MONTHYEARML13182A3502013-06-26026 June 2013 License Amendment Request 271 - Transition to 10 CFR 50.48(c) - NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants, 2001 Edition. Part 2 of 3 Project stage: Other ML13256A1972013-09-0909 September 2013 NRR E-mail Capture - Point Beach Nuclear Plant, Units 1 and 2 Acceptance Review Regarding the NFPA 805 License Amendment Request - Opportunity to Supplement Project stage: Acceptance Review NRC 2013-0092, License Amendment Request 271 Supplement 1 Transition to 10 CFR 50.48(c)- NFPA 8052013-09-16016 September 2013 License Amendment Request 271 Supplement 1 Transition to 10 CFR 50.48(c)- NFPA 805 Project stage: Supplement ML13267A0372013-09-25025 September 2013 Acceptance Review of Licensing Action License Amendment Request to Transition to NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants Project stage: Acceptance Review ML14127A2942014-05-0909 May 2014 Regulatory Audit in Support of License Amendment Request to Implement NFPA 805, as Incorporated Into 10 CFR 50.48(c) Project stage: Other ML14153A3902014-05-27027 May 2014 NRR E-mail Capture - Point Beach Nuclear Plant, Units 1 and 2 Final Requests for Additional Information License Amendment Request Associated with NFPA 805 (TAC Nos. MF2372 and MF2373) Project stage: RAI ML14189A3652014-07-0808 July 2014 NRR E-mail Capture - Point Beach Nuclear Plant, Units 1 and 2 Final (Revised) Requests for Additional Information License Amendment Request Associated with NFPA 805 Project stage: RAI NRC-2014-0043, Response (60 Day) to Request for Additional Information License Amendment Request Associated with NFPA 8052014-07-29029 July 2014 Response (60 Day) to Request for Additional Information License Amendment Request Associated with NFPA 805 Project stage: Request NRC 2014-0054, Response (90 Day) to Request for Additional Information License Amendment Request Associated with NFPA 8052014-08-28028 August 2014 Response (90 Day) to Request for Additional Information License Amendment Request Associated with NFPA 805 Project stage: Request NRC 2014-0056, Response (120 Day) to Request for Additional Information and Revision to 60 Day Response License Amendment Request 271 Associated with NFPA 8052014-09-25025 September 2014 Response (120 Day) to Request for Additional Information and Revision to 60 Day Response License Amendment Request 271 Associated with NFPA 805 Project stage: Request ML14325A5412014-11-14014 November 2014 NRR E-mail Capture - Point Beach Nuclear Plant, Units 1 and 2 - Follow-up Requests for Additional Information (Afpb) NFPA 805 License Amendment Request Review Project stage: RAI NRC 2014-0073, Response to Request for Additional Information (Radiation Release) License Amendment Request 271 Associated with NFPA 8052014-11-14014 November 2014 Response to Request for Additional Information (Radiation Release) License Amendment Request 271 Associated with NFPA 805 Project stage: Response to RAI ML14325A5402014-11-19019 November 2014 NRR E-mail Capture - Point Beach Nuclear Plant, Units 1 and 2 - Follow-up Requests for Additional Information (Afpb) NFPA 805 License Amendment Request Review Project stage: RAI ML15091A5172015-04-0606 April 2015 4/6/2015, Meeting Slide for Public Teleconference on Point Beach MCR Abandonment Analysis for Loss of Control Scenarios Project stage: Request ML15106A5932015-04-14014 April 2015 NRR E-mail Capture - Request for Additional Information - Point Beach Nuclear Plant, Unit 1 and 2 - MF2372 and MF2373 Project stage: RAI ML15106A7122015-04-23023 April 2015 Summary of April 6, 2015, Meeting with NextEra Energy Point Beach, LLC, to Discuss License Amendment Request to Transition to NFPA 805 Project stage: Meeting ML15121A0572015-05-15015 May 2015 June 9 - 12, 2014 Summary of Audit at Point Beach Nuclear Plant, Unit Nos. 1 and 2, Associated with License Amendment Request to Transition to National Fire Protection Association Standard 805 Project stage: Other NRC 2016-0012, Response to Request for Additional Information, License Amendment Request 271 Associated with NFPA 8052016-04-0707 April 2016 Response to Request for Additional Information, License Amendment Request 271 Associated with NFPA 805 Project stage: Response to RAI 2014-07-29
[Table View] |
|
---|
Category:Letter type:NRC
MONTHYEARNRC 2023-0013, Response to Regulatory Information Summary 2023-01 Preparation and Scheduling of Operator Licensing Examinations2023-07-0707 July 2023 Response to Regulatory Information Summary 2023-01 Preparation and Scheduling of Operator Licensing Examinations NRC 2023-0006, Post-Exam Submittal Cover Letter2023-03-0101 March 2023 Post-Exam Submittal Cover Letter NRC 2023-0005, Report of Changes to Emergency Plan2023-02-21021 February 2023 Report of Changes to Emergency Plan NRC 2022-0032, Sixth 10-Year Interval Inservice Testing (1ST) Program Plan2022-09-30030 September 2022 Sixth 10-Year Interval Inservice Testing (1ST) Program Plan NRC 2022-0025, License Amendment Request 295, Beacon Power Distribution Monitoring System2022-09-26026 September 2022 License Amendment Request 295, Beacon Power Distribution Monitoring System NRC 2022-0019, Report of Changes to Emergency Plan2022-07-13013 July 2022 Report of Changes to Emergency Plan NRC 2022-0022, Response to Request for Supplemental Information (Rsi) Regarding License Amendment Request (LAR) 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2,2022-07-11011 July 2022 Response to Request for Supplemental Information (Rsi) Regarding License Amendment Request (LAR) 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2, NRC 2022-0015, Fall 2021 Unit 2 (U2R38) Steam Generator Tube Inspection Report2022-04-27027 April 2022 Fall 2021 Unit 2 (U2R38) Steam Generator Tube Inspection Report NRC 2022-0014, 2021 Annual Monitoring Report2022-04-14014 April 2022 2021 Annual Monitoring Report NRC 2021-0012, Core Operating Limits Report (COLR) Unit 1 Cycle 41 (U 1 C41)2022-04-0707 April 2022 Core Operating Limits Report (COLR) Unit 1 Cycle 41 (U 1 C41) NRC 2022-0003, License Amendment Request 296, Application for Technical Specification Improvement to Eliminate Requirements for Post-Accident Systems Using the Consolidated Line Item Improvement Process2022-03-25025 March 2022 License Amendment Request 296, Application for Technical Specification Improvement to Eliminate Requirements for Post-Accident Systems Using the Consolidated Line Item Improvement Process NRC 2022-0006, Notification of Deviation from Pressurized Water Owners Group (PWROG) Report WCAP-17451-P, Revision 1, Reactor Internals Guide Tube Wear - Westinghouse Domestic Fleet Operational Projections2022-02-22022 