ML17334A139

From kanterella
Jump to navigation Jump to search
Evaluation of High Energy Line Breaks & Consequential Control Sys Failures (IE Info Notice 79-22 Summary Rept)
ML17334A139
Person / Time
Site: Columbia 
Issue date: 02/28/1983
From: Parker J
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
Shared Package
ML17277A605 List:
References
REF-SSINS-6835 NUDOCS 8306200251
Download: ML17334A139 (56)


Text

EVALUATION OF HIGH ENERGY LINE BREAKS AND CONSEQUENTIAL CONTROL SYSTEMS FAILURES (IE INFORMATION NOTICE 79-22

SUMMARY

REPORT)

WASHINGTON PUBLIC POWER SUPPLY SYSTEM NUCLEAR PLANT NO.

2 RICHLAND'ASHINGTON Prepared By:.E. Parker Reviewed By:

S.R. Kirkendall Approved By: ~Med.

5 5 &

W.G.

Conn Senior Group Supervisor hgggg 0 06)P 6200251 8

5000397 PbR

TABLE OF CONTENTS PAGE 1 ~ 0 INTRODUCTION 2 '

1.1 OBJECTIVE 1 ~ 2 APPROACH

1.3 CONCLUSION

S ANALYSIS CRITERIA 1

1 2

2 '

2 '

APPLICABLE EVENTS Criteria for Event Applicability Applicable Events Control System Components Identification HIGH ENERGY LINES 2.2.1 'riteria for High Energy Lines 2.2.2 Criteria for Break Locations 2.2.3 Break Effects 2.2.3.1 Pipe Whip 2.2.3.2 Jet Impingment 4

4 10 11llll 12 12 3

~ 0 2

~ 3 ZONE DETERMINATION HELB POSTULATION/CONTROL SYSTEM DAMAGE 14 14 3 '

SINGLE EVENT ANALYSIS FOR POTENTIAL EVENTS 3 ~ 1 ~ 1 3 '

~ 2 3 '

~ 3 3 '

~ 4 3

~ 1 ~ 5 Loss of Feedwater Heating 3.1.1.1 Mechanism for Failure Feedwater Controller Failure Maximum Demand 3 '.2.1 Mechanism for Failure Pressure Regulator Fail-Open Inadvertent Opening of a Safety or Relief Valve Pressure Regulator Fail Closed 15 15 18 18 18

1 1l g

I

TABLE OF CONTENTS (Continued)

PAGE 3.1.5.1 Mechanism for Failure 3.1.6 Generator Load Rejection, Bypass On 3.1.6.1 Mechanism for Failure 3.1.7 Generator Load Rejection, Bypass Off 3 '

~ 7.1 Mechanism for Failure 19 19 19 20 20 3.1.8 Turbine Trip, Bypass On 3.1.8.1 Mechanism for Failure 3.1.9 Turbine Trip, Bypass Off 21 22 3.1.9.1 Mechanism for Failure 3.1.10 Inadvertent MSIV Closure 22 23 3.1.10.1 Mechanism for Failure 23

'3.1.11 Loss of Condenser Vacuum 3.1.12 Loss of Feedwater Flow 3.1.12.1 Mechanism for Failure 24 24 24 3.1.13 Loss of Partial or Total Recirculation Flow 25 3.1.14 Inadvertent HPCS Pump Start 25 3 '

MULTIPLE EVENT ANALYSIS 26 3.2.1 3 ~ 2 ~ 2 Worst Case Event Combinations Other Event Combinations 26 28 3.2.2.1 Loss of Feedwater Heating and Loss 29 of Feedwater Flow 3.2.2.2 Loss of Feedwater Heating and Turbine Trip, Bypass On 3.2.2.3 Loss of Feedwater Heating and Inadvertent MSIV Closure 29 29

I

I 1

e'ABLE OF CONTENTS (Continued)

PAGE 3 '

Loss of Feedwater

Heating, Turbine Trip, Bypass On and Inadvertent MSIV Closure 30 3 ' ' '

3 ' '-6 Loss of Feedwater Heating and Pressure Regulator Fail-Closed Loss of Feedwater Heating and Feedwater Controller Failure-Maximum Demand 30

'0 3 ~ 2 ~ 2 ~ 7 Loss of Feedwater

Heating, Inadvertent MSIV Closure, Pressure Regulator Fail-Closed and Loss of Feedwater Flow.

30 Figure 1

Figure 2

Table 1

Approach Sequence Zone Map Cone Length Zone Summary

II

)

I I

INTRODUCTION OBJECTIVE The objective of this analysis was to determine if any non-safety grade control equipment, if subjected to the adverse environment of a High Energy Line Break (HELB), could impact the WNP-2 safety analysis and/or the adequacy of the protec-tive functions performed by the plants safety grade equip-ment.

Investigations conducted were consistent with concerns identified by IE Information Notice 79-22 and in answer to WNP-2 NRC question. 031.137.

1.2 APPROACH The approach described below outlines the. actions completed during this review.

The sequence of this approach is shown graphically in Figure 1.

