Programs and Manuals 5.5 5.5 Programs and Manuals 5.5.8 ExDlosive Gas and Storage Tank Radioactivity Monitoring Program (continued)

b.

A surveillance program to ensure that the quantity of radioactivity contained in any temporary outdoor tanks not including liners for shipping radwaste is

  • 10 curies, excluding tritium and dissolved or entrained noble gases..

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Explosive Gas and Storage Tank Radioactivity Monitoring Program surveillance frequencies.

.5.5.9 DieselFuel Oil Testing Program A diesel fuel oil testing program to implement required testing of both new fuel oil and stored fuel oil shall be established.

The program shall include sampling and testing requirements, and aciceptance criteria, all in accordance with applicable ASTM Standards.

The purpose of the program is to establish the following:

a.

Acceptability of new fuel oil for use prior to addition to storagetanks by determining that the fuel oil has:

1.

an API gravity or an absolute specific gravity within

limits,
2.

a flash point and kinematic viscosity within limits for ASTM 2D fuel oil, and

3.

a clear and bright appearance with proper color, or a water and sediment content within limits;

b.

Within 31 days following addition of the new fuel oil to storage tanks, verify that the properties of the new fuel oil, other than those addressed in a.. above, are within limits for ASTM 2D fuel oil; and

c.

Total particulate concentration of the fuel oil in the storage tanks is

  • 10 mg/l when tested every 31 days.

The provisions of SR 3.0.2 and SR 3.0.3 are applicable to the Diesel Fuel Oil Testing Program testing frequencies.

(continued)

PERRY - UNIT 1 5.0-13 Amendment No. 146