Text
OfFEN 5501 North State Route 2 First Energy Nuclear Operating Company OkHarbor, Ohio 43449 Mark B. Bezilla 419-321-7676 Vice President - Nuclear Fax: 419-321-7582 Docket Number 50-346 License Number NPF-3 Serial Number 3288 October 6, 2006 United States Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555-0001I
Subject:
Technical Specifications 4.4.5.5.b and 6.9.1.5.b: Report of Steam Generator Tube Inservice Inspection Results Ladies and Gentlemen:
This letter is submitted in accordance with the Davis-Besse Nuclear Power Station, Unit Number 1, Operating License, Appendix A Technical Specifications, Technical Specification Surveillance Requirement 4.4.5.5.b and Administrative Controls requirement 6.9.1.5.b require the FirstEnergy Nuclear Operating Company (FENOC) to.
submit the complete results of each Steam Generator tube inservice inspection. These results are presented in Attachment 1. Attachment 2 describes identification codes used in Attachment 1. Attachment 3 provides a list of any regulatory commitments made in this submittal.
If there are any questions or if additional information is required, please contact Mr. Gregory A. Dunn, Manager - FENOC Fleet Licensing, at (330) 315-7243.
Very truly yours, Attachments cc:
Regional Administrator, NRC Region III NRC/NRR Project Manager NRC Senior Resident Inspector Utility Radiological Safety Board
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 1 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Eddy Current Examination Techniques The tubing in the Once Through Steam Generators (OTSG's) at the Davis-Besse Nuclear Power Station Unit #1 was examined in March, 2006, during the 14th Refueling Outage.
The examinations were conducted by Framatome Technologies to meet the requirements of the Davis-Besse Unit #1 Technical Specifications.
The eddy current examinations were performed utilizing various eddy current probes. The bobbin coil technique was used to perform the standard American Society of Mechanical Engineers (ASME) Code examination for flaw detection. This technique was applied to the complete length of all in-service tubes. The rotating plus point and pancake techniques (RPP) were used to examine specific areas of interest. These areas included upper tube end roll expansion regions, upper tubesheet crevice region, critical areas of tubes bordering the sleeved (lane & wedge) region, non-stress relieved roll transitions, the lower tubesheet crevice region and select dent locations. These techniques were also used to characterize indications of interest reported by the bobbin technique. Both bobbin coil and the pancake coil were used to provide depth sizing of Tube Support Plate wear indications. The largest Tube Support Plate wear indication depths from either technique are reported. Both plus point and bobbin techniques were used to examine tube sleeves.
The rotating plus point probe was applied to the rolled regions and lower sleeve end while the bobbin probe was used to examine the unrolled portion. contains the Eddy Current Identification Codes used in the tables in this attachment.
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page2 o 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS STEAM GENERATOR #1(B3)
Table 1: Number and Extent of Tubes Inspected SG #1:
Examination Number Technique Tubes Extent Inspected Bobbin All In-Service Full Length 15,220 Tubes Bobbin 34% of Sleeves Full Length 73 Tubes Bobbin 100% of Sleeve GMVD Region 39 Tubes Geometric Mean
_____________Distortions (GMDs)
Plus Point 41 % of Sleeve GMD Region 16 Tubes
_________GMDs Plus Point 33% of Sleeves Upper and lower rolls 70 Tubes and parent tube pressure boundary portion just below the lowest sleeve roll, extending approximately 6 inches past the sleeve1 Plus Point 67% of Sleeves Just below the lowest 142 Tubes sleeve roll, extending approximately 6 inches past the sleeve Plus Point and 79% of non Upper Tube Roll 11,856 Tubes Rotating Sleeved In-Service Expansion Area Pancake Coil Tubes including inservice Rerolls; (8) and shop non-stress relieved Roll Expansions (3)
Plus Point and 21% of non Upper tube end to upper 3,152 Tubes Rotating Sleeved In-Service tubesheet exit of non-Pancake Coil Tubes sleeved in-service tubes Plus Point and 100% of In-Service Lower Tube Roll 15,220 Tubes Rotating Tubes Expansion Area Pancake Coil Plus Point and Tubes bordering 15 TSP +/-1 inch and UTS 81 Tubes Rotating the Sleeved Secondary Face -1 inch Pancake Coil Region to + 4 inches Plus Point and Tubes with Flaw-Flaw-Like Indication 205 Locations Rotating Like Indications (i-Area Pancake Coil codes, new TWD and large growth TWDs)
Plus Point and All dent locations Dent Locations 163 Dents Rotating greater than 2.5 Pancake Coil volts by bobbin coil located below 14S
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachmnent 1 Page 3 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table I Continued SG # I Plus Point and All dent indications Dent Locations 397 Dents Rotating greater than I volt Pancake Coil located in non-periphery tubes at
____________and above 14S Plus Point and All dent indications Dent Locations 17 Locations Rotating greater than 0.5 Pancake Coil volts between 1 4S and UTS in the I periphery region I________I___
Plus Point and 20% of Lower Sludge Pile Region at 1120 Tubes Rotating Tube Sheet sludge LTS +3 inches to LTS -3
.Pancake Coil pile Iinches
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 4 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTSG Row Tube Ind Location
%TW Indication
____Count 1-13 1
3 TWD) 08S
+0.61 12 1
1-B3 1
5 TWO 13S
+0.34 8
2 1-13 1
5 TWD 14S
-0.86 8
3 1-13 1
6 TWO 14S
-0.71 9
4 1-13 2
2 TWD 14S
-0.76 6
5 1-B3 2
4 TWD 14S
-0.65 8
6 1-B3 2
27 TWD) 12S
+0.70 14 1 7
1-B3 2
27 TWD 14S
-0.66 10 8
1-B3 3
12 TWO los
+0.50 5
9 1-B3 3
14 TWO ___0S
+0.59 10 10 1-13 3
16 TWO ___0S
+0.62 11 11 1-B3 3
31 TWD 12S
+0.70 4
12 1-B3 4
16 ITWD 10S 1+0.50 6
13 1-B3 4
17 JTWO 10S 1+0.59 10 14 1-B3 4
34 TWD 09S
+0.59 6
15 1-B3 4
39 TWO 12S
-0.57 7
16 1-B3 5
9 TWO 08S
+0.59 5
17 1-B3 5
9 TWD 08S
+0.61 3
18 1-B3 5
12 ITWD 10S 1+0.62 12 19 1-B3 5
13 TWD) l0S
+0.50 7
20 1-B3 5
14 TWD 105
+0.48 12 21 1-B3 5
15 TWD ___lS
+0.55 5
22 1-13 5
16 TWD 105
+0.65 9 1-23 1-B3 5
18 ITWO 10S 1+0.53 12 24 1-B3 5
31 TWO 115
-0. 75 11 25 1-B3 5
44 TWO) 13S
+0.57 9
26 1-B3 6
13 TWO l0S
+0.62 7
27 1-B3 6
17 TWO l0S
+0.64 4
1 28 1-B3 6
19 ITWO 10S 1+0.57 5
29 1-B3 6
22 TWO 14S
+0.50 8
30 1-13 6
39 TWO 09S
+0.65 9
31 1-B3 6
49 TWO 14S
+0.66 7
32 1-B3 6
50 TWO 13S
+0.65 12 33 1-B3 7
10 ITWO l0S
+0.65 2
34 1-B3 7
20 TWO 14S
-0.72 6
35 1-B3 7
35 TWO uiS
-0.75 11 36 1-B3 7
43 TWO 11S
-0.73 9
37 1-B 7
46 TWO) 14S
-0.67 10 38 1-B3 7
50 ITWO 11S
-0.74 10 39
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachment I Page 5 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for OTSG Row Tube -Ind -
Location
%TW Indication S~Count 1-B3 8
6 TWD) 14S
-0.65 14 40 1-B3 8
48 TWO) 115
-0.75 9
41 I-B3 9
41 TWD 14S
+0.71 10 42 1-B3 9
43 JTWD 12S
-0.71 8
43 1-B3 9
52 TWI) 13S
+0.57 9
44 1-B3 9
54 TWO) 14S
+0.68 7
45 1-B3 9
60 TWO) 095
+0.25 6
1 46 1-B3 10 24 TWD 095
-0.82 6
47 1-B3 10 40 ITWO 14S 1+0.66 12 48 1-B3 10 42 JTWO 14S5
+0.64 8
49 1-B3 10 56 TWO 145
-0.62 10 50 1-B3 10 63 TWD) 095
+0.00 9
51 1-B3 10 65 TWO) 115
-0.27 8
52 1-B3 10 65 TWO) 13S
+0.57 11 53 1-B3 10 65 ITWO 145
-0.59 6
54 1-B 110 65 JTWO 14S5
+0.61 9
55 1-B3 11 24 TWO 13S
+0.59 6
56 1-B3 11 44 TWO 145
+0.65 10 57 1-B3 11 48 TWO 08S
+0.68 10 58 1-B3 11 55 TWI) 115
-0.68 8
59 1-B3 11 56 ITWO 14S
+0.64 6
60 1-B3 11 58 TWD) 06S
+0.68 6
61 1-B3 11 58 TWO) 14S
+0.67 6
62 1-13 12 11 TWO 04S
+0.30 5
63 1-B3 12 50 TWO) 08S
+0.66 4
64 1-B3 13 2
ITWO 12S 1+0.58 8
65 1-B3 13 46 TWO 14S
+0.65 10 66 1-B3 13 52 TWO 14S
+0.69 9
67 1-B3 13 57 TWO) 115
-0.73 5
68 1-B3 13 58 TWO 14S
+0.60 7
69 1-B3 14 9 jTWO) 01S
-0.29 4
70 1-B3 14 73 TWO 11S 1+0.28 5
71 1-B3 14 74 TWO 115
+0.71 9
72 1-B3 14 74 TWO) 12S
-0.21 16 73 1-B3 15 2
TWO
.12S
+0.53 6
74 1-B3 15 55 TWO 145
+0.64 7
75 1-B3 15 67 ITWO 09S5
+0.66 6
76 1-B3 15 76 TWO 095
-0.23 4
77 1-B3 15 76 TWO) 13S
+0.63 9
78 1-B3 16 78 TWO) 14S
+0.72 9
79 1-B3 17 77 TWO 6S
+06 5
80
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 6 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTSG Row Tube Ind.
