ML20134H950
| ML20134H950 | |
| Person / Time | |
|---|---|
| Site: | Grand Gulf |
| Issue date: | 05/12/2020 |
| From: | Siva Lingam NRC/NRR/DORL/LPL4 |
| To: | |
| Lingam S | |
| References | |
| Download: ML20134H950 (37) | |
Text
SSW System and UHS B 3.7.1 GRAND GULF B 3.7-5 LBDCR 14043 BASES ACTIONS C.1 (continued)
A low water level in the UHS basin indicates that the required 30 day water supply for the post LOCA cooling requirements may not be available. However, changes in water level for such a large volume are slowly occurring events and the degradation when discovered is unlikely to have significantly degraded the basin capability. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Time was developed taking into account the remaining capability of the UHS basin, the low probability that this inoperability occurring during the assumed maximum heat load conditions, and the low probability of a DBA occurring during this period.
E.1 If any Required Action and associated Completion Time of Condition A, C, or D are not met the unit must be placed in a MODE in which overall plant risk is minimized. To achieve this status, the unit must be placed in at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
Remaining in the Applicability of the LCO is acceptable because the plant risk in MODE 3 is similar to or lower than the risk in MODE 4 (Ref. 8) and because the time spent in MODE 3 to perform the necessary repairs to restore the system to OPERABLE status will be short. However, voluntary entry into MODE 4 may be made as it is also an acceptable low-risk state.
Required Action E.1 is modified by a Note that states that LCO 3.0.4.a is not applicable when entering MODE 3. This Note prohibits the use of LCO 3.0.4.a to enter MODE 3 during startup with the LCO not met.
However, there is no restriction on the use of LCO 3.0.4.b, if applicable, because LCO 3.0.4.b requires performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering MODE 3, and establishment of risk management actions, if appropriate. LCO 3.0.4 is not applicable to, and the Note does not preclude, changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
The allowed Completion Time is reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
(continued)
SSW System and UHS B 3.7.1 GRAND GULF B 3.7-6 LBDCR 18127 BASES ACTIONS F.1 and F.2 (continued)
If both SSW subsystems are inoperable, more than one of the UHS cooling towers have inoperable cooling tower fan(s), or the UHS basin is inoperable for reasons other than condition C, the unit must be placed in a MODE in which the LCO does not apply. To achieve this status, the unit must be placed in at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in MODE 4 within 36 hours4.166667e-4 days <br />0.01 hours <br />5.952381e-5 weeks <br />1.3698e-5 months <br />. The allowed Completion Times are reasonable, based on operating experience, to reach the required unit conditions from full Clpower conditions in an orderly manner and without challenging unit systems.
SURVEILLANCE SR 3.7.1.1 REQUIREMENTS This SR ensures adequate long term (30 days) cooling can be maintained. With the UHS water source below the minimum level, the UHS basin must be declared inoperable. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.1.2 Operating each cooling tower fan for 15 minutes ensures that all fans are OPERABLE and that all associated controls are functioning properly.
It also ensures that fan or motor failure, or excessive vibration can be detected for corrective action. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.1.3 Verifying the correct alignment for each required manual, power operated, and automatic valve in each SSW subsystem flow path provides assurance that the proper flow paths will exist for SSW operation. This SR does not apply to valves that are locked, sealed, or otherwise secured in position, since these valves were verified to be in the correct position prior to locking, sealing, or securing. A valve is also allowed to be in the nonaccident position and yet considered in the correct position, provided it can be automatically realigned to its accident position within the required time. This SR does not require any testing or valve manipulation; rather, it involves verification that those valves capable of potentially being mispositioned are in the correct position.
(continued)
SSW System and UHS B 3.7.1 GRAND GULF B 3.7-7 LBDCR 18127 BASES SURVEILLANCE SR 3.7.1.3 (continued)
REQUIREMENTS This SR does not apply to valves that cannot be inadvertently misaligned, such as check valves.
Isolation of the SSW System to components or systems does not necessarily affect the OPERABILITY of the SSW subsystem. As such, when all SSW pumps, valves, and piping are OPERABLE, but a branch connection off the main header is isolated, the SSW subsystem needs to be evaluated to determine if it is still OPERABLE.
