Sample ID:
142449 Type: RLSSS Type Detail: SAND
==
Description:==
140528BD 19 STAR 19-20 Dirt Sample
[Common-[
Resp Org: P4000 - PROJECT MANAGEMEr
Contact:
COOPER, TERRY L Reference ID:
Comments: COUNT TO MDA Reviewed: DYNES, WILLIAM J Comments:
Origin -I Health Physics Sample Records Status: APPROVED Cross Ref Sample ID:
Survey No:
Accounting Subcode:
Unknown Mat:
NO Date: 05/30/14 09:01 Mat. SizeNolume:
2221 GRAMS Docmnt/MO/Act #:
Proposed Ship Date: 00/00/00 00:00
==
Description:==
STAR 19 SOIL SAMPLE I Collection Sample Tech:
DYNES, WILLIAM J Tritium Req:
No Instructions:
Comments:
COUNT TO MDA I RLsss I Exempt:
No Chem Notification:
No Offsite Analysis:
No Container Surveyed:
No Container Evaluated:
Yes
[Location[
Unit: NON-UNIT RE Stored By:,
Sample Loe:
Other:
Material Loe:
06/18/201411:55 Area: MS Sample Date: 05/29/14 08:15 Sample SizeNolume: 2221 GRAMS Evaluated:
No State Permit:
No Effluent Permit:
No Cleared For Release:
Yes Form 212 Ready:
~
Elev: 100 Room:
Depth: 3" (in.)
Equip ID:
Date: 00/00/00 00:00 Rasterized: r Priority: N Hazardous Mat:
NO Count Time:
900 (secs.)
Page 1 of 3
Health Physics Sample Records Sample ID:
142449 Type: RLSSS Type Detail: SAND Status: APPROVED
==
Description:==
140528BD 19 STAR 19-20 Dirt Sample
!Analysis I Geometry MCAID Quant.
Units Method FP/AP Lab Analysis By C _ 1 L _marinelli_ sand_
30297 2221 GR
.000 PARK, MICHAEL C Isotope Mode Activity Activity Uncert.
LLD/MDA
%Abund.
Atom. No.
Comments 0
K-40 NT 0.000011311.16E-6 r
69.696%
40 0
TL-208 NT 2.656E-7 7.26E-8 r
1.637%
208 0
PB-212 NT 8.025E-7 9.01E-8 r
4.945%
212 0
Bl-214 NT 2.14E-7 1.031E-7 r
1.319%
214 0
PB-214 NT 7.054E-7 2.321E-7 r
4.347%
214 0
RA-224 NT 2.036E-6 8.1E-7 r
12.546%
224 0
AC-228 NT 8.942E-7 1.68E-7 r
5.510%
228 0
BE-7 AP 6.2356E-7 Iv" 0.000%
7 0
0.000%
54 0
MN-56 AP 9.487E-8 w
0.000%
56 0
C0-57 AP 8.1745E-8
~
0.000%
57 0
C0-58 AP 9.1172E-8 0.000%
58 0
C0-60 AP 8.4669E-8 0.000%
60 0
SB-124 AP 6.6535E-8
~
0.000%
124 0
SB-125 FP 2.4056E-7 Iv' 0.000%
125 0
CS-134 FP 6.2965E-8
~
0.000%
134 0
~
0.000%
137 Analysis Review Re-Analize:
No Lie Rad Mat Present:
No Reviewed: COOPER, TERRY L HP Notified Name:
Hp Eng Rvw Reqd:
Yes Comments:
06/18/201411:55 Rad Mat Present:
Yes Rasterized: r Date Mod ID Mod Date 06/02/14 09:58 Mod Id Mod Date Date: 06/10/1410:21 Page2 of 3
Sample ID:
142449 Type: RLSSS Type Detail: SAND
==
Description:==
140528BD 19 STAR 19-20 Dirt Sample Review/Approve I Reviewed: COOPER, TERRY L Comments:
Disposition: OTHER Remarks:
Approved: COOPER, TERRY L Comments:
06/18/201411:55 Health Physics Sample Records Status: APPROVED Rasterized: r HP En_g_ Review Date: 06/10/14 10:21 Disposition Result Sample contains only natural isotopes Final Approval Date: 06/10/14 10:21 Page 3 of 3
SONGS HEALTH PHYSICS REPORT 2-JUN-20:4 09:55
- Title
>>>>> SAMPLE PARAMETERS<<<<<
140528BD 19 STAR 19-20 DIRT SAMPLE
- .ID 30297 Acquisition date: 2-JUN-2014 09:52:37. *
- Start Time:
- Stop Time:
- Quantity
- Geometry 2-JUN-2014 09:52:00.