February 2022 Notification of Deviation from Pressurized Water Owners Group (PWROG) Report WCAP-17451-P, Revision 1, Reactor Internals Guide Tube Wear - Westinghouse Domestic Fleet Operational Projections NRC 2022-0004, Report of Changes to Emergency Plan2022-02-0909 February 2022 Report of Changes to Emergency Plan NRC 2022-0005, Refueling Outage U2R38 Owner'S Activity Report for Class 1, 2, 3 and Mc ISI Examinations2022-02-0101 February 2022 Refueling Outage U2R38 Owner'S Activity Report for Class 1, 2, 3 and Mc ISI Examinations NRC 2022-0001, Report of Changes to Emergency Plan2022-01-11011 January 2022 Report of Changes to Emergency Plan NRC 2021-0046, Core Operating Limits Report (COLR) Unit 2 Cycle 39 (U2C39) and Changes to Unit 1 COLR Unit 1 Cycle 40 (U1C40)2021-10-28028 October 2021 Core Operating Limits Report (COLR) Unit 2 Cycle 39 (U2C39) and Changes to Unit 1 COLR Unit 1 Cycle 40 (U1C40) NRC 2021-0031, Registration of Holtec Hi STORM Casks HI-STORM-37-054, HI-STORM-37-055, and HI-STORM-37-0562021-07-15015 July 2021 Registration of Holtec Hi STORM Casks HI-STORM-37-054, HI-STORM-37-055, and HI-STORM-37-056 NRC 2021-0027, Registration of Holtec Historm Casks HISTORM-37-051, HISTORM-37-052, and HISTORM-37-0532021-06-30030 June 2021 Registration of Holtec Historm Casks HISTORM-37-051, HISTORM-37-052, and HISTORM-37-053 NRC 2021-0028, Generic Letter 2004-02 Containment Sump Debris Transport Calculation Non-Conservatism2021-06-23023 June 2021 Generic Letter 2004-02 Containment Sump Debris Transport Calculation Non-Conservatism NRC 2021-0021, 2020 Annual Monitoring Report2021-04-29029 April 2021 2020 Annual Monitoring Report NRC 2021-0019, Response to Regulatory Information Summary 2021-01 Preparation and Scheduling of Operator Licensing Examinations2021-04-22022 April 2021 Response to Regulatory Information Summary 2021-01 Preparation and Scheduling of Operator Licensing Examinations NRC-2021-0010, CFR 50.59 Evaluation and Commitment Change Summary Report2021-04-0202 April 2021 CFR 50.59 Evaluation and Commitment Change Summary Report NRC-2021-0011, Technical Specification Bases and Technical Requirement Manual Change Summary2021-04-0202 April 2021 Technical Specification Bases and Technical Requirement Manual Change Summary NRC 2021-0006, Report of Changes to Emergency Plan2021-03-18018 March 2021 Report of Changes to Emergency Plan NRC 2021-0005, Withdrawal of Exemption Request Supporting Updated Final Response to NRC Generic Letter 2004-022021-02-11011 February 2021 Withdrawal of Exemption Request Supporting Updated Final Response to NRC Generic Letter 2004-02 NRC 2021-0002, Refueling Outage U1 R39 Owner'S Activity Report for Class 1, 2, 3 and Mc ISI Examinations2021-01-21021 January 2021 Refueling Outage U1 R39 Owner'S Activity Report for Class 1, 2, 3 and Mc ISI Examinations NRC 2021-0003, Refueling 39 (U1 R39) Reactor Coolant Pump Analytical Evaluation Report2021-01-21021 January 2021 Refueling 39 (U1 R39) Reactor Coolant Pump Analytical Evaluation Report NRC 2021-0001, Report of Changes to Emergency Plan2021-01-13013 January 2021 Report of Changes to Emergency Plan NRC 2020-0044, Response to Request for Additional Information Request for Exemption from 10 CFR 73, Appendix B, Section VI Regarding Annual Force-On-Force Exercise2020-12-0808 December 2020 Response to Request for Additional Information Request for Exemption from 10 CFR 73, Appendix B, Section VI Regarding Annual Force-On-Force Exercise NRC 2020-0032, Application for Subsequent Renewed Facility Operating Licenses2020-11-16016 November 2020 Application for Subsequent Renewed Facility Operating Licenses NRC 2020-0039, Core Operating Limits Report (COLR) Unit 1 Cycle 40 (U1 C40)2020-11-0202 November 2020 Core Operating Limits Report (COLR) Unit 1 Cycle 40 (U1 C40) NRC 2020-0031, NextEra Energy Point Beach, LLC Response to Apparent Violation in NRC Inspection Report 05000266/2020012, 05000301/2020012: EA-20-0812020-10-0505 October 2020 NextEra Energy Point Beach, LLC Response to Apparent Violation in NRC Inspection Report 05000266/2020012, 05000301/2020012: EA-20-081 NRC 2020-0029, Supplement to License Amendment Request (LAR) 293, One-Time Extension of Renewed Facility Operating License Condition 4.1, Containment Building Construction Truss2020-09-15015 September 2020 Supplement to License Amendment Request (LAR) 293, One-Time Extension of Renewed Facility Operating License Condition 4.1, Containment Building Construction Truss NRC 2020-0024, Response to Request for Additional Information Request for Exemption from Certain Operator Requalification Requirements2020-08-17017 August 2020 Response to Request for Additional Information Request for Exemption from Certain Operator Requalification Requirements NRC 2020-0020, License Amendment Request (LAR) 293, One-Time Extension of Renewed Facility Operating License Condition 4.1, Containment Building Construction Truss2020-08-13013 August 2020 License Amendment Request (LAR) 293, One-Time Extension of Renewed Facility Operating License Condition 4.1, Containment Building Construction Truss NRC 2020-0023, NextEra Energy Point Beach, LLC - Revised Response to Regulatory Information Summary 2020-01, Preparation and Scheduling of Operator Licensing Examinations2020-08-12012 August 2020 NextEra Energy Point Beach, LLC - Revised Response to Regulatory Information Summary 2020-01, Preparation and Scheduling of Operator Licensing Examinations NRC 2020-0021, Response to NRC Inspection Report and Preliminary White Finding2020-08-12012 August 2020 Response to NRC Inspection Report and Preliminary White Finding NRC 2020-0018, Report of Changes to Emergency Plan2020-07-15015 July 2020 Report of Changes to Emergency Plan NRC-2020-0016, Supplement to Exemption Request for Access Authorization and Fitness for Duty Requirements Due to COVID-19 Pandemic2020-06-12012 June 2020 Supplement to Exemption Request for Access Authorization and Fitness for Duty Requirements Due to COVID-19 Pandemic NRC 2020-0012, Refueling Outage U2R37 Owner'S Activity Report for Class 1, 2, 3 and Mc ISI Examinations2020-05-20020 May 2020 Refueling Outage U2R37 Owner'S Activity Report for Class 1, 2, 3 and Mc ISI Examinations NRC 2020-0008, Report of Changes to Emergency Plan2020-04-0606 April 2020 Report of Changes to Emergency Plan NRC 2020-0007, Core Operating Limits Report (COLR) Unit 2 Cycle 28 (U2C38)2020-03-27027 March 2020 Core Operating Limits Report (COLR) Unit 2 Cycle 28 (U2C38) NRC 2020-0003, License Amendment Request 289: Tornado Missile Protection Licensing Basis2020-02-0606 February 2020 License Amendment Request 289: Tornado Missile Protection