The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.1.4 This SR verifies that the automatic isolation valves of the SSW System will automatically switch to the safety or emergency position to provide cooling water exclusively to the safety related equipment during an accident event. This is demonstrated by use of an actual or simulated initiation signal. This SR also verifies the automatic start capability of the SSW pump and cooling tower fans in each subsystem. The LOGIC SYSTEM FUNCTIONAL TEST in SR 3.3.5.1.6 overlaps this SR to provide complete testing of the safety function.
The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
REFERENCES
- 1. Regulatory Guide 1.27, Revision 2, January 1976.
- 2. UFSAR, Section 9.2.1.
- 3. UFSAR, Table 9.2-3.
- 4. UFSAR, Section 6.2.1.1.3.3.
- 5. UFSAR, Chapter 15.
- 6. UFSAR, Section 6.2.2.3.
- 7. UFSAR, Table 6.2-2.
- 8. NEDC-32988-A, Revision 2, Technical Justification to Support Risk-Informed Modification to Selected Required End States for BWR Plants, December 2002.
HPCS SWS B 3.7.2 GRAND GULF B 3.7-9 LBDCR 18128 BASES (continued)
LCO The HPCS SWS is required to be OPERABLE to ensure that the HPCS System will operate as required. An OPERABLE HPCS SWS consists of an OPERABLE pump; and an OPERABLE flow path, capable of taking suction from the UHS basin and transferring the water to the appropriate unit equipment.
The OPERABILITY of the UHS is discussed in LCO 3.7.1. However, the OPERABILITY of the basin cooling tower fans does not affect the OPERABILITY of the HPCS SWS, due to the limited heat removal during its operation.
APPLICABILITY In MODES 1, 2, and 3, the HPCS SWS is required to be OPERABLE to support OPERABILITY of the HPCS System since it is required to be OPERABLE in these MODES.
In MODES 4 and 5, the OPERABILITY requirements of the HPCS SWS and the UHS are determined by the HPCS System.
ACTIONS A.1 When the HPCS SWS is inoperable, the capability of the HPCS System to perform its intended function cannot be ensured. Therefore, if the HPCS SWS is inoperable, the HPCS System must be declared inoperable immediately and the applicable Conditions of LCO 3.5.1, "ECCS - Operating," or LCO 3.5.2, "RPV Water Inventory Control,"
entered.
SURVEILLANCE SR 3.7.2.1 REQUIREMENTS Verifying the correct alignment for each required manual, power operated, and automatic valve in the HPCS service water flow path provides assurance that the proper flow paths will exist for HPCS service water operation. This SR does not apply to valves that are locked, sealed, or otherwise secured in position, since these valves are verified to be in correct position prior to locking, sealing, or securing.
A valve is also allowed to be in the nonaccident position and yet considered in the correct position, provided it can be automatically realigned to its accident position within the required time. This SR does not require any testing or valve manipulation; rather, it involves verification that (continued)
HPCS SWS B 3.7.2 GRAND GULF B 3.7-10 LBDCR 18127 BASES SURVEILLANCE SR 3.7.2.1 (continued)
REQUIREMENTS those valves capable of potentially being mispositioned are in the correct position. This SR does not apply to valves that cannot be inadvertently misaligned, such as check valves.
Isolation of the HPCS SWS to components or systems may render those components or systems inoperable, but may not affect the OPERABILITY of the HPCS SWS. As such, when all HPCS SWS pumps, valves, and piping are OPERABLE, but a branch connection off the main header is isolated, the HPCS SWS needs to be evaluated to determine if it is still OPERABLE.
The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.2.2 This SR verifies that the automatic isolation valves of the HPCS SWS will automatically switch to the safety or emergency position to provide cooling water exclusively to the safety related equipment during an accident event. This is demonstrated by use of an actual or simulated initiation signal. This SR also verifies the automatic start capability of the HPCS SWS pump. The LOGIC SYSTEM FUNCTIONAL TEST in SR 3.3.5.1.6 overlaps this SR to provide complete testing of the safety function.
