ML20151W355

From kanterella
Jump to navigation Jump to search
Suppl 2 to Rev 2 to UT-AUSTENITIC-M, Suppl for Manual Ultrasonic Exam of Dissimilar Metal Welds
ML20151W355
Person / Time
Site: Limerick 
Issue date: 11/19/1987
From: Miller W
BECHTEL POWER CORP.
To:
Shared Package
ML20151W267 List:
References
UT-AUSTENITIC-M, NUDOCS 8808240069
Download: ML20151W355 (9)


Text

% N.A A fA ECA b

% C l l'f 7,A) j pQ h

SUBJECT:

SUPPLEMENT FOR MANUAL ULTRASONIC NUCLEAR PLANT EXAMINATION OF DISSIMILAR !ETAL WELDS SERVICES DEPARTMENT UT-AUSTENITIC-M fg SUPPLElENT 2 REV. 2 PAGE 1 0F 9 PREPARED BY/DATE k

d(

l/ /h h /

/ E O 4.ZZZ" '

APPROVED BY/DATE Wh[ @M //// g/ S; OA APPROVED BY/DATE M

w

. A,)

STATEMENT OF INTENDED USE THIS DOCUMENT CONTAINS INFORMATION PREPARED BY THE CENERAL ELECTRIC COMPANY FOR THE PHILADELPHIA ELECTRIC COMPANY UPON THE CONDITION THAT IT WILL BE USED IN THE CONDU OF PHILADELPHIA ELECTttIC COMPANY INTERNAL TECHNICAL WORK AND WILL NOT BE RELEASED BY THE PliILADELPHIA ELECTRIC COMPANY TO COMPETITORS, WILL NOT BE DISTRIBUTED FOR CENERAL USE, AND WILL NOT BE USED DIRECTLY OR INDIRECTLY IN AN UNFAIR C0!!PETITIVE.

? TANNER TO THE INTERESTS OF Tile GENERAL ELECTRIC C0?tPANY.

O

~

\\

'i'.3.., R E C E V E 3

[(,'N'VP'j.p %,C[

'v,.

DEC 0 01987 N

BECHTEL

.O

\\

b O

g o^t#

eL M h M'-

k h

y /, $ d yn b W Co ACHYY //ffth7

/

O 624 C 06*) 880815

(;

A'IUCH 0500~)353 PNV

+

e PROCEDLRE:

UT-AUSTENITIC-M d

SUPP. 2 REVISION-2 DATE:

11/18/87 7,)

PACE:

20F9 TABLE OF CONTENTS SECTION DESCRIPTION PACE 1.0 SCOPE 3

2.0 CENERAL 3

3.0 REFERENCES

3 4.0 PERSONNEL REQUIREMENTS 3

5.0 EQUIPMENT 4

6.0 CALIBRATION 5

7.0 EXAMINATION 7

C')

G 8.0 DATA RECORDING 7

9.0 REPORTS AND RECORDS 8

10.0 DATA EVALUATION 9

4

.n' o.

d PROCEDURE NO. : UT-AUSTENITIC-M SUPP. 2 ew REVISION:

2

(,).

DATE:

li/18/87 PAGE NO. :

30F9 1.0 SCOPE

-1.1 This supplement defines the techniques, equipment, and requirements for manual contact ultrasoale examinatien of dissimilar metal welds, weld buttering, and cladding materials for circumferential1y and axially oriented flaws.

1.2 These examinations should be performed in addition to the ASME Section XI examinations.

2.0 CENERAL 2.1 The ultrasonic examinations shall consist of 1/2 VEE path techniques, utilizing longitudinal wave search units.

The applicable material thickness range for this examination is from 0.200" to 2.50".

2.2 Examinations shall be performed from the outside surface of the components.

()

2.3 The techniques described in this supplement are the results of work performed by the General Electric Company.

The work was sponsored by the BWR Owners Group through EPRI.

2.4 The provisions permitted in ASME Section XI Paragraph IWA-2240 are the basis of this supplement.

3.0 REFERENCES

3.1 The references identified in Section 2.0 of UT-AUSTENITIC-H are co'nsidered s part of :his supplement as applicable.

3.2 EPRI Final Report, NP4606.LD, May 1986, Examination of Dissimilar Metal Welds in BWR Nozzle to Safe-End Joints.

4.0 PERSONNEL REQUIREMENTS 4.1 General personnel requirements are as described in Section 3.0 of UT-AUSTENITIC-M.

4.2 Examination personnel shall be indoctrinated in the use of the applicable procedures and this supplement.

Evidence of this indoctrination

hall be included in the final records package.