Location
%TW Indication
________Count 1-13 17 79 TWD 09S
-0.41 7
81 1-B3 17 79 TWD 09S
+0.66 6
82 1-B3 17 81 TWD los
+0.58 11 83 1-B3 18 4
JTWD 09S
+0.61 7
84 1-B3 18 47 TWD 115
-0.71 11 85 1-13 18 68 TWD 14S
+0.67 8
86 1-B3 18 79 TWD 09S
+0.61 10 1 87 1-B3 18 80 TWD) 09S
+0.66 8
88 11-B3 18 84 ITWD 13S 1+0.47 12 89 1-B3 19 1
TWD 12S
+0.57 5
90 1-B3 19 15 TWD 08S
+0.41 8
91 1-B3 19 62 TWD 14S
+0.57 7
92 1-B3 19 83 TWD 09S
+0.61 5
93 1-B3 20 2
ITWD 12S
+0.50 5
94 1-B3 20 2
TWD 13S
+0.53 4
95 1-B3 20 41 TWD 095
-0.74 7
96 1-B3 20 79 TWD 09S
-0.72 6
97 1-B3 20 79 TWD 09S
+0.59 13 98 1-B3 20 84 ITWD 09S
+0.24 4
99 1-B3 20 84 TWD uiS
-0.6 7
100 1-B3 21 28 TWD 08S
+0.49 7
101 1-B3 21 68 TWD 14S
+0.56 7
102 1-B3 21 68 TWD 14S
+0.56 8
103 1-B3 21 89 ITWD 105
-0.73 4
104 1-B3 22 5
JTWID 09S
+0.59 14 105 1-B3 22 88 TWD 09S
+0.68 7
106 1-13 22 91 TWD 095
-0.24 9
107 1-B3 23 78 TWD) 08S
+0.55 5
108 1-13 23 80 TWD 14S
+0.60 8
109 1-B3 24 92 ITWD 09S
-0.69 7
110 1-B3 25 97 JTWD 10S
+0.71 7
ill 1-B3 25 97 MAI 15S
-1.25 84 112 1-B3 26 14 TWD 12S
-0.81 8
113 1-13 26 80 TWD 14S
+0.65 5
114 1-B3 27 90 TWD 08S
+0.36 7
115 1-B3 27 96 ITWD 09S
+0.61 5
116 1-B3 27 97 TWO 09S
+0.64 16 117 1-B3 28 94 TWO 08S
+0.25 7
118 1-B3 281 96 TWD 095
+0.68 11 119 1-B3 28 99 TWO 09S
+0.70 5
120 1-B3 28 100 ITWO lOS
+0.60 8
121
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 7 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTSG Row Tube Ind Location
%TW Indication S
~Count 1-B3 29 66 MAA UTE
-0.34 N/A 122 1-B3 29 102 TWO los
+0.64 8
123 1-B3 30 14 SAA UTE
-0.29 N/A 124 1-B3 30 104 JTWO 10S
-0.70 7
125 1-B3 31 98 TWO 07S
-0.71 5
126 1-B3 31 104 TWO 09S
+0.70 5
127 1-B3 33 108 TWO 095
+0.25 7 1128 1-B3 34 4
TWD l0S
+0.48 5
129 1-B3 35 88 1SMA UTE
-0.28 N/A 13 1-B3 36 5
TWO l0S
+0.44 5
131 1-B3 36 91 SMA UTE
-0.29 N/A 132 1-B3 37 7
TWO 095
+0.69 5
133 1-B3 39 4
TWOD 095
+0.63 3
134 1-B3 39 108 ITWO 095
-0.18 6
135 1-B3 39 108 JTWO 09S 1-0.16 3
136 1-B3 40 104 SMA UTE
-0.34 N/A 137 1-B3 40 115 TWO 09S
-0.09 6
138 1-B3 41 108 TWO 09S
-0.27 7
139 1-B3 41 112 TWO 09S
+0.70 4
140 1-B3 41 114 ITWO 055
-0.78 5
141 1-B3 42 106 TWO 08S
+0.65 9
142 1-B3 42 112 TWO 09S
-0.55 6
143 1-B3 43 92 SMA UTE
-0.27 N/A 144 1-B3 43 108 SMA UTE
-0.29 N/A 145 1-B3 43 116 ITWO lOS
+0.55 11 146 1-B3 44 117 TWOD lOS
+0.66 6
147 1-B3 45 30 TWO 06S
-0.83 2
148 1-B3 45 81 TWO 06S
+0.55 10 149 1-B3 45 118 TWO lOS
+0.59
.7 150 1-B3 46 114 ITWO 08S
+0.61 8
151 1-B3 48 121 TWO 08S
-0.38 6
152 1-B3 50 122 TWO 09S
+0.67 6
153 1-B3 52 89 TWO 05S
-0.67 11 154 1-B3 52 120 TWO 07S
-0.43 3
155 1-B3 53 126 ITWO 12S
-0.72 10 156 1-B3 54 1
TWO 11S
-0.85 5
157 1-B3 54 1
TWO 14S
-0.65 8
158 1-B3 54 116 TWO 03S
+0.72 4
159 1-B3 54 125 TWO 10S
+0.67 10 160 11-B3 56 1104 1SAl UTE
-1.48 97 161 11-B3 56 1122 ITWOI 09S 1+0.51 9
162
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 8 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTSG Row Tube Ind Location
%TW Indication Count 1-B3 57 2
TWD 05S
-0.80 5
163 1-B3 57 113 TWD) 08S
-0.48 6
164 1-B3 58 1
TWD 12S
+0.53 5
165 1-B3 60 113 TWD) 03S
-0.65 10 166 1-B3 60 127 TWD 09S
+0.71 8
167 1-B3 60 128 TWD) los
+0.51 16 168 1-B 61 121 TWO 09S
+0.74 8
169 1-B3 61 125 ITWO l0S
+0.45 12 170 1-B3 62 1
TWO 14S
-0.42 7
171 1-B3 62 1
TWO 14S
+0.37 9
172 1-B3 62 128 TWO lOS
+0.72 9
173 1-B3 63 1
SAI 15S
-2.12 18 174 1-B3 63 1
1SAl 15S
-1.81 31 175 1-B3 63 126 TWD 09S
+0.71 10 176 1-B3 64 1
SAl 15S
-3.19 25 177 1-B3 64 1
SAl 15S
-1.03 33 1178 1-B3 64 27 TWO 04S
-0.76 11 179 1-B3 67 1
ITWO 12S5
-0.02 21 180 1-B3 67 48 TWO 03S
+0.62 5
181 1-B3 67 118 TWO 05S
-0.72 4
182 1-B3 68 2
TWO) 12S
+0.32 5
183 1-B3 68 3
TWO) 15S
-0.61 9
184 1-B3 69 2
ITWO 12S
+0.27 13 185 1-B3 69 3
TWO) 12S
+0.62 6
186 1-B3 69 60 TWO 04S
+0.43 7
187 1-B3 69 66 TWO 09S
+0.68 11 188 1-B3 70 2
TWO __12S
+0.43 9
189 1-B3 70 6
ITWO 12S
+0.56 8
190 1-B3 70 14 TWO 12S
+0.30 4
191 1-B3 70 22 TWO 12S
+0.52 6
192 1-B3 70 37 TWO) 06S
+0.41 6
193 1-B3 71 2
TWO 13S
-0.63 7
194 1-B3 71 28 ITWO 11S
+0.44 5
195 1-B3 72 2
TWO 12S5
-0.68 12 196 1-B3 72 10 TWO lOS
+0.45 15 197_
1-B3 72 71 SMA UTE
-0.32 N/A 198 1-B3 73 4
TWO 13S
-0.38 7
199 1-B3 73 9
TWO 12S
+0.58 5
200 1-B3 73 12 TWO 12S
+0.60 7
201 1-B3 74 4
TWO 13S
+0.60 8
202 1-B3 75 39 TWO) 04S
-0.78 3
203
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 9 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTSG Row Tube Ind Location
%TW Indication
_____Count 1-13 77 43 TWD 04S
-0.64 7
204 1-B3 77 68 TWO 03S
-0.17 4
205 1-B3 78 58
,SAI UTE
-1.50 65 206 1-B3 79 3
JTWO 12S
-0.60 4
207 1-B3 79 4
TWD 12S
-0.69 7
208 1-B3 79 57 SAl UTE