Licensing Basis NRC 2020-0001, Pressure Temperature Limits Report (PTLR)2020-01-0909 January 2020 Pressure Temperature Limits Report (PTLR) NRC 2019-0044, Report of Changes to Emergency Plan2019-11-0101 November 2019 Report of Changes to Emergency Plan NRC 2019-0036, Submittal of 2018 Update to Final Safety Analysis Report2019-10-18018 October 2019 Submittal of 2018 Update to Final Safety Analysis Report NRC 2019-0037, Technical Specification Bases Change Summary2019-10-18018 October 2019 Technical Specification Bases Change Summary NRC 2019-0034, Technical Requirements Manual Change Summary2019-10-18018 October 2019 Technical Requirements Manual Change Summary NRC 2019-0032, CFR 50.59 Evaluation and Commitment Change Summary Report2019-10-18018 October 2019 CFR 50.59 Evaluation and Commitment Change Summary Report NRC 2019-0042, NextEra Energy Point Beach, LLC, Relief Request 1-RR-13 and 2-RR-13, Response to Request for Additional Information2019-10-17017 October 2019 NextEra Energy Point Beach, LLC, Relief Request 1-RR-13 and 2-RR-13, Response to Request for Additional Information 2023-07-07
[Table view] Category:Response to Request for Additional Information (RAI)
MONTHYEARL-2023-155, Supplement to Response to Request for Additional Information, Revised NextEra Common Emergency Plan, and Revised Site-Specific Emergency Plan Annexes Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-06542023-11-28028 November 2023 Supplement to Response to Request for Additional Information, Revised NextEra Common Emergency Plan, and Revised Site-Specific Emergency Plan Annexes Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, L-2023-098, and Point Beach Units 1 and 2 - Response to Request for Additional Information Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 22023-08-0707 August 2023 and Point Beach Units 1 and 2 - Response to Request for Additional Information Regarding License Amendment Request for Common Emergency Plan Consistent with NUREG-0654, Revision 2 L-2023-075, Response to Request for Additional Information (RAI) Regarding Exemption Request, License Amendment Request and Revised Response in Support of a Risk-Informed Resolution of Generic Letter 2004-022023-06-0909 June 2023 Response to Request for Additional Information (RAI) Regarding Exemption Request, License Amendment Request and Revised Response in Support of a Risk-Informed Resolution of Generic Letter 2004-02 L-2023-073, Subsequent License Renewal Application, Second Annual Update Request for Additional Information Set 1 Response2023-06-0101 June 2023 Subsequent License Renewal Application, Second Annual Update Request for Additional Information Set 1 Response L-2023-011, Response to Requests for Additional Information (Rais) Regarding License Amendment Request 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2, Provide Risk Informed2023-02-21021 February 2023 Response to Requests for Additional Information (Rais) Regarding License Amendment Request 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2, Provide Risk Informed ML23011A2802023-01-11011 January 2023 Units 1 and 2 - Response to Requests for Additional Information (Rals) Regarding License Amendment Request 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2, Provide Risk Informed . ML22229A1052022-08-17017 August 2022 Response to Questions Regarding Point Beach Nuclear Power Plant with Attachment NRC 2022-0022, Response to Request for Supplemental Information (Rsi) Regarding License Amendment Request (LAR) 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2,2022-07-11011 July 2022 Response to Request for Supplemental Information (Rsi) Regarding License Amendment Request (LAR) 297, Revise Technical Specifications to Adopt Risk Informed Completion Times TSTF-505, Revision 2, L-2022-013, Subsequent License Renewal Application - Environmental Report Review Review Request for Additional Information (RAI) No. HCR-1 Supplemental Response2022-01-25025 January 2022 Subsequent License Renewal Application - Environmental Report Review Review Request for Additional Information (RAI) No. HCR-1 Supplemental Response L-2021-240, Subsequent License Renewal Application - Aging Management Request for Additional Information Set 13 Response2022-01-0606 January 2022 Subsequent License Renewal Application - Aging Management Request for Additional Information Set 13 Response L-2021-248, Subsequent License Renewal Application Aging Management Requests for Additional Information (RAI) Set 14 Response2022-01-0606 January 2022 Subsequent License Renewal Application Aging Management Requests for Additional Information (RAI) Set 14 Response L-2021-223, Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 12 Response2021-12-0909 December 2021 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 12 Response L-2021-222, Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 11 Response Revision 12021-11-23023 November 2021 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 11 Response Revision 1 L-2021-199, Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 10 Responses2021-11-0404 November 2021 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 10 Responses L-2021-208, Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 9 Response Supplement 12021-11-0404 November 2021 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 9 Response Supplement 1 L-2021-190, Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 2 Responses Revision 12021-11-0303 November 2021 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 2 Responses Revision 1 L-2021-200, Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 11 Response2021-10-25025 October 2021 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 11 Response L-2021-174, NextEra Energy Point Beach, LLC - Subsequent License Renewal Application - Aging Management Request for Additional Information (RAI) Set 9 Response2021-10-0101 October 2021 NextEra Energy Point Beach, LLC - Subsequent License Renewal Application - Aging Management Request for Additional Information (RAI) Set 9 Response L-2021-172, Subsequent License Renewal Application - Aging Management Requirement for Additional Information Set 7, Response2021-09-20020 September 2021 Subsequent License Renewal Application - Aging Management Requirement for Additional Information Set 7, Response L-2021-173, Subsequent License Renewal Application-Aging Management Request for Additional Information (RAI) Set 8 Response2021-09-16016 September 2021 Subsequent License Renewal Application-Aging Management Request for Additional Information (RAI) Set 8 Response L-2021-157, L-2021-157 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 