ML18082A762
Text
,
~**
I I f
~
I Docket Nos:
50-272, 50-311, 50-327' 50-328 MEMORANDUM FOR:
Olan Parr, Cnief, Auxiliary Systems Branch, OSI FROM:
Themis P.
Speis~ Chief, Reactor Systems Branch, OSI
SUBJECT:
AFW FLOW REQUIREMENTS FOR SALEM AND SEQUOYAH Reactor.Systems Branch has reviewed responses.by Salem, Units 1 and 2, and S~quoyah, Units 1 and 2, to the. NRG information request of September 21, 1979, "Basis for Auxiliary Feedwater System Flow Requirements.
11 Our comments are as follows:
- 1.
The auxiliary feedwater system must have a capacity to supply at least 440 gallons per minute total (to the steam generators to meet referenced
,analyses' assumptions).
- 2. 'The above auxiliary feedwater capacity must be supplied to at least two steam generators. (in. order. to provtcle adequate heat transfer area).
- 3.
The aux*il iary feedwater system must be g~arariteed to satisfy requirements inumbers 1 and 2 for an initiating ~tv.ent pl us Auxiliary Systems Branch failure Griteria for auxiliary feedwater systems"
- 4.
The licensing ana.1yses (feedwater 1 ine break) assume operator action at 10 minutes to properly distribute auxiliary feedwater flow.
Auxiliary Systems Branch should determine the acceptability of this assumed time for
- operator actions to assure adequ*ate aux*il iary feedwater system performance following a feedwater 1 ine break event.
- 5.
Reactor Systems Branch considerations impose no upper bound for maximum auxiliary feedwater. flow rates permissible for these plants; however, a bound may be set /lD~ased on a1nother branch's Branch criteria 7 for example, Containment Systems Branch.
Containment Systems may be consulted to-verify maximum* penrnissible auxiliary feedwater flow rate.
Themis P. Speis, Chief Reactor Systems Branch Division of Systems Integration
..,£~~t ~:.=..... ~:... ?:.:.:.. *~~~.'... =~~:... ~7.~: l.. P.~.l.:[!~§......... P.?.:ItB.................
eURNAMI:~
.......................... ***********...'************ **** F.Qr.r.;.P.~IJl.._...... Y.P.?:,.\\J.~r.?:._...... *******
DATE~................................................... ** Q7.f../Q....f.'?>.Q.. Q?.f...Ji~..../~Q...... 9.U..,i)....l~.9...... ~.?l.1.J.
.l~.~.
NJlC l'ORM 318 (9*76) NB.CM 0240 "It. u.s. OOVl!RNM*NT l'RINTING Ofl'P"ICI!!:: lil71
- 2115 - 799