-1.13 70 209 1-B3 80 6
TWD 095
+0.42 5
210 1-B3 80 28 TWD 11S
-0.69 4
211 1-B3 80 36 ITWD 12S
-0.54 8
212 1-B3 81 65 TWD 11S
+0.39 3
213 1-13 81 74 SCI LTE
+1.57 72 214 1-B3 81 126 TWO 095
-0.83 4
215 1-B3 82 69 SAA UTE
-0.36 N/A 216 1-B3 83 4
ITWO lOS 1+0.52 6
217 1-13 84 57 TWO 065
-0.59 9
218 1-B3 84 82 SCI UTE
-0.16 93 219 1-B3 86 103 TWO 04S
-0.78 3
220 1-B3 88 3
TWO 09S
+0.65 6
221 1-B 89 126 1SMA UTE
-0.31 N/A 222 1-B3 90 6
JTWO 10S 1+0.54 5
223 1-B3 91 13 JTWO 07S
-0.55 7
224 1-B 92 1
TWO 14S
+0.72 10 225 1-B3 94 1
TWO 08S
-0.54 5
226 1-B3 97 31 TWO 07S
-0.55 8
227 1-B3 97 31 TWO 07S
-0.50 5
228 1-B3 99 42 ITWO 06S
-0.32 11 229 1-B3 99 94 TWO 06S
-0.63 5
230 1-B3 100 45 TWO 06S
+0.53 12 231 1-B3 100 53 TWO 06S
-0.18 8
232 1-13B 101 124 TWO 12S
-0.64 4
233 1-B3 103 46 TWO 06S
-0.66 9
234 1-B3 103 46 TWO 06S
+0.69 10 235 1-B3 103 113 TWO 07S
+0.58 5
236 1-B3 104 70 TWO 06S
+0.50 6
2.37 1-B3 104 121 ITWO 03S 1-0.74 8
238 1-B3 105 119 SVI UTS
+8.25 38 239 1-13 106 65 TWO 06S
+0.15 12 240 1-B3 109 69 TWO 06S
+0.51 8
241 1-B3 109 74 SAl UTE
-1.39 68 242 1-B3 111 6
1TWO1 06S
+0.56 6
243 1-B3 112 171 ITWOI 03S
-0.77 4
244
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 10 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTSG Row Tube
- Ind, Location
%TW Indication S____
Count 1-B3 113 9
TWD 08S
+0.71 7
245 1-B3 114 4
TWD 09S
+0.75 5
246 1-B3 114 56 TWD 07S
+0.33 12 247 1-B 1115 113 JTWD loS
-0.78 4
248 1-B3 115 114 TWD) 07S
-0.72 8
249 1-B3 116 111 TWD l0S
-0.69 3
250 1-B3 117 1
TWD 09S
+0.59 6
251 1-B3 119 105 TWD l0S
+0.70 6
252 1-B3 121 41 ITWD 04S5
+0.50 4
253 1-B3 121 90 JTWD 07S5
+0.58 7
254 1-B 121 105 TWD l0S
-0.65 4
255 1-B3 121 105 TWD) l0S
+0.64 5
256 1-B3 122 6
TWID 08S
-0.26 5
257 1-B3 122 104 TWO l0S
-0.65 14 258 1-B3 123 86 1TWD) 03S
+0.61 8
259 1-B3 123 100 TWO) l0S
+0.60 8
260 1-B3 123 102 TWD l0S
-0.74 10 261 1-B3 124 98 TWO) l0S
+0.61 8
262 1-B3 124 100 TWD) l0S
-0.70 4
263 1-B3 125 99 1TWO) 105
-0.69 8
264 1-B3 126 98 TWD) l0S
-0.74 7
265 1-B3 126 98 TWO) lOS
+0.61 8
266 1-B3 127 49 TWD 09S
-0.76 4
267 1-13 127 77 TWD 105
-0.68 4
268 1-13 128 94 JTWO 10S
-0.64 10 269 1-B3 128 95 TWOD 1S
-0.70 3
270 1-B3 129 9
TWO 06S
+0.73 3
271 1-13 129 93 TWO lOS
-0.67 10 272 1-B3 129 94 TWO) 10S
-0.82 4
273 1-B3 129 94 ITWOD 1S
-0.68 5
274 1-B 130 74 TWO) 05S
+0.00 3
275 1-B3 131 6
TWOD 105
-0.64 8
276 1-B3 131 89 TWO) 12S
-0.33 5
277 1-B 132 6
TWO) 105
+0.71 12 278 1-B3 133 86 TWO 14S
-0.84 6
279 1-B3 134 50 TWO lOS
+0.74 10 280 1-B3 134 78 TWO 105
+0.63 10 281 1-B3 134 84 TWO 12S
+0.55 6
282 1 -B 135 54 TWO 03S
+0.44 6
283 1-B3 135 179 ITWO 06S
+0.57 5
284 1-B3 1351 82 JTWO 12S
+0.55 7177 285
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 11I of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:
OTG owTue d
- Location,
%TW Indication Count 1-B3 136 44 TWD) 07S
+0.36 3
286 1-B3 137 5
TWD 09S
-0.73 7
287 1-B3 138 6
TWD los
+0.62 6
288 1-B3 138 75 JTWD 10S
-0.76 6
289 1-B3 139 7
TWD) 10S
+0.64 10 290 1-B3 140 1
TWD 12S
-0.76 4
291 1-B3 140 2
TWD 12S
-0.66 8
292 1-B3 140 7
TWID 03S
+0.18 6
293 1-B3 141 1
ITWO 12S
-0.68 6
294 1-B3 141 2
TWD 12S
-0.71 5
295 1-B3 141 47 TWD 14S
+0.54 5
296 1-B3 141 65 MAI 15S
-0.83 41 297 1-B3 141 67 TWO 14S
+0.61 9
298 1-B3 141 68 ITWD __14S
-0.79 7
299 1-B3 141 68 JTWO __14S
+0.29 6
300 1-B3 142 56 TWO __03S
+0.36 4
301 1-B3 143 46 TWID __14S
+0.62 3
302 1-13 143 62 SAl 15S
-4.88 25 303 1-B3 145 21 TWO 14S
+0.57 5
304 1-B3 145 30 TWO 03S
+0.64 4
305 1-B3 145 42 TWO 14S
+0.6 3
306 1-B3 147 20 TWO lOS
-0.76 6
307 1-B3 147 25 TWO 09S
-0.86 4
308 1-B3 147 33 TWO lOS
+0.59 7
309 1-B3 148 2
ITWO 14S
+0.64 15 310 1-B3 148 22 TWO 09S
-0.56 4
311 1-B3 148 39 TWOD 12S
+0.59 5
312 1-B3 148 41 TWOD 1S
-0.27 4
313 1-B3 148 41 TWO) 1S
+0.18 4
314 1-B3 149 17 ITWO lOS
+0.60 11 315 1-B3 149 19 TWO 09S
-0.76 3
316 1-B3 149 28 TWO) uS
-0.18 4
317 1-13 149 28 TWO) 12S
+0.62 8
318 1-B3 149 30 TWO
- 10S,
+0.65 5
319 1-B3 149 32 TWO) 12S
+0.20 6
320 1-B3 149 33 TWO 12S
+0.34 6
321 1-B3 150 20 TWOD lOS
+0.60 6
322 1-B3 150 23 TWO 12S
+0.63 6
323 1-B3 150 26 TWD 115
-0.09 4
324 1-B3 150 27 TWD 11S
-0.27 5
325 1-13 150 27 TWO 14S
-0.21 8
326
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 12 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 2: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #1:____
OTSG Row Tube Ind Location
%TW Indication Count 1-B3 151 5
TWO lOS
-0.78 5
327 1-B3 151 5
TWO 12S
+0.56 6
328 1-B3 151 9
TWO 14S
+0.55 8
329 1-B3 151 10 JTWO 14S
+0.14 13 330 1-B3 151 12 TWO) 12S
+0.67 7
331 1-B3 151 13 TWO) 14S
-0.04 17 332 1-B3 151 14 TWO) l0S