1.2.1 Identify non-safety grade control systems which may impact reactor pressure, water level, Critical Power Ratio (CPR)g Feedwater (FW) temperature and/or the performance of safety-grade equipment.

1.2.2 Establish criteria for high energy line determination, break postulation and consequence evaluation.

1.2.3 Identify and locate all high energy lines.

For the reactor building, pipe break studies previously completed were referenced for line and break locations as well as targets.

Establish Criteria for Event Applicability Establish Criteria for High Energy Line Identify Applicable Control Systems Identify High Energy Lines Identify Control Systems Components Locate High Energy Lines Locate Control Systems Components In High Energy Line Areas Establish Break Location Criteria Postulate Pipe Break a Determine Control Systems Affected Establish Break Effect Criteria Evaluate Consequences Identify Required Actions FIGURE 1

1l l

I

~

~

1.2.4 For each applicable control system, identify and locate instrumentation, equipment, process tubing and control cables from all systems in high energy line areas that could affect the control system's operation.

1.2.5 Postulate breaks in identified high energy lines.

Identify control, system damage incurred due to jet impingement and/or pipe whip for each break.

l. 2.6 Evaluate the consequences resulting from each postulated break.

If a single control system is affected, verify that the event incurred is bounded by FSAR Chapter

15. If more than one control system is affected, determine if the com-bined event is bounded by FSAR Chapter 15 analysis.

If the single or combined event is not bounded, analyze an event which is bounding and determine the consequences.

1.2.7 For any single or combined event analyzed as unacceptable, define required operator actions or hardware modifications.

1.3 CONCLUSION

S A detailed and comprehensive study was completed to determine if any non-safety grade control equipment, if subjected to the adverse environment of a HELB, could impact the WNP-2 safety analysis and/or the adequacy of protective functions performed by the plants safety grade equipment.

The entire plant has been evaluated for the effects of high energy

line breaks on applicable control systems.

Worst case failure of all equipment, instrumentation, process

tubing, control cables and power cables was considered.

It was determined, that there are events which fall outside the limits of FSAR Chapter 15 transient analysis.

In eva-luating these new events, a single bounding event, incor-porating the worse case combination of each of the new

events, has been postulated and analyzed using a General Electric computer code.

The results of this analysis indi-cated that the reactor Delta Critical Power Ratio (4CPR) exceeded the FSAR required operating limit of 0.18 for a very short duration.

However, the WNP-2 FSAR Chapter 4.4. indica-tes that even if boiling transition should occur for a short
duration, no fuel damage would be expected to occur.

These results are well within the bounds of the design basis acci-dents analyzed in Chapter 6 of the WNP-2 FSAR.

The protection functions performed by safety grade equipment are not significantly impaired by the effect of any-plant HELB.

Therefore, safe plant shutdown is assured at all times.

No potential event results in any increase in risk to the health and safety of the public.

II I

i

~

I

~

~

2.0 2.1 ANALYSIS CRITERIA APPLICABLE EVENTS The Chapter 15 transient analysis was used as a guide in establishing the applicable analysis events.

Determination of the final list of applicable events was accomplished by evaluating the Chapter 15 transient events against tne cri-teria in Section 2.1.1.

These applicable events were then used in the analysis as the bounding events which could affect either a plant safety system or a critical reactor parameter (level, press, CPR, etc.).

All plant control systems are then analyzed to determine their ability to result in one of these bounding applicable events.

2.1.1 Criteria for Event Applicability

~

~

1.

Events must be capable of occurring at 100%

reactor power.

2.

Events must result from a HELB

'I If an event did meet these criteria but tended to reduce the severity of the overall consequence when combined with other

events, the single event was analyzed alone.

2.1.2 Applicable Events

1)

Loss of Feedwater Heating (Chapter 15.1.1).

Applicable Event 2)

Feedwater Controller Failure - Maximum Demand (Chapter 15.1.2).

Applicable Event 3)

Pressure Regulator Fail Open (Chapter 15.1.3).

Applicable Event 4)

Inadvertent Opening of a Safety or Relief Valve (Chapter 15.1.4).

Applicable Event 5)

RHR Shutdown Cooling Malfunction Decreasing Temperature (Chapter 15.1.6).

This event is not applicable as it cannot occur at 100%

reactor power.

6)

Pressure Regulator Fail - Closed (Chapter 15.2.1).

Applicable Event 7)

Generator Load Rejection, Bypass On (Chapter 15.2.2).

Applicable Event 8)

Generator Load Rejection, Bypass Off (Chapter 15.2.2).

Applicable Event

I I

~

.p I~

~

~,J

~

C 9)

Turbine Trip, Bypass On (Chapter 15.2.3).

Applicable Event 10)

Turbine Trip, Bypass Off (Chapter 15.2.3).

Applicable Event ll)

Inadvertent MSIV Closure (Chapter 15.2.4).

Applicable Event 12)

Loss of Condenser Vacuum (Chapter 15.2.5).

Applicable Event 13)

Loss of Auxiliary Power Transformers (Chapter 15.2.6).

This event results in an immediate reactor scram decreasing the severity of any other event combined with it.

This event is not applicable.

