RBG-47773, Supplement to License Renewal Application
ML17213A064 | |
Person / Time | |
---|---|
Site: | River Bend |
Issue date: | 08/01/2017 |
From: | Vercelli S Entergy Operations |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
RBG-47773 | |
Download: ML17213A064 (66) | |
Text
EntergY.
August 1, 2017 RBG-47773 U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555
Subject:
Supplement to License Renewal Application River Bend Station - Unit 1 Docket No. 50-458 License No. NPF-47
References:
- 1. License Renewal Application, River Bend Station letter no. RBG-47735, dated May 25, 2017
- 2. NRC letter dated July 10, 2017, River Bend Station, Unit 1 License Renewal Application - Supplemental Information Needed for Acceptance of Requested Licensing Action (CAC No. MF9747)
Dear Sir or Madam:
By way of Reference 1, Entergy Operations, Inc. submitted an application for renewal of the operating license for River Bend Station, extending its license term to August 29, 2045.
On July 10, 2017, RBS received by way of Reference 2 a request that the application be supplemented with certain information.
Attachments 1 and 2 to this letter contain the requested information. This document contains no commitments. If you require additional information, please contact the Manager-Regulatory Assurance, Mr. Tim Schenk, at 225-381-4177.
I declare under penalty of perjury that the foregoing is true and correct. Executed on August 1, 2017.
s; nc 0r-iJ Li!2 '
SPV/dhw Attachments RBF1-17-0083
Supplement to License Renewal Application RBG-47773 Page 2 of 2 cc: U. S. Nuclear Regulatory Commission Attn: Emmanuel Sayoc 11555 Rockville Pike Rockville, MD 20852 U. S. Nuclear Regulatory Commission Attn: Lisa Regner 11555 Rockville Pike Rockville, MD 20852 U. S. Nuclear Regulatory Commission Attn: Elaine Keegan 11555 Rockville Pike Rockville, MD 20852 U.S. Nuclear Regulatory Commission Region IV 1600 East Lamar Blvd.
Arlington, TX 76011-4511 NRC Resident Inspector PO Box 1050 St. Francisville, LA 70775 Central Records Clerk Public Utility Commission of Texas 1701 N. Congress Ave.
Austin, TX 78711-3326 Department of Environmental Quality Office of Environmental Compliance Radiological Emergency Planning and Response Section Ji Young Wiley P.O. Box 4312 Baton Rouge, LA 70821-4312
Attachment 1 to RBG-47773 Supplement to License Renewal Application
RBG-47773 Page 1 of 7 Question 1:
The list of transients for Class 1 components in RBS LRA Table 4.3-1 is not consistent with the transient sets defined in the subsections of Updated Safety Analysis Report (UFSAR)
Chapter 3.9.1 B or in UFSAR Table 3.9B-1. With this inconsistency, the staff is unable to evaluate the fatigue monitoring methodology against specific transient sets defined for components in the UFSAR, or evaluate Entergy's acceptance of fatigue time-limited aging analysis (TLAA) for Class 1 components using 10 CFR § 54.21 (c)(1 )(iii) and the Fatigue Monitoring AMP.
Response
Updated Safety Analysis Report (USAR) Section 3.9.1 B, including Table 3.9B-1, identifies the transients which were used in the design of major NSSS ASME Section III, Code Class 1 and Class 2 components. RBS LRA Table 4.3-1 defines the transients used in Class 1 fatigue analyses that require tracking. Differences can occur for a number of reasons. For example, emergency and faulted events do not require tracking because they are infrequent events.
Therefore, apparent inconsistencies are not unexpected.
LRA Table 4.3-1 summarizes the results from RBS calculation 6247.547-604-014, "Adequacy of Cycles Being Tracked for Fatigue Monitoring," which was generated to determine the transients that must be tracked to ensure the ongoing validity of fatigue analyses during plant operations. This calculation documents the review of reactor pressure vessel thermal cycle diagrams, thermal cycle diagrams for power uprate, reactor pressure vessel nozzle thermal cycle diagrams, piping system histograms, and the USAR, and identifies the transients that are considered in the fatigue analyses. The calculation identifies transients that must be tracked to assure the ongoing validity of the fatigue analyses.
In response to this request for additional information, Entergy is providing a copy of RBS calculation 6247.547-604-014, which contains the comparison between the USAR design transients and the information summarized in LRA Table 4.3-1.
Question 2:
RBS LRA Section 4.3.3 provides the applicant's Environmentally Assisted Fatigue (EAF) analysis for Class 1 components, however the applicant did not include, address, or justify its methodology for identifying plant-specific component locations in the reactor coolant pressure boundary that may be more limiting than the components identified in NUREG/CR-6260 for the assessment. The staff is unable to evaluate the applicant's EAF methodology without the necessary supplemental information.
Response
General As indicated in the enhancement to the Fatigue Monitoring Program described in LRA Section B.1.18, Entergy will develop a set of fatigue usage calculations that consider the effects of the reactor water environment for a set of sample reactor coolant system components. In developing the calculations, Entergy will evaluate all of the Class 1 fatigue analyses in order
RSG-47773 Page 2 of 7 to identify the transients that the Fatigue Monitoring Program must track to ensure that the fatigue usage factors considering environmental effects will not exceed 1.0 without appropriate corrective actions as specified in the program. This will include all of the NUREG-6260 locations.
The EAF evaluation utilizes NUREG/CR-6909 (ANL-06/08), "Effect of LWR Coolant Environments on the Fatigue Life of Reactor Materials," in the evaluation of environmentally assisted fatigue for all materials. (NUREG/CR-6583 and NUREG/CR-5704 will not be used.)
Environmental correction factors applied to CUFs with different material types are material-specific environmental correction factors. A cumulative usage factor (CUF) from one material type will not be used to bound a CUF for another material type.
Piping RSS is a newer vintage plant (SWR-6) that has extensive Class 1 piping fatigue analyses with calculated CUFs. The piping evaluations for RSS are performed using ASME Code NS-3600.
The fatigue analyses for Class 1 piping locations throughout the plant are based on the loads experienced at those locations. For purpose of evaluating environmentally assisted fatigue, a thermal zone is a section of piping that experiences the same transients and the transients are the same from a pressure and temperature perspective. A CUF in one thermal zone can only be used to bound a CUF for the same material in other thermal zones if a bounding temperature is used and the transients in the other thermal zones are the same or a subset of the transients in the first thermal zone. The following criteria are used to select the bounding locations in each thermal zone for further consideration of environmentally assisted fatigue.
- The location with the highest CUF.
- The location with the second highest usage if it is at least 50 percent of the highest CUF.
- The location with the third highest usage if it is at least 75 percent of the highest CUF.
The NUREG/CR-6260 locations are evaluated regardless of their CUF.
Reactor Vessel The reactor vessel fatigue analysis has CUFs calculated for more locations than the locations identified in NUREG/CR-6260. The CUFs for reactor vessel locations that are part of the wetted reactor coolant system pressure boundary are included.
Valves and Pump Casings The RSS Class 1 valves and the reactor recirculation pump casings have fatigue analyses with CUFs that are included in the review. Class 1 valves in the following systems are included:
- Main steam (including safety relief valves)
- Reactor recirculation
RBG-47773 Page 3 of 7
- Low pressure core spray
- Reactor core isolation cooling Piping Penetrations The evaluation includes the fatigue analyses for the pressure boundary location on the flued heads of Class 1 piping penetrations.
Conclusion The environmentally assisted fatigue evaluation for RBS Class 1 components is a comprehensive evaluation of plant-specific component locations in the wetted portions of the reactor coolant pressure boundary. The evaluation includes all NUREG/CR-6260 locations.
The completed evaluation will demonstrate that the Fatigue Monitoring Program is monitoring the transients necessary to ensure that fatigue analyses that are adjusted to reflect the effects of the reactor coolant environment remain valid during the period of extended operation. If monitoring indicates that a CUF may exceed 1.0 when considering environmental effects, then appropriate corrective actions will be taken as specified in the Fatigue Monitoring Program.
Question 3:
Certain Class 3 support components, identified in the UFSAR, are assessed for aging effects with a cumulative usage factor (CUF) type of fatigue analysis. RBS LRA Table 3.5.2-1 identifies the analysis as a TLAA for these components, however, Section 4 of the LRA does not include any evaluation of a fatigue analysis for these components. The applicant did not demonstrate that the components were analyzed with a CUF per ASME NB-3200 or NB-3600, and did not identify or evaluate the applicable analysis in accordance with either 10 CFR 54.21 (c)(1)(i), (ii), or (iii). The staff is therefore unable to evaluate the TLAAs on these components without the necessary supplemental information.
Response
Appendix 6A to the USAR contains the details of the containment dynamic loading assessment. Attachment A to Appendix 6A provides additional information for determination of the safety/relief valve discharge loads. Section A.6A. 7.2 identifies that the X-quenchers were designed and analyzed as Class 3 piping in accordance with the requirements of Section ND-3600 of the ASME Boiler and Pressure Vessel Code. USAR Section A.6A.7.2 documents a supplemental analysis that was generated in response to an NRC question regarding the X-quencher at the connection to its support bracket. USAR Section A.6A.7.2 identifies that while ND-3645 does not require a separate analysis, the bracket-quencher interface connection was analyzed to the requirements of NB-3600 of the ASME code. Based on 4,200 cycles of the most severe transient of a step change from 70 to 350 degrees F, the resultant usage factor was identified as 0.47.
LRA Table 4.3-1 identifies that safety/relief valve actuations are tracked with limiting values of 1,295 single safety/relief valve actuations and 58 multiple safety/relief valve actuations. The
Attachment 1 RSG-47773 Page 4 of 7 4,200 cycles used in the analysis identified in USAR Section A.6A.7.2 are far in excess of the limiting values provided in Table 4.3-1. Therefore, the bracket-quencher interface connection fatigue analysis described in the USAR Section A.6A.7.2 will remain valid for the period of extended operation per 10 CFR 54.21 (c)(1 )(i).
Since the fatigue analysis description in USAR Section A.6A.7.2 is for the X-quencher at the connection to the welded bracket, the analysis is not for a support. Therefore, this line item is removed from LRA Table 3.5.2-1.
LRA Section 4.3.2.2 is amended by adding a new paragraph that discusses the quencher fatigue analysis identified in USAR Section A.6A. 7.2.
Additions are underlined and deletions are lined through.
LRA Table 3.5.2-1 Aif--
Steel elements: fn.Gw!:
TL/\/\
SRV quenoher Stainless unoontroll II.B2.2.C &&
~ Craoking metal G support and stoeJ. ed or fluid ~ 4-9 restraint environme ~
At Add to LRA Section 4.3.2.2 as new paragraph:
USAR Section A.6A.7.2 identifies that an ASME subsection NS-3600 analysis was performed for the bracket-guencher interface connection. The 4,200 cycles used in the analysis identified in USAR Section A.6A.7.2 are far in excess of the limiting values for safety/relief valve actuations provided in Table 4.3-1. Therefore. the analysis identified in USAR Section A.6A.7.2 remains valid in accordance with 10 CFR 54.21(c)(1)(i).
Question 4:
The LRA did not provide information that the staff requires in order to perform an independent review of the applicant's site-specific analysis of potential surface water use conflicts for continued operations during the license renewal term. Specifically, the staff requires the last five years' of surface water withdrawal and associated consumptive water use data in order to perform a projection of operational impacts on surface water flow. The staff cannot perform this review without the necessary supplemental information.
Response
Mississippi River water withdrawals and blowdown discharges for the years 2012 - 2016 are shown in the following table. Slowdown discharges were obtained from the monthly discharge monitoring reports submitted to the Louisiana Department of Environmental Quality and are based on monitored effluent from Outfall 001 (cooling tower blowdown) which is recorded at the exposed vacuum-break chamber of the buried 30-inch diameter discharge pipeline prior to discharge to the Mississippi River. Outfall 001 also receives previously monitored intermittent effluent from Internal Outfalls 101 (low-volume waste treatment system), 201 (treated sanitary
RBG-47773 Page 5 of 7 wastewater), 301 (mobile metal-cleaning wastewaters), 401 (low-volume wastewater), 501 (low-volume wastewater), 601 (low-volume wastewater) and 007 (hydrostatic test wastewater).
As shown in the following tables, there were days during which no surface water withdrawals occurred; however, during refueling outages or plant shutdowns, discharges can still occur at Outfall 001 without makeup water.
RBS Surface Water Withdrawals and Blowdown Discharges (2012-2013)
MonthNear Withdrawals Blowdown Consumption (Average MGD) (Average MGD) (MGD)
January 2012 17.10 4.215 12.89 February 2012 15.41 3.989 11.42 March 2012 18.16 4.255 13.91 April 2012 17.83 4.221 13.61 May 2012 9.61 (a) 3.396 6.21 June 2012 14.23 (D) 3.560 10.67 July 2012 20.16 3.856 16.30 August 2012 19.90 3.570 16.33 September 2012 19.10 3.752 15.35 October 2012 18.71 3.945 14.77 November 2012 19.03 3.794 15.24 December 2012 18.00 3.969 14.03 January 2013 17.81 4.146 13.66 February 2013 10.38 (e) 3.782 6.60 March 2013 5.67 (a) 4.150 1.52 April 2013 18.34 4.240 14.10 May 2013 19.62 4.295 15.33 June 2013 17.87 4.212 13.66 July 2013 21.44 4.234 17.21 August 2013 21.41 3.922 17.49 September 2013 21.58 3.918 17.66 October 2013 20.72 3.765 16.96 November 2013 19.87 3.916 15.95 December 2013 19.24 3.998 15.24
RBG-47773 Page 6 of 7
- a. There were 7 days in the month during which no surface water withdrawals occurred.