+0.88 6 1333 1-B3 151 14 TWO) uS
-0.75 3
334 1-B3 151 116 ITWOI 14S 1-0.74 3
335
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 13 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 3: Identification of Tubes Repaired SG #1:
SIG ROW ITUBE Reason for Repair Tube I
I ICount Repaired by Plugging 1-13 25 97 MAI 15S
-1.25 1
1-13 63 1
SAl 15S
-2.12 2
______SAl 155
-1.81 1-B3 64 1
SAl 155
-3.19 3
______SAl 15S
-1.03 1-13 81 74 SCI LTE
+1.57 4
1-13 105 119 SVI UTS
+8.25 5
1-B 141 65 MAI 15S
-0.83 6
1-B3 143 62 SAl 15S
-4.88 7
Repaired By Hot Leg Reroll_____
1-B3 29 66 MMA UTE
-0.34 1
1-B3 30 14 SMA UTE
-0.29 2
1-B3 35 88 SMA UTE
-0.28 3
1-B 36 91 SMA UTE
-0.29 4
1-B3 40 104 SMA UTE
-0.34 5
1-B 43 92 SAA UTE
-0.27 6
1-B3 43 108 SMA UTE
-0.29 7
1-B 56 104 SAl UTE
-1.48 8
1-B 72 71 SMA UTE
-0.32 9
1-B 78 58 SAl UTE
-1.50 10 1-B3 79 57 SAl UTE
-1.13 11 1-B 82 69 SMA UTE
-0.36 12 1-B 84 82 Sdl UTE
-0.16 13 1-B3 89 126 SMA UTE
-0.31 14 1-B3 109 74 SAl UTE
-1.39 1
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 14 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS STEAM GENERATOR #2 (A)
Table 4: Number and Extent of Tubes Inspected SG-#2:
Examination Number Technique Tubes Extent Inspected Bobbin All In-Service Full Length 14,888 Tubes Bobbin 34% of Sleeves Full Length 68 Tubes Plus Point 33% of Sleeves Upper and lower rolls 66 Tubes and parent tube pressure boundary portion just below the lowest sleeve roll, extending approximately 6 inches
_______________past the sleeve Plus Point 67% of Sleeves Just below the lowest 133 Tubes sleeve roll, extending approximately 6 inches past the sleeve Plus Point and 79% of non Sleeved Upper Tube Roll 11,604 Tubes Rotating In-Service Tubes Expansion Area Pancake Coil including inservice Rerolls Plus Point and 21 % of non Sleeved Upper Tube Roll 3,085 Tubes Rotating In-Service Tubes Expansion Area Pancake Coil including inservice Rerolls (2) and shop non-stress relieved Roll Expansions (106)
Plus Point and 33% of In-Service Lower Tube Roll 4,913 Tubes Rotating Tubes Expansion Area
-Pancake Coil Plus Point and Tubes bordering the 15 TSP +/-1 inch and 91 Tubes Rotating Sleeved Region UTS Secondary Face Pancake Coil
-1 inch to + 4 inches Plus Point and Tubes with Flaw-Flaw-Like Indication 302 Locations Rotating Like Indications (i-Area Pancake Coil codes, new TWO and large growth TWDs)
Plus Point and All dent locations Dent Locations 201 Dents Rotating greater than 2.5 Pancake Coil volts by bobbin coil below 14S Plus Point and All dent indications Dent Locations 277 Dents Rotating greater than 1 volt Pancake Coil located in non-periphery tubes at and above 14S
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachmnent I Page 15 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 4 Continued SG #2 Plus Point and All dent indications Dent Locations 21 Locations Rotating greater than 0.5 between 1 5S and UTS Pancake Coil volts between 1 5S in the periphery region and UTS in the periphery region Plus Point and 20% of Lower Tube sludge Pile Region at 986 Tubes Rotating Sheet sludge pile LTS +3 inches to LTS Pancake Coil
__________-3 inches
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 16 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each OTSG
-ROW; TUBE-IND LOCATION
%TW Indication
___Count 2-A 1
2 TWD 11S
+0.58 8
1 2-A 1
2 TWD 11S
-0.79 11 2
2-A 1
5 TWD 14S
+0.59 5
3 2-A 1
10 TWO 04S
-0.72 7
4 2-A 1
15 TWO 13S
-0.75 11 5
2-A 2
25 TWO 14S
+0.57 7
6 2-A 2
25 TWO 13S
-0.73 5
7 2-A 2
26 TWO 09S
-0.73 7
8 2-A 2
27 TWO 14S
-0.65 10 9
2-A 3
3 TWD 14S
-0.73 13 10 2-A 3
11 TWD 08S
-0.34 6
11 2-A 3
14 TWO 14S
+0.55 5
12 2-A 3
29 TWO 13S
-0.74 6
13 2-A 3
33 TWD 13S
+0.55 8
14 2-A 4
1 TWO 14S
+0.60 8
15 2-A 4
2 TWO 11S
-0.74 9
16 2-A 4
4 TWO 14S
-0.75 9
17 2-A 4
33 TWO 09S
+0.66 4
18 2-A 4
35 TWO 135
-0.67 7
19 2-A 4
40 TWO 12S
-0.83 5
20 2-A 4
41 TWO 13S
+0.59 13 21 2-A 5
12 TWO 10S
+0.57 11 22 2-A 5
20 TWO 08S
+0.33 11 23 2-A 5
41 TWO" 13S 1-0.76 4
24 A 5
42 TWO 13S
-0.70 6
25 2-A 5
42 TWO 13S
+0.57 6
26 2-A 5
45 TWO 14S
-0.71 10 27 2-A 5
45 TWO 135
+0.62 6
28 2-A 5
45 TWO 13S
-0.62 8
29 2-A 5
46 TWO 13S
+0.62 6
30 2-A 5
46 TWO 13S
-0.60 6
31 2-A 6
14 TWO 10S
+0.59 9
32 2-A 6
41 TWO 14S
+0.46 5
33 2-A 6
47 TWO 14S
+0.62 8
34 2-A 7
2 TWO 13S
-0.67 7
35 2-A 7
11 TWO 10S
+0.50 11 36 2-A 7
12 TWO 10S
+0.41 7
37 2-A 7
16 TWO 07S 1+0.66 4
38 2-A 7
36 TWO 08S 1+0.62 9
39 2-A 7
36 TWO 08S 1+0.52 7
1 40
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachment I Page 17 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
.OTSG.
ROW TUBE IND LOCATION '.%.TW.