6 Responses2021-09-10010 September 2021 L-2021-157 Subsequent License Renewal Application - Aging Management Requests for Additional Information (RAI) Set 6 Responses L-2021-165, Submittal of Subsequent License Renewal Application - Aging Management Requests for Confirmation Of/Additional Information (Rci/Rai) Set 1 Responses Supplement 12021-09-10010 September 2021 Submittal of Subsequent License Renewal Application - Aging Management Requests for Confirmation Of/Additional Information (Rci/Rai) Set 1 Responses Supplement 1 L-2021-155, Subsequent License Renewal Application on Aging Management - Request for Additional Information (Rai), Set 4 Response2021-08-30030 August 2021 Subsequent License Renewal Application on Aging Management - Request for Additional Information (Rai), Set 4 Response L-2021-154, Subsequent License Renewal Application -Aging Management Requests for Confirmation Of/Additional Information (Rci/Rai) Set 3 Responses2021-08-25025 August 2021 Subsequent License Renewal Application -Aging Management Requests for Confirmation Of/Additional Information (Rci/Rai) Set 3 Responses L-2021-144, Subsequent License Renewal Application-Aging Management Requests for Additional Information (RAI) Set 2 Responses2021-08-11011 August 2021 Subsequent License Renewal Application-Aging Management Requests for Additional Information (RAI) Set 2 Responses L-2021-116, Subsequent License Renewal Application Environmental Report Review Requests for Confirmation Of/Additional Information (Rci/Ral) Set Response2021-06-10010 June 2021 Subsequent License Renewal Application Environmental Report Review Requests for Confirmation Of/Additional Information (Rci/Ral) Set Response NRC 2020-0044, Response to Request for Additional Information Request for Exemption from 10 CFR 73, Appendix B, Section VI Regarding Annual Force-On-Force Exercise2020-12-0808 December 2020 Response to Request for Additional Information Request for Exemption from 10 CFR 73, Appendix B, Section VI Regarding Annual Force-On-Force Exercise NRC 2020-0024, Response to Request for Additional Information Request for Exemption from Certain Operator Requalification Requirements2020-08-17017 August 2020 Response to Request for Additional Information Request for Exemption from Certain Operator Requalification Requirements NRC 2019-0042, NextEra Energy Point Beach, LLC, Relief Request 1-RR-13 and 2-RR-13, Response to Request for Additional Information2019-10-17017 October 2019 NextEra Energy Point Beach, LLC, Relief Request 1-RR-13 and 2-RR-13, Response to Request for Additional Information NRC-2018-0050, Response to Request for Additional Information Regarding License Amendment Request 288, Request to Extend Containment Leakages Rate Test Frequency2018-11-16016 November 2018 Response to Request for Additional Information Regarding License Amendment Request 288, Request to Extend Containment Leakages Rate Test Frequency NRC 2018-0044, Supplement to Response to Request for Additional Information Regarding License Amendment Request 287, Application to Adopt 10 CFR 50.69, Risk Informed Categorization and Treatment of Structures, ...2018-09-28028 September 2018 Supplement to Response to Request for Additional Information Regarding License Amendment Request 287, Application to Adopt 10 CFR 50.69, Risk Informed Categorization and Treatment of Structures, ... NRC 2018-0038, Response to Request for Additional Information Regarding License Amendment Request 287, Application to Adopt 10 CFR 50.69, Risk Informed Categorization and Treatment of Structures, System, and Components (Sscs) for Nuclear2018-08-10010 August 2018 Response to Request for Additional Information Regarding License Amendment Request 287, Application to Adopt 10 CFR 50.69, Risk Informed Categorization and Treatment of Structures, System, and Components (Sscs) for Nuclear NRC 2018-0014, NextEra Energy Point Beach, LLC, Construction Truss License Amendment Request 278, Response to Request for Additional Information2018-04-12012 April 2018 NextEra Energy Point Beach, LLC, Construction Truss License Amendment Request 278, Response to Request for Additional Information L-2018-068, Florida Power and Light Co. - Response to Request for Additional Information Re Decommissioning Funding Plan Updates for Independent Spent Fuel Storage Installations2018-04-0303 April 2018 Florida Power and Light Co. - Response to Request for Additional Information Re Decommissioning Funding Plan Updates for Independent Spent Fuel Storage Installations ML17363A1452017-12-21021 December 2017 Response to Request for Additional Information Regarding License Amendment Request 286, Adoption of Emergency Action Level Scheme Pursuant to NEI 99-01, Revision 6, Development of Emergency Action Levels for Non-Passive Reactor NRC 2017-0052, Supplement to LAR 287, Application to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems, and Components for Nuclear Power Plants2017-10-26026 October 2017 Supplement to LAR 287, Application to Adopt 10 CFR 50.69, Risk-Informed Categorization and Treatment of Structures, Systems, and Components for Nuclear Power Plants NRC 2017-0041, to License Amendment Request 286, Adoption of Emergency Action Level Scheme Pursuant to NEI 99-01, Revision 6, Development of Emergency Action Levels for Non-Passive Reactors2017-08-21021 August 2017 to License Amendment Request 286, Adoption of Emergency Action Level Scheme Pursuant to NEI 99-01, Revision 6, Development of Emergency Action Levels for Non-Passive Reactors NRC 2017-0010, Response to Final Request for Additional Information Steam Generator License Amendment Request for H* Alternate Repair Criteria for Steam Generator Tube Sheet Expansion Region2017-04-20020 April 2017 Response to Final Request for Additional Information Steam Generator License Amendment Request for H* Alternate Repair Criteria for Steam Generator Tube Sheet Expansion Region NRC 2017-0008, Response to Final Request for Additional Information on Steam Generator Tube Inspection Report2017-02-23023 February 2017 Response to Final Request for Additional Information on Steam Generator Tube Inspection Report L-2016-137, Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-545, Revision 3, TS Inservice Testing Program Removal & Clarify SR Usage...2016-12-15015 December 2016 Response to Request for Additional Information Regarding Application to Revise Technical Specifications to Adopt TSTF-545, Revision 3, TS Inservice Testing Program Removal & Clarify SR Usage... NRC 2016-0048, Response to Request for Additional Information Regarding LAR 280 - Removal of Completed License Conditions and Change to the Ventilation