Comparision of Electrical Design of Wye Pattern Globe Valve Actuator W/Ball Valve,Hanford 2 & River Bend Design. Five Oversize Drawings Encl
ML17279A191
Person / Time
Site: Nine Mile Point, Columbia, River Bend, 05000000
Issue date: 04/07/1987
From:
NIAGARA MOHAWK POWER CORP.
To:
Shared Package
ML17279A190 List:
References
29766, NUDOCS 8704130450
Download: ML17279A191 (24)


Text

87Q413pq5p 87pqp7 PDR AOOCK Qgppp397 RDR NINE MILE POINT UNIT 2 DOCKET NO. 50-410 COMPARISON OF ELECTRICAL DESIGN OF THE WYE PATTERN GLOBE VALVE ACTUATOR WITH THE BALL VALVE, HANFORD 2 and RIVER BEND DESIGN

TABLE OF CONTENTS TITLE PAGE I.

SUMMARY

II.

ELECTRICAL AND ACTUATOR COMPARISON OF NYE-PATTERN AND BALL VALVE DESIGN III.

ELECTRICAL COMPARISON OF NMP2 AND RIVER BEND IV.

ELECTRICAL COMPARISON OF NMP2 AND HANFORD (NPPSS UNIT ¹2)

V.

ATTACHMENTS a.

One Line Diagram EE-M01D-6 b.

Pneumatic Control Circuits Schematic c.

Proposed Electrical Elementary Diagrams

d. Simplified MSIV Power Supply One Line Diagram 2976G

I

SUMMARY

This report provides a description of the Nine Mile Point Unit 2 electrical portions of the.Wye-Pattern Main Steam Isolation Valves (MSIVs).

The electrical design of the system is essentially the standard General Electric design.

The Protection System philosophy is unchanged.

Section II provides a comparison of the Wye-Pattern valves and the ball valves, while Section III provides a comparison of NMP2 and River Bend, and Section IV contains a comparison of NMP2 and Hanford (WPPSS Unit

¹2).

Section V includes diagrams and a schematic to assist in the review of the proposed changes.

2976G

C"

II.

ELECTRICAL AND ACTUATOR COMPARISON OF WYE-PATTERN 5 BALL VALVE DESIGN Initiation Si nals and Power Su lies a.

The Protection System signals that provide the trips for the Wye-Pattern MSIVs are the same signals utilized in the ball valve design.

The power supplies are the same non-Class 1E 120VAC supplied by UPS3A (Trip System A) and UPS38 (Trip System 8).

The design utilizes the same electrical protection assemblies (EPA), distribution panels and the same cables.

The fail safe de-energize to operate logic function, used for the ball valves, remains with the Wye-Pattern valves.

There has been no change in the routing of the field cables.

Physical separation of the four channels of power supply remains the same.

However, for the Wye-Pattern MSIV, the channel separation is maintained up to the junction box adjacent to the MSIV where the field cables end.

This was addressed in the proposed changes to the Unit 2 FSAR Section 8.3.1 submitted on March 11, 1987.

c

~

Attached for your information are selected General Electric elementary wiring diagrams of the trip logic and a Stone and Webster One Line Diagram of the power distribution system.

2.

Controls and Lo ic Each Wye-Pattern MSIV contains two electrically operated solenoid valves, a three way pilot solenoid valve with two coils and a test solenoid valve.

The two pilot solenoid coils on a MSIV is fed from a different trip system.

Since the two (2) trip pilot solenoid coils are supplied power from two (2) different trip systems and both trip systems must de-energize to operate, a transfer and isolation scheme is not required on the Wye-Pattern valves.

This change and the standard General Electric control scheme have reduced the number of field cables.

See expanded description in Section IV, comparison of NMP2 and Hanford.

The original ball valve design had 5 solenoids (2-trip solenoids, 2-latch solenoid valves, 1-test solenoid) and pump motors for each MSIV as electrical load.

Two trip solenoids and 2-latch solenoid valves were fed from two different channels of power supply (Class 1E).

The test solenoid was fed from 120V Class 1E bus; the pump motor was fed from 600V non-Class lE bus.

The hydraulic MSIV ball valve equipment is being deleted along with the local relay control panel.

2976G

Each Wye-Pattern inboard and outboard MSIV is controlled by a three position maintained selector switch (close-auto-test) and a pushbutton switch for testing each valve.