14)

Loss of All Grid Connections (Chapter 15.2.6).

This event is not the result of a high energy line break and is therefore not applicable.

In addition, this event is bounded by generator load rejection, bypass on.

15)

Loss of Feedwater Flow (Chapter 15.2.7).

I Applicable Event 16)

Feedwater Piping Break (Chapter 15.2.8).

This event is bounded by loss of feedwater flow and is not considered separately.

17 )

Failure of RHR Shutdown cooling (Chapter

15. 2. 9 ).

The RHR Shutdown Cooling System is not in operation at 100%

power.

Therefore, this is not an applicable transient event.

18)

Trip of One Recirculation Pump Motor (Chapter 15.3.1).

A reduction of recirculation flow reduces the severity of any other event or event combination.

This event is bounded by the analysis presented in FSAR Chapter 15.3.1.

19)

Trip of Both Recirculation Pump Motors (Chapter 15.3.1).

A reduction of recirculation flow reduces the severity of any other event or event combination.

This event is bounded by the analysis presented in FSAR Chapter 15.3.1.

20)

Fast Closure of One Hain Recirculation Valve (Chapter 15.3.2).

A reduction of recirculation flow reduces the severity of any other event or event combination.

This event is bounded by the analysis presented in FSAR Chapter 15.3.2.

21)

Fast Closure of Two Main Recirculation Valves (Chapter 15.3.2).

A reduction of recirculation flow reduces the severity of any other event or event combination.

This event is bounded by the analysis presented in FSAR Chapter 15.3.2.

1

~

~

~

22)

Seizure of One Recirculation Pump (Chapter 15.3.3).

A reduction of recirculation flow reduces the severity of any other event or event combination.

This event is bounded by the analysis presented in FSAR Chapter 15.3.3.

23)

Recirculation Pump Shaft Break (Chapter 15.3.4).

A reduction of recirculation flow reduces the severity of any other event or event combination.

This event is bounded by the analysis presented in FSAR Chapter 15.3.4.

24)

Rod Withdrawal Error Refueling (Chapter 15.4.1.1).

This event is not applicable as it does not occur at 100%

power operation.

25)

Rod Withdrawal Error Startup (Chapter 15.4.1.2).

This event is not applicable as it does not occur at 100%

'ower operation.

26)

Rod Withdrawal Error At Power (Chapter 15.4.2).

This event is not applicable as it is not the result of a HELB.

27)

Control Rod Misoperation (Chapter 15.4.3).

This event is not applicable as it is not the result of a HELB.

28)

Abnormal Startup of Idle Recirculation Loop (Chapter 15.4.4).

1 This event is not applicable as it does not occur at 100%

power operation.

29)

Fast Opening of One Main Recirculation Valve (Chapter

-15.4.5).

This event is not applicable as it does not occur at 100%

power operation.

30)

Fast Opening of Both Main Recirculation Valves (Chapter 15.4.5).

This event is not applicable as it does not occur at 100%

power operation.

31)

Misplaced Bundle Accident (Chapter 15.4.7).

This event is not applicable as it does not occur at 100%

power operation.

32)

Rod Drop Accident (Chapter 15.4.9).

This event is not applicable as it is not the result of a HELB.

33)

Inadvertent HPCS Pump Start (Chapter 15.5.1).

As described, this event 'is the result of operator error.

However, the event is possible as a result of a HELB and is applicable.

I I

P

Control System Components Identification All plant system components were considered in this analysis.

For each event found applicable in Section 2.1.2, all com-ponents of any plant system which could result in that event were addressed in the analysis.

This included all ihstrumen-

tation, equipment, process
tubing, power cables and control cables.

Failure modes were considered as follows:

1)

Instrumentation When the instrumentation was mechanically damaged by a HELB, it was assumed to command controlled equipment to the worst failure mode.

2)

Equipment When the equipment was mechanically damaged by a HELB, it was assumed to fail in the worst failure mode.

3)

Process Tubing Process tubing was evaluated for the worst case of two failure mechanisms, crimping and rup-ture.

In the event of crimping, controlled equipment was considered to freeze in place.

For rupture, controlled equipment was considered to operate normally for a loss of signal.

4)

Power Cables F'ailure of power cables was assumed to act as a simple power loss, not necessarily a worst case failure mode.

Resultant control actions due to the power loss were considered.

10

5)

Control Cables Control cables were assumed to command controlled equipment to the worst failure mode.

2 '

HIGH ENERGY LINES The definition of high energy lines used in this analysis is based on the criteria established in Section 3.6.1 of the Standard Review Plan and Chapter 3.6.2 of the NNP-2 FSAR.

A summary of that criteria is presented below.

2.2.1 Criteria for High Energy Lines High energy lines were defined to include those lines whose process fluid exceeds a temperature of 200oF or a pressure of 275 psig during normal 100% power operation.

All piping systems larger than 1 inch NPS which meet this criteria for more than 2% normal 100% power operating time were included.

2.2.2 Criteria for Break Locations High energy lines not previously analyzed during other pipe break studies (Reference FSAR Chapter 3.6) were assumed to break at terminal ends and intermediate pipe fittings.