Filter Testing Program2016-11-0404 November 2016 Response to Request for Additional Information Regarding LAR 280 - Removal of Completed License Conditions and Change to the Ventilation Filter Testing Program L-2016-188, Response to Generic Letter 2016-01, Monitoring of Neutron Absorbing Materials in Spent Fuel Pools, Response to NRC Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f)2016-11-0303 November 2016 Response to Generic Letter 2016-01, Monitoring of Neutron Absorbing Materials in Spent Fuel Pools, Response to NRC Request for Information Pursuant to Title 10 of the Code of Federal Regulations 50.54(f) NRC-2016-0033, Response to Request for Additional Information, License Amendment Request 279, Elimination of Technical Specification Section 3.7.14, Primary Auxiliary Building Ventilation2016-07-27027 July 2016 Response to Request for Additional Information, License Amendment Request 279, Elimination of Technical Specification Section 3.7.14, Primary Auxiliary Building Ventilation NRC 2016-0029, Response to Request for Additional Information Regarding License Amendment Request 280 - Removal of Completed License Conditions and Change to the Ventilation Filter Testing Program2016-07-11011 July 2016 Response to Request for Additional Information Regarding License Amendment Request 280 - Removal of Completed License Conditions and Change to the Ventilation Filter Testing Program NRC 2016-0012, Response to Request for Additional Information, License Amendment Request 271 Associated with NFPA 8052016-04-0707 April 2016 Response to Request for Additional Information, License Amendment Request 271 Associated with NFPA 805 NRC 2016-0008, Response to Request for Additional Information on NFPA 805 License Amendment Request 2712016-02-22022 February 2016 Response to Request for Additional Information on NFPA 805 License Amendment Request 271 NRC 2016-0006, License Amendment Request 277. Revision to Staff Augmentation Times in the Emergency Plan, Supplemental Response to Request for Additional Information No. 5 -Correction to Table 5.12016-02-0909 February 2016 License Amendment Request 277. Revision to Staff Augmentation Times in the Emergency Plan, Supplemental Response to Request for Additional Information No. 5 -Correction to Table 5.1 NRC 2016-0003, License Amendment Request 277, Revision to Staff Augmentation Times in the Plant Emergency Plan, Supplemental Response to Request for Additional Information No. 52016-01-26026 January 2016 License Amendment Request 277, Revision to Staff Augmentation Times in the Plant Emergency Plan, Supplemental Response to Request for Additional Information No. 5 NRC 2015-0068, Request for Additional Information for Relief Request 2-RR-11 - MF66152015-11-19019 November 2015 Request for Additional Information for Relief Request 2-RR-11 - MF6615 NRC-2015-0069, Response to Request for Information Supporting Flooding Hazards Reevaluation Report Audit2015-11-0606 November 2015 Response to Request for Information Supporting Flooding Hazards Reevaluation Report Audit 2023-08-07
[Table view] |
Text
April?, 2016 NRC 2016-0012 10 CFR 50.90 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, DC 20555 Point Beach Nuclear Plant, Units 1 and 2 Dockets 50-266 and 50-301 Renewed License Nos. DPR-24 and DPR-27 Response to Request for Additional Information.
License Amendment Request 271 Associated with NFPA 805
References:
(1) Next Era Energy Point Beach, LLC, letter to NRC, dated June 26, 2013, "License Amendment Request 271, Transition to 10 CFR 50.48(c)-
NFPA 805, 'Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants,' 2001 Edition" (ML131820453)
(2) NextEra Energy Point Beach, LLC, letter to NRC, dated September 16, 2013, "License Amendment Request 271, Supplement 1, Transition to 10 CFR 50.48(c)- NFPA 805" (ML13259A273)
(3) NRC letter to NextEra Energy Point Beach, LLC, dated September 25, 2013, "Point Beach Nuclear Plant, Units 1 and 2 -Acceptance of Licensing Action re: License Amendment Request to Transition to NFPA 805, 'Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants" (TAC NOS. MF2372 and MF2373)" (ML13267A037)
(4) NextEra Energy Point Beach, LLC letter to NRC, dated August 26, 2015, "Supplement 2 to License Amendment Request 271 Associated with NFPA 805 (ML15238A870)
(5) NRC e-mail to NextEra Energy Point Beach, LLC, dated October, 9, 2015, "Request for Additional Information - Point Beach Nuclear Plant, Units 1 and 2- NFPA 805 LAR- MF2372 and MF2373" (ML15348A262)
(6) NRC e-mail to NextEra Energy Point Beach, LLC, dated January, 20, 2016, "Request for Additional Information- Point Beach Nuclear Plant, Units 1 and 2- NFPA 805 LAR- MF2372 and MF2373" (ML16022A004)
Pursuant to 10 CFR 50.90, NextEra Energy Point Beach, LLC, (NextEra) requested to amend Renewed Facility Operating Licenses DPR-24 and DPR-27 for Point Beach Nuclear Plant (PBNP), Units 1 and 2 (Reference 1 and supplemented via References 2 and 4). The NRC accepted the license amendment request for review as documented in Reference (3).
The NRC Staff has determined that additional information (References 5 and 6) is required to complete its evaluation. The enclosure provides the NextEra response to the NRC Staff's request for additional information.
NextEra Energy Point Beach, LLC, 6610 Nuclear Rd., Two Rivers, WI. 54241 Security-Related Information -Withhold from Public Disclosure Under 10 CFR 2.390:
Attachment W of the Enclosure to this letter contain security-related information. Upon removal of Attachment W of the Enclosure, this letter is uncontrolled.
Document Control Desk Page 2 This letter contains no new Regulatory Commitments and no revisions to existing Regulatory Commitments.
If you have any questions regarding this letter, please contact Mr. Bryan Woyak, Licensing Manager, at (920) 755-7599.
I declare under penalty of perjury that the foregoing is true and correct.
Executed on April 7, 2016.
Very truly yours, NextEra Energy Point Beach, LLC Eric McCartney Site Vice President Enclosure cc: Administrator, Region Ill, USNRC Project Manager, Point Beach Nuclear Plant, USNRC Resident Inspector, Point Beach Nuclear Plant, USNRC PSCW
ENCLOSURE NEXTERA ENERGY POINT BEACH, LLC POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION LICENSE AMENDMENT REQUEST 271 ASSOCIATED WITH NFPA 805 Pursuant to 10 CFR 50.90, NextEra Energy Point Beach, LLC, (NextEra) requested to amend Renewed Facility Operating Licenses DPR-24 and DPR-27 for Point Beach Nuclear Plant (PBNP),
Units 1 and 2 (Reference 1 and supplemented via References 2 and 4). The NRC accepted the license amendment request for review as documented in Reference (3).
