- OPERATING DATA REPORT DOCKET NO. 050-237 DATE August 1, 1983 l j 1 COMPLETED By B. A. Schroeder l TELEPHONE (815) 942-2920 l
OPERATING STATUS .
NOTES i
- 1. Unit Name: Dresden II
- 2. Reporting Period: July. 1983 3 Licensed Thermal Power (NWt): 2,527
- 4. Nameplate Rating (Gross MWe): 828
- 5. Design Electrical Rating (Net MWe): 794
- 6. Maximum Dependable Capacity (Gross MWe): 812
- 7. Maximum Dependable Capacity (Net MWe): 772
- 8. If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:
N/A 9 Power Level to Which Restricted, if Any (Net MWe): N/A
- 10. Reasons For Restrictions, if Any: N/A This Month Yr-to-Date Cumulative.
- 11. Hours in Reporting Period 744 5087 115847
- 12. Number of Hours Reactor Was Critical 408.95 1849.83 88.708.68 13 Reactor Reserve Shutdown Hours 0 0 0
- 14. Hours Generator On-Line 335.30 1647.72 87.467.78 15 Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 726,247 3,285,412 168,744.921 17 Gross Electrical Energy Generated (MWH) 225.425 1.038,748 53,927,014
- 18. Net Electrical Energy Generated.(MWH) 209,311 963.950 50.961.140 19 Unit Service Factor 45.07 32.39 75.50
- 20. Unit Availability Factor 45.07 32.39 75.50
- 21. Unit Capacity Factor (Using MDC Net) 36.44 24.55 56.98
- 22. Unit Capacity Factor (Using DER Net) 35.43 23.87 55.40 23 Unit Forced Outage Rate 54.94 33.64 11.8 6
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
N/A 25 If Shut Down At End Of Report Period, Estimated Date of Startup: N/A l
'N OPERATING DATA REPORT DOCKET NO. 050-249 l
DATE August 1. 1983 )
l COMPLETED BY B. A. Schroeder I i TELEPHONE rgsg gg7_797n i
OPERATING STATUS '
NOTES
- 1. Unit Name: Dresden III
- 2. Reporting Period: July, 1983 3 Licensed Thermal Power (MWt): 2,527
- 4. Nameplate Rating (Gross MWe): R2a 5 Design Electrical Rating (Net MWe): 794
- 6. Maximum Dependable Capacity (Gross MWe): 812 7 Maximum Dependable capacity (Net MWe): 773
- 8. If Changes Occur in Capacity Ratings (items 3 Through 7) Since Last Report, Give Reasons:
N/A 9 Power Level to Which Restricted, If Any (Net MWe): N/A
- 10. Reasons For Restrictions, if Any: N/A l W
This Month Yr-to-Date Cumulbtive.
- 11. Hours in Reporting Period 744 5087 105.432
- 12. Number of Hours Reactor Was Critical 744 4.990.30 81.381.00
- 13. Reactor Reserve Shutdown Hours 0 0 0
- 14. Hours Generator On-Line 744 4,942.55 78.400.52 15 Unit Reserve Shutdown Hours 0 0 0
- 16. Gross Thermal Energy Generated (MWH) 1,520,885 11.151.432 157.413.172 17 Gross Electrical Energy Generated (MWH) 479.931 3.598.957 51.164.08R
- 18. Net Electrical Energy Generated.(MWH) 451.914 3.422.382 48.505.027 19 Unit Service Factor 100 97.16 74 .36
, 20. Unit Availability Factor 100 97.16 74.36
- 21. Unit Capacity Factor (Using MDC Net) 78.58 87.03 59.52
- 22. Unit Capacity Factor (Using DER Net) 76.50 84.73 57.94 23 Unit Forced Outage Rate 0.0 2.84 12.87
- 24. Shutdowns Scheduled Over Next 6 Months (Type, Date, and Duration of Each):
Refueling outage tentatively scheduled to commence September 30, 1983.