Indication Count 2-A 7
41 TWOD 08S
+0.57 13 41 2-A 7
41 TWO 08S
-0.47 6
42 2-A 8
4 TWO 14S
+0.59 9
43 2-A 8
5 TWO 14S
+0.59 7
44 2-A 8
23 TWO 14S 1+0.52 6
45 2-A 9
1 TWO 13S
-0.74 9
46 2-A 9
1 TWO 09S
-0.87 10 47 2-A 9
60 TWO 14S
-0.77 7
48 2-A 9
62 TWO 13S
-0.52 7
49 2-A 9
62 TWO 13S 1+0.59 9
50 2-A 10 1
TWO 14S
+0.58 8
51 2-A 10 1
TWO 09S
-0.89 5
52 2-A 10 2
TWO 14S
-0.74 8
53 2-A 10 4
TWO 14S
-0.74 12 54 2-A 11 1
TWO 13S 1-0.74 10 55 2-A 11 3
TWO 09S
-0.68 5
56 2-A 11 3
TWO 09S
-0.84 7
57 2-A 11 21 TWO 14S
+0.58 10 58 2-A 12 1
TWO) 13S
+0.55 8
59 2-A 12 1
TWO) 13S
+0.72 10 60 2-A 12 1
TWO 13S
-0.70 14 61 2-A 12 1
TWO 13S
-0.72 18 62 2-A 12 2
TWO 13S
-0.70 11 63 2-A 12 22 TWO) 07S
-0.50 8
64 2-A 13 1
TWO 13S
-0.75 15 65 2-A 13 1
TWO 13S
-0.73 16 66 2-A 13 2
TWO) 13S
-0.63 10 67 2-A 13 2
TWO 13S
-0.65 14 68 2-A 13 66 TWO 07S
+0.72 5
69 2-A 14 3
TWO 13S
-0.68 10 70 2-A 14 5
TWO 14S
-0.79 12 71 2-A 14 74 TWO 11S
+0.60 10 72 2-A 14 74 TWO 11S 1+0.53 7
73 2-A 15 2
TWO 13S
-0.69 10 74 2-A 15 2
TWO 14S
+0.301 7
75 2-A 15 7
TWO 13S
-0.77 7
76 2-A 16 2
TWO 13S
-0.71 24 77 2-A 16 18 TWOD 06S
+0.12 4
78 2-A 16 80 TWO 11S
+0.58 9
79 2-A 16 81 TWO) 13S
-0.63 9
80 2-A 17 1
TWO 13S
-0.67 9
81
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 18 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
OTSG ROW TUBE IND iLOCATION
%TW Indication Count 2-A 17 2
TWD 13S
-0.66 7
82 2-A 17 81 TWD 13S
-0.72 8
83 2-A 18 1
TWD 14S
+0.53 7
84 2-A 18 1
TWD 13S
-0.69 10 85 2-A 18 2
TWD 13S
-0.64 9
86 2-A 19 1
TWD 09S
-0.81 8
87 2-A 19 53 TWD 12S
-0.83 8
88 2-A 20 27 TWO 15S
-0.80 8
89 2-A 20 80 TWD 10S
+0.53 6
90 2-A 21 1
TWD 13S
-0.60 8
91 2-A 21 10 TWD 03S
-0.79 8
92 2-A 21 49 SAA UTE
-0.23 N/A 93 2-A 22 1
TWD 12S
+0.57 6
94 2-A 23 1
TWD 13S
-0.62 6
95 2-A 24 1
TWD 08S
+0.65 6
96 2-A 24 46 TWD 06S
-0.59 9
97 2-A 24 51 SAA UTE
-0.30 N/A 98 2-A 25 1
TWD 12S
-0.77 5
99 2-A 25 1
TWD 08S 1+0.44 8
100 2-A 25 1
TWD 12S
+0.51 13 101 2-A 25 1
TWO 13S
-0.74 10 102 2-A 25 88 TWO 08S
+0.59 6
103 2-A 26 80 SAA UTE
-0.27 N/A 104 2-A 30 1
TWD 14S 1+0.26 3
105 2-A 31 3
TWO 10S
+0.43 4
106 2-A 31 13 TWD 08S
-0.52 7
107 2-A 32 61 TWD 06S
-0.57 8
108 2-A 32 83 SAA UTE
-0.39 N/A 109 2-A 33 1
TWO 14S
+0.66 10 110 2-A 33 2
TWO 13S
-0.64 7
ill 2-A 33 108 TWO 13S
-0.71 4
112 2-A 34 1
TWO 12S
+0.62 16 113 2-A 34 84 TWO 03S
-0.76 5
114 2-A 35 1
SCI UTE 1-0.23 47 115 2-A 35 1
TWO 12S 1+0.58 10 116 2-A 35 1
TWO 11S
-0.70 5
117 2-A 35 1
TWO 13S
-0.63 8
118 2-A 35 2
TWO 09S
-0.84 6
119 2-A 35 68 TWO 06S
-0.51 4
120 2-A 35 108 TWO 14S 1-0.78 5
121 2-A 35 108 1TWO 14S 1+0.53 6
1 122
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 19 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
ýOTSG ROW TUBE
'IND~
LOCATION -
%TWI Indication
- Count, 2-A 36 I
TWO 12S
+0.65 12 123 2-A 36 1
TWO 13S
-0.54 17 124 2-A 36 2
TWO 13S
-0.65 8
125 2-A 36 113 TWO 14S
+0.54 12 126 2-A 37 1
TWO 14S 1+0.43 6
127 2-A 37 1
TWO 13S
-0.62 8
128 2-A 37 1
TWO 11S
-0.75 8
129 2-A 37 1
TWO 12S
+0.55 8
130 2-A 37 2
TWD 13S
-0.72 8
131 2-A 37 56 TWD 06S 1+0.46 8
132 2-A 37 75 TWD 06S
+0.21 3
133 2-A 38 1
TWO 12S
+0.48 5
134 2-A 38 3
TWO 12S
+0.59 10 135 2-A 38 5
SCI UTE
-0.32 41 136 2-A 38 17 TWO 07S5
-0.28 5
137 2-A 39 62 TWO 06S
-0.46 4
138 2-A 39 113 TWO 14S
-0.85 14 139 2-A 39 116 TWO 13S
-0.76 6
140 2-A 40 36 TWO 07S
+0.18 6
141 2-A 40 117 TWO 14S
+0.68 11 142 2-A 41 3
TWO 13S
-0.52 12 143 2-A 41 36 TWO 06S
+0.57 9
144 2-A 41 36 TWO 06S
-0.34 4
145 2-A 42 1
TWO 13S
-0.68 8
146 2-A 42 66 TWO 06S
-0.12 8
147 2-A 43 1
TWO 14S
-0.74 4
148 2-A 43 1
TWO 13S
-0.68 13 149 2-A 44 69 TWO 06S
+0.49 4
150 2-A 47 122 TWO 14S
+0.52 9
151 2-A 48 14 TWO 05S
-0.60 5
152 2-A 48 23 TWD 05S
+0.55 3
153 2-A 49 5
TWD 09S
-0.75 4
154 2-A 50 122 TWO 10S
+0.57 7
155 2-A 51 54 TWO 06S
+0.34 7
156 2-A 52 1
TWO 13S
-0.77 11 157 2-A 52 1
TWD 12S
+0.60 9
158 2-A 52 45 TWD 06S
-0.21 5
159 2-A 52 125 TWO 13S
-0.78 8
160 2-A 54 50 TWD 06S
+0.44 5
161 2-A 54 127 TWD 14S 1+0.52 13 162 2-A 55 1
TWO 12-S 1+0.56 7
163
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 20 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each OTSG ROW TUBE IND LOCATION
%TW Indication Count 2-A 56 8
TWD 07S 1+0.37 2
164 2-A 58 1
TWD 13S
-0.72 12 165 2-A 58 1
TWD 11S
-0.89 10 166 2-A 58 1
TWD 12S
+0.60 11 167 2-A 58 1
SAl 15S
-2.93 53 168 2-A 59 1
TWO 07S 1+0.56 6
169 2-A 59 1
SMA UTE
-0.28 N/A 170 2-A 59 108 TWO 06S
+0.59 7
171 2-A 59 108 TWO 06S
-0.68 7
172 2-A 61 80 TWO 05S
+0.39 7
173 2-A 63 1
TWO 14S 1+0.59 6
174 2-A 63 1
TWO 12S
+0.45 5
175 2-A 63 6
TWO 07S
+0.32 5
176 2-A 65 93 TWO 14S
+0.55 5
177 2-A 66 102 TWO 06S
-0.58 7
178 2-A 68 1
TWO 08S 1+0.57 7
179 2-A 68 1
TWO 14S
+0.57 8
180 2-A 68 23 TWO 09S
+0.73 6
181 2-A 68 72 TWD 15S
+0.57 8
182 2-A 69 1
TWD 13S
+0.53 7
183 2-A 69 5
TWO 10S
-0.6 7
184 2-A 69 32 TWO 10S
+0.69 6
185 2-A 69 32 TWO 10S
+0.55 6
186 2-A 69 49 TWO 10S
+0.49 11 187 2-A 70 1
TWO 14S
+0.56 5
188 2-A 70 10 TWD 10S
-0.54 11 189 2-A 70 78 TWO 10S
+0.63 10 190 2-A 70 78 TWO 11S
+0.58 7
191 2-A 70 79 TWO 105
+0.55 7
192 2-A 70 79 TWO 105
-0.59 10 193 2-A 71 2
TWO 14S
-0.65 7
194 2-A 71 2
TWO 13S
+0.58 5
195 2-A 71 4
TWO 11S
+0.59 7
196 2-A 71 7
TWO 11S
+0.651 5
197 2-A 71 19 TWO 14S
+0.51 6
198 2-A 71 77 TWO 11S
+0.44 8
199 2-A 71 78 TWO 10S
-0.83 7
200 2-A 72 1
TWO 14S
+0.58 10 201 2-A 72 1
TWD 08S
+0.57 7
202 2-A 72 1
TWO 13S
+0.63 5
203 2-A 72 28 TWO 14S
+0.64 5
204
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachment I Pag 2 of29TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each
_____Imperfection SG #2:
OTSG ROW TUBE-.