- b. There were 3 days in the month during which no surface water withdrawals occurred.
- c. There were 12 days in the month during which no surface water withdrawals occurred.
- d. There were 17 days in the month during which no surface water withdrawals occurred.
RBS Surface Water Withdrawals and Blowdown Discharges (2014-2015)
MonthlYear Withdrawals Blowdown Consumption (Average MGD) (Average MGD) (MGD)
January 2014 15.29 3.598 11.69 February 2014 15.93 3.557 12.37 March 2014 15.77 3.670 12.10 April 2014 17.53 4.076 13.45 May 2014 18.94 4.165 14.78 June 2014 20.17 4.171 16.00 July 2014 20.00 4.110 15.89 August 2014 20.10 4.111 15.99 September 2014 19.53 3.989 15.54 October 2014 15.19 3.906 11.28 November 2014 18.73 4.051 14.68 December 2014 18.71 4.042 14.67 January 2015 18.71 3.922 14.79 February 2015 15.39 (e) 2.837 12.55 March 2015 7.26 (f) 3.297 3.96 April 2015 18.73 3.966 14.76 May 2015 18.71 4.104 14.61 June 2015 18.40 3.965 14.44 July 2015 18.71 4.102 14.61 August 2015 19.16 3.998 15.16 September 2015 20.40 4.039 16.36 October 2015 19.68 4.036 15.64 November 2015 16.30 (9) 3.787 12.51 December 2015 14.77 (n) 3.741 11.03
- e. There were 5 days in the month during which no surface water withdrawals occurred.
RBG-47773 Page 7 of 7
- f. There were 19 days in the month during which no surface water withdrawals occurred.
- g. There were 4 days in the month during which no surface water withdrawals occurred.
- h. There were 5 days in the month during which no surface water withdrawals occurred.
RBS Surface Water Withdrawals and Blowdown Discharges (2016)
MonthNear Withdrawals Blowdown Consumption (Average MGD) (Average MGD) (MGD)
January 2016 6.16 (I) 2.873 3.29 February 2016 12.97 3.755 9.22 March 2016 18.29 3.952 14.34 April 2016 20.90 4.001 16.90 May 2016 21.52 4.159 17.36 June 2016 11.07(J) 3.966 7.10 July 2016 22.29 4.226 18.06 August 2016 22.29 4.211 18.08 September 2016 21.83 4.126 17.70 October 2016 20.90 3.995 16.91 November 2016 19.97 3.827 16.14 December 2016 19.48 3.610 15.87
- i. There were 18 days in the month during which no surface water withdrawals occurred.
- j. There were 15 days in the month during which no surface water withdrawals occurred.
Attachment 2 to RBG-47773 RBS Calculation No. 6247.547-604-014 (55 pages)
Page 1 of 55 RIVER BEND SDDF STATION SUPPLIERS DOCUMENT DATA FORM (1) DOCUMENT NO.
6247.547-604-014, Rev. 000 (3) VENDOR CODE: (4) VENDOR NAME S981 Structural Integrity (5) Document Title Structural Integrity Calculation associated with Adequacy of Cycles Being Tracked For Fatigue Monitoring (6) VENDOR DOC. NO.: (7) SH. NO. (8) REV.
1401192.301 000 (9) REFERENCES (9) REFERENCES (10) KEYWORDS (10) KEYWORDS Fatigue FatiguePro Software (11) PREPARER KCN DATE See AS for Electronic Signature See AS (12) SUPERVISOR KCN DATE See AS for Electronic Signature See AS (13) COMMENTS:
Original Issue of this SDDF was Generated by EC-63155.
ATTACHMENT 9.1 VENDOR DOCUMENT REVIEW STATUS Sheet 1 of 1 ENTERGY NUCLEAR MANAGEMENT MANUAL EN-DC-149 VENDOR DOCUMENT REVIEW STATUS FOR ACCEPTANCE FOR INFORMATION IPEC JAF PLP PNPS ANO GGNS RBS W3 NP Document No.: 6247.547-604-014 Rev. No.000 Document Title: Structural Integrity Calculation associated with Adequacy of Cycles Being Tracked For Fatigue Monitoring EC No.: 63155 Purchase Order No. N/A (N/A for NP)
STATUS NO:
- 1. ACCEPTED, WORK MAY PROCEED
- 2. ACCEPTED AS NOTED RESUBMITTAL NOT REQUIRED, WORK MAY PROCEED
- 3. ACCEPTED AS NOTED RESUBMITTAL REQUIRED
- 4. NOT ACCEPTED Acceptance does not constitute approval of design details, calculations, analyses, test methods, or materials developed or selected by the supplier and does not relieve the supplier from full compliance with contractual negotiations.
Responsible Engineer Jordan Carter / See AS See AS Print Name Signature Date Engineering Supervisor Paul Matzke / See AS See AS Print Name Signature Date EN-DC-149 REV 10
File No.: 1401192.301 Project No.: 1401192 CALCULATION PACKAGE Quality Program Type: Nuclear Commercial PROJECT NAME:
LRA Support CONTRACT NO.:
10448988 CLIENT: PLANT:
Entergy Operations, Inc. River Bend Station (RBS)
CALCULATION TITLE:
Adequacy of Cycles Being Tracked For Fatigue Monitoring Project Manager Preparer(s) &
Document Affected Revision Description Approval Checker(s)
Revision Pages Signature & Date Signatures & Date 0 1 - 53 Initial Issue Keith R. Evon Keith R. Evon
[KRE] 2/9/16 [KRE] 2/9/16 Minji Fong
[MF] 2/9/16 Page 1 of 53 F0306-01R2
Table of Contents 1.0 OBJECTIVE .................................................................................................................. 5 2.0 METHODOLOGY ........................................................................................................ 5 3.0 TRANSIENT REVIEW................................................................................................. 5 3.1 Cycle Counting and Cycle Based Fatigue Report ............................................. 5 3.2 Reactor Pressure Vessel (RPV) Thermal Cycle Diagram (TCD) ...................... 7 3.3 Reactor Pressure Vessel (RPV) Nozzle Thermal Cycle Diagrams (TCDs) ...... 8 3.3.1 Recirculation Outlet........................................................................................... 9 3.3.2 Recirculation Inlet ............................................................................................. 9 3.3.3 Steam Outlet....................................................................................................... 9 3.3.4 Feedwater .......................................................................................................... 9 3.3.5 Drain ................................................................................................................ 13 3.3.6 Head Cooling Spray ........................................................................................ 13 3.3.7 Low Pressure Core Spray (LPCS) ................................................................... 13 3.3.8 High Pressure Core Spray (HPCS) ................................................................. 13 3.3.9 Control Rod Drive Hydraulic System Return (CRDHSR) Nozzle ................... 14 3.3.10 Instrumentation Nozzle .................................................................................... 14 3.3.11 Core Differential Pressure & Liquid Control (CDP&LC) .............................. 14 3.3.12 Control Rod Drive (CRD) Nozzle .................................................................... 14 3.3.13 Jet Pump Diffuser ............................................................................................ 17 3.3.14 Low Pressure Coolant Injection (LPCI) .......................................................... 18 3.4 Class 1 Piping Thermal Cycle Diagrams (TCDs)............................................ 18 3.4.1 Main Steam Supply System & RPV Vent Lines ................................................ 18 3.4.2 RCIC Pump Turbine System Steam Line (RCIC) ............................................ 19 3.4.3 Feedwater System (FWS) ................................................................................. 22 3.4.4 Main Steam Isolation Valve Drain Piping (DTM) .......................................... 23 3.4.5 LPCI Injection Lines (RHR) ............................................................................ 24 3.4.6 RHR Suction Piping ......................................................................................... 26 3.4.7 Reactor Water Cleanup (RWCU) and Drain Piping ....................................... 27 3.4.8 Standby Liquid Control (SLC) Piping ............................................................. 28 3.4.9 Reactor Core Isolation Cooling (RCIC) Head Spray Piping .......................... 30 3.4.10 Low Pressure Core Spray (LPCS) Piping ....................................................... 31 3.4.11 High Pressure Core Spray (HPCS) Piping ..................................................... 32 3.4.12 Recirculation Piping ........................................................................................ 34 3.5 USAR Design Transients ................................................................................. 35 File No.: 1401192.301 Page 2 of 53 Revision: 0 F0306-01R2
3.6 Class MC Penetrations ..................................................................................... 47
4.0 CONCLUSION
S AND DISCUSSION ....................................................................... 48
5.0 REFERENCES
............................................................................................................ 50 List of Tables Table 1: Transients Counted ..................................................................................................... 6 Table 2: Transients Shown on RPV TCD................................................................................. 8 Table 3: Transients Shown on Feedwater Nozzle TCD ......................................................... 12 Table 4: Transients Shown on Head Cooling Spray Nozzle TCD ......................................... 13 Table 5: Transients Shown on CRD Nozzle TCD .................................................................. 17 Table 6: Transients Shown on Main Steam Supply System & RPV Vent Lines Histogram . 19 Table 7: Transients Shown on RCIC Pump Turbine System Steam Line Histogram ............ 21 Table 8: Transients Shown on FWS Histogram ..................................................................... 22 Table 9: Transients Shown on DTM Histogram..................................................................... 24 Table 10: Transients Shown on RHR Histograms .................................................................. 25 Table 11: Transients Shown on RHR Suction Histograms .................................................... 26 Table 12: Transients Shown on RWCU and Drain Piping Histograms.................................. 28 Table 13: Transients Shown on SLC Piping Histograms ....................................................... 29 Table 14: Transients Shown on RCIC Head Spray Piping Histograms ................................. 30 Table 15: Transients Shown on LPCS Piping Histograms ..................................................... 31 Table 16: Transients Shown on HPCS Piping Histograms .................................................... 33 Table 17: Transients Shown on Recirculation Piping Histogram .......................................... 34 Table 18: USAR Section 3.9.1.1.1B (CRD Transients) ......................................................... 36 Table 19: USAR Section 3.9.1.1.2B (CRD Housing and Incore Housing Transients) .......... 37 Table 20: USAR Section 3.9.1.1.3B (Hydraulic Control Unit Transients) ............................ 38 Table 21: USAR Section 3.9.1.1.4B (Core Support and Reactor Internals Transients) ......... 38 Table 22: USAR Section 3.9.1.1.5B (Main Steam System Transients) ................................. 39 Table 23: USAR Section 3.9.1.1.6B (Recirculation System Transients) ............................... 40 Table 24: USAR Section 3.9.1.1.7B, Table 3.9B-1 (Reactor Assembly Transients) ............. 41 Table 25: USAR Section 3.9.1.1.8B (Main Steam Isolation Valve Transients) .................... 42 Table 26: USAR Section 3.9.1.1.9B (Safety/Relief Valve Transients) .................................. 43 Table 27: USAR Section 3.9.1.1.10B (Recirculation Flow Control Valve Transients) ......... 44 Table 28: USAR Section 3.9.1.1.11B (Recirculation Pump Transients)................................ 45 Table 29: USAR Section 3.9.1.1.12B (Recirculation Gate Valve Transients) ....................... 46 File No.: 1401192.301 Page 3 of 53 Revision: 0 F0306-01R2
Table 30: Transients Required For Fatigue Monitoring ......................................................... 49 List of Figures Figure 1. Feedwater Nozzle Safe End Designs ...................................................................... 11 Figure 2. CRD Housing and Thermal Sleeve Configuration .................................................. 16 Figure 3. Penetration ASME Code Class Regions ................................................................. 47 Figure 4. Steel Containment Stress Evaluation Locations...................................................... 48 File No.: 1401192.301 Page 4 of 53 Revision: 0 F0306-01R2
1.0 OBJECTIVE The objective of this calculation package is to prepare a list of transients that should be tracked for fatigue monitoring purposes at River Bend Station.
2.0 METHODOLOGY The cycle counting and cycle-based fatigue report for River Bend Station [1] contains the list of transients that are counted. The transients identified in the cycle counting report [1] are compared with the transients identified in documents that define the design basis transients for the components in the fatigue management program to provide assurance that all applicable transients are identified.
Documents that define the design basis transients are:
o Reactor pressure vessel (RPV) thermal cycle diagrams [3].
o RPV thermal cycle diagrams for power uprate [4].
o RPV nozzle thermal cycle diagrams [5].
o Piping system histograms [6].
o Updated safety analysis report (USAR) for RBS [2]
Faulted or emergency events are not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
3.0 TRANSIENT REVIEW Design basis transients are defined in RPV thermal cycle diagrams [3] [4], nozzle thermal cycle diagrams [5], piping thermal cycle diagrams [6], and the updated safety analysis report (USAR) [2].
Cycle counts and fatigue usage are tracked using FatiguePro [8]. The transients tracked for cycle counts and locations for which fatigue usage is calculated are defined in Reference [1]. The latest update to cycle counts and fatigue usage is contained in Reference [7]. In the following subsections, design basis documents are reviewed to determine if all design transients are being tracked. For those design transients not being tracked, a determination is made whether that transient should be added to the monitoring program.