2-JUN-2014 09:52:00.
Counting System 2.22100E+03 GR IHPS Sample Number:
C lL marinelli_sand_l Analysis Library Operator: MICHAEL PARK U2GSP 142449 HP NATURAL
>>>>> C #41-TP11750A PARAMETERS<<<<<
- Elapsed Live Time
- Elapsed Real Time
- Deadtime
- Activity Mult Factor:
- Half Life Ratio 0 00:03:00.38 0 00:03:00.45 0.0%
1.00000E+OO 8.00000 Calibration Energy Offset Energy Slope Energy Tolerance:
Sensitivity 1-JUN-2014 20:29:
-1.46898E-01 4.99817E-01
- 1. 00000 5.00000 Post-NID Peak Search Report It Energy Area Bkgnd FWHM Channel Left Pw %Err Fit Nuclides 1
77.24 35 63 0.99 154.82 152 8 43.2 2.39E+OO BI-214 PB-212 PB-214 3
238.58 106 14
- 1. 08 477.61 471 18 11. 2 1.99E+OO PB-212 3
241.60 24 7
- l. 50 483.66 471 18 39.8 RA-224 PB-214 1
295.23 35 22
- 1. 73 590.94 586 12 32.9 1.67E+OO PB-214 1
338.37 27
- 4
- 1. 62 677.26 673 8 22.3 2.93E-01 AC-228 1
351.83 38 18
- 1. 30 704.17 700 10 26.6 1.59E+OO PB-214 1
583.25 25 5
- 1. 04 1167.11 1163 10 27.3 6.31E-01 TL-208 1
609.13 15 14
- 1. 74 1218.89 1215 8 48.2 1. 30E+OO BI-214 1
911. 06 29 0
- 1. 86 1822.83 1818 9 18.8 8.17E-01 AC-228 1
968. 83 23 3
- 2. 62 1938.38 1933 11 24.1 7.56E-01 AC-228 1
1460.57 99 0
- 1. 93 2921.86 2916 11 10.3 1.81E+OO K-40
Summary of Nuclide Activity Sample ID : 30297 Acquisition date Page :
2 2-JUN-2014 09:52:37 Total number of lines in spectrum 11 Number of unidentified lines 0
Number of lines tentatively identified by NID 11 100.00%
Nuclide Type : natural Uncorrected Decay Corr Decay Corr 1-Sigma Nuclide Hlife Decay uCi/GR uCi/GR 1-Sigma Error
%Error Flags K-40 1.28E+09Y
- 1. 00 1.131E-05 l.131E-05 0.116E-05 10.25 A
TL-208 3.05M
- 1. 59 1.673E-07 2.656E-07
- 0. 726E-07 27.33 A
PB-212 10.64H
- 1. 00 8.006E-07 8.025E-07 0.901E-07
- 11. 22 A
BI-214 19.90M
- 1. 08 1.989E-07 2.140E-07 1.031E-07 48.17 A
PB-214
- 26. SOM
- 1. 06 6.679E-07 7.054E-07 2.321E-07 32.90 A
RA-224 3.66D
- 1. 00 2.036E-06 2.036E-06 O.SlOE-06 39.75 A
AC-228 6.13H
- 1. 00 8.906E-07 8.942E-07 l.680E-07 18.79 A
Total Activity 1.607E-05 1.623E-05 Grand Total Activity :
1.607E-05
- 1. 623E-05 Flags: "K" Keyline not found "M"
Manually accepted "E"
Manually edited "A"
Nuclide specific abn. limit
Unidentified Energy Lines Sample ID : 30297 None Flags: "T" Tentatively associated Page :
3 Acquisition date 2-JUN-2014 09:52:37
Interference Report Sample ID : 30297 No interference correction performed Acquisition date Page :
4 2-JUN-2014 09:52:37
Nuclide Line Activity Report Page :
5 Sample ID : 30297 Acquisition date 2-JUN-2014 09:52:37 Nuclide Type: nalural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area
%Abn
%Eff uCi/GR uCi/GR
%Error K-40 1460.83 99 10.67*