Those lines evaluated during previous studies for HELB were con-sidered to break as identified in those studies.

2.2.3 Break Effects HELB effects were evaluated in detail for damage due to pipe whip and jet impingement.

The general criteria used in eva-

luating the effects of pipe whip and jet impingement is pre-sented in Chapter 3.6.2 of the WNP-'2 FSAR.

A summary of that criteria is provided below.

2 '.3.1 Pipe Nhip Pipe whip was analyzed in the plane defined by the piping geometry.

Movement was analyzed in the direction of the jet reaction while hinging at the nearest rigid support,

anchor, or penetration.

The pipe was allowed to move in a radius about the hinge point until hitting a line of equal to or larger size, a reinforced concrete wall or column.

2.2.3.2 Jet Zmpingment Jet impingement was considered for all circumferential and longitudinal breaks.

Longitudinal breaks were postulated to occur in high energy lines 4 inches NPS and larger with a flow area equal to the flow area of the piping system.

Circumferential breaks were postulated to occur in high energy lines larger than 1 inch NPS with the two halves being displaced laterally by a distance of one pipe diameter rela-tive to each other.

To simplify the evaluation of the effects of jet impingement on targets, the jets were con-sidered to have an effective cone angle of 10', with a jet le'ngth equal to 2 times the distance required for the pressure of the fluid jet to diminish to 10 psig.

A sample

-12

calculation is provided below.

Table 1 provides a summary of jet lengths considered in the evaluation.

Concrete walls were considered to be an effective barrier against further cone propagation.

Sam le Calculation:

Line Size Di = 2" Pressure at Dz Pq 10 psi Pressure at Break ~ Pg

~ 1000 psi 10 P XAAM PzA2 PgAg Pg m

PgDg Dz Dz ~

Dz

~Pg mDg

/4

- Pz m 4 (r> + rz)'4

~ PzA2 Dx

/4 ~ Pz

~ 4 (rx + r2)

/4

= 4Pq (Dg /2 + Dq Tan 10')

(/PPa PPaa-1)

Da /2 Taa 10

[(/1000/10 - 1) 2/12] / 2(.176) 4.25 ft.

I Pa~

2Dz

~ 8.5 ft.

13

s

~

~

I

PROCESS PRESSORE Pi e Diameter 1000 si 900 si 800 si 700 si 600 si 500 si 400 si 300 si 200 si 100 si 50 si 25 si 2 II 8.5 7.5 6.4 5.7 4.2 3.3

.5 2 1/2" 10.6 10 9.4 8.7 7.1 6.3 5.3 4.1 2.5 1.5

.7 3 ~

12.7 12 11.2 10.4 9.5 8.6 7.5 6.3 1.7

.8 17 16 15 13.9 12.7 11.5 10 8 '

6.5 2.3 6"

25.5 24 22.5 20.8 19

17. 1 15 12.7 9.8 6.1 3.5 1.6 10" 34 42.5 32 40'0 37 '

27.8 35 25.5 31.8 23 28.6 20 25 16.9 21 13.1 16.4 8.1 10.2 4.7 5.8 2.2 2.7 nO 12" 51 48 45 38 34.4 30 25.3 19.6 12.2 3-3 14" 59.5 56 52.5 48.5 44.5 40 35 30 23 14.3 8.1 3.8 16 68 60 55.5 51 45.8 40 26.2 16.3 9.3 4.4 18" 76 72 67.5 62.5 57 51.5 45 29.5 18.3 10.5 4.9 20" 85 80 75 69.5 63.5 57.5 50.2 42 33 20.4 11.6 5.4 24 102 96 90 83.4 76 68 '

60 '

50.5.

39 24.5 6.6 30" 127 120 112.5 104 95.5 85.9 75.5 63.5 49 30.5 17.5 8.2 42" 178 168 157 146 134 120 105 89 69 43 25 11.5

2.3 ZONE DETERMINATION For purposes of this analysis, buildings were divided into zones for reference only (See Figure 2).

However, the effects of a given break were not confined to these reference zones.

They were instead based on the criteria established in Section 2.2, in the discussions of pipe whip and jet impingement.

3

~ 0 HELB POSTULATION/CONTROL SYSTEM DAMAGE 3.1 HELBs were analyzed for each zone (Section 2.3).

Targets were identified due to the resulting pipe whips and jet impingments.

The targets were then evaluated with the appli-cable control system components identified and located in Section 2.1.3; potential transient events resulted from this evaluation.

See Example 1 for a typical zone evaluation.

SINGLE EVENT ANALYSIS FOR POTENTIAL EVENTS All applicable transient

events, as determined by Section 2.1.2, found to be a potential event due to a HELB were ana-'yzed to determine the effect on critical reactor parameters.

Each identified event not discussed below was evaluated as a

part of the multiple event analysis performed in Section 3.2.

Single events bounded by the FSAR Chapter 15 transient analy-sis are discussed below.