3.1 Cycle Counting and Cycle Based Fatigue Report Table 1 lists the transients that are counted [1] and [7, Table 3].
File No.: 1401192.301 Page 5 of 53 Revision: 0 F0306-01R2
Table 1: Transients Counted No. FatiguePro Transient Name(14) Allowable Cycles Counting Method 1 Boltup 123 Manual 2 Design Hydrotest 50(1) Automatic
- Leak Check (to 400 psig) 360 Automatic 3 Startup 120 Automatic 4 Turbine Roll 120 Automatic 8 Turbine Bypass 10 Automatic 9 Partial FW Heater Bypass 70 Automatic 10 & 11 Scram (Includes Turbine Generator Trip (10) and Other Scrams (11)) 180 Automatic 13 Power Reduction to Zero 111 Automatic 14 Hot Standby 111 Automatic 15 & 17 Shutdown (initial and final cooldowns) 111 Automatic 16 Vessel Floodup 111 Automatic 18 Unbolt 123 Manual 20 Loss of Feedpumps 10 Automatic 21 Blowdown Scram 8 Automatic 23 Automatic Blowdown 1(2) Manual 27 Pipe Rupture 1(3) Manual
-(4) LPCS Injection 10(5) Automatic
-(6) HPCS Injection 40(7) Automatic
-(8) RCIC Injection 181(9) Automatic
-(10) SLC Injection 10(11) Manual
-(12) LPCI Injection to Vessel (3 separate events) 10/nozzle(13) Automatic LPCI A Injection 10 Automatic LPCI B Injection 10 Automatic LPCI C Injection 10 Automatic SRV Actuation 1800 Automatic Notes:
(1) Reference [3] indicates 40 cycles for fatigue evaluation and an additional 10 that can occur without being evaluated for fatigue [3, note 2].
(2) This is classified as an emergency condition for the reactor pressure vessel [3] but is evaluated for fatigue at various piping locations [1, Section 4].
(3) This is classified as a faulted condition for the reactor pressure vessel [3] but is evaluated for fatigue at various piping locations [1, Section 4].
(4) Occurs during startup or shutdown [5, sheet 7].
(5) The design number of cycles is indicated on Reference [5, sheet 7]. One additional injection is indicated to occur during a pipe rupture which is a faulted condition [3, sheet 2, event 27] that is counted.
(6) Can occur at any time during rated power normal operation [5, sheet 7] or during a loss of feedpumps event.
(7) The design number of cycles is indicated on Reference [5, sheet 7]. Ten (10) injections at rated power normal operation are indicated along with three (3) injections for every loss of feedpumps event. The total number of design cycles is therefore 10 + 3 x 10 = 40. One additional injection is indicated to occur during a pipe rupture which is a faulted condition [3, sheet 2, event 27] that is counted.
(8) Can occur during shutdown, loss of feedpumps, or normal operation [5, sheet 6].
(9) The design number of cycles is indicated on Reference [5, sheet 6]. One (1) injection is indicated for each shutdown, three (3) injections for each loss of feedpump, and forty (40) injections during normal operation. The total number of design cycles is therefore 111 + 3 x 10 + 40 = 181.
(10) Can occur at any time [5, sheet 9].
(11) The design number of cycles is indicated on Reference [5, sheet 9].
(12) Postulated to occur during startup or shutdown [5, sheet 12]. The automatic cycle counting logic will count these transients regardless of when they occur.
File No.: 1401192.301 Page 6 of 53 Revision: 0 F0306-01R2
(13) The design number of cycles is indicated on Reference [5, sheet 12]. Each nozzle will be affected by an injection through that nozzle only, therefore each nozzle is designed for 10 cycles.
(14) Normal operation and zero load state are tracked but are load states for which there arent an allowable number of cycles. Zero load state is used in the fatigue calculation for the HPCS/LPCS nozzle [1, Section 3.3] and RPV support skirt [1, Section 3.6] and therefore is required for the fatigue management program.
3.2 Reactor Pressure Vessel (RPV) Thermal Cycle Diagram (TCD)
The RPV thermal cycle diagrams show the design basis events for the RPV for original licensed power
[3] and power uprate [4]. The events shown on the RPV TCD are listed in Table 2. The last column in Table 2 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add). Of the events shown, twelve are not counted. Seven of the twelve events not counted are emergency or faulted events which are not required to be analyzed in the design basis fatigue analyses and therefore not required to be counted. Four of the twelve events (Nos. 5, 6, 7, and 19) not counted show no thermal or pressure change on the RPV TCD and therefore are not required to be counted. The last event, 50% Maximum Seismic Loadings, that is not counted is an upset seismic event which should be added to the transient cycle counting.
File No.: 1401192.301 Page 7 of 53 Revision: 0 F0306-01R2
Table 2: Transients Shown on RPV TCD No. Event Name Design Cycles Type Counted?
1 Bolt Up 123(1) Normal 2 Design Hyd Test 50(2) Normal
- Leak Check (to 400 psig) 360(3) Normal 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Reduction 75% 10,000 Normal Not Required(4) 6 Weekly Reduction 50% 2,000 Normal Not Required(4) 7 Rod Pattern Change 400 Normal Not Required(4) 8 Turbine Trip with 100% Steam Bypass 10 Upset 9 Partial Feedwater Heater Bypass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On 40 Upset 11 Scram - Other Scrams 140 Upset 12 Rated Power Normal Operation [4, note 8] Normal Not Required(4)
- 50% Maximum Seismic Loadings (5)
Upset Add
- 100% Maximum Seismic Loadings (6)
Faulted Not Required 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal 15 Shut Down (initial cooldown at 100°F/hr) 111 Normal 16 Vessel Flooding 111 Normal 17 Shut Down (final cooldown at 100°F/hr) 111 Normal 18 Unbolt 123(1) Normal 19 Refueling --- Normal Not Required(4) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary 10 Upset Power & Turbine Generator Trip Without Bypass 21 Turbine By-pass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Recirc Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Each of the 123 cycles is the complete cycle of operations required for installation or removing the vessel top head.
(2) References [3] and [4] indicates 40 cycles for fatigue evaluation and an additional 10 that can occur without being evaluated for fatigue [3, note 2] [4, note 2].
(3) Leak checks at 400 psig prior to power operation, 3 cycles/start up [3, note 10] [4, note 10].
(4) No thermal or pressure change is indicated.
(5) The occurrence of 50% maximum seismic loadings under event (12) conditions is an upset event.
(6) The occurrence of 100% maximum seismic loadings under event (12) conditions is a faulted event.
3.3 Reactor Pressure Vessel (RPV) Nozzle Thermal Cycle Diagrams (TCDs)
The RPV nozzle thermal cycle diagrams show the design basis events for the RPV nozzles if they have a thermal profile different from the RPV [5]. There are twelve sheets, each covering a different nozzle.
When the event for a nozzle is the same as the RPV it is not shown on the nozzle TCD (See Section 3.2 for events shown on the RPV TCD). The events shown on the nozzle TCDs will be reviewed in this section. The following subsections will cover the individual sheets.
File No.: 1401192.301 Page 8 of 53 Revision: 0 F0306-01R2
3.3.1 Recirculation Outlet The recirculation outlet nozzle TCD [5, Sheet 1] shows one event with a thermal profile different from the RPV, No. 24. As already indicated in Table 2, event 24 is an emergency event and therefore not required to be counted.
3.3.2 Recirculation Inlet The recirculation inlet nozzle TCD [5, Sheet 2] shows one event with a thermal profile different from the RPV, No. 25, which is an emergency event, see Table 2, and therefore not required to be counted. It also shows event numbers 14 to 17, which are counted, with a thermal profile different from the RPV.
Events 18 and 19 are shown but do not show a thermal change and therefore are not required to be counted for this nozzle.
3.3.3 Steam Outlet The steam outlet nozzle TCD [5, Sheet 3] does not show any events with a thermal profile different from the RPV.
3.3.4 Feedwater The feedwater nozzle TCD [5, Sheets 4 and 5] shows all events as having a thermal profile different from the RPV. The events shown on the feedwater nozzle TCD are listed in Table 3. The last column in Table 3 indicates whether the event is counted (), is not required to be counted (Not required), or should be added to the event cycle counting (Add). One event, rod pattern change, is not counted.
There is one feedwater nozzle that is different than the rest as it is a tuning fork design (see Figure 1)
[14] rather than a triple sleeve (see Figure 1) [15].
The fatigue evaluation for the tuning fork design is contained in Reference [14]. Reference [14, Table 4-1] indicates that rod pattern change, daily reduction, and weekly reduction were lumped together and evaluated as the most severe of the three transients which is the weekly reduction. The three transients are grouped together in family number 7 [14, Table 5-1] for fatigue analysis. Fatigue results for normal and upset events are presented in Reference [14, Sheets 67 to 69]. Based on those results, family 7 which contains rod pattern change does not show up as specifically contributing to fatigue for location A which is the only location for which detailed fatigue results are presented. The second highest location, location B, has a total usage slightly less than location A. Because this event is only expected to occur quarterly [24], and the analyzed number of cycles is 12,400 [14, Table 5-1, family 7] due to lumping with transients that will not occur (RBS is not a load following plant), there is sufficient margin between the anticipated number of cycles (240) and the analyzed number of cycles (12,400) such that tracking of this event is not required.
File No.: 1401192.301 Page 9 of 53 Revision: 0 F0306-01R2
The fatigue evaluation for the triple sleeve design is contained in Reference [15]. Reference [15, sheet 26] indicates that rod pattern change, daily reduction, and weekly reduction were lumped together and evaluated as the most severe of the three transients which is the weekly reduction. The three transients are grouped together in family number 3 [15, sheet 93] for fatigue analysis. Fatigue results are presented in Reference [15, Sheets 222 to 252]. Reference [15, Sheet 79] presents the normal and upset stress analysis cases which abbreviates the weekly reduction transient as WR15.0 and WR50.0 for the cooldown and heatup portions of the transient. The total number of cycles analyzed for the WR15.0 and WR50.0 stress analysis cases is the summation of daily reduction, weekly reduction, and rod pattern change. Even with the conservative methodology applied, point 228 [15, Sheet 225] is the only location for which load cases WR15.0 or WR50.0 contribute to fatigue. Since the rod pattern change is conservatively accounted for as a weekly reduction transient and still only contributes 0.00005
[15, Sheet 225] to fatigue at one location, there is no need to count the transient for the nozzle with the triple sleeve design.
It is also noted that the feedwater nozzles are monitored for fatigue using stress based fatigue methodology [35].
File No.: 1401192.301 Page 10 of 53 Revision: 0 F0306-01R2
Triple Sleeve Design Tuning Fork Design Figure 1. Feedwater Nozzle Safe End Designs File No.: 1401192.301 Page 11 of 53 Revision: 0 F0306-01R2
Table 3: Transients Shown on Feedwater Nozzle TCD No. Event Name Design Cycles Type Counted?
1 Bolt Up 123 Normal 2 Design Hyd Test 50(1) Normal
- Leak Check (to 400 psig) 360(2) Normal 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Reduction 75% 10,000 Normal Not Required(3) 6 Weekly Reduction 50% 2,000 Normal Not Required(3) 7 Rod Pattern Change 400 Normal Not Required(6) 8 Turbine Trip with 100% Steam Bypass 10 Upset 9 Partial Feedwater Heater Bypass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On 40 Upset 11 Scram - Other Scrams 140 Upset 12 Rated Power Normal Operation [4, note 8] Normal Not Required(5) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal 15 Shut Down (initial cooldown at 100°F/hr) 555(4) Normal 16 Vessel Flooding 111 Normal 17 Shut Down (final cooldown at 100°F/hr) 111 Normal 18 Unbolt 123 Normal 19 Refueling --- Normal Not Required(5) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary 10 Upset Power & Turbine Generator Trip Without Bypass 21 Turbine By-pass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Recirc Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) References [3] and [4] indicate 40 cycles for fatigue evaluation and an additional 10 that can occur without being evaluated for fatigue [3, note 2] [4, note 2].
(2) Leak checks at 400 psig prior to power operation, 3 cycles/start up [3, note 10] [4, note 10].
(3) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(4) The TCD indicates 5 cycles during the first 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> of shutdown for a total of 555 cycles (111x5).
(5) No thermal or pressure change is indicated.
(6) A rod pattern change occurs on a scheduled basis quarterly [24] and therefore would occur 240 times over a 60 year lifetime. Since rod pattern change was lumped with daily and weekly reduction for fatigue analysis (see Section 3.3.4 discussion), and those transients dont apply since RBS is not a load following plant, there is sufficient margin between the anticipated number of cycles (240) and the analyzed number of cycles (12,400) such that tracking of this event is not required.
File No.: 1401192.301 Page 12 of 53 Revision: 0 F0306-01R2
3.3.5 Drain The drain nozzle TCD [5, Sheet 6] does not show any events with a thermal profile different from the RPV.
3.3.6 Head Cooling Spray The head cooling spray nozzle TCD [5, Sheet 6] shows events 15 to 20 as having a thermal profile different from the RPV (See Table 4). The last column in Table 4 indicates whether the event is counted
(), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
There are no events shown on the head cooling spray nozzle TCD that require addition to the fatigue monitoring program.
Table 4: Transients Shown on Head Cooling Spray Nozzle TCD No. Transient Name Design Cycles Type Counted?
- RCIC Injection 181(1) Normal 15 Shut Down (initial cooldown at 100°F/hr) (2)
Normal 16 Vessel Flooding (2)
Normal 17 Shut Down (final cooldown at 100°F/hr) (2)
Normal 18 Unbolt (2)
Normal 19 Refueling (2)
Normal Not Required(3) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary (2) (4)
Upset Power & Turbine Generator Trip Without Bypass Notes:
(1) See Table 1, note 9. Also note that RCIC was rerouted to the feedwater system [36].
