Letter Sequence RAI |
---|
CAC:MF8060, Clarify Application of Setpoint Methodology for LSSS Functions (Open) |
|
MONTHYEARGO2-16-096, License Amendment Request to Revise Operating License and Technical Specifications for Measurement Uncertainty Recapture Power Uprate2016-06-28028 June 2016 License Amendment Request to Revise Operating License and Technical Specifications for Measurement Uncertainty Recapture Power Uprate Project stage: Request ML16218A3902016-08-0808 August 2016 Supplemental Information Needed for Acceptance of Requested Licensing Action, Request for Measurement Uncertainty Recapture (Mur) Power Uprate (from 3486 Mwt to 3544 Mwt) Project stage: Acceptance Review GO2-16-124, Response to License Amendment Request, Opportunity to Supplement2016-08-18018 August 2016 Response to License Amendment Request, Opportunity to Supplement Project stage: Supplement ML16243A3662016-09-0101 September 2016 Acceptance of Requested Licensing Action Measurement Uncertainty Recapture Project stage: Acceptance Review ML16246A2812016-09-14014 September 2016 Request for Withholding Information from Public Disclosure, 6/9/16 Affidavit Executed by J. Harrison, GE-Hitachi and 6/14/16 Affidavit Executed by N. Wilmshurst, EPRI, Related to NEDC-33853P, Revision 0 Project stage: Withholding Request Acceptance ML16207A0162016-09-14014 September 2016 Request for Withholding from Public Disclosure - 5/18/16 Affidavit Executed by E. Hauser, Caldon Ultrasonics Technology Center, Cameron Engineering Report ER-1074, Revision 0 Project stage: Other ML16207A0332016-09-14014 September 2016 Request for Withholding from Public Disclosure - 5/18/16 Affidavit Executed by E. Hauser, Caldon Ultrasonics Technology Center, Cameron Engineering Report ER-1049, Revision 3 Project stage: Other ML16302A0392016-10-27027 October 2016 NRR E-mail Capture - Request for Additional Information, Columbia Mur LAR: Fire Protection Project stage: RAI ML16306A2942016-11-0101 November 2016 NRR E-mail Capture - Request for Additional Information, Columbia Mur LAR: Esgb, Coating and FAC, CAC MF8060 Project stage: RAI ML16323A1192016-11-16016 November 2016 NRR E-mail Capture - Eicb RAIs for Columbia Mur Project stage: RAI ML16327A1842016-11-22022 November 2016 NRR E-mail Capture - Non Proprietary Request for Additional Information Regarding Columbia Mur Power Uprate Project stage: RAI GO2-16-161, Response to Request for Additional Information, Columbia Mur LAR: Esgb, Coating and FAC2016-12-0808 December 2016 Response to Request for Additional Information, Columbia Mur LAR: Esgb, Coating and FAC Project stage: Response to RAI ML17006A0902017-01-0404 January 2017 NRR E-mail Capture - Non Proprietary Request for Additional Information Regarding Columbia Mur Power Uprate Project stage: RAI ML17006A0922017-01-0404 January 2017 NRR E-mail Capture - Eicb RAIs for Columbia Mur Project stage: RAI GO2-17-015, Energy Northwest - Transmittal of Response to Request for Additional Information, Columbia Mur LAR: Electrical Instrument and Controls Branch (Eicb) and Reactor Systems Branch (Srxb)2017-01-12012 January 2017 Energy Northwest - Transmittal of Response to Request for Additional Information, Columbia Mur LAR: Electrical Instrument and Controls Branch (Eicb) and Reactor Systems Branch (Srxb) Project stage: Response to RAI GO2-17-049, Response to Request for Additional Information, Columbia Mur LAR Evib Rais, Enclosure 22017-02-16016 February 2017 Response to Request for Additional Information, Columbia Mur LAR Evib Rais, Enclosure 2 Project stage: Response to RAI ML17047A7492017-02-16016 February 2017 Response to Request for Additional Information, Columbia Mur LAR Evib Rais Project stage: Request ML17087A5692017-04-12012 April 2017 Request for Withholding Information from Public Disclosure for Columbia Generating Station Project stage: Withholding Request Acceptance 2016-08-18
[Table View] |
|
---|
Category:E-Mail