14

I

~

~

V

284 2C4 2E4 2F4 ZC5 2DS 4

2KS 295 ZCS 286

, 206 2D6 2E6 276 2C6 287 207 2D7 2E7 2F7 207 288 208 2DB 2E8 2FB 208 289 209 2D9 2E9 2F9 209 QIO=

Qll 2ALO ZAII 2BLO 2811

'CIO 2CLL 2DIO 2DLI 2KLO 2ELI 2FLO ZFLI 2GIO I

ZOLL QZ 2AI2 2812 2CL2 2D12 2E12 2F12 2012 QL3 ZAI 3 2813 2013 ZD13 sc'I 3 2F13 2013 ZA14 2814 2014 2014 2814 2F14 2014 QLS 2AI5 2BLS 2015 2DL5 2EIS 2F15 2015 QI6 ZAL6 2816 2016 2D16 EI6 2716 2016 TURBINE BUILDING 471'LEVATION FIGURE 2.

1 I

i ~

~

~->> ~-

p. A ~

~

ZONE

SUMMARY

Bldg:

Turbine Elev:

471'one:2E10 BREAK/TARGET

SUMMARY

Line No.

o BS(7)-1 COND(4)-3 BS(7)-1 HV(12)-2 12" MS(2)-4 2" BS(6)-1 24" BS(8)-1 16" HD(9'-2 12" BS(1)-2 18" BS(6)-1 HV(9~-1 6" SS(10)-1

='20" BS(7)-1 Temp.

(oF) 541 358 216 365 448 358 358 216 282 282 170 282 453 Press (psig) 955 52 1

148 399 52 52 1

27 27 428 27 399 No.

Breaks None None 8

3 None 4

None 5

5 None 1

None 4

Jet (Feet) 0 21 10.5 0

6 53 7 '

Whip Damage No Yes Yes No No No Yes Targets None Cable Trays:

PBgCB,SB Cable Trays:

PBgCBgSBgPAJCA/SA None Cable Trays:

PA,CA,SA None (FW Trip)

Cable Trays:

CAgPAgCBgPB Target TARGET EVALUATION Event Evaluation Cable Cable Cable Cable Cable Cable Tray PB Tray CB Tray SB Tray PA Tray CA Tray SA None FW Temperature

Reduced, Turbine Trip None None FW Temperature Reduced None ZONE POTENTIAL EVENT

SUMMARY

Breaks in 16" HD(9)-2, 18" BS(6)-1 or 3" HV(12)-2 could result in a partial loss of FW heating and a turbine trip with bypass.

(2)

Breaks in 20" BS(7)-1 could result in a partial loss of FW heating.

(3)

Breaks in 20" COND(4)-3 could result in a total loss of FW.

Example 1

I

~

I

~

I

~

I I

~

~

~

t

~

~

~

3.1.1 Loss of Feedwater Heating Feedwater (FH) heating controls are located in the vicinity of high energy lines on the three main levels of the turbine building.

The-overall FW temperature control system is diversely segregated with each component failure capable of contributing only a small amount to the loss of feedwater temperature.

A strategically located high energy line break is potentially capable of damaging several controls resulting in a ramping feedwater temperature decrease.

As the tem-perature decreased, reactor power would increase until the APRMs initiated a reactor scram on high thermal power.

Any temperature decrease of approximately 65'F or greater would result in a scram and is therefore bounded by FSAR Chapter 15 transient analysis event 15.1.1, which assumes 100'F tern perature decrease.

For multiple event analysis including loss of feedwater

heating, a 65'F reduction in temperature will be considered.

This decrease will bring the reactor to a thermal power level just beneath the APRM scram point which is considered worst case for multiple event analysis.

l 3.1.1.1 Mechanism For Failure Feedwater heating can be reduced by various mechanisms; all requiring reduced feedwater (tube side) or steam (shell side) flow through the heaters.

15

Reduced feedwater flow.through the heaters requires conductor shorts simulating a valve movement demand signal in the cables controlling heater isolation and bypass valves, or damage to the valves themselves.

Reduced steam flow to the heaters also requires conductor shorts in valve control cables or level controllers, or damage to the valves or controllers themselves.

In addition, steam can be bypassed directly to the main condenser if controlling process tubing is ruptured, resulting in FW heater extraction steam bypass valves failing open.

Approximately 165 valves control flow to the 16 feedwater heaters.

A single cable short, tubing rupture or component

damaged, can in most cases alter the position of only 1 or 2

valves.

Valve control cables are normally 9 conductor cables.

A short resulting in valve movement requires the proper 2 conductors in these 9 conductor cables to selec-tively short without blowing circuit protective fuses.

Tube rupture cannot isolate heating steam but can dump steam to the main condenser and bypass the heaters.

All heaters are instrumented with high and low level alarms located in the control room.

All the major FW heater related motor operated valves have position indication in the control room.

Any HELB resulting in significant reduction of feed-water heating would not go unnoticed by plant operators.

16

I

~

~

3.1.2

~

~

Feedwater Controller Failure Maximum Demand Feedwater flow controls were reviewed for control system failures which could potentially drive the turbine controls to maximum demand.

The feedwater flow controller sums signals from reactor water level, steam line flow and feed-water flow and sends the resultant signal to the reactor feedpump turbines.

Reactor water level and steamline flow signals were found to be unaffected by any high energy line breaks.