(2) See Table 2.
(3) No thermal or pressure change is indicated.
(4) The TCD for this nozzle shows three injections for every event 20. The actual number of RCIC injections during any event is tracked separately, see the first row of this table.
3.3.7 Low Pressure Core Spray (LPCS)
The LPCS nozzle TCD [5, Sheet 7] shows event 27 as having a thermal profile different from the RPV and 10 cycles of LPCS injection that can occur during start up (event 3) or shutdown (events 15 to 18).
Since event 27 is a faulted event, it does not require counting. As shown in Table 1, LPCS injection is a counted transient with an allowable of 10. There are no events shown on the LPCS nozzle TCD that require addition to the fatigue monitoring program.
3.3.8 High Pressure Core Spray (HPCS)
The HPCS nozzle TCD [5, Sheet 7] shows events 20, 27, and 10 cycles of HPCS injection that can occur at any time during rated power normal operation having a thermal profile different from the RPV. Since event 27 is a faulted event, it does not require counting. Event 20 is a counted event. As shown in Table 1, HPCS injection is a counted transient with an allowable of 40 which accounts for the 10 during rated power normal operation and 30 (3 injections per event) during event 20. There are no events shown on the HPCS nozzle TCD that require addition to the fatigue monitoring program.
File No.: 1401192.301 Page 13 of 53 Revision: 0 F0306-01R2
3.3.9 Control Rod Drive Hydraulic System Return (CRDHSR) Nozzle The CRDHSR nozzle TCD [5, Sheet 8] indicates that for nozzles that have been capped there are no transients that have a thermal profile different from the RPV. The RBS updated safety analysis report (USAR) [2, Chapter 4.6.1.1.2.4.2.4] indicates that the CRDHSR has been capped and there are therefore no transients shown on the CRDHSR nozzle TCD that require addition to the fatigue monitoring program.
3.3.10 Instrumentation Nozzle The instrumentation nozzle TCD [5, Sheet 9] indicates that event 2 has a thermal profile different from the RPV. Since event 2 is counted, there are no events shown on the instrumentation nozzle TCD that require addition to the fatigue monitoring program.
3.3.11 Core Differential Pressure & Liquid Control (CDP&LC)
The CDP&LC nozzle TCD [5, Sheet 9] indicates that event 19 has a thermal profile different from the RPV and that liquid control system operation can occur during normal operation. Since event 19 is only shown as a 20°F change, the event is insignificant and does not require counting. Liquid control system operation is a counted transient, see SLC injection in Table 1. There are no events shown on the CDP&LC nozzle TCD that require addition to the fatigue monitoring program.
3.3.12 Control Rod Drive (CRD) Nozzle The control rod drive nozzle TCD [5, Sheet 10] shows multiple events having a thermal profile different from the RPV. The events shown on the CRD nozzle TCD are listed in Table 5. The last column in Table 5 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
There are two events for the control rod drive nozzle that are postulated to occur during rated power normal operation. The two events are C. R. Drive Isolation at Rated Power Normal Operation and Single C.R.D. Scram. In the thermal analysis of this component, the CRD isolation event was selected as a limiting transient [10, sheet 10 of T5]. The single CRD scram event was not listed as a transient
[10, sheets 10 to 13 of T5] but was referred to as one of the events which had a 2.3 second change in temperature which would not affect the CRD housing [10, sheet 27 of T5]. This is due to the fact that the transient only lasts for 2.3 seconds [10, sheet 27 of T5] and occurs between the control rod drive and innermost thermal sleeve as seen in Figure 2 [10, sheet 4 of T5]. Single CRD Scram therefore has no effect on the analyzed CRD tube and does not require tracking.
In the subsequent stress analysis, CRD isolation was analyzed as cases 5, 6, and 7 [11, sheet 11 of S5].
Stress results for what were determined to be limiting transients are presented in the stress analysis [11].
In the fatigue analysis, all cycles were lumped together with 50 cycles of CRD drive isolation and 10 cycles of single CRD scram included in the lumping of cycles [12, sheet 4 of F5]. Two locations were File No.: 1401192.301 Page 14 of 53 Revision: 0 F0306-01R2
evaluated for fatigue [12, sheet 5 of F5], point 185 which is an SB-166 location and point 504 which is an SA508 Class II location. The worst stress pairing was used to evaluate all cycles.
While CRD isolation is a severe event for this location, it is not an event that is expected to occur with any frequency [32] and therefore does not require tracking.
File No.: 1401192.301 Page 15 of 53 Revision: 0 F0306-01R2
Figure 2. CRD Housing and Thermal Sleeve Configuration File No.: 1401192.301 Page 16 of 53 Revision: 0 F0306-01R2
Table 5: Transients Shown on CRD Nozzle TCD No. Event Name Design Cycles Type Counted?
1 Bolt Up (1)
Normal 2 Design Hyd Test (1)
Normal 3 Start Up (1)
Normal 4 Turbine Roll (Increase to Rated Power) (1)
Normal
- Leak Check (to 400 psig) (1)
Normal 5 Daily Reduction 75% (1)
Normal Not Required(2) 6 Weekly Reduction 50% (1)
Normal Not Required(2) 7 Rod Pattern Change (1)
Normal Not Required(2) 8 Turbine Trip with 100% Steam Bypass (1)
Upset 9 Partial Feedwater Heater Bypass (1)
Upset 10 Scram - Turbine Generator Trip Feedwater On (1)
Upset 11 Scram - Other Scrams (1)
Upset 12 Rated Power Normal Operation (1)
Normal Not Required(2)
- C. R. Drive Isolation at Rated Power Normal Operation 50 Normal Not Required(3)
- Single C.R.D. Scram 10 Normal Not Required(4) 13 Reduction to 0% Power (1)
Normal 14 Hot Stand-by (1)
Normal 15 Shut Down (initial cooldown at 100°F/hr) (1)
Normal 16 Vessel Flooding (1)
Normal 17 Shut Down (final cooldown at 100°F/hr) (1)
Normal 18 Unbolt (1)
Normal 19 Refueling 300 Normal Not Required(5) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary (1)
Upset Power & Turbine Generator Trip Without Bypass 21 Turbine By-pass Single Relief or Safety Valve Blowdown (1)
Upset 22 Reactor Overpressure with Delayed Scram, Feedwater (1)
Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown (1)
Emergency Not Required 24 Improper Start of Cold Recirc Loop (1)
Emergency Not Required 25 Sudden Start of Pump in Cold Recirc Loop (1)
Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart (1)
Emergency Not Required 27 Pipe Rupture & Blow down (1)
Faulted Not Required Notes:
(1) See Table 2.
(2) No thermal or pressure change is indicated.
(3) While CRD isolation is a severe event for this location, it is not an event that is expected to occur with any frequency [32] and therefore does not require tracking.
(4) See Section 3.3.12 discussion.
(5) Since only a 10°F temperature change is shown and the transient only lasts 2.3 seconds, this event is insignificant from a thermal stress standpoint. Mechanical loads and resulting stresses [11, sheets 11, 12, and 96 to 102 of S5]
would occur but would not be significant enough by themselves to result in any fatigue usage. This event therefore does not require counting.
3.3.13 Jet Pump Diffuser The jet pump diffuser TCD [5, Sheet 11] indicates that events 15 to 19 and 25 have a thermal profile different from the RPV. Events 15 to 18 are counted, see Table 1 and Table 2. Since event 19 is shown File No.: 1401192.301 Page 17 of 53 Revision: 0 F0306-01R2
at a constant temperature, the event is insignificant and does not require counting. Event 25 is an emergency event, see Table 2. There are no events shown on the jet pump diffuser TCD that require addition to the fatigue monitoring program.
3.3.14 Low Pressure Coolant Injection (LPCI)
The low pressure coolant injection (LPCI) nozzle TCD [5, Sheet 12] indicates that event 27 has a thermal profile different from the RPV and that injections can occur during start up or shut down. The injections during start up or shut down are counted, see Table 1 events LPCI A Injection, LPCI B Injection, and LPCI C Injection. Event 27 is a faulted event. There are no events shown on the low pressure coolant injection nozzle TCD that require addition to the fatigue monitoring program.
3.4 Class 1 Piping Thermal Cycle Diagrams (TCDs)
The Class 1 piping thermal and pressure histograms show the design basis events for the Class 1 piping for original licensed power [6]. References [6.a] to [6.aa] are the histograms for individual Class 1 piping systems. The following subsections will cover the individual sheets.
3.4.1 Main Steam Supply System & RPV Vent Lines The main steam histogram [6.a] [6.b] shows multiple unique events. The events shown on the main steam histogram are listed in Table 6. The last column in Table 6 indicates whether the event is counted
(), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
The shutdown vessel flooding event for the main steam piping was split into a normal and alternate type with the alternate being more severe. The fatigue tracking for main steam locations conservatively accounts for both event types when a vessel flooding event occurs [1, Sections 4.4, 4.8, and 4.13] [13].
To reduce conservatism, separate tracking of the normal and alternate vessel flooding events could be implemented.
File No.: 1401192.301 Page 18 of 53 Revision: 0 F0306-01R2
Table 6: Transients Shown on Main Steam Supply System & RPV Vent Lines Histogram No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360 Normal 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated) 120 Normal 5 Daily Reduction 75% 10,000 Normal Not Required(1) 6 Weekly Reduction 50% 2,000 Normal Not Required(1) 7 Rod Pattern Change 400 Normal Not Required(1) 8 Turbine Trip 100% Steam By-pass N/A(2) Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 & 11 Scram - Turbine Generator Trip Feedwater On Isolation 190 Upset Valves Stay Open & Other Scram 12 Rated Power Normal Operation N/A(3) Normal Not Required(1) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal 15 Shut Down Vessel Flooding 111 Normal 16 Shutdown Vessel Flooding Case A 91 Normal 17 Shutdown Vessel Flooding Case B 20 Normal Not Required(4) 17 Shut Down (final cooldown at 100°F/hr) 111 Normal 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(1) 20 Composite Loss of Feedwater Loss of Auxiliary Power & 10 Upset Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stays Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) No thermal or pressure change is indicated.
(2) Histogram indicates that this event is not applicable to RBS.
(3) The histogram does not indicate a number of cycles.
(4) The cycle counting doesnt distinguish between case A and case B. Case B is more severe. Fatigue tracking [1, Sections 4.4, 4.8, and 4.13] [13] accounts for both cases when vessel flooding occurs which is conservative. To reduce conservatism, separate tracking of the normal and alternate vessel flooding events could be implemented.
3.4.2 RCIC Pump Turbine System Steam Line (RCIC)
The RCIC steam system histogram [6.c] shows multiple unique events. The events shown on the main steam histogram are listed in Table 7. The last column in Table 7 indicates whether the event is counted
(), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
There are alternate, more severe, cases of shutdown and vessel flooding events that are counted. A review of the stress report [16] for this piping indicates that the alternate, more severe, events do have File No.: 1401192.301 Page 19 of 53 Revision: 0 F0306-01R2
more of a fatigue impact and were analyzed for 20 cycles. An example of this is for Valve 50 [16, p.
2086 to 2087] which has a load pair with 20 cycles (E, 6-16) which shows up higher in the fatigue table than a load pair with 91 cycles (E, 8-14). The cycle counting doesnt distinguish between case A and case B. Case B is more severe. Similar to other locations already tracked for fatigue, all cycles of this type should be assumed to be of the more severe type if fatigue tracking is performed for this location.
File No.: 1401192.301 Page 20 of 53 Revision: 0 F0306-01R2
Table 7: Transients Shown on RCIC Pump Turbine System Steam Line Histogram No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360 Normal 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated) 120 Normal 5 Daily Reduction 75% 10,000 Normal Not Required(1) 6 Weekly Reduction 50% 2,000 Normal Not Required(1) 7 Rod Pattern Change 400 Normal Not Required(1) 8 Turbine Trip 100% Steam By-pass N/A(2) Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 50 Upset Valves Stay Open 11 Other Scrams 140 Upset 12 Rated Power Normal Operation N/A(3) Normal Not Required(1) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal 15 Shut Down - (Initial Phase) with RCIC Head Spray - 111(4) Normal Case A and Case B 16 Vessel Flooding Case A 91 Normal 16 Vessel Flooding Case B 20 Normal Not Required(5) 17 Shut Down - Case A 91 Normal 17 Shut Down - Case B 20 Normal Not Required(5) 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(1) 20 Composite Loss of Feedwater Loss of Auxiliary Power & 10 Upset Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required 28 Rated Power Accidental Trip and RCIC 40 Upset Not Required(1) 29 RCIC System Test 480 Upset Not Required(1)
Notes:
(1) No thermal or pressure change is indicated.
(2) Histogram indicates that this event is not applicable to RBS.
(3) The histogram does not indicate a number of cycles.
(4) The histogram shows 91 cycles of Case A and 20 cycles of Case B. Since both transients are represented identically on the histogram, Case A and Case B do not require separate tracking.
(5) The cycle counting doesnt distinguish between case A and case B. Case B is more severe. Similar to other locations already tracked for fatigue, all cycles of this type should be assumed to be of the more severe type if fatigue tracking is performed for this location.
File No.: 1401192.301 Page 21 of 53 Revision: 0 F0306-01R2
3.4.3 Feedwater System (FWS)
The FWS histogram [6.d] shows multiple unique events. The events shown on the FWS histogram are listed in Table 8. The last column in Table 8 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add). There are alternate forms of events which are not explicitly counted but which are accounted for in the fatigue formulas for the monitored feedwater system locations [1] [13]. There are no unique events for the feedwater system that require addition to the fatigue monitoring program.