- 25. If Shut Down At End Of Report Period, Estimated Date of Startup: N/A
,r "
DOCKET NO. 050-249 UNIT NAME Dresden III UNIT SHUTDOWNS AND POWER REDUCTIONS DATE August 1, 1983 COMPLETED BY B. A. Schroeder TELEPHONE (815) 942-2920 REPORT MONTH July. 1983 METHOD OF LICENSEE CAUSE & CORRECTIVE NO, DATE TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS) DOWN REACTOR 3 REPORT # CODE 4 CODES PREVENT RECURRENCE None 1 2 3 4 F: Forced Reason: Method:
S: Scheduled A-Equipment Failure (Explain) Exhibit G-Instructions for 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee
, C-Refueling 3-Automatic Scram D-Regulatory Restriction Event Report ( ) File 4-Other (Explain) (NUREG-0161)
- E-Operator Training & License Examination F-Administrative G-Operational Error H-Other (Explain)
DOCKET NO. 050-237 UNIT NAME Dresden II UNIT SHUTDOWNS AND POWER REDUCTIONS DATE August 1, 1983 COMPLETED BY B. A. Schroeder TELEPHONE (815) 942-2920 REPORT MONTH Julv. 1983 METHOD OF . LICENSEE CAUSE & CORRECTIVE NO. DATE TYPEl DURATION REASON 2 SHUTTING EVENT SYSTEM COMPONENT ACTION TO (HOURS) DOWN REACTOR 3 REPORT # CODE 4 CODES PREVENT RECURRENCE 8 83-6-20 F 371.5 A 3 -- -- --
Fire in main generator / excitor slip ring area. Repaired.
9 83-7-19 F 37.3 H 1 -- -- --
Contractor dropped welding stick and burned hole in bellows for primary containment. Repaired.
I i
1 2 3 4 F: Forced Reason: Method:
S: Scheduled A-Equipment Failure (Explain) Exhibit G-Instructions for 1-Manual Preparation of Data B-Maintenance or Test 2-Manual Scram Entry Sheets for Licensee C-Refueling 3-Automatic Scram Event Report ( ) File D-Regulatory Restriction 4-Other (Explain) (NUREG-0161)
E-Operator Training & License Examination F-Administrative G-Operational Error H-Other (Explain)
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 050-249 UNIT III DATE August 1, 1983
, COMPLETED BY B. A. Schroeder TELEPHONE (815) 942-2920 MONTH July, 1983 DAY AVERAGE DAILY POWER LEVEL . DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MWe-Net) 1 526 17 615 2 624 18 605 3 681 19 595 4 664 20 602 1
5 629 21 598 i
6 661 22 586 7 657 23 584 8 648 24 597 9 651 25 552 10 646 26 589 11 637 593 27 1
12 634 28 586 13 627 29 580 14 626 30 584 15 623 580-31 16 617 i
I
[
AVERAGE DAILY UNIT POWER LEVEL i
DOCKET NO. 050-237 UNIT II DATE August 1, 1983 COMPLETED BY B. A. Schroeder l TELEPHONE (815) 942-2920 MONTH July, 1983 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net) (MUe-Net) 1 0 17 506 2 0 18 612 3 0 19 613 4 0 20 0 5 0 21 222 6 0 22 640 7 0 23 639 8 0 24 583 9 0 25 698 10 0 26 734 11 0 27 741 12 0 28 661 13 0 749 29 14 0 742 30 15 0 623 31 16 190
,,, r- V- - -' -m- - r - - * * - v =-wv' s-~'+- v'a '--e r
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MAL CT IO.3 EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION
- Fuel Channels, Preventive W.R. #23438 ---
N/A N/A Channels and spring clips installed.
Asssmblies and
- Channel
~ Fasteners
$CRD Accumulator Preventive W.R. #28092 N/A N/A Removed and replaced accumulator.
- 38-35 (K-9)
CRD F-4 (22-15) Preventive W.R. #26954 ---
N/A N/A Adjusted scram inlet valve.
! EPN #CV-2-0305-126
'2-1-C MSIV Preventive W.R. #22063 ---
N/A N/A Rebuild test 3-way and 4-way pilot l EPN #2-203-1C valve.
2-1-D MSIV Preventive W.R. #22064 N/A N/A Rebuild test 3-way and 4-way pilot
!EPN #2-203-ID valve.
2B MSIV-U2 Preventive W.R. #22058 ---
N/A N/A Rebuild test 3-way and 4-way pilot EPN #2-203-2B -
valve.
