i

'c s..

l t.

l Procedure No.

W-SITP-12 J. A. JONES CONSTRUCTION COMPANY SITE INSPECTION AND TEST PROCEDURE FOR i

BACKFILL AND COMPACTION INSPECTION l

l l

WATERFORD SES UNIT NO. 3 l

CONTRACT NO. W3-NY-4 l

l ENGINEERING CONSTRUCTION QUALITY ASSURANCE i

REV.

DATE REVIEWED BY DATE~

REVIEWED BY DATE APPROVED BY DATE o

ieig rs af

,o,-j n. pgW: dc4s v3rLe.R'// nicu

/

3-/6-7/caff5 2//c/ps Anu $kuh JAtbe (C&C k ML/y g, a 2 +A/w ed emO' W6 4//k%DNKl 44/x 3 '//2a/7C a//& W eoJ n Y fm Y2//74 W 0A <tho/u 'l b/15/76 b'0 cull #$ 0/25/ 8 LH&/$ 04r7/ Ld iN#<., e / 6/zsha 5 'hl1<- affa 7/7/76;, W fm '7/WA D& 6.O 1/9 17s (o 9121n. dAS -a q{f c W/mI$9/7s Lad 8bw c.PD/ elsl7s 6 7 ila/>r C p n, if>5/77 9//%l 2.2iAli ./ac),, i.za.?r FREE 4vM OF INFORMATION ACT REQUEST f4-est 4/667 8506220099 850222 PDR FDIA GARDEB4-455 PDR l

J. A. JONES CONSTRUCTION COMPANY PAGE 1 0F 3 SITE INSPECTION AND TEST PROCCDURE: PROCCDURE NO. W-SITP-12 REV. NO. 7 TITLE: BACKFILL AND COMPACTIO!! lNSPECTION DATE: 1-25-77 PROJECT TITLE: WATERFORD SES UNIT NO. 3 CONTRACT No. W3-NY-4 1.0 PURPOSE To specify the inspection and surveillance acti.vities that will be per-formed by J. A. Jones Quality Assurance / Quality Verification personnel to assure that backfill is placed and compacted in accordance with approved drawings, specifications and procedures. 2.0 SCOPE This procedure governs the placing and compaction of backfill material for Waterford SES Unit No. 3, Phase I Concrete Construction. 30 DEFINITIONS 3.1 Class "A" fill shall be either sand containing no more than twelve (12) percent material passing a number 200 selve or Pleistocene clay. O 32 Class "B" fill shall be selected sand, silt, clay, or a combination thereof, selected from the excavation. 33 Location of Class "A" and Class "B" fill shall be as shown on Ebasco Drawing No. LOU-1564 4497 Sol," General Backfill Plan and Sections".

4.0 REFERENCES

4.1 J. A. Jones Construction Work Procedure, W-WP-12. "Backfilling and Compaction". 4.2 Ebasco Services, Inc. Specification No. LOU-1564.482, " Filter and Dack fi l l". 4.3 Ebasco Drawing No. LOU-1564-G-490, " Nuclear Plant Island Structure - Construction Sequence." 5.0 RES'PONSIBILITIES 5.1 Ebasco Services, Inc. is responsible for the furnishing of all back-fill material and for all testing of backfill material and compacted backfill. 5.2 J. A. Jones is responsible for the proper placing and compaction of backfill in accordance with approved drawings, specifications and procedures. 9

