|
---|
Category:LICENSEE EVENT REPORT (SEE ALSO AO
MONTHYEARML20029E3351994-05-10010 May 1994 LER 94-006-00:on 940415,both Trains of CREVS Declared Inoperable.Caused by Tornado Warning & Sighting of Tornado Moving Toward Plant.Tornado Warnings downgraded.W/940510 Ltr ML20029E2021994-05-0909 May 1994 LER 94-004-00:on 940408,determined That TS Pressurizer Cooldown Limit Exceeded on 930618 & Not Restored within Required Timeframe.Caused by Unanticipated Sys Interaction. SI for Check Valve Opening Tests revised.W/940509 Ltr ML20029D8151994-05-0303 May 1994 LER 94-005-00:on 940403,inadvertent Fwis Occurred.Caused by Personnel Failure to Follow Work Document Instructions. Corrective Action:Individuals Were Counseled on Requirements to Follow Work Document Instruction steps.W/940503 Ltr ML20046B8351993-07-30030 July 1993 LER 93-017-00:on 930621,discovered 24-hour Telephone Notification Had Not Been Carried Out as Required by TS LCO 3.7.11.1 Action Statement (b)(2)(a) Due to Personnel Error. NRC Informed of Missed notification.W/930730 Ltr ML20046B8501993-07-30030 July 1993 LER 93-018-00:on 930704,DG Started Due to Improper WO Planning.Restored Power to 1BB Shutdown Board & Stopped Running DGs.W/930730 Ltr ML20046A4691993-07-19019 July 1993 LER 93-016-00:on 930619,Phase A,Auxiliary Bldg & Containment Isolations Manually Initiated as Result of Fuel Assembly Failing to Remain in Upright Position After Being Released. All Fuel Movement stopped.W/930719 Ltr ML20045J0111993-07-14014 July 1993 LER 93-015-00:on 930614,1A Start Bus Alternate Feeder Breaker Tripped Upon Start of Unit 1 RCP Which Resulted in Start of DG Due to Current Transformer Wired Incorrectly. Restored Offsite Power & Secured Final DG.W/930714 Ltr ML20045H0171993-07-12012 July 1993 LER 93-014-00:on 930611,determined That Inadequate Ventilation Design Resulted in Potential Inoperability of Vital Power Equipment.Design Being modified.W/930712 Ltr ML20045B9951993-06-15015 June 1993 LER 93-004-01:on 930222,determined That Blind Flange on Elevation 734 Personnel Airlock Outer Housing Leaking.Due to Improper Installation of Blind Flange.Evaluation Performed of Other 14 Double O-ring Blind flanges.W/930615 Ltr ML20045B9311993-06-10010 June 1993 LER 93-013-00:on 930514,fire Watch Was Not Performed within Time Frame Required by Tech Specs Due to Inadequate Supervision by Fire Protection Foreman.Fire Watch Patrol reestablished.W/930610 Ltr ML20045A7261993-06-0707 June 1993 LER 93-011-00:on 930507,discovered That Fire Barrier Breached W/O Proper Compensatory Measures Established.On 930505,door Leading to Room Housing Containment Spray HX 1A Breached.Roving Fire Watch Established & LCO 3.7.12 Entered ML20044H4501993-06-0303 June 1993 LER 93-012-00:on 930504,apparent Failure to Properly Identify & Plug SG Tube Determined to Exceed TS Plugging Limit.Caused by eddy-current Coordinator Not Ensuring Task requirements.Eddy-current Procedure revised.W/930603 Ltr ML20044H1561993-05-28028 May 1993 LER 93-010-00:on 930430,Westinghouse Identified Error in Development of Calculations for Cold Overpressure Mitigation Sys Setpoints.Caused by Vendor Failure to Consider Elevation Difference.Engineering Evaluation Performed ML20044E6341993-05-17017 May 1993 LER 93-009-00:on 930417,TS Surveillance Not Performed for Three Pipe Support Snubbers Because of Omission of Snubbers from Surveillance Instruction for Visual Insp.Snubbers Visually Inspected & Functionally tested.W/930517 Ltr ML20044B6751993-02-23023 February 1993 LER 93-001-00:on 930124,Unit 1 Ice Bed Temperature Recorder in MCR Declared Inoperable.Caused by Ineffective Communication.Appropriate Personnel Involved W/Event Have Been counseled.W/930223 Ltr ML20044B6141993-01-21021 January 1993 LER 92-026-00:on 921222,determined That Several ASME Section XI Pressure Tests Not Performed Due to Section XI Program Implementation Not Being well-defined,controlled or Documented.Test Expeditiously performed.W/930121 Ltr ML20024H2441991-05-22022 May 1991 LER 91-007-00:on 910422,LCO 3.0.3 Entered When Shaft of Train a Main Control Room Air Handling Unit Failed from Fatigue & Train B Out of Svc for Maint.Caused by Shaft Misalignment.New Shaft installed.W/910522 Ltr ML20029C1761991-03-21021 March 1991 LER 91-002-00:on 910211,unit Operated in Condition Prohibited by Tech Spec 3.3.3.8 Limiting Condition for Operation.Cause Under Investigation.Night Order Issued to Personnel Re Removal of Equipment from svc.W/910321 Ltr ML20029C1231991-03-18018 March 1991 LER 90-016-01:on 901117,determined That Calibr of Nuclear Instrumentation Sys intermediate-range Channels Set Nonconservatively.Caused by Lack of Operability Control for Rod Motion.Action Plan developed.W/910318 Ltr ML20029A6711991-02-25025 February 1991 LER 91-002-00:on 910124,LCOs 3.0.5 & 3.8.1.1 Entered When Both Trains of Emergency Gas Treatment Sys Declared Inoperable.Caused by Blown Fuse & Excessive Cycling of Air Start Sys.Fuse replaced.W/910225 Ltr ML20028H0331990-09-27027 September 1990 LER 90-019-00:on 900828,failure to Update P-250 Plant Computer Constants Resulted in Axial Flux Difference.Caused by Inadequate Procedures & Inappropriate Personnel Actions. Procedure 0-PI-NXX-092-001.0 revised.W/900927 Ltr ML20028G9201990-09-26026 September 1990 LER 90-020-00:on 900829,ventilation Sys Inoperable Due to Train B Diesel Generator Out of Svc.Caused by Stuck Microswitch Contacts on Pressure Switch 0-PS-311-172. Pressure Switch Adjusted & Returned to svc.W/900926 Ltr ML20044A9361990-07-0909 July 1990 LER 90-011-00:on 900608,determined That Actual Nuclear Instrumentation Sys Power Range Detector Currents Were 20% to 31% Lower than Predicted.Caused by Calibr Values Being Incorrectly Calculated.Channels corrected.W/900709 Ltr ML20044A3241990-06-25025 June 1990 LER 90-010-00:on 900526,limiting Condition for Operation Entered Because MSIV Failed to Close When Another MSIV Inoperable for Maint.Cause Attributed to Valve Stem & Valve Guide Binding.Operations Training Ltr issued.W/900625 Ltr ML20043H5091990-06-21021 June 1990 LER 90-009-00:on 900527,automatic Start of Auxiliary Feedwater Pumps Occurred When Both Main Feedwater Pumps Placed in Tripped Condition.Caused by Personnel Error.Trip Circuitry Reset & Operators counseled.W/900621 Ltr ML20043E5401990-06-0707 June 1990 LER 90-008-00:on 900514,two