MSIV-U2 Preventive W.R. #22059 ---
N/A N/A Rebuild test 3-way and 4-way pilot EPN #2-203-2D valve.
MSIV Pilot U2 Preventive W.R. #22060 ---
N/A N/A Rebuild test 3-way and 4-way pilot EPN #2-203-2A valve.
D2-lC MSIV Preventive W.R. #27098 ---
N/A N/A Failed LLRT relap valve. Disassembled, EPN #2-203-1-C repaired and reassembled valve.
U2 MSIV-ID Preventive W.R. #26778 ---
N/A N/A Repaired valve.
EPN #2-203-lD U2 MSIV-lC Preventive W.R. #26777 ---
N/A N/A Repaired valve.
EPN #2-203-lC
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION l
Accumulator Preventive W.R. #27196 ---
N/A N/A Replaced accumulator.
- 34-27 (J-7)
ECCS Initia- Preventive W.R. #26281 ---
N/A N/A Removed and installed ECCS jumpers.
tion Relays Fuse Block Preventive W.R. #27342 ---
N/A N/A Replaced fuse block.
A.A. (Inboard MSIV)
MSIV 203-1B Preventive W.R. #27334 ---
N/A N/A Repaired fuseholder.
EPN #2-203-18 MSIV 203-10 Preventive W.R. #27333 N/A N/A Replaced relay.
, EPN #2-203-10 Accumulator Preventive W.R. #25836 N/A N/A Tightened loose fitting.
- 46-51 Accumulator Preventive W.R. #24741 N/A N/A Rebuilt solenoids.
- 50-35 U2 Rx Bldg./ Preventive W.R. #28355 N/A N/A Replaced springs on magnets.
Turbine Bldg.
Interlock
, Doors HPCI Steam- . Preventive W.R. #27786 ---
N/A N/A Replaced bonnet and internals.
lina Drain Pot, <
EPN #2-2301-1 2-A0V-220-44' Preventive W.R. #28660 ---
N/A N/A Installed new diaphram.
EPN #2-220-44 Ricire. 202-7A Preventive W.R. #27695 N/A N/A Repacked valve.
Valva EPN
- 2-202-7A
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE 11ALFUNCTION EQUIPMENT MAINTENANCE NUMllER CAUSE RESULT CORRECTIVE ACTION Accumulator Preventive W.R. #24739 ---
N/A N/A Rebuilt solenoids.
- 22-31 Accumulator Preventive W.R. #24740 N/A N/A Rebuilt solenoids.
- 58-39 U2 1501-13B Preventive W.R. #28616 ---
N/A N/A Removed and reinstalled bolts and applied Valva locktite.
LPCI Pump Min Preventive W.R. #28144 N/A N/A Replaced cap screw.
Flow M.O.V.
EPN #2-1501-13A D MSL Snubber Preventive W.R. #28657 ---
N/A N/A Replaced snubber.
- 52 Drywall Equip- Preventive W.R. #27201 ---
N/A N/A Opened and closed equipment hatch for m:nt Hatch refuel outage.
A MSL Snubber Preventive W.R. #28670 ---
, N/A N/A Repositioned snubber bracket and rein-
- 42 stalled snubber.
2-1001-5A Preventive W.R. #28715 ---
N/A N/A Tested and adjusted breaker.
Valva Breaker U2 Rx Bldg./ Preventive W.R. #28685 ---
N/A N/A Adjusted magnets and replaced fuse.
Turbina Bldg.
Interlock LPCI CCSW Hx Preventive W.R. #26563 N/A N/A Inspected and repaired torque switch as Outlet 1501- necessary.
3A EPN
- 1501-3A
DRESDEN UNIT 2 SAFCTY RELATED !!AIflTENANCE - JULY, 1983 ,_
NATURE OF LER OR OUTAGE MAI. FUNCTION EQUIPMENT !!AINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Alares 902-5 Preventive W.R. #27520 --->
N/A N/A Rewired alarms to correct terminals.
D-14 cnd 902-5-DIO Snubbers (13) Preventive W.R. #28654 ---
N/A N/A Stroke tested mechanical anubbers.
CRD G-5 Preventive W.R. #26948 --
N/A N/A Replaced solenoid valves.