The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
REFERENCES
- 1.
UFSAR, Section 9.2.1.
- 2.
UFSAR, Chapter 6.
- 3.
UFSAR, Chapter 15.
CRFA System B 3.7.3 GRAND GULF B 3.7-14 LBDCR 18128 BASES LCO individual at the opening who is in continuous communication (continued) with the operators in the CRE. This individual will have a method to rapidly close the opening and to restore the CRE boundary to a condition equivalent to the design condition when a need for CRE isolation is indicated.
APPLICABILITY In MODES 1, 2, and 3, the CRFA System must be OPERABLE to ensure that the CRE will remain habitable during and following a DBA, since the DBA could lead to a fission product release.
In MODES 4 and 5, the probability and consequences of a DBA are reduced due to the pressure and temperature limitations in these MODES. Therefore, maintaining the CRFA System OPERABLE is not required in MODE 4 or 5.
ACTIONS A.1 With one CRFA subsystem inoperable for reasons other than an inoperable CRE boundary, the inoperable CRFA subsystem must be restored to OPERABLE status within 7 days. With the unit in this condition, the remaining OPERABLE CRFA subsystem is adequate to perform the CRE occupant protection function. However, the overall reliability is reduced because a failure in the OPERABLE subsystem could result in loss of CRFA System function. The 7 day Completion Time is based on the low probability of a DBA occurring during this time period, and that the remaining subsystem can provide the required capabilities.
B.1, B.2, and B.3 If the unfiltered inleakage of potentially contaminated air past the CRE boundary and into the CRE can result in CRE occupant radiological dose greater than the calculated dose of the licensing basis analyses of DBA consequences (allowed to be up to 5 rem TEDE), or inadequate protection of CRE occupants from hazardous chemicals or smoke, the CRE boundary is inoperable. Actions must be taken to restore an OPERABLE CRE boundary within 90 days.
(continued)
CRFA System B 3.7.3 GRAND GULF B 3.7-15 LBDCR 14043 BASES ACTIONS B.1, B.2, and B.3 (continued)
During the period that the CRE boundary is considered inoperable, action must be initiated to implement mitigating actions to lessen the effect on CRE occupants from the potential hazards of a radiological or chemical event or a challenge from smoke. Actions must be taken within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to verify that in the event of a DBA, the mitigating actions will ensure that CRE occupant radiological exposures will not exceed the calculated dose of the licensing basis analyses of DBA consequences, and that CRE occupants are protected from hazardous chemicals and smoke. These mitigating actions (i.e., actions that are taken to offset the consequences of the inoperable CRE boundary) should be preplanned for implementation upon entry into the condition, regardless of whether entry is intentional or unintentional. The 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> Completion Time is reasonable based on the low probability of a DBA occurring during this time period, and the use of mitigating actions. The 90 day Completion Time is reasonable based on the determination that the mitigating actions will ensure protection of CRE occupants within analyzed limits while limiting the probability that CRE occupants will have to implement protective measures that may adversely affect their ability to control the reactor and maintain it in a safe shutdown condition in the event of a DBA. In addition, the 90 day Completion Time is a reasonable time to diagnose, plan and possible repair, and test most problems with the CRE boundary.
C.1 In MODE 1, 2, or 3, if the inoperable CRFA subsystem or the CRE boundary cannot be restored to OPERABLE status within the required Completion Time, the unit must be placed in a MODE that minimizes overall plant risk. To achieve this status, the unit must be placed in at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
Remaining in the Applicability of the LCO is acceptable because the plant risk in MODE 3 is similar to or lower than the risk in MODE 4 (Ref. 5) and because the time spent in MODE 3 to perform the necessary repairs to restore the system to OPERABLE status will be short. However, voluntary entry into MODE 4 may be made as it is also an acceptable low-risk state.
(continued)
CRFA System B 3.7.3 GRAND GULF B 3.7-16 LBDCR 18128 BASES ACTIONS C.1 (continued)
(continued)
Required Action C.1 is modified by a Note that states that LCO 3.0.4.a is not applicable when entering MODE 3. This Note prohibits the use of LCO 3.0.4.a to enter MODE 3 during startup with the LCO not met.