Control Room Isolations Occurred as Result of Spurious Spikes.Caused by Loose Terminations on Relay Socket.Loose Connections Properly terminated.W/900607 Ltr ML20043A4211990-05-16016 May 1990 LER 90-010-00:on 900416,containment Ventilation Isolation Occurred.Caused by Allowing Gaseous Radiation Level to Increase Too Close to Alarm Setpoint.Recovery from Isolation initiated.W/900516 Ltr ML20043A2261990-05-14014 May 1990 LER 90-009-00:on 900404,lower Containment Radiation Monitor Found Inoperable & Lower Containment Atmosphere Aligned to Upper Containment Radiation Monitor During Sampling.Caused by Personnel Error.Chemistry Training revised.W/900514 Ltr ML20043A2271990-05-14014 May 1990 LER 90-006-00:on 900414,auxiliary Bldg Isolation Occurred from Spent Fuel Pit Area Radiation Monitors 0-RM-90-102 & 103.Caused by Personnel Error.Training Ltr Issued to Instrument Mechanics & Operations personnel.W/900514 Ltr ML20043A2201990-05-14014 May 1990 LER 90-007-00:on 900413,discovered That Tech Spec Surveillance Requirement Not Performed within Required Interval.Caused by Personnel Error.Surveillance Successfully Performed Since missed.W/900514 Ltr ML20042G7861990-05-0909 May 1990 LER 90-005-00:on 900409,emergency Start of Four Emergency Diesel Generators Occurred While Attempting Transfer of Power.Caused by Personnel Error.Individuals Reprimanded, Training Initiated & Procedures revised.W/900509 Ltr ML20042G7931990-05-0909 May 1990 LER 90-008-00:on 900410,reactor Trip Occurred Resulting from General Warning Alarm on Both Trains of Solid State Protection Sys.Caused by Personnel Error.Individuals Disciplined & Site Wide Message distributed.W/900509 Ltr ML20042F3741990-05-0202 May 1990 LER 90-003-00:on 900404,control Room Ventilation Sys (CRVS) Transferred to Pressurization Mode.Caused by Electrical Transient in Vital Instrument Ac Bus PY-21A.CRVS Reset & Returned to Normal Operating modes.W/900502 Ltr ML20042E4191990-04-13013 April 1990 LER 90-007-00:on 900317 & 26,containment Ventilation Isolations Occurred During Purge Activities.Caused by Inadequate Procedural Guidance for Setpoint Determination. Alarm & Trip Setpoints increased.W/900413 Ltr ML20042E2021990-04-13013 April 1990 LER 90-005-00:on 900315,inadvertent Containment Vent Isolation Occurred While Preparing to Purge Containment. Caused by Lack of Attention to Detail by Operator.Operator Counseled & Received Administrative reprimand.W/900413 Ltr ML20012F5221990-04-0505 April 1990 LER 90-006-00:on 900307,containment Ventilation Isolation Occurred.Caused by Containment Particulate Level Too Close to Setpoint.Module Replaced.Radiation Alarm Setpoint Increased from 10% to 40% of Tech Spec limit.W/900406 Ltr ML20012D8611990-03-23023 March 1990 LER 90-004-00:on 900221,handswitches Controlling Operation of Isolation Valves on Steam Supply Line to Auxiliary Feedwater Pump Found in Manual Position.Cause Undetermined. Handswitches Placed in P-auto position.W/900323 Ltr ML20012C4271990-03-12012 March 1990 LER 90-003-00:on 900211,inadvertent Containment Vent Isolation Occurred.Caused by Lack of Attention to Detail in That Operator Did Not Look Closely Enough at Switch Designations.Personnel Involved counseled.W/900312 Ltr ML20011F7191990-03-0101 March 1990 LER 89-031-01:on 891205,RHR Pumps Determined to Have Deadheading Problem Identified by NRC Bulletin 88-004.Caused by Inadequate Technical Response to Bulletin.Training Ltr Issued to 10CFR50.59 reviewers.W/900301 Ltr ML20011F7421990-02-26026 February 1990 LER 90-002-00:on 900127,control Room Isolation Occurred When Circuit Breaker Opened Supplying Power to Radiation Monitor. Caused by Failure by Personnel to Exercise Sufficient Caution.Responsible Engineers reinstructed.W/900226 Ltr ML20011F7391990-02-26026 February 1990 LER 90-002-00:on 891122,value for Distance from Floor to Ctr Line of Level Switch 2-LS-87-21 Transposed in Variable Leg Calculation.Caused by Inattention to Detail.Procedure Revised to Replace Incorrect setpoint.W/900226 Ltr ML20006E3311990-02-0909 February 1990 LER 90-001-00:on 900112,Limiting Condition for Operation 3.0.3 Entered When Three of Four Lower Compartment Cooler Fan Motors Exceeded Lubrication Frequency.Caused by Personnel Error.Personnel counseled.W/900209 Ltr ML20006D5341990-02-0707 February 1990 LER 90-001-00:on 900108,discovered That Several ERCW Valves Not Being Periodically Verified to Be Correct.Caused by Personnel Error During Procedure Revs & Workplan Reviews. Info Notice Issued to Workplan reviewers.W/900207 Ltr ML19354E1631990-01-22022 January 1990 LER 89-036-00:on 891221,discovered That Surveillance Test Results Used for Declaring Diesel Generator 1B-B Operable Deficient.Caused by Instruction Not Including 60 Minute Run Time.Event Will Be Reviewed w/supervisors.W/900122 Ltr ML19354D8941990-01-16016 January 1990 LER 89-034-00:on 891215,leak Identified from Fitting on Vol Control Tank Level Transmitter & Auxiliary Bldg Evacuated, Preventing Fire Watch Patrol from Entering Bldg for Hourly Rounds.Fitting tightened.W/900116 Ltr ML19354D9061990-01-16016 January 1990 LER 89-033-00:on 891216,refueling Water Storage Tank Level Transmitters Failed High Due to Freezing from Extremely Cold Weather & Inappropriate Use of Calculations.Engineering Procedures Revised & Heating Installed in encl.W/900116 Ltr ML20005F8851990-01-0909 January 1990 LER 89-035-00:on 891210,turbine/reactor Trip Occurred from hi-hi Feedwater Level of 75% in Steam Generator 3.Caused by Failure of Loop 3 Main Feedwater Regulating Valve to Close. Equipment Adjusted & repaired.W/900109 Ltr ML20005E0801989-12-22022 December 1989 LER 89-032-00:on 891205,RHR Pumps Determined to Have Deadheading Problem,Per NRC Bulletin 88-004,resulting in Plant Operation Outside Design Basis.On 891128,RHR Pump Exceeded Head Criteria.Pumps started.W/891222 Ltr ML20005E0831989-12-22022 December 1989 LER 89-032-00:on 891201,discovered That Tech Spec Surveillance Requirement to Verify That Valves 1-67-748 & 2-67-748 in Open Position Not Met.Caused by Personnel Error.Correct Valve Position verified.W/891222 Ltr ML20005E1161989-12-22022 December 1989 LER 89-030-00:on 891204,fire Suppression Sys Deluge Valve Isolated More than 1 H W/O Required Continuous Fire Watch Establishment.Caused by Personal Communication Breakdown. Valve Opened & Foreman in Charge counseled.W/891222 Ltr 1994-05-09