The NRC Staff on October 9, 2015, requested additional information via email in order to complete its evaluation (Reference 5). NextEra initially provided the information to the NRC via electronic portal.
Subsequently, the NRC via email dated January 20, 2016 (Reference 6) requested that the answers to the information request in Reference (5) be provided to the NRC on the docket. Additionally, the January 20, 2016, email requested additional information in order to complete the evaluation of the NextEra NFPA-805 LAR. This Enclosure provides the NextEra responses to both the October 9, 2015, and the January 20, 2016, NRC Staff's requests for additional information.
Request for Additional Information PRA RAJ 501 (Modelling inadequate breaker fuse coordination in the Fire PRA)
The NextEra letter, dated August 26, 2015 (ADAMS Accession No. ML15238A870), transmitting Supplement 2 of the Point Beach Nuclear Plant NFPA 805 LAR explains that "uncoordinated breakers were explicitly modelled in the Fire PRA after the 120 day response,' and that "[t]his change resulted in new Variance from Deterministic Requirements (VFDRs) and a change in the calculated risk results from the Fire PRA." The Jetter appears to indicate that re-assessment of breaker coordination and cable protection performed since providing the 120-day PRA RAJ responses have revealed breaker coordination and cable protection vulnerabilities. Updated LAR, Attachment B, Section 3.5.2.4 provided as part of Supplement 2 states that 13kV and 4kV Switchgear, 480V switchgear and Motor Control Centers (MCCs), and 120VAC and 125VDC distribution panels "not properly coordinated and impacting safe shutdown power loads, cables and fire zone/scenario information were evaluated and VFDRs were generated." Also, updated LAR , Attachment 8, Section
- 3. 4. 2. 5 states that for 13kV and 4kV Switchgear that inadequate cable protection associated with the ability of certain breakers to clear a fault was identified and so a "risk-informed approach was utilized and this condition was incorporated into the Fire PRA model." Neither the Jetter nor the Supplement itself describes the specific sources of the circuit inadequacies, which could be undersized protective breakers or fuses or other deficiencies, or how these inadequacies were modelled in the Fire PRA. NRC notes that little NRC guidance exists on how to model inadequate breaker fuse coordination or cable protection. In light of these observations:
a) Explain how inadequate breaker fuse coordination and cable protection was modelled in the Fire PRA and justify that this treatment addresses the failures that could occur as a result of the identified circuit inadequacies.
Page 1 of 7
b) Include a description of the circuit failure modes addressed and how associated component failures were modelled in the Fire PRA. Also, describe and justify assumptions made in the Fire PRA about how fire-induced faults associated with inadequately coordinated/protected circuits impact upstream and downstream components from the fault.
c) Given that the lack of beaker coordination and/or cable protection have been acknowledged and the sizing and coordination of electrical protective devices appear to be in question, include an explanation of how the potential for secondary fires was addressed in the Fire PRA. If secondary fires were not modelled and fire-induced faults in inadequately protected circuits could lead to secondary fires, then justify this modeling exclusion. Alternatively, include modeling of secondary fires in the integrated analysis requested in PRA RAJ 03.
d) In line with the issues described above, NRC staff also notes that the response to PRA RAJ 25.01 in NextEra letter dated January 16, 2015, ML15015A281 explains a risk-informed approach that was used in association with removal of cirouit protection related modifications No. 17 and No. 30 by modeling overcurrent failure modes and secondary fires. These modifications would have provided overcurrent trip protection for a certain circuits including protection/backup 125 VDC control power to 4 kV and 13.8 kV switchgear. As a result,
- i. Describe how the plant response model addresses fire-induced faulting of one or more load circuits at the same time that DC control power has been lost due to fire damage.
ii. Explain how the lack of circuit protection and the resulting potential for common enclosure issues are analyzed.
iii. Discuss the potential for secondary fires and describe how secondary fires are modeled (fire size, zone of influence, propagation, etc.).
iv. Discuss the potential for High Energy Arcing Faults (HEAFs) to be created as a result of inability to clear fire-induced load faults at the load breaker. Without DC control power being available at the switchgear, circuit breakers upstream may have to clear the fault and those breakers will very likely have a much higher overcurrent setpoint than that required to protect the integrity of the cables being faulted.
NextEra Response a)
Breaker/fuse coordination was addressed by reviewing plant calculations to identify buses, panels, and circuits with coordination concerns that could impact the NFPA 805 analysis for the fire probabilistic risk assessment (FPRA). Plant elementary and wiring diagrams were reviewed to identify cables whose breaker/fuse are not properly coordinated with the supply breaker/fuse.
Cables related to inadequate coordination, when damaged by fire, are assumed to result in the failure of the upstream uncoordinated bus, panel, or circuit. This treatment is considered conservative as not all cable failures would fail and/or prevent recovery of uncoordinated components.
Page 2 of 7
Cable protection, or the ability of protective devices to provide short-circuit protection for power cables, was considered acceptable in the FPRA. Circuits identified as lacking proper short-circuit protection will be addressed by MOD-24 and MOD-26-2 committed to and listed in table S-2 of"Supplement 2 to License Amendment Request 271 Associated with NFPA 805." Risk-informed methods were not used for this failure mode.
Breaker failures due to control circuit damage or power loss is addressed in part (d) of this RAI response.
NextEra Response b)
Circuit failure modes addressed include hot shorts, shorts-to-ground, and open circuits, as applicable.
The scope of this review is described in part (a) of this RAI response.
Cable fire damage to uncoordinated circuits is assumed to result in the failure of the upstream uncoordinated bus, panel, or circuit in the FPRA. The loss of downstream equipment due to cable damage was previously modeled in the FPRA and is retained. This provides a conservative representation in the FPRA model for inadequate coordination because the upstream device may not be failed or could be recovered.
As described in part (a) of this RAI response, short-circuit protection for power cables is assumed adequate in the FPRA.
NextEra Response c)
Cable protection is assumed adequate in the FPRA as described in part (a) of this RAI response; therefore, a secondary fire due to a lack of breaker coordination and/or cable protection is not considered a feasible failure mode in the FPRA.
Secondary fires are considered a possible failure mode for breakers that require external DC control power. FPRA modeling for secondary fires is described in part (d) of this RAI response.