MONTHYEARML24008A0022024-01-0505 January 2024 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of License Amendment Request for Application to Revise TS to Adopt TSTF-584, Eliminate Automatic RWCU System Isolation on SLC Initiation - EPID L-2023-LLA-0170 ML23278A0042023-10-0404 October 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia - Application to Revise Technical Specifications to Adopt TSTF-230, Revision 1, Add New Condition B to LCO 3.6.2.3, RHR Suppression Pool Cooling - EPID L-2023-LLA-0128 ML23275A0092023-09-29029 September 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia - Application to Revise Tech Specs to Adopt TSTF-230, Revision 1, Add New Condition B to LCO 3.6.2.3, RHR Suppression Pool Cooling - EPID: L-2023-LLA-0128 ML23150A2502023-05-26026 May 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia Generating Station - License Amendment Request to Clean-Up Operating License and Appendix a, Technical Specifications - EPID L-2023-LLA-0062 ML23124A2412023-05-0404 May 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia - Application to Revise TS to Adopt TSTF-541, Add Exceptions to Surveillance Requirements for Valves and Dampers Locked in the Actuated Position - EPID L-2023-LLA-0063 ML23124A0062023-05-0303 May 2023 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia Generating Station - Application to Revise Tech Specs to Adopt TSTF-541, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling - EPID L-2023-LLA-0063 ML23065A0422023-02-23023 February 2023 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2022 Biological Monitoring Report ML22343A1802022-12-0808 December 2022 February 2023 Emergency Preparedness Program Inspection - Request for Information ML22349A2002022-12-0101 December 2022 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2022 Priority Pollutant Discharge Monitoring Report ML22312A0042022-11-0707 November 2022 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of Fourth 10 Year ISI RR 4ISI-11 - EPID L-2022-LLR-0071 ML22301A1432022-10-28028 October 2022 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - License Amendment Request to Adopt TSTF-505 - EPID L-2022-LLA-0023 ML22256A2002022-09-13013 September 2022 NRR E-mail Capture - Draft - Additional Audit Question - Columbia Generating Station - Regulatory Audit Question for LAR to Revise TS to Adopt TSTF-505, Revision 2 ML22241A0182022-08-26026 August 2022 NRR E-mail Capture - Draft - Additional Audit Question - Columbia Generating Station - Regulatory Audit Question for LAR to Revise TS to Adopt TSTF-505, Revision 2 ML22235A1052022-08-22022 August 2022 August 2022 Emergency Preparedness Exercise Inspection Request for Information ML22210A0072022-07-28028 July 2022 NRR E-mail Capture - Draft - Additional Audit Question - Columbia Generating Station - Regulatory Audit Question for LAR to Revise TS to Adopt TSTF-505, Revision 2 ML22173A0682022-06-17017 June 2022 Email Concurrence on SE Input for Columbia Pltr LAR ML22166A4122022-06-15015 June 2022 NRR E-mail Capture - LIC-109 Acceptance Review of LAR for Columbia Generating Station - Application to Revise TS to Adopt TSTF-580, Provide Exception from Entering Mode 4 with No Operable RHR Shutdown Cooling - EPID L-2022-LLA-0081 ML22144A0342022-05-18018 May 2022 NRR E-mail Capture - Draft - Request for Additional Information - Columbia Generating Station - LAR to Change TS 3.4.11 - Reactor Coolant System Pressure and Temperature Limits - EPID L-2021-LLA-0191 ML22075A3392022-03-15015 March 2022 NRR E-mail Capture - Columbia Generating Station - Audit Questions - Regulatory Audit of License Amendment Request to Adopt 50.69 - Categorization Process - EPID L-2021-LLA-0207 ML22067A0132022-03-0707 March 2022 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of License Amendment Request to Adopt TSTF-505, Revision 2, Provide RISK-INFORMED Extended Completion Times - RITSTF Initiative 4b - EPID L-2022-LLA-0023 A002515, NRR E-mail Capture - (External Sender) Energy Northwest Columbia Generating Station 2021 Priority Pollutant Discharge Monitoring Report2022-01-12012 January 2022 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2021 Priority Pollutant Discharge Monitoring Report ML21348A1852021-12-14014 December 2021 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia - License Amendment Request to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems and Components for Nuclear Power Reactors - EPID L-2021-LLA-0207 ML21335A0182021-11-30030 November 2021 NRR E-mail Capture - Columbia Generating Station - LIC-109 Acceptance of Requested Licensing Action - License Amendment Request to Change TS 3.4.11 Reactor Coolant System Pressure and Temperature Limits - EPID L-2021-LLA-0191 ML21216A0502021-08-0303 August 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia - License Amendment Request to Adopt TSTF-439, Eliminate Second Completion Times Limiting Time from Discovery of Failure to Meet an LCO EPID L-2021-LLA-0259 ML21209A9792021-07-28028 July 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - License Amendment Request to Remove License Condition 2.C.