[Table view] Category:RO)
MONTHYEARML20029E3351994-05-10010 May 1994 LER 94-006-00:on 940415,both Trains of CREVS Declared Inoperable.Caused by Tornado Warning & Sighting of Tornado Moving Toward Plant.Tornado Warnings downgraded.W/940510 Ltr ML20029E2021994-05-0909 May 1994 LER 94-004-00:on 940408,determined That TS Pressurizer Cooldown Limit Exceeded on 930618 & Not Restored within Required Timeframe.Caused by Unanticipated Sys Interaction. SI for Check Valve Opening Tests revised.W/940509 Ltr ML20029D8151994-05-0303 May 1994 LER 94-005-00:on 940403,inadvertent Fwis Occurred.Caused by Personnel Failure to Follow Work Document Instructions. Corrective Action:Individuals Were Counseled on Requirements to Follow Work Document Instruction steps.W/940503 Ltr ML20046B8351993-07-30030 July 1993 LER 93-017-00:on 930621,discovered 24-hour Telephone Notification Had Not Been Carried Out as Required by TS LCO 3.7.11.1 Action Statement (b)(2)(a) Due to Personnel Error. NRC Informed of Missed notification.W/930730 Ltr ML20046B8501993-07-30030 July 1993 LER 93-018-00:on 930704,DG Started Due to Improper WO Planning.Restored Power to 1BB Shutdown Board & Stopped Running DGs.W/930730 Ltr ML20046A4691993-07-19019 July 1993 LER 93-016-00:on 930619,Phase A,Auxiliary Bldg & Containment Isolations Manually Initiated as Result of Fuel Assembly Failing to Remain in Upright Position After Being Released. All Fuel Movement stopped.W/930719 Ltr ML20045J0111993-07-14014 July 1993 LER 93-015-00:on 930614,1A Start Bus Alternate Feeder Breaker Tripped Upon Start of Unit 1 RCP Which Resulted in Start of DG Due to Current Transformer Wired Incorrectly. Restored Offsite Power & Secured Final DG.W/930714 Ltr ML20045H0171993-07-12012 July 1993 LER 93-014-00:on 930611,determined That Inadequate Ventilation Design Resulted in Potential Inoperability of Vital Power Equipment.Design Being modified.W/930712 Ltr ML20045B9951993-06-15015 June 1993 LER 93-004-01:on 930222,determined That Blind Flange on Elevation 734 Personnel Airlock Outer Housing Leaking.Due to Improper Installation of Blind Flange.Evaluation Performed of Other 14 Double O-ring Blind flanges.W/930615 Ltr ML20045B9311993-06-10010 June 1993 LER 93-013-00:on 930514,fire Watch Was Not Performed within Time Frame Required by Tech Specs Due to Inadequate Supervision by Fire Protection Foreman.Fire Watch Patrol reestablished.W/930610 Ltr ML20045A7261993-06-0707 June 1993 LER 93-011-00:on 930507,discovered That Fire Barrier Breached W/O Proper Compensatory Measures Established.On 930505,door Leading to Room Housing Containment Spray HX 1A Breached.Roving Fire Watch Established & LCO 3.7.12 Entered ML20044H4501993-06-0303 June 1993 LER 93-012-00:on 930504,apparent Failure to Properly Identify & Plug SG Tube Determined to Exceed TS Plugging Limit.Caused by eddy-current Coordinator Not Ensuring Task requirements.Eddy-current Procedure revised.W/930603 Ltr ML20044H1561993-05-28028 May 1993 LER 93-010-00:on 930430,Westinghouse Identified Error in Development of Calculations for Cold Overpressure Mitigation Sys Setpoints.Caused by Vendor Failure to Consider Elevation Difference.Engineering Evaluation Performed ML20044E6341993-05-17017 May 1993 LER 93-009-00:on 930417,TS Surveillance Not Performed for Three Pipe Support Snubbers Because of Omission of Snubbers from Surveillance Instruction for Visual Insp.Snubbers Visually Inspected & Functionally tested.W/930517 Ltr ML20044B6751993-02-23023 February 1993 LER 93-001-00:on 930124,Unit 1 Ice Bed Temperature Recorder in MCR Declared Inoperable.Caused by Ineffective Communication.Appropriate Personnel Involved W/Event Have Been counseled.W/930223 Ltr ML20044B6141993-01-21021 January 1993 LER 92-026-00:on 921222,determined That Several ASME Section XI Pressure Tests Not Performed Due to Section XI Program Implementation Not Being well-defined,controlled or Documented.Test Expeditiously performed.W/930121 Ltr ML20024H2441991-05-22022 May 1991 LER 91-007-00:on 910422,LCO 3.0.3 Entered When Shaft of Train a Main Control Room Air Handling Unit Failed from Fatigue & Train B Out of Svc for Maint.Caused by Shaft Misalignment.New Shaft installed.W/910522 Ltr ML20029C1761991-03-21021 March 1991 LER 91-002-00:on 910211,unit Operated in Condition Prohibited by Tech Spec 3.3.3.8 Limiting Condition for Operation.Cause Under Investigation.Night Order Issued to Personnel Re Removal of Equipment from svc.W/910321 Ltr ML20029C1231991-03-18018 March 1991 LER 90-016-01:on 901117,determined That Calibr of Nuclear Instrumentation Sys intermediate-range Channels Set Nonconservatively.Caused by Lack of Operability Control for Rod Motion.Action Plan developed.W/910318 Ltr ML20029A6711991-02-25025 February 1991 LER 91-002-00:on 910124,LCOs 3.0.5 & 3.8.1.1 Entered When Both Trains of Emergency Gas Treatment Sys Declared Inoperable.Caused by Blown Fuse & Excessive Cycling of Air Start Sys.Fuse replaced.W/910225 Ltr ML20028H0331990-09-27027 September 1990 LER 90-019-00:on 900828,failure to Update P-250 Plant Computer Constants Resulted in Axial Flux Difference.Caused by Inadequate Procedures & Inappropriate Personnel Actions. Procedure 0-PI-NXX-092-001.0 revised.W/900927 Ltr ML20028G9201990-09-26026 September 1990 LER 90-020-00:on 900829,ventilation Sys Inoperable Due to Train B Diesel Generator Out of Svc.Caused by Stuck Microswitch Contacts on Pressure Switch 0-PS-311-172. Pressure Switch Adjusted & Returned to svc.W/900926 Ltr ML20044A9361990-07-0909 July 1990 LER 90-011-00:on 900608,determined That Actual Nuclear Instrumentation Sys Power Range Detector Currents Were 20% to 31% Lower than Predicted.Caused by Calibr Values Being Incorrectly Calculated.Channels corrected.W/900709 Ltr ML20044A3241990-06-25025 June 1990 LER 90-010-00:on 900526,limiting Condition for Operation Entered Because MSIV Failed to Close When Another MSIV Inoperable for Maint.Cause Attributed to Valve Stem & Valve Guide Binding.Operations Training Ltr issued.W/900625 Ltr ML20043H5091990-06-21021 June 1990 LER 90-009-00:on 900527,automatic Start of Auxiliary Feedwater Pumps Occurred When Both Main Feedwater Pumps Placed in Tripped Condition.Caused by Personnel Error.Trip Circuitry Reset & Operators counseled.W/900621 Ltr ML20043E5401990-06-0707 June 1990 LER 90-008-00:on 900514,two