Table 8: Transients Shown on FWS Histogram No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360 Normal 3 Start Up 105 Normal 3 Alternate Start Up RPV-RWCU Heatup 15 Normal Not Required(1) 4 Turbine Roll (Increase to Rated) 105 Normal 4 Alternate Turbine Roll 15 Normal Not Required(1) 5 Daily Power Reduction 10,000 Normal Not Required(2) 6 Weekly Power Reduction 2,000 Normal Not Required(2) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass N/A(4) Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 40 Upset Valves Stay Open 11 Other Scrams 140 Upset 12 Rated Power Normal Operation 12,800(8) Normal Not Required(7) 13 Reduction to 0% Power 111 Normal 14A Hot Stand-by Case A 96 Normal Not Required(1) (5) 14B Hot Stand-by Case B 15 Normal (5) 15A Shut Down Initiation Case A 96 Normal 15B Shut Down Initiation Case B 15 Normal (6) 16A Vessel Flooding Case A 96 Normal 16B Vessel Flooding Case B 15 Normal Not Required(1) 17A Shut Down - Case A 91 Normal 17B Shut Down - Case B 20 Normal Not Required(1) 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(7) 20 Composite Loss of Feedwater Loss of Auxiliary Power & 10 Upset Turbine Trip Without Bypass
- RCIC Injection (During Loss of Feedwater) 30(9) Upset 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
File No.: 1401192.301 Page 22 of 53 Revision: 0 F0306-01R2
(1) The cycle counting doesnt distinguish between the normal and alternate cases. Two limiting locations in this system are monitored [1] with the first having an allowable usage of 0.1 and the second having an allowable usage of 1.0 [1, Table 4-1]. Loads due to normal and alternate event types are accounted for in the cycle based fatigue calculations for feedwater piping locations [1] [13].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) Rod pattern change is accounted for in the cycle based fatigue calculations for feedwater piping locations [1] [13].
(4) Histogram indicates that this event is not applicable to RBS.
(5) The cycle counting counts a hot standby when feedwater flow is cycled. Case A does not involve feedwater flow cycling and is not counted [6.d, event no. 14-A].
(6) Event 15B involves feedwater flow cycling and is monitored as combined with Event 14B [1, p. 2-16].
(7) No thermal or pressure change is indicated.
(8) Since RCIC was rerouted to feedwater [36], a spurious injection resulting in an insignificant transient in feedwater loop A is also included in the design transients during normal operation [37, PICL No. AP-17, Attachment A, p. 7].
(9) Thirty (30) RCIC injections [37, PICL No. AP-17, Attachment A] into the FW system during loss of FW are accounted for since the reroute.
3.4.4 Main Steam Isolation Valve Drain Piping (DTM)
The DTM histogram [6.e] shows multiple unique events. The events shown on the DTM histogram are listed in Table 9. The last column in Table 9 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
File No.: 1401192.301 Page 23 of 53 Revision: 0 F0306-01R2
Table 9: Transients Shown on DTM Histogram No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360 Normal 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction to 75% 10,000 Normal Not Required(1) 6 Weekly Power Reduction to 50% 2,000 Normal Not Required(1) 7 Rod Pattern Change 400 Normal Not Required(2) 8 Turbine Trip 100% Steam By-pass N/A(3) Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 50 Upset Valves Stay Open 11 Other Scrams 140 Upset 12 Rated Power Normal Operation N/A(4) Normal Not Required(2) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (2) 15 Shut Down Vessel Flooding 111 Normal 16 Vessel Flooding Case A 91 Normal 17 Vessel Flooding Case B 20 Normal Not Required(5) 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(2) 20 Composite Loss of Feedwater Loss of Auxiliary Power & 10 Upset Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(2) No thermal or pressure change is indicated.
(3) Histogram indicates that this event is not applicable to RBS.
(4) Histogram indicates that a number of cycles is not applicable.
(5) The cycle counting doesnt distinguish between the normal and alternate cases. For every vessel flooding event, the normal and alternate loads are conservatively accounted for [1, Section 4.4] [13, Appendix C] so the alternate case does not require counting.
3.4.5 LPCI Injection Lines (RHR)
The RHR histograms [6.f] [6.g] [6.h] show multiple events. The events shown on the RHR histogram are listed in Table 10. The last column in Table 10 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
File No.: 1401192.301 Page 24 of 53 Revision: 0 F0306-01R2
Table 10: Transients Shown on RHR Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360 Normal 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction to 75% 10,000 Normal Not Required(1) 6 Weekly Power Reduction to 50% 2,000 Normal Not Required(1) 7 Rod Pattern Change 400 Normal Not Required(2) 8 Turbine Trip 100% Steam By-pass 10 Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 40 Upset Valves Stay Open 11 Other Scrams 140 Upset 12-1 Rated Power Normal Operation with Leak 10 Normal Not Required(3) 12-2 Rated Power Normal Operation with Pump Test 500 Normal Not Required(2) 12-3 Monthly Injection Valve Test 500 Normal Not Required(2) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (2) 15A Shut Down - Blowdown to the Condenser & RHR 106 Normal Initiation Case A 15B Shut Down - Blowdown to the Condenser & RHR 5 Normal Not Required(4)
Initiation Case B 16 Vessel Flooding 111 Normal (5) 17 Shutdown 111 Normal (5) 18 Unbolt 123 Normal 19 Refueling RHR Pump Test 100 Normal Not Required(6) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary 10 Upset Power & Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(2) No thermal or pressure change is indicated.
(3) This is the largest contributor to fatigue at one location [1, Section 4.3] [13, Appendix B] and ten are assumed to have occurred already in fatigue monitoring for that location. Because this event has never occurred and it isnt expected to occur in the future [31], assuming the design basis number of cycles is sufficient for 60 years of operation and this event therefore does not require tracking.
(4) The cycle counting doesnt distinguish between the normal and alternate cases. The fatigue analysis for this piping treated the normal and alternate events types as the same severity so separate counting of the alternate event is not required [13, Appendices B and D].
(5) The histogram shows 106 cycles of the normal case and 5 cycles of an alternate case. Since both transients are represented identically on the histogram, the two cases do not require separate tracking.
File No.: 1401192.301 Page 25 of 53 Revision: 0 F0306-01R2
(6) The histogram indicates a transient with a temperature delta of only 30°F. In addition, the event does not show up as contributing to fatigue and therefore does not require counting [1, Sections 4.3 and 4.5] [13, Appendices B and D].
3.4.6 RHR Suction Piping The RHR suction histograms [6.i] [6.j] [6.k] show multiple events. The events shown on the RHR suction histograms are listed in Table 11. The last column in Table 11 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
Table 11: Transients Shown on RHR Suction Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360 Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction to 75% 10,000 Normal Not Required(2) 6 Weekly Power Reduction to 50% 2,000 Normal Not Required(2) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass 10 Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 40 Upset Valves Stay Open 11 Other Scrams 140 Upset 12 Rated Power Normal Operation - Normal Not Required(4) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (4) 15A Shut Down - Early Blowdown to the Condenser & RHR 91(5) Normal (5)
Initiation Case A 15B Shut Down - Early Blowdown to the Condenser & RHR 20(5) Normal Not Required(5)
Initiation Case B 16 Vessel Flooding 111(6) Normal (6) 17 Shutdown 111(6) Normal (6) 18 Unbolt 123(7) Normal (7) 19 Refueling 40 Normal Not Required(4) 20 Composite Loss of Feedwater Pumps Including Loss of 10 Upset Auxiliary Power & Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
File No.: 1401192.301 Page 26 of 53 Revision: 0 F0306-01R2
(1) Leak checks at 400 psig prior to startup and power operation (listed under the startup transient in [6.i]), 3 cycles/start up [3, note 10] [4, note 10].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal change is indicated and only a 30 psi pressure change is indicated.
(4) No thermal or pressure change is indicated.
(5) The histograms show 91 cycles of Case A and 20 cycles of Case B. The cycle counting doesnt distinguish between the normal and alternate cases. Since Case A is more severe, accounting for all events as Case A is conservative and counting of the alternate case is not required.
(6) The histograms show 91 cycles of Case A and 20 cycles of Case B. Since both transients are represented identically on the histograms, Case A and Case B do not require separate tracking.
(7) [6.i] indicates 123 cycles, [6.j] [6.k] show 91 cycles of Case A and 20 cycles of Case B which do not sum to 123 cycles. Since both transients on [6.j] [6.k] are represented identically on the histograms, Case A and Case B do not require separate tracking.
3.4.7 Reactor Water Cleanup (RWCU) and Drain Piping The RWCU and Drain piping histograms [6.l] [6.m] show multiple events. The events shown on the RWCU and Drain piping histograms are listed in Table 12. The last column in Table 12 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
File No.: 1401192.301 Page 27 of 53 Revision: 0 F0306-01R2
Table 12: Transients Shown on RWCU and Drain Piping Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360(1) Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction to 75% 10,000 Normal Not Required(2) 6 Weekly Power Reduction to 50% 2,000 Normal Not Required(2) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass 10 Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater 40 Upset 11 Other Scrams 140 Upset 12A Rated Power Normal Operation - RWCU Pumps On - Normal Not Required(4) 12B Rated Power Normal Operation - RWCU System Trip 250 Add 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal 15 Shut Down - Shut-Down Initiate 111 Normal 16 Shut Down - Vessel Flooding 111 Normal 17 Shut Down - Shutdown Complete 111 Normal 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(4) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary 10 Upset Power & Turbine Trip Without Bypass 21 Turbine Bypass Single SRV Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Recirc Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to startup and power operation (listed under the startup transient in [6.l] [6.m]), 3 cycles/start up [3, note 10] [4, note 10].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal change is indicated and only a 30 psi pressure change is indicated.
(4) No thermal or pressure change is indicated.
3.4.8 Standby Liquid Control (SLC) Piping The SLC histograms [6.n] [6.o] [6.p] show multiple events. The events shown on the SLC histograms are listed in Table 13. The last column in Table 13 indicates whether the event is counted (), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
File No.: 1401192.301 Page 28 of 53 Revision: 0 F0306-01R2
Table 13: Transients Shown on SLC Piping Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360(1) Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction 10,000 Normal Not Required(2)(3) 6 Weekly Power Reduction 2,000 Normal Not Required(2)(3) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass N/A Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 50 Upset Valves Stay Open 11 Other Scrams 140 Upset 12A Rated Power Normal Operation - Normal Not Required(3) 12B-C Rated Power Normal Operation - SLC Injection 10 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (3) 15 Shut Down - Vessel Flooding 111 Normal 16 Vessel Flooding 111 Normal 17 Shut Down 111 Normal 18 Unbolt 123 Normal 19 Refueling - SLC Injection 40 Normal Not Required(4) 20 Composite Loss of Feedwater Loss of Auxiliary Power & 10 Upset Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to startup and power operation (listed under the startup transient in [6.n]), 3 cycles/start up [3, note 10] [4, note 10].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal or pressure change is indicated.
(4) An injection during a refueling outage is postulated but only involves a 20°F temperature change and no pressure change. The injection is therefore insignificant from a thermal transient standpoint. Activation of the system is key locked and therefore highly unlikely to occur accidentally [25, Section 3.2.1]. Technical specification surveillance 3.1.7.8 requires demonstration that the SLC system can inject the proper amount of water into the RPV every 2 years
[26]. This is accomplished via STP-201-6601 [27]. Even if it was assumed that the test is performed every 18 months, the design basis number of cycles (40) would not be exceeded for a 60 year plant life [26].
File No.: 1401192.301 Page 29 of 53 Revision: 0 F0306-01R2
3.4.9 Reactor Core Isolation Cooling (RCIC) Head Spray Piping The RCIC histograms [6.q] [6.r] [6.s] [6.t] show multiple events. The events shown on the RCIC histograms are listed in Table 14. The last column in Table 14 indicates whether the event is counted
(), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
Table 14: Transients Shown on RCIC Head Spray Piping Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360(1) Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated PWR) 120 Normal 5 Daily Power Reduction to 75% 10,000 Normal Not Required(2)(3) 6 Weekly Power Reduction to 50% 2,000 Normal Not Required(2)(3) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass N/A Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 50 Upset Valves Stay Open 11 Other Scrams 140 Upset 12A Rated Power Normal Operation 40 Normal Not Required(3) 12B-C Rated Power - Accidental Trip - RCIC Injection 40 Normal (4) 13 Reduction to 0% Power 111 Normal (3) 14 Hot Stand-by 111 Normal 15 Shut Down - RCIC Injection 111 Normal (4) 16 Shutdown Vessel Flooding 111 Normal 17 Shutdown Vessel Flooding 111 Normal 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(3) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary 10(4) Upset (4)
Power & Turbine Trip Without Bypass - RCIC Injection 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to startup and power operation (listed under the startup transient in [6.q] [6.r] [6.s]
[6.t]), 3 cycles/start up [3, note 10] [4, note 10].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal or pressure change is indicated.
(4) [6.q] [6.r] [6.s] [6.t] define three RCIC injections per Loss of FW Pumps, 40 RCIC injections during normal operation, and one injection during shutdown (See note 9 in Table 1).
