Control Rod Block Instrumentation 3.3.2.1 Table 3.3.2.1-1 (page 1 of 1)

Control Rod Block Instrumentation APPLI CABLE MODES OR OTHER SPECIFIED REQUIRED SURVEILLANCE FUNCTION CONDITIONS CHANNELS REQUIREMENTS

1.

Rod Pattern Control System

a.

Rod withdrawal limiter (a) 2 SR 3.3.2.1.1 SR 3.3.2.1.6 SR 3.3.2.1.9 (b) 2 SR 3.3.2.1.2 SR.3.3.2.1.5 SR 3.3.2.1.7 SR 3.3.2.1.9 (C) (c) 2 SR 3.3.2.1.3 b.- Rod pattern controller 1,2 SR 3.3.2.1.4 SR 3.3.2.1.5 SR 3.3.2.1.7 SR 3.3.2.1.9

2.

Reactor Mode Switch-Shutdown Position (d) 2 SR 3.3.2.1.8 (a)

THERMAL POWER > 66.7% RTP.

(b)

THERMAL POWER > 33.3% RTP and

(c)

With THERMAL POWER

  • 19.0% RTP, except during the reactor shutdown process if the coupling of each withdrawn control rod has been confirmed.

(d)

Reactor mode switch in the shutdown position.

I FIFRR.Y - UNIT 1 3.3-19 Amendment No.150