Common Sensor Failures Evaluation Rept.
ML17277A607
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 04/30/1983
From: Scherer P
GENERAL ELECTRIC CO.
To:
Shared Package
ML17277A605 List:
References
NUDOCS 8306200253
Download: ML17277A607 (95)


Text

COMMON SENSORS FAII,URES EVALUATION REPORT APRIL 1983 PREPARED FOR WASHINGTON PUBLIC POWER SUPPLY SYSTEM NUCLEAR PROJECT NO. 2 PREPARED BY P. R. SC1iEKR GENERAL ELECTRIC COMPANY, NUCLEAR ENERGY BUSINESS OPERATIONS SAN JOSE, CALIFORNIA 95125 APPROVED:

T. R. Wortham, Manager Technical Iicensing Nuclear Control and Instrumentation DePartment P. B.. Kingston, Licensing Engineer Safety and Licensing Operation 12-0288 PDR 5~ 8~phip AD0cg PgPPO~9y PDR I

COMMON SENSORS FAITURES EVALUATION REPORT FOR WASHINGTON PUBLIC POWER SUPPLY SYSTEM NUCLEAR PROJECT NO. 2

l. 0 OBJECT This document constitutes:

An analysis in response to the NRC concern that the failure of an instrument line which contains sensors to multiple control systems could result in consequences outside the bounds'f the Washington Public Power Supply System Nuclear Project No. 2 (WNP-2) Final Safety Analysis Report (FSAR) Chapter 15 analysis and beyond the capabil>>

ities of operators or safety systems.

~ A positive demonstration that adequate 'common 'sensor review and analysis has been performed to ensure that despite such failure the WNP-2 FSAR Chapter 15 analyses are bounding, and no consequences beyond the capability of operators or safety systems would result.

A comprehensive approach was developed to analyze the control systems capable of affecting reactor water level, pressure, or power in the Nuclear Plant No. 2 Evaluation Report for Control Systems Failures. This Cosmon Sensor Report uses the knowledge of which systems affect reactor water level, pressure or power, gained in Evaluation Report for Control Systems Failures, for valid restriction of this analysis to only those systems.

This report was prepared by General Electric Company for Washington Public Power Supply System Nuclear Pro]ect No. 2 with a significant technical contribution from Burns 6 Roe, Incorporated (BSR Inc.), the Principal Architect Engineer.

2. 0 CONCLUSIONS This report, supplemented by existing FSAR Chapter 15 transient analysis, documents an evaluation of WNP-2 Nuclear Power Station for common sensor failures. No new transient category events have been postulated as a result of this study. All the uncovered consequences (Reactor Scram, Turbine trip, Feedwater increased/decreased flow) are bounded by FSAR Chapter 15 analysis.

3.0 ANALYSIS METHODOLOGY The common sensor failure analysis was conducted in the following manner by GE and BSR Inc:

12-0288 2

Activit

~ Identify Common Sensors BSR Inc 8 GE Determine Failure Mode BSR Inc S GE Summarize Common Sensor Failures

~ Analyze Combined Effects GE Compare Results to Chapter 15

~ Analyze Exceptions

~ Modify/Augment Chapter 15 if Necessary

3. 1 IDENTIFY COMMON SENSORS The systems that effect reactor water level, pressure or power were analyzed for instrument lines with sensors for more than one system.

The Evaluation Report for Control Systems Failure identified those systems that effect reactor water level, pressure or power as follows:

SPL ~Sstess SPL ~Settee NB Nuclear Boiler MS Main Turbine Generator RRC Reactor Recirculation CW Circulating Water CRD CRD Hydraulic SW Service Water RFT Feedwater Turbine CAS Control and Service Air NMS Neutron Monitoring AR Air Removal PRM Process Radiation Monitoring COND Condensate ARM Area Rad Monitoring DEH Main Turbine Control RWCU Reactor Water Cleanup TO Main Turbine and Feedwater MS Main Steam Turbines Lube Oil ES Exhaust Steam Seal Steam BS Bleed Steam-Extraction Steam Main Generator Cooling HV Heater Vents Main Generator Hydrogen and HD Heater Drains C02 Purge MD'iscellaneous Drains RCC RB Cooling Water MV Miscellaneous Vents TSW TB Cooling Water 3.2 DETERMINE FAILURE MODE The postulated probable failures are either that an instrument line is plugged (pinched) or broken.

The worst case would be any total combination of common sensor failures that can, be postulated from a single failure.12-02SS 3

3.3 SUMMARIZE COMMON SENSOR FAIIURES The common sensor failure table (attachment to this report) lists all the instrument lines with sensors and their failure modes. The combined failures are the consequences that the NRC is concerned with.

3.4 ANALYZE COMBINE EFFECTS This step used two approaches.

The first approach totaled all effects as worst case failure of the instrument line. There were no single effects that mitigated the total failure consequences.

The second approach considered piobable failures where the reactor scram had taken precedent over the other failure effects. In these instances the instrument line was analyzed as to whether a probable failure could be postulated without the reactor scramming. No such failure could be postulated.

3.5 COMPARE RESULTS TO CHAPTER 15 The combined effects as identified in common sensor table were reviewed and evaluated. Section 4 includes these evaluations, considering worst case effects.

3.6 ANALYZE EXCEPTIONS There were no exceptions to FSAR Chapter 15 analysis.

3.7 MODIFY/AUGMENT CHAPTER 15 IF NECESSARY This step was not necessary in the WNP-2 analysis.

4.0 COMMON SENSOR

SUMMARY

RESULTS AND CHAPTER 15 COMPARISONS Instrument Line Line Failure Conse uences No. 1 Line break initiates a decrease in feedwater flow and trip of Recirc Pump A. Reactor scram is 'a direct consequence. Reactor scram will not cause adverse consequences. Plugged line has no effect.

No. 2 Line break initiates increased feedwater flow, resulting in reactor scram. Reactor scram will not cause adverse consequences. Plugged line has no effect.

No. 3 No effect No. 4" No effect No. 5 No effect 12-0288 4

Instrument Line Zine Failure Cense uences No. 6 Breaking of this instrument line initiates a Main Turbine Trip. A Main Turbine Trip event is analyzed in Chapter 15. Plugged line has no effect.

No. 7 No effect No. 8 No effect No. 9 No effect No. 10 No effect No. 11 No effect No. 12 No effect No. 13 Line break initiates a decrease in feedwater flow resulting in reactor scram. Reactor scram will not cause adverse consequences. Plugged line has no effect.

No. 14 Line break prevents automatic SRV initiation; this event is analyzed in Chapter 5. Plugged line has no effect.

No. 15 Line break initiates closure of all main steam line valves causing a reactor scram. Reactor scram takes precedence over other sensor failure consequences.

Reactor scram will not cause adverse consequences..

Plugged line has no effect.

No. 16 No effect No. 17 Breaking this instrument, line decreases feedwater flow resulting in Reactor Scram. Reactor scram will not cause adverse consequences. Plugged line has no effect.

No. 18 Same as No. 15 No. 19 Same as No. 17 No. 20 Same as No. 15 No. 21 Same as No. 17 No. 22 Same as No. 15 No. 23 Same as No. 17 No. 24 Same as No. 15 12-0288 5

1*h, ~ )

Instrument I ine Line Failure Conse uences No. 25 Same as No. 2 No. 26 No effect No. 27 No effect No. 28 Line break transfers Re'circ Pumps A and B to low speed. A decrease in reactor flow is analyzed in Chapter 15. Plugged line has no effect.

No. 29 Same as No. 28 No. 30 No effect 12-0288 6

.ttAHFORD COt0tON SENSOR FAILURE TABLE TABLE PACE I 41 PhfiiS TOTAL Fhl LURE TYPE COtQSH TAP (BROKEH OR SYSTEH ID SEHSOR HPL PLUCGEU PRIHARY EFFECT SECONDARY EFFECT COMB INED EFFECT NUCIZAR B22-NOSlh = BROKEH HIM INUH REACTOR PRESSURE SIGNAL RECORDER R623A RED PEll IHOPERATIVE NONE BOILER PLUGGED COHSTANT REACTOR PRESSURE SIGNAL RECORDER R623h RED PEH AT COHSTAHT READING B22-H023h BROKEN HIHIHUH PRESSURE SIGNAL RPS CHANNEL "hl" HIGII RPV PRESSURE TRIP INOPERATIVE PLUCGED CONSTANT PRESSURE SIGNAL llPS CHANNEL "hl" HIGH RPV PRESSURE TRIP IHOPERATIVE B22-H020h BROKEN HIHIHUH REACTOR PRESSURE SIGNAL GIVES HSIV CLOSURE BYPASS SIGNAL MONEt REACTOR HODR SNITCH IH TO SCRhtt lltIP LOCIC "hl" ONLY IN "RUN" POSITION BLOCKS THE BYPASS SttUSOt0t, REFUEL, AMD STARTUP SIGNAL PLUGGED CONSTANT REACTOR PRESSURE SIGNAL REACTOR HIGH PRESSURE TRIP OF HSIV NONEt REACTOR NODE SMITCH IH CLOSURE SCRAH BYPASS IS "RUll" POSITION BLOCKS TltE BYPASS INOPERATIVE SI CHAL B22-H026h BROKEll HAXIHUH DIFFERENTIAL PRESSURE REACTOR IAN LOU HATER LEVEL tlhIH STEAN LIME ISOIATION VALVES SIGNAL ISOLATIOH LOGIC "h" TRIP IS CLOSURE I/2 TRIP REMAINS OPERATIVE INOPERATIVE FROH CHANNEL "C" CIRCUITRY PLUCGED CONSTANT DIFFERENTIAL PRESSURE REACTOR LOU LOU MATER LEVEL NOME SICMAL ISOLATIOH LOGIC "h" TRIP INOPERATIVE B22-Hl OOA BROKEN HAXIHUH DIFFERENTIAL PRESSURE DIV I HALF OF HPCS ltlGH LEVEL NONE SIGHAL SEAL-IN TRIPPED IHSTRUNEtlT LIHE I 3404 Hl4 REFEtlEHCE LEG (CONDEHSIHG CIIANBER B22-D004A)

PACE I OF 3 12-0286 (I)

NANFORD COMMON SENSOR FAILURE TABLE TABLE PAGE 2 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEN OR SYSTEM ID SENSOR NPL PLUGGED PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT PLUGGED CONSTANT DIFFEREHTIAL PRESSURE DIV I HALF OF HPCS HIGH LEVEL SIGNAL SEAL-IH IHOPERATIVE B22-N03 lb BROKEH NAXINW DIFFERENTIAL PRESSURE REACTOR HIGH PRESSURE CORE SPRAY ALLOMS IMPROPER OPERATION OF HPCS AHD SIGNAL DIVISIOH I LOM LEVEL TRIP PUMP DISCHARGE VALVE LOGIC RESET B22-H031C IHOPERATIVE CIRCUIT PLUGGED CONSTANT DIFFERENTIAL PRESSURE REACTOR HIGH PRESSURE CORE SPRAY HOME SIGHAL DIVISIOH I IAN LEVEL TRIP INOPERATIVE REACTOR B35-N038A BROKEH MINIMUM PRESSURE SIGNAL RECIRC PUMP A TRIPS AMD IS RECIRC PUMP h 18 INOPERATIVE RECIRC BLOCKED PRON TRANSFER TO LOll SPEED PLUGGED COHSTANT PRESSURE SIGNAL IF PUMP B IS AT HIGll SPEED AHD HONE STOPS, MPSll INTERLOCK IHOPERATIVE REACTOR C34-M005 BROKEH MINIMUM PRESSURE SI CHAL C34-R605 NIGH LEVEL RECORDER NONE FEEDMATER INOPERATIVE PLUGGED CONSTANT PRESSURE SIGNAL C34-R605 HIGll LEVEL RECORDER NONE IHOPERATIVE C34-NOOSA = BROKEll MINIMUM PRESSURE SIGNAL RECORDER C34-R609 RED PEM HOME INOPERATIVE PLUGGED COHSTAHT PRESSURE SIGHAL RECORDER C34-R609 RED PEH AT HONE COMSTAHT READING INSTRUMENT LINE I 3404 H14 REFEREHCE LEG (COHDEHSIHG CHAMBER B22-D004A)

PAGE 2 OF 3 12-0286 (2)

HAHFORD COIOION SEHSOR FAILURE TABLE TABLE PACE 3 41 PACES TOTAL FAILURE TYPE COtBION TAP (BROKEN OR SYSIKtl ID SENSOR tlPL PLUCCED PRI tlhRY EFfECT SECONDARY EFfECT COHBI RED EFFECT REACTOR C34-N004h BROXEH HAXIIIUIIDI FFKREHTIAL PRESSURE C34-R606A MATER LEVEL RECORDER FKKDMATKR DECREASED FLOM iKEDMATKR SIGNAL IHOPERATIVE; REACTOR FEEDMATER DECREASED FLOM PLUGCED COHSTAHT DIFFERENTIAL PRESSURE C34-R606A MATER LEVEL RECORDER AT NONE SIGHAL CONSTANT READING; REACTOR FKED-MATKR ERROR IH LEVEL FOLLOMING B22-N024A BROKEN IIAXItmtl DIFFERENTIAL PRESSURE RPS CHANNEL hl LOM LEVEL SCRAII SICNAL I HOPERATIVE PI,UGGED CONSThllT DIFFEREHTIAL PRESSURE RPS CHAHNEL hl LOM LEVEL SCRAII HONE SIGNAL INOPERATIVE IHSTRUIIENT LINE I 3404 NI4 REFEREHCE LKG (COHDEHSIHG CIIAIIBER 822-D004h)

PACE 3 OF 3 12-0286 (3)

~ a I l

NANFORD COMMOH SEHSOR FAILURE TABLE TABLE PAGE 4 41 PAGES TOTAL FAILURE TYPE COtQSH TAP (BROKEH OR PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT 8YSTKM ID SENSOR MPL PLUGGED 822" H10 lb BROKEN MINIMUM DIFFERENTIAL PRESSURE RCIC ISOLATION VALVE 851-F045 RCIC ISOLATIOH VALVE E51-F045 NUCLEAR SIGNAL CLOSURE OH HIGjl REACTOR LEVEL CLOSURE OH MANUAL INITIATION ONLY BOILER INOPERATIVE PLUGGED CONSTANT DIFFERENTIAL PRESSURE RCIC ISOLATION VALVE 851-F045 RCIC ISOIATIOH VALVE E51-F045 SIGNAL CLOSURE OH HIGH REACTOR LEVEL CLOSURE OH MANUAL INITIATIONOHLY INOPERATIVE 822-H024A BROKEN MINIMUM DIFFERENTIAL PRESSURE RPS CtULHHEL hl IAN LEVEL SCRAM I/2 REACTOR SCRAM SIGHAL TRIP PLUGGED CONSTANT DIFFERENTIAL PRESSURE RPS CHANNEL hl QN LEVEL SCRAM SIGHAL TRIP IHOPKRATIVE 822-N0248 BROKEN MINIMUM DIFFERENTIAL PRESSURE RPS CHAHNEL Bl IlN LEVEL SCRAM I/2 REACTOR SCRAM SIGNAL TRIP PLUGGED CONSTANT DlFFEREHT IAL PRESSURE RPS CHANNEL 81 QN LEVEL SCRAM

'SIGHAL TRIP IHOPERATIVE 822-N038h BROKEN MINIMUM DIFFERENTIAL PRESSURE I/3 DIVISION 1 AUTO DKPRESSURIZA- TQO ADDITIOHAL RPV LOU LEVEL TRIPS SIGNAL TIOH LOGIC TRIP HEEDED TO ALllW ADS IHITIATIOH FROM DIVISIOH I PLUGGED COHSTANT DIFFEREHTIAL PRESSURE DIVISIOH 1 AUTO DEPRESSURIZATIOH ADS IHITIATION AVAILABLEFROM SIGHAL LOGIC IHOPKRATIVE DIVISION 2 822-H100h BROKEN MININN DIFFERENTIAL PRESSURE DIVISION 1 HALF OP NPCS )lIGH NONE SIGNAL LEVEL SEAL-IH IHOPERATIVE I

t

~

IHSTRUMKHT LINE 2 104 H13 VARIABLE SIGHAL SENSING LIHE PAGE I OF 2

%i ~

12-0286 (4)

UANFORD COHHOH SEHSOR FAILURE TABLE TABLE PAGE 5 41 PAGES TOTAL FAILURE TYPE COHHON TAP (BROKEN OR COHBINED EFFECT SYSTKN In SENSOR HPL PIUGGED PRIHARY EFFECT k PLUGGED COHSTAHT DIFFERENTIAL PRESSURE DIVISIOH I HALF OF HPCS HIGH NONE SI CHAL LEVEL SEAL-IH IHOPERATIVE REACTOR C34-N004A BROKEN H IN I HUH DIFFERENTIAL PRESSURE C34-R606A MATER LEVEL RECORDER FEKDMATER INCREASED FLOM FEKDMATER SIGHAL IHOPERATI VE; REACTOR FEEDMATER INCREASED FLOM PLUGGED CONSTANT DIFFEREHTIAL PRESSURE C34-R606A MATER LEVEL RECORDER AT NONE SIGNAL CONSTANT READIHGi REACTOR FEED MATER ERROR Ill. LEVEL FOLLOMIHG I

~

~

INSTIlUHEHT LINK 2 104 HI3 VARIABLE SIGHAL SEHSIHG LINE PAGE 2 OF 2 12-02S6 (S)