(34) and Revise License Condition 2.C.(35) - EPID L-2021-LLA-0074 ML21162A3062021-06-11011 June 2021 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia Generating Station - License Amendment Request to Adopt TSTF-546, Revise APRM Channel Adjustment Surveillance Requirement - EPID L-2021-LLA-0084 ML21137A0012021-05-14014 May 2021 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia Generating Station - License Amendment Request to Remove License Condition 2.C.(34) and Revise License Condition 2.C.(35) - EPID L-2021-LLA-0074 ML21120A1182021-04-30030 April 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - On-Site Cooling System Sediment Disposal Approval Request - EPID L-2020-LLL-0031 ML21109A2762021-04-0808 April 2021 Email Request for Information for Columbia Generating Station'S PIR Inspection_Redacted ML21068A2842021-03-0404 March 2021 2021002 Inservice Inspection (ISI) Request for Information (RFI) ML21036A2932021-02-0404 February 2021 NRR E-mail Capture - (External_Sender) Energy Northwest Columbia Generating Station 2020 Biological Monitoring Report ML20357B1502020-12-22022 December 2020 NRR E-mail Capture - LIC-109 Acceptance Review - Columbia - License Amendment Request - Adoption of TSTF-439, Eliminate Second Completion Times Limiting Time from Discovery of Failure to Meet an LCO, Rev. 2 - EPID L-2020-LLA-0259 ML20336A1852020-11-30030 November 2020 NRR E-mail Capture - Final - RAI - Columbia - One -Time Exemption from 10 CFR 73, App B, Sect VI, Subsection C.3.(l)(1) Regarding Annual Force-On-Force Exercises Due to COVID-19 Pandemic - EPID L-2020-LLE-0172 ML20325A0402020-11-19019 November 2020 NRR E-mail Capture - Draft - RAI - Columbia - One -Time Exemption from 10 CFR 73, Appendix B, Section VI, Subsection C.3.(I)(1) Regarding Annual Force -On-Force Exercises Due to COVID-19 Pandemic - EPID L-2020-LLE-0172 ML20314A0452020-11-0606 November 2020 NMFS to Energy Northwest, Entrainment Study Results for Columbia Generating Station ML20297A3032020-10-22022 October 2020 NRR E-mail Capture - LIC-109 Acceptance Review of License Amendment Request for Columbia - Application to Revise Tech Specs to Adopt TSTF-582, Reactor Pressure Vessel Water Inventory Control (RPV WIC) Enhancements - EPID L-2020-LLA-0212 ML20267A5162020-09-23023 September 2020 NRR E-mail Capture - Columbia Generating Station - Final - Request for Additional Information - Fourth Ten-Year Interval Inservice Inspection (ISI) Program Relief Request 4ISI-09 - EPID L-2020-LLR-0068 ML20265A3242020-09-20020 September 2020 Email 9-20-2020 - Req_ Kick-Off Call Columbia Generating Station RFI Provided for Roll-Back EP Program Inspection (Week of Nov 2 2020) ML20245E2822020-08-31031 August 2020 NRR E-mail Capture - Columbia Additional Request for Additional Information: Exigent License Amendment Request to Extend Technical Specification 3.8.7, Distribution Systems - Operating, Completion Time ML20239A9702020-08-26026 August 2020 NRR E-mail Capture - Columbia Additional Request for Additional Information: Exigent License Amendment Request to Extend Technical Specification 3.8.7, Distribution Systems - Operating, Completion Time ML20149K4362020-05-26026 May 2020 NRR E-mail Capture - Formal RAIs for Columbia (COVID-19) QA Plan Change Surveillance, Request Response by Tuesday June 2, 2020 ML20136A0112020-05-14014 May 2020 NRR E-mail Capture - Acceptance Columbia Relief Request ISI Reactor Pressure Vessel Feedwater Nozzles, 4ISI-09 ML20112F4572020-04-21021 April 2020 NRR E-mail Capture - Official Release of NRC RAIs for Columbia Covid Exigent Due Friday April 24, 2020 ML20090F5532020-03-30030 March 2020 NRR E-mail Capture - Accepted: Columbia Relief Request, EPID: L-2020-LLR-0035 ML20063G1522020-03-0202 March 2020 NRR E-mail Capture - Columbia Generating Station - Acceptance of Requested Licensing Action TSTF-564 Amendment ML20056E3592020-02-25025 February 2020 NRR E-mail Capture - Columbia Generating Station - Acceptance of Requested Licensing Action TSTF-566 Amendment ML20034E6082020-02-0303 February 2020 NRR E-mail Capture - RAI Formal Release Columbia TSTF 563 LAR, 30 Day Response Period Due March 3, 2020 ML20013G7642020-01-10010 January 2020 Revised Questions to Support the Columbia SPRA Audit ML19305C9342019-11-0101 November 2019 50.54(f) SPRA Submittal - Completeness Review Done and Path Forward ML19291A0322019-10-17017 October 2019 NRR E-mail Capture - Subject: Columbia Generating Station - Acceptance of Requested Licensing Action TSTF-529 Amendment 2024-01-05