5.560E-01 1.131E-05 1.131E-05 10.25 TL-208
- 72. 80 2.14 1.486E+OO Line Not Found ------
74.97 ------
3.60 l.577E+OO Line Not Found ------
84.79 ------
- 1. 27 1.917E+OO Line Not Found ------
252.45 ------
0.80 2.004E+OO Line Not Found ------
277.28 6.80 1.917E+OO Line Not Found ------
510.61 ------
- 21. 60 1.298E+OO Line Not Found ------
583.02 25 86.00*
1.157E+OO l.673E-07 2.656E-07 27.33 763.06 ------
- 1. 64 8.934E-01 ------
Line Not Found ------
860.30 ------
12.00 7.922E-01 ------
Line Not Found ------
PB-212 74.81 ------
10.50
- 1. 570E+OO Line Not Found ------
77.11 35 17.70 1.666E+OO 7.949E-07
- 7. 968E-07 43.18 87.19 ------
6.27
- 1. 983E+OO Line Not Found ------
90.13 ------
- 1. 86 2.055E+OO Line Not Found ------
115. 12 ------
0.59 2.376E+OO Line Not Found ------
238.58 106 43.60*
2.055E+OO 8.006E-07 8.025E-07 11.22 300.03 ------
3.34 1.843E+OO Line Not Found ------
BI-214 76.86 35 0.58
- 1. 666E+OO 2.426E-05
- 2. 611E-05 43.18 79.29 ------
0.97 1.741E+OO Line Not Found ------
609.31 15 46.10*
- 1. 112E+OO l.989E-07 2.140E-07 48.17 665.44
- 1. 56 1.023E+OO Line Not Found ------
7 68. 35 4.88 8.873E-01 Line Not Found ------
806.16 ------
- 1. 23 8.454E-01 Line Not Found ------
934.04 3.16 7.310E-01 ------
Line Not Found ------
1120. 27 15.00 6.242E-01 ------
Line Not Found ------
1155.18 ------
- 1. 69 6.105E-01 ------
Line Not Found ------
1238.11 ------
5.92 5.846E-Ol ------
Line Not Found ------
1280.95 ------
- 1. 4 7 5.747E-01 Line Not Found ------
1377.66 ------
4.02 5.602E-01 Line Not Found ------
1385. 30 0.78 5.595E-01 ------
Line Not Found ------
1401. 48
- 1. 39 5.583E-01 ------
Line Not Found ------
1407.97 ------
2.48 5.578E-01 ------
Line Not Found ------
1509.22 ------
2.19 5.568E-01 Line Not Found ------
1583.22 ------
0.72 5.628E-01 Line Not Found ------
1661. 26 1.15 5.753E-01 Line Not Found ------
1729.58 ------
3.05 5.918E-01 ------
Line Not Found ------
1764.49 ------
15.90 6.023E-01 Line Not Found ------
1847.41 2.12 6.331E-01 ------
Line Not Found ------
PB-214 53.17 ------
1.10 5.203E-01 ------
Line Not Found ------
74.81 ------
6.52 1.570E+OO Line Not Found ------
77.11 35
- 11. 00 l.666E+OO 1.279E-06 1.351E-06 43.18 87.19 ------
3.88 1.983E+OO Line Not Found ------
90.13 ------
1.15 2.055E+OO Line Not Found ------
241. 92 24 7.46 2.044E+OO
- 1. 064E-06 1.124E-06 39.75 258.94 0.55 1.981E+OO Line Not Found ------
295.09 35 19.20*
1.858E+OO 6.679E-07 7.054E-07 32.90 351. 87 38 37.10
- 1. 686E+OO 4.124E-07 4.356E-07 26.63 785.83
- 1. 09 8.674E-01 ------
Line Not Found ------
839.00 ------
0.59 8.122E-01 ------
Line Not Found ------
Nuclide Line Activity Report (continued)