However, there is no restriction on the use of LCO 3.0.4.b, if applicable, because LCO 3.0.4.b requires performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering MODE 3, and establishment of risk management actions, if appropriate. LCO 3.0.4 is not applicable to, and the Note does not preclude, changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
The allowed Completion Time is reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
D.1 If both CRFA subsystems are inoperable in MODE 1, 2, or 3 for reasons other than an inoperable CRE, the CRFA System may not be capable of performing the intended function and the unit is in a condition outside of the accident analyses. Therefore, the plant must be brought to a MODE in which the overall plant risk is minimized. To achieve this status, the plant must be brought to at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
(continued)
CRFA System B 3.7.3 GRAND GULF B 3.7-16a LBDCR 18128 ACTIONS D.1 (continued)
(continued)
Remaining in the Applicability of the LCO is acceptable because the plant risk in MODE 3 is similar to or lower than the risk in MODE 4 (Ref. 5) and because the time spent in MODE 3 to perform the necessary repairs to restore the system to OPERABLE status will be short. However, voluntary entry into MODE 4 may be made as it is also an acceptable low-risk state.
Required Action E.1 is modified by a Note that states that LCO 3.0.4.a is not applicable when entering MODE 3. This Note prohibits the use of LCO 3.0.4.a to enter MODE 3 during startup with the LCO not met.
However, there is no restriction on the use of LCO 3.0.4.b, if applicable, because LCO 3.0.4.b requires performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering MODE 3, and establishment of risk management actions, if appropriate. LCO 3.0.4 is not applicable to, and the Note does not preclude, changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
The allowed Completion Time is reasonable, based on operating experience, to reach the required plant conditions from full power conditions in an orderly manner and without challenging plant systems.
(continued)
CRFA System B 3.7.3 GRAND GULF B 3.7-16b LBDCR 18127 BASES (continued)
SURVEILLANCE SR 3.7.3.1 REQUIREMENTS This SR verifies that a subsystem in a standby mode starts from the control room on demand and continues to operate. Standby systems should be checked periodically to ensure that they start and function properly. Operation for t 15 continuous minutes demonstrates OPERABILITY of the system. Periodic operation ensures that blockages fan or motor failure, or excessive vibration can be detected for corrective action. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.3.2 This SR verifies that the required CRFA testing is performed in accordance with the Ventilation Filter Testing Program (VFTP). The VFTP includes testing HEPA filter performance, and minimum system flow rate. Specific test frequencies and additional information are discussed in detail in the VFTP.
SR 3.7.3.3 This SR verifies that each CRFA subsystem starts and operates and that the isolation valves close in 4 seconds on an actual or simulated initiation signal. The LOGIC SYSTEM FUNCTIONAL TEST in SR 3.3.7.1.1 overlaps this SR to provide complete testing of the safety function. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.3.4 This SR verifies the OPERABILITY of the CRE boundary by testing for unfiltered air inleakage past the CRE boundary and into the CRE. The details of the testing are specified in the Control Room Envelope Habitability Program.
(continued)
CRFA System B 3.7.3 GRAND GULF B 3.7-16c LBDCR 14043 BASES SURVEILLANCE SR 3.7.3.4 (continued)
REQUIREMENTS The CRE is considered habitable when the radiological dose to CRE occupants calculated in the licensing basis analyses of DBA consequences is no more than 5 rem TEDE and the CRE occupants are protected from hazardous chemicals and smoke. This SR verifies that the unfiltered air inleakage into the CRE is no greater than the flow rate assumed in the licensing basis analyses of DBA consequences. When unfiltered air inleakage is greater than the assumed flow rate, Condition B must be entered. Required Action B.3 allows time to restore the CRE boundary to OPERABLE status provided mitigating actions can ensure that the CRE remains within the licensing basis habitability limits for the occupants following an accident. Compensatory measures are discussed in Regulatory Guide 1.196, Section C.2.7.3, which endorses, with exceptions, NEI 99-03, Section 8.4 and Appendix F (Ref. 9). These compensatory measures may also be used as mitigating actions as required by Required Action B.2. Temporary analytical methods may also be used as compensatory measures to restore OPERABILITY (Ref. 10).