These switches are located on the operating benchboard in the PGCC similar to the ball valve design.

The. following table provides a descriptive comparison of the MSIV operation:

W e-Pattern Modified Ball

~0e n l n Opening the NSIV i s accomplished by energizing either pilot solenoid coil A or B on the 3 way solenoid valve.

This directs air to the 4 way control valve which directs the air to the cylinder piston to open the MSIV.

Opening the NSIV is accomplished by energizing both solenoid

valves, and forcing the valve open using hydraulic fluid.

Solenoid valves remain closed as long as HSIV is open.

Hydraulic pressure is maintained by hydraulic pump and Jockey pump.

a)

One 3 way solenoid valve a) Both solenoid valves needed with dual coils (A & B) is to open HSIV.

Solenoid needed to open an HSIV.

valves are connected in Only one pilot solenoid coil parallel.

is energized to open the MSIV.

b)

One out of two taken twice NS4 trip inputs shall not be present to open MSIV (A or C +

B or D) b)

Same C~los l n Closing the NSIV is accom-plished by de-energized both coils A & B of the pilot solenoid valve.

a)

Both coils of solenoid valve must be de-energize to close HSIV.

Closing the HSIV is accomplished by de-energized any solenoid valve A or 8, thus bleeding fluid from the piston and closing the MSIV.

a)

One solenoid valve de-energization causes NSIV to close.

b)

One out of two taken twice NS4 inputs close MSIV.

(A or C +

B or 0) b)

Same c)

A single power failure of either UPS3A or UPS38 will not close the HSIV.

c)

A single power failure will close the HSIV.

2976G

~Testln Testing of the MSIV is accom-plished by energizing sole-noid "C" (test solenoid) on the second 3 way solenoid valve.

This solenoid valve directs control air to the pilot air operated control valve and-shifts it to allow the 'air cylinder piston to exhaust at a controlled rate through an adjustable orifice.

Both green/red lights of MSIV will light, thus indicating valve is in intermediate position.

Testing of MSIV is accomplished by de-energizing testing sole-noid valve, which wi 11 initiate

'low closing of MSIV by bleeding fluid. When HSIV is 90/. open, the test circuit is automatically disconnected.

Thus solenoid valve will energize and HSIV will open again.

Test com-pleted indication light will light when valve 90/. open.

Also both green/red lights of HSIV will light, thus indicating'he valve is in intermediate position.

a) Test solenoid is normally a) Test solenoid normally ener-de-energized.

Energize to gized, de-energize to perform perform test.

test.

b) Test solenoid is Class lE b) Test solenoid is non-Class 1E c) Operator action required to return HSIV to full open position of the test.

Limit switches are not wired in the test circuit.

c) MSIV return to full open position of the test automatically.

Limit switches wired in test cir-cuit to automatically dis-connect test circuit.

C.

The trip logic for the Wye-Pattern valves remains the same as the ball valves, one out of two taken twice.

Isolated interlocks between trip system logic have been maintained to meet the requirements of NUREG 0737,Section II.E.4.2, Position 4 (Containment Isolation Dependability) as it pertains to resetting containment isolation valves.

The NUREG requirement is still maintained.

All logic and controls are located in the control room.

d.

With the Wye-Pattern valves, there are some minor hardware changes in the logic, as delineated in (c) above.

The relays used by General Electric are qualified MDR (Potter

& Brumfield) and Agastat.

The ball valve, local J10 Gould relays are not being used and are being removed.

Ball valve reed switches that were used in the control circuits have been deleted from 'the Wye-Pattern valve circuitry.

MSIV Limit Switch In uts to the Reactor Tri S stem The HSIV limit switch inputs to the Reactor Trip System logic remains unchanged from the ball valve design.

However, there are two changes associated with the HSIV limit switches.

2976G

4,.

R

a 0

b.

The trip setpoint for the ball valves was 941. open, while the trip setpoint for the Nye-Pattern valves has been changed to 92K open.

This change is reflected in the Technical Specifications.

White status lights have been added to the two (2)

Reactor Trip System vertical panels to assist the operating!staff during surveillance testing of the MSIVs.

The white status lights will be extinguished when the MSIV limit switch reaches the trip setpoint during the performance of the test described in paragraph 2.B above.

Actuators b.