Control Room Isolations Occurred as Result of Spurious Spikes.Caused by Loose Terminations on Relay Socket.Loose Connections Properly terminated.W/900607 Ltr ML20043A4211990-05-16016 May 1990 LER 90-010-00:on 900416,containment Ventilation Isolation Occurred.Caused by Allowing Gaseous Radiation Level to Increase Too Close to Alarm Setpoint.Recovery from Isolation initiated.W/900516 Ltr ML20043A2261990-05-14014 May 1990 LER 90-009-00:on 900404,lower Containment Radiation Monitor Found Inoperable & Lower Containment Atmosphere Aligned to Upper Containment Radiation Monitor During Sampling.Caused by Personnel Error.Chemistry Training revised.W/900514 Ltr ML20043A2271990-05-14014 May 1990 LER 90-006-00:on 900414,auxiliary Bldg Isolation Occurred from Spent Fuel Pit Area Radiation Monitors 0-RM-90-102 & 103.Caused by Personnel Error.Training Ltr Issued to Instrument Mechanics & Operations personnel.W/900514 Ltr ML20043A2201990-05-14014 May 1990 LER 90-007-00:on 900413,discovered That Tech Spec Surveillance Requirement Not Performed within Required Interval.Caused by Personnel Error.Surveillance Successfully Performed Since missed.W/900514 Ltr ML20042G7861990-05-0909 May 1990 LER 90-005-00:on 900409,emergency Start of Four Emergency Diesel Generators Occurred While Attempting Transfer of Power.Caused by Personnel Error.Individuals Reprimanded, Training Initiated & Procedures revised.W/900509 Ltr ML20042G7931990-05-0909 May 1990 LER 90-008-00:on 900410,reactor Trip Occurred Resulting from General Warning Alarm on Both Trains of Solid State Protection Sys.Caused by Personnel Error.Individuals Disciplined & Site Wide Message distributed.W/900509 Ltr ML20042F3741990-05-0202 May 1990 LER 90-003-00:on 900404,control Room Ventilation Sys (CRVS) Transferred to Pressurization Mode.Caused by Electrical Transient in Vital Instrument Ac Bus PY-21A.CRVS Reset & Returned to Normal Operating modes.W/900502 Ltr ML20042E4191990-04-13013 April 1990 LER 90-007-00:on 900317 & 26,containment Ventilation Isolations Occurred During Purge Activities.Caused by Inadequate Procedural Guidance for Setpoint Determination. Alarm & Trip Setpoints increased.W/900413 Ltr ML20042E2021990-04-13013 April 1990 LER 90-005-00:on 900315,inadvertent Containment Vent Isolation Occurred While Preparing to Purge Containment. Caused by Lack of Attention to Detail by Operator.Operator Counseled & Received Administrative reprimand.W/900413 Ltr ML20012F5221990-04-0505 April 1990 LER 90-006-00:on 900307,containment Ventilation Isolation Occurred.Caused by Containment Particulate Level Too Close to Setpoint.Module Replaced.Radiation Alarm Setpoint Increased from 10% to 40% of Tech Spec limit.W/900406 Ltr ML20012D8611990-03-23023 March 1990 LER 90-004-00:on 900221,handswitches Controlling Operation of Isolation Valves on Steam Supply Line to Auxiliary Feedwater Pump Found in Manual Position.Cause Undetermined. Handswitches Placed in P-auto position.W/900323 Ltr ML20012C4271990-03-12012 March 1990 LER 90-003-00:on 900211,inadvertent Containment Vent Isolation Occurred.Caused by Lack of Attention to Detail in That Operator Did Not Look Closely Enough at Switch Designations.Personnel Involved counseled.W/900312 Ltr ML20011F7191990-03-0101 March 1990 LER 89-031-01:on 891205,RHR Pumps Determined to Have Deadheading Problem Identified by NRC Bulletin 88-004.Caused by Inadequate Technical Response to Bulletin.Training Ltr Issued to 10CFR50.59 reviewers.W/900301 Ltr ML20011F7421990-02-26026 February 1990 LER 90-002-00:on 900127,control Room Isolation Occurred When Circuit Breaker Opened Supplying Power to Radiation Monitor. Caused by Failure by Personnel to Exercise Sufficient Caution.Responsible Engineers reinstructed.W/900226 Ltr ML20011F7391990-02-26026 February 1990 LER 90-002-00:on 891122,value for Distance from Floor to Ctr Line of Level Switch 2-LS-87-21 Transposed in Variable Leg Calculation.Caused by Inattention to Detail.Procedure Revised to Replace Incorrect setpoint.W/900226 Ltr ML20006E3311990-02-0909 February 1990 LER 90-001-00:on 900112,Limiting Condition for Operation 3.0.3 Entered When Three of Four Lower Compartment Cooler Fan Motors Exceeded Lubrication Frequency.Caused by Personnel Error.Personnel counseled.W/900209 Ltr ML20006D5341990-02-0707 February 1990 LER 90-001-00:on 900108,discovered That Several ERCW Valves Not Being Periodically Verified to Be Correct.Caused by Personnel Error During Procedure Revs & Workplan Reviews. Info Notice Issued to Workplan reviewers.W/900207 Ltr ML19354E1631990-01-22022 January 1990 LER 89-036-00:on 891221,discovered That Surveillance Test Results Used for Declaring Diesel Generator 1B-B Operable Deficient.Caused by Instruction Not Including 60 Minute Run Time.Event Will Be Reviewed w/supervisors.W/900122 Ltr ML19354D8941990-01-16016 January 1990 LER 89-034-00:on 891215,leak Identified from Fitting on Vol Control Tank Level Transmitter & Auxiliary Bldg Evacuated, Preventing Fire Watch Patrol from Entering Bldg for Hourly Rounds.Fitting tightened.W/900116 Ltr ML19354D9061990-01-16016 January 1990 LER 89-033-00:on 891216,refueling Water Storage Tank Level Transmitters Failed High Due to Freezing from Extremely Cold Weather & Inappropriate Use of Calculations.Engineering Procedures Revised & Heating Installed in encl.W/900116 Ltr ML20005F8851990-01-0909 January 1990 LER 89-035-00:on 891210,turbine/reactor Trip Occurred from hi-hi Feedwater Level of 75% in Steam Generator 3.Caused by Failure of Loop 3 Main Feedwater Regulating Valve to Close. Equipment Adjusted & repaired.W/900109 Ltr ML20005E0801989-12-22022 December 1989 LER 89-032-00:on 891205,RHR Pumps Determined to Have Deadheading Problem,Per NRC Bulletin 88-004,resulting in Plant Operation Outside Design Basis.On 891128,RHR Pump Exceeded Head Criteria.Pumps started.W/891222 Ltr ML20005E0831989-12-22022 December 1989 LER 89-032-00:on 891201,discovered That Tech Spec Surveillance Requirement to Verify That Valves 1-67-748 & 2-67-748 in Open Position Not Met.Caused by Personnel Error.Correct Valve Position verified.W/891222 Ltr ML20005E1161989-12-22022 December 1989 LER 89-030-00:on 891204,fire Suppression Sys Deluge Valve Isolated More than 1 H W/O Required Continuous Fire Watch Establishment.Caused by Personal Communication Breakdown. Valve Opened & Foreman in Charge counseled.W/891222 Ltr 1994-05-09