Options for restoring the CRE boundary to OPERABLE status include changing the licensing basis DBA consequence analysis, repairing the CRE boundary, or a combination of these actions. Depending upon the nature of the problem and the corrective action, a full scope inleakage test may not be necessary to establish that the CRE boundary has been restored to OPERABLE status.
REFERENCES
- 1.
FSAR, Section 6.5.1.
- 2.
FSAR, Section 9.4.1.
- 3.
FSAR, Chapter 6.
- 4.
FSAR, Chapter 15.
- 5.
NEDC-32988-A, Revision 2, Technical Justification to Support Risk-Informed Modification to Selected Required End States for BWR Plants, December 2002.
- 6.
Engineering Evaluation Request 95/6213, Engineering Evaluation Request Response Partial Response dated 12/18/95.
- 7.
Amendment 145 to GGNS Operating License.
(continued)
CRFA System B 3.7.3 GRAND GULF B 3.7-16d LBDCR 14043 BASES REFERENCES
- 8.
UFSAR, Section 9.5 (continued)
- 9.
NEI 99-03, Control Room Habitability Assessment, June 2001.
- 10.
Letter from Eric J. Leeds (NRC) to James W. Davis (NEI) Use of Generic Letter 91-18 Process and Alternative Source Terms in the Context of Control Room Habitability. (ADAMS Accession No. ML04300694).
Control Room AC System B 3.7.4 GRAND GULF B 3.7-17a LDC 18128 BASES APPLICABLE accidents (e.g., LOCA, main steam line break).
The Control Room AC System satisfies Criterion 3 of the NRC Policy Statement.
(continued)
Control Room AC System B 3.7.4 GRAND GULF B 3.7-18 LBDCR 18128 BASES (continued)
LCO Two independent and redundant subsystems of the Control Room AC System are required to be OPERABLE to ensure that at least one is available, assuming a single failure disables the other subsystem. Total system failure could result in the equipment operating temperature exceeding limits.
The Control Room AC System is considered OPERABLE when the individual components necessary to maintain the control room temperature are OPERABLE in both subsystems. These components include the cooling coils, fans, chillers, compressors, ductwork, dampers, and associated instrumentation and controls. The heating coils are not required for Control Room AC System OPERABILITY.
APPLICABILITY In MODE 1, 2, or 3, the Control Room AC System must be OPERABLE to ensure that the control room temperature will not exceed equipment OPERABILITY limits.
In MODES 4 and 5, the probability and consequences of a Design Basis Accident are reduced due to the pressure and temperature limitations in these MODES. Therefore, maintaining the Control Room AC System OPERABLE is not required in MODE 4 or 5.
ACTIONS A.1 With one control room AC subsystem inoperable, the inoperable control room AC subsystem must be restored to OPERABLE status within 30 days. With the unit in this condition, the remaining OPERABLE control room AC subsystem is adequate to perform the control room air conditioning function. However, the overall reliability is reduced because a single failure in the OPERABLE subsystem could result in loss of the control room air conditioning function. The 30 day Completion Time is based on the low probability of an event occurring requiring control room isolation, the consideration that the remaining subsystem can provide the required protection, and the availability of alternate cooling methods.
(continued)
Control Room AC System B 3.7.4 GRAND GULF B 3.7-19 LBDCR 14043 BASES ACTIONS B.1 and B.2 If both control room AC subsystems are inoperable, the Control Room AC System may not be capable of performing its intended function.
Therefore, the control room area temperature is required to be monitored to ensure that temperature is being maintained low enough that equipment in the control room is not adversely affected. With the control room temperature being maintained within the temperature limit, 7 days is allowed to restore a control room AC subsystem to OPERABLE status.
This Completion Time is reasonable considering that the control room temperature is being maintained within limits, the low probability of an event occurring requiring control room isolation, and the availability of alternate cooling methods.