The design change to Wye-Pattern MSIVs necessitated the addition of an air supply system for operation of the

-Nye-Pattern valves.

The air system includes the use of individual air accumulators of sufficient reserve to close each valve one time.

The ball valve relied on stored spring force alone to close the valve.

The Wye-Pattern valves utilize a pneumatic cylinder to provide the necessary force to compress the MSIV springs.

The hydraulic portion of the actuator consists of hydraulic cylinders and flow control valves.

This system is the hydraulic speed control system.

There are no electrical controls involved for the hydraulic speed control system.

The ball valves used a hydraulic actuator and opened the valve by hydraulic pressure.

Solenoids and hydraulic pumps were used to maintain pressure against the piston to keep the MSIV open.

When the fluid is bled from the

piston, the valve closes.

Attached is a pneumatic and hydraulic control circuit schematic of the Wye-Pattern valves.

The four inboard MSIV pilot valves and MSIV actuator accumulators are supplied with nitrogen gas from the instrument nitrogen system (GSN).

The four outboard MSIV pilot valves and MSIV actuator accumulators are supplied from the reactor building instrument air system (IAS).

2976G

i

Monitorin a.

Red and green status lights located on the operating benchboard indicates that the valve is open or closed based on input from the HSIV limit switches.

Additionally, white status lights for each MSIV solenoid valve energized are'also located on the same benchboard.

These monitoring lights remain the same as the ball valves.

Monitoring -lights have been deleted for associated ball valve specific controls that have been deleted.

b.

MSIV limit switch inputs to the Emergency

Response

Faci 1 i ty (ERF) remains unchanged as are the limit switch inputs to the General Electric transient analysis recording computer (GETARS).

Off normal status inputs also remain unchanged with the Wye-Pattern valves.

Process computer and annunciator inputs remain unchanged except for ball valve specific hydraulic controls that have been deleted.

III.

ELECTRICAL COMPARISON OF NMP2 AND RIVER BEND STATION (RBS)

Initiation Si nals and Power Su lies a

0 b.

The Protection System signals for NMP2 remain unchanged and are the standard General Electric design.

The initiation signals are essentially the same as RBS.

The electrical power distribution system of NHP2 with Wye-Pattern HSIV is very similar to the power distribution system of RBS Wye-Pattern MSIV.

The RBS M-G sets used to supply power to the MSIVs are non-Class 1E, and are normally fed from plant non-Class lE buses.

These are connectible to the emergency buses except during a

LOCA.

The NHP2 UPS used to supply power to the Wye-Pattern HSIVs are non-Class lE AC and DC buses.

The alternate power supply at the output of the RBS M-G set is from the plant non-Class 1E bus through step down and regulating transformers.

The alternate power supply at the output of the NMP2. UPS is also from the plant non-Class lE buses through step down and regulating transformers which are connectible to the emergency

buses, except during a

LOCA.

RBS considers these power sources non essential because the system is of fail-safe designs NMP2 also considers these power sources non essential because the system is of fail safe design.

2976G

RBS uses two series electrical protection assemblies (EPA) to protect the logic circuits from overvoltage, undervoltage and under frequency conditions.

The EPAs are Class lE.,

NMP2 also uses two series Class lE EPAs, and provides the same protective functions.

Both RBS and NMP2 designs treat this distribution system beyond EPAs as Class lE.

Both designs have used 4 channels.

The cables associated wi,th each channel are uniquely identified in both designs.

In both cases,

.the channel separation is maintained up to the junction box adjacent to the MSIVs.

RBS uses two high integrity, alternating current motor-generator sets as the normal power source for the MSIV power supply.

NHP2 uses two uninterruptible power supplies (UPS) as the normal power source for the Wye-Pattern MSIVs.

Controls and Lo ic The control of the NMP2 MSIV Wye-Pattern valve is similar to the operation of the River Bend MSIV Wye-Pattern valves.

Protection System logic for isolation are developed in the same fashion as to cause a trip of the HSIV valves.

The manual,

auto, and test hardware,,operator control functions and monitoring devices located in PGCC are also similar.

In both plants, each MSIV valve is operated by two normally energized solenoids to keep the HSIV valve open under normal plant operation.

Failure of one channel will de-energize only one solenoid keeping the MSIV valve open, failure of two channels of power will de-energize both solenoids closing the MSIV valve Both plants are also equipped with a HSIV test solenoid valve, which can be manually operated from the control room.

