LER 82-123/01T-0:on 821029 & 1109,during Mode 6 Operation, Control Room Emergency Vent Sys Declared Inoperable Due to Partial Closing of Suction Dampers 0-31A-102 & 0-31A-103. Caused by Duct Vibration.Design Change Being Expedited
ML20028A593
Person / Time
Site: Sequoyah Tennessee Valley Authority icon.png
Issue date: 11/10/1982
From: Hardin M, Rogers H
TENNESSEE VALLEY AUTHORITY
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20028A589 List:
References
LER-82-123-01T, LER-82-123-1T, NUDOCS 8211220319
Download: ML20028A593 (2)


Text

- - - .. .w. .:-

- w =w CO# 9809022 . - . . . . 20:9I OI/II.

Cord ract. s t.CCK: l l l l l l_ _ l_

.h (PLE ASE PAINY OR TYPE ALL f1ECUlRED INFCRMATIONI M

) lT S 5l N l LICtf45tt S l NCOOL  ! P l1 l@l0 i* 15 l0 l- ( 0 ! _0l LICENSE 0 lNueUtn O l O I - l 01025 l@1l1 16 l1 11 11 l@(57 carl an,lQ tiCAN5% fyra Jo Cord *T

,I,.

lolil 8

",3%WI L i@l 68 o 151010 Cocetg r Ny?/ GEM

[0 la [2 l'71@l 68 69 11 n 12191812 l@liliit_lo18 12 l@

EVf NT QAf t 24 JS PEPoRT DAT & 60 ,

EVENr DESCnfPT!Qrd APIO PACD A8LE CONSECUENCES h I o 121 l _ With unit _1 in mode 6 and unit __2 in mode 1 (96% power) at 1500 CST on l'0/29/82, the g l o 13 I I control room emergency ventilation system was declared inoperable due to the cor= ton g

[7171 I suction dampers 0-31A-102 and -103 partially closing causing the system to be _

lo(s) i unable to maintain its rated flow of 4000 cfm. A similar event occurred at 0800 CST; 4~ g<. ' l~ ~on 1T/d9/82.- Both events rei l uired entry into the ~ action statements of LCO 3.7.7 F6T7'l I and 3.0.3.

There was no effect upon public. health and safety. Previousoccurrenceg

,,,3j l one (SQRO-50-327/82071). _g

..ap SYSitu

. 40 CAU$f CAU$f CCup.

CCCE CoOF $UUCcDt Vatvs Cou'ONENT Coot 306Ccot suecoag

[oi9l 7 8

[Sddh 9 IO 13 h l B lh lVtJlA lL lV {E lXte l h l Nl h ' W h 32 , to ;3 tVENT YEAR SE C'J E N TI A L -

CCCunntNC(- gt t roq y MtvliioN ttpfpo af ronT No. 2008 YvPE 40.

O",agg,a' I a l 21 l-l i 11213 i Ld l o' I i l l Tl 1-1 1 01 21* 22 23 74 26 27 24 29 30 31 JJ T E8 A T Cl o fet ANT 7 u HOUSi$ $ tlU8 T f t F0n i n'v e. Sv*rti t MAN 8 ac tusit h 3

Ej@j34X l@ l Zl@ lZl@ l_0 l0 l0 l0ggl y@ [Nl@ lLl@ lX l 9l 9 l 91 33 31 __

33 43 42 43 44 47 CAU3t DESCRIPTION AND CORRECTIVE ACTIONS 27 ,

ITIT] I ' In both events, it una found that' the adjustment screw holding the' dampers open had i U,,,1,',,,,l l backed out due to vibration in'the duct allowing the suction damper to partially  ;

p. .c .

, El clese. The screw was immediately readjusted to open the dampers. Design change

'.r u . .

El roq ues t (DCR) 1650 is being exg dited to provide a new dampet. Until work is .

__ 3 yI complete, the darmer's position will be verified on a daily basis. _ _

t 6 8 _ _

80 i S

  1. ^YNf sr srowsa of otn s ra tu: h $sNtN oiscovenv etsemipitos h l Glh l 0 l 0 l0 l@[_n NA l W hl Systen Walkdown i

' ' Ac9tivery Co'O rcNr 62 44 45 de 50

, r:s t e Att 8 Lzg $] @o or ntLcAteLzJhl NA AucuNror Activery h l l NA LoCAflOf40F AELE ASE @

7 10 l 33 44 43 PtnSoNNEL Emposunts $$

Peu,Ae t a TYPE OtSCRiptsON 39

  • i >

I O I o l O' l@LzJ@L NA _

j

'f . * ' ,t a s e~,. 'L ,~,o'J,i s

l kuvat a

@ l0l0l0lhlotseniericNh

, . . to f:

NA

  • l toS1oF TYPE Cn DauaCE To FAcattrY -

Q($CRi#ffQN E, L,U@l e to N^

l cualiCity o 8211220319 821110 ,

es scaatio= s:'y PDR ADOCK 05000327 une usg cr.t ,

@ issutoW hl NA S PDR l l l l l l l [_ l_ [ l l l l . _

Name of Preparer: H. R, F gers /M.'R.'HardinR Phone: (615) 75$-0349 CMN. <

, -- - - . . - - .- - - --. ,,m- , . - - - -

,.,,y--- - ,------,.----y.- .

i

- #0# 9809022 80:9I OI/II

[ Sequoych Nuclear Plcnt e

    • LER SUPPLDENTAL INFORMATION e

Technical Specification Involved: 3.7.7 SQRO-50-327/82123 Reported Under Technical Specification: 6.9.1.12.b Date of Occurrence: 10/29/82, Time of Occurrence: 1500 CST Identi_f_ic_ation _and D_escription of Occurrence:

At 1500 CST on 10/29/82, during a walkdown of the control room emergency ventilation system, suction dampers 0-31A-102 and -103 were found parcially closed. This would have prevented the system f rom maintaining a flow rating of 4000 cfm in the event of control room isolation. A similar event occurred at 0800 CST on 11/09/82. Upon discovery of each event, the unit entered the action statements of LC0 3.7.7 and 3.0.3.

Conditicns Prior to Occurrence:

For both events unit 1 was in node 6 (refueling) and unit 2 was in mode 1

  • (96% power) .

Apparent Cause of Occurrence _:

The louvered dampers are held open by an adjustment screw. In each case, vibration of the duct and damper from air flow across the damper caused the adjustment screw to loosen and the damper to partially close.

Analysis of Occurrence:

In the event of control room isolation, the control room emergency ventilation system is designed to provide 4000 cfm (1 10%) air flow to the control room.

Suction dampers 0-31A-102 and -103 are common to both trains of 4he emergency air cleanup fans. These dampers are preset to casure 3800 cfm (- 10%) flow of ,

filtered air to the control room. When the dampers vibrated partially closed, the system would have been unable to meet the needed flow criteria.

Corrective Action:

For each event, the damper was immediately opened to the preset position and the adjustment screw tightened. Measures are being taken to block the damper in the open position to maintain system operability. The design of a new damper is being reviewed by Design through DCR 1650. Until modifications are made, a daily surveillance will be performed to verify the damper setting.

Failure Data:

None.