ML113210289
| ML113210289 | |
| Person / Time | |
|---|---|
| Site: | Monticello |
| Issue date: | 11/30/1993 |
| From: | Northern States Power Co |
| To: | |
| Shared Package | |
| ML113210287 | List: |
| References | |
| NUDOCS 9312090229 | |
| Download: ML113210289 (60) | |
Text
Con Ti 9312090229 9311307 PDR ADOCK 05000263 W P
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study TABLE OF CONTENTS SECTION PAGE EXECUTIVE
SUMMARY
m
1.0 INTRODUCTION
1-1 2.0 TOXIC CHEMICAL STUDY METHODOLOGY AND SURVEY RESULTS 2-1 2.1 NRC Regulations for Control Room Habitability.....................
2-1 2.2 Toxic Chemical Survey.......................................
2-8 23 Toxic Chemical Spill Models........................
2-12 2.4 Incapacitation Assessment Criteria..............................
2-16 2.5 Probabilistic Assessment of Chemical Releases from Trucking Accidents 2-18 3.0 FINAL RESULTS 3-1 3.1 Toxic Chemicals Stored Onsite...........................
3-1 3.2 Toxic Chemicals Stored Within Five Miles of the MNGP..............
3-3 3.3 Toxic Chemicals Transported by Truck...........................
3-14 3.4 Toxic Chemicals Transported by Barge...........................
3-14 3.5 Toxic Chemicals Transported by Rail............................
3-15
4.0 REFERENCES
...............................................4-1 4.1 NRC Regulations and Other Regulatory Requirements...............4-1 4.2 Toxic Chemical Survey Information.............................4-2 4.3 Technical and Descriptive References............................
4-3 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study LIST OF TABLES Table 2-1 NRC Regulatory Requirements for Control Room Habitability...
2-3 Table 2-2 Hazardous Chemicals Stored Onsite at the MNGP that Exceed SARA Reportable Limits.........................
2-10 Table 2-3 Chemicals Transported By Rail On The Burlington Northern Line that Equal or Exceed 30 Shipments Per Year.............
2-12 Table 3-1 Final Results for Surveyed Chemicals.......................
3-22 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study EXECUTIVE
SUMMARY
Due to design changes at the Monticello Nuclear Generating Plant (MNGP), chlorine is no longer stored onsite and regulations requiring early warning of onsite chlorine releases do not apply. NSP recognized that removal of onsite chlorine may eliminate the need for the control room HVAC chlorine detectors. A calculation was prepared in 1986 [Ref. 43.27]
to determine if the detectors could be removed. The calculation concluded that Interstate 94 truck shipments of chlorine, using conservative deterministic models, posed a significant enough hazard to warrant the continued use of the detectors.
During subsequent Design Bases Document Program activities it was determined that the original chemical survey was incomplete and that the assumed atmospheric condition (Pasquill Category) was non conservative. Follow-on Items (FOIs) were written [Refs. 4.3.28 and 4.3.29] to document these concerns and an initial assessment was prepared to identify any operability impact or unanalyzed condition.
No operability impact or reportable condition was identified. The completed assessments of the FOIs recommended the survey be formally revised and deterministic analyses be prepared to assure complete and formal resolution of these concerns (see recommended corrective action 2 of FOI 92-0013 and L.a of FOI 92-0037). Additionally, a revised analysis would provide a current basis for deciding if the chlorine chemical detectors were still required. The results of this reassessment are contained in this report.
A new toxic chemical survey was performed which identified toxic chemicals in sufficient quantities stored onsite, stored in the vicinity of the site, or shipped near the plant at sufficient frequency to warrant further evaluation. These toxic chemicals were evaluated in accordance with applicable regulatory requirements. It was deterministically concluded that all chemicals stored onsite and transported near the plant, with the exception of chemical shipments by truck, do not pose a significant threat to control room operators. No early detection equipment is required for postulated chemical releases as sufficient time (at least two minutes) is available for the control room (CR) operators to don protective breathing equipment.
For the case of chemicals transported by truck, a probabilistic model was developed which accounts for the frequency of trucking accidents, hazardous material shipments, and various weather conditions to determine the likelihood of a trucking accident which results in a toxic chemical release.
Calculated probabilities were compared to the criteria of Standard Review Plan (SRP) Section 2.2.3 [Ref. 4.1.5] and USNRC Regulatory Guide (Reg. Guide) 1.70 [Ref. 4.1.12]. Reg. Guide 1.70, Section 2.2.3.1 states: "Design basis events external to the nuclear plant are defined as those accidents that have a probability of occurrence on the order of about 107 per year or greater and have potential consequences serious enough to affect the safety of the plant to the extent that Part 100 guidelines could be exceeded." The SRP indicates that offsite hazardous releases need not be considered if "a conservative calculation showing that the probability of occurrence of potential exposures in excess of the 10 CFR Part 100 guidelines is approximately 10' per year..." This "is acceptable if when combined with reasonable qualitative arguments, the realistic probability can be shown to be lower." The probability of a toxic chemical release from a trucking accident resulting in TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study control room operator incapacitation to the extent that Part 100 guidelines could be exceeded is less than 3.78X10-' per year. This probability was determined with a number of conservatisms in the analysis approach. Therefore, the acceptance criteria of both the Reg. Guide and SRP were demonstrated.
Based on this study, potential hazardous releases from all sources in the survey need not be considered in the design of the MNGP and no special CR HVAC chemical detectors are required.
iv TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study
1.0 INTRODUCTION
Draft Atomic Energy Commission (AEC) 1967 General Design Criterion (GDC) [Ref.
4.1.11] Number 11 requires facilities to provide a "control room from which actions to maintain safe operational status of the plant can be controlled." The criterion also requires that the control room provide adequate radiation protection of personnel during both normal and accident conditions. This criterion is not part of the Monticello Nuclear Generating Plant (MNGP) operating license or design bases as the MNGP design preceded the 1967 draft GDC. However, the MNGP performed a comparative evaluation of the plant design bases with the 1967 draft GDC, and concluded that the MNGP is in conformance with the intent of the draft GDC (see Appendix E of Reference 4.3.21).
Following the Three Mile Island (TMI) accident, the Nuclear Regulatory Commission (NRC) reinforced the requirement of adequate CR operator protection by requiring all plants to perform a Control Room Habitability Study in response to Item lIl.D.3.4 of NUREG-0737 [Ref. 4.1.2]. This study was to evaluate both the effects of postulated toxic chemical spills and post-accident radiation on CR operators. For toxic chemicals where it could not be demonstrated that adequate time exists for CR operator response, special design features such as early chemical detection and CR HVAC automatic isolation were to be provided.
Bechtel Corporation was contracted by NSP to perform the Control Room Habitability Study (Original Study) in response to NUREG-0737 requirements. The Original Study
[Ref. 4.3.1] was completed in 1981 and concluded that four chemicals either shipped on nearby railcars or stored onsite posed a significant enough risk to require detection and automatic CR HVAC isolation. In 1984, Bechtel was again contracted by NSP to re-evaluate the incapacitation effects of the four chemicals using more current modeling techniques [Ref. 4.3.2]. It was concluded that only one of the original four chemicals, chlorine, still required early detection. The principal source of chlorine was onsite as it was used in the water treatment process.
Due to design changes [Ref. 4.3.3] at the MNGP, chlorine is no longer used in water treatment and is no longer stored onsite. Therefore, regulations requiring early warning of potential onsite chlorine releases are no longer applicable. NSP recognized that such a design change may eliminate -the need for the chlorine detectors. An additional calculation was prepared by Bechtel in 1986 [Ref. 4.3.27] to determine if the chlorine detectors were still required. It was concluded that truck shipments of chlorine on Interstate 94 posed a significant enough hazard to warrant continued use of the chemical detectors.
During subsequent Design Bases Document Program activities it was determined that the original chemical survey was incomplete and that the assumed atmospheric condition (Pasquill Category) in the toxic chemical spill calculations was non conservative, i.e., Pasquill Category F was used whereas G is more appropriate for Monticello (worst case category that occurs at least 5% of the time). Follow-on Items 1.1 TENERA
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study (FOIs) were written [Refs. 4.3.28 and 4.3.29],to document these concerns and an initial assessment was prepared to identify any operability impact or unanalyzed condition.
No operability impact or reportable condition was identified.
The completed assessments of the FOIs recommended the survey be formally revised and deterministic analyses be prepared to assure complete and formal resolution of these concerns (see recommended corrective action 2 of FOI 92-0013 and L.a of FOI 92-0037).
Additionally, a revised analysis would provide a current basis for deciding if the chlorine chemical detectors were still required.
This report presents the results of this reassessment. The implemented approach is in accordance with applicable regulatory requirements as outlined in Section 2.1 below.
The remaining parts of Section 2.0 describe the analysis approach and present the survey results.
Final incapacitation assessments are presented in Section 3.0.
References are itemized in Section 4.0.
1-2 TENERA
.-2 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 2.0 TOXIC CHEMICAL STUDY METHODOLOGY AND SURVEY RESULTS The toxic chemical study approach consisted of the following steps:
Define regulatory requirements, Perform a survey to identify hazardous materials, Develop a toxic chemical spill analysis model, Define incapacitation assessment criteria, Determine the probability of a release due to trucking accidents, and Assess the effects of toxic chemical spills on control room operators.
The first five steps, including the results of the survey, are presented below. The effect of various toxic chemical spills on CR operators are presented in Section 3.0.
2.1 NRC Regulations for Control Room Habitability The first step of the study was to review current and past regulations on control room habitability and their applicability to the MNGP license. The objective of this review was twofold: 1) to ensure the approach implemented complies with all applicable regulations, and 2) to determine if any recent regulatory changes have occurred which might provide improved criteria upon which to base this study.
Results of both objectives are presented below.
In summary, the modeling techniques employed have not changed since the Original Study, however, additional tools are now available to model the probabilistic aspect of chemical spills. As shown in Section 3.0, such tools were employed in the evaluation of postulated chemical releases due to trucking accidents in the vicinity of the plant.
NRC regulations on control room habitability are contained in a number of documents including NUREG-0800, Standard Review Plan (SRP) [Ref. 4.1.5], and various regulatory guides (see Table 2-1). These regulations all ultimately refer to 10CFR50 Appendix A General Design Criteria [Ref. 4.1.1] as the basis for implementation. Though MNGP is not a 10CFR50 Appendix A plant (the MNGP design preceded the draft AEC GDC), control room habitability analysis is a requirement as a result of the Three Mile Island (TMI) accident. All plants were required to examine control room habitability for both toxic chemical spills and post design basis accident radiation effects. These requirements are contained in NUREG-0737, Section WI.D.3.4 [Ref. 4.1.2].
The effects of toxic chemical vapors on control room operators depend on a number of factors including chemical type, spill distance from the control room, 2-1 TENERA
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study volume of spill, wind speed, etc. The NRC position on many of these factors is contained in two Regulatory Guides (RGs). These are RG 1.78, "Assumptions for Evaluating the Habitability of a Nuclear Power Plant Control Room During a Postulated Hazardous Chemical Release," June 1974 [Ref. 4.1.3], and RG 1.95, "Protection of Nuclear Power Plant Control Room Operators Against an Accidental Chlorine Release," Revision 1, January 1977 [Ref. 4.1.4]. The accepted NRC model for calculating toxic chemical spill concentrations in the control room is contained in NUREG-0570, 'Toxic Vapor Concentrations in the Control Room Following a Postulated Accidental Release," June 1979 [Ref. 4.1.6]. Additionally, modeling techniques for control room operator incapacitation are contained in NUREG/CR-1741, "Models for the Estimation of Incapacitation Times Following Exposures to Toxic Gases or Vapors," December 1980 [Ref. 4.1.7].
The calculations generated for this study use the criteria of RG 1.78 and the models of NUREG-0570 and NUREG/CR-1741 to select which hazardous materials to model and to assess the potential for CR operator incapacitation.
The probabilistic aspect of the trucking accident calculation used the acceptance criteria of Section 2.23 of the Standard Review Plan, "Evaluation of Potential Accidents," July 1981 [Ref. 4.1.5].
Table 2-1 provides an overview of the existing regulatory documents for control room habitability and discusses the specific requirements of these documents. The table identifies which documents are part of the MNGP license as requirements or as guidance used to meet the. requirements.
TENERA 2-2
M,
.icello Nuclear Generating Plant Toxic Chemical Study Table 2-1 NRC Regulatory Requirements for Control Room Habitability If not MNGP Commitment used Regulatory Document Commitment as Guidance?
Overview of Requirements Atomic Energy Commission (AEC)
No Yes Per 10CFR5O.34.a3.i all nuclear power plants Draft General Design Criteria shall be designed and evaluated during the license Criterion 11 - Control Room: The facility shall be application against a set of Principal Design provided with a control room from which actions to Criteria. As MNGP design was nearly complete maintain safe operational status of the plant can be prior to the issuance of the 1967 draft of controlled. (Abridged) 10CFR5O, Appendix A, General Design Criteria, these criteria are not part of the plant license as a design requirement. However, the MNGP does conform to the intent of the 1967 draft GDC.
Criterion 11 defines requirements for a control room with a safe operating environment. Later regulations, such as RG 1.78 invoke 10CFR5O Appendix A as the basis for their application.
Though this implies such regulatory guides are not part of the plant license, the election to invoke such requirements assures the intent of the Draft AEC GDC and later NUREG-0737 requirements are met.
2-3 UA 0
N ern States Power Company Control Room HAit
'y
M...icello Nuclear Generating Plant Loxic Cnemical Swuy If not MNGP Commitment used Regulatory Document Commitment as Guidance?
Overview of Requirements NUREG-0737 Yes This Toxic Chemical Study is an update of the Section III D3.4. - Control Room Habitability Original Study completed in 1981 to address Requirements NUREG-0737 requirements. As a result of TMI, the NRC required all licensees to re-evaluate control room habitability. This review for previously licensed plants, such as MNGP, was to focus on the effects of the accidental release of toxic gases and radioactive materials. The objective was to demonstrate that control room operators are adequately protected in the event of such accidents, and that the plant could be safely operated or shutdown. The NUREG identified RGs 1.78 and 1.95 as acceptable guidance for meeting CR habitability analysis requirements.
RG 1.78, "Assumptions for Evaluating the Habitability No Yes This RG provides the guidelines for performing of a Nuclear Power Plant Control Room During a the toxic chemical analysis. It specifically outlines Postulated Hazardous Chemical Release," June 1974 a position acceptable to the NRC for selecting and analyzing the effects of hazardous chemical spills on CR operators.
The RG provides acceptance criteria when, if met, require no special automatic detection or HVAC control equipment installation. Specifically, if there is at least two minutes between the time that the toxic chemical is detected in the control room and the control room operators become incapacitated, no special monitoring or control equipment is required. Two minutes is considered sufficient time for a trained operator to don any necessary protective breathing apparatus.
TENERA 2.4 Control Room liabit.
.ly N
ern States Power Company
lk.ticello Nuclear Generating Plant Toxic Chemical Study If not MNGP Commitment used Regulatory Document Commitment as Guidance?
Overview of Requirements RG 1.95, "Protection of Nuclear Power Plant Control No This RG was issued to provide guidance on how Room Operators Against an Accidental Chlorine to design acceptable CR operator protection from Release," Revision 1, January 1977.
postulated onsite chlorine releases. If chlorine is stored onsite, the RG indicates (a) the control room is to be capable of being isolated on a high chlorine level, (b) chlorine detectors shall be installed, (c) the chlorine detectors should meet single failure criteria, be qualified Seismic Category I, and be environmentally qualified "for all expected environments that could clearly lead to or be a result of a chlorine release." In addition, technical specification limits were to be specified.
Through part of the original study, this RG no longer applies to the MNGP since chlorine is no longer stored onsite. This is a result of a design change that replaced chlorine as the biocide agent for the cooling water system with a sodium bromide, sodium hypochlorite mixture (see Design Modification 86Z035, Rev. 2, [Ref. 4.33]).
RG 1.70, "Standard Format and Content of Safety No Yes Though the MNGP has no explicit commitment to Analysis Reports for Nuclear Power Plants,"
meet this RG, it does provide acceptance criteria Revision 3, November 1978.
for use when evaluating new plant Final Safety Analysis Reports. The RG indicates a probability of 10'/year as the cutoff for considering man made external event hazards in power plant design.
2.S T
4 l"
tern States Power Company Control Room Habif
.ty
fP *tern States Power Company Control Room Habit ty TENERA 2.6 Ms..(ticello Nuclear Generating Plant Toxic Chemical Study If not MNGP Commitment used Regulatory Document Commitment as Guidance?
Overview of Requirements NUREG-0800, "Standard Review Plan" (SRP),
No Yes Though the MNGP has no explicit commitment to Revision 2, July 1981 meet these sections of the SRP, they do outline Section 2.2.1-2.2.2, "Identification of Potential Hazards guidance to be used by the NRC in the review of in Site Vicinity" license applications. Hence, they were reviewed to ensure the intent was being met. This section of the SRP requires that for every site, a review be performed to identify potential hazards. These hazards are to include external hazards or hazardous materials that could present a problem to the plant. This review is to encompass a five mile radius of the plant.
Section 2.2.3, "Evaluation of Potential Accidents" This section of the SRP discusses the offsite toxic accidents as an initiating event that could impact control room habitability and potentially result in offsite dose releases to the general public. The intent of this section is to provide guidance to determine what type of potential accidents need to be considered. This determination is based on the expected occurrence rate for the accident. The objective is to show that "the potential for causing onsite accidents leading to the release of significant quantities of radioactive fission products, and thus pose an undue risk of public exposure" is significantly low. Significantly low is defined as an occurrence rate of approximately 1076 per year when combined with reasonable qualitative arguments.
NUREG-0570 No Yes This NUREG describes an NRC accepted "Toxic Vapor Concentrations in the Control Room approach for determining toxic chemical vapor Following a Postulated Accidental Release," June 1979 concentrations both outside and inside the control room.
M..icello Nuclear Generating Plant Toxic Chemical Study If not MNGP Commitment used Regulatory Document Commitment as Guidance?
Overview of Requirements NUREG/CR-1741 Models for the Estimation of Incapacitation Times Following Exposures to Toxic Gases or Vapors, December 1980 NUREG/CR-2650 "Allowable Shipment Frequencies for the Transport of Toxic Gases Near Nuclear Power Plants," October 1982.
NUREG/CR-5042 "Evaluation of External Hazards to Nuclear Power Plants in the United States," December 1987 No Yes No Yes No Yes S27 This NUREG provides five modeling techniques for assessing the potential for CR operator incapacitation resulting from toxic chemical exposure. The model selected depends on how the chemical effects a human and how it is ultimately detected. These modeling techniques were used by Bechtel in 1984 [Ref. 43.2] to justify the elimination of all CR HVAC toxic chemical monitors except chlorine.
This NUREG provides more realistic (less conservative) criteria for when evaluation of chemicals, based on shipment frequencies, is required. The NUREG concludes that frequencies of 208 per year for railroad traffic and 1820 per year for truck traffic are more realistic criteria than 30 and 10, respectively, as required by Reg. Guide 1.78. Note: The more restrictive frequency requirements of Reg. Guide 1.78 were used in this analysis.
This NUREG provides a probabilistic evaluation method to deal with the potential for nuclear power plant accidents initiated by external events, including toxic chemical spills.
7TA N
ern States Power Company Control Room IlablL
- !y
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 2.2 Toxic Chemical Survey The objective of this survey was to identify all hazardous materials stored at, shipped to, or near the MNGP and to determine which materials from this survey required further evaluation. The steps employed to determine which materials required modeling for comparison evaluation and the resultant list of hazardous materials are presented below.
The first step in performing the survey was to develop a comprehensive list of hazardous materials. The Original Study used RG 1.78, NUREG-0570 and data provided by the Association of American Railroads and the Committee on Safety of Nuclear Installations Organization to develop a list of hazardous materials. In this study both RG 1.78 and NUREG-0570 were used but the list of hazardous materials from Title 29, Code of Federal Regulations, Part 1910 [Ref. 4.1.9] was used in place of railroad data. This list was used as a basis for confirming that the list of hazardous materials provided by different survey contacts included chemicals defined as hazardous.
The next step in the survey was to perform a review of all fixed sites and shipping routes near the MNGP which may store or transport hazardous materials. The guidance of RG 1.78 was applied to define the scope of this review. In accordance with the Reg. Guide, any hazardous chemicals stored or transported beyond a five mile radius of the plant require no evaluation. Therefore, this review was limited to all transportation routes and fixed sites within the five mile radius. Per the MNGP Emergency Plan drawing [Ref. 4.3.6] these are:
The MNGP (Section 2.2.1)
Monticello area users of hazardous materials (Section 2.2.2) a Truck transport near the MNGP (Section 2.2.3)
The Burlington Northern rail line (Section 2.2.4)
It should be noted that no commercial ship traffic exists on the Mississippi River within five miles of the MNGP [Ref. 4.2.2]. Consequently, commercial shipping and barge traffic were not included in the survey.
The rail company noted above was contacted to obtain information on all hazardous materials transported on routes within five miles of the plant, frequency of shipment, and shipment size. The individual users, local authorities, and state and federal agencies provided hazardous material data for all other transport routes and industry users.
Once the list of chemicals transported and stored was obtained, the remaining criteria of RG 1.78 were applied to determine which chemicals required further 24 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study evaluation.
These criteria include frequency of shipment, stored or shipped quantity and chemical toxicity. The results of this survey are presented below and form the basis for the modeling and comparison evaluations presented in Section 3.0.
2.2.1 Toxic Chemicals Stored Onsite (MNGP)
As required by State and Federal Law, every user of hazardous substances must maintain a list of non-exempt quantities of these substances used at the facility. The "Hazardous Substance Inventory" at the MNGP [Ref.
4.2.7] was used in the survey.
This list identifies substances, storage location, maximum storage capacity, average daily amount and if the substance is SARA (Superfund Amendments and Reauthorization Act) reportable. It should be noted that additional chemicals are stored onsite that are not included on the "Hazardous Substance Inventory." A complete listing of chemicals used at the MNGP is contained in the Chemical Materials and Manufacturers List [Ref. 4.2.8]. This list was reviewed to determine if any chemicals not contained in the "Hazardous Substance Inventory" required evaluation.
It was concluded that none of these chemicals required evaluation because either: 1) They are stored in quantities below the 100 pound limit specified by RG 1.78, or 2) They are stored in enclosed structures that do not interface with the control room air intake or ventilation system. In these cases it is not considered credible that these materials could pose a risk to the control room operators.
During the development of this study it was noted that the SARA Title III Report contains a discrepancy on the size of the propane tank. There is no 1,700 gallon propane tank at Monticello. The actual installed tank is 120 gallons and serves as the pilot light source for the heating boiler. This was confirmed during a plant walkdown.
As this discrepancy was identified, the Monticello Chemistry Department performed an independent walkdown of the site to identify all chemicals stored in quantities in excess of Regulatory Guide 1.78 limits. This walkdown was also performed to resolve Corrective Action 1 of FOI 92-0013 [Ref. 4.3.28].
Results of the study [Ref. 4.3.30] do not change the conclusions of this report or in any way modify the chemical list contained in Table 2-2.
With the exception of propane, Table 2-2 lists all chemicals maintained on the "Hazardous Substance Inventory" stored at the MNGP site in excess of SARA limits and that were further evaluated as noted in subsequent sections of this report.
2-9 TENERA
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study Table 2 Hazardous Chemicals Stored Onsite at the MNGP that Exceed SARA Reportable Limits Chemical Maximum Capacity (per container)
- 1. Diesel Fuel #2
- 2. Sodium Bromide
- 3. Sodium Hypochlorite
- 4. Hydrogen (liquid)
- 5. Nitrogen (liquid & gas)
- 6. Oxygen (liquid)
- 7. Propane (liquid & gas)
- 8. Stoddard Solvent'
- 9. Turbine Oil
- 10. Gasoline'
- 11. Lube Oil 60,000 gallons 2,000 gallons 6,000 gallons 9,000 gallons 9,000 gallons 9,000 gallons 120 gallons (see Section 2.2.1) 110 pounds 10,000 gallons 500 gallons 10,000 gallons Quantity is not SARA reportable. Listed on Hazardous Substance Inventory and included in this table for completeness 2.2.2 Toxic Chemicals Stored Within Five Miles of the MNGP To obtain information regarding industrial producers or users of hazardous materials near the plant, the "Listing of Facilities and 311 Chemicals"
[Refs. 4.2.4 and 4.2.5] was obtained from the Minnesota Department of Public Safety for Wright County and Sherburne County.
This listing identifies all facilities that store SARA reportable quantities of hazardous materials. The listing identifies the facility, the location, and the types and quantities of materials stored. It should be noted that the quantities of material given in the listing are shown as an order of magnitude (e.g. 1,000 to 9,999 pounds, 10,000 to 99,999 pounds, etc.); if the maximum quantity of material for a given range could not be shown to be acceptable, the facility was contacted to determine the actual quantity stored.
All facilities shown on the listing within five miles of the plant were evaluated for their potential threat to the MNGP control room operators.
The results of the evaluation for each facility are given in Section 3.0.
TENERA 2-10
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 2.23 Toxic Chemicals Transported by Truck Within a Five Mile Radius of the MNGP Transport of hazardous materials by truck within a five mile radius of the plant is generally limited to two primary highways: Interstate 94 passes approximately one-half mile southwest of the plant and Highway 10 passes approximately two miles northeast of the plant. Other roadways within five miles of the plant are primarily limited to local service and carry vastly less traffic than these two highways. These other roadways were evaluated and determined to have insignificant risk contributions relative to the two primary highways. The evaluation of the risk to the control room operators posed by truck transport of hazardous materials was performed using probabilistic techniques.
To perform this evaluation, information was obtained from the Federal Highway Administration, the Minnesota Department of Transportation, and the Minnesota Department of Public Safety, regarding truck traffic, accident rates, hazardous spill frequencies, etc. Additionally, information on the proximity and layout of the various highways relative to the control room intake was obtained from Northern States Power Company site drawings. This information was evaluated in Reference 4.3.11, and the results are summarized in Section 3.0 of this report.
2.2.4 Railroad Traffic Within Five Miles of the MNGP The Burlington Northern rail line passes within five miles of the MNGP.
No other rail lines pass within five miles of the plant. The Burlington Northern line travels past the plant on the opposite side of the Mississippi River with a point of closest approach of two miles. From information provided by the railroad line [Ref. 4.2.3], Table 2-3 was compiled. This table identifies the chemicals that are shipped at frequencies equal to or in excess of the RG 1.78 criterion of 30 times per year. The railroad company considers each individual tanker as a separate shipment.
Therefore, the number of shipments shown in Table 2-3 for a particular chemical is conservative as it does not account for the potential of multiple car shipments of a chemical on a single train. Multiple car shipments on a single train would reduce the total number of shipments for RG 1.78 criterion comparisons.
No specific information on the average weight of each shipment could.be obtained from the railroad company. However, a tank car manual [Ref.
4.3.4] was obtained that provides information on chemical shipping weights.
This information was used in various calculations to provide the basis for chemical shipment weights evaluated.
2-11 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Table 2 Chemicals Transported by Rail on the Burlington Northern Line that Equal or Exceed 30 Shipments per Year Chemical Number of Shipments
- 1. Anhydrous Ammonia 736
- 2. Carbon Dioxide, Refrigerated Liquid 34
- 3. Butadiene, Inhibited 1761
- 4. Butane 456
- 5. Isobutane 30
- 6. Liquefied Petroleum Gas 287
- 7. Propane 707
- 8. Propylene 116
- 9. Vinyl Chloride 327
- 10. Ethylene Oxide 30
- 11. Styrene Monomer, Inhibited 82
- 12. Benzene 100
- 13. Denatured Alcohol 844
- 14. Ethyl Alcohol 228
- 15. Ethylene Dichloride 442
- 16. Isopropanol 37
- 17. Methyl Alcohol 620
- 18. Naphtha & Petroleum Naphtha 524
- 19. Flammable Liquid, N.O.S.
36
- 20. Flammable Liquid, N.O.S. (Aromatic Concentrates) 424
- 21. Diesel Fuel 576
- 22. Combustible Liquid, N.O.S.
52
- 23. Sodium, Metal 32
- 24. Sulfur, Molten 3540
- 25. Hydrogen Peroxide 84
- 26. Sodium Chlorate 69
- 27. Chlorine 71
- 28. Phenol 67
- 29. Phosphoric Acid 80
- 30. Acetic Acid, Glacial 93
- 31. Titanium Tetrachloride 70
- 32. Sodium Hydroxide, Solution 285
- 33. Maleic Anhydride 66
- 34. Mixed Loads of Hazardous Materials (TOFC/COFC) 4623
- 35. Hazardous Substance, Liquid, N.O.S.
50
- 36. Hazardous Substance, Liquid, N.O.S. (Diethyl Phthalate) 69
- 37. Hazardous Substance, Liquid, N.O.S. (Contains Creosote) 38
- 38. Hazardous Substance, Solid, N.O.S. (Benzo-A-Pyrene) 75 2.3 Toxic Chemical Spill Models During the initial stages of the study, it was recognized that many chemicals would require further evaluation beyond the application of RG 1.78 shipment frequency criteria.
Two models were developed to determine the buildup rate of a postulated chemical spill in the control room: 1) Model 1 for compressed gases and chemicals whose boiling point is less than ambient temperature and 2) Model TENERA 2-12
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 2 for chemicals with boiling points higher than ambient temperature. These models were used, in combination with appropriate incapacitation models, to determine if the two-minute criteria of RG 1.78 could be met. Not all chemicals identified in Section 2.2 were modeled -
only those chemicals which could not be eliminated from further consideration using the criteria described in Section 2.4 were modeled.
Both toxic chemical models simulate spill release, atmospheric dispersion and eventual buildup in the control room.
These models were developed in accordance with the requirements of NUREG-0570 and are described in detail in TENERA Calculation 1961-2.2-001 [Ref. 4.3.7]. Many conservatisms exist in the models including:
One complete container of the chemical is assumed immediately released in the accident, Wind direction carries the spill directly to the control room intake, Worst case 5% atmospheric dispersion conditions are assumed (Pasquill Category G),
No credit for intervening structures or topology is assumed which would dilute concentration at the control room intake, No credit is assumed for an elevated control room intake which reduces the concentration at the intake, and No credit is assumed for spill absorption or dilution in surrounding ground or water.
Summary descriptions of both models are provided below. Specific equations and design inputs are contained in the detailed TENERA calculations [Refs. 4.3.7 to 4.3.10].
2.3.1 Model 1: Chemicals Whose Boiling Point is Less Than Ambient According to NUREG-0570, two release phenomena are assumed for chemical spills when the chemical boiling point temperature is below ambient temperature.
These phenomena are instantaneous puff and vaporization. Each spill phenomena acts independently. Therefore, each phenomena is modeled separately and the contributions to control room vapor concentration are summed at corresponding time steps.
An ambient temperature of 70*F was used in the calculations [Refs. 4.3.7 to 4.3.10]. However, a significant change in ambient temperature would not change the model applied as chemical boiling points were typically well 2-13 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study below ambient temperature.
Instantaneous Puff:
The percentage of total spill which is instantaneously released depends on the chemical's heat capacity, boiling point, and heat of vaporization. The total amount released is dependent upon the temperature difference between the boiling point and ambient temperature, the above chemical properties, and the total spill mass.
The instantaneous puff assumes the shape of a three dimensional exponential bell curve with the maximum vapor concentration (top of the bell) at the point of spill release. The maximum vapor concentration and puff shape are dependent upon the mass of the instantaneous release, the assumed atmospheric distribution coefficients (Pasquill Category), and the distance to the control room intake. The puff travels in a straight line directly to the control room intake. As no deviation in wind direction is assumed, the problem becomes two-dimensional. The shape of the puff curve is conservatively assumed to remain unchanged during its transport to the control room intake. Therefore, the maximum vapor concentration at the point of release will ultimately reach the control room intake depending on wind speed and distance to CR intake.
Chemical buildup and dissipation in the control room will assume a similar exponential bell shape response over time for an unisolated control room.
How quickly control room vapor concentration increases and dissipates depends upon the air exchange rate of the control room, the shape of the outside CR puff at the intake, and the speed at which the puff passes the CR intake.
Vaporization:
The remaining spill is released through vaporization.
The rate of vaporization depends upon the spill area rate of change, atmospheric and solar heat fluxes, ambient and chemical boiling point temperature difference, and ground and chemical boiling point temperature difference.
The spill area is assumed to spread uniformly outward in a circular fashion to a maximum spill depth of 1 cm. The spill then remains at this maximum area until completely vaporized.
Typically, the spill expands to its maximum area quickly with respect to total time to complete vaporization.
This spill area model is conservative as it assumes no credit for surrounding topology which might impede spill growth. As mass release is largely dependent on spill area, any impediments to spill area growth would slow chemical release rate.
2-14 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Atmospheric dispersion is modeled similar to the instantaneous puff release.
The applicable Pasquill Gifford -Category is combined with distance to spill to determine the appropriate dispersion coefficients.
These coefficients are then combined with the vaporization model, wind speed, spill area model, and remaining spill mass to determine the rate of chemical mass release and its progression to the CR intake.
The vaporization cloud assumes the shape of an exponential bell curve in the dimensional plane perpendicular to the direction of propagation. This shape is similar to the instantaneous puff. However, in the direction of propagation, the cloud shape is different due to the interactive effects of the spill area and vaporization models. The cloud assumes a step function shape at the time of spill release. This step function then grows and finally dissipates over time in an exponential manner until the entire spill has vaporized. An end step function then occurs and the mass release rate drops back to zero.
Control room buildup is modeled using the identical equations implemented for the puff release. Buildup and dissipation in the CR is dependent upon the same factors.
As the vaporization cloud is not instantaneously distributed, like the puff release, its contribution to CR chemical buildup will not take effect until the cloud has traveled to the control room at the wind speed rate. By the time it reaches the control room, detection and corrective actions in response to the instantaneous puff may have already occurred.
If left unisolated, the CR will experience two separate maximums resulting from each release phenomena's contribution. Typically, the higher maximum is contributed by the puff.
2.3.2 Model 2: Chemicals Whose Boiling Point is Greater than Ambient A simpler model was developed for chemicals whose boiling point temperature exceeds ambient temperature.
For these chemicals, only evaporation exists as the mass release phenomena. The evaporation rate is dependent on the chemical's molecular weight, vapor pressure, Reynolds Number, Schmidt Number, diffusion coefficient, spill area model, and ambient temperature. The spill area model, atmospheric dispersion model, and control room buildup model are all identical to those developed for the vaporization release as described above. The remaining terms are combined into one of two equations for calculating mass release for either turbulent or laminar flow. The selection of laminar or turbulent flow is done conservatively by selecting that equation which results in the highest mass release rate. These equations are described in detail in Reference 4.3.7. For evaporation releases the spill will first reach the control room intake only after it is carried by the wind. Due to much slower release rates than chemicals with below ambient temperature boiling points, these TENERA 2-ISs
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study chemicals do not typically pose a threat to CR operators and release over a much longer period.
2.4 Incapacitation Assessment Criteria The final step in the Toxic Chemical Study was to evaluate the chemicals identified in the survey for potential CR operator incapacitation.
A set of incapacitation assessment criteria were developed and applied to each chemical from the final survey described in Section 2.2. These criteria are:
Is the chemical listed in 29CFR Part 1910 as an air contaminant? Also, does the chemical have a TLV or other limit(s) specified by NIOSH in Reference 4.3.5 or by ACGIH in Reference 4.3.20?
Based on other locations and quantities of the chemical, can one bounding location be identified such that other locations/quantities can be eliminated?
Based on known properties of the chemical as compared to spill model results for comparable chemical types, can it be demonstrated that incapacitation will not occur?
Based on spill model results, will the CR chemical concentration exceed the chemical's Threshold Limit Value (TLV) or the Immediately Dangerous to Life or Health (IDLH) Value?
Based on spill model results, will the CR chemical concentration result in incapacitation in less than two minutes using the modeling techniques of NUREG/CR-1741?
Each successive criterion was applied until a result of "no incapacitation" could be demonstrated.
Only those chemicals transported by truck, due to unknown content, required a probabilistic analysis to determine the likelihood of accidental release.
The acceptance criteria used were in accordance with the regulatory requirements outlined in Section 2.1. Final results for all chemicals are presented in Section 3.0 and a more detailed discussion of each incapacitation assessment criteria is provided below.
2.4.1 29CFR Part 1910, NIOSH or ACGIH Listed The first step in determining CR operator incapacitation was to review the list of chemicals from the survey against 29CFR Part 1910. An extensive list of hazardous materials is provided in Title 29 and is in accordance with federal standards. Chemicals identified in the survey which are not listed 2-16 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study as air contaminants in Title 29 were removed from further consideration provided they also were not contained in the 1990 to 1991 American Conference of Governmental Industrial Hygienist (ACGIH) Threshold Limit Value (TLV) Guidelines [Ref. 4.3.20] or in the Pocket Guide to Chemical Hazards by the National Institute for Occupational Safety and Health (NIOSH) [Ref. 4.3.5]. The ACGIH and NIOSH lists were also used to further substantiate the removal of any chemical from further consideration on the basis of 29CFR Part 1910. However, no instance was found where a chemical from the survey was not listed in Title 29 but was listed in ACGIH or NIOSH.
2.4.2 Comparison to Other Locations/Quantities The second step in determining potential CR operator incapacitation was to compare each of the surveyed chemicals against other locations where the same chemical was stored or transported. If a bounding location could be determined based on its distance from the plant and the quantity of chemical present, other locations could be eliminated from further consideration.
2.4.3 Chemical Properties Comparison The third step was to determine if the chemical could be eliminated from further consideration based on its physical properties. This included a review of the chemicals' toxicity and properties which affect mass release.
For example, molten sulfur was not evaluated using the toxic spill models as it has an extremely low vapor pressure and an extremely high boiling point. Though shipped in a heated tank car, the chemical's tendency is towards extremely low dispersion and becomes a solid at ambient temperature.
2.4.4 Spill Model Results Comparison to TLV and IDLH Chemicals which did not meet the first three criteria were modeled and CR concentrations calculated. All calculations were carried out over the first eight hours following the spill. The CR HVAC remained unisolated over the entire period with normal outside air intake rate assumed.
The calculated CR vapor concentration was first compared to its TLV. If it could be shown that for the entire eight-hour period the TLV was not exceeded, incapacitation would not occur and protective breathing equipment would not be required. This acceptance criteria is consistent with RG 1.78.
The TLV is defined by the American Conference of Governmental Industrial Hygienist (ACGIH) as that time weighted average chemical concentration that a worker could be exposed to with no long term health effects. TLVs published by the ACGIH and NIOSH were 2.17 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study used.
For those cases where the TLV was exceeded, a comparison to IDLH values was made.
The IDLH is defined by the NIOSH as that concentration to which a worker may be exposed for 30 minutes without any escape-impairing symptoms or any irreversible health effects. If it could be demonstrated that two minutes subsequent to CR operator detection the IDLH has not been exceeded, it was concluded that incapacitation would not occur. The total time interval of concern was from the point the TLV is first exceeded to two minutes subsequent to detection. This total time span could be more or less than a total time of two minutes, as the TLV could be greater or lower than the concentration at which detection would occur.
This comparison was extremely conservative as-constant exposure at the IDLH value is allowed. In most cases the IDLH was never approached and the total time was well within 30 minutes.
2.4.5 Incapacitation Assessment Using NUREG/CR-1741 Models If TLV or IDLH values were exceeded or could not be found, a comparison using appropriate NUREG/CR-1741 incapacitation models was performed.
NUREG/CR-1741 presents five separate models for determining chemical incapacitation. The selection of which model to implement depends on the properties of the chemical and the biological mechanisms of incapacitation, i.e., concentration or accumulated dose dependent.
If it could be demonstrated through the use of the appropriate model that incapacitation in two minutes subsequent to detection would not occur, the chemical was eliminated from further consideration. Specific incapacitation models and design inputs used are included in the various calculations. These models are identical to those used in the Bechtel reanalysis of incapacitation effects performed in 1984 [Ref. 4.3.2].
2.5 Probabilistic Assessment of Chemical Releases from Trucking Accidents As discussed in Section 3.0, due to a lack of information regarding the types and quantities of hazardous materials transported by truck, a probabilistic study was performed to assess the likelihood of a spill event and the likelihood that the spill would result in control room operator incapacitation. This study conservatively assumed that all hazardous chemicals transported by truck could potentially incapacitate the CR operators. Wind conditions were weighted by their frequency of occurrence using historical meteorological data for the site [Ref. 4.3.16]. This was then combined with state and national data on frequency of trucking accidents and probability of chemical release in an accident [Refs. 4.3.12 and 4.3.13] to determine overall probability of an external event and likelihood of incapacitation.
2-18 TENERA
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study It was further assumed that if CR operator incapacitation occurred, the probability of exceeding 10CFR100 limits is 0.158 per year, consistent with Reference 4.3.15.
Such an assumption gives no credit for operator response prior to incapacitation or response by others. The following formula was developed for determining probability:
Probability of a Release Exceeding 10CFR100 Limits X Number of Trucks per Year
=
Truck Accident Rate per Mile X
Fraction of Trucks Carrying Hazardous Material X
Highway Miles of Risk X
Fraction of Hazmat Accidents Resulting in Release X Fraction of Releases Severe Enough to Cause CR Operator Incapacitation X
Probability of Exceeding 10CFR100/Operator Incapacitation The acceptance criteria of Standard Review Plan Section 2.2.3 [Ref. 4.1.5] and Reg. Guide 1.70 [Ref. 4.1.12] were used to determine if the likelihood of a spill resulting from a trucking accident warranted any special control room design features for operator protection. If it could be shown that the probability of an accident where 10CFR100 limits are exceeded, resulting from a trucking accident, is less than 10' per year or 106 per year with conservative assumptions, special design features are not required.
TENERA 2.x19
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 3.0 FINAL RESULTS The Toxic Chemical Survey identified a number of chemicals that exceeded the screening requirements of RG 1.78.
These chemicals were -evaluated using the assessment criteria of Section 2.4. With the exception of truck shipments, the results are summarized in Table 3-1 and presented below in chemical groupings by locale or transport mechanism similar to Section 2.2. Table 3-1 includes each chemical, identifies the applicable elimination criteria, and summarizes the final analytical results. Each chemical is discussed in more detail below based on the most limiting, conservative, calculation. Many of the chemicals listed below were evaluated in the Original Study and no special detectors were required. The additional bases used in this study further substantiates the conclusion that special detectors for the same chemicals are still not required. However, credit for results of the Original Study was not taken and reanalysis provides added assurance that early detection is not required.
3.1 Toxic Chemicals Stored Onsite The survey identified a total of eleven chemicals stored onsite that are identified in the MNGP "Hazardous Substance Inventory" [Ref. 4.2.7].
Five of these chemicals (sodium bromide, sodium hypochlorite, liquid oxygen, turbine oil, and lube oil) were eliminated from further consideration as they are not identified in 29CFR 1910 or by the ACGIH [Ref. 4.3.20] or NIOSH [Ref. 4.3.5] as toxic and, due to their physical properties, due not pose a risk to operators. The remaining six chemicals are discussed individually below. It should be noted that additional chemicals are stored onsite that are not included on the "Hazardous Substance Inventory." A complete listing of chemicals used at the MNGP is contained in the Chemical Materials and Manufacturers List [Ref. 4.2.8]. This list was reviewed to determine if any chemicals not contained in the "Hazardous Substance Inventory" required evaluation. It was concluded that none of these chemicals required evaluation because either: 1) They are stored in quantities below the 100 pound limit specified by RG 1.78, or 2) Their individual storage quantity is not significantly greater than 100 pounds and they are stored in enclosed structures that do not interface with the control room air intake or ventilation system. In these cases it is not considered credible that these materials could pose a risk to the control room operators.
During the development of this study it was noted that the SARA Title III Report contains a discrepancy on the size of the propane tank. There is no 1,700 gallon propane tank at Monticello. The actual installed tank is 120 gallons and serves as the pilot light source for the heating boiler. This was confirmed during a plant walkdown.
As this discrepancy was identified, the Monticello Chemistry Department performed an independent walkdown of the site to identify all chemicals stored in quantities in excess of Regulatory Guide 1.78 limits. This walkdown was also performed to resolve Corrective Action 1 of FOI 92-0013 [Ref.
4.3.28]. Results of the study [Ref. 4.3.30] do not change the conclusions of this report or in any way modify the chemical list contained in Table 2-2.
3.1 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Diesel Fuel:
Diesel fuel is not specifically identified in 29CFR 1910 or by the ACGIH or NIOSH as toxic. The vast majority of the diesel fuel stored onsite is stored in underground tanks. A rupture of the underground tanks would result in ground seepage and not vapor release. That portion stored above ground is stored in tanks of approximately 500 gallon and 1,500 gallon capacity. The 1,500 gallon tanks are located indoors which would delay and reduce the release rate to the atmosphere. One 500 gallon tank is located outdoors; however, due to its location behind Warehouse #4 and due to the low evaporation rate and low toxicity of diesel fuel, it is considered to pose no threat to the control room operators.
Consequently, diesel fuel was eliminated from further consideration.
Liquid Nitrogen:
Nitrogen is not listed as a toxic material, however, it can act as an asphyxiant by displacing oxygen. It should also be noted that no direct means of nitrogen detection is feasible due to its normal concentration in air. As noted in Reference 4.3.10, conservative modeling methods result in a brief peak CR nitrogen concentration (contribution from the storage tank) of 90,500 ppm. Reference 4.3.25 notes that workplace oxygen levels should equal or exceed 18% (or a 3%
reduction in oxygen concentration). A 3% reduction in oxygen concentration due to nitrogen displacement would correspond to an additional nitrogen concentration of 143,000 ppm. Since the peak nitrogen concentration is well below this value, early detection of nitrogen is not required.
Liquid Hydrogen:
Hydrogen is not listed as a toxic material. It acts as an asphyxiant in a manner similar to nitrogen. As the hydrogen stored onsite is stored in an above ground tank of the same size as the above ground nitrogen storage tank, and since the hydrogen storage tank is located approximately 0.2 miles further from the control room intake than the nitrogen tank, the conclusions reached for nitrogen are considered to bound hydrogen releases.
Propane:
Propane was modeled in Reference 4.3.10. The concentration rises rapidly past the detection level (5,000 ppm) at 14 seconds, past the IDLH level (20,000 ppm) at 16 seconds, reaches 143,000 ppm at 94 seconds, and peaks at 178,000 ppm at 256 seconds. At two minutes subsequent to detection, the concentration is 162,000 ppm.
As noted in Reference 4.3.10, propane acts as a simple asphyxiant.
Although the maximum workplace concentration for asphyxiants of 143,000 ppm (see nitrogen discussion above) is slightly exceeded, the additional oxygen depletion is minor (3.4% at two minutes versus 3% at 143,000 ppm). Also, if the time-weighted-average (TWA) IDLH is considered and conservatively compared 3-2 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study to the peak concentration for two minutes, the result is still below the TWA IDLH of 3.6X10 ppm-sec. These results ai-e considered acceptable since it must be noted that the analysis of Reference 4.3.10 assumed a very conservative, worst case scenario where no credit was taken for dilution caused by building wake effects or elevation effects. Also, an appreciable amount (one minute and twenty seconds) of the two minute response time has passed from the time of detection to the time when 143,000 ppm is exceeded.
Based on the analysis conclusions and the conservatisms built into this worst-case analysis, the onsite propane tank does not pose an incapacitation threat to the CR operators. Therefore, early detection of propane is not required.
Stoddard Solvent:
Stoddard Solvent is stored in a maximum quantity of 110 pounds in a tank in warehouse #5. This quantity is not reportable under SARA Title M requirements.
Due to the quantity stored (which only slightly exceeds the RG 1.78 cutoff criterion of 100 pounds), the storage location, its low vapor pressure (approximately 2 mm Hg), and its relatively high TLV of 500 ppm and IDLH level of 5,000 ppm, stoddard solvent does not pose a risk to CR operators and does not require early detection.
Gasoline:
Gasoline was modeled in Reference 4.3.10. As noted in Reference 4.3.10, the modeling analysis used conservative enveloping values for various components of gasoline to develop the incapacitation analysis. The 30 minute IDLH of the most limiting component is exceeded, however, the CR concentration is still below the IDLH values for the other representative components. If the concentration of the limiting component (without taking credit for dilution in the gasoline mixture) two minutes subsequent to recognition is conservatively assumed to have existed throughout the entire time between exceeding the TLV and two minutes subsequent to recognition (131 seconds), the total dose is 4.11X10' ppm-sec. This is far below the TWA IDLH of the limiting component of 3.6X10' ppm-sec.
Operators will have had sufficient time to don protective breathing apparatus before the TWA IDLH is reached. Therefore, early detection of gasoline is not required.
3.2 Toxic Chemicals Stored Within Five Miles of the MNGP As noted in Section 2.2, the survey obtained listings of hazardous chemicals and their quantities for facilities within five miles of the MNGP. Table 3-1 provides a summary of the chemicals and quantities stored at each facility. Table 3-1 also indicates whether each chemical is listed in 29CFR 1910, ACGIH, or NIOSH, whether each chemical can be eliminated based on other bounding locations and quantities, whether each chemical can be eliminated based on its chemical properties, whether the TLV or IDLH levels are exceeded, and whether greater 3-3 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study than two minutes are available to the operators. Not all of the above evaluations are performed for each chemical; only those evaluations that are necessary to demonstrate that early detection is not required for the specific chemical are performed.
Details of the evaluations for each facility are provided below.
Facility:
Sherburne County Generating Plant (Sherco)
Chemical:
Anhydrous Ammonia:
Eliminated based on bounding case rail shipment.
Ammonia (Hydroxide):
Eliminated based on its not being listed in 29CFR 1910, ACGIH, or NIOSH (hereinafter this will simply be stated as "Not listed"). Also bounded by rail shipment of anhydrous ammonia.
Chlorine:
Eliminated based on bounding case rail shipment.
Sulfuric Acid:
Sulfuric acid was modeled in Reference 4.3.10.
The maximum concentration of sulfuric acid in the CR is 0.001807 ppm. This is significantly below the TLV of 0.25 ppm. Therefore, early detection of sulfuric acid as a result of a spill at the Sherco plant is not required.
Hydrazine (35%):
Approximately 3.5 miles from the Monticello site hydrazine is stored inside a building in a maximum quantity of 690 gallons at 35%
solution (approximately equivalent to 240 gallons of pure hydrazine).
Hydrazine has an IDLH of 80 ppm [Ref. 4.3.5] which equates to approximately 106 mg/m. Based on comparison to the exclusion criteria of Table C-2 of Reg. Guide 1.78 [Ref. 4.1.3], it is concluded that analysis of hydrazine is not required. The result of the analysis for a Type C control room (unisolated with no chemical detectors) is presented below:
TENERA
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study Pasquill G versus F:
106 mg/mn toxicity limit:
CR air exchange rate:
Type C CR 3 to 4 miles:
(From Table C-2)
Decrease maximum storage amount to 40%
Increase storage amount by 106/50
= 2.12 1.2 chgs/hr / 16.5 chgs/hr [Ref.
4.3.7] = 0.073 33,000 lbs or less allowable storage Using the above inputs, the maximum storage amount becomes:
33,000 lbs x 0.4 x 2.12 x 0.073 = 2,043 lbs As the liquid density of hydrazine is almost exactly that of water, 240 gallons is equivalent to 2,047 lbs of hydrazine. In conclusion, further analysis of hydrazine is not required as hydrazine at the maximum storage quantity is approximately that of Table C-2 of Reg. Guide 1.78, the storage location (3.5 miles) exceeds the minimum allowable distance of 3 miles that the above analysis can be applied to, and the material is stored inside a building which further limits and impedes its release should the container fail.
Sodium Hydroxide (50% solution):
Eliminated based on the location 3.5 miles away and the non-volatile properties of NaOH solutions and the consequent lack of significant toxic vapor releases.
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Lime:
Eliminated based on chemical properties. Lime is a solid material with essentially zero vapor pressure. Consequently, no significant toxic vapor releases are postulated.
Gasoline:
Eliminated based on bounding case of gasoline storage at the Pump N-Munch in Monticello.
TENERA 3-5
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Propane:
Eliminated based on bounding case rail shipment.
Carbon Dioxide:
Eliminated based on bounding case rail shipment.
Fly/Bottom Ash:
Eliminated based on chemical properties. Ash is a solid material with essentially zero vapor pressure. Consequently, no significant toxic vapor releases are postulated.
Ethylene Glycol (50% solution):
Eliminated based on chemical properties. Liquid ethylene glycol is not listed. Only ethylene glycol vapor is listed. Further, ethylene glycol has a vapor pressure of 0.06 mm Hg. Consequently, any vapor releases from an ethylene glycol solution at a 3.5 mile distance would be insignificant.
Lube Oil:
Eliminated based on chemical properties. Lubricating oils are not listed and due to their physical properties (e.g. low volatility) they do not present a risk to the CR operators.
EHC Fluid:
Eliminated based on the argument given above for lube oils.
Betz Foamtrol & Flowpro:
These substances are used for material handling treatment. They are stored indoors in small quantities (under 400 gallons), are not listed, and are exempt from SARA reporting requirements.
Consequently, they can be eliminated.
Betz Powerline:
The following three Powerline products are stored in SARA reportable quantities: Powerline 2105, Powerline 2107, and Powerline 2151. All are used as material handling treatments or dust suppressants.
Powerline 2105 is based on a proprietary formula; however, according to its Material Safety Data Sheet 3-6 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study (MSDS) [Ref. 4.2.10], it has no established TLV, has a low vapor pressure (18 mm Hg), and can cause slight skin irritation and moderate eye irritation. It is stored indoors in a maximum capacity of 8,400 gallons. Due to its low toxicity, its low volatility, its storage location and quantity, and its large distance from the MNGP, the effects of a spill of Powerline 2105 will be bounded by releases of larger quantities of more volatile and toxic materials from the BN railroad line. Consequently, Powerline 2105 can be eliminated.
Powerline 2107 is made up of sodium olefin sulfonate and ethyl alcohol per its MSDS [Ref. 4.2.10].
It is stored indoors in a maximum capacity of 12,800 gallons. Sodium olefin sulfonate has no established TLV. Ethyl alcohol releases are bounded by releases from the BN railroad line which is much closer to the MNGP and which transports larger quantities.
For these reasons and the reasons given above for Powerline 2105, Powerline 2107 can be eliminated.
Powerline 2151 is made up of heavy naphthenic distillates. It has a TLV of 5 mg/m (oil mist) and a vapor pressure of 10 mm Hg. It is stored indoors in a maximum capacity of 11,000 gallons.
According to its MSDS [Ref. 4.2.10] it is slightly irritating to the skin and eyes. Due to its oil-like physical properties, it has a very low volatility.
For these reasons and the reasons given above for Powerline 2105, Powerline 2151 can be eliminated.
Paints:
Paints are not listed and due to the small quantities (5 gallon containers) can be eliminated.
Painter Solvents:
Eliminated based on bounding case rail shipments of various volatile materials in much larger quantities at much smaller distances.
Facility:
Becker Tom Thumb Chemical:
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
3-7 TENERA
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study Fuel Oil:
Due to similar properties as diesel fuel oil, fuel oil is eliminated for the same reasons.
Gasoline:
Eliminated based on bounding case of gasoline storage at the Pump N-Munch in Monticello.
Facility:
Anderson-Gilyard Chemical:
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Fuel Oil:
Due to similar properties as diesel fuel oil, fuel oil is eliminated for the same reasons.
Gasoline:
Eliminated based on bounding case of gasoline storage at the Pump N-Munch in Monticello.
Propane:
Eliminated based on bounding case rail shipment.
Facility:
Becker Schools Chemical:
Antifreeze:
Antifreeze is typically based on ethylene glycol.
Antifreeze is eliminated based on the bounding case arguments presented above for ethylene glycol stored at the Sherburne County Generating Plant.
Chlorine:
Eliminated based on bounding case rail shipment.
TENERA 3-8
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Fuel Oil:
Due to similar physical properties as diesel fuel oil, fuel oil is eliminated based on the arguments presented above for diesel fuel stored at the MINGP.
Lube Oil:
Eliminated based on chemical properties. Lubricating oils are not listed and due to their physical properties (e.g. low volatility) they do not present a risk to the CR operators.
Facility:
Howe Co.
Chemical:
Aldicarb, Carbofuran, Endosulfan, Phorate, and Terbufos Eliminated based on physical properties, location, and quantities stored. All of the chemicals listed are insecticides and are stored in dry form in containers no larger than 40 gallons per Reference 4.2.11. They are not volatile and due to their distance from the MNGP (approximately 4-5 miles) they pose no threat to the CR operators.
Paraquat:
Eliminated based on physical properties, toxicity, location, and quantities stored. Paraquat is stored in liquid form in containers no larger than 40 gallons. According to the ACGIH, paraquat causes mild irritation of the eyes, nose and throat. It should be noted that paraquat does cause cumulative lung damage and is a suspected teratogen, however, these are long term effects. Due to the small quantity stored, the distance from the MNGP, and the mild acute symptoms resulting from exposure, early detection of paraquat is not required.
Facility:
Tom Thumb #239 Chemical:
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
3-9 TENERA
Northern States Power Company Montie.lln Nuwtler Gnrating Plant Control Room Habitability Toxic Chemical Study Gasoline:
Eliminated based on bounding case of gasoline storage at the Pump N-Munch in Monticello.
Sand Plains Soil Service Chemical; Anhydrous Ammonia:
Eliminated based on bounding case rail shipment.
Barton Sand & Gravel Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Facility:
Bondhus Corp.
Nitrogen (liquid):
Eliminated based on the large distance (greater than 4 miles) and the non-toxic nature of nitrogen which only poses a risk as an asphyxiant. Also, nitrogen stored at the MNGP much closer to the control room intake poses no asphyxiant hazard.
Selenious Acid:
Greater than 4 miles from the Monticello site selenious acid is stored in a quantity less than 1,000 lbs. Selenium compounds have an IDLH of 100 mg/m [Ref. 4.3.5). Based on comparison to the exclusion criteria of Table C-2 of Reg. Guide 1.78 [Ref. 4.1.3], it is concluded that analysis of selenious acid is not required. The result of the analysis for a Type C control room (unisolated with no chemical detectors) is presented below:
Pasquill G versus F:
100 mg/in' toxicity limit:
CR air exchange rate:
Type C CR 4 to 5 miles:
3-10 Decrease maximum storage amount to 40%
Increase storage amount by 100/50
=2 1.2 chgs/hr / 16.5 chgs/hr [Ref.
4.3.7] = 0.073 60,000 lbs or less allowable storage TENERA Facility:
0s Facility:
Chemical:
Chemical:
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Using the above inputs, the maximum storage amount becomes:
60,000 lbs x 0.4 x 2 x 0.073 = 3504 lbs In conclusion, further analysis of selenious acid is not required as the stored quantity is less than that allowed by the Reg. Guide.
Facility:
Sunny Fresh Foods Chemical:
Anhydrous Amnioa:
Eliminated based on bounding case rail shipment.
Carbon Dioxide (liquid):
As discussed in Section 3.5 of this report, carbon dioxide shipments on the rail line do not require analysis as they meet the exclusion criteria of Reg. Guide 1.78 [Ref. 4.1.3] for the amount shipped and the distance to the site. If the results of that analysis are applied to the Sunny Fresh Foods facility which is farther from the site (3.2 miles versus 2 miles for the rail line) the allowable storage quantity can be increased (per Reg. Guide 1.78 Table C-2) by approximately 2.5 (33,000 lbs/13,000 lbs) and still meet the exclusion criteria. The resulting allowable storage quantity exceeds both the maximum amount normally stored and the maximum amount allowed to be stored at this facility (see Table 3-1).
Facility:
Pump-N-Munch Chemical:
Gasoline:
Gasoline is stored in underground tanks of up to 8,000 gallon capacity per Reference 4.2.12. Due to the underground location of the tanks, any leakage or rupture would result primarily in ground seepage with minimal vapor release.
Further, due to the large distance (approximately 3 miles) and the relatively low toxicity of gasoline, no impact on the MNGP is postulated.
Additionally, gasoline stored onsite was deterministically modeled and demonstrated not to result in incapacitation. Consequently, gasoline at this location can be eliminated.
Facility:
Monticello Waste Treatment Plant 3-1 TENERA
Northern States Power Company Monticepllo Nuclear enerating Pnt Control Room Habitability Toxic Chemical Study Chemical:
Chlorine:
Eliminated based on bounding case rail shipment.
Facility:
Minnesota Dept. of Transportation Chemical:
Asphalt:
Eliminated based on the low toxicity and low volatility of asphalt and due to the inability to produce an atmospheric "release" of asphalt due to its physical properties.
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Fuel Oil:
Due to similar physical properties as diesel fuel oil, fuel oil is eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Facility:
Monticello Middle School Chemical:
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Fuel Oil:
Due to similar physical properties as diesel fuel oil, fuel oil is eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Facility:
Pinewood Elementary School Chemical:
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
TENERA 3-12 M-nfl-llo Nuclear Generatina Plant
Northern States Power Company Monticello Nuclear Generating Plant Control Room Habitability Toxic Chemical Study Facility:
Bridgewater Telephone Co.
Chemical:
Sulfuric Acid:
Eliminated based on bounding case quantities/location at Sherburne County Generating Plant.
Facility:
Monticello High School Chemical:
Chlorine:
Eliminated based on bounding case rail shipment.
Fuel Oil:
Due to similar physical properties as diesel fuel oil, fuel oil is eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Facility:
JM Oil Co.
Chemical:
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Fuel Oil:
Due to similar physical properties as diesel fuel oil, fuel oil is eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
Gasoline:
Eliminated based on bounding case of gasoline storage at the Pump N-Munch in Monticello.
Kerosene:
Kerosene is not listed and is not particularly volatile. Due to the large distance (3 miles), the quantity stored (less than 10,000 pounds), and its low toxicity and volatility, kerosene can be eliminated from consideration.
TENERA 3-1
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Facility:
AT&T Chemical:
Sulfuric Acid:
Eliminated based on bounding case of sulfuric acid storage at the Sherco plant.
Facility:
Amoco Oil SS 7399 Chemical:
Gasoline:
Eliminated based on bounding case of gasoline storage at the Pump N-Munch in Monticello.
Facility:
Vision Energy MN Chemical:
Propane:
Eliminated based on bounding case rail shipment.
3.3 Toxic Chemicals Transported by Truck Toxic chemicals transported by truck were evaluated based on probabilistic techniques as documented in Reference 4.3.11. In regard to truck transport of toxic materials, there are two principal highways of concern in the vicinity of the MNGP: Interstate 94 passes approximately one-half mile to the southwest of the site, and Highway 10 passes approximately two miles northeast of the site. As documented in Reference 4.3.11, the probability of a radioactive release from the MNGP in excess of 10 CFR 100 guidelines due to operator incapacitation resulting from a trucking accident on the above mentioned highways is less than 3.78X10 per year. This value is well below the acceptance criterion of approximately 10-6 per year stated in Reference 4.1.5. The actual probability of this event is lower than the value calculated due to conservatisms used throughout the analysis of Reference 4.3.11. Consequently, no actions are required to protect the control room operators from hazardous materials transported by truck.
3.4 Toxic Chemicals Transported by Barge There is no commercial barge traffic on the Mississippi River within a five mile radius of the MNGP [Ref. 4.2.2].
Consequently, no barge shipments were evaluated.
0 3-14 TNR
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 3.5 Toxic Chemicals Transported by Rail The Burlington Northern (BN) rail line constitutes a major source of toxic chemicals transported by the plant. No other active rail lines pass within five miles of the MNGP. The survey results indicate that 38 chemicals carried by the Burlington Northern Railroad past the plant exceed the shipping frequencies of 30 per year defined in RG 1.78. These chemicals are listed in Tables 2-3 and 3-1 and are discussed individually below.
Anhydrous Ammonia:
Anhydrous ammonia was modeled in Reference 4.3.8. The time between detection and incapacitation is 3 minutes 12 seconds. Since this exceeds the 2 minute limit established in RG 1.78, no automatic detection is required.
Carbon Dioxide:
Carbon dioxide is transported in 20,000 gallon containers by rail approximately 2 miles from the Monticello site.
"Carbon dioxide when inhaled in elevated concentrations may act to produce mild narcotic effects" [Ref. 4.3.26] and as such, it has a high IDLH (50,000 ppm). Based on comparison to the exclusion criteria of Table C-2 of Reg. Guide 1.78 [Ref. 4.1.3], it is concluded that analysis of carbon dioxide is not required. The result of the analysis for a Type C control room (unisolated with no chemical detectors) is presented below:
Pasquill G versus F:
Decrease maximum storage amount to 40%
91,462 mg/m' toxicity limit: Increase storage amount by 91,462/50 = 1829 (based on a 50,000 ppm IDLH and molecular weight of 44 g/mole)
CR air exchange rate:
1.2 chgs/hr / 16.5 chgs/hr [Ref. 4.3.7] =
0.073 Type C CR 2 miles:
13,000 lbs or less allowable storage Using the above inputs, the maximum storage amount becomes:
13,000 lbs x 0.4 x 1829 x 0.073 = 694,000 lbs In conclusion, further analysis of carbon dioxide rail shipments is not required as the-shipped quantity is less than that allowed by the Reg. Guide.
Butadiene:
Butadiene was modeled in Reference 4.3.8.
Two minutes subsequent to recognition, the concentration is 170.7 ppm which is well below the TLV of 1,000 3-5 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study ppm. Consequently, early detection is not required.
Butane:
Butane was modeled in Reference 4.3.8. Two minutes subsequent to detection, the CR concentration is 406.4 ppm. This is well below the TLV of 800 ppm.
Therefore, early detection is not required.
Isobutane:
Isobutane was modeled by analyzing butane releases from the BN line. As noted in the modeling results for butane, significantly greater than two minutes are available prior to operator incapacitation. Therefore, early detection of isobutane is not required.
Liquified Petroleum Gas (LPG):
LPG is primarily a combination of butane and propane.
Reference 4.3.8 demonstrates that for butane and propane CR operators have greater than two minutes until incapacitation subsequent to detection. This analysis conservatively assumes detection at a propane concentration of 5,000 ppm. This is much higher than the detection threshold for butane. Also, a foul smelling odorant is typically added to LPG to aid in its detection. Consequently, early detection of LPG is not required.
Propane:
Propane was modeled in Reference 4.3.8. The TLV (1,000 ppm) is first exceeded at 3118 seconds following the release. Two minutes subsequent to detection, the CR concentration is 8377 ppm. At this point, the concentration is decreasing with a peak of 8505 ppm occurring 20 seconds earlier.
The time-weighted-average (TWA) of the IDLH is 3.6X107 ppm-sec. If the peak concentration is conservatively assumed present over the entire period from when the TLV is first exceeded, the TWA for propane is 1.75X10" ppm-sec. This value is well below the IDLH TWA and well below an asphyxiant level. Therefore, early detection of propane is not required.
Propylene:
Propylene was modeled in Reference 4.3.10. Propylene is a simple asphyxiant and consequently must displace a significant quantity of oxygen to pose a threat to the CR operators. Two minutes subsequent to recognition, the concentration is 2,876 ppm.
This is far below the TLV of 143,000 ppm for simple asphyxiants.
Consequently, early detection of propylene is not required.
3-16 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Vinyl Chloride:
Vinyl chloride was modeled in Reference 4.3.8.
Vinyl chloride can be first detected at 20 ppm. Two minutes subsequent to detection the CR concentration has climbed to 853 ppm. Model D of Reference 4.1.7 integrates the curve chemical concentration versus time to determine the incapacitating dose, which for vinyl chloride is 4.5X10' ppm-sec. The lower limit is the time at which the concentration equals the value C0, at which significant and immediate physiological effects are evident. The upper limit is the time at which incapacitation occurs. In this case, the sum within the time interval between reaching a concentration Co and two minutes subsequent is approximately 2.1X10s ppm-sec which is significantly below the incapacitating dose. Therefore, early detection for vinyl chloride is not required.
Ethylene Oxide:
Ethylene oxide was modeled in Reference 4.3.8.
The TLV (1 ppm) is first exceeded at time = 2986 seconds. Recognition occurs (concentration at 490 ppm) at time = 3170 seconds.
Two minutes subsequent to recognition, the CR concentration has. risen to 1352 ppm. The average concentration over the time period beginning at the TLV being exceeded and ending at two minutes subsequent to recognition (about five minutes) is under 700 ppm. Both the average concentration and total time are less than the IDLH of 800 ppm.
Consequently, early detection of ethylene oxide is not required.
Styrene Monomer:
Styrene monomer was modeled in Reference 4.3.9. The peak CR concentration is 10.63 ppm. This is well below the TLV of 100 ppm. Therefore, early detection of styrene monomer is not required.
Benzene:
Benzene was modeled in Reference 4.3.9. The CR concentration two minutes subsequent to recognition is 142.9 ppm. The 30 minute IDLH for benzene is 2,000 ppm. Consequently, the CR operators have sufficient time to don protective breathing gear and early detection of benzene is not required.
Denatured Alcohol:
Denatured alcohol is not listed as a toxic vapor in 29CFR 1910, nor does it have an established TLV in the ACGIH or NIOSH references. Also, the modeling results for other alcohols show acceptable results; it can therefore be concluded that although potentially harmful, denatured alcohol poses no incapacitation threat.
Therefore, early detection is not required.
3-17 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Ethyl Alcohol:
Ethyl alcohol was modeled in Reference 4.3.7. The peak CR concentration is 175 ppm. This is far below the TLV of 1,000 ppm, indicating that CR operator incapacitation will not occur. Therefore, early detection is not required.
Ethylene Dichloride:
Ethylene dichloride was modeled in Reference 43.9. The results indicate a TWA of 61,716.6 ppm-sec which is significantly below the IDLH TWA of 1.8X10' ppm sec. Consequently, early detection of Ethylene dichloride is not required.
Isopropanol:
Isopropanol is transported in identical quantities to ethyl alcohol. Isopropanol has a higher boiling point and a lower vapor pressure than ethyl alcohol.
Consequently, the concentrations obtained from modeling ethyl alcohol can be assumed to be bounding for isopropanol. Isopropanol has a TLV of 400 ppm which is significantly greater than the peak CR concentration of 175 ppm obtained for ethyl alcohol. Therefore, isopropanol does not pose an incapacitation threat and early detection is not required.
Methyl Alcohol:
Methyl alcohol was modeled in Reference 4.3.9. The peak concentration of 478.6 ppm occurs at approximately 5300 seconds (1.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />) following the release. The detection and recognition thresholds for Methyl alcohol are 160 ppm and 690 ppm respectively. Therefore, although recognition will not occur, detection will prompt operator actions. Also, the time required for the peak to be reached should allow notification to the CR operators that a release has occurred. Finally, the IDLH of 25,000 ppm is never approached for Methyl alcohol.
Consequently, early detection is not required.
(Petroleum) Naphtha:
Petroleum naphtha was modeled in Reference 4.3.9. The peak CR concentration is 201.1 ppm. This is well below the TLV of 500 ppm. Therefore, early detection is not required.
Diesel Fuel:
Eliminated based on the arguments presented above for diesel fuel stored at the MNGP.
3.18 TENERA TENERA 3-18
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Metallic Sodium:
This material is a solid at ambient temperature and has an extremely low mass release rate due to a low vapor pressure.
Therefore, early detection is not required.
Molten Sulfur:
Molten sulfur is not listed in NIOSH or ACGIH. Due to the physical nature of sulfur, it is a solid at room temperature and is shipped in a liquid state in heated tank cars. According to Reference 43.23, sulfur has a vapor pressure of only 1 mm Hg at 184*C. As there is no physical means to keep sulfur heated once it has spilled, it does not pose a threat to the CR operators. Therefore, early detection is not required.
Hydrogen Peroxide:
Hydrogen peroxide was modeled in Reference 4.3.9. The peak CR concentration of 5.861 ppm occurs at 5700 seconds (1.6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />) following the release. This concentration exceeds the TLV of 1 ppm, however, the 30 minute IDLH is 75 ppm. Consequently, it can be expected that the CR operators will have:
(30 minutes)-(75ppm/5.861 ppm) = 6.4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> without significant ill effects. It is also reasonable to assume detection will occur and protective actions will be taken prior to reaching the peak concentration given the long time periods involved.
Consequently, early detection of Hydrogen peroxide is not required.
Sodium Chlorate:
This chemical is a solid at ambient temperature and has an extremely low mass release rate due to a low vapor pressure. Therefore, early detection is not required.
Chlorine:
Chlorine was modeled in Reference 4.3.7. A conservative detection level of 1 ppm is used, even though Reference 4.3.24 cites a value of 0.08 ppm.
The concentration in the CR reaches 1 ppm at 2970 seconds following the spill. The incapacitation analysis performed in Reference 4.3.7 indicates that an incapacitating concentration in the CR is reached at 3106 seconds following the spill. The time between detection and incapacitation is 136 seconds (2 minutes and 16 seconds). This exceeds the limit of 2 minutes set in RG 1.78. Because the 2 minute limit is exceeded, early detection for Chlorine is not required.
TENERA 3-19
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study Phenol:
This chemical is a solid at ambient temperature and has a very low mass release rate due to a very low vapor pressure (0.4 mm Hg at S.T.P.). Therefore, early detection is not required.
Phosphoric Acid:
Phosphoric acid was modeled in Reference 43.9. The peak CR concentration is 0.1508 ppm. This is well below the TLV of 0.245 ppm. Consequently, early detection for Phosphoric acid is not required.
Acetic Acid, Glacial Acetic acid was modeled in Reference 4.3.10. Detection occurs at 0.074 ppm at time = 3222 seconds. The TLV (10 ppm) is exceeded at time = 3298 seconds, one minute and 16 seconds later. Although no recognition value is identified, a conservative estimate of ten times the detection threshold results in 62 seconds before the TLV is exceeded. It should be noted, however, that the TLV is an eight hour exposure limit. When the peak concentration of 55.31 ppm is compared to the IDLH value, which signifies that the operators have 30 minutes when exposed to a concentration of 1000 ppm of Acetic Acid to respond and not incur any escape-impairing symptoms or irreversible health effects, it is evident that operators have sufficient time to don protective masks. Therefore, early detection is not required.
Titanium Tetrachloride:
Titanium Tetrachloride is not listed in 29CFR 1910 as an air contaminant, nor is it listed in NIOSH or ACGIH.
According to Reference 4.3.23, titanium tetrachloride is a liquid with a density and boiling point greater than water. It is used commercially to produce smoke screens and, consequently, can be expected to have a low capacity for incapacitation.
Therefore, early detection is not required.
Sodium Hydroxide (solution):
Sodium hydroxide solutions are non-volatile (behaving similarly to water) and have insignificant. release rates for sodium hydroxide vapors.
Consequently, no incapacitation threat is posed to the CR operators and early detection is not required.
Maleic Anhydride:
Maleic anhydride is a non-volatile, solid material at ambient conditions and has an extremely low vapor pressure. As such, there is no potential for significant 3-20 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study airborne releases to travel to the CR intake and pose a threat to the CR operators.
Therefore, early detection is not required.
Flammable Liquid, Aromatic Concentrates, Combustible Liquid, Mixed Loads of Hazardous Materials, Hazardous Liquid, Hazardous Liquid containing Diethyl Phthalate, Hazardous Liquid containing Creosote, and Hazardous Solid containing Benzo-A-Pyrene:
None of these materials are described in sufficient detail to conclusively identify each of their constituents. Also, they are generally not listed in 29CFR 1910 or ACGIH or NIOSH. However, they can reasonably be expected to be bounded in their effects by other materials that are modeled. For example, the flammable liquid, aromatic concentrates, and combustible liquid are expected to be bounded by results for other flammable or volatile materials such as benzene, alcohols, or propane.
For the reasons given above, it can be concluded that these materials pose no incapacitation risk to the CR operators. Consequently, early detection is not required.
3-21 TENERA 3-21
?
hemn States Power Company N...tticello Nuclear Generating Plant Control Room Ilnbi lity Toxic Chiemical Study Final Remjfts for Surveyed Chemicals Chemical Faclifty/
Total uanlity Stored Max Ouanttykn Not Listed i Elmhated~ased Elimiated Baed TLV Not IOXl Not Greater The 2 Pro~bblity Orstece Me4Ave Largest Storage ACGH, NIOSH on Otier Bounding on Chemical Exceeded?
Exceeded?
M~iues Using of Not Exoeedig Container or2GdR 1910?
tLncalkrns anties? Propertes?
LJREGXC4-1741 0F 100n iUnits Toxic: Chemricads
.4 X
.~
- 1. Diesel Fuel MNGS 94.170/84.100 80.000 gallons Yea No yes 0 miles gallons________
- 2. SodUmn Bromide MNGS 2,00Y1.50 2,000 gallons Yes (Nalco Actibrom) 0 miles callons
- 3. Sodim' MNGS 8,OOQ/8.000 8,000 gallons Yes Hypodrlorhes 0 miles gallons_____________
- 4. Hydrogen Qliquld) MNGS 0.000Y.000 9.000 gallons No Yes (5) (Note 1) 0 miles gallons
- 5. Nitrogen MNGS 9,000 gal + 21.644c. 9.000 gallons No No No Yes Piquld end gas) 0 miles G. Oxygen (iqkiud MNGS 9,000.000 9g000 gallons yes No Yes 0 miles gallons_______________
7.Propane MNOS 12Ogal 120 gallons NO NO NO NO yes (liquid end gas) 0 miles________
S. Stoddard Solver MNGS IlO/1lt1be 110,,
NO No Yes 0 miles
- 1. TurbieORs Shero 10(110 82.00 gallons Yes Yes (74)
Ammona 3. miles gall"_____
- 13. Gmasol NShec 1.0C00 300 gallons NoeNoYes (O7Ye
- 3. Mils galloconanss
- 11. Sulfri Aci MNShe 510013.000 1.00gallons Nos No No Ye
- 3. miles galions Toxic chmclsMA kv
-M 3-22
Ilhera States Power Company Mounticello Nuclear Generating Plant Control Room lab,.
jIlly Toxic Chemical Study Chemical F.aciiy/
Total QuanttyStored Max Guantty i Not Lsted In EflmnhatedBased Ellmhalsd Based TLV Not IDHNot GreaterThan 2 Prob~alit1y Distance Max/Ave Largest Storage ACGIH. NiOSH an Olher Bouding - a Chemical Exceeded?
Exceeded?
Minutes Usig of Not Exceeding Container or 29CFA 1910?
Locallons/Ouanitles? Properties?
NUEG/CR-1741 I 0CR 100 Umils
- 16. Hydrazine Sherco 1.035120 gal (35%)
SOO gal (35%)
No No yes (2%& 35% So lutlon 3.5Smiles 393/Zi gal (2%)
2 62 gal (2%)
- 17. Sodium Hydroxide Shewco 8.00013,600 8.000 gallons No No yes (50% Sokluton) 3.5 miles aln 1S. Diesl Fuel
- Sherco, 43.475t280,01)(
40.00 gallons Yes NO Yes
_______________3.5 miles 19 r.Sherco 5.00CV3.000 5.000 ton No No Yes
_____________3.5 miles ton
- 20. Gasoline Sherco 2.50y1.500 2.500 gallons No Yes (56)
____________3.5 milesgaln 2 1. Propane Sherco 10,000/8.000 I0.000gallons No Yes (60)
____________3.5 Miles R
- 22. Carbon Dioxide Sheroo 24.000/14.400 12.000 be No Yea (75)
____________3.5 miles ba
- 23. FlyA~otbrm Ash Sherco not given not given Yea No Yes
_________________3.5 miles_________
- 24. EUhylene Glycol Sheroo 74,000/80.000 40.000 gallons No No Yes (50% Solution)
- 3. Smiles
- 25. Lube Oil Sherco 100.248/64.800 14,450 gallons Yes No Yes
____________3.5 miles aln
- 26. EHC Fld Sheroo I,600/1.600 800 gallons yes No Yes
___________3.5 miles als
- 27. Betz Foarol
- Sherco, 455/273 400 gallons Yes No yes
& Fbowpro 3.5 milesgaln
- 26. Betz Powedlkrte
- Sherco, 33,110/10,848 12.500 gallons yes Yes CVarlous Rail Yes rVarklous) 3.5 miles gallons Shipments)_______
- 29. Paints Sherco 700/592 5 gallons yes No yes
_________3.5 miles aon
- 30. Painter Solvents Sherco 500/MS 65 gallon NO Yes (Varlous Rail 3 Smiles ~~hk~ments
~.................
- 31. Dlead Fuel
.Becker Tom Thumb IlE5-IlEe'tE4-lE5 yes No Yes
____________4-5Smiles be
- 32. FueIl 0 BsckarTommurrb IE4-126,'1E4-tE$
Yes No Yes
____________4-8 milse be
- 33. Gasoline Seker Tom Tumb IE5-1Eej1E4-lE5 No Yes (6
- a. 4-Smiles be 323TE NERA 3-73
N' Ifer States Power Company
- 1. Aiceilo Nuclear Generating Plant Control Room ]lab[,
ity Toxic Chemical btudy Chemical Fclity/
Total COjatity Stored Max Ouwntity Int Not Listed In Elminated Based Ellmhatedgaed TLV Not 10124 Not Greater Then 2 Protaiility Distance Max/Ave Largest Storage ACGIH, NIaSH on Obler Bacxidiig an Chemical Exceeded?
Exceeded?
Mkxies Usig of Not Exceedhg Contlaker or 29CFR 1910?
LocaionsdtOuaittlehl Properties?
NUREGCR-1741 lOaIF I lOGUmils
- 34. Dlesd Fuel Anderson-Ollyad IlE5-lEe/lE4-E5 yes No Yes
___________4-5Smiles lbe 35.FuRiot Adersan-Gilyard IES-lEe'lE4-E5 yes No Yes 4-5 miles Ils_______
- 36. Gasolke Andeorsoni-Gilyard lES-lE~ftE4-1E5 No Yes (56) 4-Smles lbs 37.Proprn Andersan-Gilyard lE4-IESIIE3-lE4 No Yea (60) 4-Smiles lbs
- 38. Arytifreeze BeckerSchools lE2-IE3'0-lE2 No Yes (24) 4.4 miles Ils
- 39.
C2,14*
Becker Schools lP2-iE3M-E2 No Yes (100) 4.4 mites lbs
- 40. FeLM 0 BeckerSchools 1E5-lElIE4-IES Yes No yes
_____________4.4 miles bhe______________________________________
4 1.
Lube 01 Becker Schools IlE2-tE31-lE2 yes No yes
_____________4.4 miles ha__________
~.
- 42. Aldicart, H
eCo.
1E3-1E4rtE2-1E3 Yes No Yes
__________4-Smles R)3(40 gal ms.)
- 43. Cabi~oran Howe Co.
IlE3-IE'11E2-1E3 NO No yes
___________4-Smiles Ill (40 oaf max.)
4.Enodosulffan Howe Co.
1E3-1E4'0-IE2 NO No yes 4-Smiles lbe (40 gal max.)_______
- 45. Paraqual Howe CO.
tE2-1E3M-IE2 No No Yes 4-5Smiles bs (40 nall I.
- 46. Ph orate HOe CO.
1E3-1E4'1E2-1E3 No No yes 4-S miles be (40 gal max.)
47.Tectbulo Howe Co.
IE3-1E411E2-1E3 yes No Yes 4-Smiles bel (40 gal max.)_______________
~~~~~~~
48.DWesel Ful TonThumbI0239 IE3-IE41IE2-1E3 yes No Yes
____________4-Smiles lbe UTA7
'hern States Power Company tv.unficello Nuclear Generating Plant Control Room llab Illy Toic Chemical Qfudr~
Chemical Faility/
Total Cluantfty Stored Max Oluarity in Not Usted In Ellmhatod Based Efimhated Based TLV Not C W Nol GrederThan 2 Probaility Dstance May/Ave Largest Storage ACGH. NIOSH on Obier Bounding on Chemical Excdd?
Exceeded?
Minutes tsig of Not Exceadiing Container of 29CfR 1910?
Locedlcns/uamilles? Properties?
NLREGICRt-1741I 1OCFF 100 Limits
- 49. Gasoline Tom Thumb 0239 lE5-1Ee'IE4-IES No Yes (Sa)
____________4-Smileslb
- 50. Anhydrous Sand PlainsSolltSent lES-lEe/lE4-IlES NO Yea (74)
Ammonia 3.2 miles bs (30.00G aatmax.)______
- 51. DieselFuel BartonSand&Gravel lE4-lE!WIE4-IES Yes No Yes
______________112-Smiles b
- 52. Nitrogent (~Qkpd)
Bondhtus Corp.
tE5-lEejlES-IE6 No Yes (5) yes
______________Over 4 miles be
- 53. Selenlous Acid Bonitaje Corp.
E2 IE:VO-1E2 NO NO Yes
_________Over 4 miles be
- 5. Anihydrous Sunny Fres Foods 1E3 1E411E3-IE4 No Yes (74)
Armonia Ap~prox. 3.2 miles be________
S5. Carbon icloside Sunny FrothFoods IES 1Ee/IE4-IES No No yes Olild)
Prox. 3.2 miles b
SO. Gasoline Pumnp.N stolth IES IEe'IES-IEO OCO00gat No Yes (tO)
Yes
__3.1___
3miles bs (22.000galmax.)
- 57. Chorine Monhi. Waste Plant 1E3-1E4/1E3-1E4 No Yes (100)
____________4.3 miles b
U
- 58. Asphsalt MN/CCIT lE4-1Ef'lE4-IE5 No No Yes 3.7-S miles b3______
- 59. Diesel Fel MN/DOT 1E3-IE4I1E2-1E3 Yes No yes 13.7-Smiles Ibs 60.Fuel 00 MNXICOT IE4-IESIlE3-IE4 Yes IN.
Yes 3.7-Smiles ba 35TE NER A 3-25
V 'hern States Power Company
- h.
icello Nuclear Generating Plant Control Room Ilabl, Aty Toxic Chemical Study Chemica Facility/
Total Quanititorsd Max Otity In Not Lised i Ellmheledamed Ellmhated Based TLV Not Iout Not Greater Than 2 Probaity Distance Max/Ave Largest Storage ACGIH. NIOSN on Othe Bounding on Cemical Exceeded?
Exceeded?
Mirsee Usling of Not Exceeding Container or 29CFR 19 10?
Locallons/Ouanlthies? Properties?
NL.NREOIXR-141 I 0F 1001.1mits
................................................................ 7777 7:7777.7 7 6l.OieselFuel Moni. Middle Scholi 1E2-1EWIE2-1E3 yes No yes 4.8 miles
- 62. Fuel Oil Monti. Middle School IE4-lE.VIE4-IES Yes No Yes
- 4. Smiles b
~........
~~~...
8.: : M
- 63. Fueel Oil Piwod.
Scoo E-IE3/lE2-IE3 yes No Yes Aprx mile mile Og~asoih..
tI o
.E3..........4 N;Y.....
64.aSlice Acid BrigewterTel7Co IE2-IENOl5~E No Ye (15) 3.3 miles lbe
-26
-26 I
hemn States Power Company
?hunficello Nuclear Generating Plant Control Room Ilabl,.iiy Chemical Facility/
Total Qualty Stored Max Oluailty I Not Usted In EllmhatieclBased Ellmhatod Based TLV Not 1311 No Greater Then 2 Probabiity Distance MaxifAve Largest Storage ACO.
NIOSH on Otier Bounding on Chemical Exceeded?
Exceeded?
Minu~tes Using at Not Exceeding Container or 29CFR IQ 10?
Locationsatitites? Propeulie?
NL5ttEX-1741 t0CF lOO1.mits
- 73. Propane Vision Energy MN 1E4-IE~ftE2-iE3 No Yes (80)
__________Greater than 3.2 mile3 los Chemical Faiityl Max Quantity Not Uisted I Etimhated Based Etimhated Based TLV Not OLH Not GreateraT 2
Probabilty Distance Shipped per ACGH, NIOSH on Other BounIdig on Chemical Exceeded?
Exieeed?
Minutes Using of Not Exceeding Contaier or 29CFR 1910?
LocationAdnuantities? Properbes3?
NUR1EG/7-1741 IOCFR I00 Limits T o i
h e m ica ls
~~~
- " ~
N(See Section 3.
)
Toxic Chemicalm ie e
~
',:~
~.5 Shipped by Bail e Re.
.'.~
~.
.~
- s.
Noe(Sem ton 3.4
- 77.
Raile 0350 alN:N e
- 78. Anyobus 33.500 gal No No No.
YesoYe
- 79. LBuadiede 33.5(n gal No No NO No Ye Petroleum Gas
- 80. Propane 33,501) gal NO No No NO Yes al. Propylene 33.500 gal NO No NO Yes
- 82. Vnyt Chkio 24.750 gal No NO NO No No Yes 3.27 TENERA 3-27
V 1siern States Power Company I
licello Nuclear Generating Plant Control Room Ilabi Ity Toxic Chemical caudy Chemical FaciltyI Max Ouantity Not Usted In Ellmhated8med Ellmhatedfamed TLV Not IOLH Not Graer Than 2 Probability Distace Shipped per ACGIH, NIOSH on Other Bounding on Chemical Exceeded?
Exceeded?
Minutes Using of Not Exceeding Container or 29CFR 1910?
LocadlonaJOuantlnest Properties?
NUREOXR-1741 IOCFR 100 Umits
- 83. Ethylene Oxide 33.500 gal No No No No Yes
- 84. Styrene Monomer 20,000 gal No No No Yes
- 85. Buene 20.000 gal No No No No Yes
- 88. Denaured Alchol 29.200 gal Yes No Yes
- 87. Etvyl Alcohol 29,200 gal No No No Yes 88.EthyleDihodd 20.000 gal No No No No Yes
- 89. Isopropmot 29.200 gal No No No Yes
- 90. Me"yl Alcohol 29,200 gal No No No No Yes
- 91. Nphthe 20.000 gal No No No Yes
- 92. Flanmable Lquid 20.000 gal Yes No Yes
- 93. Aromaio 20.000 gal Yes No Yes Concentraes
- 94. Dlesd Fuel 20.000 gal Yes No Yes
- 95. Corbustble Uclik 20.000 gal Yes No Yes
- 96. Metallic Sodim Yes No Yes
- 97. Moti SulUr 13.550 get Yes No Yes
- 98. Hydrogen P 20,000 gal No No No No Yes
- 99. Sodium Cdorde 20.000 gal Yes No Yes 100. Chlorine 90ton No No No No No Yes 101.Phnot 20,000ga No No Yes 3-28 TAU
N'-*hern States Power Company i
.Icello Nuclear Generating Plant Control Room labtL ly
. oxic Chemical Study Chemical Facilityl Max Ouaity Not Usted h Elimbated Based EIlmbated9ased TLV Not IDLH Not Greaderhen 2 Probablity Distame Shipped per ACGiH. NIOSH on Other Bxndig on Chemicd Exceeded?
Exceeded?
Minutes Ushg of Not Exceeding Container or 29CFR 1910?
Locallone/Ouantitles? Properties?
NUREGICR-1741 IOUR IOoUmits 102.Phosphorc Acid 20,003 gal No No No Yes 103. Acetic AcId.
20.000 gal No No No No Yes Glacial 104.Thinlun 20.000 gal Yes No Yes Tetrachloride 10S. Sodium Hydroxid 20,0D gal No No Yes (Solution) 10S. Malec Anydride 20.003 gal No No Yes 107. Mixed Loads of 20.000 gal Yes No Yes HarM__
108. Hazardous Liquid 20.000 gal Yes No Yes 109. Hazardous Liquid 20.000 gal No No Yes (Diehyl Phthalde)
I10.HarerdousUqud 20,000gal Yes No Yes (Contane Creosote 111. Hazardous Solid 20,000 gd No No Yes (Benzo-A-Prn e
- 1. Number moNm in parenheses represents he number corresponding to Ibe bounding chemical loodlonfquentity.
TENERA Notes; 3-29
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study
4.0 REFERENCES
4.1 NRC Regulations and Other Regulatory Requirements 4.1.1 10 CFR 50 Appendix A -
General Design Criteria for Nuclear Power Plants.
4.12 NUREG-0737, "Clarification of TMI Action Plan Requirements," Item III.D3.4, "Control Room Habitability," November 1980.
4.13 Regulatory Guide 1.78, "Assumptions for Evaluating the Habitability of a Nuclear Power Plant Control Room During a Postulated Hazardous Chemical Release," June 1974.
4.14 Regulatory Guide 1.95, "Protection of Nuclear Power Plant Control Room Operators Against an Accidental Chlorine Release," Revision 1, January 1977.
4.1.5 NUREG-0800, "Standard Review Plan," Revision 2, July 1981.
- a. Section 2.2.1-2.2.2, "Identification of Potential Hazards in Site Vicinity."
- b. Section 2.2.3, "Evaluation of Potential Accidents."
- c. Section 6.4, "Control Room Habitability System."
4.1.6 NUREG-0570, 'Toxic Vapor Concentrations in the Control Room Following a Postulated Accidental Release," June 1979.
4.1.7 NUREG/CR-1741, "Models for the Estimation of Incapacitation Times Following Exposures to Toxic Gases or Vapors," December 1980.
4.1.8 NUREG/CR-2650, "Allowable Shipment Frequencies for the Transport of Toxic Gases Near Nuclear Power Plants," October 1982.
4.1.9 29 CFR, Part 1910, Subpart Z, Toxic and Hazardous Substances, Section 1910.1000, Air Contaminants," Revised July 1, 1985.
4.1.10 NUREG/CR-5042, "Evaluation of External Hazards to Nuclear Power Plants in the United States," December 1987.
4.1.11 Draft Atomic Energy Commission General Design Criteria, 1967.
4.1.12 Regulatory Guide 1.70, "Standard Format and Content of Safety Analysis Reports for Nuclear Power Plants," Revision 3, November 1978.
TENERA 4-1
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 4.2.13 Telecon from G. Kellund, TENERA, to Bruce Opp, Burlington Northern Railroad, "Burlington Northern Rail Line South of MNGS," dated February 18, 1993.
42.14 Telecon from G. Kellund, TENERA, to Dave Anderson, Sherburne County Emergency Services Director, "Location of Burlington Northern Line in Sherburne County," dated February 25, 1993.
4.2.15 Telecon from G. Kellund, TENERA, to Richard Latsch, Senior Plant Chemist, Sherco Power Plant, "Chlorine Storage at Sherco Power Plant,"
dated March 1, 1993.
4.2.16 Telecon from G. Kellund, TENERA, to Janelle Reese, Wright County Civil Defense Director, "Location of AT&T Facility in Monticello," dated March 2, 1993.
4.3 Technical and Descriptive References 4.3.1 "Monticello Nuclear Generating Plant -
Main Control Room Toxic Chemical Study," prepared by Bechtel Power Corporation, dated January 1981.
4.3.2 "Monticello Nuclear Generating Station Toxic Chemical Study Incapacitation Study Determination of Monitoring Requirements," prepared by Bechtel Power Corporation, dated May 29, 1984.
4.3.3 MNGP Design Modification 86ZO35, Rev 2, "Replace Chlorination System."
4.3.4 "GATX Tank Car Manual," published by General American Transportation Corporation, Fifth edition, dated February 1984.
4.3.5 Pocket Guide to Chemical Hazards, U.S. Department of Health and Human Services, National Institute for Occupational Safety and Health, September 1985.
4.3.6 Drawing NF-108565-2, "Monticello Emergency Plan Sirens and Contours,"
Revision B, dated November 3, 1992.
4.3.7 TENERA Calculation 1961-2.2-001, "Verification of TOXPUFF and TOXEVAP Lotus 1-2-3 Spreadsheets," Revision 2, April 30, 1993.
4.3.8 TENERA Calculation 1961-2.2-002, "Analysis of Toxic Chemical Spills Using the Lotus 1-2-3 Spreadsheet TOXPUFF," Revision 1, April 26, 1993.
TENERA 4-3
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 4.2 Toxic Chemical Survey Information 4.2.1 Letter from G. Kellund, TENERA, to R. Tobosa, Hazardous Materials Office, Burlington Northern Railroad, "Requesting Information on Hazardous Chemicals Type, Weight, and Frequency of Shipment Past Monticello," dated January 7, 1993.
4.2.2 Letter from G. Kellund, TENERA, to M. Edlund, U.S. Army Corps of Engineers, "Requesting Information on Commercial Ship Traffic on the Mississippi River Near Monticello," (with concurrence signature) dated January 5, 1993.
4.2-3 Letter from M. B. Henry, Director Hazardous Materials, Burlington Northern Railroad, to G. Kellund, TENERA, "Hazardous Materials Shipments in Monticello, Minnesota Area," dated January 21, 1993.
4.2.4 Letter from D. L Anderson, Director of Emergency Services, Sherburne County, to G. Kellund, TENERA, "Listing of Facilities and 311 Chemicals,"
dated January 7, 1993.
4.2.5 Minnesota Department of Public Safety, Emergency Response Commission, "Listing of Facilities and 311 Chemicals" for Wright County, dated November 19, 1992.
4.2.6 Telecopy from Michele Clarizio, Minnesota Department of Public Safety, Emergency Response Commission, to G. Kellund, TENERA, "Codes Table for Title III Section 312 Reporting," dated January 25, 1993.
4.2,7 Monticello Plant, "Hazardous Substance Inventory," dated January, 1992.
4.2.8 Monticello Plant, "Chemical Materials and Manufacturers List," dated February 18, 1993.
4.2.9 Sherburne County Generating Plant, "Hazardous Substance Inventory,"
dated January 22, 1993.
4.2.10 Material Safety Data Sheets for Betz Powerline 2105, 2107, and 2151 dated February 16, 1991, May 31, 1991, and February 16, 1991 respectively.
4.2.11 Telecon from G. Kellund, TENERA, to John Creswell, Howe Co., "SARA Title III Materials Stored at Howe Facilities," dated February 8, 1993.
4.2.12 Telecon from G. Kellund, TENERA, to Jay Clark, B&F Distributing, "Gasoline Storage at Pump-N-Munch Facility in Monticello," dated February 8, 1993.
4-2 TENERA
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 4.3.22 Department of Transportation Coast Guard (CHRIS) Hazardous Chemical Data, October 1978 4.3.23 Handbook of Chemistry and Physics. CRC Press, 55th Edition, 1974-1975.
4.324 Odor Thresholds for Chemicals with Established Occupational Health Standards published by the American Industrial Hygiene Association, copyright 1989.
43.25 Chemical Hazards of the Workplace Nick Proctor & James Hughes, 3rd Edition, published by Von Nostrand Reinhold.
43.26 Documentation of the Threshold Limit Values 4th Edition 1980 (with 1984 Supplemental Documentation), published by the American Conference of Governmental Industrial Hygienists Inc.
4.3.27 Monticello Nuclear Generating Plant Offsite Chlorine Gas Study Summary of Results, prepared by Bechtel Power Corporation, Calculation Number 10040-237-MOO1.
4.3.28 Assessment of Follow-on Item 92-0013, "PCB Filled Transformers Not Included in Study of Onsite Hazardous Chemicals, Among Others." dated January 29, 1993.
4.3.29 Assessment of Follow-on Item 92-0037, "Effects of Pasquill Stability Conditions on MCR Habitability and 10CFR100 Calculations," dated March 24, 1993.
4.3.30 Monticello Nuclear Generating Plant Interoffice Memorandum, "CAR 92 0013-01," from Brian Thompson to Anne Ward, dated June 7, 1993.
(TENERA Project File Number 196101-2.4-054).
TENERA 4-5
Northern States Power Company Control Room Habitability Monticello Nuclear Generating Plant Toxic Chemical Study 4.3.9 TENERA Calculation 1961-2.2-003, "Analysis of Toxic Chemical Spills Using the Lotus 1-2-3 Spreadsheet TOXEVAP," Revision 0, March 15, 1993.
4.3.10 TENERA Calculation 1961-2.2-005, "Analysis of Additional Toxic Chemical Spills", Revision 1, June 10, 1993.
43.11 TENERA Calculation 1961-2.2-004, "MNGP Toxic Chemical Analysis Probability Analysis of Trucking Accidents," Revision 1, April 11, 1993.
4.3.12 'Truck Trends in Minnesota - An Examination of Truck Traffic and Accidents from 1984 thru 1990," July 1991, Truck and Economic Studies Section, Minnesota Department of Transportation.
4.3.13 Publication No. FHWA-RD-89-013, "Present Practices of Highway Transportation of Hazardous Materials," May 1990, U.S. Department of Transportation, Federal Highway Administration.
4.3.14 TENERA Correspondence File 1961-2.4-013, confirmation letter from C.
Dahlin (MN Dept. of Transportation) regarding truck traffic information on Interstate 94 and Highway 10.
4.3.15 NSP Nuclear Analysis Department calculation for MNGP, "Level 1 Sensitivity Studies," Calculation No. II.SMR.90.026.
4.3.16 Monticello Calculation CA-92-012, Attachment 5, "Monticello Toxic Chemical Study Update - Accidental Chlorine Release Analysis,"
Preliminary issue.
4.3.17 U.S. AEC Safety Evaluation for Monticello Nuclear Generating Plant Unit No. 1, Full Term Operating License, February 5, 1973 (DSS Sequence
- HEJ00501).
4.3.18 Monticello Procedures Manual A4, Volume 2, "Chemical Spill/Hazardous Materials Procedures."
4.3.19 Telecon between G. Kellund (TENERA) and W. Martinson (MN DOT),
"Highway Traffic Data on Highways 25 and 75," April 2, 1993.
4.3.20 1990-1991 Threshold Limit Values for Chemical Substances and Physical Agents and Biological Exposure Indices, copyright American Conference on Governmental Industrial Hygienists.
4.3.21 Monticello Nuclear Generating Plant, Updated Safety Analysis Report.
TENERA a