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20212J6311999-10-0101 October 1999 SER Accepting Request for Relief from ASME Boiler & Pressure Vessel Code,Section Xi,Requirements for Certain Inservice Insp at Plant,Unit 1 ML20217G3721999-09-30030 September 1999 Monthly Operating Repts for Sept 1999 for Sequoyah Nuclear Plant.With ML20212F0831999-09-23023 September 1999 Safety Evaluation Granting Relief from Certain Weld Insp at Sequoyah Nuclear Plant,Units 1 & 2 Pursuant to 10CFR50.55a(a)(3)(ii) for Second 10-year ISI Interval ML20212F4761999-09-23023 September 1999 Safety Evaluation Supporting Amends 246 & 237 to Licenses DPR-77 & DPR-79,respectively ML20212C4761999-08-31031 August 1999 Monthly Operating Repts for Aug 1999 for Sequoyah Nuclear Plant.With ML20210L4361999-08-0202 August 1999 Cycle 9 12-Month SG Insp Rept ML20216E3781999-07-31031 July 1999 Monthly Operating Repts for July 1999 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20210L4451999-07-31031 July 1999 Unit-2 Cycle 10 Voltage-Based Repair Criteria 90-Day Rept ML20210G6631999-07-28028 July 1999 Cycle 9 90-Day ISI Summary Rept ML20196H8621999-06-30030 June 1999 NRC Regulatory Assessment & Oversight Pilot Program, Performance Indicator Data, June 1999 Rept ML20209H3831999-06-30030 June 1999 Monthly Operating Repts for June 1999 for Sequoyah Nuclear Plant.With ML20211F9031999-06-30030 June 1999 Cycle 9 Refueling Outage ML20196J8521999-06-28028 June 1999 Safety Evaluation Authorizing Proposed Alternative to Use Iqis for Radiography Examinations as Provided for in ASME Section III,1992 Edition with 1993 Addenda,Pursuant to 10CFR50.55a(a)(3)(i) ML20195K2951999-05-31031 May 1999 Monthly Operating Repts for May 1999 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20206Q8951999-05-0505 May 1999 Rev 0 to L36 990415 802, COLR for Sequoyah Unit 2 Cycle 10 ML20206R5031999-04-30030 April 1999 Monthly Operating Repts for April 1999 for Sequoyah Units 1 & 2.With ML20205P9811999-03-31031 March 1999 Monthly Operating Repts for Mar 1999 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20204C3111999-02-28028 February 1999 Monthly Operating Repts for Feb 1999 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20205B6631999-02-28028 February 1999 Underground Storage Tank (Ust) Permanent Closure Rept, Sequoyah Nuclear Plant Security Backup DG Ust Sys ML20203H7381999-02-18018 February 1999 Safety Evaluation of Topical Rept BAW-2328, Blended U Lead Test Assembly Design Rept. Rept Acceptable Subj to Listed Conditions ML20211A2021999-01-31031 January 1999 Non-proprietary TR WCAP-15129, Depth-Based SG Tube Repair Criteria for Axial PWSCC Dented TSP Intersections ML20198S7301998-12-31031 December 1998 Cycle 10 Voltage-Based Repair Criteria 90-Day Rept ML20199G3641998-12-31031 December 1998 Monthly Operating Repts for Dec 1998 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20197J5621998-12-0303 December 1998 Unit 1 Cycle 9 90-Day ISI Summary Rept ML20197K1161998-11-30030 November 1998 Monthly Operating Repts for Nov 1998 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20195F8061998-10-31031 October 1998 Monthly Operating Repts for Oct 1998 for Sequoyah Nuclear Plant.With ML20154H6091998-09-30030 September 1998 Monthly Operating Repts for Sept 1998 for Sequoyah Nuclear Plant,Units 1 & 2.With ML20154H6251998-09-17017 September 1998 Rev 0 to Sequoyah Nuclear Plant Unit 1 Cycle 10 Colr ML20153B0881998-08-31031 August 1998 Monthly Operating Repts for Aug 1998 for Sequoyah Nuclear Plant.With ML20239A0631998-08-27027 August 1998 SER Accepting Licensee Response to GL 95-07, Pressure Locking & Thermal Binding of Safety-Related Power-Operated Gate Valves, for Sequoyah Nuclear Plant,Units 1 & 2 ML20236Y2091998-08-0707 August 1998 Safety Evaluation Accepting Relief Requests RP-03,RP-05, RP-07,RV-05 & RV-06 & Denying RV-07 & RV-08 ML20237B5221998-07-31031 July 1998 Monthly Operating Repts for July 1998 for Snp ML20237A4411998-07-31031 July 1998 Blended Uranium Lead Test Assembly Design Rept ML20236P6441998-07-10010 July 1998 LER 98-S01-00:on 980610,failure of Safeguard Sys Occurred for Which Compensatory Measures Were Not Satisfied within Required Time Period.Caused by Inadequate Security Procedure.Licensee Revised Procedure MI-134 ML20236R0051998-06-30030 June 1998 Monthly Operating Repts for June 1998 for Sequoyah Nuclear Plant ML20249A8981998-05-31031 May 1998 Monthly Operating Repts for May 1998 for Sequoyah Nuclear Plant,Units 1 & 2 ML20247L5141998-04-30030 April 1998 Monthly Operating Repts for Apr 1998 for Sequoyah Nuclear Plant ML20217K4471998-04-27027 April 1998 Safety Evaluation Supporting Requests for Relief 1-ISI-2 (Part 1),2-ISI-2 (Part 2),1-ISI-5,2-ISI-5,1-ISI-6,1-ISI-7, 2-ISI-7,ISPT-02,ISPT-04,ISPT-06,ISPT-07,ISPT-8,ISPT-01 & ISPT-05 ML20217E2221998-03-31031 March 1998 Monthly Operating Repts for Mar 1998 for Sequoyah Nuclear Plant ML20248L2611998-02-28028 February 1998 Monthly Operating Repts for Sequoyah Nuclear Plant,Units 1 & 2 ML20199J2571998-01-31031 January 1998 Cycle 9 Voltage-Based Repair Criteria 90-Day Rept ML20202J7911998-01-31031 January 1998 Monthly Operating Repts for Jan 1997 for Sequoyah Nuclear Plant,Units 1 & 2 ML20199J2441998-01-29029 January 1998 Snp Unit 2 Cycle Refueling Outage Oct 1997 ML20199F8531998-01-13013 January 1998 ASME Section XI Inservice Insp Summary Rept for Snp Unit 2 Refueling Outage Cycle 8 ML20199A2931997-12-31031 December 1997 Revised Monthly Operating Rept for Dec 1997 for Sequoyah Nuclear Plant,Units 1 & 2 ML20198M1481997-12-31031 December 1997 Monthly Operating Repts for Dec 1997 for Sequoyah Nuclear Plant,Units 1 & 2 ML20197J1011997-11-30030 November 1997 Monthly Operating Repts for Nov 1997 for Sequoyah Nuclear Plant,Units 1 & 2 ML20199C2951997-11-13013 November 1997 LER 97-S01-00:on 971017,vandalism of Electrical Cables Was Observed.Caused by Vandalism.Repaired Damaged Cables, Interviewed Personnel Having Potential for Being in Area at Time Damage Occurred & Walkdowns ML20199C7201997-10-31031 October 1997 Monthly Operating Repts for Oct 1997 for Sequoyah Nuclear Plant L-97-215, SG Secondary Side Loose Object Safety Evaluation1997-10-23023 October 1997 SG Secondary Side Loose Object Safety Evaluation 1999-09-30
[Table view] |
Text
BF
-TENNESSEE VALLEY AUTHORITY ?