M02-2301-49 Preventive W.R. #26813 ---
N/A N/A Removed motor gear and key. Replaced.
EPN #2-230!-49 Containment Preventive W.R. #27113 ---
N/A N/A Removed and installed pancake.
Vent Purge Velve 2-1601-63 CRD D-2 (14-07) Preventive W.R. #27054 ---
N/A N/A Removed and replaced CRD D-2.
S/N 991 CRD F-1 Preventive W.R. #27147 ---
N/A N/A Removed and replaced drive.
(22-03)
CRD G-5 (26- Preventive W.R. #27053 N/A N/A Removed and replaced CRD G-5.
- 19) S/N B05 U2 125 VDC Preventive W.R. #26141 U/A N/A Replaced switch.
R13. Bus CRD 18-19 E-5 Preventive W.R. #26845 ---
N/A N/A Replaced accumulator.
D2 HPCI NGU Preventive W.R. #27309 ---
N/A N/A Replaced LVDT and adjusted.
LVDT APRM #1 Preventive W.R. #26829 ---
N/A N/A Readjusted APRM Ch #1
DI ESDEN UNIT 2 SAFETY RET.ATED MAINTEN.WCE - JULY, 1983 NATURE OF MAI, FUNCTION LER OR OUTAGE _ _ _ _ _ .-
EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION R:cire. 202-7A Preventive W.R. #27694 ---
N/A N/A Backseated valve.
Velva HPCI Steam Preventive W.R. #27402 N/A N/A Replaced gasket.
Trip outlet froa Drain Pot i "B" MSIV Prewmative W.R. #27441 ---
N/A N/A Adjusted limit switch.
Accumulator Preventive W.R. #27379 ---
N/A N/A Changed accumulator.
EPN #0301 23 Accumulator Preventive W.R. #27123 N/A N/A Removed and replaced accumulator.
- 14-39 Accumulator Preventive W.R. #26492 N/A N/A Removed and replaced accumulator.
- C-7 CRD 26-03 Preventive W.R. #26659 N/A N/A Tightened packing.
(G-1)
Accumulator Preventive W.R. #24737 N/A N/A Replaced solenoid.
- 06-31 24-48 "B" Top Preventive W.R. #27302 N/A N/A Checked for proper charger operation.
(W:st)
B'2.t terie s U2 Drywell Preventive W.R. #27697 N/A N/A Inspected and repaired.
Equipment Sump Pipe R cire.
V2001-4 Valve to Discharge Vriva V-2001-3 Cls
DRE::DEti UNIT 2 SAFETY 1tELATED IIAlfiff U \NCE - JULY t 1983 IIATURE OF I.ER OR OUfAGF "bI' U" EQUIPMENT MAINTENAt!CE !!U;lnER CAUSE EESULT CORRECTIVE ACTION SDV Level Preventive W.R. #27360 ---
N/A N/A Level transducers readjusted.
X-Ducers 2A 125 Bat- Preventive W.R. #27384 ---
N/A N/A Inspected and repaired trip alarm.
tery Charger M in Steamline Preventive W.R. #26313 ---
N/A N/A Installed and removed jumpers to allow Rad. Monitor H2 addition modification to be installed.
Scram and Iso.
Cir.
Condensate Preventive W.R. #27011 ---
N/A N/A Turned float to free-up magnetrol.
Pump Room Flow Suitch RBM Channel 7 Preventive W.R. #28274 ---
N/A ,
N/A Repaired trip unit on quad trip card.
LPCI Test MCC Preventive W.R. #26333 ---
N/A N/A Replaced two jumpers.
29-4 (BI)
Velve 1501-38B Rad Block Preventive W.R. #28370 ---
N/A N/A Replaced relay 28/101 U2 4KV & 480V Preventive W.R. #23460 ---
N/A N/A Performed routine relay calibration Protective checks.
R21ays Ricirc. Riser Preventive W.R. #26422 ---
N/A N/A Repaired weld defects in overlay welds.
Overlay Re-psir M02 1402-25B Preventive W.R. #28438 ---
N/A N/A Reset breaker settings.
M02- 1402-25B Preventive W.R. #28428 ---
N/A N/A Reset breaker.
EPN #2-1402- l 25B
'l .