File No.: 1401192.301 Page 30 of 53 Revision: 0 F0306-01R2
3.4.10 Low Pressure Core Spray (LPCS) Piping The LPCS histograms [6.u] [6.v] [6.w] show multiple events. The events shown on the LPCS histograms are listed in Table 15. The last column in Table 15 indicates whether the event is counted
(), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
Table 15: Transients Shown on LPCS Piping Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360(1) Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction 10,000 Normal Not Required(2)(3) 6 Weekly Power Reduction 2,000 Normal Not Required(2)(3) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass 10 Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 40 Upset Valves Stay Open 11 Other Scrams 140 Upset 12A Normal Operation with Leak 10 Normal Not Required(4) 12B Normal Operation with Pump 500 Normal Not Required(3) 12C Normal Operation - Monthly Injection Test 500 Normal Not Required (5) 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (3) 15A Shut Down - Normal 101 Normal 15B Shutdown - LPCS Injection 10 Normal 16 Shutdown - Flooding 111 Normal 17 Shutdown - Flooding 111 Normal 18 Unbolt 123 Normal 19 Refueling - Pump Test 40 Normal Not Required(6) 20 Composite Loss of Feedwater Pumps, Loss of Auxiliary 10 Upset Power & Turbine Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down - LPCS Injection 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to startup and power operation (listed under the startup transient in [6.u] [6.v] [6.w]), 3 cycles/start up [3, note 10] [4, note 10].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal or pressure change is indicated.
(4) This event has never occurred and it isnt expected to occur in the future [30]. Assuming the design basis number of cycles is sufficient for 60 years of operation and this event therefore does not require tracking.
File No.: 1401192.301 Page 31 of 53 Revision: 0 F0306-01R2
(5) No thermal transient is indicated, however a pressure transient is present for event 12C indicating system pressurization and depressurization. Per Reference [22, Section 4.2.2], the injection shutoff valve is not permitted to open unless the reactor pressure is less than or equal to 487 psig. Injection test at full reactor pressure therefore cannot occur and does not require tracking.
(6) Although this is a very minor thermal transient, it is one of the lowest temperatures reached by this system and shows up in the top load pairs in the design fatigue analysis for one bounding location [13, Appendix F]. Since this test was only performed 2 to 3 times in the past and is no longer performed [29], assuming the design basis number of cycles for 60 years of operation is conservative. This event does not require tracking.
3.4.11 High Pressure Core Spray (HPCS) Piping The HPCS histograms [6.x] [6.y] [6.z] show multiple events. The events shown on the HPCS histograms are listed in Table 16. The last column in Table 16 indicates whether the event is counted
(), is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
File No.: 1401192.301 Page 32 of 53 Revision: 0 F0306-01R2
Table 16: Transients Shown on HPCS Piping Histograms No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360(1) Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction to 75% 10,000 Normal Not Required(2)(3) 6 Weekly Power Reduction to 50% 2,000 Normal Not Required(2)(3) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass 10 Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 40 Upset Valves Stay Open 11 Other Scrams 140 Upset 12A-1 Injection Valve Leaks 10 Normal Not Required(4) 12A-2 Motor Operated Pump Test 500 Normal Not Required(3) 12A-3 Motor Operated Injection Valve test 500 Normal Not Required(5) 12A-4 HPCS Pump Accidental On 10 Normal 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (3) 15 Shutdown Vessel Flooding 111 Normal 16 Shutdown Vessel Flooding 111 Normal 17 Shutdown Vessel Flooding 111 Normal 18 Unbolt 123 Normal 19-1 Normal Refuel 20 Normal Not Required(3) 19-2 Refuel Pump Trip 20 Normal Not Required(6) 20 Composite Loss of Feedwater Loss of Auxiliary Power & 10(7) Upset Turbine Trip Without Bypass - HPCS Injection 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down - HPCS Injection 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to startup and power operation (listed under the startup transient in [6.x] [6.y] [6.z]), 3 cycles/start up [3, note 10] [4, note 10].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal or pressure change is indicated.
(4) Only one of these events has occurred to date and the projected number of cycles is therefore expected to stay well below the design number of cycles of 10 [28].
(5) A large pressure transient is indicated for Region C. The usage for location 199 [19], which is in Region C, is affected by this transient. This valve is only tested during cold shutdown so this transient will not occur [28].
(6) This is not an event that will occur frequently and it does not affect the bounding Node 45 location [13, Appendix A]
within this piping system. It therefore does not require tracking.
(7) [6.x] [6.y] [6.z] define three HPCS injections per Loss of FW Pumps.
File No.: 1401192.301 Page 33 of 53 Revision: 0 F0306-01R2
3.4.12 Recirculation Piping The recirculation histogram [6.aa] shows multiple events. The events shown on the recirculation histogram are listed in Table 17. The last column in Table 17 indicates whether the event is counted (),
is not required to be counted (Not Required), or should be added to the event cycle counting (Add).
Table 17: Transients Shown on Recirculation Piping Histogram No. Event Name Design Type Counted?
Cycles 1 Bolt Up 123 Normal 2 Design Hydro Test 40 Normal
- Leak Check (to 400 psig) 360(1) Normal (1) 3 Start Up 120 Normal 4 Turbine Roll (Increase to Rated Power) 120 Normal 5 Daily Power Reduction 75% 10,000 Normal Not Required(2) 6 Weekly Power Reduction 50% 2,000 Normal Not Required(2) 7 Rod Pattern Change 400 Normal Not Required(3) 8 Turbine Trip 100% Steam By-pass 10 Upset 9 Partial Feedwater Heater By-pass 70 Upset 10 Scram - Turbine Generator Trip Feedwater On Isolation 40 Upset Valves Stay Open 11 Other Scrams 140 Upset 12 Rated Power Normal Operation 111 Normal Not Required(3)
- Rated Power Normal Operation - RWCU System Trip 250(4) Normal Add 13 Reduction to 0% Power 111 Normal 14 Hot Stand-by 111 Normal (3) 15 Shutdown Vessel Flooding 111 Normal 16 Shutdown Vessel Flooding 111 Normal 17 Shutdown Vessel Flooding 111 Normal 18 Unbolt 123 Normal 19 Refueling 40 Normal Not Required(3) 20 Composite Loss of Feedwater Pumps Loss of Auxiliary 10 Upset Power & Turbine Generator Trip Without Bypass 21 Turbine Bypass Single Relief or Safety Valve Blowdown 8 Upset 22 Reactor Overpressure with Delayed Scram, Feedwater 1 Emergency Not Required Stays On, Isolation Valves Stay Open 23 Automatic Blowdown 1 Emergency Not Required 24 Improper Start of Cold Recirc Loop 1 Emergency Not Required 25 Sudden Start of Pump in Cold Loop 1 Emergency Not Required 26 Hot Standby-Drain Shut-Off - Pump Restart 1 Emergency Not Required 27 Pipe Rupture & Blow down 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to startup and power operation, 3 cycles/start up [6.aa, note 5].
(2) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(3) No thermal or pressure change is indicated.
(4) 250 RWCU system trips are assumed to occur during rated power normal operation [6.aa, note 7]
File No.: 1401192.301 Page 34 of 53 Revision: 0 F0306-01R2
3.5 USAR Design Transients USAR Appendix 6A [2] contains the containment dynamic loading assessment. USAR Appendix A, Section 6A.16.2.5, indicates that total SRV discharges are split into 1500 single and 300 multiple discharges. It is therefore recommended that the counting of SRV actuations be split into single and multiple categories.
Safe shutdown (SSE) and operational basis (OBE) seismic events are list in USAR Appendix A [2], Table 6A.15-1 for the containment system. One SSE and five OBE events are assumed to occur in a 40 year plant life with 20 cycles per event assumed. OBE events are tracked and SSE is an emergency type event.
Location specific transients are listed in the USAR [2, Sections 3.9.1.1.1.1 through 3.9.1.1.1.12 and Table 3.9-1]. The Tables within this calculation list the location specific transients and correlate them to counted transients listed in Table 1 when possible. If a matching counted transient cannot be determined, an explanation is provided in the table.
File No.: 1401192.301 Page 35 of 53 Revision: 0 F0306-01R2
Table 18: USAR Section 3.9.1.1.1B (CRD Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles
- 1. Reactor startup/shutdown 120 normal/upset Startup (3), Shutdown (13-17), and Blowdown Scram (21)
- 2. Vessel pressure tests 130 normal/upset Design Hydrotest (2)
- 3. Vessel overpressure 10 normal/upset See Note 1
- 4. Scram tests 140 normal/upset See Note 1
- 5. Startup scrams 160 normal/upset See Note 1
- 6. Operational scrams 300 normal/upset Turbine Generator Trip (10), Other Scrams (11), Shutdown (13-17), and Blowdown Scram (21)
- 7. Jog cycles 30,000 normal/upset See Note 1.
- 8. Shim/drive cycles 1,000 normal/upset See Note 1
- 9. Scram with inoperative buffer 24 normal/upset See Note 1
- 10. Operating Basis Earthquake (OBE) 10 normal/upset Not counted, Add
- 11. Safe Shutdown Earthquake 1 faulted N/A, faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 12. Scram with stuck control blade 1 faulted N/A, faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 13. Control rod ejection accident 1 faulted N/A, faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
Notes:
(1) In the design basis evaluation [9], the only transients causing any amount of fatigue are Scrams (Items 4, 5, and 6 in Table 18) and the Scram w/inoperative Buffer. The analysis was performed in a conservative manner by assuming that worst case loadings occurred together and therefore assumed more cycles than specified. For instance, at the highest fatigue location [9, Sht. No. 1-8], Scrams were grouped together (Items 4, 5, and 6 in Table 18) [9, Sht. 10-6] and they were all assumed to include an inoperative buffer [9, Sht. 10-2]. The counting of Operational Scrams is therefore considered adequate to ensure that the CRD remains within the design basis from a cycle count perspective.
File No.: 1401192.301 Page 36 of 53 Revision: 0 F0306-01R2
Table 19: USAR Section 3.9.1.1.2B (CRD Housing and Incore Housing Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles
- 1. Startup and Shutdown 120 normal/upset Startup (3), Shutdown (13-17), and Blowdown Scram (21)
- 2. Design pressure tests 403 normal/upset Design Hydrotest (2), and Leak Check (-)
- 3. Loss of feedwater pumps 10 normal/upset Loss of Feedpumps (20)
- 4. Relief or safety valve blowdown 8 normal/upset Blowdown Scram (21)
- 6. Operation Basis Earthquake (OBE) 10 normal/upset Add
- 7. Safe Shutdown Earthquake (SSE) 1 Emergency/faulted N/A, faulted or emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
(1) See Note 1 of Table 18.
File No.: 1401192.301 Page 37 of 53 Revision: 0 F0306-01R2
Table 20: USAR Section 3.9.1.1.3B (Hydraulic Control Unit Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles
- 1. Reactor startup/shutdown 120 normal/upset Startup (3), Shutdown (13-17), and Blowdown Scram (21)
- 2. Scram tests 140 normal/upset (1)
- 3. Startup scrams 160 normal/upset (1)
- 4. Operational scrams 300 normal/upset Turbine Generator Trip (10), Other Scrams (11), Shutdown (13-17), and Blowdown Scram (21)
- 5. Jog cycles 30,000 normal/upset (1)
- 6. Shim/drive cycles 1,000 normal/upset (1)
- 7. Scram with stuck scram discharge valve 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 8. OBE 10 normal/upset (1)
- 9. SSE 1 faulted N/A, faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
Notes:
(1) As shown on Reference [21], the hydraulic control unit [21, H8] is a Class 2 [21, C7] component which is not subject to a Class 1 fatigue analysis. Therefore, no cycle counting is required for this location.
Table 21: USAR Section 3.9.1.1.4B (Core Support and Reactor Internals Transients)
The cycles listed in [2, Table 3.9B-1] were considered in the design and fatigue analysis for the reactor internals. Refer to Table 24 for an evaluation of those transients.
File No.: 1401192.301 Page 38 of 53 Revision: 0 F0306-01R2
Table 22: USAR Section 3.9.1.1.5B (Main Steam System Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles
- 1. Hydrotest 40 test Design Hydrotest (2)
- 2. Leaktest 360 Test Leak Check (-)
- 3. Startup 120 normal Startup (3)
- 4. Turbine trip 10 upset Turbine Bypass (8)
- 5. Scram and trip isolation valves open 40 upset Turbine Generator Trip (10)
- 7. Shutdown 111 normal Shutdown (13-17)
- 8. Loss of feedwater pumps isolation valves 10 upset Loss of Feedpumps (20) closed
- 9. Turbine bypass single relief of safety 8 upset Blowdown Scram (21) valve
- 10. Reactor over pressure delayed scram 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 11. Automatic blowdown 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 12. Operating basis earthquake (OBE) 50 upset/normal Add
- 13. Turbine stop valve closure (TSV) 600 upset This event is a short duration pressure pulse that occurs during other transients and is therefore accounted for already as a part of other transients.
- 14. Relief valve lift (RVL) 5433 upset SRV Actuation File No.: 1401192.301 Page 39 of 53 Revision: 0 F0306-01R2
Table 23: USAR Section 3.9.1.1.6B (Recirculation System Transients)
USAR Transient Name Design Cycles Type Counted Transient(s) (Transient #)?
- 1. Hydrotest 40 test Design Hydrotest (2)
- 2. Startup 120 normal Startup (3)
- 3. Turbine trip 10 upset Turbine Bypass (8)
- 4. Partial feedwater heater bypass 70 upset Partial FW Heater Bypass (9)
- 5. Turbine generator trip F.W. on isolation valves open 40 upset Turbine Generator Trip (10)
- 7. Shutdown 111 normal Shutdown (13-17)
- 8. Loss of feedwater pumps isolation valves closed 10 upset Loss of Feedpumps (20)
- 9. Turbine bypass single S/RV blowdown 8 upset Blowdown Scram (21)
- 10. Reactor over pressure with delayed scram 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 11. Automatic blowdown 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 12. Operating basis earthquake (OBE) 50 upset/normal Add
- 13. Single Loop Operation 25 normal Not Required(1)
Notes:
(1) See Table 28, Note 3.