Actuators The NMP2 MSIV is a 26" Rockwell valve while the River Bend HSIV is a 24" Atwood Morill Valve.

A comparison of the NMP2 Wye-Pattern valve and the River Bend Wye-Pattern valve reveals no functional differences.

This is because both valves were designed to meet General Electric's specification requirements for HSIVs (i.e., closure times).

Both valves utilize loaded springs and/or pneumatic pressure to close the valve.

A comparison of air systems shows that both plants use an accumulator to supply the air quantity required for pneumatic closure of the valve if the normal air supply is unavailable.

NMP2 and River Bend protect this air reserve with a check valve which isolates each accumulator from a loss of upstream pressure.

NHP2 and River Bend use filters in the air piping to meet General Electric's air quality requirements.

Both plants use stainless steel piping downstream of the air filters to maintain air quality to the HSIVs.

2976G

The air supply systems to the MSIV actuator accumulators on NMP2 is similar to that found on the RBS with the following exceptions.

NMP2 supplies the four inboard MSIV pilot valves and MSIV actuator accumulators with nitrogen gas from the instrument nitrogen system (GSN).

The four NMP2 outboard MSIV pilot valves and MSIV actuator accumulators are supplied with air from the reactor building instrument" system (IAS).

On River Bend both inboard and outboard main steam isolation valves and MSIV actuator accumulator are supplied from the instrument air system (IAS).

4.

~Moni torin Monitoring for NMP2 was described in detail in Section II.5 above.

NMP2 monitoring devices are essentially the same as RBS with the following exceptions.

NMP2 has MSIV status inputs to the off normal status display, while RBS does not.

NMP2 and RBS both have indicator lights to monitor both MSIV pilot solenoid valves energized.

RBS utilizes ammeters to monitor pilot solenoid valve

current, while NMP2 does not utilize this feature.

ELECTRICAL COMPARISON OF NMP2 AND HANFORD (WPPSS UNIT ¹2) a.

General Descri tion of Control Lo ic The NMP2 Nuclear Steam Supply Shutoff System (NS4) functions are initiated when sensor

signals, monitoring key parameters, exceed setpoints and de-energize relay control circuits, which initiate closure of the isolation valves.

The control circuitry is arranged in dual systems so that a trip must occur in both trip systems to cause a closure of a main steam isolation valve.

Each trip system contains two independent tripping sensors from each measured variable, only one of which is required to activate a trip system.

The trip systems designated A and 8 are subdivided into logic channels A through D.

MSIV logic channels A and C are in trip system A and logic channels B and D are in trip system B.

2976G

For MSIVs, a tripped sensor provides open inputs to a logic function which causes the sensor relay in the associated trip channel to de-energize.

The open contacts from the de-energized sensor relay are connected in logic functions which cause a trip relay to de-energize.

Output from the de-energized trip relays are combined in one-out-of-two-twice logic which generates closure signals for the main steam isolation valves.

The Hanford MSIV trip logic functions the same as the NMP2 logic described above.

b.

Outputs from the main steam isolation valve limit switches are connected into the Reactor Protection System (RPS) circuits for both Hanford and NMP2, which is the standard General Electric design.

MSIV Tri Variables There are seven monitored parameters that make up a trip logic channel for MSIV isolation.

A comparison of these for NMP2 and Hanford follows:

NMP2 HANFORD Reactor Low-Low Ntr Lvl Instrument make-Setpoint-Rosemount XMTR 5 Trip 17.8" (-5 to 205 scale)

(Level 1)

Barton XMTR/Switch

-50" (-150 to 60 scale (Level 2)

STM Ln HI Flow Instrument make-Setpoint Main STM Line Low Press Instrument make Setpoint Main STM Line HI Rad Instrument make Setpoint Main Cond.

Low Vac Instrument make Setpoint Turbine Bld HI Tem Instrument make Main Stm Ln Area HI Tem Instrument make Rosemount XMTR & Trip 103 psid (prelim)

Rosemount XMTR 5 Trip 766 psig GE 1181.

Rosemount XMTR 5 Trip 8.5" vac.

Riley (part of main stm line area HI temp)

Riley Barton Press Switch 105.5 psid (prelim)

Barksdale Press Switch 831 psig GE 1181.