Potential for generating a high feedwater flow demand signal as the result of HELB exists on the 441'nd 471'evels of the turbine building.

Damage to these signals was. considered to result in a feedwater controller failure maximum demand event.

Single event occurrence is bounded by FSAR Chapter 15 transient analysis.

3.1.2.1 Mechanism For Failure Feedwater controller failure maximum demand can occur in two ways, loss of fee'dwater flow signal or loss of feedpump turbine speed feedback to the controller.

Loss of'he feedwater flow signal requires open circuit of 2 separate cables or rupture of at least 2 process instrument lines.

These controls are located on the 471'evel of the turbine building.

Due to the nature of the 3-element feed-water flow controls, failure of this signal will not result

in the 146% upper limit demand as analyzed in FSAR Chapter 15.

The flow demand will be of a lesser

degree, decreasing as vessel level increases.

Loss of the feedpump turbine speed feedback to the controller requires open circuit of 2 separate cables.

These controls are located on the 441'evel of the turbine building.

Loss of both of these signals would drive the turbine valves wide open, similar to the event analyzed in FSAR Chapter 15.

This failure mechanism can only occur as a single event from a HELB and is bounded by FSAR Chapter 15 transient analysis.

3.1.3 Pressure Regulator Fail Open The DEH pressure regulator is designed to switch to manual control on a pressure regulator signal failure.

Control system analysis found no credible failures resulting in a pressure regulator fail open event due to a

HELB'.

inadvertent Opening of a Safety Relief Valve This event cannot occur due to a high energy line break out-side of containment.

3. 1. 5 Pressure Regulator Fail Closed Loss of signals positioning the governor and bypass valves could result in this event.

These signal cables are located on the 471'levation of the turbine building and could be

damaged by an HELB.

Single event occurrence is. bounded by FSAR Chapter 15 transient analysis.

3.1.5.1 Mechanism For Failure A pressure regulator fail-closec event as the result of a HELB would be a slow developing event.

Complete failure requires open circuit of the 8 s"'gnals (in 8 different cables) used in the positioning of the governor and bypass valves.

Open circuit,of these cables would allow controlled valves to slowly drift closed due to servo valve leakage.

Should a turbine trip occur during this event, the bypass valves would still remain operable during the trip transient.

3.1.6 Generator Load Rejection, Bypass On

~

~

A true generator load rejection cannot result from a high energy line break.

However, cable damage or hydraulic line damage could simulate this event and fast close the governor valves.

This event is considered and as a single event is bounded by FSAR Chapter 15 transient analysis.

3.1.6.1 Mechanism For Failure A generator load rejection, bypass-on event due to a HELB can result from control cable damage or damage to the turbine electro-hydraulic (FH) fluid lines.

These controls are located on the 471'nd 501'levation of the turbine building.

19

~

~

~

A single short requesting governor valve fast closure for overspeed protection control would appear as a load rejection to the reactor.

For all HELBs resulting in governor valve fast closure, Reactor Protection System (RPS) signal func-tions remained unaffected.

A rupture of the EH fluid lines controlling trip of the governor valves would also fast close these valves.

Again, for all HELBs resulting in governor valve fast closure, RPS signal functions remained unaf fected.

3.1.7 Generator Load Rejection, Bypass Off A true generator load rejection cannot result from a high energy line break.

However, hydraulic line damage could simulate this event and fast close the governor valves while disabling the bypass valves.

This event is considered and as a single event is bounded by FSAR Chapter 15 transient analy-sis

~

3.1.7.1 Mechanism For Failure A, generator load rejection, bypass off event due to the HELB can result from EH fluid line damage only.

These lines are located on the 471'evel of the turbine building.

The exact location for failure is uncertain as the HELB would have to rupture the governor valve EH fluid trip line and the bypass valve positioning EH fluid lines.

The large volume of EH 20

~

~

1

~

~

~

I

~

~

fluid contained near the bypass valves in accumulators and the positioning of the hydraulic lines makes this event very unlikely.

HELBs hitting the bypass valves were assumed to cause this event,

however, no break results in a loss of the turbine RPS signals function.

3.1.8 Turbine Trip, Bypass On Several high energy line breaks in the turbine building could result in this event by damaging cables and/or hydraulic lines.

This event is considered and as a single event is bounded by FSAR Chapter 15 transient analysis.

3.1.8.1 Mechanism For Failure A turbine trip, bypass on event due to a HELB can result from cable

damage, damage to the turbine EH fluid lines, vacuum sensing line damage or condenser damage.

These controls and equipment are located on the 471'nd 501'levation of the turbine building.

Several trip signals run from the turbine to the control room in control cables.

Shorting of the cable conductors or damage to the controlling equipment could signal a turbine trip.

For all HELBs resulting in a turbine trip from control cable

damage, RPS signal function was unaffected.

A rupture of the EH fluid lines controlling trip of the tur-bine valves would also result in a turbine trip.

For all 21

~ \\

~ I

~

HELBs resulting in a turbine trip due to EH Fluid Line

Rupture, RPS single function was unaffected.