HAHFORD COHHON SENSOR FAILURE TABLE TABLE PAGE 6 41 PAGES TOTAL FAILURE TYPE COJBJOH TAP (BROKEH OR SYSIEH ID SENSOR HPL PLUGGED PRItJARY EFFECT SECONDARY EFFECT COHBINED EFFECT NUCLEAR B22-H023C BROKEH ttIHIHUH PRESSURE SIGJlhL RPS ~ CHAHHEL h2 HlGH RPV BOILER PRESSURE TRIP INOPERATIVE PLUGGED CONSTANT PRESSURE SIGNAL RPS, CHANNEL <<h2<<HIGH RPV NONE PRESSURE TRIP IHOPERATIVE B22-H026C BROKE Jl tJAXItJUH DIFFEREHTlhl PRESSURE REACTOR DN QN MATER LEVEI tfAIN STEAtl ISOLATION VALVES SIGHAL ISOLATIOH LOGIC <<C<<TRIP CLOSURE 1/2 TRIP REtlhlHS INOPERA-INOPERATIVE TIVE FROH CHANNEL <<A" CIRCUITRY PLUGGED CONSTANT DIFFERENTIAL PRESSURE REACTOR LOM LOM MATER LEVEL MAIN STEhtt ISOLATIOH VALVES SIGHAL ISOLATIOH IDGIC <<C<< TRIP CLOSURE l/2.TRIP REHAIHS INOPERA-INOPERATIVE TIVE FROH CHANNEL <<A<<CIRCUITRY B22-HIOOB tJAXItmH DIFFERENTIAL PRESSURE DIVISION 2 tthlF OF BPCS HIGH HONE SIGHAL LEVEL SEAL-IH TRIPPED PLUGGED CONSTAHT DIFFERENTIAL PRESSURE DIVISIOH 2 HALF OF HPCS HIGJl NONE Sl GHAL LEVEL SEAL IH INOPERATIVE 822-H020C BROKEN HINItmtt REACTOR PRESSURE SIGNAL GIVES tJSIV CMSURE BYPASS SIGNAL NONE J REACTOR NODE SNITCH IH TO SCRhtf TRIP LOGIC "A2<<ONLY IH <<RUll<<POSITIOH BLOCKS TJJE BYPASS SJJWJOMts REFUEL, AND STARTUP tJODE SIGHAL PLUGGED CONSTANT REACTOR PRESSJJRE SIGNAL REACTOR BIGJI PRESSURE TRIP OF lJSIV NONm: ImhCIOR !JOBE SMITCH IJJ CLOSURE SCRAtf BYPASS IS <<RUJl'OSITIOH BLOCKS TJJE BYP'4S I HOPERATIVE SIGNAL 822-H024C BROKEH tthXItGJJI DIFFERENTIAL PRESSURE RPS CHANNEL h2 MM LEVEI SCRAM SIGNAL INOPERATIVE IHSTRWEHT LINE 3 160~ H14 REFERENCE LEG (CONDENSING CJJhtJBER B22-D004C)

PAGE I OF 2 t2-0286 (6)

MAHFORD COSIGN SEHSOR FAILURE TABIE TABLE PAGE 7 41 PAGES 'TOTAL FAILURE TYPE

, COMMON TAP (BROXEN OR PRIMARY EFfECT SECOHDARY EFFECT COMBINED EFFECT SYSTEM ID SENSOR liPL PLUGGED PLUGGED CONSTANT DIFFERENTIAL PRESSURE RPS CHANNEL A2 UN LEVEL SCRAII SIGNAL INOPERATIVE B22-H03IB BROXEH HAXINRi DIFFERENTIAL PRESSURE REACTOR HIGH PRESSURE CORE SPRAY ALLOHS IMPROPER OPERATION OF HPCS SIGNAL DIVISIOH 2 UN LEVEL TRIP PUMP DISCIIARGE VALVE LOGIC RESET AND B22-H03ID IHOPERATIVE CIRCUIT PLUGGED CONSTANT DIFFERENTIAL PRESSURE REACTOR NIGH PRESSURE CORE SPRAY NONE SIGNAL DIVISION 2 LOll LEVEL INOPERATIVE REACTOR C34-N004C BROKEN HAXINml DIFFERENTIAL PRESSURE C34-R606C MAIER fXVEL RECORDER NONE FEEDHATER SIGNAL IHOP ERAT IVE PLUGGED COHSTAHT DIFFERENTIAL PRESSURE C34-R606C MATER LEVEL RECORDER AT NOME SIGNAL CONSTANT READING INSTRUMENT LINE 3 1604 HI4 REFEREHCE LEG (CONDEHSIMG CIIANBKR B22-D004C)

PAGE 2 OF' 12-0286 (7)

HANFORD COHHOH SENSOR FAILURE TABLE TABIE PAGE 8 41 PAGES TOTAL FAILURE mE COHHOH TAP (BROKEN OR PRI HART EFFECT SECONDARY EFFECT COMBIHED EFFECT SYSTEH ID SENSOR HPL PLUGGED NUCLEAR B22-H047h BROKEH LOSE DIVISION 1 HIGH DRYNELL HONE - BACKED UP BY DIVISIOH 2 HONE BOILER AND PRESSURE SIGNAL B22-N047C PLUGGED LOSE DIVISIOH I HIGH DRYNELL NONE PRESSURE SIGHAL REACTOR C72-H002h BROKEN LOSE REACTOR SCRAH OH PRIHARY NONE - BACKED UP BY Blo A2s AND HONE PROTECTIOH COHTAINHEHT HIGH PRESSURE "hl" B2 CIRCUITS PLUGGED LOSE REACTOR SCRAH OH PRIHARY NONE HOHE CONTAIHHEHT HIGH PRESSURE "hl" C72-N004 BROKEH LOSE PRIHARY CONTAIHMEHT HIGH NONE PRESSURE ALARH PLUGGED LOSE PRIHARY CONTAINHEHT HIGH NONE NONE PRESSURE ALARH I HSTRUHENT LINE 4 PAGE I OF I 12-0206 (e)

MAHFORD COMMON SENSOR FAILURE TABLE TABLE PAGE 9 41 PAGES TOTAL FAII,URE TYPE COMMON TAP (BROKEH OR SYSTEM ID SENSOR NFL PLUGGED PRIMARY EFFECT SECONDARY EFFECT COMBIHED EFFECT MAIM STEAM MS-PID-20h BROKEN LOSE TURBIHE DEH FEEDBACK CONTROL LARGER ERROR IH TURBINE OUTPUT NOHE SIGHAL POMKR CONTROL, BUT DOES HOT SIGHIFICANTLY AFFECT TURBINE OPERATION PLUGGED LOSE TURBINE DEll FEEDBACK CONTROL LARGER ERROR IH TURBINE OUTPUT NOHE SIGNAL POMKR CONTROL, BUT DOES NOT SIGHIFICAHTLY AFFECT TURBINE OPKRATIOH REACTOR . C)2-H003h BROKEN FIRST STAGE TURBINE PRESSURE TURBIHE CONTROL VALVE FAST NONE PROTECT IOH SMITCH MII,L HOT OPEN, SEHSES 30$ CLOSURE, STOP VALVE AHD RPT TRIP POVKR "hl" BYPASS INOPERATIVE PLUGGED F I RST STAGE TURBINE PRESSURE HOHE NOME SMITCH MILL NOT OPEN, SENSES 30'X POVKR CONTROL C12-N054h BROXKH HINIMUH FIRST STAGE TURBINE ROD SEQUENCE COHIROL IHITIATES MONE ROD DRIVE PRESSURE SI CHAL ROD BUKX DIVISIOH I HYDRAULICS PLUGGED CONSTANT FIRST STAGE TURBINE LOU POVKR ROD SEQUENCE CONTROL NONE PRESSURE SI CHAL LOGIC DIVISIOH I IHOPERATIVE INSTRUMENT LINE 5 PAGE I OF 1 12-0286 (9)

NANFORD COHHOH SENSOR FAILURE TABLE TABLE PAGE 10 41 PAGES TOTAL FAILURE TYPE COHHOH TAP (BROXEH OR SYSTKH ID SENSOR HPL PLUGGED PRIHARY EFFECT SECONDARY EFfECT COHBINED EffKC?

HAIN STEAN NS-PTD-20B BROXEJl HINIJSJH FIRST STAGE TURBINE HETER NS-PI-20B INOPERATIVE NONE PRESSURE Sl GHAL PLUGGED CONSTANT fIRST STAGE TURBINE HETER PS-PI-20B AT CONSTANT PRESSURE SIGNAL READING HS-PT-20BG BROKEN HIHIHUH FIRST STAGE PRESSURE INDICATOR IJS-P I-20BG IHOPERATIVE NONE IHDICATIOH PLUGGED CONSTANT FIRST STAGE PRESSUJlE INDICATOR HS-Pl-20BG AT CONSTANT NONE I

INDI CAT OH READING NS-DPIS-63 BROXKN HIHIHUM DIFfEREHTIAL PRESSURE HAIN TURBINE TRIPS AT LESS TIJAN HAIN TURBlllE TRIP SIGNAL 15 PSID PLUGGED CONSTANT DIFfEREHTIAL PRESSURE HO TRIP CAPABILITY OH LOM NONE SIGNAL Dl FFKREHTIAL PRESSURE REACTOR C34-N007 BROXEll HIHIHUH TlJRBIHK STEhli FLOW SIGNAL RECORDER C34-R609 BLACK PEH fEKOWATER INOPERATIVE PLUGGED CONSTANT TURBINE STEAN FLOW RECORDER C34-R609 BLACK PEN AT HONE SIGHAL COHSTANT READING REACTOR C72-N003C BROXEH FIRST STAGE 11JRBINK PRESSURE TlJRBINE COHTROL VALVE FAST NONE PROTKCTIOJI SWITCH MILL NOT OPEN, SENSES 30$ CLOSURE, STOP VALVE AND RPT TRIP POWER "h2" BYPASS INOPERATIVE PLUGGED FIRST STAGE TURBIHE PRESSURE NONE NONE SHITCJJ WILL NOT OPEN, SEHSES 30X POWER IHSTRUHEHT LINE 6 PAGE I OF 2 12-0286 (10)

HANFORD COHHOH SEHSOR FAILURE TABLE TABLE PAGE 11 41 PAGES TOTAL FAILURE TYPE COHHON TAP (BROKEN OR .

SYSTEll ID SEHSOR HPL PLUGGED PRIHARY EFFECT SECONDARY EFFECT C72-N003D BROKEH FIRST STAGE TURBIHE PRESSURE TURBINE CONTROL VALVE FAST NONE SWITCH WILL NOT OPEH, SEHSES 30$ CLOSIHE, STOP VALVE AHD RPT TRIP POWER "B2" BYPASS IHOPERATIVE COHTROL C12-N054B BROKEH HINIHUM FIRST STAGE TURBINE ROD SEQUEHCE CONTROL IHITIATES NOHE ROD DRIVE PRESSURE SIGNAL ROD BLOCK DIVISIOH 2 HYDRAULICS PLUGGED COHSTAHT FIRST STAGE TURBINE MW POWER ROD SEQUEHCE CONTROL NOHE PRESSURE SIGHAL LOGIC DIVISIOH 2 INOPERATIVE I NSTRUHEHT LIHE 6 PAGE 2 OF 2 12-0286 (II)

HAHFORD COHHON SENSOR FAILURE TABLE TABLE PAGE 12 41 PAGES TOTAL FAILURE TTPE COHHON TAP (BROKEH OR SYSTEH ID SEHSOR HPL PLUGGED PRIHARY EFFECT SECOHDARY EFFECT COHBINED EFFECT NUCLEAR B22 N047$ BROKEN LOSE DIVISIOH 2 HIGH DRYVELL HOHE - BACKED UP BY DIVISION I NONE BOILER AHD PRESSURE SIGHAL B22-N04)D PIAJGGED LOSE DIVISIOH 2 HIGH DRYVELL HONE HONE PRESSURE SIGNAL REACTOR C72 N002C BROKEH IOSE REACTOR SCRAH ON PRIHARY NONE - BACKED UP BY Al, Bl, AND HONE PROTECTIOH COHTAIHHEHT HIGH PRESSURE A2 CIRCUITS I NSTRUHENT LINE 1 PACE I OF I 12-0286 (12)

NANFORD COttttOH SEHSOR FAILURE TABLE TABLE PAGE 13 41 PAGES TOTAL FAILURE TYPE COtBION TAP (BROKEN OR SYSTEM ID SEltSOR HPL PLUGGED . PRIMARY EFFECT SECONDARY EFFECT COttBINED EFFECT BS-PT-3B3 BROXEN ttlMItmtt GLAND SEAL STEhtt PRESSURE LOU GLAHD SEAL STEhtt PRESSURE NOHE S IGltAL ALARtt IN CONTROL ROOtt CONSTANT GLAND SEAL STEhtt MONE PRESSURE SIGNAL ttAIH STEhtt HS-DPIS-63 BROKEtt tthXlttUtt DIFFERENTIAL PRESSURE LOSE CAPABILITY TO TRIP HAIN SIGNAL TURBIHE OH LOU PRESSURE PLUGGED CONSTANT DIFFERENTIAL PRESSURE LOSE CAPABILITY TO TRIP HAIH HONE SIGNAL TURBINE OH IAN PRESSURE I tlSTRUHENT LINE 8 PAGE 1 OF 1

.12-0286 (13)

HAHFORD COMHOH SEHSOR FAILURE TABLE TABLE PAGE 14 41 PAGES TOTAL FAILURE TYPE COHHOH TAP . (BROKEH OR SYSTEH ID SENSOR HPL PLUGGED PRI NARY EFFECT SECONDARY EFFECT NUCLEAR B22-H032 BROKEN HAXIHUM DIFFEREHTIAL PRESSURE RECORDER R613 CORE PLATE DIFF HONE BOILER SIGNAL PRESSURE BLACK PEll INOPERATIVE PLUGGED CONSTANT DIFFEREHTIAL PRESSURE RECORDER R613 CORE PLATE DIFF NOHE SIGHAL PRESSURE BLACK PEH CONSTANT INDICATION B22-N034 BROKEH HAXIHUH DIFFEREHTIAL PRESSURE RECORDERS R608i R61IhiB AHD R613 NOHE (h TI1RU H) SIGHAL RED PEH INOPERATIVE PLUGGED COHSTANT DIFFEREHTIAL PRESSURE RECORDERS R608 ~ R61 IhiB AHD R613 HOHE SIGHAL RED PEH IHOPERATIVE REACTOR G33-H037 BROKEH IIAXIHUH DIFFERENTIAL PRESSURE RECORDER R610 INOPERATIVE NONE MATER SIGNAL CLEAHUP PLUGGED COHSTAHT DIFFERENTIAL PRESSURE RECORDER R610 CONSTANT IHDICATION HONE Sl GHAL INSTRUHEHT LINE 9 PAGE 1 OF 1 12-0286 (14)

HANFORD COHHOH SKHSOR FAILURE TABLE TABIE PAGE 15 41 PAGES TOTAL FAILURE TYPE CONHOH TAP (BROKEN'OR SYSTEH ID SKHSOR NPL PLUCCKD I PR NARY EFFECT SECONDARY EFFECT COtfB IHED EFFECT NUCLEAR B22-H027 BROKKH lihXIHUH REACTOR VESSEL LEVEL B22-R605 HETER INOPERATIVE OFF NONE BOILER SICHAL SCALE, HIGH LEVEL PLUCGKD CONSTANT REACTOR VESSEL LEVEL B22-R605 HETER hT CONSTANT HOHE SICHAL READIHG REACTOR C34-HO I I t!AXINPI MIDE RANCE REACTOR LEVEL C34-R60S RECORDER REGISTERS IIAXI- NONE FKEDMATER SICHAL HUM SICHAL PLUGGED COHSTAHT VIDE RANCE REACTOR LEVEL C34-R60S RECORDER REGISTERS SIGHAL I COHSTANT S CHAL IHSTRUHENT LIHE 10 VESSEL I1KAD NOZZLK HB, REFERQlCE LEG (CONDKNSIHG Cl!AHBER 822-D002)

PACK 1 OF 1 12-0286 (15)

NANFORD COHHOH SENSOR FAILURE TABLE TABLE PAGE 16 41 PAGES TOTAL FAIUIRE TYPE COHHOH TAP (SROKEH OR STSTEH ID SENSOR HPL PLUCGED PRIHARY EFFECT SECONDARY EFFECT COHBINED EFFECT NUCLEAR B22-N048A SROKEH DIVISION I AUTO DEPRESSURIZATIOH NONE - BACKED UP BT DIVISIOH 2 HONE BOILER AND LOGIC INOPERATIVE 822-H048C PLUGGED DIVISION 1 AWO DEPRESSUR IZATION NONE MGIC INOPERATIVE REACTOR C12-N0028 BROKEN LOSE REACTOR SCRAH ON PRIHARY HONE - BACKED UP BY hl ~ A2, AHD HONE PROTECTION COHTAINHEHT HIGH PRESSURE "Sl" 82 CIRCUITS PLUCGED LOSE REACTOR SClUQI ON PRIHARY HONE HONE COHTAIHHEHT NIGH PRESSURE "Sl" I NSTRUHEHT LIKE l1 PACE I OF I 12-0286 (16)

ffhNFORD C010fON SENSOR FAILURE TABLE TABLE PAGE 17 41 PAGES TOTAL FAILURE TYPE COf0fOH TAP (BROKElf OR SYSTEH ID SENSOR ffPL PLUGGED PRIHARY EFFECT COHBIHED EFFECT B22-N048B BROKEH DIVISION 2 AUTO DEPRESSURIZAT10N HONE " BACKED UP BY DIVISIOH I HONE AND LOGIC INOPERATIVE B22-H048D PLUGGED DIVISIOH 2 AUTO DEPRESSURIZATIOH HONE NONE LOGIC INOPERATIVE REACTOR C72-N002D BROXEH LOSE REACTOR SCRhff OH PRIHhflY HOHE - BACXED UP BY hl, h2, AND NONE PROTECTION COHThlf0fENT Hl Glf PRESSURE "h2" B2 CIRCUITS PLUGGED MSE REACTOR SCRAH OH PRI!fhRY HOHE NONE COHTAIHliEfiT NIOff PRESSURE "h2" I HSTRUHENT LINE 12 PAGE 1 Oi 1 12-0286 (17)

