d eeoe N

e o$bY$$n R wGO( $O00 hnoa Florida Power C O h P O H A T 10 N June 6, 1979 Mr. Robert W. Reid Chief Operating Reactors Branch #4 Office of Nuclear Reactor Regulation U.S. Regulatory Commission Washington, DC 20555

Subject:

Docket No. 50-302 Operating License No. DPR-72 Reactor Cavity Annulus Seal Ring Support

Dear Mr. Reid:

In response to an NRC letter dated February 2,1978, analyses were per-formed which showed that the seal ring, while positioned on the original designed seal ring support, could become a missile during operation due to a LOCA pipe break inside the reactor cavity.

Additional calculations were performed to show that the seal ring missile could impact the CRDM shroud with suf ficient energy to damage both the shroud and the control rods.

Due to the above referenced analyses and calculations the design of a new seal ring support system is currently being reviewed by Florida Power Corporation.

The new design holds the seal ring, during operation, in a raised position which would alleviate the seal ring from becoming a poten-tial missile in the event 'f a LOCA.

Since the seal ring is only used during refueling and until FPC and the NRC approve the new seal ring support system, FPC will store the seal ring on the floor of the containment ouilding (EL. 160'-0") during plant operation.

Once the new support system is approved and installed the seal ring will be removed from the floor and placed on the new support system.

2284 286 7006120 %

[

General Office 32o1 Thirty-fourin street soutn. P O Box 14042. St. Petersburg. Florata 33733 e 813-866-5151

Mr. Robert W. Reid Page Two June 6, 1979 Storing the seal ring on the floor will in no way af fect the safe and effi-cient operatiota of the plant.

Should you have any questions concerning this matter, please contact this office.

Very truly yours, FLORIDA POWER CORPORATION

[d.

. dre dom W.

P.

Stewart Manager Nuclear Operations ETeke%01(D47) 2284 287

STATE OF F'.0RIDA COUNTY OF PINELLAS W.

P. Stewart states that he is the Manager Nuclear Operations, of Florida Power Corporation; that he is aut',aorized on the part of said company to sign and file with the Nuclear Regulatory Commission the information attached hereto; and that all such statements made and cntters set forth therein are true and correct to the best of his knowledge, information and belief, e

v

'jLL W.

P.

Stewart Subscribed and sworn to before me, a Notary Public in and for the State and County above named, this 6th day of June, 1979.

b(&C Ch Notary Public/

Notary Public, State of Florida at Large, 2284 288 My Commission Expires: July 25, 1980 (CRPNotary 1 D12)