Vacuum sensing line damage or condenser damage could result in a turbine trip on low vacuum.

The extent of damage would determine the time to trip ranging from immediately to several minutes.

For all HELBs resulting in vacuum sensing line damage or condenser

damage, RPS signal function was unaffected.

3.1.9 Turbine Trip, Bypass-Off Hydraulic line damage due to a high energy line break in the turbine building could cause this event.

This event is con-sidered and as a single event is bounded by FSAR Chapter 15 transient analysis.

3.1.9.1 Mechanism For Failure A turbine trip, bypass on event due to a

HELB can result from damage to the turbine EH fluid lines only.

These controls are located on the 471'levation of the turbine building.

The exact location for failure is uncertain as the HELB would have to rupture the turbine trip EH fluid line and the bypass valve positioning EH fluid lines.

The large volume of EH fluid contained near the bypass valves in accumulators and the positioning of the hydraulic lines makes this event very unlikely.

HELBs hitting the bypass valves were assumed to 22

cause this event,

however, no break resulted in a loss of the turbine RPS signal function.

3.1.10 Inadvertent MSIV Closure The potential for a high energy line break which would inad-vertently close the MSIVs exists on the 471'levation of the turbine building.

Damage to the control loops sensing low condenser

vacuum, low steamline
pressure, high radiation or high room temperature could result in this event.

This event is considered and as a single event is bounded by FSAR Chapter 15 transient analysis.

3.1.10.1 Mechanism For Failure Inadvertent MSIV closure can result from both normal and abnormal initiation.

Controls causing this event due to a HELB are-located on the 471'nd 501'evel of the turbine building.

Normal closure will occur for any HELB heating leak detection thermocouples to their trip point.

These thermocouples are located over the main steam lines in the turbine building.

Abnormal closure would occur from equipment, control cable or process tubin'g damage from main steam pressure

sensors, vacuum switches or radiation detectors.

All components would have to be damaged such that an open circuit is simulated.

23

All other instrumentation designed to close the MSIVs'is pro-tected from the effects of a HELB.

RPS signals function nor-mally for all HELBs inadvertently closing the MSIVs.

3.1.11 Loss of Condenser Vacuum Loss of Condenser Vacuum is a potential event due to a high energy break in the turbine building.

This event has no direct effects on reactor parameters.

In all cases, a loss of condenser vacuum results in a turbine trip.

Therefore the loss of condenser vacuum event is included with the turbine trip event analyses.

As a single event it is bounded by FSAR Chapter 15 transient analysis.

3.1.12 Loss of Feedwater Flow Several high energy line breaks on the 441'nd 471'leva-tion of the turbine building could result in a loss of feed-water (FW) flow.

This event is considered and as a single event is bounded by FSAR Chapter 15 transient analysis.

3.1.12.1 Mechanism For Failure Loss of feedwater flow'illoccur for any HELB resulting in reactor feedpump turbine (RFPT) trip or feedwater isolation.

Any main feedwater line break will cause this event.

In

addition, any main condensate line break will cause a

RFPT trip on low suction pressure.

24

I

~

~

~

I

1

~

g

~

On. the 441'levation of the turbine building, several spurious signals resulting in a RFPT trip could result from a HELB.

In each of these

cases, the signals are the result of either shorts or open circuits in the damaged cables.

Damage to level switches, process tubing or control cables on turbine building.elevation 471'ould simulate FW heater high level and isolate portions of the FW flow.

Also, shorts in control cables located on elevations 471'nd 501'n the turbine building could result in closing combinations of the FW heating system valves.

These valve closures would require selective control cable damage resulting from the proper 2

conductors in a 9 conductor cable shorting together without blowing circuit protective fuses.

3.1.13 Loss of Partial or Total Recirculation Flow The 6

FSAR Chapter 15 transient events which discuss loss of partial or total recirculation flow were analyzed for single event occurrence only.

Note, the vessel water level (L-8) trip and the turbine throttle valve reactor protection switch scram signals, which terminate these

events, cannot be lost due a HELB.

Any decrease in recirculation flow is bounded by Chapter 15 transient analysis.

3.1.14 Inadvertent HPCS Pump Start A review of the HPCS pump control system showed that an inad-vertent start cannot occur due to a high energy line break.

25

tI e

3 '

MUITIP LE EVENT ANALYSIS Multiple events were considered to be the result of pipe whip and jet impingement from a high energy line break with reactor scram culminating the events.

Each event was con-sidered to have occurred as described in Section 3.1 of this report.

Multiple events were. not necessarily considered to occur simultaneously but were instead considered to occur at worst case timing until reactor scram.

The single active failure assumed per MEB 3-1 in FSAR Chapter 3.6 was not considered.

Breaks in main steam lines were considered to activate RPS signals prior to the development of multiple events.

Reviews indicated that in no case can the RPS system be incapacitated due to any high energy line breaks.

Breaks in main conden-sate or feedwater lines which would trip the feedwater pumps or terminate feedwater to the reactor were not considered capable of resulting in the loss of feedwater temperature event.

Leak detection system temperature detectors designed to close MSIVs in case of high temperature were considered to activate for breaks in their immediate vicinity.

