ML17335A175

From kanterella
Jump to navigation Jump to search
LER 98-005-00:on 980715,potential for HELB to Degrade Component Cooling Water Sys Was Noted.Investigation & Analysis of Signficance of Event Is Continuing.Method May Be Developed to Protect CCW Pump area.W/980814 Ltr
ML17335A175
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 08/14/1998
From: Mangan P, Sampson J
AMERICAN ELECTRIC POWER CO., INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
LER-98-005-01, LER-98-5-1, NUDOCS 9808190100
Download: ML17335A175 (6)


Text

HIIICII'ldllClt'4lllo I'VVifL~

Cook Noctear P(ant One Cook Place Bridgrnan. MI 49106 6>6465 5901 AMERICAN EI.ECTRIC

~WER August 14, 1998 United States Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Operating License DPR-74 Docket No. 50-316 Document Control Manager:

lllhfll la ill In accordance with the criteria established by 10 CFR 50.73 entitled Licensee Event i d:

98-005-00 Sine ely, J. R. Sampan Site Vice President lmbd Attachment J. L. Caldwell (Acting), Region III B. P. Powers P. A. Barrett J. B. Kingseed R. Whale D. Hahn Records Center, INPO NRC Resident Inspector Enclosure 3

I!RC Form 366 U.S. NUCLEAR REGULATORY COMMISSION APPROVKD SY DMS NO. SI504IOS (4-95) EXPIRES 04/Se/SS ESTSAATED SVRDKN PER RESPONSE TO COI/PLY WITH TIOS MANDATCRY LICENSEE EVENT REPORT (LER) INFORMATIONCOLLECTCN REOVESTI 50 0 HRS. REPORTED LESSONS LEARN D ARK NCORPORATEO INTO THE UCKNSING PROCESS A)ID FED BACK TO V/DVSTRY. FORWARD COMMENTS REGARDO/G SVRDEN KSTNATE TO THK INFORMATICNAND RECORDS MANAGEMKNTSRANCH IT@ FS1). U.S. NUCLEAR REGVIATORY COMIWSSION. WASHINGTON. DC 201$ S.C00I. ANO TO THK (See reverse for required number of PAPERWORK REDVCTION PRO/ECT IM$0410S). CFF/CE 0 MANAGEMENT AND BUDGET, WAS/0 NGTON. DC 20101 digits/characters for each block)

FACILITYNAME (1) DOCKET NUMBER (2) PAGE (2)

Cook Nuclear Plant Unit 2 50-316 1of1 TITLE (0)

Interim LER - Potential for High Energy Line Break to Degrade Component Cooling Water System EVENT DATE (5) LER NUMBER (6) REPORT DATE (7) OTHER FACILITIES INVOLVED (8)

MONTH DAY YEAR YEAR A ILI NAM NUM SEQUENTIAL REVISION MONTH DAY Donald C. Cook- Unit1 50-315 07 OPERATING 15 98 98 NUMBER 005 NUMBER 00 '8 14 98 A ILI NAM THIS REPORT IS SUBMITTED PURSUANT TO THE REQUIREMENTS OF 10 CFR g: (Check one or more) (11)

D CKE NUMBER MODE (9) 20.2201 (b) 20.2203(a)(2)(v) 50.73(a)(2)(i) 50.73(a)(2)(viii)

POWER 20.2203(a)(1) 20.2203(a)(3)(i) 50.73(a)(2)(ii) 50.73(a)(2)(x)

LEVEL(10) 20.2203(a)(2)(i) 20.2203(a)(3)(ii) 50.73(a)(2)(iii) 73.71 20.2203(a)(2)(ii) 20.2203(a)(4) 50.73(a)(2)(iv) OTHER eI Absvsot below or 20.2203(a)(2)(iii) 50.36(c)(1) 50.73(a)(2)(v) SI NRC Form S66A 20.2203(a)(2)(iv) 50.36(c)(2) 50.73(a)(2)(vii)

LICENSEE CONTACT FOR THIS LER (12)

NAME TELEPHONE NUMBER (In'/de Ares Code)

Mr. Pat Mangan - Mechanical Design Manager 616/697-5198 COMPLETE ONE LINE FOR EACH COMPONENT FAILURE DESCRIBED IN THIS REPORT (13)

CAUSE SYSTEM COMPONENT MANUFACTURER REPORTABLE TO CAUSE SYSTEM COMPONENT MANUFACTURER REPORTASLE NPROS TO NPRDS n,,..