Supplied by AE By AE Riley Riley 2976G

>r,.

y

Reset Function To reset the relay circuits and re-energize the pilot solenoids following a main steam line isolation (i.e.,

a trip in both trip system A and B which is subsequently cleared),

the manual switches for all of the main steam line isolation valves must be operated to the closed position.

The switches in the reset circuit which energize relays whose contacts are in parallel with the seal-in contacts of the trip relays are then actuated.

To reset the relay

'circuits following a spurious trip of either system A or system B (not both) after the sensor(s) is reset, only the isolation reset switches must be actuated.

This reset operation is the same for both NMP2 and Hanford.

Test Function Manual switches for the MSIVs are loca,ted on panel H13-P602.

There are two switches associated with each valve.

One is a

3 position maintained-contact switch for valve control and one momentary switch for testing the valve.

After the main control switches are placed in the closed position and the trip logic reset the valves may be opened by placing the control switch in auto.

To test the valve, assume the valve is open.

The control switch is then placed in the test position.

This provides a

permissive for the momentary test switch to energize the test solenoid.

Pushing the test switch and holding it, energizes the test solenoid and the valve proceeds to close.

When the test switch is released the valve reopens.

This operation is the same for both NMP2 and Hanford.

Hanford differs only in that the main control switch is a different type GE 3 position maintained-contact switch mounted on panel H13-P601 and the test switch is a different type pushbutton switch also mounted on panel H13-P601.

Monitorin and Annunciation NMP2 has two white indicating lights for each valve (one on each pilot solenoid) to indicate solenoid energized.

These lights are mounted on panel H13-P602.

Also mounted on panel H13-P602 is

a. red and green indicating light to indicate valve open or closed.

Hanford has the same light configuration except the red and green lights are mounted on panel H13-P601 and the white lights are mounted on backrow panels H13-P622 and H13-P623.

NMP2 monitors valve-open, valve-closed and valve initiation (valve solenoid A energization) by the GETARS system whereas Hanford monitors control switch in auto position by their TDAS system and "logic ready for valve opening" (both pilot solenoids inboard and outboard valves) to an isolation valve status and display system.

Both NMP2 and Hanford annunciate the following parameters:

Reactor vessel low water level, main condenser low vacuum

bypass, main steam line high flow, main steam line low pressure, main condenser low vacuum.

Also, main steam line high flow is sent to the computer for both plants. 2976G

1azg 1

NMP2 annunciates main steam line isolation system-out-of-service by monitoring the Rosemount trip units while Hanford monitors MSIV Div.

1 and Div. 2 trip channel de-energization.

NMP2 monitors trip unit in CAL or gross failure with status lights that. have an integral test switch.

Hanford does not have trip units and therefore does not monitor this parameter.

NMP2 annunciates inboard and outboard reactor isolation system-out-of-service whereas Hanford annunciates NSSS Div.

1 and Div.

2 out-of-service.

ATTACHMENTS a.

NMP2 One Line Diagram Normal 600V and 120VAC EE-M01D-6 b.

Pneumatic Control Circuits Schematic of MSIV Actuator C.

d.

Proposed NMP2 Nuclear Steam Supply Shutoff System (NS4)

Elementary Wiring Diagrams of Logic and Controls (four diagrams)

Simplified,MSIV Power Supply One Line Diagram

- 11 2976G

~ ~

~

0 0

~

o

~

s Qg Qg 0

t 0

~

~

nSIV ACTUATOR OPEN Ql Bg EXHAUST EXHAUST (RESTRICTEO) 8-MAY 2-NAY Qz CLOSE VENT S

SOL-1 EXHAUST TO VALVE BOOY F51 V Y-PATTERN PNEUMATIC ACTUATOR (SHORN IN OE-ENERBIEEO/CLOSEO CONDITION)

VENT S

SOL-2 S

SOL-3 TABLE OF OPERA'llONS MSIV OPEN OA SOL-I ls OE-ENEROIZEO-S-NAT VLY ACTUATEO 08 SOL-2 OR SOL-S EIKROIZEO

~

o) 2-NAT VLV CLOSES b) 4-NAT VLV ACTUATED 4 AIRF LOII ttfQIRECTED I A~O/B~C) NHICH ALLONS VOLUIIE OI TO EXHAUST VIA 8-C C YOI.UIIE O2 TO PRESSURE VlA A-0 A S-NAT VLV~ ltl$1V OPfNS ~

JPJLERX.