DRFJiDEN UNIT 2
.j ^ ,
SAFETY RELATED MAINTENANCE - JULY,_1983 NATURE OF !!M, FUNCTION LER OR OUTAGE EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION
- B MSIV Preventive W.R. #28659 N/A N/A Removed section of tubing with leak and EPN #A02203-1B installed swaglock union.
l U2 125 VDC Preventive W.R. #28407 N/A N/A Located and repaired electrical ground.
Ground '
I MO- 1402-25B Preventive W.R. #27483 ---
N/A N/A Checked for proper heater settings and (25C) heater sizes.
MO- 1402-25A Preventive W.R. #27484 ---
N/A N/A Checked for proper heater settings and heater sizes.
Main Steamline Preventive W.R. #28721 N/A N/A Calibrated and adjusted as needed.
Precs. Switches Channel A Power Preventive W.R. #27218 ---
N/A N/A Replaced power supply with like for like, g Supply Process-
' Man.
2A APRM Flow Preventive W.R. #28280 N/A N/A Repaired flow converter.
Converter A0-2-1601-60 Preventive W.R. #28517 ---
N/A N/A Changed out versa valve. .
EPN #A02-1601-60 I 10% Functional Preventive W.R. #25935 N/A N/A Functionally tested snubbers. l l Test of Mech.
Snubbar l i
MO-2-1201-1 Preventive W.R. #24167 N/A N/A Replaced limitorque on valve. ! '
EPN #MO-2-1201-1 -
2-1301-4 MOV Preventive W.R. #25196 ---
N/A N/A Lubed and adjusted packing.
Valve I' n i
i
- l. -
. - . _ , ._ ...f
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - J ULY , 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Accumulator Preventive W.R. #28522 N/A N/A Replaced accumulator.
- 34-55 Accumulator Preventive W.R. #28529 N/A N/A Adjusted scram outlet valve.
- 18-15 Drive E-4 LPCI II Minimum Preventive W.R. #28258 N/A N/A Replaced valve block.
Flow Switch
- 2 Diesel Preventive W.R. #28713 N/A N/A Performed both mechanical and electrical Gintrator inspections.
Diesel Genera- Preventive W.R. #28723 ---
N/A N/A Replaced solenoid valve.
tor Functional Test Preventive W.R. #26019 N/A N/A Functionally tested snubbers.
of Mschanical Snubbers Mechanical Preventive W.R. #25963 ---
N/A N/A Functionally tested snubbers.
Snubbar Stroke Tact Bid Limit Preventive W.R. #28284 N/A N/A Repaired and adjusted limit switch.
Switch on D.M.S.L U2 250VDC Preventive W.R. #8796 N/A N/A Inspected motor starters and DC valve Motor Starters contactors as listed in work request.
and Contactors (Work package WR8796-1 thru WR8796-36.)
R cire. Riser Preventive W.R. #25401 ---
N/A N/A Performed weld overlays on recirc. riser Inlet Welds (E,A,H,F,J,K) inlet pipe walds per work package.
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION 4KV 2B LPCI, Preventive W.R. #27237 ---
N/A N/A Installed permanent ground wire on WYE 2A LPCI, 2A connected current transformer.
Core Spray U2 Rx Prot. Preventive W.R. #27793 ---
N/A N/A Investigated and readjusted as necessary.
Sys. M-G Set 2B MO 1402-25A Preventive W.R. #28506 N/A N/A Determined if it was the correct overload relay. Found correct.
MO 1402-25B Preventive W.R. #28505 ---
N/A N/A Determined if it was the correct overload (25C) relay. Found correct.
MSIV Fuse Preventive W.R. #27715 ---
N/A N/A Inspected blown fuse problem. Replaced bad wire.
LPRM'c Preventive W.R. #24868 ---
N/A N/A Completed installation and inspection of LPRM's for EOC 8.
Spira MSIV Preventive W.R. #27154 N/A N/A Repaired MSIV pilot blocks.
Pilot Blocks MO 2-205-2-4 Preventive W.R. #24163 ---
N/A N/A Replaced limitorque.
EPN #2-205-2-4 CRD Press. Sw. Preventive W.R. #28145 ---
N/A N/A Replaced defective pressure switch.
