summarized as a function of depth in Figs. E and 9.

Since each test was performed at different strain levels, the magnitude of the modulus obtained will depend upon the test procedure used and its corresponding strain level.

In general, geophysical and resonant column tests are performed at strain levels smaller than would occur during strong motion earthquakes, while repeated loading triaxial tests are performed at higher strain leve's.

To obtais realistic moduli values which are

(

consistent with the strain levels of interest for earthquakes, adjustments of the test data are necessary. Since the resonant column test values were performed at reduced relative densities and on predominantly sandy samples (as discussed in Appendix C),

a somewhat lower modulus was anticipated and obtained than would be expected under actual field conditions.

The shaded areas in Figs. 8 and 9 represent what we believe to be realistic moduli values" for design use at the Hanford No. 2 site when considering strain levels corresponding to strong motion earthquakes.

Also for use in seismic analyses, the damping ratio was measured using resonant column tests and repeated loading triaxial compression tests.

Damping values of 1 to 2 percent I

were obtained from four resonant column tests, while higher values of 7.9 and 9.4 percent were obtained using the repeated loading triaxial test.

These data are superimposed at their

p A.

3 Elastic Modulus, E (X10 ) psi

~

10 0 150 200 250 300 110 0 1300 O

S.O i

i i te i

i 0

/l

  • N\\g Droined Tricalot fests (O)

O' 2...undroined Trioniot Tests' (+)

9 gn.We!GHig... s - ---- --- - - - -- - - - ---,

50-9.b!

{ f Geophysical Tests f rom Burns or:d Roo,Inc.

O t

t l

I\\

I :1.: *- '

7 t.------.------------.,

8 J....

ft,esonant Column Tests (9) h I

L{:.',

tsc0 -

l00 -

L-.

\\.

1

~

Modulus for dynamic onelyses l

a s.

M g

g... -

.c I

c 15 0 -

i l.

.~

~

~

ct I

~

o' as E

O

\\

w g

i I

4 9

M 7

,2 o

I

~

nm 1

x g

-~I E

200-1 E $ g :d to "

n 8

-I. Modulus used to'-

M 2

llh,!cornpute settlement $:

I>%

o Ek O6x?

..9(See. T.o. b.le. s. 4 8.. 5...).

1, o'

. ju*nder static loads l:

'9

%I*

o>

2P ON,,*

C -< E -

' :.):....

1 c$

c' n V 250 -

..i:isii r

'. F COG in m n

? us 400<'

.:g.:;;

o

=

y

,,, z ea de D C

I 7

m t(

p.

-1 I

x O

i Ya

//M/S Bosoft Dedrock of 420 f t. //M//

tn o

e Os i

em N'

us I

\\

l j *4 I

l L

O ll-e

(.

r--

l i

I O

t O-O p_...J t

I oa: 8 I

,':a 5l l

EI I

E I 51 8

'~

E :

r"

.?

l 8

O I

4

-oa 8

=

, OM 4,

ou O

o I N

w

,l Y

w e5 Nl 5

~

I t

E 4

O 2

O-g N

l w

W e

E o

O E

U l

e

.c b

M I

j I

u 3

0:-

stens ut abuoyo O-c---8 g

g

= = - - -

l 8

5

...I m

x I

1 8

8 i

O.

D I

I I.

[ i[

!!h!!

!!dji I!I!Ii%!h!!!b h =im m!E "

~

/.

lf-O O

O O

O O

O O

O o

O o

u.

a (sel yldeO l

i i

l l

W. P. P. S. S.

HANFORD NO. 2 HUCLEAR PLANT

SUMMARY

OF l

SHEAR MODULUS DATA nr 2e,1971 r-2tasti SH ANNON & WILSON SolL W E OM A NICF h FOU N D ATION FNGINrtes H-,

rib. r M

, l

' corresponding strain levels on a summary plot of other published

(

data for sands 1 in Fig. 10 From the data shown on this plot, it is evident that the damping ratio is strain dependent, increasing with higher levels of shear strain as suggested by the curves through the data points.

These data may be used to guide the selection of soil damping factors appropriate to the shear strains considered for design at the Hanford No.

2 site.

2.5 GROU::DWATER In order to obtain grouncwater informaticn, chservatica welic were installed in three of the four corner bori'ngs at the plant site.

At the northwest corner, a sealed pie:cneter was in-stalled to determine the hydrostatic pressure in the cong1cmerate zone of the Ringold Formation.