$ I,gI SUPPLEMENTAL REPORT EXPECTED (14)

EXPECTED M NK AY YES NO SUBMISSION DATE (15) 10 30 98 (If Yes, complete EXPECTED SUBMISSION DATE).

Abstract (Limit to 1400 spaces, i.e., approximately 15 single. spaced typewritten lines) (16)

On July 15, 19981 with Unit 1 and Unit 2 in Cold Shutdown, it was determined that the potential existed for a postulated critical crack in a Unit 2 main steam line to degrade the ability of adjacent Component Cooling Water (CCW) pumps to perform their design function. The CCW pumps for both units are adjacent to one another in a semi-enclosed area in the Auxiliary Building. Adjacent to the pumps is a pipe chase enclosing two Unit 2 main steam lines and a main feedwater line, which can be accessed through any of 3 doors. Although the pipe chase walls provide a qualified High Energy Line Break (HELB) barrier, no calculation could be found which shows that the doors would withstand the energy released from a postulated critical crack. As the adjacent CCW pump motors and other equipment are not qualified for a high temperature/high humidity environment, this was determined to constitute an unanalyzed condition. An ENS notification was made on July 15 at 1521 hours0.0176 days <br />0.423 hours <br />0.00251 weeks <br />5.787405e-4 months <br /> EDT in accordance with 10CFR50.72(b)(2)(i). This interim LER is therefore submitted under 10CFR50.73(a)(2)(ii)(B) for an unanalyzed condition The investigation and analysis of the significance of the event is continuing. Based on the results of the investigation and analysis, a methodmay be developed to protect the CCW pump area from the effects of the postulated crack. It is anticipated that an update to this LER will be submitted by October 30, 1998.

NRC FORM 366 (4-95)

R.P. Powers September 27, 1999 Please contact me at 301-415-1345 if you have any questions regarding this request. This request is covered by the existing OMB clearance number (3150-0104) for NRC staff followup review of events documented in,LERs. Your response to this request is voluntary and does not constitute a licensing requirement.

Sincerely, Original signed by:

John F. Stang Sr. Project Manager, Section 1 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-315 and 50-316

Enclosures:

As stated cc w/encls: See next page Distribution:

Docket File PUBLIC PD31r/f JZwolinski/S Black OGC J. Stang (2)

ACRS G. Grant, Rill S. Mays RES/DREA/OERAB S. Weerakkody, RES/DREA/OERAB P. O'Reilly S. Mays DOCUMENT NAME: G:)PD31>DCCOOK1 2<dcc98st.wpd To receive a copy of this document, indicate in the box: "C" = Copy without attachment/enclosure 'E" = Co with attachment/enclosure "N" = No co OFFICE PM:PD3 E LA:PD31 E SC:PD 1 NAME JStan EBarnhill CCrai, DATE 0/>'7/ 9 / J99 / /99 /99 OFFICIAL RECORD COPY

~ ~

ft l

t 4

R.P. Powers September 27, 1999 Please contact me at 301-415-1345 if you have any ques'..:ons regarding this request. This request is covered by the existing OMB clearance number (3150-0104) for NRC staff followup review of events documented in LERs. Your response to this request is voluntary and does not constitute a licensing requirement.

Sincerely, Original signed by:

John F. Stang, Sr. Project Manager, Section 1 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-315 and 50-316

Enclosures:

As stated cc w/encls: See next page Distribution:

Docket File PUBLIC PD31r/f JZwolinski/S Black OGC J. Stang (2)

ACRS G. Grant, Rill S. Mays RES/DREA/OERAB S. Weerakkody, RES/DREA/OERAB P. O'Reilly DOCUMENT NAME: G:EPD31>DCCOOK1 2<dcc98st.wpd To receive a copy of this document, indicate in the box: "C" = Copy without attachment/enclosure ~E" = Co with attachment/enclosure "N" = No co OFFICE PM:PD3 ','/ E LA:PD31 E SCPD 1 ~ E NAME JStan EBarnhill CCrai DATE / J99 / /99 'i/I 699 OFFICIAL RECORD COPY