[Table view] Category:Request for Additional Information (RAI)
MONTHYEARML24011A1522024-01-10010 January 2024 March 2024 Emergency Preparedness Exercise Inspection-Request for Information ML23110A2642023-04-20020 April 2023 Request for Information License Renewal Phase 2 Inspection ML22343A1802022-12-0808 December 2022 February 2023 Emergency Preparedness Program Inspection - Request for Information ML22301A1432022-10-28028 October 2022 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - License Amendment Request to Adopt TSTF-505 - EPID L-2022-LLA-0023 ML22242A1082022-08-30030 August 2022 Information Request, Information Request, Security IR 2022404 ML22235A1052022-08-22022 August 2022 August 2022 Emergency Preparedness Exercise Inspection Request for Information ML22145A4462022-06-0606 June 2022 Information Request for the Cyber-Security Baseline Inspection, Notification to Perform Inspection 05000397/2022401 ML22144A0342022-05-18018 May 2022 NRR E-mail Capture - Draft - Request for Additional Information - Columbia Generating Station - LAR to Change TS 3.4.11 - Reactor Coolant System Pressure and Temperature Limits - EPID L-2021-LLA-0191 ML22041A4572022-02-10010 February 2022 Notification of NRC Design Bases Assurance Inspection (Team) (05000397/2022010) and Request for Information ML21277A3572021-10-12012 October 2021 CGS Brq RFI Letter, Columbia Generating Station - Notification of Inspection (NRC Inspection Report 05000397/2021004) and Request for Information ML21216A0502021-08-0303 August 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia - License Amendment Request to Adopt TSTF-439, Eliminate Second Completion Times Limiting Time from Discovery of Failure to Meet an LCO EPID L-2021-LLA-0259 ML21209A9792021-07-28028 July 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - License Amendment Request to Remove License Condition 2.C.(34) and Revise License Condition 2.C.(35) - EPID L-2021-LLA-0074 ML21120A1182021-04-30030 April 2021 NRR E-mail Capture - Final - Request for Additional Information - Columbia Generating Station - On-Site Cooling System Sediment Disposal Approval Request - EPID L-2020-LLL-0031 ML21068A2842021-03-0404 March 2021 2021002 Inservice Inspection (ISI) Request for Information (RFI) ML20336A1852020-11-30030 November 2020 NRR E-mail Capture - Final - RAI - Columbia - One -Time Exemption from 10 CFR 73, App B, Sect VI, Subsection C.3.(l)(1) Regarding Annual Force-On-Force Exercises Due to COVID-19 Pandemic - EPID L-2020-LLE-0172 ML20325A0402020-11-19019 November 2020 NRR E-mail Capture - Draft - RAI - Columbia - One -Time Exemption from 10 CFR 73, Appendix B, Section VI, Subsection C.3.(I)(1) Regarding Annual Force -On-Force Exercises Due to COVID-19 Pandemic - EPID L-2020-LLE-0172 ML20267A5162020-09-23023 September 2020 NRR E-mail Capture - Columbia Generating Station - Final - Request for Additional Information - Fourth Ten-Year Interval Inservice Inspection (ISI) Program Relief Request 4ISI-09 - EPID L-2020-LLR-0068 ML20245E2822020-08-31031 August 2020 NRR E-mail Capture - Columbia Additional Request for Additional Information: Exigent License Amendment Request to Extend Technical Specification 3.8.7, Distribution Systems - Operating, Completion Time ML20239A9702020-08-26026 August 2020 NRR E-mail Capture - Columbia Additional Request for Additional Information: Exigent License Amendment Request to Extend Technical Specification 3.8.7, Distribution Systems - Operating, Completion Time ML20149K4362020-05-26026 May 2020 NRR E-mail Capture - Formal RAIs for Columbia (COVID-19) QA Plan Change Surveillance, Request Response by Tuesday June 2, 2020 ML20112F4572020-04-21021 April 2020 NRR E-mail Capture - Official Release of NRC RAIs for Columbia Covid Exigent Due Friday April 24, 2020 ML20034E6082020-02-0303 February 2020 NRR E-mail Capture - RAI Formal Release Columbia TSTF 563 LAR, 30 Day Response Period Due March 3, 2020 ML20028E1512020-01-27027 January 2020 Notification of Evaluations of Changes, Tests, and Experiments Inspection (Inspection Report 05000397/2020002) and Request for Information ML19267A1842019-09-24024 September 2019 Request for Information for Upcoming Open Phase Condition Inspection at Columbia Generating Station ML19232A2282019-08-20020 August 2019 NRR E-mail Capture - Formal Release of RAIs Ref: Columbia Exigent Amendment - One Electrical RAI, ML19183A4752019-07-0202 July 2019 NRR E-mail Capture - Formal Release of RAIs Ref: Columbia HVAC LAR L-2019-LLA-0034 ML18088A0152018-03-29029 March 2018 Notification of NRC Inspection of the Implementation of Mitigation Strategies and Spent Fuel Pool Instrumentation Orders and Emergency Preparedness Communication/ Staffing/Multi-Unit Dose Assessment Plans (05000397/2018010) and Request for ML17341B0272017-12-0707 December 2017 NRR E-mail Capture - RAI Associated with Columbia Amendment Request Revise Tech Spec 5.5.12 for Permanent Extension of Type a and Type C Containment Testing Frequencies for MF9469, EPID: L-2017-LLA-0197, ILRT, LLRT LAR - New RAI Response Da ML17292A0572017-10-18018 October 2017 NRR E-mail Capture - New RWCU RAI Due Date Now November 24, 2017 ML17249A6882017-09-0606 September 2017 NRR E-mail Capture - RAIs for Columbia Relief Request RAI (MF8925), 3ISI-19 ML17205A3152017-07-20020 July 2017 Notification of Evaluations of Changes, Tests, and Experiments Inspection (05000397/2017004) and Request for Information ML17193A2192017-07-12012 July 2017 NRR E-mail Capture - Columbia RWCU LAR MF8318, Formal Release of RAIs ML17144A1702017-05-24024 May 2017 NRR E-mail Capture - NRC RAIs for Columbia Relief Request MF8922, 3ISI-16 ML17047A7492017-02-16016 February 2017 Response to Request for Additional Information, Columbia Mur LAR Evib Rais ML17006A0922017-01-0404 January 2017 NRR E-mail Capture - Eicb RAIs for Columbia Mur ML17006A0902017-01-0404 January 2017 NRR E-mail Capture - Non Proprietary Request for Additional Information Regarding Columbia Mur Power Uprate ML16356A1382016-12-21021 December 2016 NRR E-mail Capture - Columbia Mur LAR Evib RAIs Non - Proprietary Version - Revise Operating License and Technical Specifications for Measurement Uncertainty Recapture Power Uprate ML16342C4322016-12-0707 December 2016 NRR E-mail Capture - Columbia Measurement Uncertainty Recapture Power Uprate LAR Rais: Human Performance: MF8060, Formal Release for Response on Monday January 9, 2017 ML16327A1842016-11-22022 November 2016 NRR E-mail Capture - Non Proprietary Request for Additional Information Regarding Columbia Mur Power Uprate ML16323A1192016-11-16016 November 2016 NRR E-mail Capture - Eicb RAIs for Columbia Mur ML16218A3902016-08-0808 August 2016 Supplemental Information Needed for Acceptance of Requested Licensing Action, Request for Measurement Uncertainty Recapture (Mur) Power Uprate (from 3486 Mwt to 3544 Mwt) ML16194A3702016-07-11011 July 2016 Notification of NRC Triennial Heat Sink Performance Inspection 05000397/2016003 and Request for Information ML16069A3592016-03-0909 March 2016 NRR E-mail Capture - Second Round Rais: Columbia MF6042 LAR TSTF-425 ML16061A5542016-03-0101 March 2016 Notification of NRC Design Bases Inspection (05000397/2016007) and Initial Request for Information ML16061A5662016-03-0101 March 2016 Notification of Design Bases Inspection (Programs)(Inspection Report 05000397/2016008) and Initial Request for Information ML15254A2572015-09-16016 September 2015 Request for Additional Information Associated with Near-Term Task Force Recommendation 2.1 Seismic Reevaluations ML15215A0432015-08-18018 August 2015 Request for Additional Information Associated with Near-Term Task Force Recommendation 2.1, Seismic Reevaluations ML14262A3412014-09-24024 September 2014 Request for Additional Information, Round 2, License Amendment Request to Revise TS Table 3.3.1.1-1 Function 7, Scram Discharge Volume Water Level - High ML14192B0312014-08-13013 August 2014 Redacted, Request for Additional Information, Nrr/Dss/Scvb, Request to Modify Emergency Core Cooling Systems Surveillance Requirements for Low Pressure Core Spray and Low Pressure Coolant Injection Pump Flows ML14206A0112014-07-31031 July 2014 Request for Additional Information, License Amendment Request to Revise TS Table 3.3.1.1-1 Function 7, Scram Discharge Volume Water Level - High 2024-01-10
[Table view] |
Text
NRR-PMDAPEm Resource From: Klos, John Sent: Wednesday, January 04, 2017 7:07 AM To: Garcia, Richard M.