6N 38A Lookout Place Chattanooga, Tennessee 37402-2801 May 9, 1990 U.S. Nuclear Regulatory Commission ,
ATIN Document Control = Desk !
Washington, D.C. 20555 ;
i Gentlement }
TEKNESSEE VALLEY AUTHORITY - SEQUOYAH NUCLEAR PLANT UNIT 2 - DOCKET NO.
$0-328 - FACILITY OPERATING LICENSE DPR LICENSEE EVENT REPORT (LER) .
50-328/90008 The enclosed LER provides details of a reactor trip on Unit 2, which resulted ,
from a general warning on both trains of the solid state protection system, I and was caused by surveillance test steps being performed out of sequence. '
This event is being reported under 10 CFR 50.73(a)(2)(iv). i Very truly yours, TENNESSEE VALLEY AUTHORITY :
. k. Bynum, Vice President Nuclear Power Production Enclosure cc (Enclosure): l INPO Records Center Institute of Nuclear Power Operations 1100 circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 ,
NRC Resident Inspector Sequoyah Nuclear Plant 1 2600 Igou Ferry Road Soddy Daisy, Tennessee 37379 Regional Administration U.S. Nuclear Regulatory Commission Office of Inspection and Enforcement Region II 101 Marietta Street, Suite 2900 Atlanta, Georgia 30323 9005160103 900509 PDR ADOCK 05000329 PDC 7622 s ,
An Equal Opportunity Cmployer j/
F-N 090 W 306 U.S. FUCL EO L41ULaTORY COMMISSION l APPROYED OMS NO 3%0104 tlCP11E$ 4'30!92
. . IstiM Af tD tiutDtN 782 MS*0Nst TO COM*LY WTH THili CWMt,#'We1R'n'iJo'OOL. ES!iMAa*TU'l e"Ct'n"i LICENSEE EVENT REPORT (LERI
' "' " I
$NUI'A70R!c"/MMiSE'Nd"'.*Eo"NE:E*ENO" s 'Miti'0 a.i ?T O !? %'!"T.T ! M ast 8'C % f3 f ACILtf Y 4eAM4 Hi DOCR81 NUheDIR (3) FAUE 4 Sequoyah Nuclear Plant, Unit 2 0 l 6 l 0 l 0 l 013 D 18 1 l0Fl016
'6* Sequoyah Unit 2 reactor trip from general warnitig alarm on both trains of solid state protection system as a result of performing surveillance test steps out of sequence.
SWINT DAf t Ill LE R NUMet h ist klPORT Daf t (71 OTHER F ACILif f t$ INVOLVID {$l
[,'y*,$ ' *C'L'T v N Avtl 00(kti NUM8tml86 MONT H DAY YEAR YEAR M U'4 n MONTH DAv star j 016101010 1 I I
~ "~
d4 1l0 9 0 9l 0 0l0 l 8 0 l0 0 l5 0l9 9l0 0 gB io l0 iog l l TMit REPORT st SUDMITTED PUR$UANT TO TH8 ftt0UintMtNTS Of 10 Cf R $ teneca one en me,e er rne venew.ass tvil 1 OPE R A fiNo I
"00 ' " ' r0 40sisi 60n HHi 73 7t 65 1 30 40:161 X R SC 4061eHtHit to 34teH16 0033ieHtHel 7331tel (10 1l nln 30 406mHlHul 60.36k@
5033mH2HvWl
_ T,MJ 3py,r, A*prl 30 406(alH Hdil D0 73ieH2 illa 60334e Milki41H Al J66Al 30 406telH Hkt 60 73ieH3itel 90 ?Siell2Hve6tHDI 30 406teHillel DO 734eH2Helil to 73 eHtHal LICINllI CONT ACT FOR TMi$ LtR H3)
NAME TELEPHONE NUM8th ARE A CODS G:offery llipp, Compliance Licensing Engineer 611 5 8 I4 131- l 7171616 COMPLETE ON8 LINI 90R ( ACM COMPONINT f AILURt Otachitt0 IN THIS REPORT 113i M alPORTA Lt ntp0RtA 6 CAU50 8v5f tM COMPONEN, hC CAU85 8vittM COMPONENT "(WhC I I I l ! I I l l 1 l l I I I I I I I I I I I I I I I I SUPPLsMINT AL REPORT S KPECTf D (141 MONTH OAV VIAR SV0Misst0N h 4 m Pe . #e. ,aserro sumss,0= oAre, 1 No ; l i Aestat, oL,. ,,, ,, ,m ., i . . eo,<e-w?, r.r es.,, oue tw. s, o..e,> 0si On April 10, 1990, with Unit 1 defueled and Unit 2 in Mode 1 at 100 percent power, a ructor trip occurred on Unit 2 at 0134 Eastern daylight time. The trip resulted from a gsneral warning alarm on both trains of the solid state protection system (SSPS) and was c:used by surveillance test steps being performed out of sequence during a monthly SSPS Train B functional test. When the out-of-sequence situation was discovered, the process used to evaluate the situation was not as specified in plant instructions. As a consequence when the omitted steps were performed out of sequence, a reactor trip occurred. Plant systems responded properly and the shutdown posed no danger to plant smployees or the general public. The root cause of the event has been attributed to i p3rsonnel error on the part of the test director and his supervisor in not following procedures addressing an out-of-sequence situation. As corrective action, appropriate l disciplinary action has been given to both the test director and the supervisor. In addition, a site wide message has been distributed to provide lessons learned from the sv;nt and to emphasize the proper response to problems encountered during work.
l l
l N .C Form 394 i64191
i hhcPOhW St6A U 8 NWCLE AR LtOULATORV COMM10SION
- UP WD WB N4 MWMD4 4 K7C.ES o!30'97 I
,. . LICENSEE EVENT REPORT (LER) f,V&n'.Mo'.$Td',*J'So"u'!,'%CU.T ,*J"3".'!
TEXT CONTINUATlON f,%*,'",l',",!".'Nni n'"f'Alfe'0,'!E"' "'MN ,
O, f",1,'o".'or. ".*a'aa'.!Eis't&WMi?ci l o ua%acivewt A=oevDoct wasuiwovos.oc mos. j eAceuty =amitie poenat=vuesa m ,aos m l un v in m Sequoyah Nuclear Plant. Unit 2 viaa " W." %*.3 0 l5 l 0 [ 0 l 0 l 3 l2 lg gl0 -
oln lg -
nln 0 12 0F 016 i isxt ru . <Ja' w ac w mau nn :
DESCRIPTION OF EVENT On April 10, 1990, with Unit 1 defueled and Unit 2 in Mode 1 at 100 percent power, 2,232 pounds per square inch gauge (psig), 578 degrees Fahrenheit (F), a reactor trip occurred on Unit 2 at 0134 Eastern daylight time (EDT). The trip resulted from a g:neral warning alarm (EIIS Code ALM) on both trains of the solid state protection system (SSPS) (EIIS Code JC) and was caused by surveillance test steps being performed out of sequence.