The method used to install the piezcmeter and observation wells is described in Appendix A-2.

During the drilling program, groundwater readings were cbserved in all of the bor'ings following their completion.

A summary of these data is contained in Tab 1'e 2.

The latest water level read-(

ings were taken on May 3 for temporary wells,

\\'

and May 17 for perma-nent wells.

These readings indicate that the grouhdwater at the plant site is an average of 62 feet below the ground surface

~

(ele-vation 378 feet).

This depth to water is consistent with other Published groundwater contour maps prepared from wells drilled throughout the Hanford area.

The piezometer also indicates a water level reasonably, close to this average depth.

Mr. Dave T111 son of Battelle Northwest, states that Well 17-5 located approximately 2 miles north of the site, in his cpinion, provides the best indication of the expected seasonal fluctuation in this area.

His records on this well show an cverage annual fluctuation of approximately 1/2 foot, being high in the summer and low in the winter.

1Seed, H.B.

and Idriss, I.M., " Soil Moduli and Damping Factors For Dynamic Response Analyses", Earthquake Engineering Research Center Report No. EERC 70-10, December 1970. 6

P8

~

g4 LEGEND a Weissman and Hari (1961) a e' a

e Hardin (1965) e 24 o Drnevich, Hall and Richort (1966)

,d s Matsushito, Kishido ond Kyo(1967) v,'

e Silver and Seed (1969)

/

Donovan (1969) e' 20 Y Hardin and Drnevich (1970)

~

,'o y

"v Kishido and Toliano(1970)

/

=>

l l

16 f-- v 7

'g NOTE.

/

}'

/

/

O' From Seed ond Idriss,1970

/

e f

A a,

0 b

'6.

g g

/*

Y

/

/ /

E e

4 o

5,h g 7

e 7

C Repeated Loading

'- ~

f Trionial Test

  • I en Z Resonont Colvenn Tests v

- -- f- ( [, d' 8

A Honford No 2 f$

k

/

,[Honford No. 2 9

t >W V

5 g Eg, Nucteor Plant noci or Pioni K_ y
z d2p 4

w o

-U a c.

o > ~,,

/

f$

-< E k" E

EB H

$sa!"

iLE 7.a:Es'fgi[~y-d "k3' E,-

O 2

6

!: O 2

to-4 10 -3 10-2 10-8 i

1

... =

r.

i

'I o Shear Strain-percent

~

o I

'N

.O

ex.1-m a.m s m m uano w Depth to Wct:r (fsct)

Boring No.

B-1 B-2 B-3 B-4 B-5 B-6 D-7 B-8 B-9 B-10 (Elevation)

(438.8)

(437.6)

(435.2)

(439.4)

(438.9)

(439.2)

(441.1)

(440.6)

(439.8)

(439.4)

Date 1971 3 /31 Bailed

  • 4/2 67 4/3 64 4/4 62 4/5 62 4/6 62 Balled
  • Bailed
  • Y 4/7 62 63.5 70 4 /12 Bailed
  • 62.5 64.5 69 4 /13 60 62.2 62.5 69 4 /14 60 Balled * -

62.2 62.5 69 4 /15 60 71 62.2 62.5 68.5 4 /17 60 58 62*

62.2 63 68.5 4 /18 60 59 62 62.2 63 68.5 69*

~

4 /19 60 57.5 61.7 62.2 63 68.0 61.5 4/20 59.5 58 60.8 61.9 62.8

.68 61.1 4 /21 59.5 57.5 60.8 61.9 62.8 68 61 4/22 59.5 57.5 61.0 61.9 62.8 67.5 61 4/23 59.5 57.5 61.0 61.9 62.8 67.5 61.0 4/26 59.3 57.5 61.0 61.6 62.8 67.7 61.2

  • Date boring completed

TABLE 2 cont.

GROUNDWATER OBSERVATIONS _

Depth to Water (fect)

Boring No.