Page :
6 Sample ID : 30297 Acquisition date 2-JUN-2014 09:52:37 Nuclide Type: natural Uncorrected Decay Corr 1-Sigma Nuclide Energy Area
%Abn
%Eff uCi/GR uCi/GR
%Error RA-224 83.79 ------
0.20 l.887E+OO Line Not Found ------
240.76 24 3.90*
2.044E+OO 2.036E-06 2.036E-06 39.75 AC-228
- 89. 96 3.40 2.051E+OO Line Not Found ------
93.35 ------
5.60 2.124E+OO Line Not Found ------
99.55 ------
- 1. 30 2.229E+OO Line Not Found ------
105.36 ------
2.00 2.301E+OO Line Not Found ------
108.99 ------
0.67 2.335E+OO Line Not Found ------
129.03 ------
2.90 2.414E+OO Line Not Found ------
153.89 ------
0.84 2.377E+OO Line Not Found ------
209.39 ------
4.10 2.168E+OO Line Not Found ------
216.24 0.80 2.141E+OO Line Not Found 270.26 ------
3.80 1.941E+OO Line Not Found ------
328.07 ------
3.50 1.756E+OO Line Not Found ------
338.42 27 12.40
- 1. 725E+OO 8.486E-07 8.520E-07 22.30 340.94 ------
0.52
- 1. 718E+OO Line Not Found ------
409.62 2.20 l.531E+OO Line Not Found ------
463.10 ------
4.60
- 1. 401E+OO Line Not Found ------
562.65 ------
- 1. 01 l.195E+OO Line Not Found ------
581.52 ------
3.00 1.160E+OO Line Not Found ------
72 6. 63 0.87 9.382E-01 Line Not Found ------
755.28
- 1. 32 9.027E-01 Line Not Found ------
772.28
- 1. 09 8.827E-01 Line Not Found ------
782.12 0.59
- 8. 716E-01 Line Not Found ------
794.79 ------
- 4. 60 8.576E-Ol Line Not Found ------
830.59 ------
0.63 8.205E-01 Line Not Found ------
835.60 ------
- 1. 71 8.155E-01 Line Not Found ------
840.44 0.94 8.l08E-01 Line Not Found ------
904.29 ------
0.89 7.542E-01 Line Not Found ------
911.16 29 29.00*
7.488E-01 8.906E-07 8.942E-07 18.79 964. 64 5.80 7.091E-01 ------
Line Not Found ------
968. 97 23 17.40 7.062E-01 l.282E-06 l.288E-06 24.05 1246.60 ------
0.57 5.825E-01 ------
Line Not Found 1459.19
- 1. 06 5.560E-Ol ------
Line Not Found ------
1496.00 ------
- 1. 05 5.563E-01 Line Not Found ------
1501. 44 0.58 5.565E-01 ------
Line Not Found ------
1580.30 ------
- 0. 71 5.624E-01 Line Not Found ------
1588.23 ------
3.60 5.634E-Ol Line Not Found ------
1630.47 ------
- 1. 95 5.696E-01 Line Not Found ------
1638.10 ------
0.54 5.709E-01 Line Not Found ------
Flag: "*" = Keyline
Minimum Detectable Activity Report Page :
7 Sample ID 30297 Acquisition date 2-JON-2014 09:52:37 Bckgnd Energy MDA Nuclide Sum (keV)
(uCi/GR)
BE-7
- 5.
477.61 6.2356E-07 MN-54
- 4.
834.83 9.9459E-08 MN-56
- 3.
846.81 9.4870E-08 C0-57
- 23.
122.06 8.1745E-08 C0-58
- 3.
810.79
- 9. 11 72E-08 C0-60
- 1.
1173.24 8.4669E-08 SB-124
- 0.
1690.98 6.6535E-08 SB-125
- 8.
427.88 2.4056E-07 CS-134
- 3.
604. 71 6.2965E-08 CS-137
- 5.
661. 66 l.0084E-07