Th3 surveillance test being performed was a monthly SSPS Train B functional test using Surveillance Instruction (SI) 90.82, " Reactor Trip Instrumentation Monthly Functional Tost (SSPS)." The instrument and control test crew had conducted their pretest briefing ct 0015 EDT and had collected the necessary communication equipment. The SI is parformed and documented by the test crew at three work locations. Data Sheet 1 is completed in the main control room (MCR) (EIIS Code NA); Data Sheet 2 is completed in tho auxiliary instrument room (AIR) (EIIS Code NA): and Data Sheet 3 is completed in the rod control room (EIIS Code NF). This same test crew had recently performed the squivalent SI on Train A of the Unit 2 SSPS, and each person was assigned to perform the same task as before.
Tha test director (TD) was stationed in the MCR and was responsible for coordination emong the three work stations. The TD initiated the SI performance at 0109 EDT and parformed the preparatory steps of Data Sheet 1, which include obtaining operator opproval to perform the test and installing orange stickers on various status and alarm lights in the MCR designating test status. The TD then read through the next two Data Shset 1 steps (Steps 3.0 and 4.1) to Step 4.6.1, which had him ensure that the test crew members were at their assigned stations and communications were established. The TD did not take any actions to ensure Steps 3.0 or 4.1 were satisfied at this time. Step 4.1 states that Stepp 4.1 through 4.5 (which are on Data Sheet 2) are performed in the AIR to verify lamp bulbs are working, to verify the general warning alarm status of both SSPS trains, and to place the SSPS multiplexer test switch (EIIS Code MPX) in the
" normal" position.
Whsn communications between the three work locations had been verified, the TD continued th9 SI performance at Step 4.6.2. Step 4.1 had still not been performed. At Step 4.6.3, the instrument mechanic in the rod control room tested, racked-in, and closed the Train B bypass reactor trip breaker (EIIS Code AA). This bypass breaker must bo in service during performance of the SI to avoid a reactor trip. However, having the bypass breaker in service caused a general warning alarm on SSPS Train B. After the bypass breaker was put in service, the SI performance continued to Step 4.6.5. At this point, it was noted that the test crew in the AIR had not yet performed Steps 4.3 through 4.5. The TD and test performer in the AIR discussed between themselves the fact that the SI steps were out of sequence and came to the conclusion that the test could be ceught up without impact on the unit by performing the omitted steps out of sequence.
No drawingr or manuals were reviewed durir.g this decision making process, nor was the shift operations supervisor (SOS) consulted.
NRC Penn 3eSA (&891
u.. vem. aoutAvo., co . .oN g,o. A , , , , , , , , , , _
t c,m - ;
U
. . LICENSEE EVENT REPORT (LER) ($'s*L', o'N M,;'Jo$'!?o"$',,T ..cfD.' ,TM"% '
2 TEXT CONTINUATION ! $ "',",? 4 o'R;"o M '," R'C M l M M ",' M R2 PAPI WO mt u TION J '3 0 0 i Of MANAGEME NT AND DVDGtt,mASHINGTON, DC 70tS3.
8 ACILif, hAME tu DOCE41 NUMSI A (2) 4th NUM$th q$6 PADE (3' S:quoyah Nuclear Plant, Unit 2 "'" "OW UsU o l5 lo [o l013 b 18 91 0 Olo l 8 -
0b OI3 0' 0 16 gamn ,. ., t M.,wwcw m e DESCRIPTION OF EVENT (Continued)
Th3 process used by the TD to evaluate the out-of-sequence situation was not as sp;cified by Section 7.9 of Administrative Instruction (AI) 47, " Conduct of Testing."
AI-47 requires an out-of-sequence situation to be documented as a test deficiency and ,
rsquires the proposed corrective action to be reviewed and approved by the responsible I supervisor and by the SOS. A review of instruction prerequisites, preceding steps, control logic, and equipment confiE uration is also required. AI-47 urges the TD to exercise caution and judgement before proceeding and advises the TD to resist the strong-t;ndency to simply skip back and perform the omitted steps. Completion of AI-47 training is a prerequisite for being a TD. l The unit tripped at 0134 EDT when Step 4.4 was performed out of sequence. Step 4.4 directs the performer to turn the SSPS Train A multiplexer test switch to the normal position. This action passes the switch through the " input-error-inhibit" position, which results in a momentary general warning alarm on SSPS Train A that clears when the switch reaches the normal position. When SI-90.82 is performed in the proper sequence, J this step is completed before the bypass breaker for Train B is placed in service.
During the performance on April 10, 1990, however, when the multiplexer test switch passed through the input-error-inhibit position and caused a momentary Train A general warning alarm with the Train B general warning alarm already in because the bypass breaker had been placed in service, the SSPS functioned as designed and a reactor trip occurred.
After the trip, Operations personnel responded using Emergency Procedures E-0, " Reactor Trip or Safety Injection," and ES-0.1, " Reactor Trip Response," and General Operating Instruction (GOI) 3. " Plant Shutdown From Minimum Load to Cold Shutdown," to stabilize the unit. The plant response during and after the trip is discussed later in this
.raport. Overall, plant systems responded properly, and the shutdown posed no danger to plant employees or the general public.
Limiting Condition for Operation (LCO) 3.7.1.2 (auxiliary feedwater system) was entered at 0235 EDT on April 10, 1990, when the turbine-driven auxiliary feedwater pump (TDAFWP)
(EIIS Code BA) steam supply was swapped from steam generator (S/G) (EIIS Code AB) No. 1 to S/G No. A because of limit switch problems on the trip and throttle valve position.
S/G No. 4 is a qualified TDAFWP steam supply, however, because it cannot automatically swap to an alternate steam supply, the TDAFWP steam supply system was considered inoperable. The limit switch problems were subsequently resolved, and the TDAFWP steam supply was returned to S/G No. 1. LCO 3.7.1.2 was exited at 0255 EDT.
C_AUSE OF EVENT The root cause of the reactor trip has been attributed to a personnel error by the TD cnd his supervisor (who was acting as one of the test performers in the AIR) in that procedure steps were not followed in sequence, and an inadequate amount of oversight direction was provided after the out-of-sequence aituation was discovered. The TD and supervisor acted inappropriately in response to the out-of-sequence situation by not
-following the guidance of Section 7.9 of AI-47.
NAC Penn 3.SA (6491
C tonM 3esa u s Nucttu s (GULl.T v cOMMassiON APPRDvtD DMD NO. 31t44104 5x?Gil 4'30!2
, LICENSEE EVENT REP RT (LER) !J.'6*t'&*Ji?RdOJ'85tW .o*fTl IE" '".'$
TEXT CONTINUATION FJ"li,n'. ",!"M &fGi 3EU'
"'ita','A'Ji"ratna'Reic?* ace'& 0??ci OF MANAGEME NT AND DVDGtt.W A$HINGTON. DC 20h03.
f ACittiV hAMt til DOCElf NUMeth (In ten Nuppta ici PAGE 136 S;quoyah Nuclear Plant, Unit 2 vtaa " W ." '
%*,3 0 l5 l 0 l 0 l 0 l3 l 2 l8 910 -
0 l0 $ -
0l0 0l4 OF 0 l6 text u . w. wec % amawim ANALYSIS OF EVENT This event is being reported in accordance with 10 CFR 50.73(a)(2)(iv), as a reactor protection system actuation that was not part of a preplanned sequence. As shown by the following discussion of plant response during and after the trip, plant systems and parameters behaved in a manner consistent with the responses described in the SQN Updated Final Safety Analysis Report (UFSAR). Consequently, it can be concluded that there were no adverse consequences to the health and safety of plant personnel or the g:neral public as a result of this event.