IND LOCATION
%/TW Indication Count 2-A 72 28 TWO 11S
+0.54 4
205 2-A 72 35 TWO 14S
+0.48 7
206 2-A 72 51 TWO 10S
+0.53 5
207 2-A 72 66 TWD 03S
+0.46 9
208 2-A 72 76 TWO 11S
+0.55 7
209 2-A 72 77 TWO 05S
+0.51 6
210 2-A 73 1
TWO 14S
+0.65 8
211 2-A 73 2
TWO 06S
+0.60 7
212 2-A 73 2
TWO 13S
+0.69 7
213 2-A 73 2
TWO 14S
+0.61 8
214 2-A 73 3
TWO 14S
-0.87 5
215 2-A 73 27 TWO 10S
-0.17 7
216 2-A 73 46 TWO 03S
-0.78 5
217 2-A 73 61 TWO 14S
+0.58 7
218 2-A 73 76 TWO 05S
-0.30 5
219 2-A 73 77 TWO 10S
+0.59 10 220 2-A 73 78 TWO 10S
-0.81 6
221 2-A 73 88 TWO 05S
+0.35 4
222 2-A 74 1
TWO 14S
+0.61 5
223 2-A 74 63 TWO 04S
+0.59 7
224 2-A 74 71 TWO 11S
+0.62 11 225 2-A 74 72 TWO 10S
-0.84 7
226 2-A 74 72 TWO 10S
+0.56 5
227 2-A 75 6
TWO 14S
+0.56 8
228 2-A 75 7
TWO 13S
-0.75 5
229 2-A 75 28 TWO 04S 1+0.54 8
230 2-A 75 34 TWO 04S
+0.65 4
231 2-A 75 59 TWO 01S
+0.64 4
232 2-A 75 67 TWO 13S
+0.65 8
233 2-A 75 72 TWO 11S
+0.51 8
234 2-A 75 72 TWO 10S
+0.65 5
235 2-A 75 73 TWO 10S
+0.51 11 236 2-A 75 73 TWO 10S
-0.81 7
237 2-A 76 67 TWO 15S
-0.77 12 238 2-A 76 73 TWO 04S
+0.55 7
239 2-A 77 48 TWO 03S
+0.50 7
240 2-A 77 68 TWO 13S
+0.55 9
241 2-A 77 72 TWO 10S
+0.58 6
242 2-A 77 124 TWD 13S
-0.76 8
243 2-A 78 11 TWO 07S
-0.72 1 6
244 2-A 78 23 TWO 04S
-0.78 5
245
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 22 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
OTSG ROW TUBE
.IND LOCATION
"%TW Indication Count 2-A 79 2
TWD 11S
+0.62 5
246 2-A 79 25 TWD 11S
-0.46 5
247 2-A 79 44 TWO
'11S
+0.30 3
248 2-A 79 71 TWO 15S
-0.73 8
249 2-A 80 12 SMA UTE
-0.28 N/A 250 2-A 80 15 TWD 07S
-0.45 6
251 2-A 80 39 TWD 09S
-0.87 8
252 2-A 80 139 TWD 09S
-0.24 5
253 2-A 80 71 TWO 05S
+0.50 8
254 2-A 80 72 TWD 14S 1+0.57 7
255 2-A 81 2
TWO 14S
+0.61 6
256 2-A 81 33
..TWD 09S
+0.63 11 257 2-A 81 161 TWO 11S
-0.78 8
258 2-A 81 61 TWO 07S
+0.51 5
259 2-A 81 128 TWO 13S
-0.76 5
260 2-A 82 1
TWO 06S
-0.74 5
261 2-A 82 1
TWO 13S
-0.63 11 262 2-A 82 1
TWO 11S
+0.63 8
263 2-A 82 26 TWO 07S
-0.54 7
264 2-A 82 44 TWO 08S 1+0.66 6
265 2-A 82 78 TWO 10S
+0.69 11 266 2-A 82 97 TWO 06S
-0.48 4
267 2-A 82 127 TWO 13S
+0.54 7
268 2-A 83 33 TWO 08S
+0.74 6
269 2-A 83 40 TWO 06S 1-0.30 5
270 2-A 84 32 TWO 09S 1+0.70 10 271 2-A 84 75 TWD 11S
+0.69 13 272 2-A 84 75 TWD 12S
+0.54 4
273 2-A 84 76 TWO 11S
+0.61 8
274 2-A 84 79 TWO 05S
-0.59 5
275 2-A 85 31 SMA UTE
-0.26 N/A 276 2-A 85 31 TWO 09S
+0.72 13 277 2-A 85 76 TWO 11S
+0.70 11 278 2-A 85 77 TWO 11S
+0.71 10 279 2-A 85 79 TWO 11S 1+0.45 5
280 2-A 85 122 TWO 09S
-0.25 6
281 2-A 86 71 TWO 14S
+0.46 8
282 2-A 86 71 TWO 14S
+0.60 8
283 2-A 86 175 TWO 10S
+0.63 6
284 2-A 86 175 TWO 11S 1+0.731 15 285 2-A 86 195 TWO 05S
-0.59 1 9
286
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 23 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each
_____Imperfection SG #2:
OTSG ROW TUBE IND LOCATION
%TW Indication Count 2-A 86 127 TWD 14S
-0.61 11 287 2-A 86 127 TWD 13S
+0.57 12 288 2-A 87 8
TWD 03S
+0.70 8
289 2-A 87 62 TWD 06S
-0.28 8
290 2-A 87 69 TWD 05S
-0.62 8
291 2-A 87 71 TWD 13S
+0.57 8
292 2-A 87 73 TWD 11S
+0.59 7
293 2-A 87 73 TWD 12S
+0.48 5
294 2-A 87 74 TWD 11S
+0.66 8
295 2-A 87 75 TWD 11S 1+0.40 10 296 2-A 87 98 TWD 05S
+0.63 4
297 2-A 87 106 TWD 02S
+0.74 10 298 2-A 87 122 SAl UTE
-1.68 86 299 2-A 88 69 TWD 14S
+0.40 11 300 2-A 88 70 TWD 14S 1+0.48 10 301 2-A 88 76 TWD 11S 1+0.71 14 302 2-A 88 83 TWD 05S
-0.65 4
303 2-A 88 93 TWD 06S
-0.56 5
304 2-A 89 70 TWD 145
+0.55 8
305 2-A 89 71 TWD 055
+0.65 5
306 2-A 89 71 TWD 05S
+0.49 6
307 2-A 89 72 TWD 11S
+0.59 10 308 2-A 89 73 TWD 11S
+0.53 8
309 2-A 89 74 TWD 09S
+0.70 7
310 2-A 89 75 TWD 11S
+0.66 8
311 2-A 89 75 TWD loS
+0.59 6
312 2-A 89 124 TWD 08S
-0.45 8
313 2-A 89 124 TWD 08S
+0.66 5
314 2-A 90 7
TWD 08S
-0.79 4
315 2-A 90 74 TWD 10S
+0.63 7
316 2-A 90 74 TWD 11S
+0.60 10 317 2-A 90 129 TWD 13S
-0.76 7
318 2-A 91 3
TWD 09S
+0.27 5
319 2-A 91 65 TWD 05S 1-0.59 5
320 2-A 91 70 TWD 10S5
-0.67 8
321 2-A 91 70 TWO 10S
+0.62 10 322 2-A 91 70 TWD 11S
+0.61 16 323 2-A 91 70 TWO 11S
-0.71 8
324 2-A 92 3
SMA UTE
-0.26 N/A 325 2-A 92 69 TWO 11S 1+0.52 7
326 2-A 92 127 TWO 08S 1+0.31 3
327
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 24 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each OTSG.
ROW.
TUBE IND LOCATION
%TW Indication S____
Count 2-A 92 129 TWD 07S
-0.76 5
328 2-A 93 48 TWD 05S
+0.00 5
329 2-A 93 63 TWD 11S
+0.63 6
330 2-A 93 64 TWD 11S
+0.61 7
331 2-A 93 80 TWO 05S
-0.39 6
332 2-A 94 1
TWO 13S
+0.48 9
333 2-A 95 1
TWD 08S
-0.81 5
334 2-A 96 121 TWD 08S
+0.58 7
335 2-A 98 127 TWO 13S
-0.80 8
336 2-A 100 125 TWO 13S
-0.65 8
337 2-A 102 4
TWO 08S
-0.75 3
338 2-A 104 93 TWO 07S
-0.52 6
339 2-A 107 117 TWO 09S
-0.55 7
340 2-A 107 117 TWO 09S
+0.58 7
341 2-A 109 4
TWO 09S 1+0.29 6
342 2-A 109 118 TWO 09S 1-0.55 8
343 2-A 110 117 TWO 13S
-0.72 9
344 2-A 111 4
TWO 11S
+0.20 4
345 2-A 113 4
TWO 14S
+0.53 5
346 2-A 113 111 TWO 09S
+0.67 4
347 2-A 114 3
TWO 14S 1+0.68 11 348 2-A 114 40 TWO 06S
+0.23 5
349 2-A 114 111 TWD 095
-0.67 6
350 2-A 114 111 TWO 09S
+0.68 6
351 2-A 114 113 TWO 10S
+0.59 7
352 2-A 114 113 TWO 10S5
-0.67 4
353 2-A 116 9
TWO 09S
-0.21 5
354 2-A 116 22 TWO 14S
-0.84 8
355 2-A 116 107 TWO 09S
+0.67 8
356 2-A 116 107 TWO 09S
-0.66 8
357 2-A 116 109 TWO 09S 1+0.67 4
358 2-A 116 110 TWO 09S 1+0.66 7
359 2-A 116 111 TWO 08S
-0.75 3
360 2-A 116 111 MAA UTE
-0.32 N/A 361 2-A 117 104 TWO 14S
+0.42 6
362 2-A 117 107 TWO 10S
-0.80 6
363 2-A 118 104 TWO 09S 1+0.62 6
364 2-A 118 106 SAA UTE
-0.30 N/A 365 2-A 118 106 TWO 10S
-0.81 5
366 2-A 119 5
TWO 07S
-0.20 9
367 2-A 119 80 MAA UTE
-0.31 N/A 368
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachmnent 1 Page 25 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
OTSG ROW TUBE IND LOCATION*
%TW Indication
_____Count 2-A 119 105 TWO 10S
+0.43 4
369 2-A 119 105 TWO 09S
+0.69 7
370 2-A 119 107 TWO 09S
+0.67 10 371 2-A 119 107 TWD 09S
+0.62 6
372 2-A 120 102 TWD 09S 1+0.67 10 373 2-A 120 104 TWO 09S
+0.67 5
374 2-A 120 104 TWO 10S
-0.61 7
375 2-A 120 104 TWO 10S
+0.70 15 376 2-A 121 4
TWO 09S
+0.48 5
377 2-A 121 98 TWO 13S 1-0.73 6
378 2-A 121 98 TWO 13S
-0.77 6
379 2-A 121 101 TWO 09S
+0.66 5
380 2-A 121 104 TWO 09S
+0.63 7
381 2-A 121 105 TWO 10S
-0.68 4
382 2-A 122 98 TWO 14S
-0.77 5
383 2-A 122 100 TWO 09S
+0.53 7
384 2-A 122 101 TWO 04S
-0.76 8
385 2-A 122 102 TWO 10S
+0.55 5
386 2-A 122 102 TWO 10S
-0.70 7
387 2-A 122 104 TWO 10S
-0.69 6
388 2-A 123 85 TWO 14S
-0.80 8
389 2-A 123 101 TWD 10S
-0.75 6
390 2-A 123 101 TWO 10S
+0.52 9
391 2-A 123 102 TWO 10S
-0.69 9
392 2-A 124 100 TWO 10S
-0.62 7
393 2-A 124 100 TWO 13S
-0.67 8
394 2-A 124 101 TWO 10S
-0.88 5
395 2-A 125 14 SMA UTE
-0.22 N/A 396 2-A 125 96 TWO 09S
+0.32 6
397 2-A 125 98 TWO 10S
-0.79 4
398 2-A 125 99 TWO 10S
-0.79 5
399 2-A 125 100 TWO 10S
-0.71 8
400 2-A 127 16 TWO 07S
-0.50 5
401 2-A 127 97 TWO 105
-0.73 5
402 2-A 128 5
TWO 10S
+0.53 12 403 2-A 128 6
TWO 10S
+0.55 9
404 2-A 128 7
TWO 10S
+0.59 7
405 2-A 128 84 TWO 14S
-0.81 6
406 2-A 129 5
TWD 10S 1+0.52, 9
407 2-A 129 7
TWO IlOS
+40.61 1 7
408 2-A 129 8
TWO 10S 1+0.591 6
1 409
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 26 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
OT-SG ROW T.UBE.
IND LOCATION
%TW Indication
___Count 2-A 129 93 TWD 13S
-0.76 6
410 2-A 130 7
TWD loS
+0.57 7
411 2-A 130 8
TWD 10S
+0.61 9
412 2-A 130 10 TWD 13S
+0.52 5
413 2-A 130 91 TWO 10S 1+0.59 7
414 2-A 131 6
TWO 09S
+0.65 6
415 2-A 131 7
TWO 10S
+0.59 B
416 2-A 132 1
TWD 09S
-0.04 13 417 2-A 132 8
TWD 10S
+0.52 7
418 2-A 133 2
TWD 05S
-0.78 4
419 2-A 133 3
TWO 10S
-0.65 7
420 2-A 133 4
TWD 10S
+0.57 3
421 2-A 133 7
TWD 10S
+0.61 13 422 2-A 133 80 TWO 14S
-0.78 6
423 2-A 134 4
TWO 10S
+0.64 2
424 2-A 134 5
TWD 10S
-0.75 5
425 2-A 134 6
TWD 10S
+0.73 7
426 2-A 134 8
TWO 10S
+0.54 2
427 2-A 135 4
TWO 10S
+0.55 4
428 2-A 136 2
TWO 10S
-0.75 6
429 2-A 136 4
TWO 10S 1+0.57 7
430 2-A 136 7
TWD 10S
+0.57 10 431 2-A 137 1
TWO 11S
-0.81 8
432 2-A 137 6
TWO 10S
-0.72 12 433 2-A 137 6
TWO 10S
+0.65 9
434 2-A 137 6
TWO 10S
-0.69 9
435 2-A 138 11 TWO 13S
-0.86 4
436 2-A 139 3
TWO 10S
+0.61 5
437 2-A 139 14 TWO 04S
-0.68 12 438 2-A 139 74 TWO 04S
-0.80 7
439 2-A 140 1
TWO l0S
-0.76 8
440 2-A 141 8
TWO 09S
+0.09 5
441 2-A 141 67 TWO 13S
+0.59 8
442 2-A 144 48 TWO 08S
-0.34 7
443 2-A 145 11 TWO 04S
-0.79 5
444 2-A 145 36 TWO 10S
+0.70 10 445 2-A 145 39 TWO 10S
+0.71 11 446 2-A 145 39 TWO 10S
+0.64 7
447 2-A 145 42 TWO-10S
+0.68 8
1 448 2-A 145 46 TWD 10S
+0.64 9
449 2-A 145 47 TWO 10S
+0.65 7
450
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Attachment I Page 27 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
OTSG ROW TUBE IND LOCATION:
%TW.'