C.1 In MODE 1, 2, or 3, if the control room area temperature cannot be maintained less than or equal to 90°F or if the inoperable control room AC subsystem cannot be restored to OPERABLE status within the associated Completion Time, the unit must be placed in a MODE that minimizes overall plant risk. To achieve this status the unit must be placed in at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
Remaining in the Applicability of the LCO is acceptable because the plant risk in MODE 3 is similar to or lower than the risk in MODE 4 (Ref. 3) and because the time spent in MODE 3 to perform the necessary repairs to restore the system to OPERABLE status will be short. However, voluntary entry into MODE 4 may be made as it is also an acceptable low-risk state.
Required Action B.1 is modified by a Note that states that LCO 3.0.4.a is not applicable when entering MODE 3. This Note prohibits the use of LCO 3.0.4.a to enter MODE 3 during startup with the LCO not met.
However, there is no restriction on the use of LCO 3.0.4.b, if applicable, because LCO 3.0.4.b requires performance of a risk assessment addressing inoperable systems and components, consideration of the results, determination of the acceptability of entering MODE 3, and establishment of risk management actions, if appropriate. LCO 3.0.4 is not applicable to, and the Note does not preclude, changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
The allowed Completion Time is reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
(continued)
Control Room AC System B 3.7.4 GRAND GULF B 3.7-20 LDC 18128 BASES Page Intentionally Left Blank (continued)
Control Room AC System B 3.7.4 GRAND GULF B 3.7-21 LBDCR 18127, 18128 BASES SURVEILLANCE SR 3.7.4.1 REQUIREMENTS This SR verifies that the heat removal capability of the system is sufficient to remove the control room heat load assumed in the safety analysis.
The SR consists of a combination of testing and calculation. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
REFERENCES 1.
FSAR, Section 6.4.
2.
FSAR, Section 9.4.1.
3.
NEDC-32988-A, Revision 2, Technical Justification to Support Risk-Informed Modification to Selected Required End States for BWR Plants, December 2002.
Main Condenser Offgas B 3.7.5 GRAND GULF B 3.7-23 LBDCR 14043 BASES (continued)
APPLICABILITY The LCO is applicable when steam is being exhausted to the main condenser and the resulting noncondensibles are being processed via the Main Condenser Offgas System. This occurs during MODE 1, and during MODES 2 and 3 with any main steam line not isolated and the SJAE in operation. In MODES 4 and 5, steam is not being exhausted to the main condenser and the requirements are not applicable.
ACTIONS A.1 If the offgas radioactivity rate limit is exceeded, 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> is allowed to restore the gross gamma activity rate to within the limit. The 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> Completion Time is reasonable, based on engineering judgment considering the time required to complete the Required Action, the large margins associated with permissible dose and exposure limits, and the low probability of a Main Condenser Offgas System rupture occurring.
B.1, and B.2 If the gross gamma activity rate is not restored to within the limits within the associated Completion Time, the SJAE must be isolated. This isolates the Main Condenser Offgas System from the source of the radioactive steam. The 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> Completion Time is reasonable, based on operating experience, to perform the actions from full power conditions in an orderly manner and without challenging unit systems.
An alternative to Required Action B.1 is to place the unit in a MODE in which overall plant risk is minimized. To achieve this status, the unit must be placed in at least MODE 3 within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
Remaining in the Applicability of the LCO is acceptable because the plant risk in MODE 3 is similar to or lower than the risk in MODE 4 (Ref. 4) and because the time spent in MODE 3 to perform the necessary repairs to restore the system to OPERABLE status will be short. However, voluntary entry into MODE 4 may be made as it is also an acceptable low-risk state.
Required Action B.2 is modified by a Note that states that LCO 3.0.4.a is not applicable when entering MODE 3. This Note prohibits the use of LCO 3.0.4.a to enter MODE 3 during startup with the LCO not met.