File No.: 1401192.301 Page 40 of 53 Revision: 0 F0306-01R2
Table 24: USAR Section 3.9.1.1.7B, Table 3.9B-1 (Reactor Assembly Transients)
No. Event Name Design Cycles Type Counted?
1 Bolt Up 123 Normal 2 Design Hyd Test 40 Normal 2a Leak Check (to 400 psig) 360(1) Normal 3 Startup 120 Normal 4 Daily Reduction 75% 10,000 Normal Not Required 5 Weekly Reduction 50% 2,000 Normal Not Required 6 Rod Pattern Change 400 Normal Not Required 7 Loss of feedwater heaters (80 cycles total) 80 Upset 8 50% safe shutdown earthquake event at rate operating 10/50(2) Upset Add conditions 9a Scram: Turbine generator trip, feedwater on, isolation 40 Upset valves stay open 9b Scram: Other scrams 140 Upset 9c Scram: Loss of feedwater pumps, isolation valves closed 10 Upset 9d Scram: Turbine bypass, single safety or relief valve 8 Upset blowdown 10 Reduction to 0% power, hot standby, shutdown 111 Normal 11 Unbolt 123 Normal 12 Single Loop Operation (Recirculation) 25 Upset Not Required(3) 13a Reactor overpressure with delayed scram, feedwater stays 1 Emergency Not Required on, isolation valves stay open 13b Automatic blowdown 1 Emergency Not Required 14 Improper start of cold recirculation loop 1 Emergency Not Required 15 Sudden start of pump in cold recirculation loop 1 Emergency Not Required 16 Hot standby with reactor drain shut off followed by pump 1 Emergency Not Required restart 17 Pipe rupture and blowdown 1 Faulted Not Required 18 Safe shutdown earthquake at rated operating conditions 1 Faulted Not Required 19 Safe shutdown earthquake during refueling 1 Faulted Not Required Notes:
(1) Leak checks at 400 psig prior to power operation, 3 cycles/startup [2, Table 3.9B-1].
(2) Fifty peak OBE cycles for NSSS piping, 10 peak OBE cycles for other NSSS equipment and components.
(3) See Table 28, Note 3.
File No.: 1401192.301 Page 41 of 53 Revision: 0 F0306-01R2
Table 25: USAR Section 3.9.1.1.8B (Main Steam Isolation Valve Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles 1a. Heating cycle @ 100°F/hr 300 normal/upset Startup (3), Turbine Generator Trip (10), and Other Scrams (11) 1b. Cooling cycle @ 100°F/hr 300 normal/upset Turbine Generator Trip (10), Other Scrams (11), Shutdown (13-17), and Blowdown Scram (21) 1c. 29°F between 70°F and 552°F 600 normal/upset Not explicitly counted, but is part of transients 1a and 1b (1) 1d. 50°F step change between 70°F and 200 normal/upset Not explicitly counted, but is part of transients 1a and 1b (1) 552°F
- 2. Loss of feedwater pump/MSLIV 10 normal/upset Loss of Feedpumps (20) closure
- 3. Single relief valve blowdown 8 normal/upset Blowdown Scram (21)
- 4. Reactor overpressure with delayed 1 emergency N/A, emergency event not required to be included in design basis fatigue scram evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 5. Automatic and blowdown (ADS) 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 6. Pipe rupture and blowdown 1 faulted N/A, faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
Notes:
(1) These small temperature fluctuations would have an insignificant impact on fatigue. The reported fatigue usage (It) for this component is 0.0168 [2, Table 3.9B-2h, Item Number 1.11].
File No.: 1401192.301 Page 42 of 53 Revision: 0 F0306-01R2
Table 26: USAR Section 3.9.1.1.9B (Safety/Relief Valve Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles
- 1. Heating and cooldown - within the 300 normal/upset Startup (3), Turbine Generator Trip (10), Other Scrams (11), Shutdown (13-17),
temperature limits of 70°F and 552°F at a and Blowdown Scram (21) rate of 100°F/hr
- 2. Small temperature changes- of 29°F 600 normal/upset Not explicitly counted, but is part of transient 1 (1)
(either increase or decrease) at any temperature between the limits of 70°F and 552°F
- 3. 50°F temperature changes- (either 200 normal/upset Not explicitly counted, but is part of transient 1 (1) increase or decrease) at any temperature between the limits of 70°F and 552°F
- 4. Loss of feedwater pumps, isolation 10 normal/upset Loss of Feedpumps (20) valve closure
- 5. Turbine bypass, single relief or safety 8 normal/upset Blowdown Scram (21) valve blowdown (temperature drops from 552°F to 375°F in 10 minutes
- 6. Reactor overpressure with delayed 1 emergency N/A, emergency event not required to be included in design basis fatigue scram evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 7. Automatic blowdown 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 8. Pipe rupture and blowdown 1 faulted N/A, faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
9a. Hydrotests to 1045 psig at 100°F 120 testing Design Hydrotest (2) 9b. Steam line flooding during plant 120 other Vessel Floodup (16) shutdown Notes:
(1) These small temperature fluctuations would have an insignificant impact on fatigue. The reported fatigue usage (It) for this component is 0.0003 [2, Table 3.9B-2g].
File No.: 1401192.301 Page 43 of 53 Revision: 0 F0306-01R2
Table 27: USAR Section 3.9.1.1.10B (Recirculation Flow Control Valve Transients)
USAR Transient Name Design Type Counted Transient(s) (Transient #)?
Cycles
- 1. Startup (100°F/hr heatup rate 70°F to 300 normal/upset Startup (3), Turbine Generator Trip (10), and Other Scrams (11) design temperature)
- 2. Small temperature changes (29°F 600 normal/upset Not explicitly counted, but is part of transient 1 (1) step)
- 3. 50°F step changes 200 normal/upset Not explicitly counted, but is part of transient 1 (1)
- 4. Safety/relief valve blowdowns (single 8 normal/upset Blowdown Scram (21) valve)
- 5. Safety valve transient (110% of 1 normal/upset Since there is only one design cycle specified, it is assumed that this is an design pressure) emergency event which does not require counting.
6a. Installed hydrotest, 1300 psig 130 testing Design Hydrotest (2) 6b. Installed hydrotest, 1670 psig 3 testing Hydrostatic Test (Not counted, only occurs during original plant fabrication and startup)
- 7. Automatic blowdown 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 8. Improper start of pump in cold loop 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
Notes:
(1) These small temperature fluctuations would have an insignificant impact on fatigue. The reported fatigue usage (It) for this component is 0.0018 [2, Table 3.9B-2f, Item Number 1.10].
File No.: 1401192.301 Page 44 of 53 Revision: 0 F0306-01R2
Table 28: USAR Section 3.9.1.1.11B (Recirculation Pump Transients)
USAR Transient Name Design Cycles Type Counted Transient(s) (Transient #)?
- 1. Bolt up 123 normal-upset Bolt up (1)
- 2. Design hydrotest 40 testing Design Hydrotest (2)
- 3. Startup, turbine roll and increase to rated power 120 normal-upset Startup (3), Turbine Roll (4)
- 4. Daily power reduction - 75% 10,000 normal+upset Not required(1) (2)
- 5. Weekly power reduction - 50% 2,000 normal+upset Not required(1) (2)
- 6. Rod pattern change 400 normal+upset Not Required(2)
- 7. Loss of feedwater heaters 80 normal+upset Turbine Bypass (8), Partial FW Heater Bypass (9)
- 9. Special normal operation transients 20 normal+upset Not Required(3)
- 10. Shutdown 111 normal+upset Shutdown (13-17)
- 11. Unbolt 123 normal+upset Unbolt (18)
- 13. Scram - turbine bypass single relief or safety relief valve 8 normal+upset Blowdown Scram (21) blowdown
- 14. Reactor overpressure 1 emergency N/A(4)
- 15. Scram - Automatic blowdown 1 emergency N/A(4)
- 16. Improper start of pump in cold loop 2 emergency N/A(4)
- 17. Improper startup with reactor drain shutoff 1 emergency N/A(4)
- 18. Pipe rupture and blowdown 1 faulted N/A(4)
Notes:
(1) Daily and weekly power reductions are associated with load following. Since RBS is not a load-following unit, these transients do not apply [34].
(2) No pressure or temperature change is shown for these events [17].
(3) This event is associated with single recirculation loop operation as specified in the pressure temperature cycles [17] for the recirculation pump [18, Table 1.3-1]
where the recirculation suction and discharge valves are closed [17, Note 13]. Since those valves are not kept closed long enough for the recirculation line to cool off [20, Section 5.9] and the idle loop is kept within 50°F of the running loop, this transient will never occur.
(4) Emergency or faulted event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
File No.: 1401192.301 Page 45 of 53 Revision: 0 F0306-01R2
Table 29: USAR Section 3.9.1.1.12B (Recirculation Gate Valve Transients)
USAR Transient Name Design Type(1) Counted Transient(s) (Transient #)?
Cycles
- 1. 70°F-575°F-70°F of 100°F/hr 300 normal/upset Startup (3), Turbine Generator Trip (10), Other Scrams (11)
- 2. +/-29°F between limits of 70°F and 600 normal/upset Not explicitly counted, but is part of transient 1 (2) 575°F
- 3. +/-50°F between limits of 70°F and 200 normal/upset Not explicitly counted, but is part of transient 1 (2) 575°F
- 4. 552°F to 375°F, in 10 min 8 normal/upset Blowdown Scram (21)
- 5. 552°F to 281°F, in 22.3 min 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 6. 100°F to 552°F, in 15 sec 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 7. 110% of design pressure at 575°F 1 emergency N/A, emergency event not required to be included in design basis fatigue evaluations due to the low probability that one will occur. If one of these events does occur then the fatigue contribution will have to be evaluated.
- 8. 1300 psi at 100°F installed hydrostatic 130 test Design Hydrotest (2) test
- 9. 1670 psi at 100°F installed hydrostatic 3 test Hydrostatic Test (Not counted, only occurs during original plant fabrication and test startup)
Notes:
(1) USAR section 3.9.1.1.12B does not provide a category (referred to as type in this table) for the transients listed. The type of transient is determined based on similarity to transients listed in USAR table 3.9.1.1.10B.
(2) These small temperature fluctuations would have an insignificant impact on fatigue. The reported fatigue usage (It) is 0.0023 [2, Table 3.9B-2j, Item Number 1.10] for the gate valve on the suction side of the recirculation pump and 0.0012 [2, Table 3.9B-2j, Item Number 1.10] for the gate valve on the discharge side of the recirculation pump.
File No.: 1401192.301 Page 46 of 53 Revision: 0 F0306-01R2
3.6 Class MC Penetrations Penetrations at RBS have usage calculations performed according to Class 1 and ASME Code Class MC rules. The boundary between the Class 1 and Class MC region is shown in Figure 3 [23, p. 21]. The fatigue analysis for the Class 1 portion of the penetration is included in the fatigue analysis for the piping system to which it is attached [23, p. 37 and Attachment E] and the cycles to be tracked have already been evaluated in Section 3.4 of this calculation. The thermal cycle diagrams for the Class MC portion are defined in the USAR [23, pp. 224, C2] and the cycles to be tracked have already been evaluated in Section 3.5 of this calculation. The steel containment has an additional leakage rate test that is specified as being performed 3 times in every 10 years at 7.6 psig [23, p. 225] for a total of 13 cycles. As shown in Figure 4 [23, p. 238], six cuts through the steel containment were evaluated for stress. Cuts 1 and 6 were determined to be bounding from a fatigue standpoint [23, p. 237]. Cut 1 has a usage of 0.014 and the fatigue contribution due to the leakage rate test is 13 / 489647 = 0.00003 [23, p. 386]. Cut 6 has negligible usage [23, p. 532]. Since the usage contribution due to leakage rate test is so small, it does not require tracking. In addition, the leakage rate test occurs once every 10 years at the most [33] so assuming 13 cycles in the fatigue analyses is sufficient for a 60 year operating period.
Figure 3. Penetration ASME Code Class Regions File No.: 1401192.301 Page 47 of 53 Revision: 0 F0306-01R2
Figure 4. Steel Containment Stress Evaluation Locations
4.0 CONCLUSION
S AND DISCUSSION Table 30 presents the results of the review performed in Section 3.0 of this calculation. Transients listed in Table 30 are either already tracked automatically (Automatic), already tracked manually (Manual), or require addition to the fatigue monitoring program (Add).