O

- 4

'l F

,o PROCEDURE NO.:

UT-AUSTENITIC-M SUPP. 2 REVISION:

2

(~Y' L/

DATE:

11/18/87 PAGE NO. :

4 of 9 5.0 EOUIPMENT 5.1 ' Ultrasonic Instrument

~

5.1.1. General requirementsfor the Ultrasonic Instrument are as described in Section 4.1.1 of UT-AUSTENITIC-M.

5.2 Search Units 5.2.1 Dual element, ceramic type search units operating at nominal frequency from 1.0 to 4.0 MHz shall be used for this examination.

The examination shall be performed using refracted longitudinal waves with nominal angles in the range of 30" to 70'.

Maximum piezoelectric element size (each individual element) shall be 1" x 1.5".

Various roof angles and focal distances should be evaluated to choose the seach unit with the maximum signal-to-noise (S/N) ratio.

Search unit size shall be selected based upon the diamete* and configuration of the material to be examined.. allow maximum ultrasonic coupling.

()

5.2.2 Transducers / Wedges of other sizes, angles, mode of propagation, or frequencies may be used where required by material i

characteristics, geometric configuration or for the evaluation of i

indications, with-the approval of the responsible Level-III.

5.3 Cables 5.3.1 Coaxial cable sees should not exceed 12 ft.

in length.

The length and type of cable used shall be recorded on the Calibration Data Sheet.

t k

7 s.

~.

l PROCEDURE NO.:

UT-AUSTENITIC-M tf SUPP. 2 REVISION:

2 DATE -

11/18/87 PAGE No.:

5 0F 9 5.4 Calibration Blocks 5.4.1 The calibration block shall be msde from material of the same nominal diameter and wall thickness as the component to be examined. The calibration block shall be fabricated and welded from materials of the same or similar product form (s), analyses, and specifications as the welds being examined.

5.4.2 The calibration block shall contain, as a minimum, inside surface axial and c.ircumferential EDM notch reflactorg.

Notch depths shall be approximately 20% of the Basic Calib.ation Block thickness. the length of the axial notch should not exceed 0.5".

The length of the circumferential notch shall be at least 0.5" and not more than 1.0" in lonath.

5.4.3 The surface finish of the calibre:1on block shall be representative of the surface finish of the component to be examined.

It is recommended that the surface finish of the weld should be approximately 125 RMS with no valleys or wold beads present.

()

5.4.4 An IIW-2, DSC, or rompus block may be used as a simulator block for calibration checks.

Other simulator blocks may also be used for the purpose of calibration checks provided they contain suf ficient reflectors to establish the checks.

5.5 Couplant 5.5.1 The couplant shall be in accordance with Section 4.7 of UT-AUSTENITIC-M.

6.0 CALIBRATION 6.1 Instrument Linearity Verification 6.1.1 Verification of the ultrasonic instrument linearity shall be in accordance with 5.1 of UT-AUSTENITIC-M.

o.2 System Calibration 6.2.1 The general requirements for calibration of the complete ultrasonic system shall be in accordance with 5.2 of UT-AUSTENITIC-M.

t O

PROCEDURE NO.:

UT-AUSTENITIC-M SUPP. 2

~,

)

REVISION:

2 DATE:

11/18/87 PAGE NO.:

60F9 6.2.2 Detetaination of beam index - Position the angle beam search unit on an IIW-2 block or other suitable reference block so that the beam is directed toward the appropriate radius surface. Move the transducer parallel to the sides of the block until a mat.imum echo is obtained from the reflecting radius.

The beam index point.s now above the centerline of the radius, as scribed on the applicable block.

Place a mark on the side of the wedge to identi'/ the index point.

6.3 Sweep Calibration

6.3.1 Calibra

ion of the UT aystem sweep shall be in accordance with 5.3.5 of UT-AUSTENITIC-M for the 1/2 VEE path calibration.

6.4 Sensitivity Calibration 6.4.1 Position the search unit on the applicable calibration block to detect the signal from the circumferential I.D. notch located within the weld material. Maximize the signal and adjust the

(~T response to 80% FSH.

This establishes the primary reference V

level.

6.4.1.1 If a calibration block is not available that meets the specifications of 5.4 then an alternate calibration block (s) for the side under examination shall be utilized.

Position the search unit on the applicable calibration block to detect the signal from the calibration notch (es).

Maximize the signal and adjust the response to 80% FSH, repeat this process if more than one calibration block it needed.

Note the gain setting for each calibration block used.

Next a comparison on a welded mockup block should be performed. Maximize the signal from the applicable ID notch in the welded mockup, adjust the gain setting until this signal is 80% FSH, ret eat this process for both sides of the weld.

Any dB changes necessary between calibration block (s) and the welded mockup shall be noted.

The Level III responsible for the examination shsil evaluate the recorded dB changes and deteruine the appropriate adjustment to the primary reference sensitivity.

This conparison need only be performed once per UT systca/

calibration block combination.

,~

t

e

~. '

e

?

