= - - .. n - - . - -.: . . . _ _ _

_ _ _ ;: zz i .:

i APPENDIX A -

NOTICE OF VIOLATION Long Island Lighting Company Docket.No. 50-322

i. [
! This refers to the inspection conducted by representatives of the Region

! I (Philadelphia) office at the Shoreham Nuclear Power Station, Shoreham, j New York, of activities authorized by NRC Construction Pennit CPPR-95.

! During this inspection conducted on September 26-29, 1978, the following i apparent item of noncompliance was identified.

'! 10 CFR 50, Appendix B, Criterion V requires, in part, that "Activi-I

.] ties affecting quality shall be prescribed by documented instruc- '

p' tions, procedures,...and shall be accomplished in accordance with these instructions, procedures. .. ." The Shoreham Nuclear Power i

Station FSAR Section 17.1.SA requires that suppliers of safety related materials and services are respons.ible for imposing the

~

e j

above requirements on their internal ope' rations.  ;

l The implementing S&W Quality Assurance Program Manual for Shoreham, t Section 9, describes that the welding procedure specifications

...have been qualified in accordance with applicable codes and  ;

standards and are the written procedures followed for erection work  !

performed by S&W field forces." l S&W Welding Procedure Technique Shaet W70G Revision 0 is prequali-fied in accordance with applicable code AWS 01.1-72 for fillet i

welds in Skewed Tee Joints of angles greater than 60 degrees.  !

j m i IJ Contrary to the above, on September 29, 1978, S&W field forces l 1 performed welding on a Skewed Tee Joint of angle S4 degrees, on the  !

i rectangular tubular pipe support number lEll-PSA-072 of the residual  ;

! heat removal system, using non-applicable procedure W70G which was not l l prequalified for the weld joint configuration. ,

a  ;

This item is an infraction.