10-47 EPN #2-305-130 LPRM 08-33B Preventive W.R. #24750 ---
N/A N/A Inspected and repaired.
APRM 6 Control Blades Preventive W.R. #25363 ---
N/A N/A Replaced four control blades.LPRM 24-41C Preventive W.R. #20476 ---
N/A APRM Ch # 1 N/A Inspected and repaired.
DRESDEN UNIT 2 _
SAFETY RELATED MAINTENANCE - JULY. 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION IRM #12 Preventive W.R. #27400 N/A N/A Inspected and repaired as necessary.
[ R cording Preventive W.R. #27598 N/A N/A Connected and disconnected test cables Equipment from APRM and LPRM tests.
t IRM Ch #11 Preventive W.R. #24637 N/A N/A Inspected and repaired IRM indication problem.LPRM 32-17B Preventive W.R. #27081 N/A N/A Investigated LPRM indication problem and Ch #1 repaired.
Chart Recorder Preventive W.R. #27597 N/A N/A Temporarily installed chart recorder (for LPRM and APRM's) for tests.
Removed same.
902-5 Alarms Preventive W.R. #27521 ---
N/A N/A Inspected and repaired as necessary.
. A-12 and D-10 LPRM 24-57A Preventive W.R. 22872 N/A N/A Inspected and repaired.
(APRM #1) .LPRM 24-57B Preventive W.R. #25033 ---
N/A N/A Inspected and repaired.
APRM 2 Cable Connector Preventive W.R. #25177 N/A N/A Replaced cable connector.56-25A LPRM
, EPN 56-25A APRM Ch #4 Rod Preventive W.R. #27667 ---
N/A N/A Recalibrated APRM #4.
! Block LPRM 48-25C Preventive W.R. #27365 ---
N/A N/A Inspected and repaired.
(#4) EPN
- 48-25C
DRESDEN UNIT 2 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION LPRM 40-57 1A Preventive W.R. #26559 N/A N/A Inspected and repaired.
APRM #4 Preventive W.R. #27632 ---
N/A N/A Recalibrated APRM #4.
IB Inboard Preventive W.R. #27169 N/A N/A Installed new solenoid manifold MSIV assembly.
Control Rod Preventive W.R. #27599 ---
N/A N/A Adjusted scram inlet and outlet valve.
Driva F-7 (22-27)
MO 2-2201-1 Preventive W.R. #24169 N/A N/A Replaced limitorque operator, wired and EPN #2-2201-1 set limits.
IRM # 15 Preventive W.R. #27399 ---
N/A N/A Investigated and repaired as necessary.
2C T.I.P. Ball Preventive W.R. #07963 ---
N/A N/A Replaced ball valve.
Velva Limit Switch SRM #21 Preventive W.R. #28176 N/A N/A Inspected and repaired as necessary.
B Fatdwater Preventive W.R. #27580 ---
N/A N/A Replaced bonnet seal ring valve.
Lins Check Vcive Icoletion Preventive W.R. #27586 ---
N/A N/A Tightened pipe cap.
Condan er Test Vc1vac U2 MSIV l-B Preventive W.R. #26776 ---
N/A N/A Repaired valve.
EPN #2-203-1B
DRESDEN UNIT 2 SAFETY RELATED MAINT_ENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MAI.FUggTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Vacuum Breaker Preventive W.R. #27226 ---
N/A N/A Repacked vacuum breakers.
HPCI Drain Preventive W.R. #20234 N/A N/A Replaced control switch.
Valva MO 150!-20B Preventive W.R. #28785 N/A N/A Replaced receptacle.
Local MO Con-trol Valve Station
DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION SRM #22 & 24 Preventive W.R. #26252 ---
N/A N/A Repaired dual alarm card.
- 3 Diesel Preventive W.R. #28107 ---
N/A N/A Performed annual inspection.
Generitor 3C LPCI Pump Preventive W.R. #28592 ---
N/A N/A Replaced 1/2 x 5" threaded nipple.
EPN #3C-1501 CRD Accumu- Preventive W.R. #28722 ---
N/A N/A Replaced CRD accumulator, lator (N-6) 50-23 PS504D Preventive W.R. #26727 ---
N/A N/A Replaced PS504D.
