Sample ID:

142495 Type: RLSSS Type Detail: SAND

==

Description:==

140605BD06 SOUTH LAY DOWN# 12 lg_Qmm~

Resp Org: P4000 - PROJECT MANAGEMEr

Contact:

COOPER, TERRY L Reference ID:

Comments: COUNT TO MDA Reviewed: DYNES, WILLIAM J Comments:

LQrtgin I Health Physics Sample Records Status: APPROVED Cross Ref Sample ID:

Survey No:

Accounting Subcode:

Unknown Mat:

NO Date: 06/06/14 09:38 Mat. SizeNolume:

1883 GRAMS Docmnt/MO/Act #:

Proposed Ship Date: 00/00/00 00:00

==

Description:==

SOUTH LAY DOWN #12 I Collection Sample Tech: DYNES, WILLIAM J Tritium Req:

No Instructions:

COUNT TO MDA Comments:

COUNT TO MDA lkLsssl Exempt:

No Chem Notification:

No Offsite Analysis:

No Container Surveyed:

No Container Evaluated:

Yes LLocationl Unit: NON~UNIT RE Stored By:,

Sample Loe:

Area: MS Other: COUNT TO MDA Material Loe:

06/19/2014 10:05 Sample Date: 06/05/14 09:20 Sample SizeNolume: 1883 GRAMS Evaluated:

No State Permit:

No Effluent Permit:

No Cleared For Release:

Yes Form 212 Ready:

f\\7' Elev: 100 Room:

Depth:

(in.)

Equip ID:

Date: 00/00/00 00:00 Rasterized: r Priority: N Hazardous Mat:

NO Count Time:

900 (secs.)

Page 1 of3

Sample ID:

142495 Type: RLSSS Type Detail: SAND

==

Description:==

140605BD06 SOUTH LAY DOWN# 12

[AnalysisJ Geometry. __ _

MCA ID Quant.

Units Method B_ 1 L_marinelli_sand_

30392 1883GR Isotope Mode Activity Activity Uncert.

LLD/MDA 0

K-40 NT 0

PB-212 NT 0

Bl-214 NT 0

PB-214 NT 0

BE-7 AP 0

MN-54 AP 0

MN-56 AP 0

C0-57 AP 0

C0-58 AP 0

C0-60 AP 0

SB-124 AP 0

SB-125 FP 0

CS-134 FP 0

CS-137 FP 1Analysis-Review I

~-~-----*-----

0.000011811.45E-6 5.708E-7 1.346E-7 6.045E-7 1.45E-7 7.827E-7 1.777E-7 8.8749E-7 1.2811E-7 9.2536E-8 7.8648E-8 1.5594E-7 4.8849E-8 1.2513E-7 3.9241E-7 1.0923E-7 1.2077E-7 r

IV IV IV IV IV w w

IV w

IV Health Physics Sample Records Status: APPROVED FP/AP Lab Anal¥_sis By

.000 NEESE, DAVID J

%Abund.

Atom. No.

Comments 85.779%

40 4.146%

212 4.391%

214 5.685%

214 0.000%

7 0.000%

54 0.000%

56 0.000%

57 0.000%

58 0.000%

60 0.000%

124 0.000%

125 0.000%

134 0.000%

137 Re-Analize:

No Lie Rad Mat Present:

No Reviewed: COOPER, TERRY L HP Notified Name:

Hp Eng Rvw Reqd:

Yes Comments:

06/19/2014 10:05 Rad Mat Present:

Yes Rasterized:

Date Mod ID Mod Date 06/06/14 20:58 Mod Id Mod Date Date: 06/11/14 06:48 Page 2 of 3

Sample ID:

142495 Type: RLSSS Type Detail: SAND

==

Description:==

140605BD06 SOUTH LAY DOWN# 12

[ Review/Approve I Reviewed: COOPER, TERRY L Comments:

Disposition: OTHER Remarks:

Approved: COOPER, TERRY L Comments:

06/19/2014 10:05 Health Physics Sample Records Status: APPROVED Rasterized: r HP Review Date: 06/11/14 06:49 Disposition Result: Sample contains only natural isotopes Final Approval Date: 06/11/14 06:49 Page 3 of 3

SONGS HEALTH PHYSICS REPORT 6-JUN-2014 20:56

  • Title

>>>>> SAMPLE PARAMETERS<<<<<

140605BD06 SOUTH LAY DOWN# 12

  • ID 30392 Acquisition date: 6-JUN-2014 20:53:09. *
  • Start Time:
  • Stop Time:
  • Quantity
  • Geometry 6-JUN-2014 20:53:00.

6-JUN-2014 20:53:00.

Counting System 1.88300E+03 GR IHPS Sample Number:

B lL marinelli sand 1 Analysis Library Operator: DAVID NEEBE U2GSP 142495 HP NATURAL

>>>>> B #42-TP11663A PARAMETERS<<<<<

  • Elapsed Live Time
  • Elapsed Real Time
  • Deadtime
  • Activity Mult Factor:
  • Half Life Ratio 0 00:03:00.42 0 00:03:00.46 0.0%

1.00000E+OO 8.00000 Calibration Energy Offset Energy Slope Energy Tolerance:

Sensitivity 6-JUN-2014 20:09:

-4.40560E-01 5.00074E-01

1. 00000 5.00000 Post-NID Peak Search Report It Energy Area Bkgnd FWHM Channel Left Pw %Err Fit Nuclides 1