B-1 '

B-2 B-3 B-4 B-5 B-6 B-7 B-8 B-9 B-10 (Elevation)

(438.8)

(437.6)

(435.2)

(439.4)

(438.9)

(439.2)

(4 41.1)

(440.6)

(439.8)

(439.4)

Date 1971 4/27 59.5 57.2 61.1 61.5 63.4 67.1 61.2 4/28 59.5 57.5 61.2 Bailed

  • 61.7 62.3 66.9 61.2 4/29 Pulled 57.2 61.1 63 2 61.5 63.8 66.6 61.0 4/30 57.0 60.9 62.3 61.3 62.3 66.7 61.0

~

3 5/1 57.1 61.0 62.2 61.4 62.2 66.7 61.5 Y

5/2 57.2 50.9 62.0 61.5 62.2 66.5 60.9 5/3 Bailed

  • 57.1 60.9 61.9 61.5 62.3 66.6 50.8 5/4 61.4 66.3 5/5 60.4' 57.2 66.3 5/6 60.4 56.9 66.5 5/7 59.9 57.2 66.5

~

5/8 60.2 57.2 Bailed

  • 66.3 65.2 65.9 I

5/10 60.1 57.1 5/11 60,1 57.0 62.5 65.9 5 /12 60.1 57.0 62.3 65.9 5 /13 60.0 57.2 6 2..'.

66.0 O

5 /14 60.0 s7 2 62.6 66.0 5 /17 60.1 57.1 62.5 65.8

  • Date bor uig completed c

Rsviecd 8/5/71 4%

t i

IV.

FOUNDATION AND CONSTRUCTION CONSIDERATIONS The foundation and construction considerations contained in this section are based on the data obtained during the boring program, on laboratory testing and on foundation experience from cthcr structures in the area.

This sectica discucses betr the general foundation types and earth preccurhc that will be recuired, and also those construction prchie.s relati /c to foundaticn and earthwork, diat should be considered in preparing the finci design.

In addition, certain soil properties for usc in the prediction of ground response under earthquake loading have been furnished, daough it is understood that these analytical studies will be accomplished by others.

The conclusions and recommendations contained herein are based on data from ten borings (B-1 through 10).

As shown in Fig. 3, not all of these borings fall within the present limits of the central plant facilities because the entire central complex ik has been relocated several hundred feet to the south since i

the completion of the boring program.

However, because of the near ide'al site conditions, enecuntered in tha. borings, we believe I

this investigation provides the informa$ ion necessary for final design of the structures discussed herein, recognizing that addi-tional borings will be necessary to verify the anticipated con-sistency of the subsurface materials at the final locations of the various plant st'ructures.

In general, we believe the depositional

. nature of these soils is such that the consistency in a lateral direction is not likely to change significantly from the results presented in this report.

4.1 FOUNDATION TYPES AND BEARING PRESSURES Based on the proposed design loads for the various struc-tures (as described in Part II and summarized in Table 3), the reactor, turbine generator and radwaste buildings should be founded on either large spread footings or mat type foundations.

Because I

of their narrow configuration and light loads, the diesel generator 6 -

4 TABLE 3 i

SUMMARY

OF BUILDING LOADS AND FOUNDATION CRITERIA Estimated

~

Bearing Area Load Assumed i

Length Width Elev.

DL +-LL Foundation Building (ft.)_

(ft.)

(MSL)

(tsf)

Type t

Reactor Building 140 130 409 4.5 Mat Turbine-Generator Bldg.

304 184 432.5 2.0 Mat t

l f

Radwaste Building 218 184 429 2.75 Mat I

W j

Service Building 280

.~. 8 0 436.5 3.0*

Spread Footing l

Diesel Generator Building 124 60 436.5 2.5*

Strip i

\\

Truck Lock 166 32 436.5 2.5*

Strip We j

5 Note Specific information on other structures was not 5

available prior to the submittal of this report.

o i

E Footing stress s

l t

l m

~

1

MuVisso 0/3/11 4

C building and truck lock are best suited for strip wall footings, while the larger service building can most efficiently utilize spread footings.

As presently designed, all buildings in the central plant area, except for the reactor building, will be founded '3.5 toll.6 feet below the present ground surf ace, and bear either partially in structural fill or in the medium to

- dense sands identified in the borings.

The rcactor. building will 20 feet deeper for a total depth to foundation grade extend about of 31 feet.

At this depth the sand deposit was determined to be dense to very dense.

As cummarized in Table 3, we believe the undisturbed soils are sufficiently compact to support the large footing or mat loads imposed by the reactor, turbine generator and radwaste buildings.

Based on the high relative density of the in situ granu-lar soils (Fig. 5) the depth to foundation grade, and the proposed use of mat foundations, it was calculated that for these three structures the allowable bearing pressure, with respect to a

(

possible bearing capacity f ailure, would exceed 50 tons per square foot.

