Text

.

Appendix NOTICE OF VIOLATION Commonwealth Edison Company Docket No. 50-254 Docket No. 50-265 As a result of the inspection conducted on July 9-12, 1985, and in accordance with the General Policy and Procedures for NRC Enforcement Actions, (10 CFR Part 2, Appendix C), the following violation was identified:

Technical Specification 3.2.G.2 states that...with one or more radioactive liquid effluent monitoring instruments inoperable, take the action shown in Table 3.2-5.

Action A, for service water effluent gross activity monitor, in Table 3.2-5 states that...with less than the minimum number of operable channels, releases via this pathway may continue, provided that at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> grab samples are collected and analyzed for beta or gamma activity at an LLD of less than or equal to 10 7 uCi/ml.

Contrary to the above, the 12 hour1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> grab samples from both Unit 1 and Unit 2 service water, required about 8:00 p.m. on June 13, 1985, were not collected and analyzed (the service water monitors for both Unit 1 and Unit 2 have remained inoperable since December 19, 1984).

This is a Severity Level V violation (Supplement I ).

Pursuant to the provisions of 10 CFR 2.201, you are required to submit to this office within thirty days of the date of this Notice a written statement or explanation in reply, including for each item of noncompliance:

(1) cor-rective action taken and the results achieved; (2) corrective action to be taken to avoid further noncompliance; and (3) the date when full compliance will be achieved.

Consideration may be given to extending your response time for good cause shown.

7-3045 LO DSbAYM -

Dated W. D. Shaf er, Chfef Emergency Prepa/edness and Radiological Protection Branch i

8508050222 8507h254 _

1 gDR ADOCK 0500 PDR

]