HANFORD COtQJON SENSOR FAILURE TABLE TABLE PAGE 18 41 PAGES TOTAL FAILURE TYPE COtJHON TAP (BROKEtt OR SYSTEH ID SEHSOR HPL PLUGGED PRItthRY EFFECT SECONDARY EFFECT COHBINED EFFECT NUCLEAR B22-N026D BROKEN HAXltJUH DIFFERENTIAL PRESSURE REACTOR LOM LOM MATER LEVEL HAIH STEAH ISOIATION VALVES BOILER SIGHAL ISOLATIOJI LOGIC D TRIP INOPERATIVE CLOSURE I/2 TRIP STILL OPERATIVE FROH CHANNEL "B" CIRCUITRY PLUGGED CONSTANT DIFFERENTIAL PRESSURE REACTOR LOM 1AM MATER LEVEL HAIH STEAN ISOLATION VALVES SIGNAL ISOLATION D LOGIC TRIP INOPERATIVE CLOSURE I/2 TRIP STILL OPERATIVE FROH CHANNEL "8" CIRCUITRY B22-N020D BROKEH HINI HUH REACTOR PRESSURE SIGNAL GIVES HSIV CLOSURE BYPASS SIGNAL NONE: REACTOR HODE SMITCH IH TO SCRAH TRIP LOGIC "B2" OHLY ltt "RUH" POSITION BLOCKS TIJE BYPASS SJJUTDOMN, REFUEL, AND STARTUP NODE SIGNAL PLUGGED CONSTANT REACTOR PRESSURE SIGHAL REACTOR HIGH PRESSURE TRIP OF HSIV NONE: REACTOR MODE SMITCH IH CLOSURE SCRAH BYPASS IS "RUN" POSITIOH BLOCKS TIJE BYPASS INOPERATIVE SIGNAL B22-N023D BROKEH HIHltJUH PRESSURE SIGNAL RPS CHANNEL "82". HIGH RPV PRES- NONE SURE TRIP INOPERATIVE PLUGGED CONSTAHT PRESSURE SIGNAL RPS CIJANNEL "B2" HIGH RPV PRES- NONE SURE TRIP INOPERATIVE B22-N045C BROKEN HINIHUH PRESSURE SIGHAL RECIRC PUHP A, BKR,3A AIMS Q HIGH NONE PRESSURE TRIP; BACKED BY h AHD B CIRCUITS PLUGGED CONSTAHT PRESSURE SIGHAL REC INC PUtlP A ~ BKR 3h ATMS J HIGH Not)E PRESSURE TRIP; BACKED BY h AND B CIRCUITS INSTRIJHENT LINE 13 200 ttt4 REFEREHCE LEG (CONDENSING CJJAHBER 822-D004B)

PAGE I OF 4 12-0286 (ts)

HANFORD CQRSN SEHSOR FAILURE TABLE TABLE PAGE 19 41 PAGES TOThL FAILURE TYPE COMMON TAP (BROXEH OR PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT SYSTEM ID SENSOR MPL PLUGGED B22-N045D BROKEN MINIMUM PRESSURE SIGNAL RECIRC PUMP B, BXR 3B ATQS Q HIGH NONE PRESSURE TRIP INOPERATIVE; BACXED BY A AND B CIRCUITS PLUGGED CONSTANT PRESSURE SIGHAL RECIRC PUMP B, BXR 3B ATQS Q HIGH NOHE PRESSURE TRIP iNOPERATIVE; BACKED BY h AND B CIRCUITS B22-N051B BROKEN MIHIMUM REACTOR PRESSURE SIGNAL RECORDER R623B RED PEH IHOPERATIVE HONE PLUGGED COHSTAHT REACTOR PRESSURE SIGNAL RECORDER R623B RED PEN COHSTAHT HOHE READING B22-H036C MAXIMUM DIFFERENTIAL PRESSURE RECIRC PIMP ho BXR 3h ATQS LOQ SIGNAL LEVEL 2, I/2 TRIP IHOPERATIVE-CIRNHEL h REMAINS OPERATIVE PLUGGED COHSTANT DIFFERENTIAL PRESSURE RECIRC PUMP h, BKR 3A ATQS LOQ HOHE SIGHAL LEVEL 2, I/2 TRIP INOPERATIVE-CNANHEL h REMAINS OPERATIVE B22-N036D BROKEN MAXIMUM DIFFERENTIAL PRESSURE RECIRC PUMP B, BKR 3B ATQS LOQ SIGHAL LEVEL 2, I/2 TRIP IHOPERATIVE-

, ClthHNEL B REMAIHS OPERATIVE PLUGGED COHSTAHT DIFFEREHTIAL PRESSURE RECIRC PUMP B, BKR 3B ATQS IlN NONE SIGHAL LEVEL 2, I/2 TRIP INOPERATIVE-CNAHNEL B REMAINS OPERATIVE IHSIllUMEHT LINE 13 200 H14 REFERENCE LEG (COHDEHSIHG CIIAMBER B22-D004B)

PAGE 2 OF 4 12-0286 (19)

tthHFORD COtQtOH SENSOR FAILURE TABLE TABLE PAGE 20 41 PAGES TOTAL FAILURE TTPE COttttON TAP (BROKEN OR STSTKtt ID SENSOR HPL PLUGGED PRIMARY EFfECT SECONDARY EffKCT B22-N037$ BROKEN tihXIHUtt DlFFEREHTIAL PRESSURE I/2 DIVISION 2 ADS - AHD - RCIC AND SIGHAL LOGIC TRIP INOPERATIVE B22-N037D PLUGGED COHSTAHT DIFFEREHTIAL PRESSURE I/2 DIVISIOH 2 ADS - AHD - RCIC HONE SIGNAL LOGIC INOPERATIVE B22-N044B BROKEN tthXIttUtt DIFFEREHTIAL PRESSURE REACTOR HATER LVL ItiDICATOR R610 MOTE: THIS IHSTRUHEHT IS USED SIGNAL INOPERATIVE (SKE NOTE) -ONLT DURIHG POST ACCIDEHT REACTOR StlUTtNNtH AND llitKN RECIRC PUMPS ARE COtlSTANT DIFFERKHTIAL PRESSURE REACTOR llhTKR LVL INDICATOR R610 SECURED. DURlltG REACTOR OPERATION PLUGGED SIGNAL CONSTANT READING (SKE MOTE) IHSTRUttKHT READS OFF SCALE, tllGll.

B22-N038B BROXEH ttAXIHUtt DIFFERENTIAL PRESSURE DIVISIOH 2 AUTO DEPRKSSURIZATIOH MONE SIGNAL LOGIC TRIP IHOPERATIVE PLUGGED CONSTANT DIFFERKt TIAL PRESSURE DIVISION 2 AUTO DEPRESSURIZATIOH NONE SIGNAL LOGIC INOPERATIVE B22-N024D BROKEN tthXIttUtt DlffERKIITIALPRESSURE RPS ClthHNEL B2 LOll LEVEL SCRAH HONE SIGNAL IHOPERATIVE PLUGGED CONSTANT DIFFEREHTIAL PRESSURE RPS CIIANNEL B2 LOU IKVEL SCRhtt SIGHAL INOPERATIVE B22-HIOIB BROXKH tiAXIHUtt DIFFERENTIAL PRESSURE RCIC ISOLATIOH VALVE E51 F045 HONE s SIGHAL (IIIGH LEVEL) I/2 TRIP PLUGGED COHSTA!lT DIFFERENTIAL PRESSURE RCIC ISOLATION VALVE K51-F045 NONE SIGHAL INOPERATIVE IIIGtl IKVEL TRIP IHSTRUHKHT LINE 13 200'14 REFERENCE LKG (CONDKHSIHG CNhttBER B22-D004B)

PAGE 3 OF 4 12-0286 (20)

HANFORD COHHON SENSOR FAILURE TABLE TABLE PAGE 21 41 PAGES TOTAL FAILURE TYPE COHHOH TAP (BROKEH OR SYSTEH ID . SEHSOR NPL PLUGGED PRI NARY EFFECT SECONDARY EFFECT REACTOR C34-H004B BROKEH NAXIHUH DIFFEREHTIAI. PRESSURE C34-R606$ MATER LEVEL RECORDER FEEDMATER DECREASED FISI FEEDMATER SIGNAL INOPERATIVE'EACTOR FEEDMATER DECREASED FLOM PLUGGED CONSTANT DIFFERENTIAL PRESSURE C34-R606B MATER LEVEL RECORDER AT HOHE SIGNAL COHSTANT READING REACTOR FEED-MATER ERROR IH LEVEL FOLLOMIHG REACTOR B35-N03$ C BROKEN HINIHUN PRESSURE SIGHAL RECIRC PUHP B TRIPS AND IS HONE RECIRC BLOCKED FRON TRANSFER TO LOM SPEED PLUGGED CONSTANT PRESSURE SIGNAL (IF PUHP h IS AT HIGH SPEED) AND NONE PUNP B STOPS, NPSH INTERLOCK INOPERATIVE INSTRUHENT LIHE 13 2004 H14 REFEREHCE LEG (COHDEHSIHG CHAHBER B22-D004B)

PAGE 4 OF 4 12-0286 (21)

HANFORD COMMOH SENSOR FAIMlE TABLE TABLE PAGE 22 41 PAGES TOTAL FAILURE TYPE COMMOH TAP (BROKEN OR SYSTKH ID SEHSOR MPL PLUGGED PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT NUCLEAR B22-H036h BROKEN MAXIMUM DIFFERENTIAL PRESSURE RECIRC PUMP A BKR "3A" ATVS LOU HONE BOILER SIGHAL LEVEL 2 ~ 1/2 TRIP INOPERATIVE CIMNNEL C REMAINS OPERATIVE PUJGCED CONSTANT DIFFERENTIAL PRESSURE RECIRC PUMP A BKR "3h" ATQS LOU NONE SIGNAL LEVEL 2 ~ 1/2 TRIP INOPERATIVE-CHANHEL C REMAINS OPERATIVE B22-H036B BROKKH MAXIMUM DIFFEREHTIAL PRESSURE RECIRC PUMP B BXR "3B" ASS QN HONE SIGNAL LEVEL 2 ~ 1/2 TRIP INOPERATIVE CHANNEL D REMAINS OPERATIVE PLUCGED COHSTAHT DIFFERENTIAL PRESSURE RECIRC PUMP B BKR "3B" ATVS QN NONE SIGNAL LEVEL 2, 1/2 TRIP IHOPERATIVE-CMANNEL D REMAINS OPERATIVE B22-N026B BROXEH MAXIMUM DIFFERENTIAL PRESSURE REACTOR LOU LOU MATER LEVEL MAIN STEAM LINE ISOLATION VALVES SIGNAL ISOLATIOH LOGIC "B" TRIP CLOSURE I/2 TRIP REMAINS OPERATIVE IHOPERATIVE HIOM CHANNEL "D" CIRCUITRY PLUCGED CONSTANT DIFFEREHTIAL PRESSURE REACTOR IAN LOll MATER LEVEL MAIH STEAM I.INE ISOLATION VALVES S I CHAL ISOLATION LOGIC "B" TRIP CLOSURE I/2 TRIP REMAINS OPERATIVE INOPERATIVE FROM CHANNEL "D" CIRCUITRY B22-N037A BROKEN MAXIMUM DIFFEREHTIAL PRESSURE I/2 DIVISION I ADS ~ RCICi LPCS HONE AND SICNAL LOGIC TRIP INOPERATIVE B22-N031C PLUCCED CONSTANT DlFFERENTIAL PRESSURE 1/2 DIVISION 1 ADS INOPERATIVE; HONE SIGNAL LPCS LEVEL IHOP; RCIC 1/2 LEVEL TRIP INOPERATIVE IHSTRUMKNT LIHE 14 20 N14 REFKRKHCK LKG (COHDENSING CHAMBER B22-DOOCD)

PACE I OF 3

~

12-0286 (22)

HANFORD COt010N SEHSOR FAILURE TABLE TABLE PAGE 23 41, PAGES TOTAL FAILURE TYPE TAP (BROXEH OR 'OHHOH SYSTEH ID SENSOR MPL PLUGGED PRItlhRY EffECT SECONDARY EFFECT B22-H I 0 l A BROKEN HAXIHUH DlfFERENTIAL PRESSURE RCIC ISOLATION VALVE E41-F045 NONE SIGNAL (HIGH LEVEL) I/2 TRIP PLUGGED COHSThllT DiffEREHTIAL PRESSURE RCIC ISOLATION VALVE E41-F045 NOHE SIGNAL (NIGH LEVEL) TRIP INOPERATIVE B22-N024B BROKEH HAXIHUH DIFfEREHTIAL PRESSURE REACTOR CHANHEL Bl LOM LEVEL SCRAH NONE SIC HAL TRIP IHOPERATIVE PLUGGED COHSTANT DIFFERENTIAL PRESSURE REACTOR CIIANNEL Bl IAN LEVEL SCRAM NONE SIGNAL TRIP INOPERATIVE B22-H039 BROKEH HIHIHUH PRESSURE SIGHAL ShfETY RELIEF VALVES IHITIATIOH SAFETY RELIEF VALVES INITIATION (h TURU V) CIRCUIT IHOPERATIVE IHOPERAT IVX PLUGGED CONSTANT PRESSURE SIGNAL ShiETT RELIEF VALVES IHITIATIOH HOHE CIRCUIT INOPERATIVE B22-H045A BROKEH HIHIHUH PRESSURE SIGNAL RECIRC PUHP IA BXR "3A" ATNS HIGH PRESSURE TRIP INOPERATIVE B'Y C AND D CIRCUITS I BACKED PLUGGED CONSThhT PRESSURE S IGHAL RECIRC PUHP lh BKR "3h" ATUS HIGH NONE PRESSURE TRIP INOPERATIVE; BACKED BY C AND D CIRCUITS B22-N045$ BROKEN HIHIHUH PRESSURE SIGNAL RECIRC PUHP IB~ BXR 3B ATllS HIGH NONE PRESSURE TRIP INOPERATIVEI BACKED 'Y C AND D CIRCUITS IHSTRUHENT LINE 14 20 H14 REFERENCE LEG (CONDENSING CllhHBER B22-D004D)

PAGE 2 OF 3 12-0286 (23)

HANFORD COIOIOH SEHSOR FAILURE TABLE TABLE PAGE 24 4l PAGES TOTAL FAILURE TYPE CNON TAP (BROKKH OR SYSTEH ID SEHSOR HPL PLUCCED PRIHARY EFFECT PLUGGED 'ONSTANT PRESSURE SIGNAL RECIRC PUNP IB, BKR "3B" ATWS HIGH HONE PRESSURE TRIP INOPERATIVE) BACKED BY C AND D CIRCUITS B22-H023B BROKKH HIHIHUH PRESSURE SIGNAL RPS TRIP CHANNEL "Bl" REACTOR HONE TRIP ON HIGH RPV PRESSURE I HOPERATIVE PLUGGED CONSTANT PRESSURE SIGNAL RPS TRIP CHANHEL "Bl" REACTOR HONE TRIP ON HIGH RPV PRESSURE IHOPERA'TIVE B22-N020B BROKEN HIHIHUH REACTOR PRESSURE SIGNAL GIVE HSIV CLMURE BYPASS SIGNAL NONE: REACTOR INDE SWITCH IH TO SCRAH TRIP LOGIC "Bl" ONLY IH "RUN" POSITIOH BLOCKS TIIE BYPASS SIIUIDOWH, REFUEL, AND STARTUP HODR SIGHAL PLUGGED COHSTAHT REACTOR PRESSURE 8 IGHAL REACTOR HIGH PRESSURE TRIP OF HSIV NONEc REACTOR NODE SWITCH IH CLOSURE SCIUIH BYPASS IS "RUH" POSITION BLOCKS TIIE BYPASS I HOP ERAT IVE SIGNAL B22-N038A BROKEN HAXIHUH DIFFERENTIAL PRESSIIRE NOHE HONE PLUCCKD CONSTglT DIFFKRKHTIAL PRESSURE NONE NONE SI CHAL IHSTRUHKNT LINE 14 204 HI4 REFERENCE IEG (CONDENSIHG CIIAHBER B22-D004D)

PAGE 3 OF 3 I2-0286 (24)

HAHfORD COIOSH SENSOR FAILURE TABLE TABLE PAGE 25 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEN OR SYSTEM ID SEHSOR MPL PLUGGED PRIMARY EFfECT REACTOR C34-N003A BROKEN MAXIMUM STEAM flAN LINE "h" DIFF C34-R603h STEAM FUN METER FEEDVATER INCREASED FLOH 1EEDVATER PRESSURE SIGHAL IHOPERATIVE; REACTOR FEEDVATKR INCREASED FLOH PLUGGED COHSTAHT STEAM FuN LINE "A" DIFF C34-R603h STEAM FUN METER AT NONE PRESSURE SIGNAL COHSThllT READIHG; REACTOR iKED-HATER ERROR IH STEAM FLOH FOLIANIHG IXAX E31-NOOB C BROKEN LOSS OF TWO OF FOUR HIGH FIAN DIVISION I TURBIHE STEAM IINE MAIH STEAM LINE VALVES CLOSURE DETECTIOH E31-NOOSD MSIV DIVISION 2 ISOLATIOH SIGNALS HIGH FLOH DIVISION 2 ISOLATION INITIATED PLUGGED LOSS OF %Q OF FOUR HIGH FlAN NONE MSIV DIVISION 2 ISOLATIOH SIGHALS I HSTRUMEllT LIHE 15 PAGE 1 OF 1 12-0286 (25)

lthHFORD CQSON SENSOR FAILURE TABLE TABLE PAGE 26 41 PAGES TOTAL FAILURE TYPE CONHON TAP (BROKEN OR SYSTEM ID SEHSOR HPL PLUGGED PRIHARY EFfECT SECONDARY EFFECT COHBI RED EFFECT COHTROL C12-HOGS BROKEH HAXIHUH DIFFERENTIAL PRESSURE HETER C12-R009 THOPERATIVE NONE ROD DRIVE SIGHAL HYDRAIILICS PLUGGED CONSTANT DIFFEREHTIAL PRESSURE lSTER C12-R009 AT COHSTANT READIHG HONE SIGHAL C12-H011 BROKEH HIHIHUH DlffEREHTIAL PRESSURE HETER CI2-R005 IHOPERATIVE HONE SIGNAL PLUGGED COHSTAHT DIFFERENTIAL PRESSURE HETER C12-R005 AT CONSTANT READING HONE SIGNAL NUCLEAR B22-H032 BROKEN HIHIHUN DIFFEREHTIAL PRESSURE RECORDER R613 CORE PLATE DIFF NONE BOILER SIGHAL PRESSURE BLACK PEH IHOPERATIVE PLUGGED CONSTANT DIFFEREHTIAL PRESSURE RECORDER R613 CORE PLATE DIFF NONE SIGNAL PRESSURE BLACK PEN COHSTANT INDICATION IHSTRUHEHT LIHE 16 PAGE 1 OF 1 12-0286 (26)