QAttSIV IS OPEN SOL-1 IS EICROIZEO 8-NAT VLV OOES TO'EXHAUST POSlTION 4 ALLONS VOLUIIE g)

TO VENT T eouOH RESTaICTEa,;

EXHAUST-tISIV SLON CLOSES UNTIL-OPERATORS Of-ENERIIZE SOL-I ~

AFTER NHlCH tlSIV RETURNS TO FULL OPEN.

FAST CLOSE (EMERGENCY)

OASOL-2 C 3 ARE OE-ENEROIZEO.

i-NAT VLV GOES TO NORtlAL.

(AIRFLOK lS A - B/0 -

C )

2-NAT VLV OPENS.

VOLUIIE VENTS THROUGH 2-NAT VALVE C 4-KAT VLV IO-C).

VOLUIIE 01 1S PRESSURlZEO Y1A I-KAT VLV IA-8) KHICH FORCES IISlV CL OSF0 hl ONI) K I IH ACTUATOR SPRING'S.

H

,4(',,rjE, (,

j I, Ij !,

1 j I;j.,)II(j.I I rrlj,,'..:..', j';*,'i'j',

j.:",i,,'j

~

BI7E I 52T Y 8

IS 12 13 REVISIGN LT(2 W 2MSSN42 RA (SY AE) 5(D Yoo LTK ZM55N42 RA (SY AE)

SIC L

ZMSSNAZ (5Y AE) 0 LTI 2M55N42 (ev AE)

R LT'5 2M55N42 (BY AE)

R LT4 ZMSSNAt (BY AE) 0 LT(0 W 2M55N42 5 IA I

LT9 2MSSLI 12 (Dv AE)

R LTS ZM55 M OZ

(

(Dv AE)

(

LT7 21(55N42 (Dv AE)

R G

) ZM5SN42 (av Ael (BY AE)

LTS ZM55N12(ev AE) 3 4 H(3. Peot 2

(Al 7

U P

N K

L H

I

.19 Wo( Z c

o F

-DE)EL F

ttN.W077 357 9

-lm N

P 0

R 5

T 0358 E

W(25 I

A 8

G H

J K

M Jl (3 Sl I C

0 2

(A)

W V

T U

K L

M F

G Tl

-26 Ktla Ml CC.Z7 A

C (a

Io C

rove f('oc k 10 CII IO C-Tl 45 Ktt5 Ml CC-35

-re (20 VAC upa aua a 5EE SH.4 Flri. (9 I

E-I 81 K816 ae T4 (N

51 Ktea BI TZ 51 ESK75CZ Grlrl 54 Kt1a Bl MS Tl 0 -I

.4 K'93 8 M

DD 14

-5 Tl A

Ktca LAI K51 5 BI M4 T3 TI K'118 Ml 00 21 N(3- (%22 SEW CKTO 2MSSN42 O-54 54 K518 KBS 8 I el MS MI K5( 6 M3 Kl31$

111536 xseB Ml H(3-PL(I CC 12 CC 19 Cf CC cd c4 CC -(9 CC-IB CC ~ 17 CC.55 Cc 54 CC.53 cc.58 Cs C(7 CC

~ 19 CC-48 DD 16 DD 15 356 Na'x, 3'ltWMS Kl Ortoee 6

52tH-WI05 314 W147

)o(7oa S 5

Y~CSO J A,

wreo 513 P7oe E Tceol Jl 8

C TC 302.JI 371W144 KI 224+

Kot

-2 r

W(05-I SPL ICX 8or Is) Acr oc.)5.2 oc M r

SALICX sor (SE A(1 So.ss.z oo ss-r OAL)cc Eer Ac I oe.n-z oe.M.E SPL)CE SQE (er Acr r)A.)5.2 CON Ter IN MENT PENETRATION SA )s.r J316 A

5 soroA C

0 8

A A

C 0

8 A

A 8

C 0

8 A

A 8

C 0

e A

A NOFC NOFC NOFC NOFC iDRVWELL PILOT SOL.A PILOT SOI A PILOT SOL.A PILOT SOL.A j

VALVE 822-F0225 TEST SOL.

VALVE (322-FO22D Cl PILOT SOLB TEST SOL HI5-Pel I 5 VSLVE 822-F022(

PILOT SOL.B TEST SOL.