EPN #PS5G4D D/U Pressure Preventive W.R. #27304 ---
N/A N/A Assured that D/W pressure sensing lines Sensing Lines were open.
- 3 250 Volt Preventive W.R. #24729 N/A N/A Verified factory setting of voltage trip Bittery and reset setpoints.
Charger D MSL Rad Preventive W.R. #28812 ---
N/A N/A Replaced log rad monitor. Calibrated it Monitor as required by DIS 1700-1.
LPCI 28A Preventive W.R. #28603 ---
N/A N/A Replaced faulty auxiliary contact.
Vr.lva EPN #3-1501-20A LPCI 3-1501- Preventive W.R. #28594 N/A N/A Inspected and repaired as necessary.
3B U3 B ATWS Preventive W.R. #26348 ---
N/A N/A Found and replaced a shorted neon light-Channel bulb on inseries light.
DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Qurd Cities Preventive W.R. #27478 ---
N/A N/A Rebuilt valve.
S faty Valve Qucd Cities Preventive W.R. #27480 N/A N/A Rebuilt valve.
Rx Safety Vciva Quid Cities Preventive W.R. #27479 N/A N/A Rebuilt valve.
S:faty Valve Qurd Cities Preventive W.R. #27481 ---
N/A N/A Rebuilt valve.
Rx Safety Velve Stroka Test Preventive W.R. #26169 ---
N/A N/A Stroke tested snubbers, of Mechanical Snubbar MCC 39-1 J5 Preventive W.R. #26307 ---
N/A N/A Removed sample of # 12 wire for environ-Safety Sys. ment testing.
Jockey Pump All LPRM's Preventive W.R. #27409 ---
N/A N/A Performed plateaus on all LPRM's to remove "whishers".
Pipe Hanger Preventive W.R. #26774 N/A N/A Replaced nut and bolt on hanger.
MCC 38-1 (H3) Preventive W.R. #26308 N/A N/A Rcmoved a ssmple of wire for testing.
Sptre Skinner Preventive W.R. #25596 ---
N/A N/A Discarded uniflow valve.
Valva 2301-31 LPRM 32-17C Preventive W.R. #27279 ---
N/A N/A Inspected LPRM 32-17C.
DRESDEN UNIT 3 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNGTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION LPCI & Core Preventive W.R. #27156 ---
N/A N/A Inspected internals, LPCI and core spray Spray Press. pressure switch.
Sw.LPRM 40-41C Preventive W.R. #27320 N/A N/A Inspected and repaired as necessary.
LPRM 4B 32-17 Preventive W.R. #27183 N/A N/A Inspected and repaired as necessary.
APRM 1 Refuel Grapple Preventove W.R. #28889 ---
N/A N/A Replaced spring.
DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Control Rod Preventive W.R. #27072 ---
N/A N/A Leak tested 3 CRD's.
Drives Spare Safety Preventive W.R. #22883 ---
N/A N/A Rebuilt and tested safety valve.
Valve EPN #203 Spare Safety Preventive W.R. #22884 ---
N/A N/A Rebuilt and tested safety valve.
Valve EPN #203 Spare Safety Preventive W.R. #22886 ---
N/A N/A Rebuilt and tested safety valve.
Valve EPN #203 Stetion Preventive W.R. #27956 ---
N/A N/A Performed preventive maintenance.
Batteries Main Steamline Preventive W.R. #26500 ---
N/A N/A Completed functional check.
Log Rad Moni-tor Spare Main Steamline Preventive W.R. #26972 ---
N/A N/A Repaired and stored.
Log Rad Moni-tor Spare Elec- Preventive W.R. #25300 ---
N/A N/A Rebuilt spare electromatic.
tromatic 2/3 250 Volt Preventive W.R. #24728 ---
N/A N/A Adjusted trip.
Battery Charger A LPCI Loop Preventive W.R. #28595 ---
N/A N/A Inspected and repaired.
Flow Indica-tion
DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MALFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION MO 1402-25B Preventive W.R. 27486 N/A N/A Changed dial position to proper setting.
(25C)
MO 1402-25A Preventive W.R. #27485 ---
N/A N/A Changed dial position to proper setting.