3.2.1 Worst Case Event Combinations On the 471'evel of the turbine building, one set of Divi-sion A trays (power, control and signal) and one set of 26

Division B trays (power, control and signal) run the length of the floor gathering cables in route to the control room.

A strategically located HERB could hit both sets of trays.

Assuming worst case cable failures in all trays, either open circuit or short, the following events, or any combination

thereof, are possible:

1)

Loss of Feedwater Heating 2)

Feedwater Controller Failure-Maximum Demand 3)

Pressure Regulator Fail-Closed 4)

Loss of Feedwater Flow

5) 'SIV Closure 6)

Turbine Trip, Bypass On Using the above events, an analysis using a General Electric Computer Code was run to establish a bounding event com-bination which resulted in the worst impact on critical reac-tor parameters.

The initial conditions and. input parameters used in this analysis are consistent with those used in Chapter 15.

In establishing this bounding combination, events 1 through 4 above are taken in a worst combination to bring the reactor to a power level just beneath Thermal Power Monitor Analytical Scram Limit (122%

Vi BR).

At this power level, events 5 and 6 above were assumed to occur.

For this

event, the Delta Critical Power Ratio (BCPR) exceeded 0.18 for less than 5 seconds (0.18 bCPR sets the present FSAR 27

0

required -operating limit).

The peak vessel pressure was less than 1207 psig and the peak cladding temperature was less than

'F, which is considerably less than the allowable peak vessel pressure (1375 psig) and the allowable peak cladding temperature (1500'F).

At these levels, WNP-2 FSAR Chapter 4.4 has indicated that no fuel damage is expected.

The reac-tor can be brought to cold.shutdown with no increase in the risk to the health and safety of the public.

Considering the low probability that such a break could occur:

i.e.,

the selective combination of cable shorts and open circuits required, the assumption of worst possible event combination and the extremely conservative initial reactor parameters

used, the occurrence of this combination can'e classified as low frequency.

As such, this event should be evaluated as an accident and is bounded by the design basis accidents analyzed in the FSAR.

3..2.2 Other Event Combinations Various other breaks could result in combinations of the events considered in Section 3.2.1.

Individual computer ana-lyses were, not run for each of these combinations but many are within the bounds of FSAR Chapter 15; all are bounded by the analysis in Section 3.2.1.

28

T'r~

l ~ D

~ ~ g 3.2.2.1 Loss =-of Feedwater Heating and Loss of Feedwater Flow This combined event is bounded by the loss of feedwater heating transient event as described in FSAR Chapter 15..

The loss of feedwater flow can only reduce the severity of the loss of feedwater heating event.

The sequence of events after the loss of feedwater flow will be as described in FSAR Table 15.2-11 resulting in a safe reactor shutdown.

3.2.2.2 Loss of Feedwater Heating and Turbine Trip, Bypass On The worst case combination of these two events would be a

loss of feedwater heating raising reactor power to a level just beneath the Thermal Power Monitor Analytical Scram Point followed by the turbine trip, bypass on.

Occurrence of this event requires cable shorting on the 471'evel of the tur-bine building.

Such an event is bounded by the analysis in Section 3.2.1.

3.2.2.3 Loss of Feedwater Heating and inadvertent MSIV Closure The worst case combination of these two events would be a

loss of feedwater heating raising reactor power to a level just beneath the Thermal Power Monitor Analytical Scram Point followed by MS?V closure.

Occurrence of this event requires cable shorting or process tubing damage on the 471'evel of the turbine building.

29

This combination of events is bounded by the analysis in Section 3.2.1.

3.2.2.4 Loss of Feedwater

Heating, Turbine Trip, Bypass On, and Inadvertent MSIV Closure This combination of events is bounded by Sections 3.2.2.2 or 3.2.2.3
above, depending on event sequence.

3.2.2.5 Loss of Feedwater Heating and Pressure Regulator Fail Closed The pressure regulator fail closed event described in Section 3.1.5 of this report results in a very mild tran-sient.

Reactor scram would occur on high pressure or APRM RPS signals.

This combined event is bounded by FSAR Chapter 15 transient analysis.

3.2.2.6 Loss of Feedwater Heating and Feedwater Controller Failure, Maximum Demand This combination of events worst case could result in a tur-bine trip with bypass valves and reactor power just below Thermal Power Monitor Analytical scram levels.

This combined event is bounded by Section 3.2.2.2 above.

3.2.2.7 Loss of Feedwater

Heating, Inadvertent MSIV Closure, Pressure Regulator Fail Closed and Loss of Feedwater Flow The worst case sequence of these potential combined events would be a loss of feedwater heating, then a pressure regula-30

~

~ p tor fail closed culminated by an inadvertent MSXV closure.

Loss of feedwater flow could only reduce the severity of the transient.

The worst case combination would require the loss of feedwater heating and pressure regulator fail closed events to raise reactor power and pressure to levels just beneath RPS Scram followed by MS?V closure.

Occurrence of this event requires cable shorts and open circuits on the 471'evel of the turbine building.

Such an event is bounded by the analysis of Section 3.2.1.I 31