Lactor Coolant System (RCS) Pressure Bsfore the event RCS pressure was 2,232 psig. After the trip occurred, the RCS pressure dropped as low as 2,020 psig and rose as high as 2,250 psig before stabilizing at 2,230 psig. These values are comparable to values shown in UFSAR for this type event. Overall, RCS pressure responded as expected.
RCS Temperature B3 fore the event, RCS average temperature (Tavg) was 578 degrees F. After the trip, T:vg dropped to 541 degrees F. The operators exercised control in accordance with the guidelines of ES-0.1 and maintained Tavg above 540 degrees F. After the event Tavg stabilized at 548 degrees F. Because Tavg remained within procedural limits, no emergency boration was required.
Pressurizer Level Pressurizer level was 60 percent before the trip. During the event, the level decreased to 27 percent as compared to the program level of 26 percent. The level stabilized within limits of the control system and within the bounds of the accident analysis.
Forced / Natural Circulation All four reactor coolant pumps remained in operation for the duration of the event.
Consequently, no UFSAR assumptions were challenged.
Containment Pressure. Temperature, and Radiation No perturbations were observed in containment pressure, temperature or radiation icvels. Consequently, no technical specification (TS) requirements or UFSAR assumptions ware challenged.
Heatup/Cooldown Limits TSs limit the RCS cooldown rate to 100 degrees F in any one hour period. Based upon strip chart-recorder traces, this cooldown limit was not exceeded during this event. No haatup was experienced during the event.
. NRC tem 305A (649)
A u.. NucaAa tova, .vCo g, M . .
y ,,,,,, ,,, ,,.,,,,,,,,
(IPCES 4/3092
. . LICENSEE EVENT REPORT (LER) ',8,ls*f'Mo',yiM *JUoS**o*i',/ ..cffl ,7%1"'s j
, TEXT CONTINUATION !?,5"n'".lf,"dS'"?d M '?"f'UQ'#','!/0N,"/ "Mf"n i WA,','i, JJi*ts'a*a',#en?%?&L'th ^0?ili 0, MA v&Gt ME NT AND DVDGif WA$HINGTON. DC 20bO3.
9 ACIL,1Y hAMt (y pockg1 NQnIDLR W Lt fl HQM$$ M ($1 PA06 tai S;quoyah Nuclear Plant, Unit 2 "'" "OU' '
7#M o l6 l 0 l 0 l 0 l 312 l8 910 -
O b l8 -
) 10 015 0F 0 16 - ;
text a . , w. w we i a.s4 w nn 1 I
ANALYSIS OF EVENT (Continued)
I Reactor Power B] fore the trip, reactor power was being maintained at 100 percent rated thermal power.
After the trip, power decreased as expected.
Steam Pressure B3 fore the trip, S/G pressure varied from 850 to 860 psig. After.the trip, S/G pressure increased to slightly over 1,000 psig. Steam pressure stabilized at no-load pressure as >
RCS Tavg stabilized at-548 degrees F. No TS requirements or UFSAR accident analyses ware challenged. +
Fe-dwater Flow ,
Fs:dwater flow was steady at 100 percent flow before the trip with all four main fc dwater regulator valves in automatic. The main feedwater system responded as 0xpected after the trip. Operators took manual control of the TDAFWP to control the RCS Tcvg following the trip. The auxiliary feedwater system operated as designed.
Th9 TDAFWP steam supply was swapped to S/G No. 4 because of limit switch problems on the -
trip and throttle valve as previously discussed. The limit switch problems were rcsolved and the steam supply was returned to S/G No. 1 after approximately 20 minutes.
Steam Flow Bafore the trip, steam flow was steady at 100 percent flow. Steam flow decreased rcpidly following the reactor trip as expected. The steam flow response was bounded by UFSAR accident analyses.
S/G Level Before the event, levels in all four S/Gs were steady at 44 percent. The S/G 1evels responded within acceptable limits following the trip.
Shutdown Margin B; fore the trip, the reactor was. operating with control rods above the minimum insertion limits. Thus, by definition, adequate shutdown margin was available. Following the trip, RCS cooldown occurred as previously described. Adequate shutdown margin was maintained by conformance to ES-0.1 guidelines and by performance of SI-38, " Shutdown Margin." at 0234 EDT. No TS or accident analysis assumptions were violated.
NMC P.rm 3 6A (6 89)
g ge,,,onu ma us Nuc6un sive.ioav commimoN y,, ,,,g , ,, ,
I XPI'.t3. 4/3092
. . LICENSEE EVENT REPORT (LER) f,N;"ETAvifudWoMS%il,%cfW ,T" '"'s J' TEXT CONTINUATION ?"".',TA';!".'2"3i 3E"O R'e'*7l# '"' "M"f!
0 uANAosu NtANotuocat o,?",'.Va".M!",'la'A*'.=wassiNotow.oc mos-ie?
l 8 AclLiiv 8sAME He oocatt Nuutta (Il atm NUMeth 161 tA04 (31 Sequoyah Nuclear Plant, l' nit 2 "*a " h0P." %*,9 1 o l5 l0 jo l0 l 3l2 l 8; 9l0 -
0l0l8 -
0l0 Ol6 0F 0 16 '
f tKT (# morp slusse 4 seve*ed, use esistoomst NAC 7enn 3554U tih CORRECTIVE ACTION Th3 immediate action taken by the operators was to stabilize the unit in accordance with th] governing instructions. A posttrip review team was assembled and an assessment of tha cause of the trip and response of the unit was begun.
S:veral corrective actions have been implemented as recurrence controls. The TD and supervisor involved have been given the appropriate level of disciplinary action. To prcvide a lesson learned to all site personnel, a site wide message was issued by the Site Director describing this event and its cause and emphasizing the personal rcsponsibility of each employee for performing his or her work correctly. The message clso reiterated the policy on what to do if a mistake is made in performing a task, i.e., work is stopped immediately and any problems are resolved before proceeding.
.In addition, as a'long-term effort to reduce personnel errors, a Human Performance Enhancement System (HPES) program is being developed at SQN. This aggressive program will use an 11-part seminar developed by the Institute of Nuclear Power Operations from ir 'sstry experience gained through the evaluation of hundreds of situations involving hu.an performance. These seminars describe the major variables that have been identified as impacting human performance and are designed to provide a better understanding of human performance, and the factors that influence human behavior. The information presented builds on previously acquired technical, academic, and practical knowledge and is expected to result in a reduction of the number of events resulting from human errors.
ADDITIONAL INFORMATION There have been three previously submitted LERs reporting reactor trips that occurred as the result of personnel error by instrument mechanics during performance of surveillances SQRO-50-327/87005, 328/85001, and 328/88024. Previous corrective cetions have included counselling on the importance of following procedures, review of cvents for lessons learned, and disciplinary action. TVA believes these actions were appropriate to minimize potential for recurrence. However, recognizing random human oversight / errors cannot be totally eliminated, efforts must always be ongoing to cmphasize attention to detail. As described above TVA is emphasizing and providing cdditional focus through HPES.
COMMITMENTS None.
0825h WRc Poem se6A (649)