Indication S_____Count 2-A 145 54 TWD 13S
+0.58 10 451 2-A 146 18 TWO 13S
-0.89 6
452 2-A 146 31 TWD loS
+0.591 13 453 2-A 146 32 TWD 10S
+0.59 13 454 2-A 146 33 TWD 10S
+0.64 17 455 2-A 146 34 TWD 10S
+0.61 19 456 2-A 146 36 TWO 10S
+0.63 14 457 2-A 146 37 TWD 04S
-0.77 4
458 2-A 146 37 TWO 10S
+0.62 9
459 2-A 146 38 TWD 10S
+0.63 10 460 2-A 146 39 TWD 10S 1+0.62 6
461 2-A 146 43 TWD 10S
+0.55 5
462 2-A 147 29 TWD 10S
-0.63 6
463 2-A 147 30 TWD 10S
+0.63 10 464 2-A 147 32 TWD 10S
+0.61 7
465 2-A 147 34 TWD 10S 1+0.61 13 466 2-A 147 35 TWD 10S
+0.74 7
467 2-A 147 36 TWD 10S
+0.72 22 468 2-A 147 46 TWD 14S
+0.52 6
469 2-A 148 3
TWD 10S
+0.59 5
470 2-A 148 24 TWO 10S 1+0.70 8
471 2-A 148 26 TWD 10S
+0.61 8
472 2-A 148 27 TWD 10S
-0.74 8
473 2-A 148 28 TWD 10S
-0.69 5
474 2-A 148 29 TWD 10S
+0.66 6
475 2-A 148 30 TWD 10S 1+0.61 9
476 2-A 148 30 TWD 10S
-0.71 7
477 2-A 148 31 TWO 10S
-0.70 8
478 2-A 148 32 TWD 10S
+0.59 11 479 2-A 148 34 TWD 10S
+0.71 8
480 2-A 148 38 TWD 14S 1+0.63 10 481 2-A 148 40 TWO 14S
+0.57 13 482 2-A 149 18 TWD 10S
+0.66 8
483 2-A 149 26 TWD 10S
-0.62 11 484 2-A 149 26 TWO 10S
+0.66 13 485 2-A 149 27 TWD 105
+0.60 7
486 2-A 149 27 TWD 10S5
-0.72 8
487 2-A 149 28 TWO 10S
-0.71 6
488 2-A 149 28 TWO 10S
+0.73 8
489 2-A 149 28 TWO 10S
-0.56 11 490 2-A 149 29 1TWO 10S
-0.67 5
491
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 28 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS Table 5: Location and Percent of Wall Thickness Penetration for Each Imperfection SG #2:
OTSG ROW TUBE IND.LOCATION
%TW Indication
___Count 2-A 149 30 TWD loS
+0.61 6
492 2-A 149 31 TWD 10S
+0.64 7
493 2-A 150 18 TWD 10S
+0.68 5
494 2-A 150 13 TWD 10S
+0.73 5
495 2-A 150 15 TWD 10S 1+0.73 10 496 2-A 150 17 SAl 15S
-3.74 0
497 2-A 150 19 TWD 10S
+0.71 8
498 2-A 150 19 TWD 10S
-0.58 B
499 2-A 150 20 TWD 10S
-0.66 8
500 2-A 150 20 TWD 105
+0.68 9
501 2-A 150 20 TWD 14S
+0.54 8
502 2-A 150 21 TWD 10S
-0.67 8
503 2-A 150 21 TWD I105
+0.69 11 504 2-A 150 21 SAl 15S
-4.38 34 505 2-A 150 25 TWD 10S
-0.74 12 506 2-A 150 25 TWD 10S
+0.68 9
507 2-A 150 27 TWD 10S
-0.79 18 508 2-A 151 11 TWD 10S 1+0.39 8
509 2-A 151 5
TWD 06S
-0.54 6
510 2-A 151 6
TWD 10S
-0.31 6
511 2-A 151 12 SAI 15S
+2.24 0
512 2-A 151 13 SAl 155
+2.78 40 5137 2-A 151 13 TWD 10S 1+0.71 9
514 2-A 151 13 TWD loS
-0.74 9
515 2-A 151 15 TWD 10S
+0.70 6
516 2-A 151 15 TWD 10S
-0.75 10 517 2-A 151 15 TWD 13S
-0.78 15 518 2-A 151 15 TWD 13S 1+0.54 8
519 2-A 151 15 SAl 15S
+2.64 14 520 2-A 151 15 SAl 15S
+4.70 28 521 2-A 151 15 SAI 15S
+3.69, 32 1 522 2-A 151 16 TWD 105
-0.69 1 3
1 523
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 29 of 29 TECHNICAL SPECIFICATION REPORTING REQUIREMENTS
________Table 6: Identification of Tubes Repaired SG #2 SIG ROW TUEReason for Repair Tube Count Repaired By Plugging 2-A 35 1
SCI UTE
-0.23 1
2-A 38 5
SCI UTE
-0.32 2
Sc' Growth 2-A 45 120 OPB UTE
-0.31 3
2-A 58 1
SAI 15S
-2.93 4
SCI Growth 2-A 61 1
OPB UTE
-0.24 5
2-A 150 17 SAl 15S
-3.74 6
2-A 150 21 SAl 15S
-4.38 7
2-A 151 12 SAI 15S
+2.24 8
2-A 151 13 SAl 15S
+2.78 9
SAl 15S
+4.70 2-A 151 15 SAl 15S
+3.69 10 SAl 15S
+2.64:d Repaired By HotLe___ol 2-A 21 49 SMA UTE
-0.23 1
2-A 24 51 SMA UTE
-0.30 2
2-A 26 80 SMA UTE
-0.27 3
2-A 32 83 SMA UTE
-0.39 4
2-A 59 1
SMA UTE
-0.28 5
2-A 80 12 SMA UTE
-0.28 6
2-A 85 31 SMA UTE
-0.26 7
2-A 87 122 SAl UTE
-1.68 8
2-A 92 3
SMA UTE
-0.26 9
2-A 116 ill MMA UTE
-0.32 10 2-A 118 106 SMA UTE
-0.30 11 2-A 119 80 MMA UTE
-0.31 12 2-A 125 1
14 1SMA UTEI
-0.22 113
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 1 of 1 EDDY CURRENT IDENTIFICATION CODES The following identification codes were used in Attachment 1.
DNT Dent GMVD Geometric Mean Distortion LTE Lower Tube End LTS Lower Tube Sheet MAA Multiple Axial Tube-end Anomaly MAI Multiple Axial Indication MCI Multiple Circumferential Indication MVVI Multiple Volumetric Indications QPB Outside Pressure Boundary (above repair roll)
SAA Single Axial Tube-end Anomaly SAl Single Axial Indication SCI Single Circumferential Indication SVI Single Volumetric Indication TWO Through Wall Degradation
_______(Assigned to Wear Indications)
UTE Upper Tube End UTS Upper Tube Sheet xxS Support Plate Number
Docket Number 50-346 License Number NPF-3 Serial Number 3288 Page 1 of 1 COMMITMENT LIST The following list identifies those actions committed to by the Davis-Besse Nuclear Power Station (DBNPS) in this document. Any other actions discussed in the submittal represent intended or planned actions by the DBNPS.
They are described only as information and are not regulatory commitments.
If there are any questions or if additional information is required, please contact Mr. Gregory A. Dunn, Manager - FENOC Fleet Licensing, at (330) 315-7243.
COMMITMENTS DUE DATE NoneNA N/A