Consequently, we would conclude that bearing capacity for such foundations will not be the controlling f actor in the founda-tion design,,but rather, the settlements which*the structures may undergo, as discu'ssed subsequently in Section 4.2.

The service building, because of its wide column spacing and relatively light loads, is best suited for support by spread footings placed within the undisturbed sands encountered at the l

p'roposed grade (Elev. 436.5 feet).

For the proposed 3.5-foot depth of burial, the allovable static design pressure (factor of safety =

3 against bearing capacity failure) should not exceed 3.5 tsf.

The minimum width for spread footings should be 2.5 feet.

If the depth i

of burial is increased to 5 feet, the allowable design pressure f

may be increased to 5 tsf for the same factor of safety.

Unless extensive shoring is used to support the reactor l

buildino excavation, it will be necessary to remove much of the l

natural around needed to support the diesel generator building Because of this, it f(

and portions of other surrounding buildings.

f is recommended that the soil beneath the diesel aenerator area be Weviccd 8/5/71 h

removed to about elevation 410 feet and then replaced by compacted structural fill, as described in Section 4.7, up to final orade.

Due largely to their shallow depth, and narrow width, the wall footings for this building and the truck lock must be designed for lower loads than permitted for the deeper and larger mat foundations.

The minimum width of these footings should not be lors than 2 feet.

For a 2-foot depth of burial, the allowable static design pressure (F.S. = 3 against becring ccpacity fcilure) should not exceed 3 :sf.

For a 5-foot depth of burial the allcwable design pressure may be increased to 5 tsf.

To provide safe, temporary slopes around the recctor building, a considerable amount of excavation and subseque.nt bach-filling will be required.

As a result, portions of the surrounding buildings will bear in. highly compacted structural fill.

Compac-tion requirements for such structural fill are described in Section 4.7.

The bearing capacity, in our opinion, will not be signi-ficantly reduced if at some future date the groundwater table should rise to within a few feet of the ground surf ace, due to the construction of Ben Franklin Dam, or some other cause.

Others have calculated that with a maximum reservoir pool l'evel of Elev.

400 feet, the groundwater level at the Hanford No. 2 site would rise to within 20 ' feet of the ground surface (Elevation 420 feet).

This situation should be considered in design as long as there is l

l a possibility of this occurrence within the 40-year design life of the Hanford No. 2 Plant.

One other critical factor regarding foundation support that must be considered in the design of nuclear power plants founded on granular soils, is liquefaction of the bearing soils.

Based on I

the existing site conditions (deep water table and dense, granular soils), in our opinion, there is no potential for liquefaction at the proposed Hanford Plant.

Since there is a possibility that the t

l water table could rise some 40 feet or more in the future, we have also considered this potential condition by evaluating the in situ I

relative densities of the soils underlying the plant.

The summary e

Ravised 8/5/71 plot of penetration test values and corresponding relative densi-ties using the modified Gibbs and Holtz correlation (Fig. 5) demon-strates that below a depth of 40 feet, relative densities approach-ing 100-percent are not unrealistic, while between 25 and 40 feet, minimum relative densities on the order of 85-percent are present.

1.bove 25 feet, the median relative densities excec6 90-percent.

Further discussion and evaluation of the penetraticn resirtance values used to obtain an " equivalent" Standard Penetration Eeris-tance and relative density correlations are presented in Appendix B.

Based on the high relative densities and assuming that the placement of structural fill is adequately controlled,.we believe there will be no problem of liquefaction at this site, even under the hypothetical high water case cited.

4.2 SETTLEMENTS Potential settlements have been computed for each of the major structures.

These settlements were determined using an elastic analysis where all of the structural loads (DL+LL) were considered to act at their respective foundation grades, as uniform area loads for mat and spread footing foundations, and as indivi-dual strip loads beneath wall footings.

These analyses were based on the estimated building loads as furnished by Burns and Roe, Inc.

and the following elastic moduli.

TABLE 4

SUMMARY

OF ELASTIC MODULI VALUES _

Depth Range

  • Avg. Modulus Soil Type 40' 25,000 psi Dense SAND 0

40' - 107' 60,000 psi V. Dense SAND & GRAVEL 107' - 217' 90,000 psi V. Dense Sand & Gravel CONGLOMERATE 217' - 420' 90,000 psi Interbedded SAND, SILT, CLAY & GRAVEL

  • Note:

See Fig. 7 for generalized soil profile IG -

Rsviesd 8/5/71 (v

These average values for the major soil zones were selected based on the general trend of modulus values obtained from drained triaxial tests as shown in Fig.