Cc: Klos, John
Subject:
Re: RE: NON proprietary Request for Additional Information Regarding Columbia MUR Power Uprate (CAC No. MF8060)
Mr Garcia I am writing to acknowledge the reschedule of RAIs below to January 13, 2017.
Thank you John Klos On: 03 January 2017 15:41, "Garcia, Richard M." wrote:
- John, We would like to formally request additional time to submit the response to the SRXB questions below. Our ability to deliver these responses by the current January 5th due date has been challenged due to a forced plant outage and recovery resulting from a weather related load reject as well as reduced work hours due to adverse weather conditions.
A revised due date of January 13, 2017 is requested. Thanks, Rick Garcia Licensing Energy Northwest - Columbia Tel 509-377-8463 Fax 509-377-4317 From: Klos, John [1]
Sent: Tuesday, November 22, 2016 8:06 AM To: Garcia, Richard M.
Cc: Watford, Margaret; Klos, John
Subject:
NON proprietary Request for Additional Information Regarding Columbia MUR Power Uprate (CAC No. MF8060)
EXTERNAL: Think Before You Click!
Email sent from: "Klos, John" prvs=127edcf15=John.Klos@nrc.gov
Dear Mr. Garcia,
By letter dated June 28, 2016, (Agencywide Documents Access and Management System (ADAMS) Accession No. ML16183A365), as supplemented by letter dated August 18, 2016 (ADAMS Accession No. ML16231A511), Energy Northwest submitted a license amendment for Columbia Generating Station (CGS). The proposed amendment would revise the operating license and technical specifications to implement an increase in rated thermal power from the current licenses thermal power of 3486 megawatts thermal (MWt) to a measurement uncertainty recapture thermal power of 3544 MWt.
The U.S. Nuclear Regulatory Commission (NRC) staff, specifically the Reactor Systems Branch (SRXB) in the Office of Nuclear Reactor Regulation, has reviewed the submittal and determined that the attached NON - proprietary requests 1
for additional information (RAIs) are needed to complete its technical review and make a regulatory finding regarding this license amendment request.
Please see the formal RAIs below. A clarification call was held on November 16, 2016 to ensure your staff understood the RAIs. In the clarification call, Energy Northwest agreed to submit the response to the RAIs by Thursday Jan 5, 2017.
REQUEST FOR ADDITIONAL INFORMATION MEASUREMENT UNCERTAINTY RECAPTURE POWER UPRATE LICENSE AMENDMENT REQUEST COLUMBIA GENERATING STATION DOCKET NO. 50-397 CAC NO. MF8060 By letter dated June 28, 2016, (Agencywide Documents Access and Management System (ADAMS) Accession No. ML16183A365), as supplemented by letter dated August 18, 2016 (ADAMS Accession No. ML16231A511), Energy Northwest submitted a license amendment for Columbia Generating Station (CGS). The proposed amendment would revise the operating license and technical specifications (TS) to implement an increase in rated thermal power from the current licenses thermal power of 3486 megawatts thermal (MWt) to a measurement uncertainty recapture (MUR) thermal power of 3544 MWt.