NextEra Response d.i Secondary fire impacts are modeled for all breakers that require external DC Control Power (DCCP) to support overcurrent trip (OCT) protection. This evaluation included all 13.8kV and 4.16kV buses regardless of their function in the NFPA 805 analysis.
Circuit analysis identified cables in breaker's control circuits whose fire-induced failure could result in loss of the breakers' ability to trip in response to an OCT condition. This includes the cables in the breaker's trip scheme and also the DCCP cable supplying the bus containing the breaker.
FPRA logic for the identified breakers was created. The FPRA logic models fire induced faults on the breakers (load cables) and control failures with separate logic for each breaker. Secondary fires can occur when the load cable and the breaker controls are damaged by same fire. The breaker control can be impacted by fire damage to control circuits or loss of DCCP. For instances where a breaker's OCT function could not be ensured, the damage effects were assumed to spread from the fault to the first available upstream supply breaker with available OCT function.
Page 3 of 7
The identified failure logic modeled in the FPRA was used to evaluate failures caused by the lack of overcurrent protection and the resulting loss of credited power supplies. The analysis was evaluated for all compartments. This addressed fire-induced faulting of one or more load circuits at the same time that DCCP has been lost due to fire damage. The FPRA assumes the protection circuits are damaged prior to the load cables which has a conservative potential impact on the FPRA calculated risk.
NextEra Response d.ii The lack of circuit protection and the resulting potential for common enclosure issues are analyzed by identifying the adjacent (common enclosure) cables for each un-isolated faulted cable. The FPRA functions associated with the identified common enclosure cables are failed in the FPRA when associated secondary fires occur. Only a discrete number of secondary fire fault locations are expected to occur per event. No method was developed for predicting the fault locations for secondary fires. It is conservatively assumed that the entire cable run exposed to the high current is faulted and all common enclosure cables from the fault to the power source are considered damaged simultaneously with the primary fire scenario zone of influence (ZOI) damage set. New fire scenarios were not created for the secondary fire damage. The secondary fire failures were added to existing fire scenario damage sets.
NextEra Response d.iii Secondary fires resulting from a loss of overcurrent protection are expected to be generated by a fault drawing enough current to self-ignite the cable. As such secondary fires are modeled using guidance from FAQ 13-0005 "Cable Fires Special Cases: Self-Ignited and Caused by Welding and Cutting." This FAQ concludes that a fire caused by self-ignited cables would be contained within its immediate enclosure.
Consistent with the FAQ, the damage sets for these secondary fires consist of the cables routed in the common enclosures with the cables impacted due to the loss of overcurrent protection. Refer to response (d.ii) of this RAI for more information on the identification of damage sets for common enclosures.
NextEra Response d.iv Fire damage along the electrical cable route was described in part (d.iii) of this RAI response. FPRA assumes faulted load centers without control power are damaged.
A subsequent RAI, received on January 20, 2016, requested the potential cable HEAF damage be added to the FPRA model. This potential HEAF damage is addressed below in response to that request.
Page 4 of 7
PRA RAJ 502 (Modelling licensing limitation to cross-tie the steam supply for the turbine-driven Auxiliary Feedwater (AFW) pumps)
The NextEra letter, dated August 26, 2015, ML15238A870 transmitting Supplement 2 of the Point Beach Nuclear Plant NFPA 805 LAR explains that the Fire PRA was updated to mode/licensing limitations associated with cross-tying the Unit 1 and 2 turbine-driven AFW pump steam supply and discharge. The letter does not identify these limitations or explain whether they are associated with specific conditions, certain accident scenarios, or other factors that might be reflected in the Fire PRA. The letter does explain that "to ensure this modification was not over credited the human reliability analysis rates were increased." It is not clear what the expression "human reliability rates" means, how decreasing "human reliability analysis rates" reflects licensing limitations, and whether this treatment is a departure from NRC guidance on developing Human Error Probabilities. NRC staff notes that this modification appears to have important risk reduction impact.
Briefly describe the licensing limitations associated with this modification and how these limitations were reflected in the Fire PRA.
NextEra Response The licensing limitations associated with opening the TDAFW pump unit cross-tie isolation valves involve the use of the cross-tie in response to a single unit event and the requirement to place the unaffected unit in a technical specification action condition. Utilizing the cross-tie places an unaffected unit's AFW system in a configuration that does not comply with the technical specifications and accident analysis for that unit. The ability to use this cross-tie to mitigate a total loss of heat sink event on one unit and entering a limiting condition for operation action condition on an unaffected unit would require prior NRC approval.
The Point Beach Nuclear Plant FPRA credits operator action to cross-tie the steam supply and discharge for the 1 P-29 and 2P-29 TDAFW pumps. This is a cross-unit cross-tie. Procedure changes have not been finalized; therefore, "human reliability rates," more commonly known as Human Error Probabilities (HEP), are not final. In order to provide a reasonable HEP, it was initially assumed in the FPRA that the TDAFW pump cross-tie procedural guidance would be placed in the Critical Safety Procedures (CSPs) for response to loss of secondary heat sink. However, because prior NRC approval would be required to revise certain procedures, the HEP values have been conservatively adjusted to reflect the potential that procedural guidance may not be available in all cases. For fires in the Control Room (fire zone 326), Cable Spreading Room (fire zone 318), or the 4160 Volt Vital Switchgear Room (fire zone 305), the HEP values are expected to remain close to the value calculated for the CSPs regardless of the actual procedures containing guidance. All of the other fire zones could have a different HEP depending on the procedure used, if any, and the timing for the operator actions. To provide margin, a screening HEP is used for these other fire zones to account for potentially longer timing, other less favorable performance shaping factors and lack of procedure guidance.
Once procedures are finalized, the TDAFW cross-tie HEPs will be revised as necessary per implementation item 142, consistent with the existing HEP methodology used in the NFPA 805 submittal and the overall risk impact will be assessed (Ref. NextEra Energy letter to NRC, NRC 2015-0057, "Supplement 2 to License Amendment Request 271 Associated with NFPA 805",
dated August 26, 2015, AttachmentS Item IMP-142).
HEAF: Based on discussions between the NRC staff and the licensee, the impact of High Energy Arcing Faults (HEAFs) in cable trays as a result of fire-induced loss of DC control power and fire induced fau/t(s) of medium voltage load cables has been modeled in accordance with the guidance in FAQ 07-0035 (ADAMS Accession No. ML091610189), which addresses HEAF events in bus ducts.
Page 5 of 7
The NRC staff has several concerns with the use of FAQ 07-0035 for potential electrical faults of medium voltage cables in open cable trays (without top or bottom covers).