238.40 56 35

1. 93 477.61 475 11 23.6 3.96E+OO PB-212 1

295.24 29 5

1. 61 591.27 586 9 22.7 1. 32E+OO PB-214 1

351. 76 45 6

3.13 704.30 699 15 19.3 8.lOE-01 PB-214 1

609.40 29 6

1. 83 1219.52 1214 11 24.0 2.32E-01 BI-214 1

1460.86 67 0

2.49 2922.24 2915 13 12.3 6.37E-01 K-40

Summary of Nuclide Activity Sample ID : 30392 Total number of lines in spectrum Number of unidentified lines Acquisition date Page :

2 6-JUN-2014 20:53:09 Number of lines tentatively identified by NID 5

0 5

100.00%

Nuclide Type : natural Uncorrected Decay Corr Decay Corr 1-Sigma Nuclide Hlife Decay uCi/GR uCi/GR 1-Sigma Error

%Error Flags K-40 1.28E+09Y

1. 00 1.lBlE-05
1. lBlE-05 0.145E-05 12.27 A

PB-212 10.64H

1. 00 5.697E-07 5.708E-07 l.346E-07 23.58 A

BI-214 19.90M

1. 06 5.709E-07 6.045E-07 1.450E-07 23.99 A

PB-214 26.BOM

1. 04 7.500E-07 7.827E-07 1.777E-07
22. 71 A

Total Activity 1.370E-05

1. 377E-05 Grand Total Activity :

l.370E-05

1. 377E-05 Flags: "K" Keyline not found "M"

Manually accepted "E"

Manually edited "A"

Nuclide specific abn. limit

Unidentified Energy Lines Sample ID : 30392 None Flags: "T" Tentatively associated Page :

3 Acquisition date 6-JUN-2014 20:53:09

Interference Report Sample ID : 30392 No interference correction performed Acquisition date Page :

4 6-JUN-2014 20:53:09

Nuclide Line Activity Report Sample ID : 30392 Nuclide Type: natural Nuclide Energy Area K-40 1460.83 67 PB-212 74.81 ------

77.11 ------

87.19 ------

90.13 ------

115.12 ------

238.58 56 300.03 ------

BI-214 76.86 ------

79.29 ------

609.31 29 665.44 7 68. 35 806.16 ------

934.04 ------

1120. 27 1155. 18 1238. 11 ------

1280.95 ------

1377.66 ------

1385.30 ------

1401. 48 1407.97 1509.22 ------

1583.22 ------

1661. 26 1729.58 ------

1764.49 ------

1847.41 ------

PB-214 53.17 74.81 77.11 87.19 ------

90.13 241.92 258.94 295.09 29 351.87 45 785.83 839.00 ------

Flag: "*"

Keyline

%Abn 10.67*

10.50 17.70 6.27

1. 86 0.59 43.60*

3.34 0.58 0.97 46.10*

1. 56 4.88
1. 23 3.16 15.00
1. 69 5.92
1. 4 7 4.02 0.78
1. 39 2.48 2.19 0.72 1.15 3.05 15.90 2.12 1.10 6.52
11. 00 3.88 1.15 7.46 0.55 19.20*

37.10

1. 09 0.59 Page :

5 Acquisition date 6-JUN-2014 20:53:09 Uncorrected Decay Corr 1-Sigma

%Eff uCi/GR uCi/GR

%Error

4. 211E-01 1.181E-05 1.181E-05 12.27 1.150E+OO ------

Line Not Found ------

1.239E+OO ------

Line Not Found ------

1.579E+OO ------

Line Not Found ------

l.662E+OO Line Not Found ------

2.085E+OO Line Not Found ------

l.806E+OO 5.697E-07 5.708E-07 23.58 1.562E+OO Line Not Found ------

1.229E+OO Line Not Found ------

1.320E+OO Line Not Found ------

8.832E-01 5.709E-07 6.045E-07 23.99 8.131E-01 ------

Line Not Found ------

7.078E-01 ------

Line Not Found ------

6.754E-01 ------

Line Not Found ------

5.861E-01 ------

Line Not Found ------

4.982E-01 ------

Line Not Found ------

4.860E-01 ------

Line Not Found ------

4.615E-01 ------

Line Not Found ------

4.510E-Ol Line Not Found ------

4.323E-01 ------

Line Not Found ------

4. 311E-01 ------

Line Not Found ------

4.287E-01 ------

Line Not Found ------

4.277E-01 Line Not Found ------

4.165E-01 Line Not Found ------

4.120E-01 Line Not Found ------

4.103E-01 Line Not Found ------

4.114E-01 Line Not Found ------

4.128E-01 Line Not Found ------

4.187E-01 Line Not Found ------

2.929E-01 Line Not Found ------

1.150E+OO Line Not Found ------

1.239E+OO ------

Line Not Found ------

l.579E+OO Line Not Found ------

l.662E+OO Line Not Found ------

1.790E+OO ------

Line Not Found ------

1. 718E+OO Line Not Found ------

l.579E+OO 7.500E-07 7,827E-07 22.71 l.396E+OO 6.988E-07 7.292E-07 19.31 6.925E-01 Line Not Found ------

6.497E-01 Line Not Found ------

\\

Minimum Detectable Activity Report Sample ID 30392 Nuclide BE-7 MN-54 MN-56 C0-57 C0-58 C0-60 SB-124 SB-125 CS-134 CS-137 Bckgnd Sum

5.
3.
1.
11.
5.
0.
6.
10.
4.
3.

Energy (keV) 477.61 834.83 846.81 122.06 810.79 1332. 50 602.73 427.88 604. 71 661. 66 Acquisition date MDA (uCi/GR) 8.8749E-07

1. 2811E-07 9.2536E-08 7.8648E-08 1.5594E-07 4.8849E-08 1.2513E-07 3.9241E-07 l.0923E-07 l.2077E-07 Page :

6 6-JUN*-2014 20: 53: 09