However, there is no restriction on the use of LCO 3.0.4.b, if applicable, because LCO 3.0.4.b requires performance of a risk assessment addressing (continued)
Main Condenser Offgas B 3.7.5 GRAND GULF B 3.7-24 LBDCR 18127 BASES ACTIONS B.1, and B.2 (continued) inoperable systems and components, consideration of the results, determination of the acceptability of entering MODE 3, and establishment of risk management actions, if appropriate. LCO 3.0.4 is not applicable to, and the Note does not preclude, changes in MODES or other specified conditions in the Applicability that are required to comply with ACTIONS or that are part of a shutdown of the unit.
The allowed Completion Time is reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
SURVEILLANCE SR 3.7.5.1 and 3.7.5.2 REQUIREMENTS SR 3.7.5.2, requires an isotopic analysis of an offgas sample to ensure that the required limits are satisfied. The noble gases to be sampled include Xe-133, Xe-135, Xe-138, Kr-85, Kr-87, and Kr-88. If the measured rate of radioactivity increases significantly (by 50% after correcting for expected increases due to changes in THERMAL POWER),
an isotopic analysis is also performed within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after the increase is noted as required by SR 3.7.5.1, to ensure that the increase is not indicative of a sustained increase in the radioactivity rate. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.5.2 is modified by a Note indicating that the SR is not required to be performed until 31 days after any SJAE is in operation. Only in this condition can radioactive fission gases be in the Main Condenser Offgas System at significant rates.
REFERENCES
- 1.
FSAR, Section 15.7.1.
- 2.
- 3.
- 4.
NEDC-32988-A, Revision 2, Technical Justification to Support Risk-Informed Modification to Selected Required End States for BWR Plants, December 2002.
Fuel Pool Water Level B 3.7.6 GRAND GULF B 3.7-26 LBDCR 18127 BASES (continued)
LCO The specified water level preserves the assumption of the fuel handling accident analysis (Ref. 2. As such, it is the minimum required for fuel movement within the spent fuel storage pool and upper containment fuel storage pool.
APPLICABILITY This LCO applies whenever movement of irradiated fuel assemblies occurs in the associated fuel storage racks since the potential for a release of fission products exists.
ACTIONS A.1 Required Action A.1 is modified by a Note indicating that LCO 3.0.3 does not apply. If moving irradiated fuel assemblies while in MODE 1, 2, or 3, the fuel movement is independent of reactor operations. Therefore, inability to suspend movement of irradiated fuel assemblies is not a sufficient reason to require a reactor shutdown.
When the initial conditions for an accident cannot be met, steps should be taken to preclude the accident from occurring. With either fuel pool level less than required, the movement of irradiated fuel assemblies in the associated storage pool is suspended immediately. Suspension of this activity shall not preclude completion of movement of an irradiated fuel assembly to a safe position. This effectively precludes a spent fuel handling accident from occurring.
SURVEILLANCE SR 3.7.6.1 REQUIREMENTS This SR verifies that sufficient water is available in the event of a fuel handling accident. The water level in the spent fuel storage pool and upper containment fuel storage pool must be checked periodically. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
(continued)
GRAND GULF B 3.7-30 LBDCR 18127 Main Turbine Bypass System B 3.7.7 BASES (continued)
B.1 If the Main Turbine Bypass System cannot be restored to OPERABLE status or the LHGR and MCPR limits for two or more inoperable Main Turbine Bypass valves are not applied, THERMAL POWER must be reduced to < 70% RTP. As discussed in the Applicability section, operation at <70% RTP results in sufficient margin to the required limits, and the Main Turbine Bypass system is not required to protect fuel integrity during the feedwater controller failure, maximum demand event.
The 4 hour4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> Completion Time is reasonable, based on operating experience, to reach the required unit conditions from full power conditions in an orderly manner and without challenging unit systems.
SURVEILLANCE SR 3.7.7.1 REQUIREMENTS Cycling each Main Turbine Bypass valve through one complete cycle of full travel demonstrates that the valves are mechanically OPERABLE and will function when required. The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
SR 3.7.7.2 The Main Turbine Bypass System is required to actuate automatically to perform its design function. This SR demonstrates that, with the required system initiation signals, the valves will actuate to their required position.
The Surveillance Frequency is controlled under the Surveillance Frequency Control Program.
REFERENCES None