HANFORD COMMON SEHSOR fhlLURE TABLE TABLE PAGE 27 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEN OR PRIMARY EFfECT SECONDARY EFFECT COMBINED EFFECT SYSTEM ID SENSOR MPL PLUGGED REACTOR C34-H003A BROKEN MINIMUM STEAM FIAN LINE "A" DIFF C34-R603h S1EAll HA% METER FEEDVATER DECREASED fLOJ FEEDVATER PRESSURE SIGNAL INOPERATIVE; REACTOR FEEDHATER DECREASED FLOU PLUGGED CONSTANT STEAM fllN LINE i>An DIFF C34-R603A STEAM HlN METER HONE PRESSURE SIGNAL INOPERATIVE; REACTOR FEEDVATER ERROR IH STEAM FIAN FOLIANIHG LEAK E31-HOOdh LOSS OF DQ OF FOUR HIGll FLOH DIVISION I TURBIHE STEAM LINE HONE DETECTIOH E31-HOOSB MSIV DIVISIOH I ISOLATION SIGNALS HIGH FBI DIVISION I ISOLATION DISABlKD, BUT DIVISIOH I ISOLA-TIOH IS INTACT PLUGGED LOSS OF TlQ OF FOUR MIGll FUW HONE MSIV DIVISIOH 1 ISOLATIOH SIGNALS INSTRIRIENT LINE I7 PAGE I OF 1 12-0286 (27)

HANFORD COl0lOH SEHSOR FAILURE TABLE TABLE PAGE 2B 41 PAGES TOTAL FAILURE TYPE CONHOH TAP (BROXEH OR SYSTEH ID SENSOR HPL PLUCCED PRIHARY EFfECT SECONDARY EFFECT REACTOR C34-H003A BROKEN HAXIHUH STEAH FLAN LINE "h" Diff C34-R603h STEAH FLOM HETER FEEDMATER INCREASED FLOM FEKDMATER PRESSURE SIGNAL INOPERATIVE; REACTOR FEEDMATER IHCREASED FLOM PLUGCED CONSTANT STEAN FLOM LINE "h" DIFF C34-R603h STEAM FlAN HETER AT HONE PRESSURE SICHAL CONSTANT READING; REACTOR FEEDMATKR ERROR IH STEAN FMM FOLLOMIHG LEAK E31-HOOBA BROKEN INITIATE TMO OF fOUR HIGH FLOM DIVISION I TURBINE STEAN LINE HAIN STEAM LIHE ISOLATIOH VALVES DETECTIOH E31-NOOSB llSIV D)VISIOH I ISOLATIOH SIGNALS HICH FLOM DIVISIOH I ISOLATION CLOSURE INITIATED PLUCCED LOSS Oi TMO Oi FOUR HICH FMM NONE HSIV DIVISION 1 ISOLATION SICNALS I NSTRUHKNT LINE 1$

PACE I OF I 12-0286 (28)

IQNFORD COMMON SENSOR FAILURE TABLE TABIE PAGE 29 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEN OR PRIMARY EFFECT SECOHDARY EFFECT COMBINED EFFECT SYSTEM ID . SENSOR MPL PLUGGED REACTOR C34-H003B BROKEN MINIMUM STEAM FLOH LINE "B" DIFF C34-R603B STEAM FIAN METER FEEDNATKR DECREASED FLOH FEE DVATKR PRESSURE SIGHAL INOPERATIVE: REACTOR FKEDVATKR DECREASED FLOH PLUGGED CONSTANT STEAM FUN LINE "B" DIFF C34-R603B STEAM FIAN METER PRESSURE SIGNAL INOPERATIVE: REACTOR FEEDVATER ERROR IH STEAM FLOH FOLLONIHG LEAK E31-N009h BROKEN LOSS Of TWO Of fOUR HIGH FLOH DIVISION I TURBINE STEAM LINE DETECTION E31-N009B MSIV DIVISION 1 ISOLATION SIGHALS HIGH FLOH DIVISIOH 1 ISOLATION DISABLED, BUT DIVISION 2 ISOLA-TIOH IS INTACT PLUGGED LOSS OF TWO OF FOUR HIGH FLOM NOHE HONE MSIV DIVISIOH I ISOLATIOH SIGHALS INSTRUMEHT LINE 19 PAGE 1 OF 1 12-0286 (29)

HAHFORD COHNON SENSOR FAILURE TABLE TABLE PAGE 30 ~

41 PAGES TOTAL FAILURE TYPE CWON TAP (BROKEN OR SYSTEH ID SENSOR HPL PLUGGED PRIHARY EFFECT SECONDARY EFFECT COHBINED EFfECT REACTOR C34-N003B BROKEN HAXIHUH STEAN FLOM LINE "B" DIFF C34-R603B STEIW FIT HETER FEEDMATER IHCREASED HAM ~ C lEEDMATER PRESSURE SIGNAL IHOPERATI VE REACTOR FEEDMATER INCREASED FLOM PLUGGED CONSTANT STEAN FLOM LINE "B" DIFF C34-R603B STFJlH FLOM HETER AT NONE PRESSURE SIGNAL CONSTANT READING; REACTOR FEEDMA1ER ERROR IH STEAN FLOM FOLLOMIHG LEAN E31-N009h BROKEN IHITIATE TMO OF FOUR HIGH FLOM DIVISION I TURBINE STEhll LINE HAIH STEAN LINE ISOLATIOH VALVES DETECTIOH E31-H009B HSIV DIVISION I ISOLATIOH SIGHALS HIGH FLOM DIVISIOH I ISOLATION CLOSURE INITIATED PLUGGED LOSS OF TQO OF FOUR HIGll FLOM HOHE NOHE NSIV DIVISIOH I ISOLATIOH SIGHALS INSTRUNEHT LINE 20 PAGE I OF I 12-0286 (30)

0 HAHFORD COMMON SENSOR FAILURE TABLE TABLE PAGE 31 41 PAGES TOTAL PAI LURE TYPE COMMOH TAP (BROKEH OR SYSTEM ID SENSOR MPL PLUCCED PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT REACTOR C34-H003C BROKEH MINIMUM STEAM PION LINE "C" DIFF C34-R603C STEAM HON METER FEEDIIATER DECREASED FllN FEEDVATER PRESSURE SIGNAL INOPERATIVE; REACTOR FEEDHATER DECREASED PION PLUGGED COHSTANT STEAM FUN LINE "C" DIFF C34>>R603C STEAM FIOM METER PRESSURE SIGNAL INOPERATIVE; REACTOR FEKDVATER ERROR IH STEAM FIAN FOLLOVING LEAK E31-N010C BROKEN lOSS OF TNO OF FOUR MICH HlN DIVISION 2 TURBINE STEAM LIHE HONE DETECTIOH E31-H010D MSIV DIVISIOH 2 ISOLATION SIGHALS NIGH FlAN DIVISIOH 2 ISOLATIOH DISABLED, BUT DIVISIOH I ISOLATIOH IS INTACT PLUCCED LOSS OP TlO OF FOUR HIGH FLOM HONE NOME MSIV DIVISIOH 2 ISOLATION SIGHALS IHSTRUMENT LIHE 21 PAGE 1 OF I 12-0286 (31)

HANFORD COHHOH SENSOR FAILURE TABLE TABLE PAGE 32 41 PAGES TOTAL FAILURE TYPE COHHOH TAP (BROKEH OR SYSTEH ID SEHSOR NPL PLUGCED PRIHAllY EFFECT SECONDARY EFFECT COHBINED EFFECT REACTOR C34-H003C BROKEH HAXIHUH STEAN FLO'W LIHE "C" DIFF C34-R603C STEAN FLOW HETER FEEDWATER IHCREASED FMW FEEDWATER PRESSURE SIGNAL IHOPERATIVE REACTOR FEEDWATER INCREASED FLOW PLUCGED CONSTANT STEAN FLOW LINE "C" DIFF C34-R603C STEAN FMW HETER AT NONE PRESSURE SICNAL CONSTANT READING I REACTOR FEEDWATER ERROR IN STEAN FlAN FOLLOWING LEAK E31-N010C BROKEN INITIATE TWO OF FOUR NIGH FLOW DIVISIOH 2 TURBINE STEAM LINE HAIN STEAM LINE ISOLATION VALVES DETECTION E31-HO I OD HSIV DIVISION 2 ISOLATION SIGNALS DICH FLOW DIVISION 2 ISOLATION CLOSURE INITIATED PLUCGED LOSS OF TWO OF FOIJR HIGH FLOW NONE HONE HSIV DIVISION 2 ISOLATIOH SICNALS I NSTRUNENT L)HE 22 PACE I OF I 12-0286 (32)

SANFORD CONNOH SENSOR FAILURE TABLE TABlX PAGE 33 41 PAGES TOTAL FAILURE TYPE COOSH TAP (BROXEN OR SYSTKH ID SENSOR NPL PLUGGED PRIHARY EFFECT SECONDARY EFFECT REACTOR ,C34-N003D BROEEH HIHINUH STEAN FLOM LINE "D" DIFF C34-R603D STEAN FUN HETER FEEDMATER DECREASED FLOM FEEDMATER PRESSURE SIGHAL IHOPERATI VE; REACTOR FEEDMATER DECREASED FLOM PLUGGED CONSTANT STEAN LINE fLOM "D" DIFF NOHE NONE PRESSURE SI CHAL LEAK E31-HOI IC BROKEN LOSS Of TMO Of FOUR HIGH FLOM DIVISION 2 TURBINE STEAM LINE HONE DETECTIOH E31-NOI ID HSIV DIVISIOH 2 ISOLATIOH SIGHALS FLOM DIVISION 2 ISOLATION DISABLED, BUT DIVISION I ISOLA-TION IS IHTACT PLUGGED LOSS OF TMO Of FOUR HIGll FUN NOHE NONE NSIV DIVISIOH 2 ISOLATION SIGNALS I HSTRUNEHT LINE 23 PAGE I OF 12-0286 (33)

HAHFORD GNMOH SENSOR FAILURE TABLE TABLE PAGE 34 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEH OR SYSTEM ID SENSOR MPL PLUGGED PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT REACTOR C34-N003D BROKEN MAIIHUM STEAM FIAN LIHE "D" DIFF C34-R603D STEAM FIAN METER FEE)NATKR IHCREASED FIAN FEKDMATER PRESSURE 5 I CHAL INOPERATIVE I REACTOR FKKDMATER DECREASED FIA)M PLUGGED COHSTANT STYE FIAN LINE "D" DIFF C34-R603D STEAM FLOM METER NONE PRESSURE SIGNAL INOPERATIVE; REACTOR FEEDMATKR ERROR IN STEAM FLOM FOLIANIHG LEAK E31-NO l IC BROKEH INITIATE TMO OF fOUR HIGH FIAN DIVISION 2 TURBINE STEAM LINE MAIN STEAM LIHE ISOLATION VAI.VES DETECTIOH E31-N010D MSIV DIVISIOH 2 ISOLATIOH SIGHALS HIGH FLOM DIVISIOH 2 ISOLATION CLOSURE IH ITIATKD PLUGGED LOSS OF TlJO Oi FOUR HIGH HAN NONE NONE MSIV DIVISION 2 ISOLATION SIGHALS IHSTRUHKHT LINE 24 PAGE I OF I 12-0286 (34)

HAHFORD COMMON SENSOR FAILURE TABLE TABLE PAGE 35 41 PAGES TOTAL FAILURE TYPE COMMON TAP, (BROXKN OR SYSTEM ID SKHSOR MPL PLUGCKD PRIMARY EFFECT SECONDARY EffECT COMBINED EFfECT NUCLEAR B22-H100B BROXKN MINIMUM DIFfKREHTIAL PRESSURE DIVISION 2 HALF Of HPCS HIGH HONE BOILER SIGHAL LEVEL SEAL 'H INOPERATIVE PLUCGKD COHSTAHT DI FFEREHTIAL PRESSURE DIVISION 2 HALF Oi ItPCS HIGH HONE SICHAL LEVEL SEAL IH INOPERATIVE B22-H024C BROXKH MINIMUM DIFFERENTIAL PRESSURE RPS CHANHKL A2 AN LEVEL SCRAM I/2 REACTOR SCRAM SIGNAL TRIP PLUGGED CONSTANT DIFFERKHTIAL PRESSURE RPS CHANHEL h2 DN LEVEL SCRAM NONE SI CHAL TRIP IHOPERATIVE B22-H024D BROXKH MIHIMUM DIFFERENTIAL PRESSURE RPS CHANNEL B2 UN LEVEL SCRAM I/2 REACTOR SCRAM SIGHAL TRIP PLUGGED CONSTANT DIFFERENTIAL PRESSURE RPS CHAHNEL B2 QN LEVEL SCRAM HONE SIGHAL TRIP INOPERATIVE B22-N03$ B BROXKH MINIMUM DlifERENTIAL PRESSURE I/3 DIVISION 2 AUTO DEPRESSURIZA- %Q ADDITIOHAL RPV IAN LEVEL TRIPS SIGNAL TION LOCIC TRIP HEEDED TO ALUM ADS INITIATION FROM DIVISIOH 2 PLUGGED COHSTANT DIFFERENTIAL PRESSURE DIVISIOH 2 AUTO DEPRKSSURIZATION ADS INITIATIOH AVAILABLEFROM SICHAL LOGIC INOPERATIVE DIVISION I B22-N101B BROXEH MIHIMUM DIFFERKHTIAL PRESSURE RCIC ISOIATION VALVE E51-f045 RCIC ISOLATIOH VALVE E51-F045 CLOSURE OH HIGH REACTOR LEVEL CLOSURE OH MANUAL IHITIATIOH ONLY INOPERATIVE INSTRUMENT LINE 25 1904 H13 VARIABLE SIGNAL SENSING LINE PAGE I OF 2 12-0286 (35)

tfhNFORD CONNON SENSOR FAILURE TABLE TABLE PAGE 36 41 PAGES TOTAL FAILURE TYPE CONNOH TAP (BROKEN OR SYSTKtl ID SENSOR HPL PLUGCED PRI NARY EFFECT SECOHDARY EFFECT COtfBIHED EFFECT PlllCGKD CONSTAHT DIFFERENTIAL PRESSURE RCIC ISOLATION VALVE E51-F045 RCIC ISOLATION VALVE E51-F045 CLOSURE OH DICH REACTOR LEVEL CLOSURE ON HANUAL IHITIATIOH OHLY INOPERATIVE NUCLEAR B22-N027 BROKEN Hlgltmtt REACTOR VESSEL LEVEL B22-R605 HETER IHOPKRATIVE OFF HONE BOILER SIGHAL SCAIKi IAN LEVEL CONSTANT REACTOR VESSEL LEVEL B22-R605 METER AT COHSTAHT READING HONE SIGNAL REACTOR C34-H004B BROKEN tflHIHUtf DIFFERENTIAL PRESSURE C34-R606B MATER LEVEL RECORDER FEKDMATKR INCREASED FLOM FKKDMAIKR SIGNAL INOPERATIVE'EACTOR FEKDMATKR INCREASED FLOM PLUGGED COHSTAHT DIFFERENTIAL PRESSURE C34-R606B MATER LEVEL RECORDER AT NONE SIGNAL CONSTANT READIHG; REACTOR FKKD-MATKR ERROR IH LEVEL FOLLOMIHG C34-H004C BROKEH HIHINUtf DIFFERENTIAL PRESSURE C34 R606C MATER LEVEL RECORDER NONE SIGNAL IHOPERATIVE PLUGGED CONSTANT DIFFKRKNTfhL PRESSURE C34-R606C MATER LEVEL RECORDER AT NONE SIGNAL CONSTANT READING C34-N017 BROKEN tflgftfUtf MIDE RANGE REACTOR LEVEI, C34-R608 RECORDKR RECISTKRS NONE ~

SICNAL N 1gl tati SI CHAL PLUGGED CONSTAHT MIDE RANCE REACTOR LEVEf C34-R608 RECORDER REGISTERS NONE SICHAL CONSTANT SIGNAL IHSTRUMEHT LIHK 25 190 H13 VARIABLE SICHAL SEHSIHG LINE PAGE 2 OF 2 12-0266 (36)

NANFORD COHHON SENSOR FAILURE TABul TABLE PAGE 37 41 PAGES TOTAL FAILURE TYPE

.COHNOH TAP (BROKEN OR SYSTEH ID SENSOR HPL PLUGGED PRINARY EFfECT SECONDARY EFFECT

$ 22-N03lh BROKEH HIHI HUH DlffERENTIAL PRESSURE REACTOR HIGll PRESSURE CORE SPRAY PREVENTS HIGH 'MATER LEVEL SEAL-IH AND SIGNAL DIVISION 2 LOM LEVEL TRIP OF HPCS PUHP DISCHARGE VALVE B22-H031C CIRCUITRY PLUGGED CONSTANT DlifERENTIAL PRESSURE REACTOR NIGH PRESSllRE CORE SPRAY NONE SIGHAL DIVISION 2 LOM LEVEL IHOPERATIVE