8.

These values represent at best a conser-vative evaluation of the moduli and, in fact, are probably on the low side since it is not possible to fully recreate the in situ density conditions using small scale laboratory test methods.

What is described herein (and summarized in Table 5) as settlement, for the most part will be elastic reccmpression of the soils below the bottom of the excavation.

Since the majority of the total and differential settlement is likely to occur elastically during construction (i.e. during the application of dead loads),

pcst-construction settlements represent only that percentage of the maximum total or differential settlements (Table 5, Columns 1 and 2) due largely to the application of live loads.

It is our understanding that for other nuclear power facilities, the live loads have generally averaged only 10 to 15-percent of the total load, with a maximum of 25-percent.

The post-construction settle-ments presente.d in Table 5 (Columns 3 and 4) are based on an assumed

(

25-percent live load and thus represent the maximum expected values.

Because of the dense nature of the foundation soils at the project site,. fluctuation of the water table, in our opinion, is'not likely to significantly affect the predicted settlements, although a rise in water table reduces the effective confining pressure of the soil and thus the effective modulus.

The magnitude of this change, in our opinion, is negligible when considering the high laleral stresses that must be present between the soil grains I

due to the previous preload of approximately 360 feet of soil, which once overlaid this site.

l l

4.3 POSITIONING OF FACILITIES Because the soils in the vicinity of this site were de-l posited and subsequently eroded under the same geological environ-ment,their density, texture and gradation as a function of depth l

are generally found to be remarkably similar with only minor local variations.

Because of the lateral uniformity of the supporting r -

7 p

-O-

. ~

TABLE 5

SUMMARY

OF BUILDING SETTLEMENTS SETTLEMENT.h, inches Area 2

Maximum Loading Maximum Maximum Max. Post Diff. Post Building (DL+LL tsf)

Total Differential Construction 3 Construction 3 Reactor Building 4.5 2.1 0.8 0.5

-0.2 Turbine Generator Bldg.

2.0 1.4 0.9 0.35 0.22 Radwaste Building 2.75 1.7 1.0 0.4 0.25 Service Building 3.0 1.8 1.1 0.45 0.28 (d

4 y

Diesel Generator Bldg, 2.5 0.8 0.7 0.2 0.17 Truck Lock 2.5 0.7 0.2 0.17 0.05

'Isettlements based on an elastic analysis using estimated foundation loads furnished by Burns and Roe, Inc. and the moduli values presented in Table 4.

2Maximum settlement from time of finished,cxcavation to completion and occupancy of completed s

structures.

2 3

Dased on 75% of settlement occurring during construction.

[a Footing stress.

E R

c

WGvic;d W/5/W1 soils, we believe there is little or no advantage in shifting or

[

repositioning any of the proposed structures on the site because of foundation considerations.

4.4 EXCAVATION Excavation for the reactor building will extend 31 feet bc i : ;. the present ground surface, while the other built.r gs will be fou.ded in the upper ll feet of soil.

All of these excavations will remain well above the water table, theref ore, dry conditions should prevail during construction.

Earthwork for all excavations should be poscible using conventional earth excavation equipment.

Even though the sands and gravels are very dense with depth, they are generally un-cemented, therefore, they should be relatively easy to excavate.

No ripping should be necessary.

Because of the dry climatic condi-tions and the relatively clean nature of the materials, construc-tion equipment should be able to work the year round without inter-

ruption, e.< cept for occasional, severe dust storms.

To improve working conditions during construction, it would be desirable to place excavated materials downwind of the construction site.

The safety of side s' lopes into the various excavations generally depends indirectly upon the density of the soils.

As a preliminary estimate, temporary slopes no steeper than 1.5 horizon-tal to 1 vertical (1.5:1) should remain stable during plant construc-tion, however, local ravelling resulting from vibration, drying and wind erosion should be anticipated.

Ravelling, if found to be excessive, can be controlled or prevented either by flattening the side slopes, occasionally wetting the slopes, or by spraying the slope with one of several commercially available chemicals which provide a thin protective film or crust over the surface.