The U.S. Nuclear Regulatory Commission (NRC) staff, specifically the Reactor Systems Branch (SRXB) in the Office of Nuclear Reactor Regulation, has reviewed the submittal and determined that the following request for additional information (RAIs) are needed to complete its technical review and make a regulatory finding regarding this license amendment request.
Please note that the proprietary information in this document is identified by underlined text enclosed within double square brackets ((( ))). ((This sentence is an example.))
RAI-SRXB-1: Reactor Performance Improvement Features The proprietary General Electric-Hitachi (GEH) Report NEDC-33853P, Safety Analysis Report for Columbia Generating Station Thermal Power Optimization (TSAR), Revision 0, Section 1.3.2, Reactor Performance Improvement Features, lists Feedwater Temperature Reduction (FWTR), Feedwater Heater Out-Of-Service (FWHOOS) and Safety Relief Valve (SRV)/Automatic Depressurization System 2 Valves Out-Of-Service (SRVOOS) as the performance improvement and equipment out-of-service features currently licensed at CGS. However, the Core Operating Limit Report (COLR) for Cycle 23 does not have these features and instead, has Pressure Regulator Out-of-Service (PROOS). To meet the requirements of Title 10 of the Code of Federal Regulations (10 CFR) 50.9 Completeness and accuracy of information, please provide justification or confirmation for including FWTR, FWHOOS, and SRVOOS in the next cycles COLR with the MUR power uprate.
RAI-SRXB-2: PROOS versus MUR Power Uprate The MUR power uprate is based on a design and safety analysis assumption that the reactor dome pressure at the new uprated power level will be maintained at the currently licensed rated condition. To meet the requirements of 10 CFR 50 Appendix A, General Design Criteria for Nuclear Power Plants, General Design Criterion (GDC) 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers, please justify the impact of PROOS on the MUR power uprate in terms of maintaining the reactor dome pressure.
RAI-SRXB-3: FWTR and/or FWHOOS versus MUR Power Uprate of licensees amendment utilizes NEDC-32938P-A, Thermal Power Optimization Licensing Topical Report, which is referred to as the TLTR and its approved format and content. The TLTR, Appendix C, Section C.2.1 states content that the MUR power uprate is based on a design and safety analysis assumption that the full, standard configuration of feedwater heaters should be in service at the new uprated power level. To meet the requirements of 10 CFR 50, Appendix A, GDC 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers, please justify the appropriateness of FWTR and/or FWHOOS for the MUR power uprate in terms of maintaining the full and standard service of feedwater heaters.
RAI-SRXB-4: Fuel Thermal Margin Monitoring In Section 2.2, Thermal Limits Assessment, of the TSAR, it states ((
2
)). To meet the requirements of 10 CFR 50, Appendix A, GDC 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers, please justify the applicability of the TSAR for use of the 4.8 MWt/bundle basis or provide a plant specific analysis.
RAI-SRXB-5: Evaluation of Design Changes and Safety Evaluations To meet the requirements of 10 CFR 50, Appendix A, GDC 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers and the completeness requirement of 10 CFR 50.9, please provide a summary of the evaluation results for the impact of the MUR power uprate on any design changes/safety evaluations that have not yet been implemented in the latest Updated Final Safety Analysis Report if such design/safety evaluations exist.
RAI-SRXB-6: Emergency Core Cooling System-Loss-Of-Coolant Accident Performance Analyses Table 4.1 of TSAR shows the Emergency Core Cooling System (ECCS) Loss-Of-Coolant Accident (LOCA) analysis results for GNF2 fuel. It is not clear whether the GNF2 fuel is the only fuel type for the upcoming cycle with MUR uprated power. It is noted from the COLR for Cycle 26 that the current cycle reactor core contains GE14 in addition to the GNF2 fuel. TO meet the requirements of 10 CFR 50, Appendix A, GDC 10, GDC 15 and 10 CFR 50.46 for assuring the design and LOCA conditions with respect to the integrity of physical barriers and the completeness and accuracy requirements of 10 CFR 50.9, please provide the analysis result similar to Table 4.1 of TSAR for GE14 if GE14 is applicable and used in the next cycle. In addition, please provide a justification meeting the (( )) Peak Cladding Temperature (PCT) margin criteria if GE14 is applicable and used in the next cycle.