$ 22-N026A BROKEH HIHIHUH DIFFEREllTIAL PRESSURE REACTOR LOM LOM MATER LEVEL HAIN HAIN STEAN ISOLATIOH VALVES SIGHAL STEAN ISOLATIOH LOGIC h TRIP CLOSURE I/2 TRIP PLUGGED CONSTANT DIFFERENTIAL PRESSURE REACTOR LOM LOM 'MATER LEVEL HAIN HAIH STEAN ISOLATION VALVES SIGNAL STEA!l ISOLATION LOGIC A TRIP CLOSURE I/2 TRIP STILL OPERATIVE INOPERATIVE FRON CHANNEL "C" CIRCUITRY INSTRUHENT LINE 26 2604 H12 VARIABIX SIGNAL SENSING LINE PAGE I OF I 12-0286 (31)

HAHFORD COMMON SENSOR FAILURE TABLE TABLE PAGE 38 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKKH OR SYSTKli ID SENSOR MPL PLUGGED PRIMARY EFFECT SECONDARY KFfECT B22-H031B BROKEN MIN IMW DIFfKRENTIAL PRESSURE REACTOR HIGll PRESSURE CORE SPRAY PREVENTS NIGH HATER LEVEL SEAL-IH AND SIGHAL DIVISION 2 UN LEVEL TRIP Oi HPCS PUMP DISCHARGE VALVE B22-H03)D C I RCUITRY PLUGGED CONSTANT DIFfEREHTIAL PRESSURE REACTOR HIGH PRESSURE CORE SPRAY HONE SIGNAL DIVISION 2 IlN LEVEL INOPERATIVE B22-H026C BROKKH MINIMW DIFFKRKHTIAL PRESSURE REACTOR LOU IAN MATER LEVEL MAIN MAIN STEAM ISOLATIOH VALVES SIGNAL STEAM ISOLATIOH IOGIC C TRIP CLOSURE I/2 TRIP PLUGGKD CONSTANT DlFFKREHTIAL PRESSURE REACTOR Iul LOU MATER LEVEL MAIH MAIH STEAM ISOLATION VALVES SIGNAL STEAM ISOLATION LOGIC C TRIP .CLOSURE I/2 TRIP STILL OPERATIVE I HOPERATI VE FROM CHANHEL "h" CIRCUITRY INSTRUMENT LINK 27 160~ H12 VARIABLE SIGNAL SENSING LIHE PAGE 1 OF I 12-02S6 (3S)

HAHFORD COMMON SENSOR FAILURE TABLE TABLE PAGE 39 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEH OR SYSTEM ID SEHSOR MPL PLUGGED PRIMARY EFFECT SECONDARY EFFECT COMBINED EFFECT NUCLEAR B22-N026B BROKEH MINIMUM DIFFEREHTIAL PRESSURE REACTOR IAN LOU HATER LEVEL MAIN MAIN STEAM ISOLATIOH VALVES BOILER SIGHAL STEAM ISOLATIOH LOGIC "8" TRIP CLOSURE I/2 TRIP PLUGGED COHSTANT DIFFERENTIAL PRESSURE REACTOR LOH LOll HATER LEVEL MAIN MAIN STEAM ISOIRTIOH VALVES SIGNAL STEAM ISOLATION LOGIC "B" TRIP CLOSURE I/2 TRIP STILL OPERATIVE INOPERATIVE FROM CllhHNEL "D" CIRCUITRY B22-N036h BROKEN MINIMUM DIFFERENTIAL PRESSURE RECIRC PUMP A, BKR 3h ATUS QN RECIRC PUMPS h AND B AT LOU SPEED SIGHAL LEVEL 2 TRIPS OPERATION PLUGGED CONSTANT DIFFERENTIAL PRESSURE RECIRC PUMP h, BKR 3A ATlJS LOQ HONE SIGHAL LEVEL 2, I/2 TRIP IHOPERATIVE-CMAHHEL C REMAINS OPERATIVE B22 H036B BROKEN MIHIMUM DIFFERENTIAL PRESSURE RECIRC PUMP B, BKR 3B ASS LOU RECIRC PUMPS h AND B AT UN SPEED SI CHAL LEVEL 2 TRIPS OPERATIOH PLUGGED COHSTANT DlFFEREHT I AL PRESSURE RECIRC PUMP B, BKR 3B ATNS IlN SIGHAL LEVEL 2y I/2 TRIP INOPERATIVE CIMNHEL D RMlIHS OPERATIVE B22-N037A BROKEN MINIMUM DIFFERENTIAL PRESSURE DIVISIGH 2 AUTO DEPRESSURIZATIOH AHD SIGNAL LOGIC PARTIAL TRIP; LPCS B22-N037C INITIATED; RCIC INITIATED PLUGGED COHSTAHT DIFFEREHTIAL PRESSURE DIVISION 2 AUIO DEPRESSURIZATIOH NONE SIGNAL LOGIC IHOPERATIVE; LPCS LEVEL TRIP INOPERATIVE INSTRUMENT LINE 28 204 H12 VARIABLE SIGNAL SEHSIHG LINE PAGE I OF I 12-0286 (39) 4

HANFORD COHHOH SEHSOR FAILURE TABLE TABLE PACE 40 41 PAGES TOTAL FAILURE TYPE COHHON TAP (BROKEN OR SYSTEH ID SEHSOR HPL PLUCCED PRI HART EFFECT SECONDARY EFFECT NUCLEAR B22-H026D BROXEH HIHIHUH DIF1EREITIAL PRESSURE REACTOR UN UN MATER LEVEL HAIH HAIN STEAN ISOLATION VALVES BOILER SIGNAL STEAN ISOLATION LOGIC "D" TRIP CLOSURE I/2 TRIP PLUGGED COHSTANT DIFFEREHTIAL PRESSURE REACTOR UN UN'MATER LEVEL HAIH HAIN STEAH ISOLATION VALVES 8 I CHAL STEAN ISOLATION LOGIC "D" TRIP 'CLOSURE I/2 TRIP STILL OPERATIVE INOPERATIVE FROH CHANHEL "S" CIRCUITRY B22-H036C HIHIHUH DIFFERENTIAL PRESSURE RECIRC PUMP A, BKR 3A ATMS LOM RECIRC PUHPS h AND S AT UN SPEED SIGNAL LEVEL 2 TRIP OPERATION PLUCCED CONSTAHT DIFFERENTIAL PRESSURE RECIRC PUMP h, BXR 3h ATMS UN SICHAL LEVEL 2 TRIP IHOPERATIVE B22-N036D BROXEH HIMIHUH DIFFERENTIAL PRESSURE RECIRC PUHP B, SKR 3B ATMS UN SIGNAL LEVEL 2 TRIP PLUGGED CONSTANT DIFFERENTIAL PRESSURE RECIRC PUHP B, BKR 3B ATMS LOM HOHE SICHAL LEVEL 2 TRIP INOPERATIVE B22-H031B BROKEN HIHIHUH DIFFERENTIAL PRESSURE I/3 DIVISION 2 AUTO DEPRESSURIZA-AND SIGNAL TIOH LOGIC TRIP B22-H031D PLUCGED COHSTAHT DIFFERENTIAL PRESSURE DIVISIOH 2 AUTO DEPRESSURIEATION HONE SIGNAL LOCIC INOPERATIVE IHSTRUHEHT LINE 29 2004 MI2 VARIABLE SIGHAL SEHSIHG LINE PAGE I OF I

'I2-0286 (40)

MANFORD COMMON SKHSOR FAILURE TABLE TABLE PAGE 41 41 PAGES TOTAL FAILURE TYPE COMMON TAP (BROKEN OR SYSTKM ID SENSOR MPL PLUGGED PRIMARY EFFECT NUCLEAR B22-N044B BROKEN MINIMUM DIFFEREHTIAL PRESSURE REACTOR VATKR LEVEL IHDICATOR R610 NOTE: THIS INSTRUMENT IS USED BOILER SIGHAL SllOVS MINIMUM LEVEL ONLY DURIHG REACTOR SNUIDOUH AND NHEH RECIRC PUMPS ARE SECURED. h BROKEH INSTRUMENT LINE HILL GIVE h ZERO OR MIHIMUM VESSEL HATER LEVEL READING.

PLUGGED CONSTANT DIFFERENTIAL PRESSURE REACTOR HATER LEVEL INDICATOR R610 NONE SIGNAL CONSTANT B22-N033B BROKEH MINIMUM DIFFERENTIAL PRESSURE JET PUMP FLOV CIRCUITRY NONE SIGNAL INOPERATIVE PLUGGED ERRATIC DIFFERENTIAL PRESSURE JET PUMP FQN CIRCUITRY HONE SIGHAL INOPEIUlTIVE INSTRUMENT LIHE 30 VARIABLE SIGHAL SENSING LINE (HIGH PRESSURE PAGE I OF I CONHECTION JET PUMP) (B22-H033B llIGH SIDE) .

l2-0286 (41)

WHPP-2 CO)3) SllUTDOWH SYSTBIS - RllR LOOP h APPENDIX CROUP )) SllEET 38 v 66 iB'RIMARY BUS BUS DEVICE DEVICE PRIMARY BERBER DIV HUHBER DESCRIPTION EFFECT ON DEVICE EFFECT OH SYSTEM ALARM POINT PP>>7A-A TCS1-006 TRAHSHITTER FOR SOLENOID VALVE MILL LOSS OF RllR "h" AHD "SSM h SUPV SYSTEM TCS1-007 SW-SPV-38A CONTROL REMAIN EHERGIZED KEEP DIV 1 llVAC FROH LOSS TROUBLE" RCS)-037 RECEIVERS AHD SUPV. SW-PCV-38h CLOSED. OF SSM LOOP A "SSM h OUT-OF<<SERVICE" RCSI-038 RELAYS FOR LOSS OF POS ~ IND. NOTE 2 SCS)-037 SM-PCV-38h POS. IND.

SCS)-038 PP-7A-A RCS)-005 SUPV. RELAYS AND SUPV. REIAYS DEENER- NONE. "SSM h SUPV. SYSTEH RCS)-006 RECEIVERS FOR GIZEBLOSS OF POS TROUBLE" RCS1-007 SW-V-69A POS. INDICATION AHD VALVE "SSM h OUT-OF-SERVICE" RCS1-008 SMITCIIES MILL FAIL-AS-IS {H.O.) NOTE 2 RCS1-020 RCS1-032 SCS)-005 SCS1-006 SCS1-007 SCS)-008 SCS)-020 SCS1-032 PP-7A-A RCS1-009 RECEIVERS AND SUPV. SUPV. RELAYS DEENER- NOHE. "SSM h SUPV. SYSTEH RCS1-010 RELAYS FOR SW-V-70B CIZE LOSS OF POS. TROUBLE" RCS1-011 POS SWITCllES INDICATION AND VALVE "SSM h OUT-OF-SERVICE" RCS)-012 MILL FAIL-AS-IS (N.O,) NOTE 2 RCS)-023 RCS1-033 SCS1-009 SCS1-010 SCS1-01)

SCS1<<0)2 SCS1-023 SCS1-033 13-0187 (38)

QHPP-2 COLD SHUTDOMH SYSTEMS - R)IR LOOP h APPENDIX 'B CROUP H SIIEET 39 0 o6 BUS BUS DEVICE DEVICE PRIHARY PRIMARY EUIIBER DIV EIBIBER DESCRIPTION EFFECT ON DEVICE EPPECT OH SYSTEM hLARH POINT PP-7A-A 1 TCS1-004 TRANSHITTER POR RECEIVERS AT PUHl'OSS OP SSM LOOP "h" "SSM h SUPV. SYSTEH TCS1-005 LOCAL OPERATING HOUSE MILL NOT CHANGE PVHP LOSS OF RHR "h" TROUBLE" SCS1-026 IHDICATIOH SUPV. STATE AHD LOCAL OPER; "SSM h OUT-OP-SERVICE" SCSI-061 RELAYS AND RECEIVERS IND. QOULD NOT CIIANGE. "SSM PP llOUSE h SCS1-062 FOR CONTROL OP SUPV. RELAYS WOULD PRA-FN-h LOM FLOW" RCS1-026 PRA-FH-1h DEEHERGIZE CAUSING RCS1>>061 TIIE PAN TO FAIL TO RCS1-062 OPERATE HC-7h 1 SW-V-2A SM-P-lh DISCHARGE HOV FAILS-AS-IS LOSS OF RIIR "h" AHD RG 1 ~ 47 BISI VALVE (N.C.) DIV ) IIVAC "HOV NETMORK POWER LOSS/OL" "SSM h OVT-OF-SERVICE" HC-7A 1 SM-V-)2h I.OOP h MATER RETVRN HOV FAILS-AS-IS LOSS OF SSM 'Eh'I "HOV NETWORK POWER TO SPRAY POND "B" (H.C.) RETURN TO SPRAY LOSS/OL'I ISOL VALVE POND "B" BVT "SSW h OUT-OP-SERVICE" RETURH TO COOLING TOMERS REHAINS OPERABLE HC-7A 1 SM-V-69A SSM LOOP E'h" RETURN HOV PAILS-AS-IS "HOV NETWORK POWER TO COOLING TOMER (N.O.) LOSS/OL" ISOL. VALVE "SSM h OUT-OP-SERVICE" HC-7h 1 SM-V-70B SSM LOOP "B"- RETURN HOV PAILS-AS-IS HONE "HOV NETWORK POWER TO COOLING TOWERS (H.O.) LOSS OF POS, LOSS/OL" ISOLATION VALVE INDICATIOH "SSM h OUT-OF-SERVICE" NOTE 2 HC-7A-A 1 PRA-FN-lh SSM PUHP llOVSE "h" FAN FAILS TO OPERATE LOSS OP SSM LOOP "h" PRA FN 1h POWER LOSS FAN COIL VHIT MOTOR AND LOSS OF POS. PUMP "SSW h OUT-OF-SERVICEEE INDICATION OF HCC LOSS OF RNR "h" RG 1 '7 BISI ALARHS ON ANY SYSTEH SUPPLIED BY SSMA 13-0187 (39)

MHPP-2 COLD SIIUTDOWH SYSTEMS - RIIR LOOP h APPENDIX 'B'ROUP H SHEET 40 0 66 BUS BUS DEVICE PRIMARY PRIHARY lllMIER DIV EDRRER'EVICE DESCRIPTION EFPECT ON DEVICE EFPECT ON SYSTEH ALARH POINT HC-7B-A 1 E)2-F042h Rl)R INJECTION VALVE MOV FAILS AS IS LOSS OP LPCI h IMEC- 1) "HOV NETWORK PMR (N.C.) TION VALVE LOSS/OL" LIG)IT

2) "LPCS/RHR h OUT OP SERVICE" ANHUH.

MC-7B 1 . SM-V-24h SSM SHUTOPP VALVE HOV FAILS-AS-IS LOSS OP RIIR-P-2A RG 1.47 BISI PROM R)IR-P-2h AND (N.C.) LOSS OF POS. AND RRA-FC-2 "RHR PUHP 2h ROOH )IVAC RRA-PC-2 IND. OUT-OP-SERVICE" "R)IR h OUT-OP-SERVICE" NOTE 2 MC-7B 1 RRA-FH-2 )IVAC FOR UHIT POR LOSS OF POWER AND LOSS OP RIIR-P-2h "R)IR PUMP RM-2 RRA-PC-2 RIIR-P-2h ROOH CONTROL TO PAN. TRIP" LOSS OP LOCAL INDICA- RC 1.47 BISI TION "RHR PUHP 2h RM NVAC OUT-OP-SERVICE" "MIR h OUTWF-SERVICE" HC-78-h Dl E12-P004A HOV PUHP SUCTION HOV PAILS AS IS ~ NONE. 1) "HOV NETWORK POWER FROH SUPPRES. POOL (H.O.) LOSS/OL'I LIGHT

2) RHR h/LPCS OUT OP SERVICE ANNUNC.

E12-F024h Rl!R LOOP "h" TEST MOV PAILS AS IS ~ USED FOR SUPPRESSION 1) "HOV NETWORK POMER VALVE (H.C.) POOL COOLING LOSS/OL" LIG)IT

2) RllR h/LPCS OUT OP SERVICE ANHUHC.

E12-P064h Rl)R PUMP AS MIH. HOV PAILS AS IS, 'VALVE USED FOR START- 1) "MOV NETWORK POWER FLOM VALVE (H.C.) UP OF SYSTEM. NO LOSS/OL" LIGliT EFFECT . 2) R)IR h/LPCS OUT OP SERVICE AHHUt)C.

) 3-0 I 87 (40)

QHPP-2 COLD SIIUTDOMN SYSTEHS <<RllR LOOP h APPENDIX 'Bi CROUP H SIIEET 41 0 6 BUS BUS DEVICE DEVICE PRIHARY PRIMARY NIIHBRR DIN NDH BR R DESCRIPTIOH EFFECT ON DEVICE EFPECT ON SYSTEH ALARH POIHT HC-7B-B Dl E12-P073h RllR llX "h" OUTLET HOV PAILS AS IS ~ NEAT X. VENT CAPA- 1) "HOV NETMORK POMER VENT (H.C.) BILITY LOST. HO LOSS/OL" LIGIIT EFFECT. 2) RHR h/LPCS OUT OF SERVICE ANHlJHC.

E12-P074A RIIR HX "h" IHBOARD HOV FAILS AS IS ~ llEAT X. VENT CAPA- 1) "HOV NETWORK POWER VEHT (N.C.) BILITY LOST. NO LOSS/OL" LICHT EFFECT. 2) RllR h/LPCS OUT OF SERVICE ANHUNC, E12-F048h RIIR HX "h" BYPASS FAILS AS IS ~ (H.O.) LOSE COOLDOMN RATE 1) "HOV NETWORK POMER CONTROL LOSS/OL" LIGHT

2) RHR A/LPCS OUT OF SERVICE ANNUNC.