4.5 DRAINAGE Because of the rather dry climatic conditions in the Hanford area, we do not anticipate any significant probleins in regard to drainage.

Also, since there is very little annual groundwater fluctuation, and because the deepest f acility is located some 30 feet above the water table, we expect that thejk -

~--

R:visad 8/5/71 e

o C.

will be no water problems.

the effect of a significant water tablOne possibil e, however, is vation of 420 feet) e rise (possibly to an ele-Under this condition, drainage or waterpdue to the am.

t;::en for the reactor building rcofing ncasures must be tially changing condition. level and therefore sh cbcVe this y th:2 poten-The waterproofing system for the reacte structure should be designed to resist a hyd r building sub-sure equal to 62.4 pounds per square foot forostatic uplif t pres-water level is expected to rise above the lowr each foot that the tional lateral earth pressures on ext est floor level.

Addi-by such conditions are described in Sectierior, subsurface walls caus available information, the reactor building should hBased on j on 4.8.

dead load per unit area to overcome buoy ave sufficient l

possible uplift pressure, ancy due to the maximum 1

j As an alternate to waterproofing, an exte f

system possibly could be designed and construct d nsive drainage maintain dry conditions around the react :

to permanently e

approach is less practical since drainage faciliti building.

However, this more suited to those cases where the quantity of es generally are enough to permit removal of water at a low seepage is small i

gravity flow.

expense, usually by (i.e., high water table, soils with highThe potential c 2 site high capacity pumping equipment to remove system and j

it from the plant area.

e water and discharge l

watering system, which may never be used, in ourThe ex waterproofing system much more practical opinion, makes a 4.6 MATERIAL RESOURCES The granular glacio-fluvial deposits of clean sand and gravel mixtures),

(consisting primarily site and in various borrow pits throughout the Rlocated beneath vide an abundant source of suitable fill materi l eservation, pro-a.

Based pn grain i

g i ^

R; viced 8/5/71 s

(

size curves, water content determinations and compaction tests (as summarized in Appendix C), most of the soils to be excavated during the initial stage of site grading and building construction should be, in our opinion, suitable for use as structural fill.

To use the excavated site materials, a minimal amount of screening or possibly washing may be required to remove large cobbles or exces-02ve amounts of fines.

As an alternate, more uniform deposits of sand and gravel probably exist in other nearby borrow pits.

The glacio-fluvial deposits found throughout the Hanford Reservation likewise should provide an abundant source of aggregate for concrete.

The fine surface sands, located in the upper 2 to 3 feet at the proposed site, are unsatisfactory for use in building struc -

tural fills or for backfill.

However, these sands are probably suitable for use in random fills, though exposed surfaces will be susceptible to wind erosion.

4.7 STRUCTURAL FILL AND COMPACTION To, ensure proper drainage and satisfactory compaction, f

structural fills should consist of well graded, inorganic, sand and gravel mixtures which are free of boulders and c,obbles over 3 inches in diameter and contain no more than 10-percent fine grained, non-plastic materials (passing a 200 mesh sieve).

As discussed in Section 4.6, most of the material to be excavated at the plant site satisfies this requirement.

In some cases, a slightly higher percentage of fines (more than 10-percent) may be tolera$le since those fines observed to be present in the samples from the various borings are essentially non-plastic.

Also, the on-site materials are, in most cases, dry of optimum such that they should be easily worked under the dry climatic conditions existing in this area.

Structural fill and/or backfill which will support build-i ing loads, should be placed in 6 to 8-inch lifts and systematically compacted using heavy vibratory rollers.

Each lift should be com-pacted to a minimum of 75-percent of its relative density and with an average relative density of no less than 85-percent.

To assure that proper field control of filling operations is maintained, a

~42-

, ~ -,.

-___-.,y.,., _ -._

.---,g

. ~ _

y

e

~ "-

~

MUVAUGQ 5/3//1 o

qualified inspector or soil engineer should be present on a full-time basis to check the quality of the fill and its density in a systematic manner.

.This should also include inspection of fill placement procedures to' assure that the structural fill is uniform i

throughout and contains no loose pockets or zones.

From two compaction tests (AASI!O T180-57) performed on

.pamples of on-site materials, we have determined the maximum dry censity.to be 125 and 128 pounds per cubic foot with an optimum water content of 8 and 10-percent respectively.

Since the on-site materials generally are dry of optimum by about 1 to 5-percent, the addition of water will be required to achieve r.aximum densities 4

during compaction.