File No.: 1401192.301 Page 48 of 53 Revision: 0 F0306-01R2
Table 30: Transients Required For Fatigue Monitoring No. FatiguePro Transient Name Allowable Cycles Tracking Status 1 Boltup 123 Manual 2 Design Hydrotest 50 Automatic
- Leak Check (to 400 psig) 360 Automatic 3 Startup 120 Automatic 4 Turbine Roll 120 Automatic 8 Turbine Bypass (Turbine Trip with 100% Steam Bypass) 10 Automatic 9 Partial FW Heater Bypass 70 Automatic 10 & 11 Scram (Includes Turbine Generator Trip (10) and Other Scrams (11)) 180 Automatic 50% Maximum Seismic Loadings, Operational Basis Earthquake (OBE) 5 Add, Manual RWCU System Trip(2) 250 Add, Automatic 13 Power Reduction to Zero 111 Automatic 14 Hot Standby 111 Automatic 15 & 17 Shutdown (initial and final cooldowns) 111 Automatic 16 Vessel Floodup 111 Automatic 18 Unbolt 123 Manual 20 Loss of Feedpumps 10 Automatic 21 Blowdown Scram 8 Automatic LPCS Injection 10 Automatic HPCS Injection 40 Automatic RCIC Injection 181/30(3) Automatic SLC Injection During Normal Operation 10 Manual LPCI Injection to Vessel (3 separate events) 10/nozzle Automatic LPCI A Injection 10 Automatic LPCI B Injection 10 Automatic LPCI C Injection 10 Automatic Single SRV Actuation 1500 Automatic(1) 34 Multiple SRV Actuation 300 Automatic(1)
Notes:
(1) The automatic counting lumps single and multiple SRV actuations together. It is recommended that these be split into two categories with an allowable of 1500 for single SRV actuation and an allowable of 300 for multiple SRV actuation.
(2) See Table 12 and Table 17.
(3) RCIC was rerouted from the head spray to the feedwater system [36]. An allowable of 181 cycles applies to the time period prior to the reroute. Thirty (30) cycles of RCIC injection during Loss of Feedpumps are specified after the reroute [37, PICL No. AP-17, Attachment A]. Note that RCIC injections to feedwater during normal operation (with feedwater flowing) were deemed insignificant for the feedwater piping [37, PICL No. AP-17, Attachment A, p. 7].
File No.: 1401192.301 Page 49 of 53 Revision: 0 F0306-01R2
5.0 REFERENCES
- 1. SI Report No. SIR-95-101, Revision 2, July 2005, Cycle-Based Fatigue Report for the Transient and Fatigue Monitoring System for River Bend Station, SI File No. RBS-09Q-403 (Entergy File No. 6247.547-604-008A).
- 2. River Bend Updated Safety Analysis Report (specific sections only, not complete), SI File No.
1401192.205.
- 4. GE Drawing No. 105E2945, Revision 0, Sheets 1 and 2, Reactor Cycles River Bend 1 Power Uprate, SI File No. RBS-09Q-210 (Entergy File Nos. 0222.250-000-200 and 0222.250-000-201).
- 5. GE Drawing No. 166B7307, Revision 6, Sheets 1 to 12, Reactor Vessel Nozzle Thermal Cycles, SI File No. RBS-08Q-209 (Entergy File No. 0221.110-000-128 to 0221.110-000-139).
- 6. Piping System Histograms:
- a. 12210-SK-TR2-A-1, sheets 1 to 3, Thermal Transients for Main Steam Supply System &
RPV Vent Lines, SI File No. RBS-01Q-203.
- b. 12210-SK-TR2-A-2, sheets 1 to 3, Thermal Transients for Main Steam Supply System &
RPV Vent Lines, SI File No. RBS-01Q-203.
- c. 12210-SK-TR13-A-2, sheets 1 to 4, Thermal Transient for RCIC Pump Turbine System Steam Line (RCIC), SI File No. RBS-01Q-203.
- d. 12210-SK-TR17-A-1, sheets 1 to 5, Thermal Transients Feedwater System (FWS), SI File No. RBS-01Q-203.
- e. 12210-SK-TR31-A-2, sheets 1 to 3, Thermal Transient Main Steam Isolation Valve Drain Piping (DTM), SI File No. RBS-01Q-548.
- f. 12210-SK-TR71-A-1, sheets 1 to 4, Thermal Transients for LPCI Injection Lines (RHR)
(Region Close to RPV), SI File No. RBS-01Q-203.
- g. 12210-SK-TR71-B-1, sheet 1, Thermal Transients for LPCI Injection Lines (RHR)
(VF041 to Drywell Penetration), SI File No. RBS-01Q-203.
- h. 12210-SK-TR71-C-1, sheet 1, Thermal Transients for LPCI Injection Lines (RHR)
(Drywell Penetration to MOV F042), SI File No. RBS-01Q-203.
- i. 12210-SK-TR71-D-1, sheets 1 to 3, Thermal Transient for Shutdown Suction Line Only Residual Heat Removal System (Region Near Recirc Lines), SI File No. RBS-01Q-203.
- j. 12210-SK-TR71-E-1, sheet 1, Thermal Transient for Shutdown Suction Line Only Residual Heat Removal System (Region from Inboard Containment Isolation Valve to Penetration at Drywell Wall), SI File No. RBS-01Q-203.
- k. 12210-SK-TR71-F-1, sheet 1, Thermal Transient for Shutdown Suction Line Only Residual Heat Removal System (Region from Penetration at Drywell Wall to Outboard Containment Isolation Valve), SI File No. RBS-01Q-203.
File No.: 1401192.301 Page 50 of 53 Revision: 0 F0306-01R2
- l. 12210-SK-TR74-A-3, sheets 1 to 3, Thermal Transients for Reactor Water Cleanup Line (WCS, Regions 2 and 3), SI File No. RBS-01Q-203.
- m. 12210-SK-TR74-B-3, sheets 1 to 3, Thermal Transients for RPV Drain Line (WCS, Region 1), SI File No. RBS-01Q-203.
- n. 12210-SK-TR75-A-1, sheets 1 to 4, Thermal Transients for Standby Liquid Control System Inside Drywell Wall at RPV End, SI File No. RBS-01Q-203.
- o. 12210-SK-TR75-B-1, sheet 1, Thermal Transients for Standby Liquid Control System Inside Drywell Wall Remote from RPV, SI File No. RBS-01Q-203.
- p. 12210-SK-TR75-C-1, sheet 1, Thermal Transients for Standby Liquid Control System Outside Drywell Wall, SI File No. RBS-01Q-203.
- q. 12210-SK-TR76-A-2, sheet 1 to 3, Thermal Cycles for Reactor Core Isolation Head Spray Line (RCIC), SI File No. RBS-01Q-203.
- r. 12210-SK-TR-76A-2, sheet 1 to 2, Thermal Cycles for Reactor Core Isolation Head Spray Line (RCIC), SI File No. RBS-01Q-203.
- s. 12210-SK-TR-76A-2, sheet 1 to 2, Thermal Cycles for Reactor Core Isolation Head Spray Line (RCIC), SI File No. RBS-01Q-203.
- t. 12210-SK-TR-76B-2, sheet 1 to 2, Thermal Cycles for Reactor Core Isolation Head Spray Line (RCIC), SI File No. RBS-01Q-203.
- u. 12210-SK-TR-78-A-1, sheets 1 to 4, Thermal Transients Low Pressure Core Spray Region-1, SI File No. RBS-01Q-203.
- v. 12210-SK-TR-78-B-1, sheets 1 to 2, Thermal Transients Low Pressure Core Spray Region-2, SI File No. RBS-01Q-203.
- w. 12210-SK-TR-78-C-1, sheets 1 to 2, Thermal Transients Low Pressure Core Spray Region-3, SI File No. RBS-01Q-203.
- x. 12210-SK-TR-83-A-1, sheets 1 to 4, Thermal Transients High Pressure Core Spray System (HPCS) Region A, SI File No. RBS-01Q-203.
- y. 12210-SK-TR-83-B-1, sheets 1 to 4, Thermal Transients High Pressure Core Spray System (HPCS) Region B, SI File No. RBS-01Q-203.
- z. 12210-SK-TR-83-C-1, sheets 1 to 4, Thermal Transients High Pressure Core Spray System (HPCS) Region C, SI File No. RBS-01Q-203.
aa. 795E282, Revision 0, sheets 1 to 3, Design Basis Press/Temp Cycle Chart & Load Set Recirc Piping Sys, SI File No. RBS-01Q-224.
- 7. SI Calculation No. FP-RBS-301, Revision 0, 4/24/2014 (Entergy File No. 6247.547-604-001),
Fatigue Update for River Bend Nuclear Station using FatiguePro Software.
- 9. GE Stress Report No. 22A4912, Revision 2, 11/3/1978, Control Rod Drive, SI File No.
1401192.204 (Entergy File No. 4221.220-000-005A).
- 10. CBI Nuclear Company, VPF-3535-862-1, Revision 0, 11/21/1975, Stress Report 218 BWR-6 Section T5 Thermal Analysis CRD Penetrations, SI File No. RBS-01Q-264.
File No.: 1401192.301 Page 51 of 53 Revision: 0 F0306-01R2
- 11. CBI Nuclear Company, VPF-3535-863-2, Revision 1, 7/26/1977, Section S5 Stress Analysis Straight Through CRD 218 BWR-6, SI File No. RBS-01Q-265.
- 12. CBI Nuclear Company, VPF-3535-864-2, Revision 1, 7/26/1977, Section F5 Fatigue Analysis Straight Through CRD 218 BWR-6, SI File No. RBS-01Q-266.
- 13. SI Calculation No. RBS-01Q-318, Revision 2, 1/4/1999 (Entergy File No. 4247.547-604-016B),
Cycle-Based Fatigue Tables for Class 1 Piping Locations.
- 14. GE Certified Stress Report No. DC25A5110, Revision 0, 2/28/1992, Replacement Feedwater Safe End and Thermal Sleeve, SI File No. RBS-01Q-250 (Entergy File No. 4221.101-111-003A).
- 15. GE Stress Report No. 22A5552, Revision 1, 11/12/1980, Feedwater Nozzle Safe Ends, SI File No. RBS-01Q-251 (Entergy File No. 4221.120-000-007A).
- 16. Stone & Webster Stress Report 12210-N-SR505-0, 6/24/1985, Reactor Core Isolation Cooling and Residual Heat Removal Heat Exchanger Steam Piping System, SI File No. RBS-01Q-556.
- 17. GE Drawing 767E768, Revision 0, sheets 1 to 2, Press/Temp Cycles Recirc Loop Piping Class I, SI File No. 1401192.207 (Entergy File Nos. 0222.121-000-002 and 0222.121-000-003).
- 18. Stone & Webster Engineering Corp. Document No. 4222.111-000-002A, 7/16/1976, Stress Analysis Report on Double Volute (20x20x33 RV) Recirculation Coolant Pump, SI File No.
1401192.208.
- 19. Stone & Webster Stress Report 12210-N-SR501-0, 6/7/1985, High Pressure Core Spray System, SI File Nos. RBS-01Q-543 and RBS-01Q-552.
- 20. Entergy River Bend Station Abnormal Operating Procedure AOP-0024, Revision 028, 1/07/2016, Thermal Hydraulic Stability Controls, SI File No. 1401192.209.
- 21. Engineering P & I Diagram, LRA-PID-36-01C, Revision 0, Engineering P & I Diagram System 052 Control Rod Drive Hydraulic, SI File No. 1401192.210.
- 22. Entergy River Bend Station System Design Criteria No. SDC-205, Revision 3, 11/22/2011, Low Pressure Core Spray System Design Criteria System Number 205, SI File No. 1401192.212.
- 23. Stone & Webster Engineering Corporation Calculation No. 12210-219.710-EBC-2159, 5/10/1985, Revision 0, Stress Evaluation For Piping Penetration Z-3B, Type 12, System:
Feedwater To RPV - Loop B, SI File No. 1401192.201.
- 24. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/9/2015 11:18 AM, Sequence Exchanges, SI File No. 1401192.103.
File No.: 1401192.301 Page 52 of 53 Revision: 0 F0306-01R2
- 25. Entergy River Bend Station System Design Criteria No. SDC-201, Revision 2, 1/18/2011, Standby Liquid Control System Design Criteria System 201, SI File No. 1401192.212.
- 26. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/17/2015 3:31 PM, RE: SLC histogram that we need to evaluate for cycles, SI File No. 1401192.103.
- 27. Entergy River Bend Station Surveillance Test Procedure No. STP-201-6601, Revision 305, 4/22/2015, Standby Liquid Control System Refuel Injection Test, SI File No. 1401192.213.
- 28. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/18/2015 1:04 PM, RE: HPCS histogram transients that we need to evaluate for tracking, SI File No. 1401192.103.
- 29. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/18/2015 11:39 AM, RE: do you perform LPCS injection tests (pump refueling test identified in histogram)?, SI File No.
1401192.103.
- 30. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/18/2015 11:35 AM, LPCS normal operation with leak - site opinion if we need to track these cycles, SI File No. 1401192.103.
- 31. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/18/2015 1:47 PM, RE: RHR/LPCI histogram- one item we need to review, SI File No. 1401192.103.
- 32. Email from M. Feltner (Entergy) to S. Batch (Entergy), 9/22/2015 4:46 PM, RE: update on: new transients SIA says we need to track, SI File No. 1401192.103.
- 33. Email from S. Batch (Entergy) to K. Evon (SI), 9/17/2015 1:10 PM, once in 10 years or longer, SI File No. 1401192.103.
- 34. Email from S. Batch (Entergy) to K. Evon (SI), 10/1/2015 12:21 PM, River Bend is a Base-Load Plant, SI File No. 1401192.103.
- 35. SI Report No. SIR-95-074, Revision 2, July 2005, Transfer Function and System Logic Report for the Transient and Fatigue Monitoring System for River Bend Station, SI File No. RBS-09Q-406.
- 36. Entergy River Bend Station Modification Request No. 96-0069, 3/11/97, RCIC reroute to FW, SI File No. 1401192.216.
- 37. Entergy River Bend Station Engineering Change No. 0000018177, 11/11/2009, PICL Procedure Change, SI File No. 1401192.203.
File No.: 1401192.301 Page 53 of 53 Revision: 0 F0306-01R2