HC-7B-B Dl E12-F068A RIIR HX "h" SM OUTLN HOV PAILS AS IS, HEAT EXCHANGER COOLIHC 1) "HOV NETWORK POWER (H.C.) LOST LOSS/OL" LIGIIT

2) RIIR h/LPCS OUT OF SERVICE ANHUNC, E12 F047h . HOV IIT EXCII INLET FhILS AS IS ~ (HB0 ) NONEB 1) "HOV HETMORK POMER LOSS/OL" LICHT .
2) RIIR h/LPCS OUT OF SERVICE ANHUHC, E12 F003A HOV HT EXCH OUTLET PAILS AS IS ~ (N 0 ) NONES 1) "HOV NETWORK POMER LOSS/OL" LICHT
2) RIIR h/LPCS OUT OF SERVICE ANNUNC E12-F016h HOV COHTAIHHENT FhILS AS IS ~ (H C.) HONE. 1) "MOV HETMORK POWER SPRAY (OUTBOhRD) LOSS/OL" LIGHT
2) RHR h/LPCS OUT OP SERVICE ANNUHC.

E12-F017h HOV CONTAINHEHT FAILS AS IS, (H.C.) NONE. 1) "HOV NETWORK POMER SPRAY (IHBOhRD) LOSS/OL" LIGHT

2) RHR h/LPCS OUT OF SERVICE ANHUNC.

13-0187 (41)

k<

MHPP-2 COLD SHUTDOWN SYSTEMS - RCIC APPENDIX 'B'ROUP N SHEET 42 OF 66 BUS BUS DEVICE DEVICE PRIMARY PRIMARY NIIHBER DIE NDHBER DEECRIPPICN EFFECT ON DEVICE EPPECT ON SYSTEM ALARM POIHT MC-S2-lh 1 RCIC-V-19 RCIC MINIMUM FLOM MOV VALVE FAILS hS IS, NONE. 1) BISI LIGHT ON P601, VALVE (N.C.) (BhTT B2-1) OUT OF SERVICE).

2) ANNUNC "RCIC DIV 1 OUT OP SERVICE"
3) "MOV NETWORK PMR LOSS/OL'I LIGHT RCIC-V-22 RCIC TEST BYPASS MOV VALVE PAILS AS IS, NONE, 1) BISI LIGHT ON P601 VALVE (N.C.) ~ (BhTT B2-1) OUT OP SERVICE) ~
2) ANHUNC "RCIC DIV 1 OUT OF SERVICE"
3) "MOV NETMORK PMR LOSS/OL" LIGHT RCIC-V-59 RCIC TEST BYPASS MOV VALVE PAILS AS IS ~ NONE. 1) BISI LIGHT ON F601 (n.c.) B2-1) OUT OP 'BhTT SERVICE) ~
2) ANNUNC "RCIC DIV 1 OUT OP SERVICE"
3) "MOV NETWORK PMR LOSS/OL" LIGHT RCIC-P-2 RCIC VACUUM PUMP LOSS OP PUMP LOSS OP VhCUUM 1) BISI LIGHT ON P601, (BhTT B2-1) OUT OP SERVICE).
2) ANHUNC "RCIC DIV 1 OUT OP SERVICE"
3) "MOV NETMORK FMR LOSS/OL'I LIGHT E51-F045 STEAM TO TURBINE MOV VALVE PAILS AS IS, LOSS OP STEAM TD RCIC 1) BISI LIGHT OH P601, (N.C,) TURBINE (BhTT B2-l) OUT OP SERVICE).
2) hNNUNC "RCIC DIV 1

QNPP-2 COLD S11UTDOWN SYS1'EHS - RCIC APPENDIX GROUP N SllEET 43 66 iB'RIHARY BUS BUS DEVICE DEVICE PRIHARY llUMBER DIU NUMBER DESCRIPTION EFFECT ON DEVICE EFFECT ON 'SYSTEH ALARM POINT MC-S2-lh 1 RCIC-V<<l TRIP THROTTLE VALVE VALVE FAILS AS IS, NONE. 1) BISI LIGHT ON P601 ~

STEAH INLET (N.O.) (BATT B2-1) OUT OF SERVICE) ~

2) ANNUNC "RCIC DIV 1 OUT OF SERVICE
3) "MOV NETWORK PWR LOSS/OL" LIGHT E51-F013 PUMP DISCllhRGE MOV VALVE FAILS AS IS ~ RCIC INOPERABLE 1) BISI LIGHT ON P60),

(H.C.) (BATT B2-1) OUT OP SERVICE) ~

2) ANHUHC "RCIC DIV 1 OUT OF SERVICE"
3) "HOV NETWORK PWR LOSS/OL" LIGllT RCIC-V-64 STEAMLIHE ISOLATIOH FAILS AS IS ~ (H.O.)

VALVE RCIC-V-69 VACUlJM PIJMP DISH PAILS AS IS ~ {N.O.)

VALVE RCIC-P-4 RCIC COND. PUMP INOPERATIVE LOSS OP RCIC CONDENSER OPERATION MC-7B 1 RRA-FN-12 DC MCC RM HVAC FAN LOSS OP POWER AND LOSS OF VAC-S2-1A RG 1.47 BISI UHIT CONTROL FOR PANGLOSS {RCIC AHD RHR SllUT- RRA-FH-12 POWER LOSS's OF CONTROL ROOM AND DOWN COOLING) "RCIC DIV 1 OUT-OF-LOCAL INDICATION SERVICE" "HOV NETWORK POWER LOSS/OL" ROA-SPV-12 AC MCC RUN DAHPER LOSS OP POWER TO LOSS OP NORMAL llVAC "DC MCC-RH AOA-AO-12 OPERATOR SOLENOID SOLENOID VALVE WHICH POR MCC ROOH INLET DAMPER CLOSE" VALVE CLOSES AIR DAMPER HC 7B E5'i&00/ lR'im LEG PUMP LOSS OP PUMP 1) <<RCIC-P-y PWR LOSS LZGHT

2) "RCIC DIV SERVICE" l

M4 OVPWP'-

13-01$ 7 (43)

QHPP-2 COLD SHUTDOWN SYSTEHS - RCIC APPENDIX iBi GROUP N SHEET 44 66 BUS BUS DEVICE DEVICE PRIHARY PRIHARY NUMBER DIV NUHMR DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEM ALARM POIHT HC-SB 2 RRA-FH-6 HVAC PAN UNIT POR LOSS OP POWER AND LOSS OP RCIC SYSTEM "RCIC PUHP RM 3 RCIC ROOH CO?lTROL POR PANGLOSS OPERATION RRA-PC-6 TRIP" OP LOCAL IHDICATION RG ti47 BISI "RCIC PUMP RH llVAC OUT-OP-SERVICE" "RCIC DIV 2 OUT-OP-SERVICE" HC-SB-h 2 E51-F076 STEAM SUPPLY LINE MOV VALVE PAILS AS IS i NONEe 1) "MOV NETWORK PWR E51-F063 ISOLATION (H.O.) LOSS/OLN

2) RCIC DIV 2 OUT OP SERVICE" ANHUNC.

DP-S1-1A 1 H13-P601 CONTROL CIRCUIT PEED LOSS OP TURBINE SUPER- LOSS OP RCIC TURBIHE 1) RCIC INVERTER PWR 125 VDC POR TURBI}lE SUPER- VISORY LIGllTS 6 DRAIN STATUS FAILURE LIGHT OH BUS "A" VISORY LIGIITS 6 6 DISCHARGE AOV'S P60)

AOV's 2) RCIC DIV 1 OUT OF SERVICE ANNUNC.

3) LOSS OF POSITION IND. LIGHTS POR E51-P025, E51-F004, E51<<P054, E51-C003 ll13-P621 CONTROL CIRCUIT FEED AUTO FOR VALVES LOSS OP RCIC AUTO )) LOGIC BUS h POWER 125 VDC "h"

POR RELAY LOGIC E51 F008 '010 ~ P013 INITIATION AND MANUAL FAILURE LIGllT ON BUS AND F045. LOSS OP INITIATION PROM CON- F601 REMOTE TURBINE TRIP. TROL ROOM. 2) RCIC DIV 1 OlE OF SERVICE,AHHUNC, l 3-01 al (44)

WHPP-2 COLD SHUTDOWN SYSTEMS << RCIC hPPENDIX sB GROUP H SiiEET 45 OP 66 BUS BUS DEVICE DEVICE PRIMARY PRIMARY llUHBER DIU HUHBER DESCRIPTIOH EFFECT ON DEVICE EPPECT ON SYSTEM ALARM POINT HC<<S1-1D 1 E51-POOS STEAM SUPPLY LINE HOV VALVE PAILS AS IS, NONE. 1) HOV HETWORK POWER ISOLATION (H.O.) LOSS LIGllT ON P601

2) RCIC DIV 1 OUT OF SERVICE ANNUNC.
3) LOSS OP VALVE POSI>>

TIOH IHD. OH P601 E51-P068 TURBINE EXHAUST HOV VALVE PAILS AS IS, NONE. 1) HOV HETWORK POWER TO SUPPRESSION (N.O,) LOSS LIGHT ON P601 CllhMBER 2) RCIC DIV 1 OUT OF SERVICE ANNUNC.

3) LOSS OF VALVE POSI-TION IND. ON P601 MC-Sl-1D I E51-P031 POMP SUCTION PROM HOV VALVE FAILS AS IS ~ ISOLATES SUPPRESSION 1) HOV NETWORK POWER SUPPRESSION POOL (N.C.) POOL SUCTION PATH LOSS LIG11T ON P601
2) RCIC DIV 1 OUT OP SERVICE ANHUHC.
3) LOSS OP VALVE POSI TION IND. ON P601 E51-POlO PUMP SUCTION PROH HOV VALVE FAILS AS IS, HONED 1) MOV NETWORK POWER CONDENSATE STORAGE (N.O.) LOSS LIGHT OH P601 TANK 2) RCIC DIV 1 OUT OP SERVICE ANHUNC.
3) LOSS OF VALVE POSI-TIOH IND OH P601 RCIC-V-46 TURBINE COOLIHG HOV VALVE FAILS AS IS ~ LOSS OF RCIC TURBINE 1) HOV NETWORK POWER WATER SUPPLY VALVE (H.C.) LOSS LIG11T ON P601
2) RCIC DIV 1 OUT OP SERVICE ANNUNC.
3) LOSS OF VALVE POSI-TION IN'N P601 13-01S7 (45)

MNPP-2 COUI SHUTDOMH SYSTEMS - RCIC APPENDIX 'B'ROUP N SHEET 46 OP 66 BUS DEVICE DEVICE PRIMARY PRIMARY D1V HIIHRRR DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEM ALARM POINT RCIC-V-110 TURB. EXH TO SUP- MOV FAILS AS IS N,O. 1) MOV HETuORX POWER PRESSION ISOLATION (N.O.) LOSS LIGHT ON P60)

2) RCIC DIV 1 OUT OP SERVICE ANNUNC.
3) LOSS OP VALVE POSI TION IND. OH P601 DP-S)-2h 2 ll)3-P601 CONTROL CIRCUIT PEED LOSS OP TURBINE SUPV LOSS OP RCIC TURBINE 1) LOSS OP POSITION 125 VDC . FOR TURBINE SUPV LIGHTS AND DRAIH AHD STATUS IHD. FOR E41-F026 BUS "B" LIGllT AHD AOV'S DISCHARGE AOV'S '5)-F005 ll)3-P61B 'ory CONTROL CIRCUIT PEED AUTO ISOLATION FOR NONE. 1) LOGIC BUS B POMER 125 VDC FOR RELAY LOGIC VALVE E51-F063 FAILURE LIGHT ON BUS "B" P601
2) RCIC DIV 2 OUT OP SERVICE ANNUNC.

DP-Sl>>)D 1 MC-S2-lh CONTROL POWER FOR MOV'S PAIL AS IS. RCIC DIV 1 OUT OP 1) MOV NETMORK POMER BREAKERS RCIC-V-19'2)

(SEE MC-S2-lh ON SERVICE LOSS LIGHT ON P601

59) 45) )1 2) SHEET 2S) AND MC-S)-)D 2) RCIC DIV 1 OUT OP 13 64 69; Si 68) PUMPS ARE LOST SERVICE ANNUHC.

31 46) 3) LOSS OP VALVE POSI-RCIC-P-2; 4 TION INDICATING LIGHTS AND PUMP STATUS LIGHTS OH P601 MC-Sl-ZD 2 RCIC-V-86 VACUUM BREAKER ISO- MOV)S PAIL AS IS 1) MOV NETWORK POllER LATION VALVE (H.O.) LOSS LIGHT ON P601

2) RCIC DIV 2 OUT OP SERVICE ANNUNC.

2 SM-P-1B STANDBY SERVICE LOSS OP PUMP POWER LOSS OP RHR "B" llEAT BKR TRIP AHD UNMR-MATER PUMP EXCHANGER AHD CRI- VOLTACE ANNUNC, TICAL DIV 2 HVAC

'~~ini

WHPP-2 COLD SllUTDOWH SYSTEMS - RCIC APPENDIX 'B'ROU1 N SllEET 47 0 6 BllS BUS DEVICE DEVICE PRIHARY PRIMARY NIIHBER DIV NBHBER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEH ALARH POINT DP-S1-2D 125 VDC CONTROL SW-P-1B BREAKER CONTROL VOLTAGE PUHP HOTOR MILL NOT llAVE TRIPPERS, OR NO BREAKER CLOSURE.

LOSS OF RllR "B" RG 1 '7 BISI "BKR CB-SW1B OUT-OF<<

POWER CLOSIHG CONTROL IlEAT EXCHANGER AND SERVICE" TO SM-7 VOl.TAGE, LOSS OF DIV 2 llVAC (RCIC) "SSW "JV'UT-OF-SERVICE" IND. LIGllTS. CAN BE NOTE 2 CONTROLLED AT REHOTE SllUTDOWH PAHEI.

PP<<2A-G TS2-21 TRANSMITTER FOR LOSS OF LOW WATER RG 1 ~ 47 BISI SM-LS-1B3 TRIP OF SW-P-1B "SUPV. SYSTEH TROUBLEu "SSM B OUT-OF-SERVICE" PP-8A-G TS2-003 TRANSHITTER FOR RECEIVERS IN CONTROL LOSS OF INTERLOCK TO "STANDBY SM "B" SUPV TS2-004 SM-V-2B POS. .ROOM WILL NOT CHANGE SM-PCV-38B, KEEPING SYSTEM TROUBLE" TS2-001 SWITCHES STATE. POS. INDI- THIS VALVE SSW B OUT-OF-SERVICEw TS2-002 CATOR AHD INTERLOCKS OF SSM CLOSED'OSS "B" LOOP TS2-031 TO SM-P-1B hHD TS2-022 SW-PCV-38B PP-8A-G SM-SPV-38B SOLENOID-VALVE FOR SOLENOID VALVE MILL NONE NOHE SW-PCV-38B BACK DEEHERGIZE AHD PRESSURE CONTROL SM-PCV-38B MILL VALVE TllROTTLB OPEH TS2-037 TRAHSNITTERS FOR SUPV. RELAYS DEEHER- NONE "SSM B SUPV. SYSTEM TS2-038 S'W-PCV-38B POS. GIZE, TllEREFORE M- TROUBLE" RS2-013 IND. RECEIVERS AND EHERGIZIHG SM-SPV-38B "SSW B OUT-OF-SERVICE" RS2-014 SUPV. RELAYS FOR TO THROTTLE OPEN.

SS2-013 CONTROL OF POS. IHD WILL NOT SS2-014 SW-SPV-38B CllhHGE PP-8A-G TS2-026 TRANSMITTERS FOR RECEIVERS IN COHTROL NONE "SSM B SUPV. SYSTEN TS2-061 CONTROL OF PRA-FN-1B ROOM MILL HOT CHANGE TROUBLE" TS2-062 SUPV, RELAYS AHD STATE (FAN WOULD AUTO "SSW B OUT-OF-SERVICE" SS2-004 RECEIVERS FOR LOCAL OPERATE) SUPV. RELAYS SS2-005 OPEN INDICATION MOULD DEEHERGIZE, RS2-004 THUS LOSS OF LOCAL M2~5 OPER. INDICATION 13-0187 (47)

MHPP-2 COLD S)IUTDOMN SYSTEMS - RCIC APPENDIX iB'ROUP N SIIEET 48 66 BlJS ~ BUS DEVICE DEVICE PRIHARY PRIMARY

~ )

UUHRRR DIV UUUURR DESCRIPTION EFFECT ON DEVICE EPFECT ON SYSTEM ALARH POINT ~

PP-BA-P SCS2-021 RECEIVER AND RELAY LOSS OP LOM MATER NONE RG 1.47 BISI RCS2-021 FROM SM-LS-183 TRIP OF SM-P-18 "SUPV SYSTEM TROUBLE" "SSM 8 OUT-OF-SERVICE" PP-BA-P RCS2-003 SUPV. RELAYS hND SUPV RELAYS DEEHER- LOSS OP SSM LOOP "8's 'STANDBY SM "8" SUPV, RCS2-004 RECEIVER FOR GIZEULOSS OF POS, SYSTEH TROUBLE RCS2-001 SM-V-28 POS ItiDICATION AND VALVE "SSM 8 OUT-OF-SERVICE" RCS2-002 SMITCHES Mrr.r. PAIL-AS-IS <N.C.) NOTE 2 RCS2-022 RCS2-031 SCS2-003 SCS2-004 SCS2-001 SCS2-002 SCS2-022 SCS2-031 PP-BA-P TCS2-013 TRANSHITTERS POR RECEIVER IN PUMP LOSS OP RHR "8" AND "SSM 8 SUPV. SYSTEM TCS2-014 SW-SPV-388 CONTROL BOUSE MILL NOT CHANGE DIV 2 HVAC PROM LOSS TROUBLE" RCS2-037 RECEIVERS AND SUPV. STATE AND KEEPIHG OP SSM LOOP 8 SSM 8 OUT OP SERVICE RCS2-038 RELAYS POR SOLENOID VALVE NOR- NOTE 2 SCS2-037 SM-PCV-388 POS. IHD. MALLY ENERGIZED SCS2-038 KEEPIHG SM-PCV-388 CLOSED, LOSS OP POS ~

IHD.