4.8 LATERAL EARTH PRESSURES i

All exterior walls extending below the ground surface should be designed to resist lateral earth pressure.

The magnitude of this pressure for purposes of design is primarily dependent

,(

upon the conditions assumed (i.e., with the water table as presently exists or with the water table at some predicted level on the wall).

Earth prescures for these two conditions are summarized in Fig. 11.

Generally, flexible walls are designed for active earth pressures (K,), while rigid walls are designed for at-rest pressures (K ).

j For design of exterior, subsurface walls of the reactor building, high at-rest pressures (K, = 0.8) are considered necessary for those walls extending below elevation 432, since backfill in these areas mu'st be densely compacted to support high footing and mat loads of surrounding buildings.

Where walls,will not be subjected to adjacent footing or mat loads, a lower coefficient of earth pres-I i

j sure (K, = 0.5) may be used, as the degree of compaction need not f

be as high.

Also noted in Fig. 11 are criteria for determining earth pressures using a coefficient of passive earth pressure (K

= 8.5) p and a coefficient of active earth pressure (K, = 0.28).

These values were determined assuming the surrounding granular soils will have an internal friction angle (7) of 36 degrees, an angle of wall friction equal to 2/3 9 and a log spiral failure surface (in the case of passive pressure).

Jl It o

a li I\\

H

\\

0.3 c i

1.3 c 0

\\

.l i

H I

2 h

i

=

2 p

I i

y y

-K7H

=

.g y g,p A.

BASED ON EXISTING B.

BASED :

GRDUNDWATER CONDITIONS GROUNDWATER WHERE Ka Coef ficient of Lateral Earth Pressure Ke (et rest)

Kg (active)

Kr (paselve) 7 = 130 pcf (sels't unit selght) 73 = 68 pel,(buoyant) 7's $2.4 pcf H z Neight of sell er height ebeve er below the water table U _a ussimus unter level en sail h = Melght betecen base of sall and u;..,

any adjetent footing er set Il " Actuel contact stress of adjacent footing er set foundation.

2--

FOR DEstCN OF BASEMENT nALLS UNDER STATIC LOAD CONDITIONS

1. _

.._ _ 7 USE Ee= 0.8 below elevetten 432 l

Eez 0.5 above elevatten 432 2,m.._

l l

FOR DESIGN OF BASEMENT WALLS TO RESIST PASSlYE EARTH PRESSURE __ --

7-~

K, = B.5 f or all estis (Used f or computing the mesleum passive realstance of the soll)

.FOR DESIGN OF FLEXIBLE (YlELDING) WALLS USING ACTIVE EARTH PRET K = K.0.28 g

i W.P.P.S.:

[

HANFORD NO. 2 N" i

LATERAL EARTF j

mat 28,1971

(

SH ANNON &

e n -e

,e.

,,e S"

w o.

Rsvised 8/5/71

.?

~

4.9 ADDITIONAL EXPLORATIONS AND STUDIES Since the. original nine borings (B-1 through B-9) were laid out on a grid system prior to final building location, the borings do not coincide with the present layout of structures in the central plant area.

Though the so.11 conditionc underlying the plant site appear to be uniforn.;y very ccr : tat ac:ccc the cite and the presently available data cuf ficient f r finci design, additional explorations, in our opinion, are necessary pricr to the start of construction to verify the cercpetency of the subsur-face materials at certain locations within the ccntral plant area.

In addition, we believe the foundations for the other l

structures and appurtenant facilities such as:

cooling towers, office buildings, parking areas, roads, railroads, rail loading docks, transmission towers, switch yard, etic., at other locations around the site should also be investigated.

Many of these lighter weight structures, which presumably will be founded near the ground surface, probably can be adequately investigated with backhoe test

-(

pits and a few relatively shallow borings.

A minimal laboratory testing program also will be necessary to supplement the tests performed to date.

In addition to liquefaction, discussed in Section 4.1, there are a number of other natural phenomena which should be eval-uated during' final design but which were not included in the scope l

of this investigation.

In part, these would include such things as:

flooding 4possibly caused by the failure of an upstream dam),

volcanic activity or other geologic events (such as faulting).

We understand that these evaluations are being accomplished by others.

SHANNON & WILSON, INC.

$D P he m, M GA,ft AAeo p.8

\\

1 by may

(+c cf

' aymona r. nizier, r.E.