VALVE(&22-FO22I4 PILOT SOL.B TEST SOL.

I I

PILOT SOL.B

~+DRYWELL 2 PENETRATION NOFC NCFC NOFC NOFC NCFC NCFC NOFC NCFC

)

1413 Peo'IC J 215 A

A 8

E e

2 F

E F

e E

F A

8 CONTAINMENT ENETRATION SOVC C SOE (er N)

Sovr.e SOV6A SOV60 SPLICE ecx rev N)

SPLICE (81 AC)

SPLICE SOE ler Nl Kot C.

KOS C

W110 A

)00 31 1

~Roe 6 TCSPSJZ.

w

(

XDT 84'oeE ECeo 5 Kor Jv)o pe TC381 KlI W(04-I 2 rs S

I-CU 0)

LU Ee CO W(43 3to 223 l J III; A e

c e

c CC 102 CC 108 J(17 A

JI(2 A

8 C

Jl I 8 A

55W CKTO ZMSSN45 I

51 5 I KZ58 KIZ KI48 K

IAI MS K1275 2

84 84 2

8255 I-t)SCBOI 5

C 25K 715001 M4 T4 Mt 144 Kr K(62 ate a L

(REF) tl 14 RPS A IZO VAC Pe SUSA E 5H.4 FIG. 1 ORES CC CC

.73

-74 CC

-72 Cc CC 76

-75 CC

-71 CC

.81 CC-77 CC

-em CC

-79 CC.78 CC.82 CC

-85 CC

-83 CC

-ee CC.ee CC Cf cc-89 H(5-Pet2 8126

-5 6

E F

.3 C

D

-12

- le

-13

-14

-15 P

0

-16

-19 351 U

F 17

-18 CC CC

. 7

~ 7'I CC

-72 CC CC 76

-75 CC

-71 CC

-em CC

-7 Cc

-82 CC CC

-83 CC CC ee CC-77 CC-ee CC. 78 CC CC

-ee cc-89 92(

D IN0 Ic 510 II INO (NO I SIC SraI"I'j SIR IA (ev AE) 5 IA ~

515 IS SwrT LBV AE) 515 (NO IC 5IC IC II SWIT 1(av AE)J SIC 10 (av AEI SID IC G

Tt w

G W

RA LT 6

L (3

14 (3

)41 L

ZM5584 (BY AE) 73 w

13 (4

LT4 W

(BYAE) 211551M (iev AE)

ZM55N43 (ev AE) l4.

1 R

19 Peot 771 9 V ( 7~()OKnO)

C I

lo ti 10 9

1

(

0 t 00-4I I

'D(P4 5 DD.LF)

CCNE, P)N N)

E vLv (PErr SWITO(

ND.

5 I 8 918 9

rrrm FROA TD 33-1 VLV CLOSED IN)

Eax lmsxsm7 VLV CLC620 IN)

EsK I trsxst6 Q-s(.

3 3.53 Jd-50 J3-51 33-)

RPS REF 6 RPS REF 6 Pog I

O(7-(3(7 PO~

E.

I 0 (,-0 I

33-6 I

j 1

~or~

RPS REF 6 RPS REF 6 33-3 Esx 7scl 132. 83 ESK 75CI (3. 11 CS

-7)M 2

SK-IMS VLV CPEN IN)

ESK IQSXSI(6 VLV (PEN )11)

Esx I msxs(87 O(,06 I

Bk-L05+POQ I~ L.-lO52597.

I (k(I- 0(

33.2 (wIC- )LDLK+Of I

M~f,(L LGIV LEAK, REF 28 SISNA)URCS A r w!

r ~

'B$7EI52TY rmg '11 EEELE 8 E

OENERALIQ ELECTRIC c-rem 13 12 I

Ij

," jI ij

rr

, I I(

rj

!ii lrt I jl::j fcl

'I(

,'jj,

'4

(

j;,'.'

!'; le.

I 1;r jfvr I),

j I

I; i'4' I

I'I r 1)

! 0 I (,,"r:"I ie (

(V I r,e..pj 404)441;) gal

%PERM'CAN@

>> ~

~

~

q

~

~

I JEh QIF Wg I ~

~ ~

~ q

~

~

I

~

~

~

ggg~~oRRSI W III~I@RMEHEioEs

~

~

~

>r