- While the staff believes that there may be situations where the use of the model presented in FAQ 07-0035 may be appropriate (those situations where the faulting load cable is routed in conduit), a bus duct enclosure provides a substantial barrier to the energy released in a HEAF. The conditions present in a cable tray are different than a bus duct. Unless the cable tray has top and bottom metal covers, there is substantially more exposure of nearby trays from a HEAF event. Cables damaged as part of the HEAF event can experience significant mechanical forces causing conductors to whip around, potentially causing additional arcing and larger zones of influence.
- The damage footprint created during a HEAF is dependent upon not only the voltage and current available to "feed" the fault, but the duration of the arc event. In the situation created by the loss of DC control power, the duration and energy expended will likely be significantly higher than would otherwise be expected if protective relaying isolates the fault.
There has been a number of HEAF events in the commercial nuclear industry. These events have both similarities and differences when compared to the expected conditions at Point Beach.
- For instance, one industry operating experience event (1115113 cable fault at Beaver Valley; Licensee Event Report (LER) documented at ADAMS Accession No. ML14008A110) involved a self-ignited cable fire on a 4 kV cable in a specially designed cable tray (aluminum tray with both top and bottom covers). The damage footprint of the event was fairly substantial (there was significant collateral damage to nearby cables) but the extent of the damage was limited due to the proper operation of protective relaying. The fault was very quickly isolated as a result of the actuation of a transformer differential relay. The loss of DC control power in the postulated Point Beach scenario means that a breaker upstream of the bus providing the power would have to open, resulting in potentially higher currents and a longer arc duration before isolation. Point Beach also differs from the Beaver Valley event since that cable was run in a cable tray with top and bottom covers.
- Another industry event (3/28/1 0 cable fault at Robinson; Licensee Event Report (LER) documented at ADAMS Accession No. ML101530502) involved a 4 kV cable fault inside a conduit feeding a switchgear unit. The bus feeder providing power to the supplying switchgear had a blown fuse in the trip circuit resulting in.the need to isolate the fault using an upstream breaker (similar to the situation expected at Point Beach). However, although this event involves a degraded distribution system due to the loss of power to the trip circuit of the feeder breaker, it differs from the Point Beach scenario because the faulted cable was routed inside steel conduit. The fault caused significant damage to the conduit (portions of the conduit were blown free/vaporized by the fault) as well as damage to the top of the switchgear unit the conduit entered. Had the conduit not provided a substantial barrier that impeded the damage propagation, a larger zone of influence and more substantial damage footprint would likely have occurred.
- A third industry event (02/03/01 HEAF at San Onofre; Licensee Event Report (LER) documented at ADAMS Accession No. ML0195001 0) involved a circuit breaker fault in a 4 kV switchgear. As a result of the fault, the breaker failed to open, resulting in the need to clear the fault from upstream feeders. At the time of the breaker fault, the bus was being powered from the Unit Aux Transformer Page 6 of 7
(UA T), which sensed both overload and differential overcurrent. Actuation of protective relays isolated the UA T and the main generator. As a result of ionized gases and smoke from the initial breaker fault, the feeder breaker to the Reserve Aux Transformer (RAT) faulted also causing a differential overcurrent trip of the Reserve Aux Transformer (RAT). Although isolated from the grid, the faulted bus continued to be powered from the main generator as the turbine coasted down.
This resulted in the fault being fed electrically for a significant period of time.
Although this event involved a fault inside a switchgear unit, substantial damage occurred outside the switchgear as a result of the duration of the fault. This event forms a significant part of the basis for the recommended zone of influence in NUREG\CR-6850 Appendix M for HEAF events (5' vertical, 3' horizontal from the fault location).
- A fourth industry event (080509 HEAF at Columbia Generating Station; Licensee Event Report (LER) documented at ADAMS Accession No. ML11145A114) involved an electrical fault on a 6. 9 kV bus duct. While this event exhibited a limited zone of influence as a result of the HEAF, the conditions present differ from Point Beach in that the fault occurred inside a bus duct, which provides substantial physical protection between the fault and nearby targets.
As discussed above, each of the operating experience events indicate that there is the potential for larger zones of influence than the guidance in FAQ 07-0035 when applied to HEAFs in cable trays.
Based on the expected conditions at Point Beach for a loss of DC control power combined with a fire-induced fault on 4 kV and/or 13 kV cables, a zone of influence calculated in accordance with NUREG\CR-6850 Appendix M (5' vertical, 3' horizontal) appears to be more appropriate.
Revise your analysis with a zone of influence as calculated in accordance with NUREG/CR-6850 Appendix M (5' vertical, 3' horizontal) for the expected conditions with the loss of DC control power combined with a fire-induced fault on 4 kVand!or 13 kV cables in cable trays and provide an updated Attachment W for the Point Beach LAR using the Appendix M method.
Please provide your written response on the docket to this request and the earlier request dated October 9, 2015, within 30 days of the receipt of this email. In case of any further clarification needed, please arrange a teleconference to discuss the subject matter with the NRC staff. Thanks NextEra Response (HEAF)
The fire modeling and FPRA model have been updated to incorporate an expanded zone of influence (ZOI) for potential high energy arc faults (HEAFs) for secondary fires involving cables with voltage greater than or equal to 4-kV. These expanded ZOis were evaluated for fire scenarios impacting 4-kV and 13-kV cables located in cable trays in instances where a fire scenario causes both a fire-induced fault on the cable and a loss of DC control power to the associate breaker for the power cables. The HEAF potential is considered most likely to occur at the initial fault location in the primary fire ZOI. The ZOI expansion due to the HEAF damage is analyzed for the cables generating secondary fires located in the primary fire ZOI. Guidance in Appendix M of NUREG/CR-6850 was used to define the five foot vertical and three foot horizontal ZOI of the secondary cable HEAF. This expanded damage set is added to the primary fire potentially causing the secondary fire HEAF event An updated Attachment W for the Point Beach LAR is attached that documents the results of the revision to the analysis. This Attachment W includes integrated results for all changes made to the FPRA model as described in the RAI responses and LAR 271 supplement 4.
Page 7 of 7
ATTACHMENT NEXTERA ENERGY POINT BEACH, LLC POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 RESPONSE TO REQUEST FOR ADDITIONAL INFORMATION LICENSE AMENDMENT REQUEST 271 ASSOCIATED WITH NFPA 805 UPDATED ATTACHMENT W, LICENSE AMENDMENT REQUEST 271, TRANSITION TO NFPA 805 33 pages follow Security-Related Information- Withhold from Public Disclosure Under 10 CFR 2.390: