Technical Specifications, Issuance of Amendment Revise TS to Change the Frequency of the Mode 5 Intermediate Range Monitoring Instrumentation Channel Functional Test
ML071210291
Person / Time
Site: Perry FirstEnergy icon.png
Issue date: 04/27/2007
From:
NRC/NRR/ADRO
To:
Wengert, Thomas NRR/DORL 415-4037
Shared Package
ML070580506 List:
References
TAC MD0144
Download: ML071210291 (2)


Text

RPS Instrumentation 3.3.1.1 SURVEILLANCE REQUIREMENTS (continued)

SURVEILLANCE FREQUENCY SR 3.3.1.1.16 Verify Turbine Stop Valve Closure and 24 months Turbine Control Valve Fast Closure Trip Oil Pressure-Low Functions are not bypassed when THERMAL POWER is Ž 38% RTP.

SR 3.3.1.1.17 Calibrate flow reference transmitters. 24 months SR 3.3.1.1.18 ----------------- NOTES--------------

1. Neutron detectors are excluded.
2. For Functions 3, 4 and 5 in Table 3.3.1.1-1, the channel sensors are excluded.
3. For Function 6, "n" equals 4 channels for the purpose of determining the STAGGERED TEST BASIS Frequency.

Verify the RPS RESPONSE TIME is within 24 months on a limits. STAGGERED TEST BASIS SR 3.3.1.1.19 Perform CHANNEL FUNCTIONAL TEST 31 days PERRY - UNIT I 3.3-6 Amendment No. 141

RPS Instrumentation 3.3.1.1 Table 3.3.1.1-1 (page 1 of 3)

Reactor Protection System Instrumentation CONDITIONS APPLICABLE REQUIRED REFERENCED MODES OR OTHER CHANNELS FROM SPECIFIED PER TRIP REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS SYSTEM ACTION D.1 REQUIREMENTS VALUE

1. Intermediate Range Monitors
a. Neutron Flux- 2 3 H SR 3.3.1.1.1 < 122/125 High SR 3.3.1.1.4 divisions of SR 3.3.1.1.6 full scale SR 3.3.1.1.7 SR 3.3.1.1.13 SR 3.3.1.1.15 5 (a) 3 1 SR 3.3.1.1.1 < 122/125 SR 3.3.1.1.13 divisions of SR 3.3.1.1.15 full scale SR 3.3.1.1.19
b. Inop 2 3 H SR 3.3.1.1.4 NA SR 3.3.1.1.15 5 (a) 3 1 SR 3.3.1.1.15 NA SR 3.3.1.1.19
2. Average Power Range Monitors
a. Neutron 2 3 H SR 3.3.1.1.1 < 20% RTP Flux- High, SR 3.3.1.1.4 Setdown SR 3.3.1.1.7 SR 3.3.1.1.8 SR 3.3.1.1.11 SR 3.3.1.1.15
b. Flow Biased 1 3 G SR 3.3.1.1.1 < 0.628 W +

Simulated SR 3.3.1.1.2 63.8% RTP Thermal SR 3.3.1.1.3 and 5 113%

Power- High SR 3.3.1.1.8 RTP(b)

SR 3.3.1.1.9 SR 3.3.1.1.11 SR 3.3.1.1.14 SR 3.3.1.1.15 SR 3.3.1.1.17 SR 3.3.1.1.18 (continued)

(a) With any control rod withdrawn from a core cell containing one or more fuel assemblies.

(b) Allowable Value is ! 0.628 W + 43.5% RTP when reset for single loop operation per LCO 3.4.1, "Recirculation Loops Operating."

PERRY - UNIT 1 3.3-7 Amendment No. 141