PP-Bh-F TCS2-004 TRANSMITTERS POR RECEIVER AT PUMP LOSS OF SSM LOOP "8" "SSM 8 SUPV. SYSTEM TCS2-005 LOCAL OPERATING BOUSE MILL HOT CllhNGE PUMP. TROUBLE" RCS2-026 IHDICATIOH. SUPV. STATE, THUS LOCAL LOSS OP RllR "8" AND "SSM 8 OUT-OP-SERVICE" RCS2-061 RELAYS AND RECEIVERS OPER. IND. MOULD NOT RCIC HVAC "SSW PP HOUSE 8 RCS2-062 FOR CONTROL OP CllhNGE. SUPV. RELAYS PRA-PH-18 LOM FI.OM" SCS2-026 PRA-Fit-18 MOULD DEENERGIZE SCS2-06] ChlJSIHG TBE PAN TO SCS2-062 FAIL TO OPERATE 13-0)87 (48)

MNPP-2 COLD SHUTDDMN SYSTEMS RCIC hPPENDIX ~B'ROUP N SHEET 49 0 6 BUS BUS DEVICE DEVICE PRIMARY PRIHARY IIUHBER BIU RUBBER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEH ALARH POINT HC-BA 2 SM-V-2B SM-P-lB DISCHARGE HOV FAILS-AS-IS LOSS OP SSM B THUS LOSS OP RllR "B" AND RG I'7 BISI VALVE (N.C.) "MOV NETMORK POMER DIV 2 NVAC (RCIC) LOSSIOLI'SSM B OUT-OP-SERVICE" NOTE 2 HC-BA-A 2 PRA-FN-lB SSM PUMP lfOUSE "B" FAN PAILS TO OPERATE LOSS OP SSM LOOP "B" uPRA-FN-1B POMER LOSS'SSM PAN COlL UNIT MOTOR AND LOSS OF POS. PUMP B OUT-OF-SERVICE" INDICATION AT MCC LOSS OF RllR "B" AND RCIC llVAC PP-7CA-A h SM-SV-34 SSM SllUTOFF VALVE SOLENOID VALVE PAILS NONE - OPERATION IS NOTE 2 PROM RRA-PC-6 OPEN. AVAILABLE FROH THE FOR RCIC ROOM LOSS OP POS. IND, REMOTE SllUTDOMN PANEL, IP REQUIRED 13-D 1 B7 (49)

QNPP-2 COLD SHUTDOWN SYSTEMS - SAFETY RELIEF VALVES "h" hE'PENDIX 'B'ROUP 0 SHEET 50 OF 66

~ ~

BUS BUS DEVICE DEVICE PRXMhRY PRXMhRY NtlHBER DIV NUBBER DESCRXPTXOH EFFECT OH DEVICE EFFECT ON SYSTEM hLhRH POINT DP-Sl-lh D l B22-F013 ShFETY RELIEF VhLVES HORMhLLY CLOSEDE NONE VhLVES MILL 1) "hDS h/C LOGIC POMER BKR NO hBB,CBDBE (H.C.) ChNNOT BE STILL OPEN MECllAN- FhIL" LIGHT OPEHED EI.ECTRIChLLY ICALLY 2) "hDS h/C OUT OF TO PERFORM hDS SERVICE" hNNUNC

3) LOSS OF POS ~ IHD.

OH P601 B22-F013 hDS VhLVES HORMhLLY CLOS ED B NONE "B" POMER IS 1) "hDS h/C LOGIC POQER h,B,C,D,E (H.C.) ChHHOT BE USED PhIL" LIGllT FBGBHBJBKBL . OPENED QITll BBBEB 2) "hDS h/C OUT OF POMER TO PERFORM hDS SERVICE" hHHUNC

3) LOSS OF POS. IND.

ON F601 5 5, 5

t 13-0187 (50)

~~

llHPP-2 COLD SUUTDOW SYSTEMS - RllR SUPPRESSION POOL ih~ hPPEHDIX GROUP P SHEET 51 0 B'RIHARY

~ ~

BUS BUS DEVICE DEVICE PRIMARY H UHRRR DIU IIUHRRR DESCRIPTIOH EFFECT ON DEVICE EFFECT OH SYSTEM hLARH POIHT REFER TO GROUP 'O'OR PUMPS, VALVES hND CONTROLS TllhT ARE hLSO HEEDED FOR SUPPRESSION POOL COOLLNG h' HC-7B-h Dl E12-F027h RllR LOOP "h" DIS>> HOV FhILS hS IS ~ VhLVE USED FOR RETURN 1) NOTE 3o GROUP L CllARGE TO SUPPRES- (N.C.) LOSS OF INDI- TO SUPPRESSION POOL LOSS 01t POSITION SIOH POOL SPRAY CATION IHD. ON P601

2) "HOV HETMORK PWR LOSS/OLI'IGllT
3) "LPCS/RHR h OUT OF SERVICERU hHHUHC l3-0187 (51)

MHPP-2 COLD SHUTDORl SYSTEMS - RHR LOOP B 4 C APPENDIX EB CROUP Q SHEET 52 OF 66 BUS BUS DEVICE DEVICE PRIMARY PRIMARY NUHBER DIV NUHBER DESCRIPTXON EFFECT ON DEVICE EFFECT ON SYSTEM hLARM POINT SM-8 D2 E12<<C002B RHR PlJMP "B" PUMP INOPERABLE LOOP "B" OF RHR TMO BREAKER TRIP AND INOPERABLE BUS UHDERVOLTAGE ANNUNCIATION E12-C002C RHR PUMP "C" PUMP INOPERABLE LOOP "C" OF RHR TMO BREAKER TRIP hND INOPERABLE BUS UNDERVOLTAGE hHHUHCXATIOH SM-8 2 SM-P-1B STANDBY SERVICE LOSS OF PUMP POMER LOSS OF RHR "B" HEAT BKR TRIP AND UNDER MATER PUMP EXCHANGER hND CRI- VOLTAGE AHHUHC.

TICAL DIV 2 HVAC (RCIC)

MC-SB 2 RRA-FH-1 HVhC FAN UNIT FOR LOSS OF POMER AND LOSS OF RHR-P-2C "RHR PUMP RM-4 RRA-FC-1 RllR-P-2C ROOM CONTROL TO FAN. LOSS TRIP" OF LOCAL INDICATION RG 1.47 BISI "RHR C PlJMP RM HVAC OUT-OF-SERVICE "RHR C OUT-OF-SERVICE" HVAC PAN tulR-P-2B UNIT FOR ROOM MSS OP POWER 4 COM!o TO PANo ~

"HHR POUP IM-0 FC-3 86 So l7 BISE

~"

LOSS OP ZOCAI EHDD +BUR B PUMP RM HVAC OOS" "RHR B OUTWFMMlVECE MC-SB-A E12-F004 B MOV PUMP SUCTION MOV FAILS AS IS ~ NONE - REqUIRED TO BE LOSS OF VALVE POSITION FROM SUPPRESSION (H.O.) CLOSED DURING SHUT- INDICATIOH ON P601 POOL DOMN COOLING E12-F016B HOV COHTAINMEHT SPRAY MOV FAILS AS ISB NONE. 1) "MOV NETMORK PONER (OUTBOARD) (H.C.) LOSS/OL'I LIGHT

2) ".RHR B/C OUT OF SERVICE" hNNUNC ~

E12-F017B . MOV COHTAIHMEHT SPRAY MOV FAILS AS IS, NONE. 1) "MOV NEflfORK POllER (INBOARD) (H.C.) LOSS/OI." LIGHT

2) "RHR B/C OlJT OF

llNPP- COLD SHUTDOMN SYSTEMS - RHR LOOP B 6 C APPENDIX 'B~ GROUP Q SHEET 53 6 r

BUS DEVICE DEVICE PRIMARY PRIMARY I

D V NJ!JJB ER DESCRIPTION EFPECT ON DEVICE EFFECT ON SYSTEM ALARM POINT E12-P024B PUMP "B" TEST VALVE MOV FAILS AS IS ~ USED POR SUPPRESSION 1) "HOV NETMORK POMER (H.C.) POOL COOLING LOSS/OL" LIGHT

2) "RHR B/C OUT OP SERVICE" ANNUNC, HC-SB-A 2 SM-V-24B SSM SHUTOFP VALVE HOV FAILS-AS-IS LOSS OP BBR-P-2B RG 1 '7 BISI PROM RHR-P-2B AND (N.C.) LOSS OP POS. AND RRA-FC>>3 "RHR PUHP 2B ROOM HVAC RRA-FC-3 IND. OUT-OF-SERVICE" nRHR B OUT OP SERVICF NOTE 2 SM-V 211C SSM SHUTOFF VALVE NV PAILS-AS IS LOSS OP BURY~ "HBR C PMP BH HVAC OOSN FRe Blm-X-2C AND (H.C.) TOSS OP AND BRA FC-1 BQ 1oll7 BISI RRA-FG>>1 POSo IMD, "RHR C QF&4PJ-SERVICE" NOTE 2 MC-BB-B D2 E12-P073B RHR HX "B" OUTBOARD MOV PAILS AS ISi HEAT X VENT CAPABILITY LOSS OP VALVE POSITION VENT (N.C.) LOST, NO EPFECT. INDICATION ON P601.

E12-F074B RHR HX "B" IHBOARD HOV PAILS AS ISI BEAT X VENT CAPABILITY LOSS OP VALVE POSITIOH VENT (N.C.) LOST. NO EPFECT. INDICATION ON P601 ~

MC-BB-B D2 E12-P048B RHR HX "B" BYPASS MOV FAILS AS IS, LOSS OP COOLDOWN LOSS OP VALVE POSITION (N.o.) RATE CONTROL AND INDICATION ON P601 ~

EFPICIENCY E12-P068B RHR BX "B" SM OUTLET MOV PAILS AS IS ~ BEAT EXCllhNGER "B" LOSS OF VALVE POSITION (H.C.) COOLING LOST INDICATION ON P601 E12>>P047B MOV HEAT EXC11 INLET HOV PAILS AS IS ~ NONE. LOSS OF VALVE POSITION (N.o.) INDICATION ON P601.

E12-FOG~ MOV HEAT EXCH OUTLET NGV PAILS-AS-IS NONE

{N.O.)

DP&1~ 2 125 VDC CNIL FEED C002MC SMITCHGEAR BHEhlm GNARL PUMP MOTOR BKR MIIL NOT CLOSE NO PUMP aiba CraSURE TllEHEFOllE UOP "B"

1) <CImmR 28 ~W SENUCE" LIGHT To SMGR VPDPAOE AND TRIPPING ComHL AND "C" OP BllR IS 2) "C~lR 2C QF&4P VOLTAGE LOST INOPK BABE SERVICE" LIGllT

>) "aun ay'C OUTWP-SERVICE" ANN~

WHPP-2 COI.D SHUTDOWN SYSTEHS - RHR LOOP B & C APPENDIX ~B'ROUP Q SHEET 54 0 o6 BUS BUS DEVICE DEVICE PRIMARY PRIMARY IIUHBRR DIV NIJHSER DESCRIPTION EFFECT ON DEVICE EPFECT ON SYSTEM ALARH POINT DP>>S1-2D 2 125 VDC SM-P-1B BREAKER CON- PUMP HOTOR MILL HOT NO BREAKER CLOSURE RG 1+47 BISI COHTROL TROL VOLTAGE HAVE TRIPPING OR LOSS OP RIIR "B" HEAT "BKR CB-SMIB OUT-OP-POWER CLOSING CONTROL VOL- EXCHANCER AHD DIV 2 SERVICE" TO SM-7 TAGE. LOSS OP IHD. HVAC (RCIC) "SSM B OUT-OF-SERVICE" LIGHTS. CAN BE CON- NOTE 2 TROI.LED AT REMOTE SHUTDOWN PANEL RPS HB-P622 RHR SYSTEH INBOARD LOSS OP F009 OPEHlNG S/D COOLINC SUCTXOH 1) LOSS OP VALVE POSIT.

BUS "B" 120V REACTOR CONTROL RELAY FEED NODE. MILL FAIL THE FROM RECIRC LIHE FOR IND. POR E12-P060h C72-F001 PROTECTION VALVE CONTROL CIR- RHR LOOP h & B LOST. AND B ON P601 IIBll CUITRY AND CLOSE THE BUS 2) REACTOR. SCRAM WITH VALVES ASSOC ALARHS MC-BB-A D2 E12-P042B RHR INJECTION VALVE HOV FAILS IN POSX- LOSS OP "BII LPCI NOTE 2.

TION, (N.C.) INJECTION VALVE 1) "HOV NETWORK POMER LOSS/OL" LIGHT

2) "RHR B/C OUT OP SERVICE" ANNUNC, 812-F042C RHR INJECTIOH VALVE HOV FAILS IN POSX- LOSS OP "C" LPCI HOTE 2, TION, (H.C.) INJECTION VALVE )) "HOV NETMORK POWER LOSS/OL" LICHT
2) "RHR B/C OUT OP SERVICE" ANNUNC.

DP-Sl-2A 2 H13-F601 RHR ANALOG POSITION LOSS OP VALVE POSIT HONE. HONE, 125 VDC IND. FOR RHR-V-73B INDICATION OH P601-AND 74B FAIL DOMH SCALE DP-Sl-2A 2 H13-P61B CONTROL CKT FEED VALVE AUTO CKTS MILL LOOP "B" BLOCKED LOSS 1) "RHR B/C LOCIC PMR 125 VDC FOR RELAY LOGIC RHR PhIL. VALVES MILL OF RIIR LOOPS B&C PhIL" LIGHT BUS B I.OOPS B&C VALVE AND NOT OPEN IN AUTO (SEE 2) "RHR B/C OUT OF PUHP CONTROL ANALYSIS POR VALVES) SERVICE" AHHUNC.

PUMP MILL NOT AUTO START 13-0187 (54)

QNPP-2 COLD SHUTDOWN SYSTEMS - RIIR LOOP B 6 C hPPENDIX 'Br GROUP Q SHEET 55 6 BIJS BUS DEVICE DEVICE PRIMARY PRIMARY

~

NNHBRR DIV NBHBRR DESCRIPTIOH EFFECT OH DEVICE EFFECT ON SYSTEM ALARM POINT ~

'PP-8A-P SCS2-021 RECEIVER AND RELAY LOSS OP LOM MATER RG 1.47 BISI RCS2-021 FROM SW-LS-1B3 TRIP OP SM-P-1B "SUPV. SYS TROUBLE" "SSM B OUT-OP-SERVICE" PP-8A-P RCS2-013 SUPV. RELAYS AND SUPV. RELAYS DEENER>> LOSS OP SSM "B" RE- "STANDBY SM "B" SUPV.

RCS2-014 RECEIVERS POR GIZE. LOSS OF POS. TURH TO SPRAY POND SYSTEM TROUBLErr RCS2-015 SW-V-12B POS. IHDICATIOH AND VALVE "h" BUT RETURN TO "SSM B OUT-OF-SERVICE" RCS2-016 SMITCllES MILL FAILS-AS-IS COOLING TOWER NOTE 2 RCS2-017 (N.C.) REMAINS OPERABLE RCS2-024 SCS2-013 SCS2-014 SCS2-015 SCS2-016 SCS2"017 SCS2-024 PP-8A-P TCS2-013 TRANSMITTERS POR RECEIVERS IH PUMP LOSS OP RHR "B" AND "SSM B SUPV. SYSTEM TCS2-014 SM-SPV-38B CONTROL HOUSE MILL HOT CIIANCE DIV 2 NVAC FROM LOSS TROUBLE" RCS2-037 RECEIVERS AND SUPV. STATE AHD KEEPIHG OP SSQ LOOP B r'SSM B OIJT-OP-SERVICE RCS2-038 RELAYS FOR SM-PCV-38B CLOSED NOTE 2 SCS2-037 SM-PCV-38B POS. IHD. LOSS OP POS. IND, 8C 82&+

PP-8A-F RCS2-005 SUPV. RELAYS AND SUPV. RELAYS DEENER- NONE "SSM B SUPV. SYSTEM RCS2-006 RECEIVERS FOR GIZE. LOSS OP POS ~ TROUBLErr RCS2-007 SW-V-698 POS. IHDICATIOH AHD VALVE r'SSM B OUT-OP-SERVICErr RCS2-008 SMITCIIES MILL FAIL-AS-IS (N.O.) NOTE 2 RCS2-020 RCS2-032 SCS2-005 SCS2-006 SCS2-007 SCS2-008 SCS2-020 SCS2-032 13-0187 (55)

QHPP-2 COLD SllUTDOWH SYSTEMS - RllR LOOP B 6 C hPPENDIX GROUP Q SllEET 56 OP 66

'B'RIMARY BUS BUS DEVICE DEVICE PRIMARY NNNBRR DIV NBNBRR DESCRIPTION EPPECT ON DEVICE EFFECT ON SYSTEM hLARM POINT PP-Bh-P RCS2-009 SUPV. RELhYS hllD SUPV. RELAYS DEENER- NONE "SSM B SUPV. SYSTEM RCS2-010 RECEIVERS FOR CIZE LOSS OP POS. TROUBLE" RCS2-011 SW-V-70h POS. INDICATIOH hND VhLVE "SSW B OUT-OF-SERVICE" RCS2-012 SWITCHES MILL FhIL-hS-IS (N.O.) NOTE 2 RCS2-023 RCS2-033 SCS2-009 SCS2<<010 SCS2-011 SCS2-012 SCS2-023 SCS2-033 PP-8h-F TCS2-004 TRANSMITTERS POR RRCIEVER OP PUMP LOSS OP SSM "SSM B SUPV, SYSTEM TCS2-005 LOChL OPERATING llOUSE MILL NOT CllhNCE LOOP B PUMP TROUBLE" RCS2-026 IHDIChTION SUPV, STATE, THUS LOChL LOSS OP RllR "B" AND "SSM B OUT-OF-SERVICE" RCS2-061 RRLhYS AND RECEIVERS OPER. IHD. MOULD NOT RCIC )lVAC "SSM PP llOUSE B RCS2-062 FOR CONTROL OP CllhNGE, SUPV. RRLhYS PRA-PN>>)B LOM FLOW" SCS2-026 PRA-FN-)B WOULD DEENERCIZE SCS2<<06) CAUSIHC TllE PJN TO SCS2-062 PhIL TO OPERATE PP-Sh-G TS2-21 TRANSMITTER POR SM-I.S-)B3 LOSS OP LOM MATER SM-P-)B NONE+ RG 1 '7 BISI "SUPV. SYSTEM TROUBLE" TRIP OP "SSM B OUT-OP-SERVICE" PP-Sh-C TS2-013 TRANSMITTER POR RRCIEVERS IH CONTROL HONE "SSM B SUPV. SYSTEM TS2-014 SQ-V-12B POS ~ ROOM WILL NOT C))ANGE TROUBLE" TS2-015 SMITCllRS SThTE. POS. INDICh- "SSM B OUT-OP-SERVICE" TS2-016 TION MILL NOT CHANGE TS2-017 TS2-024

) 3-0) 87 (56)

MHPP-2 COLD SffUTDOWH SYSTEMS - RllR LOOP B & C APPENDIX sB GROUP g SlfEET 57 OP 6 BUS BUS DEVICE DEVICE PRIHARY PRIMARY HUHBER DZV HUHBER DESCRIPTION EFFFCT OH DEVICE EFPECT OH SYSTEM ALARH POINT PP-Sh-0 SM-SPV-3SB SOLENOID VALVE POR SOLENOID VALVE MILL NOHE HONE SM-PCV-38B BACK DEENERGIZE AHD PRESSURE CONTROL SM-PCV-38B MILL VALVE TllROTTLE OPEN TS2-037 TRAHSHITTERS FOR SUPV. RELAYS DEENER- HONE "SUE B SUPV. SYSTEM TS2-038 SM-PCV-38B POS. IHD. GIZE, TllEREFORE DE- TROUBLE" RS2-013 RECEIVERS AHD SUPV. EHERGIZING SM-SPV-38B "SSM B OUT-OP-SERVICE" RS2-014 RELhYS FOR CONTROL TO TllROTTLE OPEN.

SS2-013 OP SM-SPV-38B POS. IND. MILL NOT SS2Wf ff CllhNGE.

PP-8h-0 TS2-005 TRANSHITTERS POR RECEIVERS IN CONTROL NONE "SSM B SUPV. SYSTEH TS2-006 SM-V-69B POS, ROOM MILL NOT CHANGE TROUBLE" TS2-007 SMZTCllES STATE. POS. IHDICA>> "SSM B OUT-OP-SERVICE" TS2-008 TION MILL NOT CllhNGE TS2-020 TS2-030 PP-Sh-G TS2-009 TRANSHZTTERS FOR RECEIVERS IH CONTROL NONE "SSM B SUPV. SYSTEM TS2>>010 SM-V-70h POS. ROOH MILL NOT ClfhNGE TROUBLE" TS2-011 SMITCllES STATE. POS. INDICA- "SSW B OUT-OP-SERVICE" TS2-012 TION Mif.i. NOT CffhNGE TS2-023 TS2-033 PP-Sh-G TS2-026 TRANSMITTERS POR RECEIVERS FOR CONTROL "SSW B SUPV. SYSTEM TS2-061 CONTROL OF ROOH MILL NOT CHANGE TROUBLE" TS2-062 PRA>>FH-1B SUPV. STATE (FAN MOULD AUTO SSM B OUT>>OP-SERVICE SS2-004 RELAYS AND RECEIVERS OPERATE) SUPV. RELAYS SS2-005 POR LOCAL OPER. MOULD DEENERGIZE, RS2-004 IHDICATIOH TllUS LOSS OP LOCAL RS2-005 OPER. INDICATION HC-SA SM-V-12B -LOOP B MATER RETURH HOV PhiLS-AS-IS, LOSS OF SSM "B" "HOV NETMORK POWER TO SPRAY POND "B" (H.C.) LOSS OF POS. RETURN TO SPRAY POHD LOSS/OL" ISOL. VALVE IND. hi BUT RETURN TO SSM B OUT OF SERVICE COOLING TOWER REHAIHS OPERABLE IQ-Of87 (57)

~

~

QNPP-2 COLD SllUTDOWN SYSTRHS - RllR LOOP B 6 C hPPENDIX 'B'ROUP Q SllEET 58 6 BUS BUS DEVICE DEVICE PRIMARY PRIHARY

~

NUHBER DIV NUHMR DESCRIPTION EPFECT ON DEVICE EFFECT ON SYSTEM ALARH POINT ~

MC-Sh 2 SW-V-69B SSM LOOP B RETURN TO MOV PAILS-AS-IS NONE, "HOV NETMORK POWER COOLING TOWER ISOL, {N.O.) LOSS OP POS ~ LOSS/OL'I VALVE IND. "SSM B OUT-OP-SERVICE" NOTE 2 HC-SA 2 SM-V-7OA SSW LOOP h RETURN MOV FAILS-AS-IS NONE "MOV NETWORK POMER TO COOLING TOMERS (N,O.) LOSS/OLn ISOLATION VALVE "SSM B OUT-OP-SERVICE" HC-SA-A 2 PRA PN 1B SSW PUHP IlOUSE wB PAN PAILS TO OPERATE LOSS OP SSW LOOP "B" "PRA-PN-1B POWER LOSS" FAN COIL UNIT HOTOR AND LOSS OF POS ~ IND. PUHP LOSS OP RllR "B" "SSW B OUT-OP-SERVICE" AT MCC ANP RCIC llVAC l3-0187 (58)

WNPP-2 COLD SHUTDOWN SYSTEMS - HPCS .APPENDIX ~B CROUP R SHEET 59 6 BUS BUS DEVICE DEVICE PRIMARY PRIMARY NUHBER DIV HUHBER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEM ALARM POINT SM-4 2 E22-C001 - HPCS PUMP LOSS OF HPCS PUMP HPCS INOPERATIVE 'WO BREAKER TRIP ANNUNCIATION HC-4A 3 E22-C003 STANDBY WATER LEG LOSS OF PUMP NONE, 1) HPCS-P-3 POWER LOSS PUMP LIGHT ON P601

2) HOV NETWORK POWER LOSS LIGHT ON P601
3) HPCS OUT OF SERVICE ANNUNCIATOR
4) LOSS OF VhLVE POSIT.

IND, ON P601 FOR 822-F001; F004; F015; F012; F023B MC-4A 3 SW-V-29 HPCS-P-2 DISCHARGE MOV FAILS-AS-IS LOSS OF HPCS "HPCS SW OUT-OF-SERVICE" VALVE (N.C.) "HPCS OUT-OF-SERVICE" MC-4h 3 SW-V-54 SSW SllUTOFF VALVE MOV PAILS-AS-IS LOSS OF HPCS PUMP RG 1.47 BISI FOR HPCS ROOM (N.C.) LOSS OF POS. ROOM HVAC, THEREBY "HPCS PUMP RM HVhC OUT<<

RRA-FC-4 IND. DEFEATING HPCS OF>>SERVICE "HPCS OUT-OF-SERVICE" NOTE 2 HPCS-P-2 HPCS SERVICE WATER PUMP INOPERATIVE LOSS LOSS OF HPCS SSWD RG 1 ~ 42 BISZ PUMP OF LOCAL PLlJS CONTROL THEREBY DEFEATING "HPCS SW OUT-OF-SERVICE" ROOM POS. IND. HPCS "HPCS OUT-OF-SERVICE" MC-4A 3 RRA-FN-4 HVAC FAN UNIT FOR LOSS OF POWER AND LOSS OF HPCS PUMP "HPCS PUMP RM 6 HPCS PUMP ROOM CONTROL TO FAN, RRA<<FC-4 TRIP" LOSS OF LOCAL INDI-CATION RG 1 '7 BISI "HPCS PIJMP RM HVAC OUT-OF-SERVICEEB HPCS OUT-OF-SERVICE 13-0187 (59)

t MNPP-2 COLD SHUTDOWN SYSTEMS - HPCS hPPEHDIX 'B'ROUP R Sl/E'ET 60 6 BUS BUS DEVICE DEVICE PRIMARY PRIMARY N IINE ER DIV NENRER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEM ALARM POIHT (hc) E22-F001 PUMP SUCTIOH PROM VALVE PhILS AS IS, NONE, 1) HPCS-P-3 POWER LOSS CONDENSATE STORAGE (N.O,) LIGHT ON P601 TANK 2) MOV NETMORK POMER LOSS LICHT OH P601

3) HPCS OUT OP SERVICE ANHUNCIATOR
4) LOSS OF VALVE POSIT.

IND, OH P601 POR E22-F0011 F012; P023.

F004'015; E22-F004 HPCS PUMP DISCllhRGE VALVE FAILS AS IS, HPCS INOPERATIVE 1) HPCS-P-3 POMER LOSS (N.C.) LIGHT ON P601

2) HOV NETWORK POWER LOSS LIGHT ON P601
3) HPCS OUT OP SERVICE ANNUNCIATOR
4) LOSS OP VhLVE POSIT, IND, OH P60) POR E22 F001 1 F004 $

P015; F0121 F023.

MC-4A 3 E22-P015 PUMP SUCTION FROM . VALVE PAILS AS IS ~ USE SUCTIOH PROM 1) HPCS-P-3 POWER LOSS SUPPRESSION POOL (N.CN) CONDENSATE TANK LIG11T OH P601

2) MOV NETMORK POWER LOSS LIGHT ON P601
3) HPCS OUT OP SERVICE ANNUNCIATOR
4) LOSS OP VALVE POSIT.

IND. OH P601 FOR 822-POOl ~ F004 P012; P023 ~ '0151 13-0187 (60)

NHPP-2 COLD SHUTDOMH SYSTEMS - IIPCS APPENDIX 'B GROUP R SHEET 61 0 66 BUS BUS DEVICE DEVICE PRIMARY PRIMARY HHHBER DIV HllHBER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEM hLARM POINT I

E22-FOll MOV FhILS AS IS, NONE. 1) HPCS-P-3 POQER LOSS C

822-FOI2 (N.C) LIGHT ON P601 E22-FOIO 2) MOV NETMORK POMER E22-F023 LOSS LIGHT ON P601

3) HPCS OUT OF SERVICE I I

ANNUNCIATOR I

4) LOSS OR VALVE POSIT.

IND. ON P601 POR B EZZ-FOOI$ F004' t FOI5>> F012>> F023

')

ENGINE & Sl-HPCS BATTERY LOSS OR BATTERY NONE. HPCS-P-3 POQER LOSS GENERATOR CIIARCER LIGHT OH P601 LOAD PANEf 2) MOV HETuORX POWER.

BhTT CIICR LOSS LIGHT OH P601 CIRCUIT 3) HPCS OUT OF SERVICE ANNIJNCIATOR

4) LOSS OP VALVE POSIT, IND. ON P601 FOR E22-F001 '004; F015>> F012 ~ F023 Sl-HPCS 3 HI3-P625 RELAY LOGIC POR LOSS OF VALVE AND HPCS IHOPERATIVE 1) HPCS LOCIC PO1IER MANUAL AHD AUTO PUMP CONTROL PAILURE LICHT ON P601 INITIATION 2) HFCS OUT OF SERVICE ANNUNCIATOR SI-IIPCS HI3-F601 822-FOIO, E22-FOII VALVE POSITION IND. HONE - DOES HOT APPECT VALVE POSIT. INDI- INDICATE DOMNSCALE VALVE POSITION CATORS 13-0)87 (6))

'WPP-2 COLD SllUTDOMH SYSTEMS - llPCS hPPENDIX "GROUP R SHEET 62 0 6

'a'RIMARY BUS BUS DEVICE DEVICE PRIHARY NIINBBR I D V NDNB BR DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEH ALARM POINT PP-4A 3 ll13-P625 NPCS ANALOG LOOP LOSS OF HPCS FLOM hND CANNOT VERIFY PROPER POMER SUPPLY PRESSURE INDICATIOH SYSTEM OPERATION H13-P601 E27-F005 TESTABLE CllECK VALVE NOHE. LOSS OF VALVE POSITION CANNOT BE TESTED LIGllTS ON F601 E22-F009h HANUAL VALVE POSIT. NONE. LOSS OF VALVE POSITION E22-F009B INDICATION LIGllTS ON P601 E22-F003S PP-4A 3 TS3-001 TRANSMITTERS'UPV SUPV. RELAYS DEEHER- LOSS OF HPCS TS3-002 RELAYS AHD RECEIVERS GIZE LOSS OF POS.

TS3-003 FOR SM-V-29 POS, INDICATION AND VALVE TS3-004 SMITCHES hND MILL FAIL-AS-IS (N.C.)

TS3-005 SM-PROD TS3-006 RCS3-001 RCS3-002 RCS3<<003 RCS3-004 RCS3-005 RCS3-006 SCS3-001 SCS3-002 SCS3-003 SCS3-004 SCS3-005 SCS3-006 13-0187 (62)

~ g

~ ~

dh WNPP-2 COLD SHuTDOWN SYSTEHS - SAFETY RELIEF VALVE 'B' APPENDIX iB~ GROUP S SHEET 63 OF 66 BUS BUS DEVICE DEVICE PRIMARY PRIHARY HUHSER DIV HUHSER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEH ALARH POINT DP-S1<<2h D2 ADS VALVES (N C ) LOSS OF DIV 2 NONE chs POWER IS 1) "ADS B/D LOGIC POWER POWER CAN BE OPENED USED. FAIL" LICllT QITN "h" POWER TD 2) "ADS B/D OUT OF PERFORH ADS SERVICE" ANNUNC.

WHPP-2 COLD StlUTDOWH SYSTEMS - RHR SUPPRESSION POOL 'B'PPEHDIX sBs GROUP T SHEET 64 0 BUS BUS DEVICE DEVICE PRIMARY PRIMARY HllHBER DIV DUBBER DESCRIPTIOtl EFFECT ON DEVICE EFFECT ON SYSTEM ALARM POINT REFER TO CROUP 'Q'OR PUMPS'ALVES AHD CONTROLS TllhT ARE ALSO REQUIRED FOR SUPPRESSION POOL COOLING 'B ~

HC-BB-A D2 E12-F0278 RIIR LOOP "B" DIS- MOV FAILS AS IS ~ (N.C) VALVE llSED FOR RETURN I) s'HOV NETWORK POWER CtlARCE TO SUPPRES- TO SUPPRESSION POOL LOSS/OL" LICHT SION POOL MOV FLOW 2) "RllR B/C OUT OF 4

SERVICE" AHNUHC.

B~ ncaa (fll

MNPP-2 COLD SHUTDOMH SYSTEMS - MISCELLANEOUS APPEHDIX CROUP SHEET 65 66

'S'RIMARY BUS BUS DEVICE DEVICE PRIMARY NUBBER DELHI NIJHBER DESCRIPTION EFFECT ON DEVICE EFFECT ON SYSTEM hLARM POINT MC-2P<<<< 11 CAS-C-lc CAS COMPRESSOR 1C LOSS OP CAS-C>>1C AI(D REMAINING COMPRESSORS LOSS OF COMPRESSOR STATUS INDICATION HAVE ADEQUATE CAPA- LIGHTS OH BD-h CITY TSM-SV-1C PLANT SERVICE MATER TSM-SV-1C DISABLED LOSS OP 1 COMPRESSOR TO CAS-C-lc (C(.OSES IF OPEN) CAS-C-lc MC-7h<<<< 1 CAS-C-lh CAS COMPRESSOR lh LOSS OF CAS<<C-lh AND REMAINING COMPRESSORS I.OSS OP COMPRESSOR STATUS IHDICATIOH HAVE ADEQUATE CAPA- LIGHTS ON BD-h CITY TSM-SV-lh PLANT SERVICE MATER TSM-SV-lh DISABLED LOSS OP 1 COMPRESSOR LOSS OP COMPRESSOR STATUS TO CAS-C-lA (CLOSES IP Ol'EH) CAS-C-1A LIGHTS OH BD-h MC-Sh** 1 CAS-C-lS CAS COMPRESSOR lB LOSS OF CAS-C-18 AND REMAINING COMPRESSORS LOSS OP COMPRESSOR STATUS INDICATION HAVE ADEQUATE CAPA- LIGHTS ON BD-A CITY TSM-SV-1S PLANT SERVICE MATER TSM-SV-lB DISABLED LOSS OF 1 COMPRESSOR LOSS OP COMPRESSOR STATUS TO CAS-C-lB (CLOSES IF OPEN) CAS-C-1B LIGHTS ON Bn-h

<<*STANDBY COMPRESSION MILL START Ml(EN PRESSURE DROPS TO 90 PSIG. THIS MILL ANNUNCIATE IN THE CONTROL ROOM.

IP BKRS TRIPS DUE TO h GROUND OR OVERLOAD THIS MILL BE ANNUNCIATEDD HC-7h-h 1 PRA-PH-lh SM-HVAC PAN DISABLED SSM h PRA-FH-lh PMR LOSS. NOTE 1 ~

LOOP LOSS SSM h OUT OF SERVICE.

PP-7A-G 1 Tsl-21 SW-SUPV CONTROL LOSS OP SSM LOOP STAHDBY SV h SUPV SM-SPV SYSTEM TROUBLE SSM A-005 13-0187 (65)

$ tj P QNPP-2 COLD SllUTDOMH SYSTEMS - MISCELLANEOUS hPPENDIX 'B'ROUP SHEET 66 4 66 BUS BUS DEVICE DEVICE PRIMARY PRIMARY NUMBER . DIV NUMBER DESCRIPTION EFFECT OH DEVICE EFFECT ON SYSTEM . ALARH POINT HC-Bh-h 2 PRA-FN-1B SM-HVAC FAN DISABLED SSW B PRA-FN-ITS PMR LOSS EMOTE l~

LOOP LOSS SSM B OUT OF SERVICE.

13-0187 (66)