2D MSL Log Preventive W.R. #28824 N/A N/A Repaired and installed 2D monitor.
Rad Monitor Spare Electro- Preventive W.R. #22882 ---
N/A N/A Rebuilt spare electromatic, matic EPN #203 Spare Versa Preventive W.R. #25452 ---
N/A N/A Rebuilt spare versa valve.
Valve SBGTS B Train Preventive W.R. #27204 ---
N/A N/A Removed 2 charcoal test canisters.
Spire MSIV Preventive W.R. #26980 ---
N/A N/A Rebuilt (3) pilot disc. Cleaned MSIV Pilot Disc stem.
and Stem 2/3 250VDC Preventive W.R. #28379 ---
N/A N/A Made float adjustment to 261 VDC with Battery charger on U3 batteries.
Chrrger Safety Related Preventive W.R. #28236 ---
N/A N/A Inspected ring flanges and cap screws.
Control Rod Drive Parts 2/3 DG Con- Preventive W.R. #26593 ---
N/A N/A Replaced lube oil pump, tinuous T ube Oil Pump
DRESDEN UNIT 2/3 SAFETY RELATED MAINTENANCE - JULY, 1983 NATURE OF LER OR OUTAGE MLFUNCTION EQUIPMENT MAINTENANCE NUMBER CAUSE RESULT CORRECTIVE ACTION Spare Safety Preventive W.R. #22885 N/A N/A Rebuilt and tested safety valve.
Valve 2/3 Diesel Preventive W.R. #27243 ---
N/A N/A Performed quarterly inspection.
Generator
7
SUMMARY
OF OPERATING EXPERIENCE UNIT TWO l JULY, 1983 07-01 to 07-16 Repairs continued on Unit 2's main generator collector rings as a result of last months arcing and resultant fire. After testing the main generator / excitor the unit was brought critical, the generator then tested while turning. Finding no additional problems, the generator I was placed on the grid.
07-16 to 07-19 The unit reached a power level of 756 MWe when it was i
found that a contractor had burned a hole in a bellows seal for the primary containment system. The unit was manually shutdown and cooled down. After repairs the unit was once again placed back in service.
- 07-19 to 07-31 The unit operated the remainder of the month (with normal i
r power reductions on weekends for surveillances) with a capacity factor of 36.33% and an availability of 45.07%.
4 i
I i
, - - w -m. -- ~ -- , ,ys. -w -,w,,n ~ w .--, -.- ,n-,-- ~r - -- . - - - ~ v .-,
I
SUMMARY
OF OPERATING EXPERIENCE ,
l UNIT THREE JULY, 1983
- 07-01 to 07-31 Unit 3 entered the month operating at a power level of 431 MWe and operated continuously throughout the entire month (with normal power reductions on weekends for surveillances), reaching a power level of 729 MWe with a
! capacity factor of 77.53% and an availability of 100%.
i i
j i
4 l
j s
. . _ - . . - . - , -- _ . . , + , - . . . - -,w- r .,4. ,--. --, . .,_ ,...- , . ,7 .
ym-..m-
Commonwealth Edison Dresden Nuclear Power St ti;n R.R. #1 Morris, Illinois 60450 Telephone 815/942-2920 August 1, 1983 DJS LTR: 83-753 Director, Office of Inspection and Enforcement United States Nuclear Regulatory Commission Washington, DC 20555 Attention: Document Control Desk
Dear Sir:
Enclosed please find Dresden Station's operating data for last month. This information is supplied to your office per the instruc-tions set forth in Regulatory Guide 1.16.
Sincerely,
'N .[h6 N 8 D. J. Scott 5(,
Station Superi endent Dresden Nuclear Power Station DJS: BAS:hjb Enclosure cc: Region III, Regulatory Operations, U.S. NRC Chief, Division Nuclear Safety, State of IL U.S. NRC, Document Management Branch Nuclear Licensing Administrator i Nuc. Sta. Div. Vice Pres.
Statistical Research l Manager, Tech. Serv. Nuc. Sta.
l Tech. Staff EA On-Site NRC Inspector Sta Nuc. Eng. Dept.
PIP Coordinator - Sta. Nuc.
Comptro11er's Office File /NRC Op. Data File /rumerical INPO Records Center Ifl
- - _ _ _ _