PROCEDURE NO.:

UT-AUSTENITIC-M SUPP. 2 REVISION:

2 I

DATE:

11/18/87

- bt s/-

PAGE NO.:

70F9 6.5.2 It is recognized that at given gain setting,'there will be some difference in the response between the axially oriented I.D..

notch and the circumferential1y oriented I.D. notch.

To account for this difference, maximize the amplitude from the circumferential I.D. notch at 80% FSH and then maximize the amplitude of the axial I.D. notch at 80% FSH. Note this dB change on the Calibration Data Sheet for future reference.

This determination shall be performed for each calibrated.UT system /

calibration block combination.

6.6 Calibration Record 6.6.1 All calibration and calibration verification data shall be recorded on the Calibration Data Sheet.

7.0 EXAMINATION 7.1 General 7.1.1 Examinations shall be performed in accordance with Section 6.0 of

}

UT-AU3TENITIC-M as applicable.

7.1.2 Examinations shall be performed using nominal angles of both 45'

+ 3* and 60' + 3' to supplement scans 1 through 4 (Figure 3) of UT-AUSTENITIC-M.

For circumferential scans, the refracted angle shall not exceed the are sin of the inside radius /outside radius.

Alternate angles may be used if it is determined by the responsible Level III that more meaningful data can be obtained.

7.1.3 Scanning sensitivity shall be established so that the average base line noise level is between 10% and 20% FSH.

Base line ncise levels in excess of 30% vcu shall be approved by the Level III responsible for the examination.

8.0 DATA RECORDING 8.1 If, during the examination the Level II believes that indications are caused by cracks, or they are believed to be crack like in nature, they shall be noted on the Examination Data Sheet (s) regardless of amplitude.

8.2 All indications in excer.s of 10% FSH above the average noise level shall be recorded.

If in the opinion of the Examiner a signal may mask the L

recording of others, the scan shall be completed.

The suspect area i

shall be rescanned with a calibration that allows determination of whether a masking condition exists.

O

_--,.-v-

.--,-,..-._.m_-.,.-

_.,.3y y

  1. -.,,y y

7,p

,-ym.

,_,,-e._.

_.--m, g7-.-

7 4

l..

PROCEDURE NO.:

UT-AUSTENITIC-M SUPP. 2 REVISION:

2

( )

DATE:

11/18/87 PACE NO.

8 0F 9 9.0 REPORTS AND RECORDS

-9.1 Minimum Information Requirements 9.1.1 Examination records shall include, but not necessary be limited to the following:

9.1.2 Calibration Data Sheet a) Calibration sheet identification, date and time period of~

calibration.

b) name(s) of examination personnel.

c) examination procedure number and revision.

d) basic calibration block identification.

e) ultrasonic instrument identification and serial number.

f) beam angle, couplant, and mode of wave reopagation in the material.

8) orientation of search unit with respect to the pipe (longitudinal or circumferential).

h) search unit identification - frequency, size, Manuf acturer,

/~N and serial number.

' (_)

i) reviewers signature, level and date.

j) search unit cable type, and length.

k) times of initial calibration and subsequent and final calibration checks.

1) instrument settings, amplicades, and sweep positions used to establish primary reference sensitivity.

m) thermometer serial number and required calibration block temperatures.

9.1.3 Examinition Data Sheet a) data sheet indentity, examination date and time period of examination b) name(s) and ASNT Level (s) of examination personnel c) examination procedure and revision d) applicable calibration sheet indentity e) weld identification f) record of indications or of volume free from indications g) volume scanned and scan limitations if any h) reveiwers signature, level and date 1) search unit positicn and locations of recorded indications j) thermometer aerial numbers and examination surface k) acoustic equivalency adjustment where necessary

4 PROCEDURE NO.

UT-AUSTENITIC-M SUPP. 2

~J REVISION:

2 DATE:

11/18/87 PAGE 'NO.

90F9 9.2 Qualification Report 9.2.1 The-adequacy of the selected ultrasonic system / calibration

' block /proceduce combination shall be demonstrated once on a represents:ive mockup before the actual examination is performed.

The mockup may be the basic calibration block. The demonstration will be considered successful if the 20% notches are detected with a signal to noise ratio o. 2:1 or greater.

9.2.2 A report shall be prepared to document the demonstration. Any change to the specified ulcrasonic system / calibration block / procedure combination shall require a demonstration on a representative mockup and preparation of a new qualification report. The report for this demonstration may be combined with that for automated examinations if automated exams are performed.

10.0 _ DATA EVALUATION 10.1 Ultras;nic-data shall be evaluated in accordance with LIM-UTI-Evaluation.

O_

10.2 Evaluated data shall be reveiwed by n GE Level III and forwarded in accordance with contract and QA Manual requirements for final disposition.

O t