~ n I J. A. JONES CONSTRUCTION COMPANY PAGE 2 0F 3 SITE INSPECTION AND TEST PROCEDURE: PROCEDURE NO. W-SIIP-12 REV. NO. TITLE: ~ ~ BACKFILL-AND COMPACTION INSPECTION ROJEC TIR E: WATERFORD SES UNIT NO. 3 CONTRACT No. W3-NY-4 l 6.0 VERIFICATION ACTIVITIES: 6.1 The assigned Inspector (s) shall monitor the backfill place-ment and spreading activities as required to assure that: 6.1.1 Backfill sequence is in accordance with Drawing No. LOU-1564-G490; 6.1.2 Base to receive backfill is free of debris, organic material and compacted to proper density and accepted j by Ebasco; (See note 1,2, & 3) i 6.1.3 Sand fill is placed in layers no greater than 15 inches in depth; (See note 4 & 6) 6.1.4 Clay fill is placed in layers no greater than 10 inches in depth; 6.1.5 Hauling equipment does not follow the same path through the fill area; (see Note 5) 6.1.6 Fill is placed in layers of not more than 12 inches in restricted areas. 6.1.7 The waterproofing membrane is not damaged prior or during the placing of each lift. 6.2 The assigned Inspector (s) shall monitor the backfill compaction activity, as required to assure that; p 6.2.1 Roller passes are started adjacent to the foundation and move outward. 6.2.2 Each layer is compacted to its full width; 6.2.3 The required density tests are performed and acceptable prior to placing the next lif t of material. l l _--_m. _-.-,_-m.--- ._.-,--m.--

l. .l. A. J0Mf:S COi!STRUCTION COMPANY PACE 3 0F 3

  • SITE INSPECTION AND TEST Pl!OCIDURE:

PROCEDURE NO. W-SITP-12 REV. NO. 7 TITLE: DACKFILL AND C0tiPACTICH INSPECTION DATE: 1/25/77 PROJECT TITLE: VATERFORD SES UNIT NO. 3 CONTRACT NO. W3-NY-4 7.0 DOCUMENTATION The assigned. Quality Verification Inspector (s). documents his surveillance activities by filling out the Daily Backfill inspection Report (Attachment A). This report shall be filled out for each inspector for each shi f t and fill location when inspection is performed. 8.0 ATTACHMENTS 8.1 Daily Backfill inspection Report h 4 O t , = _. _ - _ _ _ .--.~r

i N W-SITP-12 ~ J. JONES CONSTRUCTION COMPANY Atttchment A WATERFORD SES UNIT #3 ggy 7 ? DAILY BACKFILL INSPECTION REPORT Time or Q.V. Inspector Date Shift 1. Fill Placement Area / Location 2. Material released by Ebasco Ebasco QC Signature 3. Spreading and cogaction equipment satisfactory: Yes No i + ace 4. Base to receive fill 3ctnn of debris and compacted Yes No 5. Backfilling done in proper sequence: Yes No 6. Fill material disc-harrowed, if necessary: Yes No N/A I 7. Surface of each lift reasonably smoothe and free of ridges or grooves: Yes No 8. Hauling equipment using different paths: Yes No 9. Till junctions cut three (3) feet minimum: Yes No N/A i

10. Layers compacted to full width:

Yes No i 4

11. Sand and clam shell lift elevation after compactioh.

12. Clay fill lif t elevation af ter cogaction. Fill material lif ts less than 'welve (12) inches in depth in restricted areas: 13. t Yes NO 14. Waterproofing membrane protected during backfilling operation: Yes No i 15. Fill placed during heavy rain or on top of or into standing water: Yes No

16. Material testing is performed and acceptable for each compacted lift:

Yes No

17. Fill layer accepted:

Ebasco QC signature

18. Comments:

l Note: Attach Daily Backfill Inspection Reports to Backfill Density Test designating affected fill number f m. .,,.__..,_.---__._m ___...,__._~m._._._..,_..,,,._..__,_,,,__.,,m_

NOTES Specific: 1. If previously compacted layer has been unworked for two days, the area may require cutting back the surface and proofrolling in order to provide a s satisfactory base for fresh fill. s 2. Material that has become over wet between lifts should be aerated, blended, or removed, and recompacted to the required densities. 3. Debris and organic material is defined as logs, stumps, compressive material or material which, through decomposition or elasticity produce a void in R7 the compacted. material. 4 Shell material may be mLxed with sand or clay; however, it must be mixed with the sand or clay such that it is firmly embedded in and supported by it. 5. Alternate path should be followed to avoid a single spot or pathway through the fill which is significantly harder than the balance of that fill sur-face, it should be leveled prior to placing fresh fill on the area. 6. Fill layers should be slightly sloped away from the structure so that the drainage is toward the unconfined edge of the fill and not into the structure. l l l l t j ,}}