RAI-SRXB-7: Anticipated Operational Occurrences (AOOs)
To meet the requirements of 10 CFR 50, Appendix A, GDC 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers and the completeness and accuracy requirements of 10 CFR 50.9, please provide information for the following questions relating to Section 9.1, Anticipated Operational Occurrences, of the TSAR:
(a) Per the footnotes of Table E-1 of the TLTR, please provide the plant-specific disposition. In other words, is ODYN, READY or TRACG used to perform the analysis? In addition, is a 2% power uncertainty continuously applied?
(b) As compared with current reload analysis for CGS (Cycle 23 COLR), is the list of AOOs in Table E-1 complete? Please provide a confirmation statement if Table E-1 list is complete.
RAI-SRXB-8: Anticipated Transient Without Scram (ATWS)
To meet the requirements of 10 CFR 50, Appendix A, GDC 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers, the completeness and accuracy requirements of 10 CFR 50.9, and the requirements for ATWS as specified in 10 CFR 50.62, Requirements for reduction of risk from anticipated transients without scram (ATWS) events for light-water-cooled nuclear power plants, please provide information for the following:
For TSAR, Section 9.3.1, Anticipated Transient Without Scram, please provide the CGS-specific ATWS analysis results at 100% Current Licensed Thermal Power (CLTP) and the margin of the ATWS acceptance criteria for the following:
(a) PCT, (b) Peak clad oxidation and, (c) Peak containment pressure RAI-SRXB-9: Fuel Pool Cooling (FPC) System Parameters In the TSAR, Table 6.6, FPC System Parameters, shows the comparison of FPC system data between CLTP and Thermal Power Optimization (TPO). To meet the requirements of 10 CFR 50.9, please provide responses to the following questions:
(a) Please confirm the MWt values for CLTP and TPO.
(b) Confirm that the data for all FPC system parameters for both CLTP and TPO are the same.
RAI-SRXB-10: Station Blackout (SBO)
Provide a confirmation of meeting the requirements in 10 CFR 50.63, Loss of alternating current power, for the MUR power uprate. Specifically, please provide a description on if the plant has sufficient condensate inventory for MUR power uprate operation and whether the reactor core isolation cooling (RCIC) or high pressure coolant injection (HPCI) systems can provide core cooling and coverage during the SBO coping period.
RAI-SRXB-11: Reactor Water Cleanup (RWCU) Line Break In the TSAR, Section 10.1.2.4, RWCU System Line Breaks, clarify why and how the RWCU process temperature and enthalpy are decreased due to the MUR power uprate to meet the completeness and accuracy requirements of 10 CFR 50.9. Also, please provide the reference reactor power used for this comparison.
RAI-SRXB-12: Reactor Vessel Fracture Toughness 3
To meet the requirements of 10 CFR 50, Appendix A, GDC 10 and 15 for assuring the design conditions with respect to the integrity of physical barriers and the completeness and accuracy requirements of 10 CFR 50.9, please provide information for the following questions.
(a) Please confirm that MUR power is used to define the 51.56 effective full power years (EFPY) in Table 3-1, CGS Upper Shelf Energy 60-Year License (51.56 EFPY).
(b) In the TSAR, Section 3.2.1, Fracture Toughness, it appears the same information has been provided in paragraphs (f) and (g) on Page 3-2 of the TSAR. Please confirm if any additional information was supposed to be presented in either paragraph.
Thank you, John Klos DORL Callaway, Columbia Project Manager U.S. NRC, Office of Nuclear Reactor Regulation, Division of Operating Reactor Licensing, O8E7 NRC/NRR/DORL/LPL4-1, MS O8H4A Washington, DC 20555-0001 301.415.5136, 301.415.2102 (fax)
John.Klos@NRC.gov
-- Reputation Score:3.5 Remote Host: mail2.nrc.gov 4
Hearing Identifier: NRR_PMDA Email Number: 3244 Mail Envelope Properties (F9811802D4A9FFC3514F422045C91C2EF4CB7B66)
Subject:
Re: RE: NON proprietary Request for Additional Information Regarding Columbia MUR Power Uprate (CAC No. MF8060)
Sent Date: 1/4/2017 7:07:17 AM Received Date: 1/4/2017 7:07:17 AM From: Klos, John Created By: John.Klos@nrc.gov Recipients:
"Klos, John" <John.Klos@nrc.gov>
Tracking Status: None "Garcia, Richard M." <rmgarcia@energy-northwest.com>
Tracking Status: None Post Office: unknown Files Size Date & Time MESSAGE 11952 1/4/2017 7:07:17 AM Options Priority: Standard Return Notification: No Reply Requested: No Sensitivity: Normal Expiration Date:
Recipients Received: