ML041240435
ML041240435 | |
Person / Time | |
---|---|
Site: | Oconee ![]() |
Issue date: | 01/31/2004 |
From: | Ingram C Duke Power Co |
To: | Office of Nuclear Reactor Regulation |
References | |
Download: ML041240435 (182) | |
Text
Oconee Nuclear Station Units 1, 2 and 3 ODCM Offsite Dose Calculation Manual 2004
Oconee Nuclear Station Units 1, 2, and 3 OFFSITE DOSE CALCULATION MANUAL (ODCM)
Prepared By:__C. D. Ingram_____ Approved By:__L. E. Haynes_____
General Office Radiation Protection Technical Manager, RP, Nuclear GO REVISION NUMBER EFFECTIVE YEAR 44 ____2004_____
Reviewed By: Reviewed By: Approved By:
__D. J. Berkshire _____ __M. I. Sanders _______ __B. H. Hamilton_____
ONS Radiation Protection ONS Radwaste Chemistry ONS Station Manager
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 TABLE OF CONTENTS Executive Summary. . . . . . . . . . . . Executive Summary-1 1.0 Radwaste Systems . . . . . . . . . . . . . 1-1 1.0.1 Liquid Radwaste Processing . . . . . . . . . . . 1-1 1.0.2 Gaseous Radwaste Processing . . . . . . . . . . . 1-3 2.0 Release Rate Calculations . . . . . . . . . . . . 2-1 2.0.1 Liquid Release Rate Limit Calculations . . . . . . . . . 2-1 2.0.1.1 Liquid Radwaste Effluent Line Release Rate Limit Calculation . . . 2-1 2.0.1.2 #3 Chemical Treatment Pond Effluent Line Discharge . . . . . 2-2 2.0.2 Gaseous Release Rate Limit Calculations . . . . . . . . . 2-5 2.0.2.1 Unit Vent Discharge Release Rate Limit Calculation . . . . . 2-5 3.0 Setpoint Calculations . . . . . . . . . . . . . 3-1 3.0.1 Liquid Radiation Monitor Setpoint Calculations . . . . . . . 3-1 3.0.2 Gaseous Radiation Monitor Setpoint Calculations . . . . . . . 3-5 3.0.2.1 Unit Vents Setpoints (RIA-45 and RIA-46) . . . . . . . 3-7 3.0.2.2 Radwaste Facility Setpoints (4RIA-45 and 4RIA-46) . . . . . 3-8 3.0.2.3 Interim Radwaste Building Setpoints (RIA-53) . . . . . . 3-9 3.0.2.4 Waste Gas Decay Tank Setpoints (RIA-37 and RIA-38) . . . . . 3-9 4.0 Effluent Dose Models . . . . . . . . . . . . . 4-1 4.0.1 Liquid Effluent Dose Model for the Maximum Exposed Individual . . . . 4-1 4.0.2 Gaseous Effluent Dose Model for the Maximum Exposed Individual . . . . 4-7 4.0.3 Direct Radiation . . . . . . . . . . . . . 4-18 4.0.4 Effluent Apportionment . . . . . . . . . . . . 4-18 5.0 Fuel Cycle Calculations . . . . . . . . . . . . . 5-1 5.0.1 Milling . . . . . . . . . . . . . . . 5-1 5.0.2 Conversion . . . . . . . . . . . . . . 5-1 5.0.3 Enrichment . . . . . . . . . . . . . . 5-1 5.0.4 Fuel Fabrication . . . . . . . . . . . . . 5-1 5.0.5 Nuclear Power Production . . . . . . . . . . . 5-2 5.0.6 Fuel Reprocessing . . . . . . . . . . . . . 5-2 5.0.7 40CFR190 Total Dose Determination . . . . . . . . . 5-2 6.0 Environmental Locations . . . . . . . . . . . . 6-1 6.0.1 Site Description and Sample Locations . . . . . . . . . 6-1 6.0.2 Land Use Census Data . . . . . . . . . . . . 6-1 6.0.3 Oconee Meteorology: Relative Air Concentrations and Deposition . . . . 6-8 6.0.3.1 XOQDOQ Methodology and Assumptions . . . . . . . 6-8 6.0.3.2 Meteorological Data . . . . . . . . . . . 6-9 6.0.3.3 Annual XOQDOQ Comparison to the ODCM . . . . . . 6-10 7.0 Licensee Initiated Changes . . . . . . . . . . . . 7-1 i
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Appendices Appendix A: Dose Factors for Exposure to a Semi-Infinite Cloud of Noble Gases . . . A-1 Appendix B: Pi Infant Dose Factors for use in the Gaseous Release Rate Limit Calculations . B-1 Appendix C: Ai Adult Dose Factors for use in the Liquid Dose Calculations . . . . . C-1 Appendix D: Ai Teen Dose Factors for use in the Liquid Dose Calculations . . . . D-1 Appendix E: Ai Child Dose Factors for use in the Liquid Dose Calculations . . . . E-1 Appendix F: Ai Infant Dose Factors for use in the Liquid Dose Calculations . . . . F-1 Appendix G: Ri Adult Dose Factors for use in the Gaseous Dose Calculations . . . . G-1 Appendix H: Ri Teen Dose Factors for use in the Gaseous Dose Calculations . . . . H-1 Appendix I: Ri Child Dose Factors for use in the Gaseous Dose Calculations . . . . I-1 Appendix J: Ri Infant Dose Factors for use in the Gaseous Dose Calculations . . . . J-1 LIST OF FIGURES 1.0-1 Liquid Radwaste System . . . . . . . . . . . . . 1-2 1.0-2 Gaseous Radwaste System (4 pages) . . . . . . . . . . 1-4 2.0-1 Liquid Radwaste Discharge Locations . . . . . . . . . . 2-4 6.0-1 Sampling Locations Map (Site Boundary). . . . . . . . . . 6-5 6.0-2 Sampling Locations Map (Ten Mile Radius) . . . . . . . . . 6-6 6.0-3 Land Use Census Map . . . . . . . . . . . . . 6-7 LIST OF TABLES 3.0-1 RIA-33 Cs-137 Equivalents. . . . . . . . . . . . . 3-4 3.0-2 Xe-133 Equivalents . . . . . . . . . . . . . . 3-11 6.0-1 Sampling Locations . . . . . . . . . . . . . . 6-2 6.0-2 TLD Sites . . . . . . . . . . . . . . . 6-3 6.0-3 Land Use Census Results . . . . . . . . . . . . . 6-4 6.0-4 Terrain Heights Above ONS Yard Grade Elevation (m) . . . . . . . 6-9 6.0-5 ONS Atmospheric Stability Frequency (1988 - 1992) . . . . . . . 6-10 6.0-6 ONS Frequency of Wind Direction and Speed (1988 - 1992) . . . . . . 6-10 6.0-7 ONS Limiting /Q and D/Q Values (1988-1992) . . . . . . . . 6-11 6.0-8 ONS Delta-T Ranges per Vertical Separation Distances . . . . . . . 6-11 6.0-9 Oconee Semi-Elevated /Q and D/Q Average Values (1988-1992) . . . . . 6-12 6.0-10 Oconee Ground Level /Q and D/Q Average Values (1988-1992) . . . . . 6-14 ii
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 EXECUTIVE
SUMMARY
The Oconee Nuclear Station (ONS) Offsite Dose Calculation Manual (ODCM) provides the methodology and parameters to be used in the calculation of offsite doses due to normal operation radioactive liquid and gaseous effluents to assure compliance with the dose limitations of the Selected Licensee Commitments (SLCs, UFSAR Chapter 16) and Technical Specifications. These dose limitations assure that:
(1) the concentration of radioactive liquid effluents released from the site to the unrestricted area will be limited to 10 times the effluent concentration (EC) levels of 10CFR20, Appendix B, Table 2, and 2.0E-04 µCi/ml for dissolved and entrained noble gases; (2) the exposures to any individual member of the public from radioactive liquid effluents will not result in doses greater than the design objectives of 10CFR50, Appendix I; (3) the dose rate at any time at the site boundary from radioactive gaseous effluents will be limited to: for noble gases; less than or equal to 500 mrem/yr to the whole body, and less than or equal to 3000 mrem/yr to the skin; and for iodine-131 and iodine-133, for tritium, and for all radioactive materials in particulate form with half- lives greater than 8 days; less than or equal to 1500 mrem/yr to any organ; (4) the exposure to any individual member of the public from radioactive gaseous effluents will not result in doses greater than the design objectives of 10CFR50, Appendix I; and (5) the dose to any individual member of the public from the nuclear fuel cycle will not exceed the limits of 40CFR190.
The methodology and parameters used to assure compliance with the dose limitations described above shall be used to prepare the radioactive liquid and gaseous effluent reports required by the SLCs and Technical Specifications. Dose calculations that demonstrate compliance with 40CFR190 will be considered to demonstrate compliance with the 10CFR20 0.1-rem annual dose limit. The ODCM also provides the Executive Summary - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 methodology and parameters to be used in the calculation of radioactive liquid and gaseous effluent monitoring instrumentation alarm /trip setpoints to assure compliance with the concentration and dose rate limitations of the SLCs and Technical Specifications. Normally RETDAS, a computer code that implement s NUREG-0133 methodology, is used for the calculation of offsite doses, but the ODCM also provides a method for the calculation of offsite doses when RETDAS is not available.
The ODCM has been prepared as generically as possible in order to minimize the need for revisions. However, some changes to the ODCM such as land- use census data are expected on an annual basis. Any changes to the methodology and parameters to be used in this ODCM shall be reviewed by knowledgeable individual(s), and approved by the Station Manager and the General Office Radiation Protection Manager prior to implementatio n. Changes to the ODCM shall be submitted to the Nuclear Regulatory Commission in accordance with the SLCs and Technical Specifications.
The ODCM does not replace any station implementing procedures. Programmatic controls for radioactive effluents and radiological environmental monitoring are contained in the Administrative Controls chapter of the Technical Specifications.
Procedural details for radioactive effluents and radiological environmental monitoring consisting of licensee commitments, applicability, remedial actions, surveillance requirements, and the bases for these requirements are contained in Section 16.11 of the SLCs.
Executive Summary - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 1.0 RADWASTE SYSTEMS 1.0.1 LIQUID RADWASTE PROCESSING The liquid radwaste system at Oconee Nuclear Station is used to collect and treat liquid chemical and radiochemical byproducts of unit operation. The system produces effluents that are discharged in small, dilute quantities to the environment. The means of treatment vary with waste type and desired product in the various systems:
(A) Filtration - Waste sources are filtered prior to processing as necessary.
(B) Ion Exchange - Ion exchange is used to remove radioactive ions from solution. Also, ion exchange is normally used in removing cations (cobalt, cesium, manganese) and anions (chloride, fluoride) from the filtrate in order to purify the filtrate for release.
(C) Gas Stripping - Removal of gaseous radioactive fission products is accomplished through venting of atmospheric holdup tanks.
Figure 1.0-1 is a schematic representation of the liquid radwaste system at Oconee.
Section 1 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 1.0-1 Oconee Nuclear Station Liquid Radwaste System Section 1 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 1.0.2 GASEOUS RADWASTE PROCESSING The purpose of the gaseous waste disposal system is to:
(1) Maintain a non-oxidizing cover gas of nitrogen in tanks and equipment that contain potentially radioactive gas; (2) Hold up radioactive gas for decay; and (3) Release gases (radioactive and non-radioactive) to the atmosphere under controlled conditions.
During power operation of the facilities, radioactive materials released to the atmosphere in gaseous effluents include low concentrations of fission product noble gases (krypton and xenon), halogens (mostly iodines), tritium contained in water vapor, and particulate material including both fission products and activated corrosion products.
The primary source of gaseous radioactive wastes is from the degassing of the primary coolant during letdown of the cooling water into various holding tanks. Additional sources of gaseous waste activity include the auxiliary building exhaust, spent fuel area exhaust, the discharge from the steam jet air ejectors, and purging and venting of the reactor containment building.
All components that can contain potentially radioactive gases are vented to a vent header.
The vent gases are subsequently drawn from this header by one of four waste gas compressors or a waste gas exhauster. The waste gas compressor discharges through a waste gas separator to one of seven waste gas tanks. The waste gas tanks and the waste gas exhauster discharge to the unit vent after passing through a filter bank consisting of a prefilter, an absolute filter, and a charcoal filter.
Radioactive gases may be released inside the reactor containment building when components of the primary system are opened to the building atmosphere for operational reasons or where minor leaks occur in the primary system. Prior to access, the reactor containment atmosphere will be monitored for radioactivity and, when necessary, purged through prefilters, high-efficiency particulate air (HEPA) filters, and charcoal filters, and released to the atmosphere through the unit vent. The purge equipment is sized for a flow rate of 50,000 cfm providing approximately 1.5 air changes per hour in the reactor building. Units 1, 2, and 3 have a separate vent stack which services each unit.
Figure 1.0-2 is a schematic representation of the gaseous radwaste system at Oconee.
Section 1 - Page 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 1.0-2 Oconee Nuclear Station Gaseous Radwaste System Page 1 of 4 Section 1 - Page 4
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 1.0-2 Oconee Nuclear Station Gaseous Radwaste System Page 2 of 4 Section 1 - Page 5
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 1.0-2 Oconee Nuclear Station Gaseous Radwaste System Page 3 of 4 Section 1 - Page 6
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 1.0-2 Oconee Nuclear Station Gaseous Radwaste System Page 4 of 4 Section 1 - Page 7
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 2.0 RELEASE RATE CALCULATIONS 2.0.1 LIQUID RELEASE RATE LIMIT CALCULATIONS There are two liquid radwaste discharge points to the environment at Oconee; (1) the liquid radwaste effluent line to the Keowee Hydroelectric Unit Tailrace, and (2) the #3 Chemical Treatment Pond effluent line to the Keowee River (See Figure 2.0-1).
2.0.1.1 LIQUID RADWASTE EFFLUENT LINE RELEASE RATE LIMIT CALCULATION Liquid releases to the Keowee Hydroelectric Unit Tailrace normally contain the radioactive releases from the site including effluents from the Waste Monitor Tanks, Recycle Monitor Tanks, and Decant Monitor Tanks. The Keowee Tailrace discharge point can also contain Turbine Building Sump Monitor Tank (TBSMT) releases, however TBSMT effluent normally contains very low (if any) activity, and, therefore is transferred to the #3 Chemical Treatment Pond prior to release. Dilution flow for the liquid radwaste effluent line is provided by the Keowee Hydroelectric Unit and the Keowee Hydro Fire Protection liquid waste release mixing line. For purposes of the release rate calculation, Keowee hydro dilution flow is assumed to be a minimum leakage flow of 38 cfs, and a maximum flow of 6600 cfs based on one hydro unit operating at 50% power. The Keowee Hydro Fire Protection liquid waste release mixing line provides an additional 38 cfs dilution flow. Since Keowee Hydro typically releases only a small percentage of time during the year, 76 cfs (38 cfs leakage + 38 cfs mixing line) is normally assumed for dilution flow when performing liquid release rate calculations.
To comply with Technical Specifications and Selected Licensee Commitments, and to assure that the concentration of radioactive liquid effluents released from the site to the unrestricted area is limited to 10 times the effluent concentrations (ECs) of 10CFR20, Appendix B, Table 2, Column 2, and 2.0E-04 µCi/ml for dissolved and entrained noble gases, the following release rate limit calculation shall be performed for liquid releases to the Keowee Hydro Tailrace via the liquid radwaste effluent line:
f F ÷ (DF 1 ) Condition: DF > 1.0 Equation 2.1 where:
f = the undiluted effluent flow, in gpm.
F = the dilution flow available, in gpm.
= normally 3.41E+04 gpm (76 cfs, based on a leakage rate of 38 cfs (19 cfs per Keowee Hydro unit), plus the Keowee Hydro Fire Protection liquid waste release Section 2 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 mixing line whose flow rate is 38 cfs. When Keowee Hydro enters an outage one of the two units is taken offline which temporarily reduces the amount of leakage by half. Therefore, during a Keowee Hydro outage the dilution flow is assumed to be 57 cfs (19 cfs leakage plus 38 cfs raw water, (2.56E+04 gpm)).
= or 2.9E+06 gpm (6600 cfs, based on one hydro unit operating at 50% power).
This value is only used if it is known that Keowee Hydro is discharging.
DF = required dilution factor to be applied to the undiluted effluent flow, unitless.
Ci DF = x (10 x ECi )
Equation 2.2 i
Note:
If DF 1.0 then no dilution is required and the release rate is unrestricted.
If DF > 1.0 then dilution flow is required and the release rate is calculated using Equation 2.1. Equation 2.1 is used only when DF > 1.0.
= the most restrictive recirculation factor at equilibrium, (dimensionless). The recirculation factor accounts for the fraction of discharged water reused by the station. This value equals 1.0 since discharged liquid effluent is not reused at Oconee.
Ci = the concentration of radionuclide, i, in the undiluted liquid effluent, in µCi/ml.
ECi = the concentration of radionuclide, i, from 10CFR20, Appendix B, Table 2, Column 2, in µCi/ml. Note: if radionuclide, i, is a dissolved noble gas, then ECi
= 2.00E-05 µCi/ml.
Once the maximum release rate, f, is calculated the value is multiplied by 0.8 for additional conservatism.
2.0.1.2 #3 CHEMICAL TREATMENT POND EFFLUENT LINE DISCHARGE The #3 Chemical Treatment Pond (CTP) effluent line is the release point for station effluents that are normally considered to be non-radioactive; that is, the pond's effluent will not normally contain measurable activity above background with the exception of very low tritium activity. Tritium releases from the #3 CTP typically account for much less than 1% of the station total tritium release. It is assumed that no activity is present in the effluent unt il indicated by radiation monitoring measurements on the pond's inputs and/or by periodic analyses of the composite sample collected at the pond's discharge point. Inputs to this pond include the station's yard drain system, the decant water from the Powdex system, the discharge from the Turbine Building Sump system, and Radwaste Facility monitor tanks whose contents have been determined to be below Section 2 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 background. Inputs that have radiation monitors associated with them will be set to assure that Selected Licensee Commitment 16.11-1 will not be exceeded. #3 CTP is a continuous release path that discharges to the Keowee River (see Figure 2.0-1).
The #3 CTP may also be the discharge path for large volumes of slightly contaminated water following a primary-to-secondary leak so long as administrative procedures are implemented to assure that release rate calculations similar to that used in Section 2.0.1.1 are performed, that all detectable radionuclides will be accounted for, and that no station limits will be exceeded.
Section 2 - Page 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 2.0-1 Liquid Radwaste Discharge Locations Section 2 - Page 4
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 2.0.2 GASEOUS RELEASE RATE LIMIT CALCULATIONS The three unit vents are the primary gaseous radioactive release points at Oconee. The unit vents are the semi-elevated release points for waste gas decay tanks, containment building purges, auxiliary building ventilation, spent fuel pool ventilation, and the condenser air ejector (see Figure 1.0-2, pages 1, 2, and 3). Each unit vent contains multi-range radiation monitors (RIAs) and flow rate measuring instrumentation.
There are four other separate gaseous effluent release points at Oconee; the Hot Machine Shop, Interim Radwaste Building, Radwaste Facility, and RCP Refurbishment Facility that are normally considered non-radioactive; that is, it is possible but unlikely that the effluent will contain measurable activity above background. Each of these release points are considered ground-level, and each has an effluent sampler and flow monitoring device (see Figure 1.0-2, page 4). In addition, the Interim Radwaste Building and Radwaste Facility have a RIA.
2.0.2.1 UNIT VENT DISCHARGE RELEASE RATE LIMIT CALCULATION In order to comply with Technical Specifications and Selected Licensee Commitments and to assure that the dose rate, at any time, at or beyond the site boundary due to radioactive materials released in gaseous effluents from the site is limited to: 500 mrem/yr to the total body, and 3000 mrem/yr to the skin for the noble gases, and is limited to 1500 mrem/yr to any organ for radioiodine and for radioactive materials in particulate form, and radionuclides other than noble gases with half lives greater than 8 days, the following release rate and radiation monitor setpoint calculations shall be performed for releases from the waste gas decay tanks and the containment building. The release rate calculations when solved for the flow rate, f, are the release rates for noble gases and for radioiodines, particulates and other radionuclides with half- lives greater than 8 days. The most conservative release rate calculated shall control the flow rate. The following equations are based on the site dose rate limits. When applied to the individual release points the site dose rate values are apportioned 1/3 to each unit vent.
- a. Noble Gases Total Body:
K i x x Qi < 500 mrem/yr Equation 2.3 i Q Skin:
(L + 1.1M ) x i i x Qi < 3000 mrem/yr Equation 2.4 i Q Section 2 - Page 5
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44
- b. Radioiodines, Particulates, and Others Inhalation and Ingestion Organ Pathways:
(P p i opi x W x Qi x Ei) < 1500 mrem/yr To include both the food and ground organ dose and the inhalation organ dose the equation can be expanded to:
({( P )
p i opi food/gr x WD / Q + (Popi )inhal x W / Q} x Q i x Ei ) < 1500 mrem/yr Equation 2.5 where:
Ki = the total body dose factor due to gamma emissions for each identified noble gas radionuclide, i, in mrem/yr per µCi/m3 (See Appendix A).
Li = the skin dose factor due to beta emissions for each identified noble gas radionuclide, i, in mrem/yr per µCi/m3 (See Append ix A).
Mi = the air dose factor due to gamma emissions for each identified noble gas radionuclide, i, in mrad/yr per µCi/m3 (See Appendix A).
Popi = the dose parameter for radionuclides other than noble gases for the inhalation pathway, in mrem/yr per µCi/m3 and for the food and ground plane pathways in (m2 x (mrem/yr per µCi/sec)) for organ, o, and radionuclide, i, (See Appendix B for the pathway specific dose commitment factors). Note: NUREG-0133, page 25, specifies use of the Infant age group for the Popi values. For the H-3 milk pathway, the /Q value is used in Equation 2.5 rather than the D/Q value.
/Q = the highest calculated annual average dispersion parameter for any area at or beyond the site boundary in sec/m3 . For the Oconee Unit Vents this value is 1.672E-6 sec/m3 . The location is the SW sector at 1.0 mile for semi-elevated releases. For the Hot Machine Shop, Interim Radwaste Building, Radwaste Facility, and RCP Refurbishment Facility this value is 7.308E-6 sec/m3 . The location is the SE sector at 1.0 mile for ground-level releases. As discussed in Oconee UFSAR Section 2.1.1.3, the boundary for establishing gaseous effluent release limits is the exclusion area boundary (EAB). The EAB is defined as a 1 mile radius from the station center.
W = the highest calculated annual average dispersion or deposition parameter for estimating the maximum dose rate to an individual from the total inhalation, food, and ground plane pathways resulting from semi-elevated releases or ground-level releases:
Section 2 - Page 6
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 W/Qse = 1.672E-6 sec/m3 , for the inhalation pathway and the H-3 milk pathway. The location is the SW sector at 1.0 mile for semi-elevated releases.
WD/Qse = 1.295E-8 m-2 , for the food and ground plane pathways. The location is the NE sector at 1.0 mile for semi-elevated releases.
W/Qgl = 7.308E-6 sec/m3 , for the inhalation pathway and the H-3 milk pathway. The location is the SE sector at 1.0 mile for ground-level releases.
WD/Qgl = 2.259E-8 m-2 , for the food and ground plane pathways. The location is the NE sector at 1.0 mile for ground-level releases.
Ei = the filter removal factor for radionuclide, i, e.g., for 99% removal Ei = 0.01.
Qi = the release rate of radionuclide, i, in gaseous effluent from all release points at the site, in µCi/sec.
Qi = k 1C if ÷ k 2 = 4.72E + 02 x Cif Equation 2.6 where:
Ci = the concentration of radionuclide, i, in undiluted gaseous effluent, in µCi/ml.
f = the undiluted effluent flow, in ft3 /min.
k1 = conversion factor, 2.83E+04 cc/ft3 .
k2 = conversion factor, 6.0E+01 sec/min.
Substituting the expression for Qi in Equation 2.6 into Equations 2.3, 2.4, and 2.5, and solving for the flow rate, f, in each equation gives:
Noble Gases - Total Body Maximum Release Rate:
500 f tb <
4.72E + 02 x / Q x (K i
i x Ci )
Noble Gases - Skin Maximum Release Rate:
3000 f sk <
4.72E + 02 x /Q x [( Li + 1.1Mi ) x Ci]
i Section 2 - Page 7
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Radioiodines, Particulates, and Others - Organ Maximum Release Rate:
1500 f or <
4.72E + 02 x p
({(Popi ) food/gr x WD / Q + ( Popi )inhal x W / Q} x Ei x Ci) i f tb , f sk, and for, are calculated for each batch prior to release. The most limiting gaseous release rate is used to assure that no instantaneous dose rate limit is exceeded.
Section 2 - Page 8
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Derivations of Iodine, Particulate, and H-3 Dose Commitment Factors (Popi )
Ground Plane Deposition Pathway - Infant Age Group (1 e i t )
Popi = K K DFG i
oi Formula: from NUREG-0133, pages 25 and 26.
Where:
Popi Dose commitment factor for infant age group, organ o, nuclide i, for ground plane deposition pathway (m2 *mrem/yr per µCi/sec). (See Appendix B for the pathway specific dose commitment factors). Note:
As tritium is a weak beta emitter, the ground plane contribution is 0 for tritium (from NUREG-0133).
K' Units conversion factor pCi/µCi (106 ).
K" Units conversion factor 8760 hr/year.
DFGoi Ground plane dose conversion factor for organ o, nuclide i (mrem/hr per pCi/m2 ), from Table E-6 of Regulatory Guide 1.109.
i Nuclide decay constant for nuclide i (sec-1 ).
t Exposure time, 3.15x107 seconds (1 year) (from NUREG-0133).
Inhalation Pathway - Infant Age Group P = K ( BR )( DFA )
opi oi Formula: from NUREG-0133, page 25.
Where:
Popi Dose commitment factor for infant age group, organ o, nuclide i, for the inhalation pathway (mrem/yr per µCi/m3 ). (See Appendix B for the pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106 ).
BR Breathing rate for the infant age group (m3 /yr, from Regulatory Guide 1.109):
Infant - 1400 DFAoi Organ inhalation factor dose conversion factor for organ o, nuclide i, age group a (mrem/pCi), from Table E-10 of Regulatory Guide 1.109.
Section 2 - Page 9
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Food - Cow Milk - Infant Age Group Q (U ) it P opi = K ( r ) F p F mi ( DFL ) e f
( i +
oi Y p w )
Formula: from NUREG-0133, pages 26 and 27.
Where:
Popi Dose commitment factor for infant age group, organ o, nuclide i, for food pathway (m2 *mrem/yr per µCi/sec). (See Appendix B for the pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106 ).
QF Cow consumption rate (50 kg/day, from Regulatory Guide 1.109).
Up Consumption rate of cow milk for the infant age group (liters/yr, from NUREG-0133, page 27).
Infant - 330 r Fraction of deposited activity retained on cows feed grass (from Regulatory Guide 1.109.
1.0 for radioiodine.
0.2 for particulates.
Yp Agricultural productivity by unit area of pasture feed grass (0.7 kg/m2 , from Regulatory Guide 1.109).
i Nuclide decay constant for nuclide i (sec-1 ).
w Decay constant for removal of activity on leaf and pla nt surfaces by weathering (5.73x10-7 sec-1 , from NUREG-0133).
DFLoi Ingestion dose conversion factor for nuclide i, organ o, from Table E-14 of Regulatory Guide 1.109 (mrem/pCi).
Fmi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-1 of Regulatory Guide 1.109 for cow milk.
tf Transport time from pasture to cow, to milk, to infant (1.73E+05 seconds, from Regulatory Guide 1.109).
Section 2 - Page 10
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Food - Tritium - Cow Milk - Infant Age Group Popi = K K F mi Q f U p ( DFL oi ) [0 . 75 ( 0 . 5 / H ) ]
Formula: from NUREG-0133, page 27.
Where:
Popi Dose commitment factor for infant age group, organ o, nuclide i, for the grass/cow/milk pathway (mrem/yr per µCi/m3 ). (See Appendix B the pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106 ).
K" Units conversion factor gm/kg (103 ).
QF Cow consumption rate (50 kg/day, from Regulatory Guide 1.109).
Up Consumption rate of cow milk for the infant age group (liters/yr, from NUREG-0133, page 27).
Infant - 330 DFLoi Ingestion dose conversion factor for nuclide i, organ o, from Table E-14 of Regulatory Guide 1.109 (mrem/pCi).
Fmi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-1 of Regulatory Guide 1.109 for cow milk.
0.75 Fraction of total feed that is water. (From NUREG-0133).
0.5 Ratio of specific activity of feed grass water to atmospheric water.
(From NUREG-0133).
H Absolute humidity of the atmosphere (8 gm/m3 , from Regulatory Guide 1.109).
Section 2 - Page 11
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 3.0 SETPOINT CALCULATIONS 3.0.1 LIQUID RADIATION MONITOR SETPOINT CALCULATIONS As shown on Figure 1.0-1, RIA-33 is the controlling radiation monitor for liquid batch releases at Oconee. Once the liquid release rate parameters have been established radiation monitor setpoints shall be calculated to assure that the concentration of radioactive liquid effluents released from the site to the unrestricted area is limited to ten times the effluent concentrations (ECs) of 10CFR20, Appendix B, Table 2, Column 2, and 2.0E-04 µCi/ml for dissolved and entrained noble gases. By substituting the dilution factor (DF) from Equation 2.2 into Equation 2.1, solving for the undiluted liquid effluent concentration, Ci, and accounting for the monitor background reading, the liquid radiation monitor setpoint can be readily obtained by multiplying Ci by the radiation monitor correlation factor, CFi, as follows:
Ci (F + f ) x (10 x ECi )
Equation 3.1 x f SP (C i
i x CFi ) + bkg Equation 3.2 where:
Ci = the maximum allowable concentration of radionuclide, i, in the undiluted liquid effluent, in µCi/ml.
SP = radiation monitor setpoint, in cpm.
CFi = radiation monitor correlation factor for radionuclide, i, in cpm/µCi/ml =
8.00E+07 cpm/µCi/ml for RIA-33.
bkg = background reading for the radiation monitor, in cpm.
All other parameters were previously defined.
Using conservative or "worst-case" parameters in Equation 3.1 and Equation 3.2 can provide a liquid radiation monitor setpoint that does not need to be revised for every release if activity is low enough to allow for this type of operation such as with continuous releases from the #3 CTP release point. However, for batch releases, e.g.,
waste monitor tanks, through the liquid radwaste effluent line to the Keowee hydro Section 3 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 tailrace the RIA-33 radiation monitor setpoints are calculated based on the actual expected activity in the release as follows:
First the "Correlation Concentration" (C CONC) is calculated:
C CONC = (C i
i x EQi )
where:
Ci = Undiluted liquid effluent concentration for each isotope, excluding tritium,
µCi/ml.
EQi = RIA-33 Cs-137 equivalence factor for each isotope, excluding tritium, to that of Cs-137 due to different gamma energies and abundance. This factor includes a 4-hour decay time due to the average time between sample and release. (See Table 3.0-1)
Next the RIA-33 setpoints are determined as follows:
If C CONC is > 9.0E-6 µCi/ml then three setpoint values are calculated. The actual "expected" count rate for the release is defined as the "Midpoint of Expected Range".
The Alert setpoint is defined as 1.5 times the expected counts from activity in the liquid effluent plus background. If the Alert setpoint is exceeded, but there is no upward trend, the release will be allowed to continue. If RIA-33 continues to trend upward then the release will be manually terminated. The "Upper Limit of Expected Range" is defined as 3 times the expected counts from activity in the liquid effluent plus background. The Upper Limit of Expected Range is called the "Trip" setpoint. If the Trip setpoint is exceeded the release will be automatically terminated. The "Lower Limit of Expected Range" is defined as 3 times lower than the expected counts from activity in the liquid effluent plus background. The Lower Limit of Expected Range provides assurance that the correct liquid effluent is being released. If the RIA-33 count rate does not increase to at least the Lower Limit of the Expected Range then the release will be terminated, and a new sample analysis will be performed. The four RIA-33 setpoints are calculated as follows:
Lower Limit of Expected Range = C CONC x (8.00E7/3) cpm/(µCi/ml) +
RIA-33 BKG Midpoint of Expected Range = C CONC x 8.00E7 cpm/(µCi/ml) +
RIA-33 BKG Alert Setpoint = C CONC x (8.00E7x1.5) cpm/(µCi/ml) +
RIA-33 BKG Upper Limit of Expected Range = C CONC x (8.00E7x3) cpm/(µCi/ml) +
(Trip Setpoint) RIA-33 BKG Section 3 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 If C CONC is 9.05E-6 µCi/ml then the RIA-33 setpoint is 2.16E3 cpm plus background (BKG) as the Upper Limit of Expected Range. This setpoint is used for low activity releases, and is based on limiting the concentration in the effluent to 10 times the 10CFR20 EC of Cs-134 which has the lowest effluent concentration value (9.0E-7
µCi/ml) for any detectable radionuclide in the effluent.
Section 3 - Page 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Table 3.0-1 RIA-33 Cs-137 Equivalents Isotope Equivalence Isotope Equivalence Isotope Equivalence Factor Factor Factor Be-7 0.1462 Mo-99 0.2668 La-141 0.0155 F-18 0.5788 Tc-99m 0.00 La-142 0.2942 Na-24 0.8519 Tc-101 0.00 Ce-141 0.00 Cl-38 0.0090 Ru-103 1.3368 Ce-143 0.7826 K-40 0.1094 Ru-105 0.8783 Ce-144 0.0273 Cr-51 0.1438 Ru-106 0.4429 I-130 3.3095 Mn-54 1.0617 Ag-108m 3.4473 I-131 1.4051 Mn-56 0.4992 Ag-110m 3.5179 I-132 1.0259 Fe-59 1.0556 Cd-115 0.5201 I-133 1.1857 Co-57 0.0022 Cd-115m 0.0235 I-134 0.1388 Co-58 1.4735 In-115m 0.3631 I-135 0.9374 Co-60 2.0495 Sb-122 0.9218 Ar-41 0.2229 Cu-64 0.3954 Sb-124 2.1617 Kr-85 0.0059 Ni-65 0.1591 Sb-125 1.1308 Kr-85m 0.4280 Zn-65 0.5584 Sb-126 5.1762 Kr-87 0.1213 Zn-69m 1.1391 Sn-113 0.9971 Kr-88 0.5278 Se-75 1.3092 Sn-123 0.0066 Kr-89 0.00 Br-80m 0.0860 Sn-126 0.00 Xe-131m 0.0167 Br-82 3.4691 Te-125m 0.00 Xe-133 0.0006 Br-83 0.0059 Te-127 0.0134 Xe-133m 0.1172 Br-84 0.0053 Te-127m 0.0001 Xe-135 0.8564 Br-85 0.00 Te-129 0.0138 Xe-135m 0.00 Rb-86 0.0894 Te-129m 0.0507 Xe-137 0.00 Rb-88 0.00 Te-131 0.0008 Xe-138 0.00 Rb-89 0.00 Te-131m 1.8463 Nd-147 0.2619 Sr-89 0.0002 Te-132 0.9766 Hf-181 1.4209 Sr-91 0.6460 Te-134 0.0408 W-187 0.8027 Sr-92 0.3900 Cs-134 2.5804 Tl-208 0.00 Y-91 0.0031 Cs-136 3.1916 Bi-212 0.0144 Y-91m 0.0439 Cs-137 1.00 Bi-214 0.0003 Y-92 0.1334 Cs-138 0.0120 Pb-212 0.4497 Y-93 0.1091 Ba-133 1.3648 Pb-214 0.0020 Zr-95 1.0909 Ba-139 0.0203 Ra-226 0.0320 Zr-97 1.1210 Ba-140 0.5307 Ac-228 0.8261 Nb-95 1.0821 Ba-141 0.0002 Th-228 0.0038 Nb-95m 0.2919 Ba-142 0.00 Np-239 0.3996 Nb-97 0.1164 La-140 2.3237 Section 3 - Page 4
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 3.0.2 GASEOUS RADIATION MONITOR SETPOINT CALCULATIONS The unit vent radiation monitor setpoints are established at the Oconee Nuclear Station to help ensure that gaseous release rate limits are not exceeded. For some release pathways in which a specific RIA exists, the setpoints also help to ensure that the effluent being released is the same concentration as indicated by manual samples, e.g. effluent from waste gas decay tanks, thereby reducing the likelihood of releasing the wrong tank. For instances in which the RIA which normally controls the release is not operable, or is "out of service", independent manual samples (IMS) are collected and the noble gas constituents from both samples are compared to help ensure that the intended "batch" is being released. For certain low potential release types, e.g. Integrated Leak Rate Tests, no RIA exists to ensure that release rate limits are not exceeded or to ensure that the effluent being released is the "expected" concentration. For such pathways, independent manual samples are required to be collected and noble gas constituents compared prior to release. The following list defines the controlling RIA for the various gaseous effluent release types at Oconee:
Pathway Controlling RIA Unit 1 "A" Waste Gas Decay Tank 1&2 RIA 37/38 Unit 1 "B" Waste Gas Decay Tank 1&2 RIA 37/38 Unit 1 "C" Waste Gas Decay Tank 1&2 RIA 37/38 Unit 1 "D" Waste Gas Decay Tank 1&2 RIA 37/38 Unit 3 "A" Waste Gas Decay Tank 3 RIA 37/38 Unit 3 "B" Waste Gas Decay Tank 3 RIA 37/38 Unit 3 "C" Waste Gas Decay Tank 3 RIA 37/38 Unit 1 Reactor Building Purge 1 RIA 45/46 Unit 2 Reactor Building Purge 1 RIA 45/46 Unit 3 Reactor Building Purge 1 RIA 45/46 Unit 1 Depressurization IMS 1 RIA 45/46 Alarm Only Unit 2 Depressurization IMS 2 RIA 45/46 Alarm Only Unit 3 Depressurization IMS 3 RIA 45/46 Alarm Only Unit 1 Hydrogen Recombiner IMS 1 RIA 45/46 Alarm Only Unit 2 Hydrogen Recombiner IMS 2 RIA 45/46 Alarm Only Unit 3 Hydrogen Recombiner IMS 3 RIA 45/46 Alarm Only Unit 1 Integrated Leak Rate Test IMS Unit 2 Integrated Leak Rate Test IMS Unit 3 Integrated Leak Rate Test IMS The following sections describe the methods by which setpoints are established. In general, gaseous radiation monitors are calibrated to Xe-133, and for continuous release points, e.g., the three unit vents, are preset at a maximum value based on the 500 mrem/year total body gaseous release rate limit according to the following methodology:
Section 3 - Page 5
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Note: when applied to the individual release points the 500 mrem/year site dose rate value is apportioned 30% to each Unit Vent (RIA-45 and RIA-46) semi-elevated release point.
The remaining 10% is allocated to the four ground-level release points, the Hot Machine Shop (no monitor), Interim Radwaste Building (RIA-53), Radwaste Facility (4RIA-45 and 4RIA-46) and RCP Refurbishment Facility (no monitor), that are normally considered non-radioactive. Recall from Section 2.0.2.1 the following equation:
KXe 133 x / Q x QXe 133 < 500 mrem/yr Solve for QXe-133:
500 QXe 133 < Equation 3.4 KXe 133 x / Q From Equation 2.6:
QXe 133 = 4.72E + 02 x CXe 133 x f Equation 3.5 Substitute Equation 3.5 into Equation 3.4:
500 4.72E + 02 x CXe 133 x f <
KXe 133 x / Q Solve for CXe-133:
500 CXe 133 <
4.72E + 02 x f x KXe 133 x / Q CXe 133 SP = + bkg Equation 3.6 CF where:
KXe-133 = 2.94E+02, the total body dose factor due to gamma emissions for Xe-133, in mrem/year per µCi/m3 (See Appendix A).
/Q = the highest calculated semi-elevated annual average dispersion parameter for any area at or beyond the site boundary in sec/m3. For Oconee this value is 1.672E-6 sec/m3. The location is the SW sector at 1.0 mile.
QXe-133 = Xe-133 equivalent release rate limit for the noble gas total body dose pathway, in µCi/sec.
4.72E+02 = Conversion factor, (cc/ft3)/(sec/min).
Section 3 - Page 6
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 CXe-133 = the maximum allowable Xe-133 equivalent concentration in the gaseous effluent, in µCi/cc.
f = the gaseous effluent flow from the tank, building, or vent, in ft3/min.
SP = radiation monitor setpoint, in cpm.
CF = the Xe-133 equivalent monitor correlation factor, in µCi/cc/cpm.
bkg = the radiation monitor background reading, in cpm.
Equation 3.6 provides the methodology to calculate the maximum setpoint for releases from the Unit Vents (RIA-45 and RIA-46), Radwaste Facility (4RIA-45 and 4RIA-46),
and Interim Radwaste Building (RIA-53).
3.0.2.1 UNIT VENTS SETPOINTS (RIA-45 and RIA-46)
Reactor Building purges from all 3 units are released via the applicable unit vent, either Unit 1, Unit 2, or Unit 3. Each of the 3 unit vents are monitored by a normal/low range RIA (RIA-45) and a high range RIA (RIA-46). In addition to Reactor Building purges, all other releases from the main plant, including the Auxiliary Building ventilation, Waste Gas Decay Tanks, and the Spent Fuel Pools are monitored by each unit's RIA-45 and RIA-46. However, RIA-45 and RIA-46 on each unit vent have release termination authority only for Reactor Building purge releases. Each unit's RIA-45 and RIA-46 will, when operable, activate Control Room alarms if the unit vent concentration exceeds the monitor's setpoint value. The setpoints for each unit's RIA-45 and RIA-46 are established on a "worst case" basis, with the upper bound normally set at 30 percent of the station release rate limit for noble gases in Xe-133 equivalent concentration as follows:
Recall Equation 3.6:
500 CXe 133 <
4.72E + 02 x f x KXe 133 x / Q 150 RIA 45unit vent =
4.72E + 02 x 6.5E + 04 x 2.94E + 02 x 1.672E 06 x 7.09E 08 RIA 45unit vent 1.40E + 05 cpm + bkg Section 3 - Page 7
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 where:
150 = 30% of the 500 mrem/yr total body release rate limit.
6.5E+04 = Unit Vent flow rate with Reactor Building Purge off, ft3/min.
1.672E-06 = Highest Semi-Elevated release point dispersion factor, sec/m3.
7.09E-08 = RIA-45 Correlation Factor, µCi/ml/cpm.
All other factors were previously defined.
150 RIA 46unit vent =
4.72E + 02 x 6.5E + 04 x 2.94E + 02 x 1.672E 06 x 3.17 E 04 RIA 46unit vent 31 cpm + bkg where:
3.17E-04 = RIA-46 Correlation Factor, µCi/ml/cpm.
All other factors were previously defined.
For instances in which the Reactor Building Purge is on, the setpoint is multiplied by 0.65 (65,000 cfm/ (65,000 cfm + 35,000 cfm purge flow)).
3.0.2.2 RADWASTE FACILITY SETPOINTS (4RIA-45 and 4RIA-46) 25 4 RIA 45 and 4RIA - 46 =
4.72E + 02 x 1.297E + 05 x 2.94E + 02 x 7.308E 06 4 RIA 45 and 4RIA - 46 1.90E - 04 µCi/ml where:
25 = 5% of the 500 mrem/yr total body release rate limit.
1.297E+05 = Radwaste Facility Vent flow rate, ft3/min.
7.308E-06 = Highest Ground-Level release point dispersion factor, sec/m3.
All other factors were previously defined.
4RIA-45 and 4RIA-46 reads in units of concentration, µCi/ml.
Section 3 - Page 8
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 3.0.2.3 INTERIM RADWASTE BUILDING SETPOINTS (RIA-53) 25 RIA 53 =
4.72E + 02 x 1.5E + 04 x 2.94E + 02 x 7.308E 06 x 3.4E 08 RIA 53 4.8E + 04 cpm + bkg where:
25 = 5% of the 500 mrem/yr total body release rate limit.
1.5E+04 = Interim Radwaste Building Vent flow rate, ft3/min.
7.308E-06 = Highest Ground-Level release point dispersion factor, sec/m3.
3.4E-08 = RIA-53 Correlation Factor, µCi/ml/cpm.
All other factors were previously defined.
In addition to the maximum setpoints discussed previously, Oconee uses "Alert" setpoints that are based on 10% of the reporting requirement from 10CFR50.73(a)(2)(viii)(A).
Each unit vent Alert setpoint is based on 60% of a Xe-133 Effluent Concentration (EC) value of 5.0E-07 µCi/ml at the site boundary. The Interim Radwaste Building and Radwaste Facility are each set at 10% of the Xe-133 EC. The method used to calculate the Alert setpoints is similar to that used to calculate the maximum setpoints except that the limit is based on concentration rather than dose rate. The Alert setpoints are approximately 42% of the maximum setpoints.
3.0.2.4 WASTE GAS DECAY TANK SETPOINTS (RIA-37 and RIA-38)
For batch releases where the effluent can contain activity significantly above background, e.g., Waste Gas Decay Tank (WGDT), two additional monitors, RIA-37 and RIA-38 are used to establish setpoints for each WGDT batch released. RIA-37 is the normal/low range noble gas monitor, and RIA-38 is the high range noble gas monitor. The following setpoint methodology is used:
CXe 133 = (C i
i x Eqi )
CXe 133 Expected Cpm = + bkg CFXe 133 CXe 133 RIA - 37 and RIA - 38 Setpoint = x 1 .5 Equation 3.7 CFXe 133 Section 3 - Page 9
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 where:
CXe-133 = Xe-133 equivalent concentration of the WGDT to be released, in µCi/ml.
Eqi = Xe-133 equivalence factor for each noble gas isotope, excluding tritium, to that of Xe-133 due to different beta energies and abundance.
(See Table 3.0-2).
CFXe-133 = The expected RIA response to a given Xe-133 equivalent concentration, in
µCi/ml/cpm. 1RIA-37 = 1.01E-08 µCi/ml/cpm, 3RIA-37 = 4.20E-08
µCi/ml/cpm, 1RIA-38 and 3RIA-38 = 1.34E-03 µCi/ml/cpm.
1.5 = An adjustment factor to account for expected minor variations in effluent concentration and RIA background.
When the release pathway is from any Unit 1 WGDT (A-D), and the Xe-133 equivalent concentration is less than 2.8E-01 µCi/ml, the 1&2 RIA-38 setpoint is established at 313 cpm, and the 1&2 RIA-37 setpoint is calculated using Equation 3.7.
When the release pathway is from any Unit 1 WGDT (A-D), and the Xe-133 equivalent concentration is greater than 2.8E-01 µCi/ml, the 1&2 RIA-37 setpoint is established as offscale high, and the 1&2 RIA-38 setpoint is calculated using Equation 3.7.
When the release pathway is from any Unit 3 WGDT (A-C), and the Xe-133 equivalent concentration is less than 2.8E-01 µCi/ml, the 3 RIA-38 setpoint is established at 313 cpm, and the 3 RIA-37 setpoint is calculated using Equation 3.7.
When the release pathway is from any Unit 3 WGDT (A-C), and the Xe-133 equivalent concentration is greater than 2.8E-01 µCi/ml, the 3 RIA-37 setpoint is established as offscale high, and the 3 RIA-38 setpoint is calculated using Equation 3.7.
Section 3 - Page 10
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Table 3.0-2 Xe-133 Equivalents Isotope Equivalence Factor Kr-83m 0 Kr-85m 2.48 Kr-85 2.56 Kr-87 2.93 Kr-88 2.78 Kr-89 2.93 Kr-90 2.93 Xe-131m 1.69 Xe-133m 1.99 Xe-133 1.0 Xe-135m 0.83 Xe-135 2.63 Xe-137 2.93 Xe-138 2.93 Ar-41 2.82 C-11 2.70 Section 3 - Page 11
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 4.0 EFFLUENT DOSE MODELS The effluent dose models used to show compliance with 10CFR50, Appendix I ALARA design objectives, 40CFR190 fuel cycle dose limits, and the dose values given in station SLCs are based on the methodology given in NUREG-0133 and Regulatory Guide 1.109.
Dose contributions to the maximum individual shall be calculated at least every 31 days, quarterly, and annually using the RETDAS computer code which implements the ODCM methodology. RETDAS, Radioactive Effluent Tracking and Dose Assessment Software, is a database application designed by Canberra Industries, Inc. to automate many of the tasks required in the administration of effluent releases at Oconee. RETDAS performs normal operation effluent dose assessment using NUREG-0133 and Regulatory Guide 1.109 methodology.
Station long-term historical and dose projection calculations are performed periodically to determine the station's status with respect to meeting annual ALARA goals specified in the Oconee SLCs. Such calculations are used to verify that adequate margin remains during a report period to allow normal station and radwaste system operation, including anticipated operational occurrences, for the remainder of the report period without exceeding applicable goals. Station 31-day dose projections that are used to assess the need to reduce effluent releases with the Gaseous Waste (GW) or Liquid Waste (LW) systems as required in the Oconee SLCs are estimated by the previous month's calculated dose results.
Fuel cycle dose calculations shall be performed annually or as required by special reports.
Dose contributions shall be calculated using the RETDAS computer program.
4.0.1 LIQUID EFFLUENT DOSE MODEL FOR THE MAXIMUM EXPOSED INDIVIDUAL Of the possible exposure pathways in the aquatic environment, only three contribute significantly to the total dose; these pathways are ingestion of potable water and aquatic foods, and direct exposure from radioactivity deposited on the shoreline. The dose contribution from these pathways for measured quantities of radioactive materials identified in liquid effluents released to unrestricted areas shall be calculated for the maximum exposed individual in each age group using the methodology provided in this section.
Liquid waste processed by the LW system can be released to the environment at Oconee from two liquid discharge points; (1) directly to the Keowee Tailrace through RIA-33 and (2) to the Chemical Treatment Pond #3 discharge point into the Keowee River (See Figure 2.0-1). Liquid dose calculations for the maximum exposed individual are performed and documented in the Annual Effluent Release Report for both locations using the applicable activity release and dilution data for each liquid effluent release point. The primary liquid effluent discharge point for Oconee is to the Keowee Tailrace Section 4 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 through RIA-33. In general, only low activity tritium releases (<1% station total) occur through the Chemical Treatment Pond #3 discharge point into the Keowee River. Dose calculations are performed for each of the two liquid discharge points for dose reporting purposes. The highest calculated dose from the two dose calculations is used to define the maximum individual dose from liquid releases at Oconee.
Section 4 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Liquid Dose Calculations The following equation is used for calculating liquid dose to the maximum exposed individual at each of the two liquid effluent release points:
(A oapi x C i ) x t x Fn x 1
Dose oa =
p i Dw f
Fn = x f +F Formula: adapted from NUREG-0133, pages 15-17. Where:
Doseoa The cumulative dose commitment for organ o and age group a, from the liquid effluent for the total time period, t. (mrem)
Aoapi Dose commitment factor for organ o, age group a, pathway p, and nuclide i (mrem/hr per µCi/ml). (See Appendices C through F for age group and pathway specific dose commitment factors).
Ci The average concentration of nuclide i, in undiluted liquid effluent during the time period, t. (µCi/ml) t The length of time over which Ci and Fn are averaged for all liquid releases. (hr)
Fn The near field average dilution factor for Ci during the period of interest,
- t. Includes the recirculation factor. (dimensionless) f Average liquid radwaste flow during the period of interest, t. (gpm)
F Average dilution flow during the period of interest, t. (gpm)
Recirculation factor. (dimensionless)
Applies to potable water, aquatic foods, and shoreline sediment. Value Keowee Tailrace (Primary liquid effluent discharge location) 1.0*
Keowee River (CTP #3) 1.0 Dw Dilution factor from the near field area to the potable water intake;
=1.0E+04 for Oconee. This factor applies to the potable water pathway only. The nearest potable water intake to Oconee is located at the Andersen water intake approximately 31.5 miles from the site on a separate arm of Lake Hartwell. From a hydrology standpoint the Andersen water intake should not be affected by liquid effluent discharges from Oconee.
1.0E+04 is a conservatively small dilution factor.
- The recirculation factor accounts for the fraction of discharged water reused by the station. Liquid effluent discharge cannot be recirculated back into the Oconee station.
Therefore, the recirculation factor is 1.0 at Oconee.
Section 4 - Page 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Derivation of Liquid Dose Commitment Factors (Aoapi)
Potable Water
- i t p Aoapi = 1.14 x105 x U aw x Daoi x e Formula: from NUREG-0133, page 16 and Regulatory Guide 1.109, page 1.109-12.
Where:
Aoapi Dose commitment factor for organ o, age group a, pathway p, and nuclide i, (mrem/hr per µCi/ml). (See Appendices C through F for age group and pathway specific dose commitment factors).
1.14x105 Units conversion factor (pCi-yr-ml)/(µCi-hr-kg).
Uaw Water consumption rate in liters per year for age group a. From Table E-5, Regulatory Guide 1.109.
Adult - 730 Teen - 510 Child - 510 Infant - 330 Daoi Dose factor for age group a, organ o, nuclide i, in mrem/pCi. From tables E-11 through E-14 of Regulatory Guide 1.109.
i Decay constant for nuclide i, in sec-1.
tp Environmental transit time from release to receptor. Default =
4.32E+04 sec (12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />). From Regulatory Guide 1.109, Table E-15.
Section 4 - Page 4
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Aquatic Foods
-it p Aoapi = 1.14 x105 xU af x BFi x Daoi x e Formula: from NUREG-0133, page 16 and Regulatory Guide 1.109, page 1.109-12.
Where:
Aoapi Dose commitment factor for organ o, age group a, pathway p, and nuclide i, (mrem/hr per µCi/ml). (See Appendices C through F for age group and pathway specific dose commitment factors).
1.14x105 Units conversion factor (pCi-yr-ml)/(µCi-hr-kg).
Uaf Fish consumption rate for age group a (kg/yr). From Table E-5, Regulatory Guide 1.109.
Adult - 21 Teen - 16 Child - 6.9 Infant - 0 BFi Bioaccumulation factor for nuclide i, in fish, in units of pCi/kg per pCi/liter. From Table A-1 of Regulatory Guide 1.109.
Daoi Dose factor for age group a, organ o, nuclide i, in mrem/pCi. From tables E-11 through E-14 of Regulatory Guide 1.109.
i Decay constant for nuclide i, in sec-1.
tp Environmental transit time from release to receptor. Default =
8.64E+04 sec (1 day). From Regulatory Guide 1.109, Table E-15.
Section 4 - Page 5
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Shoreline Sediment 1
it p Aoapi = 1.14 x 10 x 100 x DFGoi x w x U as x Ti x e 5
2 x (1 e itb )
Formula: adapted from Regulatory Guide 1.109, page 1.109-14.
Where:
Aoapi Dose commitment factor for organ o, age group a, pathway p, and nuclide i, (mrem/hr per µCi/ml). (See Appendices C through F for age group and pathway specific dose commitment factors).
5 1.14x10 Units conversion factor (pCi-yr-ml)/(µCi-hr-kg).
100 Proportionality constant used in the sediment radioactivity model, (liters/(m2-day).
DFGoi Ground plane dose conversion factor for organ o, nuclide i (mrem/hr per pCi/m2), from Table E-6 of Regulatory Guide 1.109.
w Shoreline width factor. For Oconee = 0.2, from Table A-2, Regulatory Guide 1.109.
Uas Shoreline exposure rate for age group a (hr/yr), From Table E-5, Regulatory Guide 1.109.
Adult - 12 Teen - 67 Child - 14 Infant - 0 Ti1/2 Nuclide half life for nuclide i, in days.
i Nuclide decay constant for nuclide i.
tp Average transit time to point of exposure (0 hours0 days <br />0 hours <br />0 weeks <br />0 months <br />).
tb Sediment exposure time (15 years). Page 1.109-14.
Section 4 - Page 6
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 4.0.2 GASEOUS EFFLUENT DOSE MODEL FOR THE MAXIMUM EXPOSED INDIVIDUAL The dose contributions from measured quantities of radioactive materials identified in gaseous effluent released to unrestricted areas shall be calculated for the maximum gamma and beta air dose from noble gases, and for the maximum exposed individual from radioiodines, particulates, and others using the following equations:
Gaseous Dose Calculations Noble Gas Dose Calculations Gamma Air Dose Dose = 3.17 x108 x / Q x (M i x Qi )
i Formula: adapted from NUREG-0133, page 28.
Where:
Dose Gamma air dose for the time period of interest (mrad).
3.17x10-8 Inverse number of seconds in year (year/seconds).
Mi Gamma air dose factor due to gamma emissions for nuclide i (mrad/yr per µCi/m3). (See Appendix A).
/Q The highest calculated annual average relative concentration for any area at or beyond the site boundary (sec/m3)*. (See Table 6.0-9).
Qi Activity for nuclide i released during the time period of interest (µCi).
Beta Air Dose Dose = 3.17 x 10 8 x / Q x (N i x Qi )
i Formula: adapted from NUREG-0133, page 28.
Where:
Dose Beta air dose for the time period of interest (mrad).
3.17x10-8 Inverse number of seconds in year (year/seconds).
Ni Beta air dose factor due to beta emissions for nuclide i (mrad/yr per
µCi/m3). (See Appendix A).
/Q The highest calculated annual average relative concentration for any area at or beyond the site boundary (sec/m3)*. (See Table 6.0-9).
Qi Activity for nuclide i released during the time period of interest (µCi).
Section 4 - Page 7
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Iodine, Particulates, and H-3 Dose Organ Dose Calculation Dose oa = 3 .17 x 10 8 x W x p
(R i
oapi x Qi )
Formula: adapted from NUREG-0133, pages 29 & 30.
Where:
Doseoa The cumulative dose commitment to the total body or any organ o, for an individual of age group a (mrem).
3.17x10-8 Inverse number of seconds in year (year/seconds).
Roapi Dose commitment factor for organ o, age group a, pathway p, and nuclide i. The units are based on whether a dispersion or deposition factor is used. When a /Q is used the units are mrem/yr per µCi/m3.
When a D/Q is used the units are (m2
- mrem/yr) per µCi/sec. (See Appendices G through J for age group and pathway specific dose commitment factors).
W Dispersion (/Q) or deposition factor (D/Q)*. The factor used is based upon the pathway. Note: /Q is always used for tritium.
Pathway Factor Used Ground Plane Deposition D/Q (m-2)
Inhalation /Q (sec/m3)
Vegetation D/Q (m-2)
Grass/Cow/Milk D/Q (m-2)
Grass/Goat/Milk D/Q (m-2)
Grass/Cow/Meat D/Q (m-2)
Qi Activity for nuclide i, released during the time period of interest (µCi).
- The dose from noble gases released from semi-elevated release points, e.g., unit vent, is calculated using the semi-elevated dispersion factors. The dose from noble gases released from ground level release points, e.g., Radwaste Facility vent, is calculated using the ground level dispersion factors. The total dose is the sum of the semi-elevated and ground level dose calculations. Maximum individual organ dose is determined by calculating the organ dose at each of the /Q and D/Q locations shown in Table 6.0-9 and Table 6.0-10 (128 locations) for both semi-elevated release points and ground level release points, summing the two at each location, and then choosing the dose from the maximum location. Dose is calculated only for those pathways (e.g., garden, milk animal, etc.) that actually exist at each location as determined by the land use census shown in Table 6.0-3. As discussed in Oconee UFSAR Section 2.1.1.3, the boundary for establishing gaseous effluent release limits is the exclusion area boundary (EAB). The EAB is defined as a 1 mile radius from the station center.
Section 4 - Page 8
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Derivations of Iodine, Particulate, and H-3 Dose Commitment Factors (Roapi)
Ground Plane Deposition Pathway (1 e i t )
R oapi = K K ( SF ) DFG oi i
Formula: from NUREG-0133, page 32.
Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for ground plane deposition pathway (m2*mrem/yr per µCi/sec). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
K" Units conversion factor 8760 hr/year.
SF Shielding factor (dimensionless) (0.7, from Regulatory Guide 1.109).
DFGoi Ground plane dose conversion factor for organ o, nuclide i (mrem/hr per pCi/m2), from Table E-6 of Regulatory Guide 1.109.
-1 i Nuclide decay constant for nuclide i (sec ).
t Exposure time, 4.73x108 seconds (15 years).
Inhalation Pathway Roapi = K ( BRa )( DFAoi ) a Formula: from NUREG-0133, page 31.
Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for inhalation pathway (mrem/yr per µCi/m3). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
BRa Breathing rate for age group (m3/yr), from Regulatory Guide 1.109:
Adult - 8000 Teen - 8000 Child - 3700 Infant - 1400 (DFAoi)a Organ inhalation factor dose conversion factor for organ o, nuclide i, age group a (mrem/pCi), from Tables E-7 through E-10 of Regulatory Guide 1.109.
Section 4 - Page 9
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Vegetation R oapi = K (r )
[
x ( DFL o i ) a x U a f L e L it L
+ U aS f g e i t h ]
Yv ( i + w )
Formula: from NUREG-0133, page 35. Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for vegetation pathway (m2*mrem/yr per µCi/sec). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
r Fraction of deposited activity retained on vegetation, from Regulatory Guide 1.109.
1.0 for radioiodine.
0.2 for particulates.
Yv Vegetation areal density (kg/m2) (2.0, from Regulatory Guide 1.109).
-1 i Nuclide decay constant for nuclide i (sec ).
w Decay constant for removal of activity on leaf and plant surfaces by weathering (5.73x10-7 sec-1, from NUREG-0133).
(DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Reg. Guide 1.109 (mrem/pCi).
L U a Consumption rate of fresh vegetation for age group a (kg/yr) (from Regulatory Guide 1.109).
Adult - 64 Teen - 42 Child - 26 Infant - 0 fL Fraction of annual intake of fresh leafy vegetation grown locally (1.0, from NUREG-0133).
tL Average time between harvest of leafy vegetation and consumption (8.6x104 seconds, (1 day), from Regulatory Guide 1.109).
USa Consumption rate of stored vegetation for age group a (kg/yr) (from Regulatory Guide 1.109).
Adult - 520 Teen - 630 Child - 520 Infant - 0 fg Fraction of annual intake of stored vegetation (0.76, from Regulatory Guide 1.109).
th Average time between harvest of stored vegetation and consumption (5.18x106 seconds, (60 days), from Regulatory Guide 1.109).
Section 4 - Page 10
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Vegetation - Tritium
[ ]
R oapi = K' K' " U aL f L + U aS f g ( DFL oi ) a [0 . 75 ( 0 . 5 / H ) ]
Formula: from NUREG-0133, page 36.
Where:
Roapi Dose commitment factor for organ o, age group a, for vegetation pathway and tritium (mrem/yr per µCi/m3). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
K'" Units conversion factor gm/kg (103).
ULa Consumption rate of fresh vegetation for age group a (kg/yr) (from Regulatory Guide 1.109).
Adult - 64 Teen - 42 Child - 26 Infant - 0 fL Fraction of annual intake of fresh leafy vegetation grown locally (1.0, from NUREG-0133).
USa Consumption rate of stored vegetation for age group a (kg/yr) (from Regulatory Guide 1.109).
Adult - 520 Teen - 630 Child - 520 Infant - 0 fg Fraction of annual intake of stored vegetation (0.76, from Regulatory Guide 1.109).
(DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
0.75 Fraction of total feed that is water. (From NUREG-0133).
0.5 Ratio of specific activity of feed grass water to atmospheric water.
(From NUREG-0133).
H Absolute humidity of the atmosphere (8 gm/m3, from Regulatory Guide 1.109).
Section 4 - Page 11
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Grass/Cow/Milk Q F (U ) f p fs (1 f p f s ) e i t h i t f R oapi = K ap F mi ( r )( DFL )a + e i + w oi Y p Ys Formula: from NUREG-0133, pages 32 & 33. Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for grass/cow/milk pathway (m2*mrem/yr per µCi/sec). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
QF Cow consumption rate (50 kg/day, from Regulatory Guide 1.109)
Uap Consumption rate of cow milk for age group a (liters/yr, from Regulatory Guide 1.109).
Adult - 310 Teen - 400 Child - 330 Infant - 300 r Fraction of deposited activity retained on cows feed grass, (from Regulatory Guide 1.109).
1.0 for radioiodine.
0.2 for particulates.
Yp Agricultural productivity by unit area of pasture feed grass (0.7 kg/m2, from Regulatory Guide 1.109).
Ys Agricultural productivity by unit area of stored feed (2.0 kg/m2, from Regulatory Guide 1.109).
-1 i Nuclide decay constant for nuclide i (sec ).
w Decay constant for removal of activity on leaf and plant surfaces by weathering (5.73x10-7 sec-1, from NUREG-0133).
(DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
Fmi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-1 of Regulatory Guide 1.109 for cow milk.
fp Fraction of year that the cow is on pasture (1.0, from RG 1.109).
fs Fraction of the cow feed that is pasture grass while the cow is on pasture (1.0, from Regulatory Guide 1.109).
tf Transport time for pasture to cow, to milk, to receptor (1.73E+05 seconds, from Regulatory Guide 1.109).
th Transport time from pasture, to harvest, to cow, to milk, to receptor (7.78e+06 seconds, from Regulatory Guide 1.109).
Section 4 - Page 12
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Grass/Cow/Milk - Tritium Roapi = K K Fmi Q f U ap ( DFLio ) a [0.75(0.5 / H )]
Formula: from NUREG-0133, page 34.
Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for grass/cow/milk pathway (mrem/yr per µCi/m3). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
K'" Units conversion factor gm/kg (103).
QF Cow consumption rate (50 kg/day, from Regulatory Guide 1.109).
Uap Consumption rate of cow milk for age group a (liters/yr, from Regulatory Guide 1.109).
Adult - 310 Teen - 400 Child - 330 Infant - 300 (DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
Fmi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-1 of Regulatory Guide 1.109 for cow milk.
0.75 Fraction of total feed that is water (from NUREG-0133).
0.5 Ratio of specific activity of feed grass water to atmospheric water (from NUREG-0133).
H Absolute humidity of the atmosphere (8 gm/m3, from Regulatory Guide 1.109).
Section 4 - Page 13
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Grass/Goat/Milk Q F (U ap ) f p f s (1 f p f s ) e i t h it f R oapi = K Fmi ( r )( DFL oi ) a + e i + w Y p Ys Formula: from NUREG-0133, pages 32 & 33. Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for grass/goat/milk pathway (m2*mrem/yr per µCi/sec). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
QF Goat consumption rate (6 kg/day, from Regulatory Guide 1.109).
Uap Consumption rate of goat milk for age group a (liters/yr, from Regulatory Guide 1.109).
Adult - 310 Teen - 400 Child - 330 Infant - 300 r Fraction of deposited activity retained on goats feed grass, from Regulatory Guide 1.109.
1.0 for radioiodine.
0.2 for particulates.
Yp Agricultural productivity by unit area of pasture feed grass (0.7 kg/m2, from Regulatory Guide 1.109).
Ys Agricultural productivity by unit area of stored feed (2.0 kg/m2, from Regulatory Guide 1.109).
-1 i Nuclide decay constant for nuclide i (sec ).
w Decay constant for removal of activity on leaf and plant surfaces by weathering (5.73x10-7 sec-1, from NUREG-0133).
(DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
Fmi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-2 of Regulatory Guide 1.109 for goat milk.
fp Fraction of year that the goat is on pasture (1.0, from RG 1.109).
fs Fraction of the goat feed that is pasture grass while the goat is on pasture (1.0, from Regulatory Guide 1.109).
tf Transport time for pasture to goat, to milk, to receptor (1.73E+05 seconds, from Regulatory Guide 1.109).
th Transport time from pasture, to harvest, to goat, to milk, to receptor (7.78e+06 seconds, from Regulatory Guide 1.109).
Section 4 - Page 14
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Grass/Goat/Milk - Tritium Roapi = K K Fmi Q f U ap ( DFL oi ) a [0 .75 ( 0 .5 / H ) ]
Formula: from NUREG-0133, page 34.
Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for grass/goat/milk pathway (mrem/yr per µCi/m3). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
K'" Units conversion factor gm/kg (103).
QF Goat consumption rate (6 kg/day, from Regulatory Guide 1.109).
Uap Consumption rate of goat milk for age group a (liters/yr, from Regulatory Guide 1.109).
Adult - 310 Teen - 400 Child - 330 Infant - 300 (DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
Fmi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-2 of Regulatory Guide 1.109 for goat milk.
0.75 Fraction of total feed that is water (from NUREG-0133).
0.5 Ratio of specific activity of feed grass water to atmospheric water (from NUREG-0133).
H Absolute humidity of the atmosphere (8 gm/m3, from Regulatory Guide 1.109).
Section 4 - Page 15
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Grass/Cow/Meat Q F (U ap ) f p f s (1 f p f s ) e i t h it f R oapi = K F fi ( r )( DFL i ) a + e i + w Y p Ys Formula: from NUREG-0133, pages 34 & 35. Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for grass/cow/meat pathway (m2*mrem/yr per µCi/sec). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
QF Cow consumption rate (50 kg/day, from Regulatory Guide 1.109).
Uap Consumption rate of cow meat for age group a (kg/yr, from Regulatory Guide 1.109).
Adult - 110 Teen - 65 Child - 41 Infant - 0 r Fraction of deposited activity retained on cows feed grass (from Regulatory Guide 1.109).
1.0 for radioiodine.
0.2 for particulates.
Yp Agricultural productivity by unit area of pasture feed grass (0.7 kg/m2, from Regulatory Guide 1.109).
Ys Agricultural productivity by unit area of stored feed (2.0 kg/m2, from Regulatory Guide 1.109).
-1 i Nuclide decay constant for nuclide i (sec ).
w Decay constant for removal of activity on leaf and plant surfaces by weathering (5.73x10-7 sec-1, from NUREG-0133).
(DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
Ffi Stable element transfer coefficient for nuclide i, in days/kg, from Table E-1 of Regulatory Guide 1.109 for cow meat.
fp Fraction of year that the cow is on pasture (1.0, from RG 1.109).
fs Fraction of the cow feed that is pasture grass while the cow is on pasture (1.0, from Regulatory Guide 1.109).
tf Transport time from pasture to receptor (1.73E+06 seconds, from Regulatory Guide 1.109).
th Transport time from crop field to receptor (7.78E+06 seconds, from Regulatory Guide 1.109).
Section 4 - Page 16
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Grass/Cow/Meat - Tritium Roapi = K K F fi Q F U ap ( DFL oi ) a [0 .75 ( 0 .5 / H ) ]
Formula: from NUREG-0133, page 35.
Where:
Roapi Dose commitment factor for organ o, age group a, nuclide i, for grass/cow/meat pathway (mrem/yr per µCi/m3). (See Appendices G through J for age group and pathway specific dose commitment factors).
K' Units conversion factor pCi/µCi (106).
K'" Units conversion factor gm/kg (103).
QF Cow consumption rate (50 kg/day, from Regulatory Guide 1.109).
Uap Consumption rate of cow meat for age group a (kg/yr, from Regulatory Guide 1.109).
Adult - 110 Teen - 65 Child - 41 Infant - 0 (DFLoi)a Ingestion dose conversion factor for nuclide i, organ o, and age group a, from Tables E-11 through E-14 of Regulatory Guide 1.109 (mrem/pCi).
Ffi Stable element transfer coefficient for nuclide i, in days/liter, from Table E-1 of Regulatory Guide 1.109 for cow meat.
0.75 Fraction of total feed that is water (from NUREG-0133).
0.5 Ratio of specific activity of feed grass water to atmospheric water (from NUREG-0133).
H Absolute humidity of the atmosphere (8 gm/m3, from Regulatory Guide 1.109).
Section 4 - Page 17
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 4.0.3 DIRECT RADIATION Direct radiation is that radiation from confined sources, and does not include any external component from radioactive effluents. The point kernel method has been used to calculate offsite dose rates from radioactive materials stored in the refueling water storage tanks, reactor makeup water storage tanks, and temporary onsite radwaste storage tanks. Dose calculations using this method performed for Oconee Nuclear Station indicate direct radiation doses are much less than 0.01 mrem/yr and, therefore, make a negligible contribution to individual dose. Likewise, direct and air-scatter radiation dose contributions from the onsite Independent Spent Fuel Storage Installation (ISFSI) at Oconee have been calculated. The maximum dose rate to the nearest potential resident from the Oconee ISFSI is < 0.1 mrem/yr. Direct radiation doses will not be calculated routinely.
4.0.4 EFFLUENT APPORTIONMENT For the Oconee Nuclear Station the effluent releases are apportioned equally to each unit for each site as recommended by Section 3.1 of NUREG-0133, because the shared radwaste treatment systems at each site make it impractical to accurately ascribe releases to a specific reactor unit. For Annual Effluent Release Report purposes effluent releases are summed for each unit, and the maximum individual dose to the public is reported as a site total.
Section 4 - Page 18
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 5.0 FUEL CYCLE CALCULATIONS In accordance with the requirements of 40CFR190, the annual dose commitment to any member of the general public shall be calculated to assure that doses are limited to 25 millirems to the total body or any organ with the exception of the thyroid which is limited to 75 millirems. In accordance with the requirements of the Selected Licensee Commitments, the annual dose commitment shall also be calculated any time that one of the quarterly dose limits of the Selected Licensee Commitments is exceeded; these annual dose commitments may not just be calculated for the calendar year.
The "Uranium fuel cycle" is defined in 40CFR Part 190.02(b) as:
"Uranium fuel cycle means the operations of milling or uranium ore, chemical conversion of uranium, isotopic enrichment of uranium, fabrication of uranium fuel, generation of electricity by a light-water-cooled nuclear power plant using uranium fuel, and reprocessing of spent uranium fuel, to the extent that these directly support the production of electrical power for public use utilizing nuclear energy, but excludes mining operations, operations at waste disposal sites, transportation of any radioactive material in support of these operations, and the reuse of recovered non-uranium specia l nuclear and by-product materials from the cycle."
Based on this definition of the fuel cycle and the information in 10CFR51, Table S-3, and Wash-1248, the radiological impact of the following operations has been assessed for Oconee Nuclear Station:
5.0.1 MILLING No milling operations occur within fifty miles of the Oconee Nuclear Station.
5.0.2 CONVERSION No uranium hexafluoride production occurs within fifty miles of the Oconee Nuclear Station.
5.0.3 ENRICHMENT No uranium enrichment operations occur within fifty miles of the Oconee Nuclear Station.
5.0.4 FUEL FABRICATION No fuel fabrication operations occur within fifty miles of the Oconee Nuclear Station.
Section 5 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 5.0.5 NUCLEAR POWER PRODUCTION The production of electricity for public use using light-water-cooled nuclear power stations results in increments of dose to individuals within fifty miles of any station due to liquid and gaseous effluent releases and direct radiation or skyshine. The increments of dose resulting from liquid and gaseous effluent releases will be calculated using the ODCM methodology implemented in the RETDAS computer program. The dose from direct radiation, skyshine, and radiation from the station storage facilities has been estimated using conservative assumptions (see Section 4.0.3).
In certain situations more than one nuclear power station site may contribute to the doses to be considered in making fuel cycle dose assessments in accordance with 40CFR190.
However, since the Oconee nuclear station is located over 100 miles from the Catawba and McGuire nuclear stations, the relative dose contribution from each site to the other is insignificant, and can be ignored in assessing compliance with 40CFR190.
5.0.6 FUEL REPROCESSING No fuel reprocessing operations occur within fifty miles of the Oconee Nuclear Station.
5.0.7 40CFR190 TOTAL DOSE DETERMINATION To summarize, only dose increments from nuclear power production operations (Section 5.0.5) need be considered in calculations to demonstrate compliance with the requirements of 40CFR190. The fuel cycle dose assessments for Oconee Nuclear Station only include liquid and gaseous dose contributions from Oconee since no other uranium fuel cycle facility contributes significantly to Oconee's maximum exposed individual.
For this dose assessment, the total body and maximum organ dose contributions to the maximum exposed individual from Oconee's liquid and gaseous effluents are estimated using the following calculations:
Dwb (T ) = Dwb ( l ) + D wb ( g )
Dmo(T ) = Dmo(l ) + D mo( g )
where:
Dwb (T) = Total estimated fuel cycle whole body dose commitment resulting from the combined liquid and gaseous effluents of Oconee during the calendar year of interest, in mrem.
Dm o(T) = Total estimated fuel cycle maximum organ dose commitment resulting from the combined liquid and gaseous effluents of Oconee during the calendar year of interest, in mrem.
Section 5 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 6.0 ENVIRONMENTAL LOCATIONS 6.0.1 SITE DESCRIPTION AND SAMPLE LOCATIONS Oconee Nuclear Station (ONS) is located in Oconee County, South Carolina, approximately 8 miles northeast of Seneca, South Carolina, on the shore of Lake Keowee. This lake was formed by damming the Keowee and Little Rivers in that location. Immediately to the south is the U.S. Government Hartwell Project. The Keowee Hydroelectric Plant near the station joins Lake Keowee and the upper reaches of Lake Hartwell.
To the north, the Jocassee Hydroelectric Plant joins Lake Jocassee and Lake Keowee. Jocassee is a pumped storage plant. The ONS exclusion area boundary is 1 mile.
Table 6.0-1 and Table 6.0-2 define the sampling and TLD locations for the Oconee Radiological Monitoring Program. Figure 6.0-1 and Figure 6.0-2 illustrate these locations as compared to Oconee Nuclear Station.
Air Sampling at Oconee Nuclear Station 6.0.2 LAND USE CENSUS DATA The Annual Land Use Census, required by Selected Licensee Commitments, is performed to ensure that changes in the use of areas at or beyond the site boundary are identified, and that modifications to the Radiological Environmental Monitoring Program are made if required by changes in land use. This census satisfies the requirements of Section IV.B.3 of Appendix I to 10CFR50. Results are shown in Table 6.0-3 and Figure 6.0-3.
Section 6 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 TABLE 6.0-1 OCONEE RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS Table 6.0-1 Codes W Weekly SM Semimonthly BW BiWeekly Q Quarterly M Monthly SA Semiannually C Control Site Air Rad. & Surface Drinking Shoreline Fish Milk Broadleaf Location Description* Particulate Water Water Sediment Vegetation 060 Greenville Water Intake Road (2.58 mi NNE) W M 060 Greenville Water Intake Road (3.23 NE) M 060 C ** Greenville Water Intake Road (2.28 NE) SA 062 C Lake Keowee Hydro Intake (0.85 mi ENE) M Lake Hartwell Hwy 183 Bridge 063 (0.80 mi ESE) [000.7] SA SA 063.1 Lake Hartwell Hwy 183 (0.79 mi E) M 064 C Seneca (6.67 mi SSW) [004.1] M 066 Anderson (18.9 mi SSE) [012] M Lawrence Ramsey Bridge Hwy 27 067 (4.34 mi SSE) [005.2] SA SA 068 C High Falls County Park (1.82 mi W) SA 071 Clemson Dairy (10.2 mi SSE) [006.3] SM 074 Keowee Key Resort (2.36 mi NNW) W 077 Skimmer Wall (1.00 mi SW) W M 078 Recreation Site (0.58 mi WSW) W 079 Keowee Dam (0.56 mi NE) W M 080 C Martin's Dairy (17.2 mi SE) SM 081 C Clemson Operations Center (9.33 mi SE) W M 082 Oakway Dairy (17.8 mi SSW) SM 083 Oconee Belle Farm Dairy (7.10 mi W) SM
- GPS data reflect approximate accuracy to within 2-5 meters. GPS field measurements were taken as close as possible to the item of interest.
- Control for Fish Only
[ ] Location Numbers prior to 1984 Section 6 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 TABLE 6.0-2 OCONEE RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS (TLD SITES)
Site Location* Distance Sector Site Location* Distance Sector MICROWAVE TOWER, 020 SITE BOUNDARY 0.16 miles N 040 SIX MILE 4.74 miles E 021 SITE BOUNDARY 0.25 miles NNE 041 JCT HWY 101 & 133 4.25 miles ESE LAWRENCE CHAPEL 022 SITE BOUNDARY 0.53 miles NE 042 CHURCH, HWY 133 4.93 miles SE HWY 291 AT 023 SITE BOUNDARY 0.93 miles ENE 043 ISSAQUEENA PARK 4.09 miles SSE HWY 130 AT LITTLE 024 SITE BOUNDARY 0.81 miles E 044 RIVER DAM 3.96 miles S TERMINUS OF HWY 588 025 SITE BOUNDARY 0.42 miles ESE 045 AT CROOKED CREEK 4.78 miles SSW HWY 188 AT 026 SITE BOUNDARY 0.34 miles SE 046 CROOKED CREEKE 4.61 miles SW NEW HOPE CHURCH, 027 SITE BOUNDARY 0.49 miles SSE 047 HWY 188 3.58 miles WSW 028 SITE BOUNDARY 0.46 miles S 048 JCT HWY 175 & 188 3.64 miles W 029 SITE BOUNDARY 0.56 miles SSW 049 JCT HWY 201 & 92 3.60 miles WNW STAMP CREEK LANDING, 030 SITE BOUNDARY 0.42 miles SW 050 END OF HWY 92 3.53 miles NW HWY 128, 1 MILE N OF 031 SITE BOUNDARY 0.27 miles WSW 051 HWY 130 4.64 miles NNW DPC BRANCH OFFICE 076 SITE BOUNDARY 0.19 miles W 052 SITE - PICKENS 12.4 miles ENE DPC BRANCH OFFICE 032 SITE BOUNDARY 0.19 miles WNW 053 SITE - LIBERTY 11.7 miles E POST OFFICE - HWY 93 033 SITE BOUNDARY 0.21 miles WNW 054 NORRIS 8.60 miles ESE CLEMSON 034 SITE BOUNDARY 0.22 miles NW 055 METEOROLOGY PLOT 9.27 miles SSE 035 SITE BOUNDARY 0.17 miles NNW 056 WATER TOWER - SENECA 7.30 miles SSW OCONEE MEMORIAL 036 MILE CREEK LANDING 4.32 miles N 057 HOSPITAL 8.42 miles SW KEOWEE CHURCH, BRANCH RD 037 HWY 327 4.85 miles NNE 058 C SUBSTATION, WALHALLA 9.39 miles WSW CONVENIENCE MART, 038 JCT HWY 183 & 133 4.24 miles NE 059 TAMASSEE DAR SCHOOL 9.20 miles NW HWY 133, 1 MILE EAST CLEMSON 039 OF JCT HWY 183 & 133 4.02 miles ENE 081 OPERATIONS CENTER 9.33 miles SE C = Control
- GPS data reflect approximate accuracy to within 2-5 meters. GPS field measurements were taken as close as possible to the item of interest.
Section 6 - Page 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 TABLE 6.0-3 Oconee 2003 Land Use Census Results*
Land Use Census performed 5/12 - 5/14/2003 Sector Distance Sector Distance (Miles)** (Miles)**
Nearest Residence 2.98 Nearest Residence 1.86 N Nearest Milk Animal - S Nearest Milk Animal -
Nearest Meat Animal - Nearest Meat Animal -
Nearest Residence 2.38 Nearest Residence 1.36 NNE Nearest Milk Animal - SSW Nearest Milk Animal -
Nearest Meat Animal - Nearest Meat Animal -
Nearest Residence 1.20 Nearest Residence 1.39 NE Nearest Milk Animal - SW Nearest Milk Animal -
Nearest Meat Animal (Cow) 3.15 Nearest Meat Animal -
Nearest Residence 1.23 Nearest Residence 1.81 ENE Nearest Milk Animal - WSW Nearest Milk Animal -
Nearest Meat Animal (Cow) 3.53 Nearest Meat Animal -
Nearest Residence 1.14 Nearest Residence 1.76 E Nearest Milk Animal - W Nearest Milk Animal -
Nearest Meat Animal (Cow) 2.51 Nearest Meat Animal (Cow) 3.34 Nearest Residence 1.57 Nearest Residence 1.35 ESE Nearest Milk Animal - WNW Nearest Milk Animal -
Nearest Meat Animal (Cow) 2.60 Nearest Meat Animal -
Nearest Residence 1.46 Nearest Residence 1.00 SE Nearest Milk Animal - NW Nearest Milk Animal -
Nearest Meat Animal - Nearest Meat Animal -
Nearest Residence 1.54 Nearest Residence 1.06 SSE Nearest Milk Animal - NNW Nearest Milk Animal -
Nearest Meat Animal (Cow) 4.57 Nearest Meat Animal -
- indicates no occurrences within the 5 mile radius
- The land use census identifies nearest pathways to the exclusion area boundary (EAB, ~ 1.0 mile) for each of the 16 sectors. Locations beyond the nearest pathway for each sector are assumed to contain that pathway for dose calculation purposes. At Oconee, broad leaf vegetation samples are taken in lieu of a garden census. For dose calculation purposes, since a garden location cannot be ruled out, a garden is assumed to exist at the site boundary and beyond for every sector.
- GPS data reflect approximate accuracy to within 2-5 meters. GPS field measurements were taken as close as possible to the item of interest.
Section 6 - Page 4
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 6.0-1 Sampling Locations Map (Site Boundary)
Section 6 - Page 5
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 6.0-2 Sampling Locations Map (Ten Mile Radius)
Section 6 - Page 6
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Figure 6.0-3 ONS 2003 Land Use Census Map Section 6 - Page 7
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 6.0.3 OCONEE METEOROLOGY: RELATIVE AIR CONCENTRATIONS AND DEPOSITION Calculations of annually averaged air concentrations and deposition values from routine releases provide the air dispersion and deposition factors needed for dose assessment.
The methodology is based upon Regulatory Guide 1.111, as implemented by the NRC's computer model "XOQDOQ: Computer Program for the Meteorological Evaluation of Routine Effluent Releases at Nuclear Power Stations," NUREG/CR-2919, PNL-4380, September 1982.
Five years of hourly meteorological data from the onsite instruments are processed into a representative joint frequency distribution of winds and atmospheric stability for input into the XOQDOQ model (Version 2.0). Thus, the air dispersion and deposition factors
(/Q and D/Q) output by the model are based on a five-year climatology for the site.
6.0.3.1 XOQDOQ METHODOLOGY AND ASSUMPTIONS A continuous, routine release (non-purge) is simulated from each unit vent. The unit vent release type is categorized as semi-elevated, being elevated approximately 92% of the time and being at ground-level approximately 8% of the time. This is based on RG 1.111 criteria, with the ratio (i.e. 3.64) of the average exit velocity (11.39 m/s) to the mean wind speed at the 60 m release height (3.13 m/s). To account for all release pathways, Oconee is modeled as both a totally "ground-level" release and as a "mixed-mode" release, with two model runs of XOQDOQ.
Surrounding terrain heights are not input for ground-level releases, but are used for the elevated portion of mixed-mode releases. The locale consists of rolling terrain, so the default open terrain recirculation factor is applied in XOQDOQ [KOPT(8)=1]. This correction factor is recommended in RG 1.111 to adjust the straight-line airflow of the model for spatial and temporal variations that are produced by large scale weather patterns.
In order for XOQDOQ to treat the plume as a ground-level release, the exit velocity and the inside diameter of the unit vent must be input as zero. The heat emission rate of each vent is also assumed to be zero, as recommended by the model. A release height of 10 m is assumed for the ground-level release, with actual plant grade of 796 ft msl. Using the building height (58 m) and minimum cross-sectional area of the containment building (2296 m2), XOQDOQ applies a building wake correction to the relative air concentrations.
For the mixed-mode release, the exit velocities (11.1, 11.3, and 11.7 m/s for U1-U3, respectively) and inside diameters (1.8 m) of the unit vents are input to the XOQDOQ model for each vent. The heat emission rate of each vent is still assumed to be zero, as in the ground-level release. Plant grade elevation is now input as zero, however, to properly Section 6 - Page 8
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 utilize the input terrain heights above yard grade elevation (Table 6.0-4). The height of the vent (60.7 m) above plant grade is used to determine the plume centerline height.
Table 6.0-4 Terrain Heights Above ONS Yard Grade Elevation (m)
Distance: 0.5 1 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 mile mile miles miles miles miles miles miles miles miles S 29 38 38 38 38 38 50 50 50 50 SSW 32 44 50 50 50 50 50 50 50 50 SW 38 44 44 44 50 50 50 50 50 50 WSW 44 44 44 44 44 44 44 48 48 57 W 48 48 48 48 48 55 58 73 73 73 WNW 29 29 29 38 65 65 71 71 77 80 NW 30 30 30 48 50 68 69 69 71 71 NNW 30 30 30 48 50 68 69 69 71 71 N 29 30 30 30 30 30 62 62 62 74 NNE 24 24 35 35 53 53 82 82 82 82 NE 7 13 35 44 44 50 78 88 99 100 ENE 4 23 35 38 53 62 74 80 99 100 E 1 24 24 24 57 68 68 74 84 84 ESE 1 1 13 35 62 62 62 65 71 71 SE 7 20 20 44 67 67 67 67 67 67 SSE 7 38 38 38 47 62 62 62 62 62 Calculations of relative air concentrations and deposition are made for gridded receptor distances per sector. The model's default values for half-lives are used (i.e. no decay; 2.26 days for short-lived noble gases; and 8 days with depletion factors for all iodines
[DECAYS(I)= 101; 2.26; -8.0] ).
6.0.3.2 METEOROLOGICAL DATA Five years (1988-1992) of hourly, onsite meteorological data are used to produce the joint frequency distributions of wind speed and direction per stability class. The 10 m level winds are used. It is these joint frequency distributions which are input to the XOQDOQ model. XOQDOQ extrapolates the 10 m wind speed to the release height during the elevated portion of mixed-mode releases. Hours of calm winds are distributed by direction with the same frequency as the lowest "noncalm" wind speed class
[KOPT(1)=1]. Thus, wind speed classes are established so that the lowest wind speed class is the starting threshold of the anemometer (i.e. the "calm" wind speed class). The largest wind speed class has the upper bound of (5 m/s + max hourly wind speed).
Stability classes (A-G) are based on the vertical temperature gradient, measured by the hourly averaged delta-T variable.
Section 6 - Page 9
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 6.0.3.3 ANNUAL XOQDOQ COMPARISON TO THE ODCM Each year, the prevailing winds and stability class frequencies for ONS are compared to the 5-year period (1988-1992) upon which the /Q and D/Q calculations have been made.
The 5-year climatology is summarized in Table 6.0-5 and Table 6.0-6 below. Since the comparison is being made to a 5-year climatology, significant differences should not occur in the meteorological variables of concern (i.e. winds and delta-T). The meteorological comparison serves to verify this assumption.
Table 6.0-5 ONS Atmospheric Stability Frequency (1988-1992)
A B C D E F G Frequency
(%) 8.9 5.4 6.1 39.5 33.1 5.6 1.5 Table 6.0-6 ONS Frequency of Wind Direction and Speed (1988-1992)
Wind Direction Wind Speed Class Wind Speed Sector Frequency (%) (m/s) Frequency (%)
N 5.1 CALM 1.0 NNE 5.2 0.45 - 0.74 m/s 4.7 NE 9 0.75 - 0.99 m/s 9.4 ENE 8.3 1.00 - 1.24 m/s 10.0 E 5.2 1.25 - 1.49 m/s 12.3 ESE 3.1 1.50 - 1.99 m/s 16.8 SE 3 2.00 - 2.99 m/s 20.4 SSE 3.5 3.00 - 3.99 m/s 9.6 S 3.6 4.00 - 4.99 m/s 4.5 SSW 8.5 5.00 - 5.99 m/s 1.8 SW 11.7 6.00 - 7.99 m/s 1.3 WSW 7.4 8.00 - 9.99 m/s 0.3 W 5.1 > 9.99 m/s 8.9 WNW 6.9 NW 7.2 NNW 6.3 The joint frequency distributions of wind speed and direction versus atmospheric stability class are also determined from the annual data to provide input to the XOQDOQ model.
Modeled /Q and D/Q values for the 1.0 mile Exclusion Area Boundary at ONS are Section 6 - Page 10
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 compared to the maximum of the (1988-1992) /Q and D/Q values from all sectors. If the newly calculated annual dispersion and deposition values do not result in a significant increase in the calculated offsite dose relative to the 10CFR50, Appendix I dose objectives then the 5-year /Q and D/Q values used in the Annual Radiological Effluent Release Report (ARERR) are not revised. An increase in calculated offsite dose that is greater than five percent of the 10CFR50, Appendix I dose objectives would be considered significant enough to warrant a change in the /Q and D/Q values used in the ARERR. If an increasing trend in the annual /Q and D/Q values compared to the 5-year values is noted then a revised set of 5-year /Q and D/Q values will be generated. These limiting values are listed in Table 6.0-7. The entire /Q and D/Q list based on directional sector and distance is given in Table 6.0-9 and Table 6.0-10.
Table 6.0-7 ONS Limiting /Q and D/Q Values (1988-1992)
(/Q,s/m3) Distance Sector (D/Q,1/m2)
Ground-level Release: Maximum /Q 7.308E-06 1 mile EAB SE Ground-level Release: Maximum D/Q 2.259E-8 1 mile EAB NE Mixed-mode Release: Maximum /Q 1.67E-06 1 mile EAB SW Mixed-mode Release: Maximum D/Q 1.295E-08 1 mile EAB NE Note:
The Oconee meteorological instruments were relocated from the 46 m microwave tower to a new 60 m onsite meteorological tower in April 1988. The 60 m tower became operational at 1700 hours0.0197 days <br />0.472 hours <br />0.00281 weeks <br />6.4685e-4 months <br /> on April 23, 1988. Therefore, determination of atmospheric stability should use the 36 m separation criteria for the period February 24, 1977-April 22, 1988 shown in Table 6.0-8. Data starting on April 23, 1988 or later should use the 50 m separation criteria.
Table 6.0-8 ONS Delta-T Ranges per Vertical Separation Distances Stability 36m separation Delta-T 50m separation Delta-T Class (between 46m-10m levels) (between 60m-10m levels)
FEB 24, 1977 - APRIL 18, 1988 Starting at hour 1700 on (4/18/88 ending hour 1430) April 23, 1988.
A dT < -0.68 dT < -0.95 B -0.68 < dT < -0.61 -0.95 < dT < -0.85 C -0.61 < dT < -0.54 -0.85 < dT < -0.75 D -0.54 < dT < -0.18 -0.75 < dT < -0.25 E -0.18 < dT < 0.54 -0.25 < dT < 0.75 F 0.54 < dT < 1.44 0.75 < dT < 2.00 G 1.44 < Dt 2.00 < dT Section 6 - Page 11
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Table 6.0-9 (page 1 of 2)
Oconee Semi-Elevated /Q Average Values (1988-1992)
(sec/m3)
Sector 1.0-1.5* 1.5-2.0 2.0-2.5 2.5-3.0 3.0-3.5 3.5-4.0 4.0-4.5 4.5-5.0 N 5.220E-07 2.650E-07 1.594E-07 1.069E-07 7.719E-08 7.321E-08 5.665E-08 4.542E-08 NNE 8.379E-07 4.734E-07 2.690E-07 2.003E-07 1.385E-07 1.091E-07 8.379E-08 6.676E-08 NE 9.503E-07 6.350E-07 3.962E-07 2.535E-07 1.847E-07 1.497E-07 1.157E-07 9.246E-08 ENE 8.116E-07 4.856E-07 2.919E-07 2.196E-07 1.619E-07 1.239E-07 9.609E-08 7.720E-08 E 5.950E-07 3.202E-07 2.015E-07 2.270E-07 1.745E-07 1.292E-07 1.024E-07 8.308E-08 ESE 4.531E-07 3.300E-07 3.623E-07 4.020E-07 2.822E-07 2.109E-07 1.688E-07 1.405E-07 SE 7.505E-07 4.573E-07 5.490E-07 5.110E-07 3.560E-07 2.648E-07 2.063E-07 1.665E-07 SSE 1.419E-06 7.428E-07 4.527E-07 3.489E-07 2.866E-07 2.131E-07 1.659E-07 1.337E-07 S 1.170E-06 6.099E-07 3.701E-07 2.496E-07 1.810E-07 1.552E-07 1.218E-07 9.867E-08 SSW 1.214E-06 6.327E-07 3.564E-07 2.301E-07 1.621E-07 1.213E-07 9.481E-08 7.660E-08 SW 1.672E-06 7.285E-07 4.057E-07 2.720E-07 1.891E-07 1.400E-07 1.085E-07 8.708E-08 WSW 1.558E-06 6.820E-07 3.804E-07 2.438E-07 1.708E-07 1.271E-07 1.010E-07 8.114E-08 W 1.193E-06 5.214E-07 2.909E-07 1.867E-07 1.372E-07 1.032E-07 8.326E-08 6.654E-08 WNW 4.658E-07 2.480E-07 1.760E-07 1.482E-07 1.024E-07 7.695E-08 5.943E-08 4.796E-08 NW 4.831E-07 2.524E-07 1.965E-07 1.291E-07 9.959E-08 7.356E-08 5.682E-08 4.566E-08 NNW 5.375E-07 2.769E-07 2.128E-07 1.394E-07 1.072E-07 7.913E-08 6.110E-08 4.907E-08
- Units are in miles from the station. As discussed in Oconee UFSAR Section 2.1.1.3, the boundary for establishing gaseous effluent release limits is the exclusion area boundary (EAB). The EAB is at a radius of 1.0 mile from the station center. Each /Q value is calculated at the closest location for the sector, e.g., 1.672E-06 sec/m3 is the /Q value at 1.0 mile (SW) from the station.
Section 6 - Page 12
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Table 6.0-9 (page 2 of 2)
Oconee Semi-Elevated D/Q Average Values (1988-1992)
(m-2)
Sector 1.0-1.5* 1.5-2.0 2.0-2.5 2.5-3.0 3.0-3.5 3.5-4.0 4.0-4.5 4.5-5.0 N 2.890E-09 1.184E-09 6.225E-10 3.812E-10 2.586E-10 3.380E-10 2.510E-10 1.943E-10 NNE 9.113E-09 3.989E-09 2.013E-09 1.248E-09 8.235E-10 8.997E-10 6.667E-10 5.138E-10 NE 1.295E-08 5.666E-09 2.919E-09 1.729E-09 1.145E-09 1.224E-09 9.140E-10 7.067E-10 ENE 7.899E-09 3.385E-09 1.756E-09 1.095E-09 9.819E-10 7.671E-10 5.749E-10 4.466E-10 E 4.454E-09 1.775E-09 9.252E-10 7.164E-10 7.491E-10 5.267E-10 3.981E-10 3.125E-10 ESE 4.361E-09 1.838E-09 1.086E-09 1.322E-09 8.696E-10 6.161E-10 5.153E-10 4.139E-10 SE 3.397E-09 1.385E-09 8.341E-10 1.649E-09 1.080E-09 7.595E-10 5.629E-10 4.340E-10 SSE 3.333E-09 1.323E-09 6.920E-10 4.404E-10 7.307E-10 5.202E-10 3.922E-10 3.091E-10 S 3.192E-09 1.256E-09 6.530E-10 4.020E-10 2.788E-10 2.177E-10 1.759E-10 1.501E-10 SSW 5.190E-09 1.972E-09 9.899E-10 5.895E-10 3.928E-10 2.842E-10 2.192E-10 1.778E-10 SW 1.205E-08 4.399E-09 2.193E-09 1.299E-09 8.521E-10 6.028E-10 4.518E-10 3.546E-10 WSW 1.047E-08 3.824E-09 1.908E-09 1.127E-09 7.422E-10 5.277E-10 3.980E-10 3.145E-10 W 5.577E-09 2.044E-09 1.025E-09 6.094E-10 4.134E-10 3.405E-10 3.962E-10 3.052E-10 WNW 2.185E-09 9.042E-10 5.220E-10 6.464E-10 4.227E-10 3.188E-10 2.360E-10 1.868E-10 NW 2.097E-09 8.759E-10 5.225E-10 3.196E-10 4.521E-10 3.178E-10 2.353E-10 1.812E-10 NNW 2.461E-09 1.028E-09 6.219E-10 3.765E-10 5.128E-10 3.604E-10 2.667E-10 2.054E-10
- Units are in miles from the station. As discussed in Oconee UFSAR Section 2.1.1.3, the boundary for establishing gaseous effluent release limits is the exclusion area boundary (EAB). The EAB is defined as a 1 mile radius from the station center. Each D/Q value is calculated at the closest location for the sector, e.g., 1.205E-08 m-2 is the D/Q value at 1.0 mile (SW) from the station.
Section 6 - Page 13
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Table 6.0-10 (page 1 of 2)
Oconee Ground Level /Q Average Values (1988-1992)
(sec/m3)
Sector 1.0-1.5* 1.5-2.0 2.0-2.5 2.5-3.0 3.0-3.5 3.5-4.0 4.0-4.5 4.5-5.0 N 2.115E-06 8.389E-07 4.495E-07 2.822E-07 1.952E-07 1.443E-07 1.117E-07 8.961E-08 NNE 2.898E-06 1.137E-06 6.047E-07 3.775E-07 2.602E-07 1.916E-07 1.480E-07 1.184E-07 NE 3.886E-06 1.529E-06 8.158E-07 5.108E-07 3.529E-07 2.604E-07 2.015E-07 1.616E-07 ENE 3.226E-06 1.277E-06 6.848E-07 4.305E-07 2.983E-07 2.207E-07 1.711E-07 1.374E-07 E 3.522E-06 1.410E-06 7.658E-07 4.866E-07 3.400E-07 2.534E-07 1.977E-07 1.596E-07 ESE 5.964E-06 2.407E-06 1.321E-06 8.459E-07 5.950E-07 4.457E-07 3.493E-07 2.832E-07 SE 7.308E-06 2.972E-06 1.631E-06 1.044E-06 7.342E-07 5.497E-07 4.307E-07 3.490E-07 SSE 6.604E-06 2.657E-06 1.440E-06 9.117E-07 6.354E-07 4.723E-07 3.676E-07 2.962E-07 S 5.278E-06 2.121E-06 1.146E-06 7.237E-07 5.032E-07 3.734E-07 2.901E-07 2.335E-07 SSW 3.986E-06 1.589E-06 8.536E-07 5.370E-07 3.721E-07 2.753E-07 2.135E-07 1.714E-07 SW 4.108E-06 1.620E-06 8.628E-07 5.390E-07 3.715E-07 2.735E-07 2.112E-07 1.689E-07 WSW 3.804E-06 1.503E-06 8.018E-07 5.015E-07 3.460E-07 2.549E-07 1.970E-07 1.577E-07 W 2.978E-06 1.186E-06 6.361E-07 3.995E-07 2.765E-07 2.043E-07 1.583E-07 1.270E-07 WNW 2.201E-06 8.791E-07 4.726E-07 2.974E-07 2.062E-07 1.526E-07 1.183E-07 9.502E-08 NW 2.104E-06 8.385E-07 4.499E-07 2.826E-07 1.957E-07 1.447E-07 1.121E-07 8.991E-08 NNW 2.221E-06 8.860E-07 4.755E-07 2.988E-07 2.069E-07 1.529E-07 1.185E-07 9.508E-08
- Units are in miles from the station. As discussed in Oconee UFSAR Section 2.1.1.3, the boundary for establishing gaseous effluent release limits is the exclusion area boundary (EAB). The EAB is defined as a 1 mile radius from the station center. Each /Q value is calculated at the closest location for the sector, e.g., 4.108E-06 sec/m3 is the /Q value at 1.0 mile (SW) from the station.
Section 6 - Page 14
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Table 6.0-10 (page 2 of 2)
Oconee Ground Level D/Q Average Values (1988-1992)
(m-2)
Sector 1.0-1.5* 1.5-2.0 2.0-2.5 2.5-3.0 3.0-3.5 3.5-4.0 4.0-4.5 4.5-5.0 N 6.916E-09 2.484E-09 1.232E-09 7.255E-10 4.750E-10 3.342E-10 2.477E-10 1.909E-10 NNE 1.642E-08 5.897E-09 2.924E-09 1.722E-09 1.128E-09 7.934E-10 5.880E-10 4.531E-10 NE 2.259E-08 8.114E-09 4.024E-09 2.369E-09 1.551E-09 1.092E-09 8.090E-10 6.235E-10 ENE 1.428E-08 5.130E-09 2.544E-09 1.498E-09 9.810E-10 6.902E-10 5.115E-10 3.942E-10 E 9.899E-09 3.556E-09 1.763E-09 1.038E-09 6.798E-10 4.784E-10 3.545E-10 2.732E-10 ESE 1.336E-08 4.798E-09 2.379E-09 1.401E-09 9.174E-10 6.455E-10 4.784E-10 3.686E-10 SE 1.401E-08 5.034E-09 2.496E-09 1.470E-09 9.625E-10 6.772E-10 5.019E-10 3.868E-10 SSE 1.226E-08 4.404E-09 2.184E-09 1.286E-09 8.420E-10 5.925E-10 4.391E-10 3.384E-10 S 1.008E-08 3.620E-09 1.795E-09 1.057E-09 6.922E-10 4.871E-10 3.610E-10 2.782E-10 SSW 9.941E-09 3.571E-09 1.771E-09 1.043E-09 6.828E-10 4.804E-10 3.560E-10 2.744E-10 SW 1.717E-08 6.169E-09 3.059E-09 1.801E-09 1.180E-09 8.300E-10 6.151E-10 4.740E-10 WSW 1.574E-08 5.655E-09 2.804E-09 1.651E-09 1.081E-09 7.608E-10 5.638E-10 4.345E-10 W 9.988E-09 3.588E-09 1.779E-09 1.048E-09 6.860E-10 4.827E-10 3.577E-10 2.757E-10 WNW 5.953E-09 2.138E-09 1.060E-09 6.244E-10 4.088E-10 2.877E-10 2.132E-10 1.643E-10 NW 5.891E-09 2.116E-09 1.049E-09 6.179E-10 4.046E-10 2.847E-10 2.110E-10 1.626E-10 NNW 6.672E-09 2.397E-09 1.188E-09 6.998E-10 4.582E-10 3.224E-10 2.390E-10 1.841E-10
- Units are in miles from the station. As discussed in Oconee UFSAR Section 2.1.1.3, the boundary for establishing gaseous effluent release limits is the exclusion area boundary (EAB). The EAB is defined as a 1 mile radius from the station center. Each D/Q value is calculated at the closest location for the sector, e.g., 1.717E-08 m-2 is the D/Q value at 1.0 mile (SW) from the station.
Section 6 - Page 15
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 7.0 LICENSEE INITIATED CHANGES Note: Several changes made to the ODCM are due to the addition of a gaseous effluent release point. The Reactor Coolant Pump Refurbishment Facility (RCP Refurbishment Facility) is a building onsite in which equipment was stored and in which very limited, non-invasive radiological work was performed. As part of the Oconee Steam Generator and Reactor Vessel Head replacement project, the RCP Refurbishment Facility was modified to accommodate radiological work on tall components. Part of the building modification included the installation of a ventilation system equipped with a radiological particulate and iodine sampler. No detector is associated with this sampling system.
Effluent samples are changed out periodically, and the total volume released from the facility over the sampling period is recorded. Total radiological effluent released (if any) is then calculated on a monthly basis and is entered into the Station's effluent accounting and dose calculation computer code, RETDAS.
All changes made to the Oconee ODCM are reviewed by knowledgeable individual(s),
and approved by the Station Manager and the General Office Radiation Protection Manager prior to implementation. The following changes do not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations.
Section 1 - Page 7 The RCP Refurbishment Facility including the general system layout was added to Figure 1.0-2, Page 4 of 4.
On the Interim Radwaste Facility diagram in Figure 1.0-2, Page 4 of 4, the Particulate and Iodine Sampler was moved to come before RIA-53. This revision more closely reflects the actual installation.
Section 2 - Pages 1 and 2 Note: There are two planned Keowee Hydro outages in 2004. One will remove a unit in January for 45 days, and the other will remove a unit in August for 45 days. The outages require the affected unit to be dewatered, thus temporarily reducing the amount of leakage by half during the outages. (Reference PIP O-03-06119 for further details). The following related changes shown in red were made to the dilution flow variable, F:
F = the dilution flow available, in gpm.
= normally 3.41E+04 gpm (76 cfs, based on a leakage rate of 38 cfs (19 cfs per Keowee Hydro unit), plus the Keowee Hydro Fire Protection liquid waste release mixing line whose flow rate is 38 cfs. When Keowee Hydro enters an outage one of the two units is taken offline which temporarily reduces the amount of leakage by half. Therefore, during a Keowee Hydro outage the dilution flow is assumed to be 57 cfs (19 cfs leakage plus 38 cfs raw water, (2.56E+04 gpm)).
Section 7 - Page 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Section 2 - Page 5 Section 2.0.2, the statement three other separate gaseous effluent release points was changed to four other separate gaseous effluent release points. The and prior to Radwaste Facility was deleted and the statement and RCP Refurbishment Facility was added after Radwaste Facility.
Section 2 - Page 6 In the paragraph defining /Q, the and prior to Radwaste Facility, was deleted, and the following was added , and RCP Refurbishment Facility after Radwaste Facility.
Section 3 - Page 6 In the first paragraph on the page, the statement three ground-level release points was changed to four ground-level release points. Deleted the and prior to Radwaste Facility and added , and RCP Refurbishment Facility (no monitor) after (4RIA-45 and 4RIA-46).
Section 6 - Page 2 Location distances changed to reflect three significant figures following measurement of all locations during 2003.
Location 060 (Drinking Water) was added to Table 6.0-1. GPS measurement made for drinking water site.
Location 060 (Fish) was added to Table 6.0-1. GPS measurement made for fish collection site.
Footnote added below Table 6.0-1 describing approximation of GPS measurements.
Section 6 - Page 3 Location distances changed to reflect three significant figures following measurement of all locations during 2003.
Table 6.0-2 layout modified, mileage and sector attributes split from one column to two columns.
Font changed for Table 6.0-2 footnote codes.
Footnote added below Table 6.0-2 describing approximation of GPS measurements.
Section 6 - Page 4 Changed title of Table 6.0-3 to: "Oconee 2003 Land Use Census Results".
Land use census dates were changed to reflect 2003 census dates.
All table attributes were changed due to the updated 2003 land use census.
Section 7 - Page 2
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 Font changed for Table 6.0-3 footnote.
Footnote added below Table 6.0-3 describing approximation of GPS measurements.
Section 6 - Page 5 Figure 6.0-1 regenerated to depict 2003 GPS measurements. Page rotated from portrait presentation to landscape presentation for increased detail display.
Section 6 - Page 6 Figure 6.0-2 regenerated to depict 2003 GPS measurements. Page rotated from portrait presentation to landscape presentation for increased detail display.
Section 6 - Page 7 Figure 6.0-3 regenerated to depict 2003 GPS measurements. Page rotated from portrait presentation to landscape presentation for increased detail display.
Section 6 - Page 11 Revised the criterion for when to change the 5-year /Q and D/Q values to the newly calculated annual /Q and D/Q values for use in the Annual Radiological Effluent Release Report (ARERR). The previous criterion required using the annual /Q and D/Q values if either an annual /Q or annual D/Q exceeded the corresponding 5-year /Q or D/Q value by 20%. However this criterion can result in a lower calculated dose compared to using the 5-year values. For example, an annual D/Q could exceed the 5-year D/Q by more than 20%, but the annual /Q could be less than the 5-year /Q value.
Since Oconee's gas maximum organ dose is almost completely from H-3, which is calculated using the /Q rather than D/Q, Oconee's ARERR gas maximum organ dose would be less in this example using the annual values rather than the 5-year values even though the annual D/Q value is greater than 20% of the 5-year D/Q value. The revised criterion will not result in non-conservative dose calculations for the ARERR.
Section 7 - Page 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX A Dose Factors for Exposure to a Semi-Infinite Cloud of Noble Gases
- Ki Li Mi Ni Total Body Skin Gamma Air Beta Air Nuclide mrem/yr/ mrem/yr/ mrad/yr/ mrad/yr/
µCi/m3 µCi/m3 µCi/m3 µCi/m3 AR-41 8.840E+03 2.690E+03 9.300E+03 3.280E+03 KR-83M 7.560E-02 0.000E+00 1.930E+01 2.880E+02 KR-85M 1.170E+03 1.460E+03 1.230E+03 1.970E+03 KR-85 1.610E+01 1.340E+03 1.720E+01 1.950E+03 KR-87 5.920E+03 9.730E+03 6.170E+03 1.030E+04 KR-88 1.470E+04 2.370E+03 1.520E+04 2.930E+03 KR-89 1.660E+04 1.010E+04 1.730E+04 1.060E+04 KR-90 1.560E+04 7.290E+03 1.630E+04 7.830E+03 XE-131M 9.150E+01 4.760E+02 1.560E+02 1.110E+03 XE-133M 2.510E+02 9.940E+02 3.270E+02 1.480E+03 XE-133 2.940E+02 3.060E+02 3.530E+02 1.050E+03 XE-135M 3.120E+03 7.110E+02 3.360E+03 7.390E+02 XE-135 1.810E+03 1.860E+03 1.920E+03 2.460E+03 XE-137 1.420E+03 1.220E+04 1.510E+03 1.270E+04 XE-138 8.830E+03 4.130E+03 9.210E+03 4.750E+03
- Reference Regulatory Guide 1.109, Table B-1 Appendix A Dose Factors for Exposure to a Semi-Infinite Cloud of Noble Gases - Page 1 of 1
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.380E+03 2.380E+03 2.380E+03 2.380E+03 2.380E+03 0.000E+00 2.380E+03 C-14 2.340E+09 5.000E+08 5.000E+08 5.000E+08 5.000E+08 5.000E+08 0.000E+00 5.000E+08 NA-24 1.540E+07 1.540E+07 1.540E+07 1.540E+07 1.540E+07 1.540E+07 0.000E+00 1.540E+07 P-32 1.600E+11 9.430E+09 0.000E+00 0.000E+00 0.000E+00 2.170E+09 0.000E+00 6.210E+09 CR-51 0.000E+00 0.000E+00 1.050E+05 2.300E+04 2.050E+05 4.700E+06 0.000E+00 1.610E+05 MN-54 0.000E+00 3.900E+07 0.000E+00 8.640E+06 0.000E+00 1.430E+07 0.000E+00 8.840E+06 MN-56 0.000E+00 3.100E-02 0.000E+00 2.660E-02 0.000E+00 2.810E+00 0.000E+00 5.340E-03 FE-55 1.350E+08 8.730E+07 0.000E+00 0.000E+00 4.270E+07 1.110E+07 0.000E+00 2.330E+07 FE-59 2.240E+08 3.920E+08 0.000E+00 0.000E+00 1.160E+08 1.870E+08 0.000E+00 1.540E+08 CO-58 0.000E+00 2.420E+07 0.000E+00 0.000E+00 0.000E+00 6.040E+07 0.000E+00 6.050E+07 CO-60 0.000E+00 8.820E+07 0.000E+00 0.000E+00 0.000E+00 2.100E+08 0.000E+00 2.080E+08 NI-63 3.490E+10 2.160E+09 0.000E+00 0.000E+00 0.000E+00 1.070E+08 0.000E+00 1.210E+09 NI-65 3.510E+00 3.970E-01 0.000E+00 0.000E+00 0.000E+00 3.020E+01 0.000E+00 1.800E-01 CU-64 0.000E+00 1.850E+05 0.000E+00 3.140E+05 0.000E+00 3.810E+06 0.000E+00 8.590E+04 ZN-65 5.550E+09 1.900E+10 0.000E+00 9.230E+09 0.000E+00 1.610E+10 0.000E+00 8.780E+09 ZN-69 2.020E-11 3.630E-11 0.000E+00 1.510E-11 0.000E+00 2.960E-09 0.000E+00 2.700E-12 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.340E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.260E-22 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.230E+10 0.000E+00 0.000E+00 0.000E+00 5.690E+08 0.000E+00 1.100E+10 RB-88 0.000E+00 1.880E-44 0.000E+00 0.000E+00 0.000E+00 1.830E-44 0.000E+00 1.030E-44 RB-89 0.000E+00 3.290E-52 0.000E+00 0.000E+00 0.000E+00 1.120E-52 0.000E+00 2.260E-52 SR-89 1.260E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.590E+08 0.000E+00 3.610E+08 SR-90 1.220E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.520E+09 0.000E+00 3.100E+10 SR-91 2.720E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.220E+05 0.000E+00 9.830E+03 Appendix B Pi Infant Cow Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 4.640E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.000E+01 0.000E+00 1.720E-01 Y-90 6.810E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.410E+05 0.000E+00 1.830E+01 Y-91 7.330E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.250E+06 0.000E+00 1.950E+03 Y-91M 5.670E-19 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.890E-15 0.000E+00 1.930E-20 Y-92 5.380E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.030E+01 0.000E+00 1.510E-05 Y-93 2.160E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.700E+04 0.000E+00 5.870E-02 ZR-95 6.800E+03 1.660E+03 0.000E+00 1.790E+03 0.000E+00 8.260E+05 0.000E+00 1.180E+03 ZR-97 4.060E+00 6.970E-01 0.000E+00 7.030E-01 0.000E+00 4.450E+04 0.000E+00 3.180E-01 NB-95 5.930E+05 2.440E+05 0.000E+00 1.750E+05 0.000E+00 2.060E+08 0.000E+00 1.410E+05 MO-99 0.000E+00 2.080E+08 0.000E+00 3.110E+08 0.000E+00 6.850E+07 0.000E+00 4.060E+07 TC-99M 2.750E+01 5.670E+01 0.000E+00 6.100E+02 2.960E+01 1.650E+04 0.000E+00 7.300E+02 TC-101 2.470E-59 3.110E-59 0.000E+00 3.700E-58 1.700E-59 5.280E-57 0.000E+00 3.080E-58 RU-103 8.670E+03 0.000E+00 0.000E+00 1.800E+04 0.000E+00 1.050E+05 0.000E+00 2.900E+03 RU-105 8.050E-03 0.000E+00 0.000E+00 5.920E-02 0.000E+00 3.200E+00 0.000E+00 2.710E-03 RU-106 1.900E+05 0.000E+00 0.000E+00 2.250E+05 0.000E+00 1.440E+06 0.000E+00 2.380E+04 AG-110M 3.860E+08 2.820E+08 0.000E+00 4.030E+08 0.000E+00 1.460E+10 0.000E+00 1.860E+08 TE-125M 1.510E+08 5.040E+07 5.070E+07 0.000E+00 0.000E+00 7.180E+07 0.000E+00 2.040E+07 TE-127 6.320E+03 2.120E+03 5.140E+03 1.540E+04 0.000E+00 1.330E+05 0.000E+00 1.360E+03 TE-127M 4.210E+08 1.400E+08 1.220E+08 1.040E+09 0.000E+00 1.700E+08 0.000E+00 5.100E+07 TE-129 2.720E-09 9.380E-10 2.280E-09 6.770E-09 0.000E+00 2.170E-07 0.000E+00 6.350E-10 TE-129M 5.570E+08 1.910E+08 2.140E+08 1.390E+09 0.000E+00 3.330E+08 0.000E+00 8.580E+07 TE-131 3.430E-32 1.270E-32 3.060E-32 8.760E-32 0.000E+00 1.380E-30 0.000E+00 9.610E-33 TE-131M 3.380E+06 1.360E+06 2.750E+06 9.350E+06 0.000E+00 2.290E+07 0.000E+00 1.120E+06 TE-132 2.110E+07 1.040E+07 1.540E+07 6.530E+07 0.000E+00 3.870E+07 0.000E+00 9.750E+06 I-130 3.550E+06 7.810E+06 8.750E+08 8.580E+06 0.000E+00 1.670E+06 0.000E+00 3.130E+06 Appendix B Pi Infant Cow Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 2.720E+09 3.200E+09 1.050E+12 3.740E+09 0.000E+00 1.140E+08 0.000E+00 1.410E+09 I-132 1.430E+00 2.900E+00 1.360E+02 3.240E+00 0.000E+00 2.350E+00 0.000E+00 1.030E+00 I-133 3.630E+07 5.280E+07 9.600E+09 6.210E+07 0.000E+00 8.930E+06 0.000E+00 1.550E+07 I-134 1.760E-11 3.600E-11 8.400E-10 4.030E-11 0.000E+00 3.720E-11 0.000E+00 1.280E-11 I-135 1.120E+05 2.230E+05 2.000E+07 2.490E+05 0.000E+00 8.080E+04 0.000E+00 8.140E+04 CS-134 3.650E+10 6.800E+10 0.000E+00 1.750E+10 7.180E+09 1.850E+08 0.000E+00 6.870E+09 CS-136 1.980E+09 5.810E+09 0.000E+00 2.320E+09 4.740E+08 8.820E+07 0.000E+00 2.170E+09 CS-137 5.150E+10 6.020E+10 0.000E+00 1.620E+10 6.550E+09 1.880E+08 0.000E+00 4.270E+09 CS-138 8.390E-23 1.360E-22 0.000E+00 6.800E-23 1.060E-23 2.180E-22 0.000E+00 6.610E-23 BA-139 4.270E-07 2.830E-10 0.000E+00 1.700E-10 1.720E-10 2.710E-05 0.000E+00 1.240E-08 BA-140 2.410E+08 2.410E+05 0.000E+00 5.720E+04 1.480E+05 5.920E+07 0.000E+00 1.240E+07 BA-141 3.930E-45 2.690E-48 0.000E+00 1.620E-48 1.640E-48 4.800E-44 0.000E+00 1.240E-46 BA-142 2.430E-79 2.020E-82 0.000E+00 1.160E-82 1.220E-82 1.000E-78 0.000E+00 1.200E-80 LA-140 4.050E+01 1.600E+01 0.000E+00 0.000E+00 0.000E+00 1.880E+05 0.000E+00 4.110E+00 LA-142 1.700E-10 6.250E-11 0.000E+00 0.000E+00 0.000E+00 1.060E-05 0.000E+00 1.500E-11 CE-141 4.340E+04 2.640E+04 0.000E+00 8.150E+03 0.000E+00 1.370E+07 0.000E+00 3.110E+03 CE-143 3.970E+02 2.630E+05 0.000E+00 7.670E+01 0.000E+00 1.540E+06 0.000E+00 3.000E+01 CE-144 2.330E+06 9.520E+05 0.000E+00 3.850E+05 0.000E+00 1.330E+08 0.000E+00 1.300E+05 PR-143 1.490E+03 5.550E+02 0.000E+00 2.060E+02 0.000E+00 7.840E+05 0.000E+00 7.360E+01 PR-144 5.690E-53 2.200E-53 0.000E+00 7.980E-54 0.000E+00 1.020E-48 0.000E+00 2.870E-54 ND-147 8.810E+02 9.050E+02 0.000E+00 3.490E+02 0.000E+00 5.740E+05 0.000E+00 5.550E+01 W-187 6.080E+04 4.230E+04 0.000E+00 0.000E+00 0.000E+00 2.480E+06 0.000E+00 1.460E+04 NP-239 3.650E+01 3.260E+00 0.000E+00 6.510E+00 0.000E+00 9.430E+04 0.000E+00 1.840E+00 Appendix B Pi Infant Cow Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 4.860E+03 4.860E+03 4.860E+03 4.860E+03 4.860E+03 0.000E+00 4.860E+03 C-14 2.340E+09 5.000E+08 5.000E+08 5.000E+08 5.000E+08 5.000E+08 0.000E+00 5.000E+08 NA-24 1.850E+06 1.850E+06 1.850E+06 1.850E+06 1.850E+06 1.850E+06 0.000E+00 1.850E+06 P-32 1.920E+11 1.130E+10 0.000E+00 0.000E+00 0.000E+00 2.600E+09 0.000E+00 7.460E+09 CR-51 0.000E+00 0.000E+00 1.260E+04 2.760E+03 2.460E+04 5.640E+05 0.000E+00 1.940E+04 MN-54 0.000E+00 4.680E+06 0.000E+00 1.040E+06 0.000E+00 1.720E+06 0.000E+00 1.060E+06 MN-56 0.000E+00 3.720E-03 0.000E+00 3.190E-03 0.000E+00 3.380E-01 0.000E+00 6.410E-04 FE-55 1.760E+06 1.130E+06 0.000E+00 0.000E+00 5.550E+05 1.440E+05 0.000E+00 3.030E+05 FE-59 2.920E+06 5.100E+06 0.000E+00 0.000E+00 1.510E+06 2.430E+06 0.000E+00 2.010E+06 CO-58 0.000E+00 2.910E+06 0.000E+00 0.000E+00 0.000E+00 7.250E+06 0.000E+00 7.260E+06 CO-60 0.000E+00 1.060E+07 0.000E+00 0.000E+00 0.000E+00 2.520E+07 0.000E+00 2.500E+07 NI-63 4.190E+09 2.590E+08 0.000E+00 0.000E+00 0.000E+00 1.290E+07 0.000E+00 1.450E+08 NI-65 4.210E-01 4.760E-02 0.000E+00 0.000E+00 0.000E+00 3.620E+00 0.000E+00 2.170E-02 CU-64 0.000E+00 2.070E+04 0.000E+00 3.500E+04 0.000E+00 4.240E+05 0.000E+00 9.570E+03 ZN-65 6.660E+08 2.280E+09 0.000E+00 1.110E+09 0.000E+00 1.930E+09 0.000E+00 1.050E+09 ZN-69 2.420E-12 4.360E-12 0.000E+00 1.810E-12 0.000E+00 3.550E-10 0.000E+00 3.240E-13 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.120E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.510E-23 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.670E+09 0.000E+00 0.000E+00 0.000E+00 6.830E+07 0.000E+00 1.320E+09 RB-88 0.000E+00 2.250E-45 0.000E+00 0.000E+00 0.000E+00 2.190E-45 0.000E+00 1.230E-45 RB-89 0.000E+00 3.940E-53 0.000E+00 0.000E+00 0.000E+00 1.340E-53 0.000E+00 2.720E-53 SR-89 2.640E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.430E+08 0.000E+00 7.580E+08 SR-90 2.550E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.190E+09 0.000E+00 6.500E+10 SR-91 5.700E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.750E+05 0.000E+00 2.060E+04 Appendix B Pi Infant Goat Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 9.750E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.050E+02 0.000E+00 3.620E-01 Y-90 8.170E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.130E+05 0.000E+00 2.190E+00 Y-91 8.790E+03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.300E+05 0.000E+00 2.340E+02 Y-91M 6.810E-20 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.270E-16 0.000E+00 2.320E-21 Y-92 6.450E-05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.230E+00 0.000E+00 1.810E-06 Y-93 2.590E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.040E+03 0.000E+00 7.050E-03 ZR-95 8.170E+02 1.990E+02 0.000E+00 2.140E+02 0.000E+00 9.910E+04 0.000E+00 1.410E+02 ZR-97 4.870E-01 8.360E-02 0.000E+00 8.430E-02 0.000E+00 5.340E+03 0.000E+00 3.820E-02 NB-95 7.120E+04 2.930E+04 0.000E+00 2.100E+04 0.000E+00 2.480E+07 0.000E+00 1.700E+04 MO-99 0.000E+00 2.500E+07 0.000E+00 3.730E+07 0.000E+00 8.220E+06 0.000E+00 4.870E+06 TC-99M 3.300E+00 6.800E+00 0.000E+00 7.320E+01 3.550E+00 1.970E+03 0.000E+00 8.760E+01 TC-101 2.960E-60 3.730E-60 0.000E+00 4.440E-59 2.030E-60 6.340E-58 0.000E+00 3.690E-59 RU-103 1.040E+03 0.000E+00 0.000E+00 2.170E+03 0.000E+00 1.270E+04 0.000E+00 3.480E+02 RU-105 9.660E-04 0.000E+00 0.000E+00 7.110E-03 0.000E+00 3.840E-01 0.000E+00 3.250E-04 RU-106 2.280E+04 0.000E+00 0.000E+00 2.700E+04 0.000E+00 1.730E+05 0.000E+00 2.850E+03 AG-110M 4.630E+07 3.380E+07 0.000E+00 4.830E+07 0.000E+00 1.750E+09 0.000E+00 2.240E+07 TE-125M 1.810E+07 6.050E+06 6.090E+06 0.000E+00 0.000E+00 8.620E+06 0.000E+00 2.450E+06 TE-127 7.580E+02 2.540E+02 6.170E+02 1.850E+03 0.000E+00 1.590E+04 0.000E+00 1.630E+02 TE-127M 5.050E+07 1.680E+07 1.460E+07 1.240E+08 0.000E+00 2.040E+07 0.000E+00 6.120E+06 TE-129 3.260E-10 1.130E-10 2.740E-10 8.130E-10 0.000E+00 2.610E-08 0.000E+00 7.620E-11 TE-129M 6.690E+07 2.290E+07 2.570E+07 1.670E+08 0.000E+00 3.990E+07 0.000E+00 1.030E+07 TE-131 4.110E-33 1.520E-33 3.670E-33 1.050E-32 0.000E+00 1.660E-31 0.000E+00 1.150E-33 TE-131M 4.050E+05 1.630E+05 3.310E+05 1.120E+06 0.000E+00 2.750E+06 0.000E+00 1.350E+05 TE-132 2.530E+06 1.250E+06 1.850E+06 7.840E+06 0.000E+00 4.640E+06 0.000E+00 1.170E+06 I-130 4.260E+06 9.370E+06 1.050E+09 1.030E+07 0.000E+00 2.010E+06 0.000E+00 3.760E+06 Appendix B Pi Infant Goat Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.260E+09 3.850E+09 1.260E+12 4.490E+09 0.000E+00 1.370E+08 0.000E+00 1.690E+09 I-132 1.720E+00 3.480E+00 1.630E+02 3.890E+00 0.000E+00 2.820E+00 0.000E+00 1.240E+00 I-133 4.350E+07 6.340E+07 1.150E+10 7.450E+07 0.000E+00 1.070E+07 0.000E+00 1.860E+07 I-134 2.110E-11 4.320E-11 1.010E-09 4.830E-11 0.000E+00 4.470E-11 0.000E+00 1.540E-11 I-135 1.350E+05 2.680E+05 2.400E+07 2.990E+05 0.000E+00 9.700E+04 0.000E+00 9.770E+04 CS-134 1.090E+11 2.040E+11 0.000E+00 5.250E+10 2.150E+10 5.540E+08 0.000E+00 2.060E+10 CS-136 5.930E+09 1.740E+10 0.000E+00 6.950E+09 1.420E+09 2.650E+08 0.000E+00 6.510E+09 CS-137 1.540E+11 1.810E+11 0.000E+00 4.850E+10 1.960E+10 5.650E+08 0.000E+00 1.280E+10 CS-138 2.520E-22 4.090E-22 0.000E+00 2.040E-22 3.190E-23 6.540E-22 0.000E+00 1.980E-22 BA-139 5.130E-08 3.400E-11 0.000E+00 2.040E-11 2.060E-11 3.250E-06 0.000E+00 1.480E-09 BA-140 2.890E+07 2.890E+04 0.000E+00 6.870E+03 1.780E+04 7.100E+06 0.000E+00 1.490E+06 BA-141 4.720E-46 3.230E-49 0.000E+00 1.940E-49 1.960E-49 5.760E-45 0.000E+00 1.490E-47 BA-142 2.920E-80 2.430E-83 0.000E+00 1.400E-83 1.470E-83 1.200E-79 0.000E+00 1.440E-81 LA-140 4.860E+00 1.920E+00 0.000E+00 0.000E+00 0.000E+00 2.250E+04 0.000E+00 4.930E-01 LA-142 2.040E-11 7.500E-12 0.000E+00 0.000E+00 0.000E+00 1.270E-06 0.000E+00 1.790E-12 CE-141 5.200E+03 3.170E+03 0.000E+00 9.790E+02 0.000E+00 1.640E+06 0.000E+00 3.740E+02 CE-143 4.760E+01 3.160E+04 0.000E+00 9.200E+00 0.000E+00 1.840E+05 0.000E+00 3.600E+00 CE-144 2.790E+05 1.140E+05 0.000E+00 4.620E+04 0.000E+00 1.600E+07 0.000E+00 1.560E+04 PR-143 1.780E+02 6.670E+01 0.000E+00 2.480E+01 0.000E+00 9.410E+04 0.000E+00 8.840E+00 PR-144 6.830E-54 2.640E-54 0.000E+00 9.570E-55 0.000E+00 1.230E-49 0.000E+00 3.440E-55 ND-147 1.060E+02 1.090E+02 0.000E+00 4.190E+01 0.000E+00 6.880E+04 0.000E+00 6.650E+00 W-187 7.300E+03 5.070E+03 0.000E+00 0.000E+00 0.000E+00 2.980E+05 0.000E+00 1.750E+03 NP-239 4.380E+00 3.910E-01 0.000E+00 7.810E-01 0.000E+00 1.130E+04 0.000E+00 2.210E-01 Appendix B Pi Infant Goat Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 6.470E+02 6.470E+02 6.470E+02 6.470E+02 6.470E+02 0.000E+00 6.470E+02 C-14 2.650E+04 5.310E+03 5.310E+03 5.310E+03 5.310E+03 5.310E+03 0.000E+00 5.310E+03 NA-24 1.060E+04 1.060E+04 1.060E+04 1.060E+04 1.060E+04 1.060E+04 0.000E+00 1.060E+04 P-32 2.030E+06 1.120E+05 0.000E+00 0.000E+00 0.000E+00 1.610E+04 0.000E+00 7.740E+04 CR-51 0.000E+00 0.000E+00 5.750E+01 1.320E+01 1.280E+04 3.570E+02 0.000E+00 8.950E+01 MN-54 0.000E+00 2.530E+04 0.000E+00 4.980E+03 1.000E+06 7.060E+03 0.000E+00 4.980E+03 MN-56 0.000E+00 1.540E+00 0.000E+00 1.100E+00 1.250E+04 7.170E+04 0.000E+00 2.210E-01 FE-55 1.970E+04 1.170E+04 0.000E+00 0.000E+00 8.690E+04 1.090E+03 0.000E+00 3.330E+03 FE-59 1.360E+04 2.350E+04 0.000E+00 0.000E+00 1.010E+06 2.480E+04 0.000E+00 9.480E+03 CO-58 0.000E+00 1.220E+03 0.000E+00 0.000E+00 7.770E+05 1.110E+04 0.000E+00 1.820E+03 CO-60 0.000E+00 8.020E+03 0.000E+00 0.000E+00 4.510E+06 3.190E+04 0.000E+00 1.180E+04 NI-63 3.390E+05 2.040E+04 0.000E+00 0.000E+00 2.090E+05 2.420E+03 0.000E+00 1.160E+04 NI-65 2.390E+00 2.840E-01 0.000E+00 0.000E+00 8.120E+03 5.010E+04 0.000E+00 1.230E-01 CU-64 0.000E+00 1.880E+00 0.000E+00 3.980E+00 9.300E+03 1.500E+04 0.000E+00 7.740E-01 ZN-65 1.930E+04 6.260E+04 0.000E+00 3.250E+04 6.470E+05 5.140E+04 0.000E+00 3.110E+04 ZN-69 5.390E-02 9.670E-02 0.000E+00 4.020E-02 1.470E+03 1.320E+04 0.000E+00 7.180E-03 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.810E+02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.000E+02 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.040E+01 RB-86 0.000E+00 1.900E+05 0.000E+00 0.000E+00 0.000E+00 3.040E+03 0.000E+00 8.820E+04 RB-88 0.000E+00 5.570E+02 0.000E+00 0.000E+00 0.000E+00 3.390E+02 0.000E+00 2.870E+02 RB-89 0.000E+00 3.210E+02 0.000E+00 0.000E+00 0.000E+00 6.820E+01 0.000E+00 2.060E+02 SR-89 3.980E+05 0.000E+00 0.000E+00 0.000E+00 2.030E+06 6.400E+04 0.000E+00 1.140E+04 SR-90 4.090E+07 0.000E+00 0.000E+00 0.000E+00 1.120E+07 1.310E+05 0.000E+00 2.590E+06 SR-91 9.560E+01 0.000E+00 0.000E+00 0.000E+00 5.260E+04 7.340E+04 0.000E+00 3.460E+00 Appendix B Pi Infant Inhalation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.050E+01 0.000E+00 0.000E+00 0.000E+00 2.380E+04 1.400E+05 0.000E+00 3.910E-01 Y-90 3.290E+03 0.000E+00 0.000E+00 0.000E+00 2.690E+05 1.040E+05 0.000E+00 8.820E+01 Y-91 5.880E+05 0.000E+00 0.000E+00 0.000E+00 2.450E+06 7.030E+04 0.000E+00 1.570E+04 Y-91M 4.070E-01 0.000E+00 0.000E+00 0.000E+00 2.790E+03 2.350E+03 0.000E+00 1.390E-02 Y-92 1.640E+01 0.000E+00 0.000E+00 0.000E+00 2.450E+04 1.270E+05 0.000E+00 4.610E-01 Y-93 1.500E+02 0.000E+00 0.000E+00 0.000E+00 7.640E+04 1.670E+05 0.000E+00 4.070E+00 ZR-95 1.150E+05 2.790E+04 0.000E+00 3.110E+04 1.750E+06 2.170E+04 0.000E+00 2.030E+04 ZR-97 1.500E+02 2.560E+01 0.000E+00 2.590E+01 1.100E+05 1.400E+05 0.000E+00 1.170E+01 NB-95 1.570E+04 6.430E+03 0.000E+00 4.720E+03 4.790E+05 1.270E+04 0.000E+00 3.780E+03 MO-99 0.000E+00 1.650E+02 0.000E+00 2.650E+02 1.350E+05 4.870E+04 0.000E+00 3.230E+01 TC-99M 1.400E-03 2.880E-03 0.000E+00 3.110E-02 8.110E+02 2.030E+03 0.000E+00 3.720E-02 TC-101 6.510E-05 8.230E-05 0.000E+00 9.790E-04 5.840E+02 8.440E+02 0.000E+00 8.120E-04 RU-103 2.020E+03 0.000E+00 0.000E+00 4.240E+03 5.520E+05 1.610E+04 0.000E+00 6.790E+02 RU-105 1.220E+00 0.000E+00 0.000E+00 8.990E-01 1.570E+04 4.840E+04 0.000E+00 4.100E-01 RU-106 8.680E+04 0.000E+00 0.000E+00 1.070E+05 1.160E+07 1.640E+05 0.000E+00 1.090E+04 AG-110M 9.980E+03 7.220E+03 0.000E+00 1.090E+04 3.670E+06 3.300E+04 0.000E+00 5.000E+03 TE-125M 4.760E+03 1.990E+03 1.620E+03 0.000E+00 4.470E+05 1.290E+04 0.000E+00 6.580E+02 TE-127 2.230E+00 9.530E-01 1.850E+00 4.860E+00 1.030E+04 2.440E+04 0.000E+00 4.890E-01 TE-127M 1.670E+04 6.900E+03 4.870E+03 3.750E+04 1.310E+06 2.730E+04 0.000E+00 2.070E+03 TE-129 7.880E-02 3.470E-02 6.750E-02 1.750E-01 3.000E+03 2.630E+04 0.000E+00 1.880E-02 TE-129M 1.410E+04 6.090E+03 5.470E+03 3.180E+04 1.680E+06 6.900E+04 0.000E+00 2.230E+03 TE-131 1.740E-02 8.220E-03 1.580E-02 3.990E-02 2.060E+03 8.220E+03 0.000E+00 5.000E-03 TE-131M 1.070E+02 5.500E+01 8.930E+01 2.650E+02 1.990E+05 1.190E+05 0.000E+00 3.630E+01 TE-132 3.720E+02 2.370E+02 2.790E+02 1.030E+03 3.400E+05 4.410E+04 0.000E+00 1.760E+02 I-130 6.360E+03 1.390E+04 1.600E+06 1.530E+04 0.000E+00 1.990E+03 0.000E+00 5.570E+03 Appendix B Pi Infant Inhalation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.790E+04 4.440E+04 1.480E+07 5.180E+04 0.000E+00 1.060E+03 0.000E+00 1.960E+04 I-132 1.690E+03 3.540E+03 1.690E+05 3.950E+03 0.000E+00 1.900E+03 0.000E+00 1.260E+03 I-133 1.320E+04 1.920E+04 3.560E+06 2.240E+04 0.000E+00 2.160E+03 0.000E+00 5.600E+03 I-134 9.210E+02 1.880E+03 4.450E+04 2.090E+03 0.000E+00 1.290E+03 0.000E+00 6.650E+02 I-135 3.860E+03 7.600E+03 6.960E+05 8.470E+03 0.000E+00 1.830E+03 0.000E+00 2.770E+03 CS-134 3.960E+05 7.030E+05 0.000E+00 1.900E+05 7.970E+04 1.330E+03 0.000E+00 7.450E+04 CS-136 4.830E+04 1.350E+05 0.000E+00 5.640E+04 1.180E+04 1.430E+03 0.000E+00 5.290E+04 CS-137 5.490E+05 6.120E+05 0.000E+00 1.720E+05 7.130E+04 1.330E+03 0.000E+00 4.550E+04 CS-138 5.050E+02 7.810E+02 0.000E+00 4.100E+02 6.540E+01 8.760E+02 0.000E+00 3.980E+02 BA-139 1.480E+00 9.840E-04 0.000E+00 5.920E-04 5.950E+03 5.100E+04 0.000E+00 4.300E-02 BA-140 5.600E+04 5.600E+01 0.000E+00 1.340E+01 1.600E+06 3.840E+04 0.000E+00 2.900E+03 BA-141 1.570E-01 1.080E-04 0.000E+00 6.500E-05 2.970E+03 4.750E+03 0.000E+00 4.970E-03 BA-142 3.980E-02 3.300E-05 0.000E+00 1.900E-05 1.550E+03 6.930E+02 0.000E+00 1.960E-03 LA-140 5.050E+02 2.000E+02 0.000E+00 0.000E+00 1.680E+05 8.480E+04 0.000E+00 5.150E+01 LA-142 1.030E+00 3.770E-01 0.000E+00 0.000E+00 8.220E+03 5.950E+04 0.000E+00 9.040E-02 CE-141 2.770E+04 1.670E+04 0.000E+00 5.250E+03 5.170E+05 2.160E+04 0.000E+00 1.990E+03 CE-143 2.930E+02 1.930E+02 0.000E+00 5.640E+01 1.160E+05 4.970E+04 0.000E+00 2.210E+01 CE-144 3.190E+06 1.210E+06 0.000E+00 5.380E+05 9.840E+06 1.480E+05 0.000E+00 1.760E+05 PR-143 1.400E+04 5.240E+03 0.000E+00 1.970E+03 4.330E+05 3.720E+04 0.000E+00 6.990E+02 PR-144 4.790E-02 1.850E-02 0.000E+00 6.720E-03 1.610E+03 4.280E+03 0.000E+00 2.410E-03 ND-147 7.940E+03 8.130E+03 0.000E+00 3.150E+03 3.220E+05 3.120E+04 0.000E+00 5.000E+02 W-187 1.300E+01 9.020E+00 0.000E+00 0.000E+00 3.960E+04 3.560E+04 0.000E+00 3.120E+00 NP-239 3.710E+02 3.320E+01 0.000E+00 6.620E+01 5.950E+04 2.490E+04 0.000E+00 1.880E+01 Appendix B Pi Infant Inhalation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 1.710E+07 1.710E+07 1.710E+07 1.710E+07 1.710E+07 1.710E+07 1.980E+07 1.710E+07 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 6.650E+06 6.650E+06 6.650E+06 6.650E+06 6.650E+06 6.650E+06 7.860E+06 6.650E+06 MN-54 1.100E+09 1.100E+09 1.100E+09 1.100E+09 1.100E+09 1.100E+09 1.290E+09 1.100E+09 MN-56 1.290E+06 1.290E+06 1.290E+06 1.290E+06 1.290E+06 1.290E+06 1.520E+06 1.290E+06 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 3.880E+08 3.880E+08 3.880E+08 3.880E+08 3.880E+08 3.880E+08 4.560E+08 3.880E+08 CO-58 5.260E+08 5.260E+08 5.260E+08 5.260E+08 5.260E+08 5.260E+08 6.160E+08 5.260E+08 CO-60 4.400E+09 4.400E+09 4.400E+09 4.400E+09 4.400E+09 4.400E+09 5.170E+09 4.400E+09 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 4.240E+05 4.240E+05 4.240E+05 4.240E+05 4.240E+05 4.240E+05 4.930E+05 4.240E+05 CU-64 8.670E+05 8.670E+05 8.670E+05 8.670E+05 8.670E+05 8.670E+05 9.820E+05 8.670E+05 ZN-65 6.880E+08 6.880E+08 6.880E+08 6.880E+08 6.880E+08 6.880E+08 7.910E+08 6.880E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 6.960E+03 6.960E+03 6.960E+03 6.960E+03 6.960E+03 6.960E+03 1.010E+04 6.960E+03 BR-84 2.890E+05 2.890E+05 2.890E+05 2.890E+05 2.890E+05 2.890E+05 3.380E+05 2.890E+05 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 1.280E+07 1.280E+07 1.280E+07 1.280E+07 1.280E+07 1.280E+07 1.470E+07 1.280E+07 RB-88 4.720E+04 4.720E+04 4.720E+04 4.720E+04 4.720E+04 4.720E+04 5.400E+04 4.720E+04 RB-89 1.760E+05 1.760E+05 1.760E+05 1.760E+05 1.760E+05 1.760E+05 2.110E+05 1.760E+05 SR-89 3.070E+04 3.070E+04 3.070E+04 3.070E+04 3.070E+04 3.070E+04 3.560E+04 3.070E+04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 3.070E+06 3.070E+06 3.070E+06 3.070E+06 3.070E+06 3.070E+06 3.590E+06 3.070E+06 Appendix B Pi Infant Ground Plane Deposition - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.110E+06 1.110E+06 1.110E+06 1.110E+06 1.110E+06 1.110E+06 1.230E+06 1.110E+06 Y-90 6.420E+03 6.420E+03 6.420E+03 6.420E+03 6.420E+03 6.420E+03 7.580E+03 6.420E+03 Y-91 1.510E+06 1.510E+06 1.510E+06 1.510E+06 1.510E+06 1.510E+06 1.700E+06 1.510E+06 Y-91M 1.430E+05 1.430E+05 1.430E+05 1.430E+05 1.430E+05 1.430E+05 1.660E+05 1.430E+05 Y-92 2.580E+05 2.580E+05 2.580E+05 2.580E+05 2.580E+05 2.580E+05 3.060E+05 2.580E+05 Y-93 2.620E+05 2.620E+05 2.620E+05 2.620E+05 2.620E+05 2.620E+05 3.580E+05 2.620E+05 ZR-95 3.430E+08 3.430E+08 3.430E+08 3.430E+08 3.430E+08 3.430E+08 3.980E+08 3.430E+08 ZR-97 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.920E+06 4.230E+06 NB-95 1.950E+08 1.950E+08 1.950E+08 1.950E+08 1.950E+08 1.950E+08 2.300E+08 1.950E+08 MO-99 5.710E+06 5.710E+06 5.710E+06 5.710E+06 5.710E+06 5.710E+06 6.610E+06 5.710E+06 TC-99M 2.630E+05 2.630E+05 2.630E+05 2.630E+05 2.630E+05 2.630E+05 3.010E+05 2.630E+05 TC-101 2.910E+04 2.910E+04 2.910E+04 2.910E+04 2.910E+04 2.910E+04 3.230E+04 2.910E+04 RU-103 1.540E+08 1.540E+08 1.540E+08 1.540E+08 1.540E+08 1.540E+08 1.800E+08 1.540E+08 RU-105 9.090E+05 9.090E+05 9.090E+05 9.090E+05 9.090E+05 9.090E+05 1.030E+06 9.090E+05 RU-106 2.990E+08 2.990E+08 2.990E+08 2.990E+08 2.990E+08 2.990E+08 3.590E+08 2.990E+08 AG-110M 3.120E+09 3.120E+09 3.120E+09 3.120E+09 3.120E+09 3.120E+09 3.650E+09 3.120E+09 TE-125M 2.190E+06 2.190E+06 2.190E+06 2.190E+06 2.190E+06 2.190E+06 3.000E+06 2.190E+06 TE-127 4.250E+03 4.250E+03 4.250E+03 4.250E+03 4.250E+03 4.250E+03 4.680E+03 4.250E+03 TE-127M 1.180E+05 1.180E+05 1.180E+05 1.180E+05 1.180E+05 1.180E+05 1.390E+05 1.180E+05 TE-129 3.750E+04 3.750E+04 3.750E+04 3.750E+04 3.750E+04 3.750E+04 4.430E+04 3.750E+04 TE-129M 2.820E+07 2.820E+07 2.820E+07 2.820E+07 2.820E+07 2.820E+07 3.300E+07 2.820E+07 TE-131 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.930E+07 4.170E+04 TE-131M 1.150E+07 1.150E+07 1.150E+07 1.150E+07 1.150E+07 1.150E+07 1.350E+07 1.150E+07 TE-132 6.050E+06 6.050E+06 6.050E+06 6.050E+06 6.050E+06 6.050E+06 7.120E+06 6.050E+06 I-130 7.870E+06 7.870E+06 7.870E+06 7.870E+06 7.870E+06 7.870E+06 9.560E+06 7.870E+06 Appendix B Pi Infant Ground Plane Deposition - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX B Pi Dose Factors for use in the Gaseous Release Rate Limit Calculations Agegroup: INFANT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 2.460E+07 2.460E+07 2.460E+07 2.460E+07 2.460E+07 2.460E+07 2.980E+07 2.460E+07 I-132 1.780E+06 1.780E+06 1.780E+06 1.780E+06 1.780E+06 1.780E+06 2.090E+06 1.780E+06 I-133 3.500E+06 3.500E+06 3.500E+06 3.500E+06 3.500E+06 3.500E+06 4.260E+06 3.500E+06 I-134 6.380E+05 6.380E+05 6.380E+05 6.380E+05 6.380E+05 6.380E+05 7.580E+05 6.380E+05 I-135 3.610E+06 3.610E+06 3.610E+06 3.610E+06 3.610E+06 3.610E+06 4.210E+06 3.610E+06 CS-134 2.810E+09 2.810E+09 2.810E+09 2.810E+09 2.810E+09 2.810E+09 3.280E+09 2.810E+09 CS-136 2.160E+08 2.160E+08 2.160E+08 2.160E+08 2.160E+08 2.160E+08 2.440E+08 2.160E+08 CS-137 1.150E+09 1.150E+09 1.150E+09 1.150E+09 1.150E+09 1.150E+09 1.340E+09 1.150E+09 CS-138 5.130E+05 5.130E+05 5.130E+05 5.130E+05 5.130E+05 5.130E+05 5.860E+05 5.130E+05 BA-139 1.510E+05 1.510E+05 1.510E+05 1.510E+05 1.510E+05 1.510E+05 1.700E+05 1.510E+05 BA-140 2.930E+07 2.930E+07 2.930E+07 2.930E+07 2.930E+07 2.930E+07 3.350E+07 2.930E+07 BA-141 5.960E+04 5.960E+04 5.960E+04 5.960E+04 5.960E+04 5.960E+04 6.790E+04 5.960E+04 BA-142 6.410E+04 6.410E+04 6.410E+04 6.410E+04 6.410E+04 6.410E+04 7.300E+04 6.410E+04 LA-140 2.740E+07 2.740E+07 2.740E+07 2.740E+07 2.740E+07 2.740E+07 3.110E+07 2.740E+07 LA-142 1.090E+06 1.090E+06 1.090E+06 1.090E+06 1.090E+06 1.090E+06 1.300E+06 1.090E+06 CE-141 1.950E+07 1.950E+07 1.950E+07 1.950E+07 1.950E+07 1.950E+07 2.200E+07 1.950E+07 CE-143 3.300E+06 3.300E+06 3.300E+06 3.300E+06 3.300E+06 3.300E+06 3.750E+06 3.300E+06 CE-144 5.850E+07 5.850E+07 5.850E+07 5.850E+07 5.850E+07 5.850E+07 6.760E+07 5.850E+07 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 2.620E+03 2.620E+03 2.620E+03 2.620E+03 2.620E+03 2.620E+03 3.010E+03 2.620E+03 ND-147 1.200E+07 1.200E+07 1.200E+07 1.200E+07 1.200E+07 1.200E+07 1.440E+07 1.200E+07 W-187 3.360E+06 3.360E+06 3.360E+06 3.360E+06 3.360E+06 3.360E+06 3.900E+06 3.360E+06 NP-239 2.440E+06 2.440E+06 2.440E+06 2.440E+06 2.440E+06 2.440E+06 2.830E+06 2.440E+06 Appendix B Pi Infant Ground Plane Deposition - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 8.740E+00 8.740E+00 8.740E+00 8.740E+00 8.740E+00 0.000E+00 8.740E+00 C-14 2.360E+02 4.730E+01 4.730E+01 4.730E+01 4.730E+01 4.730E+01 0.000E+00 4.730E+01 NA-24 8.140E+01 8.140E+01 8.140E+01 8.140E+01 8.140E+01 8.140E+01 0.000E+00 8.140E+01 P-32 1.570E+04 9.750E+02 0.000E+00 0.000E+00 0.000E+00 1.760E+03 0.000E+00 6.060E+02 CR-51 0.000E+00 0.000E+00 1.310E-01 4.820E-02 2.900E-01 5.500E+01 0.000E+00 2.190E-01 MN-54 0.000E+00 3.800E+02 0.000E+00 1.130E+02 0.000E+00 1.160E+03 0.000E+00 7.250E+01 MN-56 0.000E+00 3.800E-01 0.000E+00 4.820E-01 0.000E+00 1.210E+01 0.000E+00 6.740E-02 FE-55 2.290E+02 1.580E+02 0.000E+00 0.000E+00 8.820E+01 9.070E+01 0.000E+00 3.690E+01 FE-59 3.580E+02 8.420E+02 0.000E+00 0.000E+00 2.350E+02 2.810E+03 0.000E+00 3.230E+02 CO-58 0.000E+00 6.170E+01 0.000E+00 0.000E+00 0.000E+00 1.250E+03 0.000E+00 1.380E+02 CO-60 0.000E+00 1.780E+02 0.000E+00 0.000E+00 0.000E+00 3.340E+03 0.000E+00 3.930E+02 NI-63 1.080E+04 7.500E+02 0.000E+00 0.000E+00 0.000E+00 1.560E+02 0.000E+00 3.630E+02 NI-65 1.620E+00 2.100E-01 0.000E+00 0.000E+00 0.000E+00 5.340E+00 0.000E+00 9.600E-02 CU-64 0.000E+00 3.590E+00 0.000E+00 9.060E+00 0.000E+00 3.060E+02 0.000E+00 1.690E+00 ZN-65 4.020E+02 1.280E+03 0.000E+00 8.560E+02 0.000E+00 8.060E+02 0.000E+00 5.780E+02 ZN-69 1.070E-04 2.050E-04 0.000E+00 1.330E-04 0.000E+00 3.080E-05 0.000E+00 1.430E-05 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.480E-01 0.000E+00 1.030E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.270E-12 0.000E+00 6.710E-07 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.380E-77 RB-86 0.000E+00 1.720E+03 0.000E+00 0.000E+00 0.000E+00 3.400E+02 0.000E+00 8.030E+02 RB-88 0.000E+00 3.360E-12 0.000E+00 0.000E+00 0.000E+00 4.640E-23 0.000E+00 1.780E-12 RB-89 0.000E+00 3.090E-14 0.000E+00 0.000E+00 0.000E+00 1.790E-27 0.000E+00 2.170E-14 SR-89 2.550E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.080E+03 0.000E+00 7.310E+02 SR-90 6.310E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.820E+04 0.000E+00 1.550E+05 SR-91 1.960E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.350E+02 0.000E+00 7.930E+00 Appendix C Ai Adult Water - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 8.290E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.640E+02 0.000E+00 3.590E-01 Y-90 7.030E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.460E+03 0.000E+00 1.890E-02 Y-91 1.170E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.420E+03 0.000E+00 3.120E-01 Y-91M 3.360E-07 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.860E-07 0.000E+00 1.300E-08 Y-92 6.710E-03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.170E+02 0.000E+00 1.960E-04 Y-93 9.770E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.100E+03 0.000E+00 2.700E-03 ZR-95 2.520E+00 8.070E-01 0.000E+00 1.270E+00 0.000E+00 2.560E+03 0.000E+00 5.460E-01 ZR-97 8.540E-02 1.720E-02 0.000E+00 2.600E-02 0.000E+00 5.340E+03 0.000E+00 7.880E-03 NB-95 5.130E-01 2.850E-01 0.000E+00 2.820E-01 0.000E+00 1.730E+03 0.000E+00 1.530E-01 MO-99 0.000E+00 3.160E+02 0.000E+00 7.160E+02 0.000E+00 7.330E+02 0.000E+00 6.020E+01 TC-99M 5.160E-03 1.460E-02 0.000E+00 2.210E-01 7.140E-03 8.630E+00 0.000E+00 1.860E-01 TC-101 1.130E-17 1.630E-17 0.000E+00 2.930E-16 8.320E-18 4.890E-29 0.000E+00 1.600E-16 RU-103 1.530E+01 0.000E+00 0.000E+00 5.820E+01 0.000E+00 1.780E+03 0.000E+00 6.570E+00 RU-105 1.970E-01 0.000E+00 0.000E+00 2.540E+00 0.000E+00 1.200E+02 0.000E+00 7.760E-02 RU-106 2.290E+02 0.000E+00 0.000E+00 4.410E+02 0.000E+00 1.480E+04 0.000E+00 2.890E+01 AG-110M 1.330E+01 1.230E+01 0.000E+00 2.420E+01 0.000E+00 5.020E+03 0.000E+00 7.300E+00 TE-125M 2.220E+02 8.030E+01 6.670E+01 9.020E+02 0.000E+00 8.850E+02 0.000E+00 2.970E+01 TE-127 3.780E+00 1.360E+00 2.800E+00 1.540E+01 0.000E+00 2.980E+02 0.000E+00 8.170E-01 TE-127M 5.620E+02 2.010E+02 1.440E+02 2.280E+03 0.000E+00 1.880E+03 0.000E+00 6.840E+01 TE-129 1.920E-03 7.230E-04 1.480E-03 8.080E-03 0.000E+00 1.450E-03 0.000E+00 4.690E-04 TE-129M 9.470E+02 3.530E+02 3.250E+02 3.950E+03 0.000E+00 4.770E+03 0.000E+00 1.500E+02 TE-131 3.520E-09 1.470E-09 2.900E-09 1.540E-08 0.000E+00 4.990E-10 0.000E+00 1.110E-09 TE-131M 1.090E+02 5.340E+01 8.450E+01 5.400E+02 0.000E+00 5.300E+03 0.000E+00 4.450E+01 TE-132 1.880E+02 1.220E+02 1.350E+02 1.170E+03 0.000E+00 5.770E+03 0.000E+00 1.140E+02 I-130 3.210E+01 9.460E+01 8.020E+03 1.480E+02 0.000E+00 8.140E+01 0.000E+00 3.730E+01 Appendix C Ai Adult Water - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.320E+02 4.740E+02 1.550E+05 8.130E+02 0.000E+00 1.250E+02 0.000E+00 2.720E+02 I-132 4.540E-01 1.220E+00 4.250E+01 1.940E+00 0.000E+00 2.280E-01 0.000E+00 4.250E-01 I-133 7.920E+01 1.380E+02 2.020E+04 2.400E+02 0.000E+00 1.240E+02 0.000E+00 4.200E+01 I-134 6.580E-04 1.790E-03 3.100E-02 2.840E-03 0.000E+00 1.560E-06 0.000E+00 6.390E-04 I-135 1.050E+01 2.750E+01 1.810E+03 4.400E+01 0.000E+00 3.100E+01 0.000E+00 1.010E+01 CS-134 5.170E+03 1.230E+04 0.000E+00 3.980E+03 1.320E+03 2.150E+02 0.000E+00 1.010E+04 CS-136 5.280E+02 2.080E+03 0.000E+00 1.160E+03 1.590E+02 2.370E+02 0.000E+00 1.500E+03 CS-137 6.630E+03 9.070E+03 0.000E+00 3.080E+03 1.020E+03 1.760E+02 0.000E+00 5.940E+03 CS-138 8.450E-07 1.670E-06 0.000E+00 1.230E-06 1.210E-07 7.120E-12 0.000E+00 8.260E-07 BA-139 1.990E-02 1.420E-05 0.000E+00 1.330E-05 8.050E-06 3.530E-02 0.000E+00 5.830E-04 BA-140 1.640E+03 2.070E+00 0.000E+00 7.020E-01 1.180E+00 3.390E+03 0.000E+00 1.080E+02 BA-141 5.440E-12 4.120E-15 0.000E+00 3.830E-15 2.340E-15 2.570E-21 0.000E+00 1.840E-13 BA-142 6.290E-21 6.470E-24 0.000E+00 5.460E-24 3.660E-24 8.860E-39 0.000E+00 3.960E-22 LA-140 1.690E-01 8.530E-02 0.000E+00 0.000E+00 0.000E+00 6.260E+03 0.000E+00 2.250E-02 LA-142 5.720E-05 2.600E-05 0.000E+00 0.000E+00 0.000E+00 1.900E-01 0.000E+00 6.480E-06 CE-141 7.710E-01 5.210E-01 0.000E+00 2.420E-01 0.000E+00 1.990E+03 0.000E+00 5.910E-02 CE-143 1.070E-01 7.890E+01 0.000E+00 3.470E-02 0.000E+00 2.950E+03 0.000E+00 8.730E-03 CE-144 4.060E+01 1.700E+01 0.000E+00 1.010E+01 0.000E+00 1.370E+04 0.000E+00 2.180E+00 PR-143 7.460E-01 2.990E-01 0.000E+00 1.730E-01 0.000E+00 3.270E+03 0.000E+00 3.700E-02 PR-144 7.350E-16 3.050E-16 0.000E+00 1.720E-16 0.000E+00 1.060E-22 0.000E+00 3.730E-17 ND-147 5.070E-01 5.860E-01 0.000E+00 3.430E-01 0.000E+00 2.810E+03 0.000E+00 3.510E-02 W-187 6.050E+00 5.050E+00 0.000E+00 0.000E+00 0.000E+00 1.660E+03 0.000E+00 1.770E+00 NP-239 8.550E-02 8.400E-03 0.000E+00 2.620E-02 0.000E+00 1.720E+03 0.000E+00 4.630E-03 Appendix C Ai Adult Water - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.260E-01 2.260E-01 2.260E-01 2.260E-01 2.260E-01 0.000E+00 2.260E-01 C-14 3.130E+04 6.260E+03 6.260E+03 6.260E+03 6.260E+03 6.260E+03 0.000E+00 6.260E+03 NA-24 1.350E+02 1.350E+02 1.350E+02 1.350E+02 1.350E+02 1.350E+02 0.000E+00 1.350E+02 P-32 1.320E+06 8.210E+04 0.000E+00 0.000E+00 0.000E+00 1.480E+05 0.000E+00 5.100E+04 CR-51 0.000E+00 0.000E+00 7.420E-01 2.740E-01 1.650E+00 3.120E+02 0.000E+00 1.240E+00 MN-54 0.000E+00 4.370E+03 0.000E+00 1.300E+03 0.000E+00 1.340E+04 0.000E+00 8.330E+02 MN-56 0.000E+00 1.730E-01 0.000E+00 2.200E-01 0.000E+00 5.530E+00 0.000E+00 3.070E-02 FE-55 6.580E+02 4.550E+02 0.000E+00 0.000E+00 2.540E+02 2.610E+02 0.000E+00 1.060E+02 FE-59 1.020E+03 2.400E+03 0.000E+00 0.000E+00 6.720E+02 8.010E+03 0.000E+00 9.220E+02 CO-58 0.000E+00 8.830E+01 0.000E+00 0.000E+00 0.000E+00 1.790E+03 0.000E+00 1.980E+02 CO-60 0.000E+00 2.560E+02 0.000E+00 0.000E+00 0.000E+00 4.810E+03 0.000E+00 5.650E+02 NI-63 3.110E+04 2.160E+03 0.000E+00 0.000E+00 0.000E+00 4.500E+02 0.000E+00 1.040E+03 NI-65 1.720E-01 2.230E-02 0.000E+00 0.000E+00 0.000E+00 5.660E-01 0.000E+00 1.020E-02 CU-64 0.000E+00 2.680E+00 0.000E+00 6.760E+00 0.000E+00 2.290E+02 0.000E+00 1.260E+00 ZN-65 2.310E+04 7.350E+04 0.000E+00 4.920E+04 0.000E+00 4.630E+04 0.000E+00 3.320E+04 ZN-69 7.730E-07 1.480E-06 0.000E+00 9.610E-07 0.000E+00 2.220E-07 0.000E+00 1.030E-07 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.500E-02 0.000E+00 3.820E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.850E-18 0.000E+00 1.250E-12 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 9.730E+04 0.000E+00 0.000E+00 0.000E+00 1.920E+04 0.000E+00 4.530E+04 RB-88 0.000E+00 1.290E-22 0.000E+00 0.000E+00 0.000E+00 1.780E-33 0.000E+00 6.830E-23 RB-89 0.000E+00 1.640E-26 0.000E+00 0.000E+00 0.000E+00 9.560E-40 0.000E+00 1.160E-26 SR-89 2.180E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.500E+03 0.000E+00 6.260E+02 SR-90 5.440E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.570E+04 0.000E+00 1.340E+05 SR-91 7.050E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.360E+02 0.000E+00 2.850E+00 Appendix C Ai Adult Fish - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 3.320E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.570E+00 0.000E+00 1.430E-02 Y-90 4.440E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.710E+03 0.000E+00 1.190E-02 Y-91 8.340E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.590E+03 0.000E+00 2.230E-01 Y-91M 1.070E-11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.150E-11 0.000E+00 4.150E-13 Y-92 4.600E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.060E+00 0.000E+00 1.340E-05 Y-93 3.080E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.770E+02 0.000E+00 8.500E-04 ZR-95 2.380E-01 7.620E-02 0.000E+00 1.200E-01 0.000E+00 2.410E+02 0.000E+00 5.160E-02 ZR-97 4.960E-03 1.000E-03 0.000E+00 1.510E-03 0.000E+00 3.100E+02 0.000E+00 4.570E-04 NB-95 4.380E+02 2.440E+02 0.000E+00 2.410E+02 0.000E+00 1.480E+06 0.000E+00 1.310E+02 MO-99 0.000E+00 8.020E+01 0.000E+00 1.820E+02 0.000E+00 1.860E+02 0.000E+00 1.530E+01 TC-99M 5.590E-04 1.580E-03 0.000E+00 2.400E-02 7.740E-04 9.340E-01 0.000E+00 2.010E-02 TC-101 2.610E-33 3.760E-33 0.000E+00 6.770E-32 1.920E-33 1.130E-44 0.000E+00 3.690E-32 RU-103 4.350E+00 0.000E+00 0.000E+00 1.660E+01 0.000E+00 5.080E+02 0.000E+00 1.870E+00 RU-105 8.670E-03 0.000E+00 0.000E+00 1.120E-01 0.000E+00 5.300E+00 0.000E+00 3.420E-03 RU-106 6.570E+01 0.000E+00 0.000E+00 1.270E+02 0.000E+00 4.250E+03 0.000E+00 8.320E+00 AG-110M 8.790E-01 8.130E-01 0.000E+00 1.600E+00 0.000E+00 3.320E+02 0.000E+00 4.830E-01 TE-125M 2.540E+03 9.190E+02 7.630E+02 1.030E+04 0.000E+00 1.010E+04 0.000E+00 3.400E+02 TE-127 1.790E+01 6.440E+00 1.330E+01 7.300E+01 0.000E+00 1.410E+03 0.000E+00 3.880E+00 TE-127M 6.440E+03 2.300E+03 1.650E+03 2.620E+04 0.000E+00 2.160E+04 0.000E+00 7.850E+02 TE-129 1.630E-05 6.120E-06 1.250E-05 6.850E-05 0.000E+00 1.230E-05 0.000E+00 3.970E-06 TE-129M 1.080E+04 4.020E+03 3.710E+03 4.500E+04 0.000E+00 5.430E+04 0.000E+00 1.710E+03 TE-131 8.710E-17 3.640E-17 7.160E-17 3.820E-16 0.000E+00 1.230E-17 0.000E+00 2.750E-17 TE-131M 9.510E+02 4.650E+02 7.370E+02 4.710E+03 0.000E+00 4.620E+04 0.000E+00 3.880E+02 TE-132 1.950E+03 1.260E+03 1.390E+03 1.210E+04 0.000E+00 5.960E+04 0.000E+00 1.180E+03 I-130 7.050E+00 2.080E+01 1.760E+03 3.250E+01 0.000E+00 1.790E+01 0.000E+00 8.210E+00 Appendix C Ai Adult Fish - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.370E+02 1.960E+02 6.420E+04 3.360E+02 0.000E+00 5.170E+01 0.000E+00 1.120E+02 I-132 5.270E-03 1.410E-02 4.940E-01 2.250E-02 0.000E+00 2.650E-03 0.000E+00 4.940E-03 I-133 2.290E+01 3.990E+01 5.860E+03 6.950E+01 0.000E+00 3.580E+01 0.000E+00 1.210E+01 I-134 2.120E-08 5.750E-08 9.960E-07 9.140E-08 0.000E+00 5.010E-11 0.000E+00 2.060E-08 I-135 1.290E+00 3.370E+00 2.220E+02 5.410E+00 0.000E+00 3.810E+00 0.000E+00 1.240E+00 CS-134 2.980E+05 7.080E+05 0.000E+00 2.290E+05 7.610E+04 1.240E+04 0.000E+00 5.790E+05 CS-136 2.960E+04 1.170E+05 0.000E+00 6.500E+04 8.900E+03 1.330E+04 0.000E+00 8.400E+04 CS-137 3.820E+05 5.220E+05 0.000E+00 1.770E+05 5.890E+04 1.010E+04 0.000E+00 3.420E+05 CS-138 8.940E-12 1.770E-11 0.000E+00 1.300E-11 1.280E-12 7.530E-17 0.000E+00 8.750E-12 BA-139 5.650E-06 4.030E-09 0.000E+00 3.760E-09 2.280E-09 1.000E-05 0.000E+00 1.660E-07 BA-140 1.840E+02 2.310E-01 0.000E+00 7.860E-02 1.320E-01 3.790E+02 0.000E+00 1.210E+01 BA-141 8.700E-25 6.580E-28 0.000E+00 6.120E-28 3.730E-28 4.100E-34 0.000E+00 2.940E-26 BA-142 2.570E-42 2.640E-45 0.000E+00 2.230E-45 1.490E-45 3.620E-60 0.000E+00 1.610E-43 LA-140 9.900E-02 4.990E-02 0.000E+00 0.000E+00 0.000E+00 3.660E+03 0.000E+00 1.320E-02 LA-142 2.210E-07 1.000E-07 0.000E+00 0.000E+00 0.000E+00 7.330E-04 0.000E+00 2.500E-08 CE-141 2.190E-02 1.480E-02 0.000E+00 6.890E-03 0.000E+00 5.670E+01 0.000E+00 1.680E-03 CE-143 2.380E-03 1.760E+00 0.000E+00 7.760E-04 0.000E+00 6.590E+01 0.000E+00 1.950E-04 CE-144 1.170E+00 4.870E-01 0.000E+00 2.890E-01 0.000E+00 3.940E+02 0.000E+00 6.260E-02 PR-143 5.230E-01 2.100E-01 0.000E+00 1.210E-01 0.000E+00 2.290E+03 0.000E+00 2.590E-02 PR-144 1.550E-28 6.440E-29 0.000E+00 3.630E-29 0.000E+00 2.230E-35 0.000E+00 7.880E-30 ND-147 3.530E-01 4.080E-01 0.000E+00 2.390E-01 0.000E+00 1.960E+03 0.000E+00 2.440E-02 W-187 1.470E+02 1.230E+02 0.000E+00 0.000E+00 0.000E+00 4.030E+04 0.000E+00 4.300E+01 NP-239 2.120E-02 2.090E-03 0.000E+00 6.510E-03 0.000E+00 4.280E+02 0.000E+00 1.150E-03 Appendix C Ai Adult Fish - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 4.270E-01 4.270E-01 4.270E-01 4.270E-01 4.270E-01 4.270E-01 4.960E-01 4.270E-01 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 1.670E-01 1.670E-01 1.670E-01 1.670E-01 1.670E-01 1.670E-01 1.970E-01 1.670E-01 MN-54 4.960E+01 4.960E+01 4.960E+01 4.960E+01 4.960E+01 4.960E+01 5.820E+01 4.960E+01 MN-56 3.230E-02 3.230E-02 3.230E-02 3.230E-02 3.230E-02 3.230E-02 3.820E-02 3.230E-02 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 9.770E+00 9.770E+00 9.770E+00 9.770E+00 9.770E+00 9.770E+00 1.150E+01 9.770E+00 CO-58 1.360E+01 1.360E+01 1.360E+01 1.360E+01 1.360E+01 1.360E+01 1.590E+01 1.360E+01 CO-60 7.690E+02 7.690E+02 7.690E+02 7.690E+02 7.690E+02 7.690E+02 9.050E+02 7.690E+02 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 1.060E-02 1.060E-02 1.060E-02 1.060E-02 1.060E-02 1.060E-02 1.240E-02 1.060E-02 CU-64 2.170E-02 2.170E-02 2.170E-02 2.170E-02 2.170E-02 2.170E-02 2.460E-02 2.170E-02 ZN-65 2.670E+01 2.670E+01 2.670E+01 2.670E+01 2.670E+01 2.670E+01 3.080E+01 2.670E+01 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 1.740E-04 1.740E-04 1.740E-04 1.740E-04 1.740E-04 1.740E-04 2.530E-04 1.740E-04 BR-84 7.250E-03 7.250E-03 7.250E-03 7.250E-03 7.250E-03 7.250E-03 8.460E-03 7.250E-03 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 3.220E-01 3.220E-01 3.220E-01 3.220E-01 3.220E-01 3.220E-01 3.680E-01 3.220E-01 RB-88 1.180E-03 1.180E-03 1.180E-03 1.180E-03 1.180E-03 1.180E-03 1.350E-03 1.180E-03 RB-89 4.400E-03 4.400E-03 4.400E-03 4.400E-03 4.400E-03 4.400E-03 5.280E-03 4.400E-03 SR-89 7.740E-04 7.740E-04 7.740E-04 7.740E-04 7.740E-04 7.740E-04 8.990E-04 7.740E-04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 7.690E-02 7.690E-02 7.690E-02 7.690E-02 7.690E-02 7.690E-02 8.990E-02 7.690E-02 Appendix C Ai Adult Shoreline Sediment - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 2.780E-02 2.780E-02 2.780E-02 2.780E-02 2.780E-02 2.780E-02 3.090E-02 2.780E-02 Y-90 1.610E-04 1.610E-04 1.610E-04 1.610E-04 1.610E-04 1.610E-04 1.900E-04 1.610E-04 Y-91 3.840E-02 3.840E-02 3.840E-02 3.840E-02 3.840E-02 3.840E-02 4.320E-02 3.840E-02 Y-91M 3.590E-03 3.590E-03 3.590E-03 3.590E-03 3.590E-03 3.590E-03 4.150E-03 3.590E-03 Y-92 6.460E-03 6.460E-03 6.460E-03 6.460E-03 6.460E-03 6.460E-03 7.670E-03 6.460E-03 Y-93 6.560E-03 6.560E-03 6.560E-03 6.560E-03 6.560E-03 6.560E-03 8.980E-03 6.560E-03 ZR-95 8.760E+00 8.760E+00 8.760E+00 8.760E+00 8.760E+00 8.760E+00 1.020E+01 8.760E+00 ZR-97 1.060E-01 1.060E-01 1.060E-01 1.060E-01 1.060E-01 1.060E-01 1.230E-01 1.060E-01 NB-95 4.890E+00 4.890E+00 4.890E+00 4.890E+00 4.890E+00 4.890E+00 5.750E+00 4.890E+00 MO-99 1.430E-01 1.430E-01 1.430E-01 1.430E-01 1.430E-01 1.430E-01 1.660E-01 1.430E-01 TC-99M 6.590E-03 6.590E-03 6.590E-03 6.590E-03 6.590E-03 6.590E-03 7.550E-03 6.590E-03 TC-101 7.280E-04 7.280E-04 7.280E-04 7.280E-04 7.280E-04 7.280E-04 8.090E-04 7.280E-04 RU-103 3.870E+00 3.870E+00 3.870E+00 3.870E+00 3.870E+00 3.870E+00 4.520E+00 3.870E+00 RU-105 2.280E-02 2.280E-02 2.280E-02 2.280E-02 2.280E-02 2.280E-02 2.580E-02 2.280E-02 RU-106 1.510E+01 1.510E+01 1.510E+01 1.510E+01 1.510E+01 1.510E+01 1.810E+01 1.510E+01 AG-110M 1.230E+02 1.230E+02 1.230E+02 1.230E+02 1.230E+02 1.230E+02 1.440E+02 1.230E+02 TE-125M 5.550E-02 5.550E-02 5.550E-02 5.550E-02 5.550E-02 5.550E-02 7.620E-02 5.550E-02 TE-127 1.070E-04 1.070E-04 1.070E-04 1.070E-04 1.070E-04 1.070E-04 1.170E-04 1.070E-04 TE-127M 3.280E-03 3.280E-03 3.280E-03 3.280E-03 3.280E-03 3.280E-03 3.880E-03 3.280E-03 TE-129 9.390E-04 9.390E-04 9.390E-04 9.390E-04 9.390E-04 9.390E-04 1.110E-03 9.390E-04 TE-129M 7.080E-01 7.080E-01 7.080E-01 7.080E-01 7.080E-01 7.080E-01 8.270E-01 7.080E-01 TE-131 1.040E-03 1.040E-03 1.040E-03 1.040E-03 1.040E-03 1.040E-03 1.230E+00 1.040E-03 TE-131M 2.870E-01 2.870E-01 2.870E-01 2.870E-01 2.870E-01 2.870E-01 3.390E-01 2.870E-01 TE-132 1.520E-01 1.520E-01 1.520E-01 1.520E-01 1.520E-01 1.520E-01 1.780E-01 1.520E-01 I-130 1.970E-01 1.970E-01 1.970E-01 1.970E-01 1.970E-01 1.970E-01 2.390E-01 1.970E-01 Appendix C Ai Adult Shoreline Sediment - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX C Ai Adult Dose Factors for use in the Liquid Dose Calculations Agegroup: ADULT Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 6.160E-01 6.160E-01 6.160E-01 6.160E-01 6.160E-01 6.160E-01 7.480E-01 6.160E-01 I-132 4.460E-02 4.460E-02 4.460E-02 4.460E-02 4.460E-02 4.460E-02 5.240E-02 4.460E-02 I-133 8.770E-02 8.770E-02 8.770E-02 8.770E-02 8.770E-02 8.770E-02 1.070E-01 8.770E-02 I-134 1.600E-02 1.600E-02 1.600E-02 1.600E-02 1.600E-02 1.600E-02 1.900E-02 1.600E-02 I-135 9.040E-02 9.040E-02 9.040E-02 9.040E-02 9.040E-02 9.040E-02 1.050E-01 9.040E-02 CS-134 2.450E+02 2.450E+02 2.450E+02 2.450E+02 2.450E+02 2.450E+02 2.860E+02 2.450E+02 CS-136 5.400E+00 5.400E+00 5.400E+00 5.400E+00 5.400E+00 5.400E+00 6.120E+00 5.400E+00 CS-137 3.680E+02 3.680E+02 3.680E+02 3.680E+02 3.680E+02 3.680E+02 4.290E+02 3.680E+02 CS-138 1.280E-02 1.280E-02 1.280E-02 1.280E-02 1.280E-02 1.280E-02 1.470E-02 1.280E-02 BA-139 3.790E-03 3.790E-03 3.790E-03 3.790E-03 3.790E-03 3.790E-03 4.260E-03 3.790E-03 BA-140 7.350E-01 7.350E-01 7.350E-01 7.350E-01 7.350E-01 7.350E-01 8.400E-01 7.350E-01 BA-141 1.490E-03 1.490E-03 1.490E-03 1.490E-03 1.490E-03 1.490E-03 1.700E-03 1.490E-03 BA-142 1.610E-03 1.610E-03 1.610E-03 1.610E-03 1.610E-03 1.610E-03 1.830E-03 1.610E-03 LA-140 6.880E-01 6.880E-01 6.880E-01 6.880E-01 6.880E-01 6.880E-01 7.790E-01 6.880E-01 LA-142 2.720E-02 2.720E-02 2.720E-02 2.720E-02 2.720E-02 2.720E-02 3.260E-02 2.720E-02 CE-141 4.890E-01 4.890E-01 4.890E-01 4.890E-01 4.890E-01 4.890E-01 5.510E-01 4.890E-01 CE-143 8.270E-02 8.270E-02 8.270E-02 8.270E-02 8.270E-02 8.270E-02 9.400E-02 8.270E-02 CE-144 2.490E+00 2.490E+00 2.490E+00 2.490E+00 2.490E+00 2.490E+00 2.880E+00 2.490E+00 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 6.570E-05 6.570E-05 6.570E-05 6.570E-05 6.570E-05 6.570E-05 7.550E-05 6.570E-05 ND-147 3.000E-01 3.000E-01 3.000E-01 3.000E-01 3.000E-01 3.000E-01 3.600E-01 3.000E-01 W-187 8.420E-02 8.420E-02 8.420E-02 8.420E-02 8.420E-02 8.420E-02 9.780E-02 8.420E-02 NP-239 6.120E-02 6.120E-02 6.120E-02 6.120E-02 6.120E-02 6.120E-02 7.090E-02 6.120E-02 Appendix C Ai Adult Shoreline Sediment - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 6.160E+00 6.160E+00 6.160E+00 6.160E+00 6.160E+00 0.000E+00 6.160E+00 C-14 2.360E+02 4.720E+01 4.720E+01 4.720E+01 4.720E+01 4.720E+01 0.000E+00 4.720E+01 NA-24 7.690E+01 7.690E+01 7.690E+01 7.690E+01 7.690E+01 7.690E+01 0.000E+00 7.690E+01 P-32 1.570E+04 9.700E+02 0.000E+00 0.000E+00 0.000E+00 1.320E+03 0.000E+00 6.070E+02 CR-51 0.000E+00 0.000E+00 1.150E-01 4.530E-02 2.950E-01 3.470E+01 0.000E+00 2.070E-01 MN-54 0.000E+00 3.430E+02 0.000E+00 1.020E+02 0.000E+00 7.030E+02 0.000E+00 6.790E+01 MN-56 0.000E+00 3.640E-01 0.000E+00 4.610E-01 0.000E+00 2.400E+01 0.000E+00 6.480E-02 FE-55 2.200E+02 1.560E+02 0.000E+00 0.000E+00 9.880E+01 6.740E+01 0.000E+00 3.630E+01 FE-59 3.390E+02 7.900E+02 0.000E+00 0.000E+00 2.490E+02 1.870E+03 0.000E+00 3.050E+02 CO-58 0.000E+00 5.620E+01 0.000E+00 0.000E+00 0.000E+00 7.750E+02 0.000E+00 1.300E+02 CO-60 0.000E+00 1.630E+02 0.000E+00 0.000E+00 0.000E+00 2.130E+03 0.000E+00 3.680E+02 NI-63 1.030E+04 7.270E+02 0.000E+00 0.000E+00 0.000E+00 1.160E+02 0.000E+00 3.490E+02 NI-65 1.610E+00 2.050E-01 0.000E+00 0.000E+00 0.000E+00 1.110E+01 0.000E+00 9.350E-02 CU-64 0.000E+00 3.470E+00 0.000E+00 8.770E+00 0.000E+00 2.690E+02 0.000E+00 1.630E+00 ZN-65 3.340E+02 1.160E+03 0.000E+00 7.430E+02 0.000E+00 4.920E+02 0.000E+00 5.420E+02 ZN-69 1.070E-04 2.040E-04 0.000E+00 1.330E-04 0.000E+00 3.760E-04 0.000E+00 1.430E-05 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.030E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.500E-07 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.360E-77 RB-86 0.000E+00 1.700E+03 0.000E+00 0.000E+00 0.000E+00 2.520E+02 0.000E+00 7.990E+02 RB-88 0.000E+00 3.300E-12 0.000E+00 0.000E+00 0.000E+00 2.830E-19 0.000E+00 1.760E-12 RB-89 0.000E+00 2.960E-14 0.000E+00 0.000E+00 0.000E+00 4.540E-23 0.000E+00 2.090E-14 SR-89 2.540E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.030E+03 0.000E+00 7.280E+02 SR-90 4.830E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.350E+04 0.000E+00 1.190E+05 SR-91 1.950E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.850E+02 0.000E+00 7.760E+00 Appendix D Ai Teen Water - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 8.220E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.090E+02 0.000E+00 3.500E-01 Y-90 7.000E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.770E+03 0.000E+00 1.880E-02 Y-91 1.160E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.760E+03 0.000E+00 3.120E-01 Y-91M 3.330E-07 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.570E-05 0.000E+00 1.270E-08 Y-92 6.710E-03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.840E+02 0.000E+00 1.940E-04 Y-93 9.760E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.980E+03 0.000E+00 2.670E-03 ZR-95 2.380E+00 7.520E-01 0.000E+00 1.100E+00 0.000E+00 1.730E+03 0.000E+00 5.170E-01 ZR-97 8.420E-02 1.670E-02 0.000E+00 2.530E-02 0.000E+00 4.510E+03 0.000E+00 7.670E-03 NB-95 4.730E-01 2.630E-01 0.000E+00 2.540E-01 0.000E+00 1.120E+03 0.000E+00 1.440E-01 MO-99 0.000E+00 3.090E+02 0.000E+00 7.070E+02 0.000E+00 5.530E+02 0.000E+00 5.890E+01 TC-99M 4.840E-03 1.350E-02 0.000E+00 2.010E-01 7.500E-03 8.870E+00 0.000E+00 1.750E-01 TC-101 1.120E-17 1.590E-17 0.000E+00 2.880E-16 9.700E-18 2.720E-24 0.000E+00 1.560E-16 RU-103 1.470E+01 0.000E+00 0.000E+00 5.180E+01 0.000E+00 1.230E+03 0.000E+00 6.280E+00 RU-105 1.940E-01 0.000E+00 0.000E+00 2.450E+00 0.000E+00 1.570E+02 0.000E+00 7.540E-02 RU-106 2.280E+02 0.000E+00 0.000E+00 4.390E+02 0.000E+00 1.090E+04 0.000E+00 2.870E+01 AG-110M 1.190E+01 1.130E+01 0.000E+00 2.150E+01 0.000E+00 3.160E+03 0.000E+00 6.850E+00 TE-125M 2.210E+02 7.980E+01 6.180E+01 0.000E+00 0.000E+00 6.530E+02 0.000E+00 2.960E+01 TE-127 3.790E+00 1.340E+00 2.610E+00 1.530E+01 0.000E+00 2.930E+02 0.000E+00 8.150E-01 TE-127M 5.600E+02 1.990E+02 1.330E+02 2.270E+03 0.000E+00 1.400E+03 0.000E+00 6.660E+01 TE-129 1.920E-03 7.150E-04 1.370E-03 8.040E-03 0.000E+00 1.050E-02 0.000E+00 4.660E-04 TE-129M 9.380E+02 3.480E+02 3.030E+02 3.920E+03 0.000E+00 3.520E+03 0.000E+00 1.480E+02 TE-131 3.490E-09 1.440E-09 2.690E-09 1.520E-08 0.000E+00 2.860E-10 0.000E+00 1.090E-09 TE-131M 1.080E+02 5.150E+01 7.750E+01 5.380E+02 0.000E+00 4.140E+03 0.000E+00 4.300E+01 TE-132 1.820E+02 1.150E+02 1.220E+02 1.110E+03 0.000E+00 3.660E+03 0.000E+00 1.090E+02 I-130 3.050E+01 8.830E+01 7.200E+03 1.360E+02 0.000E+00 6.790E+01 0.000E+00 3.530E+01 Appendix D Ai Teen Water - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.260E+02 4.560E+02 1.330E+05 7.850E+02 0.000E+00 9.020E+01 0.000E+00 2.450E+02 I-132 4.360E-01 1.140E+00 3.850E+01 1.800E+00 0.000E+00 4.970E-01 0.000E+00 4.100E-01 I-133 7.830E+01 1.330E+02 1.860E+04 2.330E+02 0.000E+00 1.010E+02 0.000E+00 4.050E+01 I-134 6.330E-04 1.680E-03 2.800E-02 2.640E-03 0.000E+00 2.210E-05 0.000E+00 6.020E-04 I-135 1.010E+01 2.600E+01 1.670E+03 4.100E+01 0.000E+00 2.880E+01 0.000E+00 9.630E+00 CS-134 4.860E+03 1.140E+04 0.000E+00 3.640E+03 1.390E+03 1.420E+02 0.000E+00 5.310E+03 CS-136 4.860E+02 1.910E+03 0.000E+00 1.040E+03 1.640E+02 1.540E+02 0.000E+00 1.290E+03 CS-137 6.510E+03 8.660E+03 0.000E+00 2.950E+03 1.150E+03 1.230E+02 0.000E+00 3.020E+03 CS-138 8.300E-07 1.590E-06 0.000E+00 1.180E-06 1.370E-07 7.230E-10 0.000E+00 7.970E-07 BA-139 1.990E-02 1.400E-05 0.000E+00 1.320E-05 9.670E-06 1.780E-01 0.000E+00 5.810E-04 BA-140 1.610E+03 1.970E+00 0.000E+00 6.680E-01 1.320E+00 2.480E+03 0.000E+00 1.040E+02 BA-141 5.420E-12 4.050E-15 0.000E+00 3.760E-15 2.770E-15 1.150E-17 0.000E+00 1.810E-13 BA-142 6.170E-21 6.170E-24 0.000E+00 5.220E-24 4.100E-24 1.890E-32 0.000E+00 3.800E-22 LA-140 1.650E-01 8.090E-02 0.000E+00 0.000E+00 0.000E+00 4.640E+03 0.000E+00 2.150E-02 LA-142 5.590E-05 2.480E-05 0.000E+00 0.000E+00 0.000E+00 7.550E-01 0.000E+00 6.180E-06 CE-141 7.650E-01 5.110E-01 0.000E+00 2.400E-01 0.000E+00 1.460E+03 0.000E+00 5.870E-02 CE-143 1.060E-01 7.730E+01 0.000E+00 3.460E-02 0.000E+00 2.320E+03 0.000E+00 8.630E-03 CE-144 4.040E+01 1.670E+01 0.000E+00 9.990E+00 0.000E+00 1.020E+04 0.000E+00 2.170E+00 PR-143 7.420E-01 2.960E-01 0.000E+00 1.720E-01 0.000E+00 2.440E+03 0.000E+00 3.700E-02 PR-144 7.330E-16 3.000E-16 0.000E+00 1.720E-16 0.000E+00 8.080E-19 0.000E+00 3.720E-17 ND-147 5.280E-01 5.750E-01 0.000E+00 3.370E-01 0.000E+00 2.070E+03 0.000E+00 3.440E-02 W-187 5.990E+00 4.880E+00 0.000E+00 0.000E+00 0.000E+00 1.320E+03 0.000E+00 1.710E+00 NP-239 8.830E-02 8.330E-03 0.000E+00 2.610E-02 0.000E+00 1.340E+03 0.000E+00 4.630E-03 Appendix D Ai Teen Water - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Dose Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.740E-01 1.740E-01 1.740E-01 1.740E-01 1.740E-01 0.000E+00 1.740E-01 C-14 3.410E+04 6.810E+03 6.810E+03 6.810E+03 6.810E+03 6.810E+03 0.000E+00 6.810E+03 NA-24 1.390E+02 1.390E+02 1.390E+02 1.390E+02 1.390E+02 1.390E+02 0.000E+00 1.390E+02 P-32 1.440E+06 8.910E+04 0.000E+00 0.000E+00 0.000E+00 1.210E+05 0.000E+00 5.580E+04 CR-51 0.000E+00 0.000E+00 7.120E-01 2.810E-01 1.830E+00 2.150E+02 0.000E+00 1.280E+00 MN-54 0.000E+00 4.300E+03 0.000E+00 1.280E+03 0.000E+00 8.810E+03 0.000E+00 8.520E+02 MN-56 0.000E+00 1.810E-01 0.000E+00 2.300E-01 0.000E+00 1.190E+01 0.000E+00 3.230E-02 FE-55 6.890E+02 4.880E+02 0.000E+00 0.000E+00 3.100E+02 2.110E+02 0.000E+00 1.140E+02 FE-59 1.050E+03 2.460E+03 0.000E+00 0.000E+00 7.760E+02 5.820E+03 0.000E+00 9.500E+02 CO-58 0.000E+00 8.780E+01 0.000E+00 0.000E+00 0.000E+00 1.210E+03 0.000E+00 2.020E+02 CO-60 0.000E+00 2.560E+02 0.000E+00 0.000E+00 0.000E+00 3.340E+03 0.000E+00 5.770E+02 NI-63 3.230E+04 2.280E+03 0.000E+00 0.000E+00 0.000E+00 3.630E+02 0.000E+00 1.090E+03 NI-65 1.860E-01 2.370E-02 0.000E+00 0.000E+00 0.000E+00 1.290E+00 0.000E+00 1.080E-02 CU-64 0.000E+00 2.820E+00 0.000E+00 7.140E+00 0.000E+00 2.190E+02 0.000E+00 1.330E+00 ZN-65 2.100E+04 7.280E+04 0.000E+00 4.660E+04 0.000E+00 3.080E+04 0.000E+00 3.390E+04 ZN-69 8.410E-07 1.600E-06 0.000E+00 1.050E-06 0.000E+00 2.950E-06 0.000E+00 1.120E-07 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.160E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.320E-12 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 1.050E+05 0.000E+00 0.000E+00 0.000E+00 1.550E+04 0.000E+00 4.920E+04 RB-88 0.000E+00 1.380E-22 0.000E+00 0.000E+00 0.000E+00 1.180E-29 0.000E+00 7.360E-23 RB-89 0.000E+00 1.720E-26 0.000E+00 0.000E+00 0.000E+00 2.630E-35 0.000E+00 1.220E-26 SR-89 2.370E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.830E+03 0.000E+00 6.800E+02 SR-90 4.540E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.270E+04 0.000E+00 1.120E+05 SR-91 7.640E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.470E+02 0.000E+00 3.040E+00 Appendix D Ai Teen Fish - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Dose Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 3.590E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.130E+00 0.000E+00 1.530E-02 Y-90 4.820E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.980E+03 0.000E+00 1.300E-02 Y-91 9.060E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.710E+03 0.000E+00 2.430E-01 Y-91M 1.160E-11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.470E-10 0.000E+00 4.430E-13 Y-92 5.020E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.380E+01 0.000E+00 1.450E-05 Y-93 3.350E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.020E+03 0.000E+00 9.190E-04 ZR-95 2.450E-01 7.740E-02 0.000E+00 1.140E-01 0.000E+00 1.790E+02 0.000E+00 5.320E-02 ZR-97 5.330E-03 1.050E-03 0.000E+00 1.600E-03 0.000E+00 2.850E+02 0.000E+00 4.860E-04 NB-95 4.410E+02 2.450E+02 0.000E+00 2.370E+02 0.000E+00 1.050E+06 0.000E+00 1.350E+02 MO-99 0.000E+00 8.550E+01 0.000E+00 1.960E+02 0.000E+00 1.530E+02 0.000E+00 1.630E+01 TC-99M 5.720E-04 1.600E-03 0.000E+00 2.380E-02 8.860E-04 1.050E+00 0.000E+00 2.070E-02 TC-101 2.820E-33 4.010E-33 0.000E+00 7.240E-32 2.440E-33 6.840E-40 0.000E+00 3.930E-32 RU-103 4.570E+00 0.000E+00 0.000E+00 1.610E+01 0.000E+00 3.820E+02 0.000E+00 1.950E+00 RU-105 9.350E-03 0.000E+00 0.000E+00 1.180E-01 0.000E+00 7.550E+00 0.000E+00 3.630E-03 RU-106 7.140E+01 0.000E+00 0.000E+00 1.380E+02 0.000E+00 3.420E+03 0.000E+00 8.990E+00 AG-110M 8.580E-01 8.120E-01 0.000E+00 1.550E+00 0.000E+00 2.280E+02 0.000E+00 4.940E-01 TE-125M 2.760E+03 9.950E+02 7.710E+02 0.000E+00 0.000E+00 8.150E+03 0.000E+00 3.690E+02 TE-127 1.960E+01 6.950E+00 1.350E+01 7.940E+01 0.000E+00 1.510E+03 0.000E+00 4.220E+00 TE-127M 7.010E+03 2.490E+03 1.670E+03 2.840E+04 0.000E+00 1.750E+04 0.000E+00 8.340E+02 TE-129 1.770E-05 6.600E-06 1.260E-05 7.430E-05 0.000E+00 9.680E-05 0.000E+00 4.310E-06 TE-129M 1.160E+04 4.320E+03 3.760E+03 4.870E+04 0.000E+00 4.370E+04 0.000E+00 1.840E+03 TE-131 9.400E-17 3.870E-17 7.240E-17 4.110E-16 0.000E+00 7.710E-18 0.000E+00 2.940E-17 TE-131M 1.020E+03 4.900E+02 7.370E+02 5.110E+03 0.000E+00 3.930E+04 0.000E+00 4.090E+02 TE-132 2.060E+03 1.300E+03 1.370E+03 1.250E+04 0.000E+00 4.130E+04 0.000E+00 1.230E+03 I-130 7.320E+00 2.120E+01 1.730E+03 3.260E+01 0.000E+00 1.630E+01 0.000E+00 8.460E+00 Appendix D Ai Teen Fish - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Dose Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.470E+02 2.060E+02 6.000E+04 3.540E+02 0.000E+00 4.070E+01 0.000E+00 1.100E+02 I-132 5.520E-03 1.440E-02 4.870E-01 2.280E-02 0.000E+00 6.290E-03 0.000E+00 5.180E-03 I-133 2.470E+01 4.190E+01 5.850E+03 7.350E+01 0.000E+00 3.170E+01 0.000E+00 1.280E+01 I-134 2.220E-08 5.890E-08 9.810E-07 9.280E-08 0.000E+00 7.760E-10 0.000E+00 2.110E-08 I-135 1.350E+00 3.480E+00 2.240E+02 5.490E+00 0.000E+00 3.850E+00 0.000E+00 1.290E+00 CS-134 3.050E+05 7.180E+05 0.000E+00 2.280E+05 8.710E+04 8.930E+03 0.000E+00 3.330E+05 CS-136 2.970E+04 1.170E+05 0.000E+00 6.370E+04 1.000E+04 9.410E+03 0.000E+00 7.860E+04 CS-137 4.090E+05 5.440E+05 0.000E+00 1.850E+05 7.190E+04 7.730E+03 0.000E+00 1.890E+05 CS-138 9.580E-12 1.840E-11 0.000E+00 1.360E-11 1.580E-12 8.340E-15 0.000E+00 9.190E-12 BA-139 6.170E-06 4.340E-09 0.000E+00 4.090E-09 2.990E-09 5.510E-05 0.000E+00 1.800E-07 BA-140 1.960E+02 2.410E-01 0.000E+00 8.160E-02 1.620E-01 3.030E+02 0.000E+00 1.260E+01 BA-141 9.450E-25 7.050E-28 0.000E+00 6.550E-28 4.830E-28 2.010E-30 0.000E+00 3.150E-26 BA-142 2.750E-42 2.750E-45 0.000E+00 2.320E-45 1.830E-45 8.430E-54 0.000E+00 1.690E-43 LA-140 1.050E-01 5.160E-02 0.000E+00 0.000E+00 0.000E+00 2.960E+03 0.000E+00 1.370E-02 LA-142 2.350E-07 1.040E-07 0.000E+00 0.000E+00 0.000E+00 3.180E-03 0.000E+00 2.600E-08 CE-141 2.370E-02 1.590E-02 0.000E+00 7.460E-03 0.000E+00 4.540E+01 0.000E+00 1.820E-03 CE-143 2.590E-03 1.880E+00 0.000E+00 8.450E-04 0.000E+00 5.660E+01 0.000E+00 2.100E-04 CE-144 1.270E+00 5.240E-01 0.000E+00 3.130E-01 0.000E+00 3.180E+02 0.000E+00 6.810E-02 PR-143 5.680E-01 2.270E-01 0.000E+00 1.320E-01 0.000E+00 1.870E+03 0.000E+00 2.830E-02 PR-144 1.690E-28 6.900E-29 0.000E+00 3.960E-29 0.000E+00 1.860E-31 0.000E+00 8.550E-30 ND-147 4.020E-01 4.370E-01 0.000E+00 2.560E-01 0.000E+00 1.580E+03 0.000E+00 2.620E-02 W-187 1.590E+02 1.300E+02 0.000E+00 0.000E+00 0.000E+00 3.510E+04 0.000E+00 4.540E+01 NP-239 2.390E-02 2.260E-03 0.000E+00 7.080E-03 0.000E+00 3.630E+02 0.000E+00 1.250E-03 Appendix D Ai Teen Fish - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Dose Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 2.390E+00 2.390E+00 2.390E+00 2.390E+00 2.390E+00 2.390E+00 2.770E+00 2.390E+00 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 9.310E-01 9.310E-01 9.310E-01 9.310E-01 9.310E-01 9.310E-01 1.100E+00 9.310E-01 MN-54 2.770E+02 2.770E+02 2.770E+02 2.770E+02 2.770E+02 2.770E+02 3.250E+02 2.770E+02 MN-56 1.800E-01 1.800E-01 1.800E-01 1.800E-01 1.800E-01 1.800E-01 2.130E-01 1.800E-01 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 5.450E+01 5.450E+01 5.450E+01 5.450E+01 5.450E+01 5.450E+01 6.410E+01 5.450E+01 CO-58 7.570E+01 7.570E+01 7.570E+01 7.570E+01 7.570E+01 7.570E+01 8.870E+01 7.570E+01 CO-60 4.300E+03 4.300E+03 4.300E+03 4.300E+03 4.300E+03 4.300E+03 5.050E+03 4.300E+03 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 5.930E-02 5.930E-02 5.930E-02 5.930E-02 5.930E-02 5.930E-02 6.900E-02 5.930E-02 CU-64 1.210E-01 1.210E-01 1.210E-01 1.210E-01 1.210E-01 1.210E-01 1.370E-01 1.210E-01 ZN-65 1.490E+02 1.490E+02 1.490E+02 1.490E+02 1.490E+02 1.490E+02 1.720E+02 1.490E+02 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 9.730E-04 9.730E-04 9.730E-04 9.730E-04 9.730E-04 9.730E-04 1.410E-03 9.730E-04 BR-84 4.050E-02 4.050E-02 4.050E-02 4.050E-02 4.050E-02 4.050E-02 4.720E-02 4.050E-02 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 1.800E+00 1.800E+00 1.800E+00 1.800E+00 1.800E+00 1.800E+00 2.050E+00 1.800E+00 RB-88 6.610E-03 6.610E-03 6.610E-03 6.610E-03 6.610E-03 6.610E-03 7.550E-03 6.610E-03 RB-89 2.460E-02 2.460E-02 2.460E-02 2.460E-02 2.460E-02 2.460E-02 2.950E-02 2.460E-02 SR-89 4.320E-03 4.320E-03 4.320E-03 4.320E-03 4.320E-03 4.320E-03 5.020E-03 4.320E-03 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 4.290E-01 4.290E-01 4.290E-01 4.290E-01 4.290E-01 4.290E-01 5.020E-01 4.290E-01 Appendix D Ai Teen Shoreline Sediment - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Dose Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.550E-01 1.550E-01 1.550E-01 1.550E-01 1.550E-01 1.550E-01 1.720E-01 1.550E-01 Y-90 8.970E-04 8.970E-04 8.970E-04 8.970E-04 8.970E-04 8.970E-04 1.060E-03 8.970E-04 Y-91 2.140E-01 2.140E-01 2.140E-01 2.140E-01 2.140E-01 2.140E-01 2.410E-01 2.140E-01 Y-91M 2.000E-02 2.000E-02 2.000E-02 2.000E-02 2.000E-02 2.000E-02 2.320E-02 2.000E-02 Y-92 3.600E-02 3.600E-02 3.600E-02 3.600E-02 3.600E-02 3.600E-02 4.280E-02 3.600E-02 Y-93 3.660E-02 3.660E-02 3.660E-02 3.660E-02 3.660E-02 3.660E-02 5.010E-02 3.660E-02 ZR-95 4.890E+01 4.890E+01 4.890E+01 4.890E+01 4.890E+01 4.890E+01 5.670E+01 4.890E+01 ZR-97 5.910E-01 5.910E-01 5.910E-01 5.910E-01 5.910E-01 5.910E-01 6.880E-01 5.910E-01 NB-95 2.730E+01 2.730E+01 2.730E+01 2.730E+01 2.730E+01 2.730E+01 3.210E+01 2.730E+01 MO-99 7.980E-01 7.980E-01 7.980E-01 7.980E-01 7.980E-01 7.980E-01 9.240E-01 7.980E-01 TC-99M 3.680E-02 3.680E-02 3.680E-02 3.680E-02 3.680E-02 3.680E-02 4.210E-02 3.680E-02 TC-101 4.070E-03 4.070E-03 4.070E-03 4.070E-03 4.070E-03 4.070E-03 4.520E-03 4.070E-03 RU-103 2.160E+01 2.160E+01 2.160E+01 2.160E+01 2.160E+01 2.160E+01 2.520E+01 2.160E+01 RU-105 1.270E-01 1.270E-01 1.270E-01 1.270E-01 1.270E-01 1.270E-01 1.440E-01 1.270E-01 RU-106 8.430E+01 8.430E+01 8.430E+01 8.430E+01 8.430E+01 8.430E+01 1.010E+02 8.430E+01 AG-110M 6.870E+02 6.870E+02 6.870E+02 6.870E+02 6.870E+02 6.870E+02 8.010E+02 6.870E+02 TE-125M 3.100E-01 3.100E-01 3.100E-01 3.100E-01 3.100E-01 3.100E-01 4.250E-01 3.100E-01 TE-127 5.950E-04 5.950E-04 5.950E-04 5.950E-04 5.950E-04 5.950E-04 6.540E-04 5.950E-04 TE-127M 1.830E-02 1.830E-02 1.830E-02 1.830E-02 1.830E-02 1.830E-02 2.160E-02 1.830E-02 TE-129 5.240E-03 5.240E-03 5.240E-03 5.240E-03 5.240E-03 5.240E-03 6.200E-03 5.240E-03 TE-129M 3.950E+00 3.950E+00 3.950E+00 3.950E+00 3.950E+00 3.950E+00 4.620E+00 3.950E+00 TE-131 5.830E-03 5.830E-03 5.830E-03 5.830E-03 5.830E-03 5.830E-03 6.890E+00 5.830E-03 TE-131M 1.600E+00 1.600E+00 1.600E+00 1.600E+00 1.600E+00 1.600E+00 1.890E+00 1.600E+00 TE-132 8.460E-01 8.460E-01 8.460E-01 8.460E-01 8.460E-01 8.460E-01 9.950E-01 8.460E-01 I-130 1.100E+00 1.100E+00 1.100E+00 1.100E+00 1.100E+00 1.100E+00 1.340E+00 1.100E+00 Appendix D Ai Teen Shoreline Sediment - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX D Ai Teen Dose Factors for use in the Liquid Dose Calculations Agegroup: TEEN Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.440E+00 3.440E+00 3.440E+00 3.440E+00 3.440E+00 3.440E+00 4.170E+00 3.440E+00 I-132 2.490E-01 2.490E-01 2.490E-01 2.490E-01 2.490E-01 2.490E-01 2.930E-01 2.490E-01 I-133 4.900E-01 4.900E-01 4.900E-01 4.900E-01 4.900E-01 4.900E-01 5.960E-01 4.900E-01 I-134 8.930E-02 8.930E-02 8.930E-02 8.930E-02 8.930E-02 8.930E-02 1.060E-01 8.930E-02 I-135 5.050E-01 5.050E-01 5.050E-01 5.050E-01 5.050E-01 5.050E-01 5.890E-01 5.050E-01 CS-134 1.370E+03 1.370E+03 1.370E+03 1.370E+03 1.370E+03 1.370E+03 1.600E+03 1.370E+03 CS-136 3.010E+01 3.010E+01 3.010E+01 3.010E+01 3.010E+01 3.010E+01 3.420E+01 3.010E+01 CS-137 2.050E+03 2.050E+03 2.050E+03 2.050E+03 2.050E+03 2.050E+03 2.400E+03 2.050E+03 CS-138 7.170E-02 7.170E-02 7.170E-02 7.170E-02 7.170E-02 7.170E-02 8.200E-02 7.170E-02 BA-139 2.120E-02 2.120E-02 2.120E-02 2.120E-02 2.120E-02 2.120E-02 2.380E-02 2.120E-02 BA-140 4.100E+00 4.100E+00 4.100E+00 4.100E+00 4.100E+00 4.100E+00 4.690E+00 4.100E+00 BA-141 8.330E-03 8.330E-03 8.330E-03 8.330E-03 8.330E-03 8.330E-03 9.490E-03 8.330E-03 BA-142 8.970E-03 8.970E-03 8.970E-03 8.970E-03 8.970E-03 8.970E-03 1.020E-02 8.970E-03 LA-140 3.840E+00 3.840E+00 3.840E+00 3.840E+00 3.840E+00 3.840E+00 4.350E+00 3.840E+00 LA-142 1.520E-01 1.520E-01 1.520E-01 1.520E-01 1.520E-01 1.520E-01 1.820E-01 1.520E-01 CE-141 2.730E+00 2.730E+00 2.730E+00 2.730E+00 2.730E+00 2.730E+00 3.080E+00 2.730E+00 CE-143 4.620E-01 4.620E-01 4.620E-01 4.620E-01 4.620E-01 4.620E-01 5.250E-01 4.620E-01 CE-144 1.390E+01 1.390E+01 1.390E+01 1.390E+01 1.390E+01 1.390E+01 1.610E+01 1.390E+01 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 3.670E-04 3.670E-04 3.670E-04 3.670E-04 3.670E-04 3.670E-04 4.220E-04 3.670E-04 ND-147 1.680E+00 1.680E+00 1.680E+00 1.680E+00 1.680E+00 1.680E+00 2.010E+00 1.680E+00 W-187 4.700E-01 4.700E-01 4.700E-01 4.700E-01 4.700E-01 4.700E-01 5.460E-01 4.700E-01 NP-239 3.420E-01 3.420E-01 3.420E-01 3.420E-01 3.420E-01 3.420E-01 3.960E-01 3.420E-01 Appendix D Ai Teen Shoreline Sediment - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.180E+01 1.180E+01 1.180E+01 1.180E+01 1.180E+01 0.000E+00 1.180E+01 C-14 7.030E+02 1.410E+02 1.410E+02 1.410E+02 1.410E+02 1.410E+02 0.000E+00 1.410E+02 NA-24 1.940E+02 1.940E+02 1.940E+02 1.940E+02 1.940E+02 1.940E+02 0.000E+00 1.940E+02 P-32 4.680E+04 2.190E+03 0.000E+00 0.000E+00 0.000E+00 1.290E+03 0.000E+00 1.800E+03 CR-51 0.000E+00 0.000E+00 2.840E-01 7.750E-02 5.180E-01 2.710E+01 0.000E+00 5.110E-01 MN-54 0.000E+00 6.210E+02 0.000E+00 1.740E+02 0.000E+00 5.220E+02 0.000E+00 1.660E+02 MN-56 0.000E+00 7.700E-01 0.000E+00 9.320E-01 0.000E+00 1.120E+02 0.000E+00 1.740E-01 FE-55 6.680E+02 3.550E+02 0.000E+00 0.000E+00 2.010E+02 6.570E+01 0.000E+00 1.100E+02 FE-59 9.520E+02 1.540E+03 0.000E+00 0.000E+00 4.470E+02 1.600E+03 0.000E+00 7.670E+02 CO-58 0.000E+00 1.040E+02 0.000E+00 0.000E+00 0.000E+00 6.070E+02 0.000E+00 3.190E+02 CO-60 0.000E+00 3.080E+02 0.000E+00 0.000E+00 0.000E+00 1.700E+03 0.000E+00 9.070E+02 NI-63 3.130E+04 1.670E+03 0.000E+00 0.000E+00 0.000E+00 1.130E+02 0.000E+00 1.060E+03 NI-65 4.760E+00 4.480E-01 0.000E+00 0.000E+00 0.000E+00 5.490E+01 0.000E+00 2.610E-01 CU-64 0.000E+00 7.390E+00 0.000E+00 1.780E+01 0.000E+00 3.470E+02 0.000E+00 4.460E+00 ZN-65 7.950E+02 2.120E+03 0.000E+00 1.340E+03 0.000E+00 3.720E+02 0.000E+00 1.320E+03 ZN-69 3.190E-04 4.610E-04 0.000E+00 2.800E-04 0.000E+00 2.900E-02 0.000E+00 4.260E-05 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.060E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.780E-06 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.300E-76 RB-86 0.000E+00 3.820E+03 0.000E+00 0.000E+00 0.000E+00 2.460E+02 0.000E+00 2.350E+03 RB-88 0.000E+00 7.360E-12 0.000E+00 0.000E+00 0.000E+00 3.610E-13 0.000E+00 5.110E-12 RB-89 0.000E+00 6.300E-14 0.000E+00 0.000E+00 0.000E+00 5.490E-16 0.000E+00 5.600E-14 SR-89 7.620E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.950E+03 0.000E+00 2.180E+03 SR-90 9.880E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.330E+04 0.000E+00 2.510E+05 SR-91 5.810E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.280E+03 0.000E+00 2.190E+01 Appendix E Ai Child Water - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 2.430E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.610E+02 0.000E+00 9.760E-01 Y-90 2.100E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.980E+03 0.000E+00 5.620E-02 Y-91 3.480E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.640E+03 0.000E+00 9.310E-01 Y-91M 9.860E-07 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.930E-03 0.000E+00 3.590E-08 Y-92 2.000E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.770E+02 0.000E+00 5.710E-04 Y-93 2.900E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.330E+03 0.000E+00 7.970E-03 ZR-95 6.710E+00 1.470E+00 0.000E+00 2.110E+00 0.000E+00 1.540E+03 0.000E+00 1.310E+00 ZR-97 2.480E-01 3.590E-02 0.000E+00 5.150E-02 0.000E+00 5.440E+03 0.000E+00 2.120E-02 NB-95 1.300E+00 5.040E-01 0.000E+00 4.740E-01 0.000E+00 9.330E+02 0.000E+00 3.600E-01 MO-99 0.000E+00 6.820E+02 0.000E+00 1.460E+03 0.000E+00 5.640E+02 0.000E+00 1.690E+02 TC-99M 1.350E-02 2.640E-02 0.000E+00 3.840E-01 1.340E-02 1.500E+01 0.000E+00 4.380E-01 TC-101 3.330E-17 3.480E-17 0.000E+00 5.940E-16 1.840E-17 1.110E-16 0.000E+00 4.410E-16 RU-103 4.210E+01 0.000E+00 0.000E+00 1.060E+02 0.000E+00 1.090E+03 0.000E+00 1.620E+01 RU-105 5.750E-01 0.000E+00 0.000E+00 5.060E+00 0.000E+00 3.750E+02 0.000E+00 2.090E-01 RU-106 6.800E+02 0.000E+00 0.000E+00 9.180E+02 0.000E+00 1.060E+04 0.000E+00 8.480E+01 AG-110M 3.130E+01 2.110E+01 0.000E+00 3.940E+01 0.000E+00 2.510E+03 0.000E+00 1.690E+01 TE-125M 6.590E+02 1.790E+02 1.850E+02 0.000E+00 0.000E+00 6.360E+02 0.000E+00 8.780E+01 TE-127 1.130E+01 3.050E+00 7.820E+00 3.210E+01 0.000E+00 4.410E+02 0.000E+00 2.420E+00 TE-127M 1.670E+03 4.510E+02 4.000E+02 4.780E+03 0.000E+00 1.360E+03 0.000E+00 1.990E+02 TE-129 5.730E-03 1.600E-03 4.090E-03 1.680E-02 0.000E+00 3.570E-01 0.000E+00 1.360E-03 TE-129M 2.800E+03 7.830E+02 9.030E+02 8.230E+03 0.000E+00 3.420E+03 0.000E+00 4.350E+02 TE-131 1.040E-08 3.160E-09 7.930E-09 3.140E-08 0.000E+00 5.450E-08 0.000E+00 3.090E-09 TE-131M 3.170E+02 1.100E+02 2.260E+02 1.060E+03 0.000E+00 4.450E+03 0.000E+00 1.170E+02 TE-132 5.280E+02 2.340E+02 3.400E+02 2.170E+03 0.000E+00 2.350E+03 0.000E+00 2.820E+02 I-130 8.650E+01 1.750E+02 1.930E+04 2.610E+02 0.000E+00 8.180E+01 0.000E+00 9.010E+01 Appendix E Ai Child Water - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 9.580E+02 9.630E+02 3.190E+05 1.580E+03 0.000E+00 8.580E+01 0.000E+00 5.470E+02 I-132 1.250E+00 2.300E+00 1.070E+02 3.520E+00 0.000E+00 2.710E+00 0.000E+00 1.060E+00 I-133 2.310E+02 2.850E+02 5.300E+04 4.750E+02 0.000E+00 1.150E+02 0.000E+00 1.080E+02 I-134 1.820E-03 3.370E-03 7.760E-02 5.160E-03 0.000E+00 2.240E-03 0.000E+00 1.550E-03 I-135 2.890E+01 5.210E+01 4.610E+03 7.990E+01 0.000E+00 3.970E+01 0.000E+00 2.460E+01 CS-134 1.360E+04 2.230E+04 0.000E+00 6.920E+03 2.480E+03 1.200E+02 0.000E+00 4.710E+03 CS-136 1.330E+03 3.660E+03 0.000E+00 1.950E+03 2.910E+02 1.290E+02 0.000E+00 2.370E+03 CS-137 1.900E+04 1.820E+04 0.000E+00 5.930E+03 2.130E+03 1.140E+02 0.000E+00 2.690E+03 CS-138 2.440E-06 3.390E-06 0.000E+00 2.380E-06 2.570E-07 1.560E-06 0.000E+00 2.150E-06 BA-139 5.940E-02 3.170E-05 0.000E+00 2.770E-05 1.860E-05 3.430E+00 0.000E+00 1.720E-03 BA-140 4.700E+03 4.120E+00 0.000E+00 1.340E+00 2.460E+00 2.380E+03 0.000E+00 2.740E+02 BA-141 1.620E-11 9.050E-15 0.000E+00 7.830E-15 5.310E-14 9.210E-12 0.000E+00 5.260E-13 BA-142 1.800E-20 1.300E-23 0.000E+00 1.050E-23 7.630E-24 2.350E-22 0.000E+00 1.010E-21 LA-140 4.780E-01 1.670E-01 0.000E+00 0.000E+00 0.000E+00 4.650E+03 0.000E+00 5.630E-02 LA-142 1.640E-04 5.210E-05 0.000E+00 0.000E+00 0.000E+00 1.030E+01 0.000E+00 1.630E-05 CE-141 2.280E+00 1.140E+00 0.000E+00 4.990E-01 0.000E+00 1.420E+03 0.000E+00 1.690E-01 CE-143 3.160E-01 1.710E+02 0.000E+00 7.180E-02 0.000E+00 2.510E+03 0.000E+00 2.480E-02 CE-144 1.210E+02 3.790E+01 0.000E+00 2.100E+01 0.000E+00 9.870E+03 0.000E+00 6.450E+00 PR-143 2.230E+00 6.690E-01 0.000E+00 3.620E-01 0.000E+00 2.400E+03 0.000E+00 1.110E-01 PR-144 2.200E-15 6.800E-16 0.000E+00 3.600E-16 0.000E+00 1.460E-12 0.000E+00 1.110E-16 ND-147 1.570E+00 1.270E+00 0.000E+00 6.990E-01 0.000E+00 2.020E+03 0.000E+00 9.860E-02 W-187 1.760E+01 1.040E+01 0.000E+00 0.000E+00 0.000E+00 1.460E+03 0.000E+00 4.680E+00 NP-239 2.630E-01 1.890E-02 0.000E+00 5.470E-02 0.000E+00 1.400E+03 0.000E+00 1.330E-02 Appendix E Ai Child Water - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.440E-01 1.440E-01 1.440E-01 1.440E-01 1.440E-01 0.000E+00 1.440E-01 C-14 4.380E+04 8.760E+03 8.760E+03 8.760E+03 8.760E+03 8.760E+03 0.000E+00 8.760E+03 NA-24 1.510E+02 1.510E+02 1.510E+02 1.510E+02 1.510E+02 1.510E+02 0.000E+00 1.510E+02 P-32 1.850E+06 8.680E+04 0.000E+00 0.000E+00 0.000E+00 5.130E+04 0.000E+00 7.150E+04 CR-51 0.000E+00 0.000E+00 7.580E-01 2.070E-01 1.380E+00 7.240E+01 0.000E+00 1.370E+00 MN-54 0.000E+00 3.360E+03 0.000E+00 9.420E+02 0.000E+00 2.820E+03 0.000E+00 8.950E+02 MN-56 0.000E+00 1.650E-01 0.000E+00 2.000E-01 0.000E+00 2.400E+01 0.000E+00 3.730E-02 FE-55 9.040E+02 4.790E+02 0.000E+00 0.000E+00 2.710E+02 8.880E+01 0.000E+00 1.490E+02 FE-59 1.280E+03 2.070E+03 0.000E+00 0.000E+00 5.990E+02 2.150E+03 0.000E+00 1.030E+03 CO-58 0.000E+00 7.010E+01 0.000E+00 0.000E+00 0.000E+00 4.090E+02 0.000E+00 2.150E+02 CO-60 0.000E+00 2.080E+02 0.000E+00 0.000E+00 0.000E+00 1.150E+03 0.000E+00 6.130E+02 NI-63 4.230E+04 2.270E+03 0.000E+00 0.000E+00 0.000E+00 1.530E+02 0.000E+00 1.440E+03 NI-65 2.370E-01 2.230E-02 0.000E+00 0.000E+00 0.000E+00 2.740E+00 0.000E+00 1.300E-02 CU-64 0.000E+00 2.590E+00 0.000E+00 6.260E+00 0.000E+00 1.220E+02 0.000E+00 1.570E+00 ZN-65 2.150E+04 5.730E+04 0.000E+00 3.610E+04 0.000E+00 1.010E+04 0.000E+00 3.560E+04 ZN-69 1.080E-06 1.560E-06 0.000E+00 9.470E-07 0.000E+00 9.840E-05 0.000E+00 1.440E-07 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.340E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.570E-12 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 1.020E+05 0.000E+00 0.000E+00 0.000E+00 6.530E+03 0.000E+00 6.250E+04 RB-88 0.000E+00 1.330E-22 0.000E+00 0.000E+00 0.000E+00 6.510E-24 0.000E+00 9.220E-23 RB-89 0.000E+00 1.580E-26 0.000E+00 0.000E+00 0.000E+00 1.370E-28 0.000E+00 1.400E-26 SR-89 3.070E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.190E+03 0.000E+00 8.780E+02 SR-90 4.010E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.400E+03 0.000E+00 1.020E+05 SR-91 9.800E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.160E+02 0.000E+00 3.700E+00 Appendix E Ai Child Fish - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 4.580E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.670E+00 0.000E+00 1.840E-02 Y-90 6.240E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.780E+03 0.000E+00 1.670E-02 Y-91 1.170E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.560E+03 0.000E+00 3.130E-01 Y-91M 1.480E-11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.900E-08 0.000E+00 5.390E-13 Y-92 6.440E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.860E+01 0.000E+00 1.840E-05 Y-93 4.300E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.420E+02 0.000E+00 1.180E-03 ZR-95 2.980E-01 6.550E-02 0.000E+00 9.370E-02 0.000E+00 6.830E+01 0.000E+00 5.830E-02 ZR-97 6.780E-03 9.790E-04 0.000E+00 1.410E-03 0.000E+00 1.480E+02 0.000E+00 5.780E-04 NB-95 5.210E+02 2.030E+02 0.000E+00 1.900E+02 0.000E+00 3.750E+05 0.000E+00 1.450E+02 MO-99 0.000E+00 8.130E+01 0.000E+00 1.740E+02 0.000E+00 6.720E+01 0.000E+00 2.010E+01 TC-99M 6.860E-04 1.350E-03 0.000E+00 1.950E-02 6.830E-04 7.650E-01 0.000E+00 2.230E-02 TC-101 3.610E-33 3.780E-33 0.000E+00 6.440E-32 2.000E-33 1.200E-32 0.000E+00 4.790E-32 RU-103 5.650E+00 0.000E+00 0.000E+00 1.420E+01 0.000E+00 1.460E+02 0.000E+00 2.170E+00 RU-105 1.190E-02 0.000E+00 0.000E+00 1.050E-01 0.000E+00 7.790E+00 0.000E+00 4.330E-03 RU-106 9.190E+01 0.000E+00 0.000E+00 1.240E+02 0.000E+00 1.430E+03 0.000E+00 1.150E+01 AG-110M 9.720E-01 6.570E-01 0.000E+00 1.220E+00 0.000E+00 7.810E+01 0.000E+00 5.250E-01 TE-125M 3.540E+03 9.610E+02 9.950E+02 0.000E+00 0.000E+00 3.420E+03 0.000E+00 4.730E+02 TE-127 2.520E+01 6.800E+00 1.750E+01 7.170E+01 0.000E+00 9.850E+02 0.000E+00 5.410E+00 TE-127M 9.040E+03 2.430E+03 2.160E+03 2.580E+04 0.000E+00 7.320E+03 0.000E+00 1.070E+03 TE-129 2.280E-05 6.370E-06 1.630E-05 6.680E-05 0.000E+00 1.420E-03 0.000E+00 5.420E-06 TE-129M 1.500E+04 4.190E+03 4.840E+03 4.410E+04 0.000E+00 1.830E+04 0.000E+00 2.330E+03 TE-131 1.210E-16 3.680E-17 9.220E-17 3.650E-16 0.000E+00 6.330E-16 0.000E+00 3.590E-17 TE-131M 1.300E+03 4.500E+02 9.250E+02 4.350E+03 0.000E+00 1.820E+04 0.000E+00 4.790E+02 TE-132 2.570E+03 1.140E+03 1.650E+03 1.050E+04 0.000E+00 1.140E+04 0.000E+00 1.370E+03 I-130 8.950E+00 1.810E+01 1.990E+03 2.700E+01 0.000E+00 8.460E+00 0.000E+00 9.320E+00 Appendix E Ai Child Fish - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Fresh Water Fish - Sport (FFSP) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.860E+02 1.870E+02 6.190E+04 3.070E+02 0.000E+00 1.670E+01 0.000E+00 1.060E+02 I-132 6.830E-03 1.250E-02 5.820E-01 1.920E-02 0.000E+00 1.480E-02 0.000E+00 5.770E-03 I-133 3.140E+01 3.880E+01 7.210E+03 6.470E+01 0.000E+00 1.560E+01 0.000E+00 1.470E+01 I-134 2.750E-08 5.100E-08 1.170E-06 7.800E-08 0.000E+00 3.380E-08 0.000E+00 2.350E-08 I-135 1.670E+00 3.010E+00 2.660E+02 4.610E+00 0.000E+00 2.290E+00 0.000E+00 1.420E+00 CS-134 3.680E+05 6.040E+05 0.000E+00 1.870E+05 6.710E+04 3.250E+03 0.000E+00 1.270E+05 CS-136 3.510E+04 9.640E+04 0.000E+00 5.130E+04 7.660E+03 3.390E+03 0.000E+00 6.240E+04 CS-137 5.140E+05 4.920E+05 0.000E+00 1.600E+05 5.770E+04 3.080E+03 0.000E+00 7.270E+04 CS-138 1.210E-11 1.690E-11 0.000E+00 1.190E-11 1.280E-12 7.770E-12 0.000E+00 1.070E-11 BA-139 7.930E-06 4.230E-09 0.000E+00 3.700E-09 2.490E-09 4.580E-04 0.000E+00 2.300E-07 BA-140 2.480E+02 2.170E-01 0.000E+00 7.060E-02 1.290E-01 1.250E+02 0.000E+00 1.450E+01 BA-141 1.210E-24 6.800E-28 0.000E+00 5.880E-28 3.990E-27 6.920E-25 0.000E+00 3.950E-26 BA-142 3.460E-42 2.490E-45 0.000E+00 2.020E-45 1.470E-45 4.510E-44 0.000E+00 1.930E-43 LA-140 1.310E-01 4.590E-02 0.000E+00 0.000E+00 0.000E+00 1.280E+03 0.000E+00 1.550E-02 LA-142 2.970E-07 9.470E-08 0.000E+00 0.000E+00 0.000E+00 1.880E-02 0.000E+00 2.960E-08 CE-141 3.060E-02 1.520E-02 0.000E+00 6.680E-03 0.000E+00 1.900E+01 0.000E+00 2.260E-03 CE-143 3.320E-03 1.800E+00 0.000E+00 7.550E-04 0.000E+00 2.640E+01 0.000E+00 2.610E-04 CE-144 1.630E+00 5.120E-01 0.000E+00 2.830E-01 0.000E+00 1.330E+02 0.000E+00 8.710E-02 PR-143 7.340E-01 2.200E-01 0.000E+00 1.190E-01 0.000E+00 7.920E+02 0.000E+00 3.640E-02 PR-144 2.180E-28 6.750E-29 0.000E+00 3.570E-29 0.000E+00 1.450E-25 0.000E+00 1.100E-29 ND-147 5.150E-01 4.170E-01 0.000E+00 2.290E-01 0.000E+00 6.610E+02 0.000E+00 3.230E-02 W-187 2.010E+02 1.190E+02 0.000E+00 0.000E+00 0.000E+00 1.680E+04 0.000E+00 5.350E+01 NP-239 3.080E-02 2.210E-03 0.000E+00 6.390E-03 0.000E+00 1.630E+02 0.000E+00 1.550E-03 Appendix E Ai Child Fish - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 4.990E-01 4.990E-01 4.990E-01 4.990E-01 4.990E-01 4.990E-01 5.780E-01 4.990E-01 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 1.950E-01 1.950E-01 1.950E-01 1.950E-01 1.950E-01 1.950E-01 2.300E-01 1.950E-01 MN-54 5.790E+01 5.790E+01 5.790E+01 5.790E+01 5.790E+01 5.790E+01 6.790E+01 5.790E+01 MN-56 3.770E-02 3.770E-02 3.770E-02 3.770E-02 3.770E-02 3.770E-02 4.450E-02 3.770E-02 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 1.140E+01 1.140E+01 1.140E+01 1.140E+01 1.140E+01 1.140E+01 1.340E+01 1.140E+01 CO-58 1.580E+01 1.580E+01 1.580E+01 1.580E+01 1.580E+01 1.580E+01 1.850E+01 1.580E+01 CO-60 8.980E+02 8.980E+02 8.980E+02 8.980E+02 8.980E+02 8.980E+02 1.060E+03 8.980E+02 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 1.240E-02 1.240E-02 1.240E-02 1.240E-02 1.240E-02 1.240E-02 1.440E-02 1.240E-02 CU-64 2.530E-02 2.530E-02 2.530E-02 2.530E-02 2.530E-02 2.530E-02 2.870E-02 2.530E-02 ZN-65 3.120E+01 3.120E+01 3.120E+01 3.120E+01 3.120E+01 3.120E+01 3.590E+01 3.120E+01 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 2.030E-04 2.030E-04 2.030E-04 2.030E-04 2.030E-04 2.030E-04 2.960E-04 2.030E-04 BR-84 8.460E-03 8.460E-03 8.460E-03 8.460E-03 8.460E-03 8.460E-03 9.870E-03 8.460E-03 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 3.750E-01 3.750E-01 3.750E-01 3.750E-01 3.750E-01 3.750E-01 4.290E-01 3.750E-01 RB-88 1.380E-03 1.380E-03 1.380E-03 1.380E-03 1.380E-03 1.380E-03 1.580E-03 1.380E-03 RB-89 5.130E-03 5.130E-03 5.130E-03 5.130E-03 5.130E-03 5.130E-03 6.160E-03 5.130E-03 SR-89 9.030E-04 9.030E-04 9.030E-04 9.030E-04 9.030E-04 9.030E-04 1.050E-03 9.030E-04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 8.970E-02 8.970E-02 8.970E-02 8.970E-02 8.970E-02 8.970E-02 1.050E-01 8.970E-02 Appendix E Ai Child Shoreline Sediment - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 3.240E-02 3.240E-02 3.240E-02 3.240E-02 3.240E-02 3.240E-02 3.600E-02 3.240E-02 Y-90 1.880E-04 1.880E-04 1.880E-04 1.880E-04 1.880E-04 1.880E-04 2.220E-04 1.880E-04 Y-91 4.480E-02 4.480E-02 4.480E-02 4.480E-02 4.480E-02 4.480E-02 5.040E-02 4.480E-02 Y-91M 4.190E-03 4.190E-03 4.190E-03 4.190E-03 4.190E-03 4.190E-03 4.850E-03 4.190E-03 Y-92 7.530E-03 7.530E-03 7.530E-03 7.530E-03 7.530E-03 7.530E-03 8.940E-03 7.530E-03 Y-93 7.660E-03 7.660E-03 7.660E-03 7.660E-03 7.660E-03 7.660E-03 1.050E-02 7.660E-03 ZR-95 1.020E+01 1.020E+01 1.020E+01 1.020E+01 1.020E+01 1.020E+01 1.190E+01 1.020E+01 ZR-97 1.240E-01 1.240E-01 1.240E-01 1.240E-01 1.240E-01 1.240E-01 1.440E-01 1.240E-01 NB-95 5.710E+00 5.710E+00 5.710E+00 5.710E+00 5.710E+00 5.710E+00 6.710E+00 5.710E+00 MO-99 1.670E-01 1.670E-01 1.670E-01 1.670E-01 1.670E-01 1.670E-01 1.930E-01 1.670E-01 TC-99M 7.680E-03 7.680E-03 7.680E-03 7.680E-03 7.680E-03 7.680E-03 8.810E-03 7.680E-03 TC-101 8.500E-04 8.500E-04 8.500E-04 8.500E-04 8.500E-04 8.500E-04 9.440E-04 8.500E-04 RU-103 4.520E+00 4.520E+00 4.520E+00 4.520E+00 4.520E+00 4.520E+00 5.270E+00 4.520E+00 RU-105 2.660E-02 2.660E-02 2.660E-02 2.660E-02 2.660E-02 2.660E-02 3.010E-02 2.660E-02 RU-106 1.760E+01 1.760E+01 1.760E+01 1.760E+01 1.760E+01 1.760E+01 2.110E+01 1.760E+01 AG-110M 1.440E+02 1.440E+02 1.440E+02 1.440E+02 1.440E+02 1.440E+02 1.670E+02 1.440E+02 TE-125M 6.480E-02 6.480E-02 6.480E-02 6.480E-02 6.480E-02 6.480E-02 8.880E-02 6.480E-02 TE-127 1.240E-04 1.240E-04 1.240E-04 1.240E-04 1.240E-04 1.240E-04 1.370E-04 1.240E-04 TE-127M 3.830E-03 3.830E-03 3.830E-03 3.830E-03 3.830E-03 3.830E-03 4.520E-03 3.830E-03 TE-129 1.100E-03 1.100E-03 1.100E-03 1.100E-03 1.100E-03 1.100E-03 1.300E-03 1.100E-03 TE-129M 8.260E-01 8.260E-01 8.260E-01 8.260E-01 8.260E-01 8.260E-01 9.650E-01 8.260E-01 TE-131 1.220E-03 1.220E-03 1.220E-03 1.220E-03 1.220E-03 1.220E-03 1.440E+00 1.220E-03 TE-131M 3.350E-01 3.350E-01 3.350E-01 3.350E-01 3.350E-01 3.350E-01 3.950E-01 3.350E-01 TE-132 1.770E-01 1.770E-01 1.770E-01 1.770E-01 1.770E-01 1.770E-01 2.080E-01 1.770E-01 I-130 2.300E-01 2.300E-01 2.300E-01 2.300E-01 2.300E-01 2.300E-01 2.790E-01 2.300E-01 Appendix E Ai Child Shoreline Sediment - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX E Ai Child Dose Factors for use in the Liquid Dose Calculations Agegroup: CHILD Pathway: Shoreline Sediment (SHDp) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 7.180E-01 7.180E-01 7.180E-01 7.180E-01 7.180E-01 7.180E-01 8.720E-01 7.180E-01 I-132 5.200E-02 5.200E-02 5.200E-02 5.200E-02 5.200E-02 5.200E-02 6.120E-02 5.200E-02 I-133 1.020E-01 1.020E-01 1.020E-01 1.020E-01 1.020E-01 1.020E-01 1.240E-01 1.020E-01 I-134 1.870E-02 1.870E-02 1.870E-02 1.870E-02 1.870E-02 1.870E-02 2.210E-02 1.870E-02 I-135 1.050E-01 1.050E-01 1.050E-01 1.050E-01 1.050E-01 1.050E-01 1.230E-01 1.050E-01 CS-134 2.860E+02 2.860E+02 2.860E+02 2.860E+02 2.860E+02 2.860E+02 3.340E+02 2.860E+02 CS-136 6.300E+00 6.300E+00 6.300E+00 6.300E+00 6.300E+00 6.300E+00 7.140E+00 6.300E+00 CS-137 4.290E+02 4.290E+02 4.290E+02 4.290E+02 4.290E+02 4.290E+02 5.010E+02 4.290E+02 CS-138 1.500E-02 1.500E-02 1.500E-02 1.500E-02 1.500E-02 1.500E-02 1.710E-02 1.500E-02 BA-139 4.420E-03 4.420E-03 4.420E-03 4.420E-03 4.420E-03 4.420E-03 4.970E-03 4.420E-03 BA-140 8.570E-01 8.570E-01 8.570E-01 8.570E-01 8.570E-01 8.570E-01 9.800E-01 8.570E-01 BA-141 1.740E-03 1.740E-03 1.740E-03 1.740E-03 1.740E-03 1.740E-03 1.980E-03 1.740E-03 BA-142 1.870E-03 1.870E-03 1.870E-03 1.870E-03 1.870E-03 1.870E-03 2.130E-03 1.870E-03 LA-140 8.020E-01 8.020E-01 8.020E-01 8.020E-01 8.020E-01 8.020E-01 9.090E-01 8.020E-01 LA-142 3.170E-02 3.170E-02 3.170E-02 3.170E-02 3.170E-02 3.170E-02 3.810E-02 3.170E-02 CE-141 5.700E-01 5.700E-01 5.700E-01 5.700E-01 5.700E-01 5.700E-01 6.430E-01 5.700E-01 CE-143 9.650E-02 9.650E-02 9.650E-02 9.650E-02 9.650E-02 9.650E-02 1.100E-01 9.650E-02 CE-144 2.900E+00 2.900E+00 2.900E+00 2.900E+00 2.900E+00 2.900E+00 3.360E+00 2.900E+00 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 7.660E-05 7.660E-05 7.660E-05 7.660E-05 7.660E-05 7.660E-05 8.810E-05 7.660E-05 ND-147 3.500E-01 3.500E-01 3.500E-01 3.500E-01 3.500E-01 3.500E-01 4.200E-01 3.500E-01 W-187 9.820E-02 9.820E-02 9.820E-02 9.820E-02 9.820E-02 9.820E-02 1.140E-01 9.820E-02 NP-239 7.140E-02 7.140E-02 7.140E-02 7.140E-02 7.140E-02 7.140E-02 8.270E-02 7.140E-02 Appendix E Ai Child Shoreline Sediment - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX F Ai Infant Dose Factors for use in the Liquid Dose Calculations Agegro up: INFANT Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.160E+01 1.160E+01 1.160E+01 1.160E+01 1.160E+01 0.000E+00 1.160E+01 C-14 8.920E+02 1.900E+02 1.900E+02 1.900E+02 1.900E+02 1.900E+02 0.000E+00 1.900E+02 NA-24 2.190E+02 2.190E+02 2.190E+02 2.190E+02 2.190E+02 2.190E+02 0.000E+00 2.190E+02 P-32 6.240E+04 3.670E+03 0.000E+00 0.000E+00 0.000E+00 8.450E+02 0.000E+00 2.420E+03 CR-51 0.000E+00 0.000E+00 3.420E-01 7.470E-02 6.650E-01 1.530E+01 0.000E+00 5.240E-01 MN-54 0.000E+00 7.480E+02 0.000E+00 1.660E+02 0.000E+00 2.750E+02 0.000E+00 1.690E+02 MN-56 0.000E+00 1.220E+00 0.000E+00 1.050E+00 0.000E+00 1.110E+02 0.000E+00 2.100E-01 FE-55 5.230E+02 3.380E+02 0.000E+00 0.000E+00 1.650E+02 4.290E+01 0.000E+00 9.030E+01 FE-59 1.150E+03 2.010E+03 0.000E+00 0.000E+00 5.940E+02 9.590E+02 0.000E+00 7.910E+02 CO-58 0.000E+00 1.350E+02 0.000E+00 0.000E+00 0.000E+00 3.360E+02 0.000E+00 3.360E+02 CO-60 0.000E+00 4.060E+02 0.000E+00 0.000E+00 0.000E+00 9.670E+02 0.000E+00 9.590E+02 NI-63 2.390E+04 1.470E+03 0.000E+00 0.000E+00 0.000E+00 7.340E+01 0.000E+00 8.280E+02 NI-65 6.520E+00 7.380E-01 0.000E+00 0.000E+00 0.000E+00 5.620E+01 0.000E+00 3.360E-01 CU-64 0.000E+00 1.190E+01 0.000E+00 2.010E+01 0.000E+00 2.440E+02 0.000E+00 5.500E+00 ZN-65 6.910E+02 2.370E+03 0.000E+00 1.150E+03 0.000E+00 2.000E+03 0.000E+00 1.090E+03 ZN-69 4.390E-04 7.910E-04 0.000E+00 3.290E-04 0.000E+00 6.450E-02 0.000E+00 5.890E-05 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.200E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.220E-06 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.800E-76 RB-86 0.000E+00 6.280E+03 0.000E+00 0.000E+00 0.000E+00 1.610E+02 0.000E+00 3.100E+03 RB-88 0.000E+00 1.250E-11 0.000E+00 0.000E+00 0.000E+00 1.220E-11 0.000E+00 6.840E-12 RB-89 0.000E+00 9.960E-14 0.000E+00 0.000E+00 0.000E+00 3.390E-14 0.000E+00 6.860E-14 SR-89 9.380E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.930E+03 0.000E+00 2.690E+03 SR-90 6.960E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.690E+03 0.000E+00 1.770E+05 SR-91 7.830E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.270E+02 0.000E+00 2.830E+01 Appendix F Ai Infant Water - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX F Ai Infant Dose Factors for use in the Liquid Dose Calculations Agegro up: INFANT Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 3.350E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.610E+02 0.000E+00 1.240E+00 Y-90 2.870E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.970E+03 0.000E+00 7.700E-02 Y-91 4.230E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.030E+03 0.000E+00 1.130E+00 Y-91M 1.350E-06 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.510E-03 0.000E+00 4.610E-08 Y-92 2.740E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.240E+02 0.000E+00 7.710E-04 Y-93 4.010E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.170E+03 0.000E+00 1.090E-02 ZR-95 7.710E+00 1.880E+00 0.000E+00 2.020E+00 0.000E+00 9.350E+02 0.000E+00 1.330E+00 ZR-97 3.400E-01 5.840E-02 0.000E+00 5.890E-02 0.000E+00 3.720E+03 0.000E+00 2.670E-02 NB-95 1.560E+00 6.440E-01 0.000E+00 4.620E-01 0.000E+00 5.440E+02 0.000E+00 3.720E-01 MO-99 0.000E+00 1.130E+03 0.000E+00 1.680E+03 0.000E+00 3.710E+02 0.000E+00 2.200E+02 TC-99M 1.810E-02 3.740E-02 0.000E+00 4.020E-01 1.950E-02 1.090E+01 0.000E+00 4.820E-01 TC-101 4.570E-17 5.750E-17 0.000E+00 6.840E-16 3.140E-17 9.780E-15 0.000E+00 5.690E-16 RU-103 5.520E+01 0.000E+00 0.000E+00 1.150E+02 0.000E+00 6.710E+02 0.000E+00 1.850E+01 RU-105 7.850E-01 0.000E+00 0.000E+00 5.770E+00 0.000E+00 3.120E+02 0.000E+00 2.640E-01 RU-106 9.060E+02 0.000E+00 0.000E+00 1.070E+03 0.000E+00 6.880E+03 0.000E+00 1.130E+02 AG-110M 3.740E+01 2.730E+01 0.000E+00 3.910E+01 0.000E+00 1.420E+03 0.000E+00 1.810E+01 TE-125M 8.710E+02 2.910E+02 2.930E+02 0.000E+00 0.000E+00 4.150E+02 0.000E+00 1.180E+02 TE-127 1.550E+01 5.200E+00 1.260E+01 3.790E+01 0.000E+00 3.260E+02 0.000E+00 3.340E+00 TE-127M 2.190E+03 7.280E+02 6.340E+02 5.400E+03 0.000E+00 8.850E+02 0.000E+00 2.660E+02 TE-129 7.860E-03 2.710E-03 6.590E-03 1.960E-02 0.000E+00 6.280E-01 0.000E+00 1.840E-03 TE-129M 3.720E+03 1.280E+03 1.430E+03 9.310E+03 0.000E+00 2.220E+03 0.000E+00 5.730E+02 TE-131 1.420E-08 5.250E-09 1.270E-08 3.640E-08 0.000E+00 5.750E-07 0.000E+00 3.990E-09 TE-131M 4.330E+02 1.740E+02 3.540E+02 1.200E+03 0.000E+00 2.940E+03 0.000E+00 1.440E+02 TE-132 7.030E+02 3.480E+02 5.140E+02 2.180E+03 0.000E+00 1.290E+03 0.000E+00 3.250E+02 I-130 1.150E+02 2.530E+02 2.840E+04 2.780E+02 0.000E+00 5.430E+01 0.000E+00 1.020E+02 Appendix F Ai Infant Water - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX F Ai Infant Dose Factors for use in the Liquid Dose Calculations Agegro up: INFANT Pathway: Potable Water (PWtr) Units: mrem/hr / µCi/ml Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.290E+03 1.520E+03 5.010E+05 1.780E+03 0.000E+00 5.440E+01 0.000E+00 6.700E+02 I-132 1.680E+00 3.410E+00 1.600E+02 3.800E+00 0.000E+00 2.760E+00 0.000E+00 1.210E+00 I-133 3.150E+02 4.590E+02 8.350E+04 5.400E+02 0.000E+00 7.770E+01 0.000E+00 1.340E+02 I-134 2.440E-03 4.990E-03 1.160E-01 5.580E-03 0.000E+00 5.160E-03 0.000E+00 1.780E-03 I-135 3.900E+01 7.750E+01 6.950E+03 8.640E+01 0.000E+00 2.800E+01 0.000E+00 2.830E+01 CS-134 1.420E+04 2.640E+04 0.000E+00 6.810E+03 2.790E+03 7.180E+01 0.000E+00 2.670E+03 CS-136 1.680E+03 4.950E+03 0.000E+00 1.970E+03 4.030E+02 7.510E+01 0.000E+00 1.850E+03 CS-137 1.960E+04 2.300E+04 0.000E+00 6.170E+03 2.500E+03 7.190E+01 0.000E+00 1.630E+03 CS-138 3.330E-06 5.410E-06 0.000E+00 2.700E-06 4.210E-07 8.650E-06 0.000E+00 2.620E-06 BA-139 8.180E-02 5.420E-05 0.000E+00 3.260E-05 3.290E-05 5.180E+00 0.000E+00 2.370E-03 BA-140 6.260E+03 6.260E+00 0.000E+00 1.490E+00 3.840E+00 1.540E+03 0.000E+00 3.230E+02 BA-141 2.220E-11 1.520E-14 0.000E+00 9.140E-15 9.250E-15 2.710E-10 0.000E+00 7.000E-13 BA-142 2.460E-20 2.040E-23 0.000E+00 1.180E-23 1.240E-23 1.010E-19 0.000E+00 1.210E-21 LA-140 6.460E-01 2.550E-01 0.000E+00 0.000E+00 0.000E+00 2.990E+03 0.000E+00 6.550E-02 LA-142 2.220E-04 8.160E-05 0.000E+00 0.000E+00 0.000E+00 1.390E+01 0.000E+00 1.950E-05 CE-141 2.930E+00 1.790E+00 0.000E+00 5.510E-01 0.000E+00 9.230E+02 0.000E+00 2.100E-01 CE-143 4.330E-01 2.870E+02 0.000E+00 8.360E-02 0.000E+00 1.670E+03 0.000E+00 3.270E-02 CE-144 1.120E+02 4.580E+01 0.000E+00 1.850E+01 0.000E+00 6.430E+03 0.000E+00 6.270E+00 PR-143 2.980E+00 1.110E+00 0.000E+00 4.140E-01 0.000E+00 1.570E+03 0.000E+00 1.480E-01 PR-144 3.020E-15 1.170E-15 0.000E+00 4.240E-16 0.000E+00 5.440E-11 0.000E+00 1.520E-16 ND-147 2.020E+00 2.070E+00 0.000E+00 7.980E-01 0.000E+00 1.310E+03 0.000E+00 1.270E-01 W-187 2.400E+01 1.670E+01 0.000E+00 0.000E+00 0.000E+00 9.790E+02 0.000E+00 5.760E+00 NP-239 3.600E-01 3.220E-02 0.000E+00 6.430E-02 0.000E+00 9.320E+02 0.000E+00 1.820E-02 Appendix F Ai Infant Water - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 7.630E+02 7.630E+02 7.630E+02 7.630E+02 7.630E+02 0.000E+00 7.630E+02 C-14 2.630E+08 5.270E+07 5.270E+07 5.270E+07 5.270E+07 5.270E+07 0.000E+00 5.270E+07 NA-24 2.440E+06 2.440E+06 2.440E+06 2.440E+06 2.440E+06 2.440E+06 0.000E+00 2.440E+06 P-32 1.710E+10 1.060E+09 0.000E+00 0.000E+00 0.000E+00 1.920E+09 0.000E+00 6.610E+08 CR-51 0.000E+00 0.000E+00 1.710E+04 6.300E+03 3.790E+04 7.190E+06 0.000E+00 2.860E+04 MN-54 0.000E+00 8.410E+06 0.000E+00 2.500E+06 0.000E+00 2.580E+07 0.000E+00 1.610E+06 MN-56 0.000E+00 4.090E-03 0.000E+00 5.190E-03 0.000E+00 1.310E-01 0.000E+00 7.260E-04 FE-55 2.510E+07 1.740E+07 0.000E+00 0.000E+00 9.680E+06 9.950E+06 0.000E+00 4.050E+06 FE-59 2.970E+07 6.980E+07 0.000E+00 0.000E+00 1.950E+07 2.330E+08 0.000E+00 2.680E+07 CO-58 0.000E+00 4.710E+06 0.000E+00 0.000E+00 0.000E+00 9.550E+07 0.000E+00 1.060E+07 CO-60 0.000E+00 1.640E+07 0.000E+00 0.000E+00 0.000E+00 3.080E+08 0.000E+00 3.620E+07 NI-63 6.730E+09 4.660E+08 0.000E+00 0.000E+00 0.000E+00 9.730E+07 0.000E+00 2.260E+08 NI-65 3.700E-01 4.810E-02 0.000E+00 0.000E+00 0.000E+00 1.220E+00 0.000E+00 2.190E-02 CU-64 0.000E+00 2.380E+04 0.000E+00 6.010E+04 0.000E+00 2.030E+06 0.000E+00 1.120E+04 ZN-65 1.370E+09 4.370E+09 0.000E+00 2.920E+09 0.000E+00 2.750E+09 0.000E+00 1.970E+09 ZN-69 2.090E-12 4.000E-12 0.000E+00 2.600E-12 0.000E+00 6.010E-13 0.000E+00 2.780E-13 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.400E-01 0.000E+00 9.720E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.260E-28 0.000E+00 1.610E-23 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.590E+09 0.000E+00 0.000E+00 0.000E+00 5.120E+08 0.000E+00 1.210E+09 RB-88 0.000E+00 2.140E-45 0.000E+00 0.000E+00 0.000E+00 2.960E-56 0.000E+00 1.140E-45 RB-89 0.000E+00 4.330E-53 0.000E+00 0.000E+00 0.000E+00 2.510E-66 0.000E+00 3.040E-53 SR-89 1.450E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.330E+08 0.000E+00 4.160E+07 SR-90 4.680E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.350E+09 0.000E+00 1.150E+10 SR-91 2.890E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.380E+05 0.000E+00 1.170E+03 Appendix G Ri Adult Cow Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 4.880E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.680E+00 0.000E+00 2.110E-02 Y-90 7.080E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.510E+05 0.000E+00 1.900E+00 Y-91 8.590E+03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.730E+06 0.000E+00 2.300E+02 Y-91M 5.980E-20 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.760E-19 0.000E+00 2.320E-21 Y-92 5.580E-05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.770E-01 0.000E+00 1.630E-06 Y-93 2.230E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.090E+03 0.000E+00 6.170E-03 ZR-95 9.430E+02 3.030E+02 0.000E+00 4.750E+02 0.000E+00 9.590E+05 0.000E+00 2.050E+02 ZR-97 4.330E-01 8.740E-02 0.000E+00 1.320E-01 0.000E+00 2.710E+04 0.000E+00 4.000E-02 NB-95 8.260E+04 4.590E+04 0.000E+00 4.540E+04 0.000E+00 2.790E+08 0.000E+00 2.470E+04 MO-99 0.000E+00 2.480E+07 0.000E+00 5.610E+07 0.000E+00 5.740E+07 0.000E+00 4.710E+06 TC-99M 3.320E+00 9.380E+00 0.000E+00 1.420E+02 4.600E+00 5.550E+03 0.000E+00 1.200E+02 TC-101 2.590E-60 3.740E-60 0.000E+00 6.730E-59 1.910E-60 1.120E-71 0.000E+00 3.670E-59 RU-103 1.020E+03 0.000E+00 0.000E+00 3.890E+03 0.000E+00 1.190E+05 0.000E+00 4.390E+02 RU-105 8.570E-04 0.000E+00 0.000E+00 1.110E-02 0.000E+00 5.240E-01 0.000E+00 3.380E-04 RU-106 2.040E+04 0.000E+00 0.000E+00 3.940E+04 0.000E+00 1.320E+06 0.000E+00 2.580E+03 AG-110M 5.820E+07 5.390E+07 0.000E+00 1.060E+08 0.000E+00 2.200E+10 0.000E+00 3.200E+07 TE-125M 1.630E+07 5.900E+06 4.900E+06 6.630E+07 0.000E+00 6.500E+07 0.000E+00 2.180E+06 TE-127 6.530E+02 2.340E+02 4.840E+02 2.660E+03 0.000E+00 5.150E+04 0.000E+00 1.410E+02 TE-127M 4.580E+07 1.640E+07 1.170E+07 1.860E+08 0.000E+00 1.540E+08 0.000E+00 5.580E+06 TE-129 2.830E-10 1.060E-10 2.170E-10 1.190E-09 0.000E+00 2.130E-10 0.000E+00 6.880E-11 TE-129M 6.020E+07 2.250E+07 2.070E+07 2.510E+08 0.000E+00 3.030E+08 0.000E+00 9.530E+06 TE-131 3.600E-33 1.500E-33 2.960E-33 1.580E-32 0.000E+00 5.100E-34 0.000E+00 1.140E-33 TE-131M 3.610E+05 1.770E+05 2.800E+05 1.790E+06 0.000E+00 1.750E+07 0.000E+00 1.470E+05 TE-132 2.400E+06 1.550E+06 1.720E+06 1.500E+07 0.000E+00 7.350E+07 0.000E+00 1.460E+06 I-130 4.200E+05 1.240E+06 1.050E+08 1.930E+06 0.000E+00 1.070E+06 0.000E+00 4.890E+05 Appendix G Ri Adult Cow Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 2.960E+08 4.230E+08 1.390E+11 7.260E+08 0.000E+00 1.120E+08 0.000E+00 2.430E+08 I-132 1.640E-01 4.390E-01 1.540E+01 7.000E-01 0.000E+00 8.250E-02 0.000E+00 1.540E-01 I-133 3.870E+06 6.730E+06 9.890E+08 1.170E+07 0.000E+00 6.050E+06 0.000E+00 2.050E+06 I-134 2.020E-12 5.480E-12 9.490E-11 8.710E-12 0.000E+00 4.770E-15 0.000E+00 1.960E-12 I-135 1.280E+04 3.360E+04 2.220E+06 5.390E+04 0.000E+00 3.800E+04 0.000E+00 1.240E+04 CS-134 5.650E+09 1.350E+10 0.000E+00 4.350E+09 1.450E+09 2.350E+08 0.000E+00 1.100E+10 CS-136 2.630E+08 1.040E+09 0.000E+00 5.780E+08 7.930E+07 1.180E+08 0.000E+00 7.480E+08 CS-137 7.380E+09 1.010E+10 0.000E+00 3.430E+09 1.140E+09 1.950E+08 0.000E+00 6.610E+09 CS-138 9.050E-24 1.790E-23 0.000E+00 1.310E-23 1.300E-24 7.620E-29 0.000E+00 8.850E-24 BA-139 4.420E-08 3.150E-11 0.000E+00 2.940E-11 1.790E-11 7.830E-08 0.000E+00 1.290E-09 BA-140 2.690E+07 3.380E+04 0.000E+00 1.150E+04 1.930E+04 5.530E+07 0.000E+00 1.760E+06 BA-141 4.090E-46 3.090E-49 0.000E+00 2.880E-49 1.760E-49 1.930E-55 0.000E+00 1.380E-47 BA-142 2.640E-80 2.720E-83 0.000E+00 2.300E-83 1.540E-83 3.720E-98 0.000E+00 1.660E-81 LA-140 4.510E+00 2.270E+00 0.000E+00 0.000E+00 0.000E+00 1.670E+05 0.000E+00 6.010E-01 LA-142 1.860E-11 8.460E-12 0.000E+00 0.000E+00 0.000E+00 6.170E-08 0.000E+00 2.110E-12 CE-141 4.840E+03 3.280E+03 0.000E+00 1.520E+03 0.000E+00 1.250E+07 0.000E+00 3.720E+02 CE-143 4.160E+01 3.070E+04 0.000E+00 1.350E+01 0.000E+00 1.150E+06 0.000E+00 3.400E+00 CE-144 3.580E+05 1.500E+05 0.000E+00 8.870E+04 0.000E+00 1.210E+08 0.000E+00 1.920E+04 PR-143 1.580E+02 6.330E+01 0.000E+00 3.660E+01 0.000E+00 6.920E+05 0.000E+00 7.830E+00 PR-144 5.870E-54 2.440E-54 0.000E+00 1.380E-54 0.000E+00 8.450E-61 0.000E+00 2.990E-55 ND-147 9.420E+01 1.090E+02 0.000E+00 6.360E+01 0.000E+00 5.220E+05 0.000E+00 6.510E+00 W-187 6.510E+03 5.450E+03 0.000E+00 0.000E+00 0.000E+00 1.780E+06 0.000E+00 1.900E+03 NP-239 3.670E+00 3.610E-01 0.000E+00 1.130E+00 0.000E+00 7.410E+04 0.000E+00 1.990E-01 Appendix G Ri Adult Cow Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.560E+03 1.560E+03 1.560E+03 1.560E+03 1.560E+03 0.000E+00 1.560E+03 C-14 2.630E+08 5.270E+07 5.270E+07 5.270E+07 5.270E+07 5.270E+07 0.000E+00 5.270E+07 NA-24 2.930E+05 2.930E+05 2.930E+05 2.930E+05 2.930E+05 2.930E+05 0.000E+00 2.930E+05 P-32 2.050E+10 1.280E+09 0.000E+00 0.000E+00 0.000E+00 2.310E+09 0.000E+00 7.930E+08 CR-51 0.000E+00 0.000E+00 2.050E+03 7.550E+02 4.550E+03 8.620E+05 0.000E+00 3.430E+03 MN-54 0.000E+00 1.010E+06 0.000E+00 3.000E+05 0.000E+00 3.090E+06 0.000E+00 1.930E+05 MN-56 0.000E+00 4.910E-04 0.000E+00 6.230E-04 0.000E+00 1.570E-02 0.000E+00 8.710E-05 FE-55 3.260E+05 2.260E+05 0.000E+00 0.000E+00 1.260E+05 1.290E+05 0.000E+00 5.260E+04 FE-59 3.860E+05 9.070E+05 0.000E+00 0.000E+00 2.540E+05 3.020E+06 0.000E+00 3.480E+05 CO-58 0.000E+00 5.660E+05 0.000E+00 0.000E+00 0.000E+00 1.150E+07 0.000E+00 1.270E+06 CO-60 0.000E+00 1.970E+06 0.000E+00 0.000E+00 0.000E+00 3.700E+07 0.000E+00 4.340E+06 NI-63 8.070E+08 5.600E+07 0.000E+00 0.000E+00 0.000E+00 1.170E+07 0.000E+00 2.710E+07 NI-65 4.440E-02 5.770E-03 0.000E+00 0.000E+00 0.000E+00 1.460E-01 0.000E+00 2.630E-03 CU-64 0.000E+00 2.660E+03 0.000E+00 6.700E+03 0.000E+00 2.260E+05 0.000E+00 1.250E+03 ZN-65 1.650E+08 5.240E+08 0.000E+00 3.500E+08 0.000E+00 3.300E+08 0.000E+00 2.370E+08 ZN-69 2.510E-13 4.800E-13 0.000E+00 3.120E-13 0.000E+00 7.210E-14 0.000E+00 3.340E-14 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.680E-02 0.000E+00 1.170E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.520E-29 0.000E+00 1.930E-24 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 3.110E+08 0.000E+00 0.000E+00 0.000E+00 6.140E+07 0.000E+00 1.450E+08 RB-88 0.000E+00 2.570E-46 0.000E+00 0.000E+00 0.000E+00 3.550E-57 0.000E+00 1.360E-46 RB-89 0.000E+00 5.190E-54 0.000E+00 0.000E+00 0.000E+00 3.020E-67 0.000E+00 3.650E-54 SR-89 3.050E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.890E+08 0.000E+00 8.750E+07 SR-90 9.830E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.840E+09 0.000E+00 2.410E+10 SR-91 6.070E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.890E+05 0.000E+00 2.450E+03 Appendix G Ri Adult Goat Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.030E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.030E+01 0.000E+00 4.440E-02 Y-90 8.500E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.010E+04 0.000E+00 2.280E-01 Y-91 1.030E+03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.670E+05 0.000E+00 2.760E+01 Y-91M 7.170E-21 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.110E-20 0.000E+00 2.780E-22 Y-92 6.690E-06 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.170E-01 0.000E+00 1.960E-07 Y-93 2.680E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.500E+02 0.000E+00 7.400E-04 ZR-95 1.130E+02 3.630E+01 0.000E+00 5.700E+01 0.000E+00 1.150E+05 0.000E+00 2.460E+01 ZR-97 5.200E-02 1.050E-02 0.000E+00 1.580E-02 0.000E+00 3.250E+03 0.000E+00 4.800E-03 NB-95 9.910E+03 5.510E+03 0.000E+00 5.450E+03 0.000E+00 3.340E+07 0.000E+00 2.960E+03 MO-99 0.000E+00 2.970E+06 0.000E+00 6.730E+06 0.000E+00 6.890E+06 0.000E+00 5.660E+05 TC-99M 3.980E-01 1.130E+00 0.000E+00 1.710E+01 5.520E-01 6.660E+02 0.000E+00 1.430E+01 TC-101 3.110E-61 4.490E-61 0.000E+00 8.080E-60 2.290E-61 1.350E-72 0.000E+00 4.400E-60 RU-103 1.220E+02 0.000E+00 0.000E+00 4.660E+02 0.000E+00 1.430E+04 0.000E+00 5.260E+01 RU-105 1.030E-04 0.000E+00 0.000E+00 1.330E-03 0.000E+00 6.290E-02 0.000E+00 4.060E-05 RU-106 2.450E+03 0.000E+00 0.000E+00 4.730E+03 0.000E+00 1.580E+05 0.000E+00 3.100E+02 AG-110M 6.990E+06 6.460E+06 0.000E+00 1.270E+07 0.000E+00 2.640E+09 0.000E+00 3.840E+06 TE-125M 1.950E+06 7.080E+05 5.880E+05 7.950E+06 0.000E+00 7.800E+06 0.000E+00 2.620E+05 TE-127 7.830E+01 2.810E+01 5.800E+01 3.190E+02 0.000E+00 6.180E+03 0.000E+00 1.700E+01 TE-127M 5.490E+06 1.960E+06 1.400E+06 2.230E+07 0.000E+00 1.840E+07 0.000E+00 6.690E+05 TE-129 3.390E-11 1.270E-11 2.600E-11 1.430E-10 0.000E+00 2.560E-11 0.000E+00 8.260E-12 TE-129M 7.220E+06 2.690E+06 2.480E+06 3.020E+07 0.000E+00 3.640E+07 0.000E+00 1.140E+06 TE-131 4.320E-34 1.810E-34 3.550E-34 1.890E-33 0.000E+00 6.120E-35 0.000E+00 1.360E-34 TE-131M 4.330E+04 2.120E+04 3.360E+04 2.150E+05 0.000E+00 2.100E+06 0.000E+00 1.770E+04 TE-132 2.880E+05 1.860E+05 2.060E+05 1.800E+06 0.000E+00 8.820E+06 0.000E+00 1.750E+05 I-130 5.040E+05 1.490E+06 1.260E+08 2.320E+06 0.000E+00 1.280E+06 0.000E+00 5.870E+05 Appendix G Ri Adult Goat Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.550E+08 5.080E+08 1.670E+11 8.710E+08 0.000E+00 1.340E+08 0.000E+00 2.910E+08 I-132 1.970E-01 5.270E-01 1.840E+01 8.400E-01 0.000E+00 9.900E-02 0.000E+00 1.840E-01 I-133 4.640E+06 8.080E+06 1.190E+09 1.410E+07 0.000E+00 7.260E+06 0.000E+00 2.460E+06 I-134 2.420E-12 6.570E-12 1.140E-10 1.050E-11 0.000E+00 5.730E-15 0.000E+00 2.350E-12 I-135 1.540E+04 4.030E+04 2.660E+06 6.470E+04 0.000E+00 4.560E+04 0.000E+00 1.490E+04 CS-134 1.700E+10 4.040E+10 0.000E+00 1.310E+10 4.340E+09 7.060E+08 0.000E+00 3.300E+10 CS-136 7.900E+08 3.120E+09 0.000E+00 1.730E+09 2.380E+08 3.540E+08 0.000E+00 2.240E+09 CS-137 2.210E+10 3.030E+10 0.000E+00 1.030E+10 3.420E+09 5.860E+08 0.000E+00 1.980E+10 CS-138 2.710E-23 5.360E-23 0.000E+00 3.940E-23 3.890E-24 2.290E-28 0.000E+00 2.650E-23 BA-139 5.300E-09 3.780E-12 0.000E+00 3.530E-12 2.140E-12 9.400E-09 0.000E+00 1.550E-10 BA-140 3.230E+06 4.050E+03 0.000E+00 1.380E+03 2.320E+03 6.640E+06 0.000E+00 2.110E+05 BA-141 4.910E-47 3.710E-50 0.000E+00 3.450E-50 2.110E-50 2.310E-56 0.000E+00 1.660E-48 BA-142 3.170E-81 3.260E-84 0.000E+00 2.750E-84 1.850E-84 0.000E+00 0.000E+00 2.000E-82 LA-140 5.410E-01 2.730E-01 0.000E+00 0.000E+00 0.000E+00 2.000E+04 0.000E+00 7.210E-02 LA-142 2.230E-12 1.010E-12 0.000E+00 0.000E+00 0.000E+00 7.410E-09 0.000E+00 2.530E-13 CE-141 5.810E+02 3.930E+02 0.000E+00 1.830E+02 0.000E+00 1.500E+06 0.000E+00 4.460E+01 CE-143 4.990E+00 3.690E+03 0.000E+00 1.620E+00 0.000E+00 1.380E+05 0.000E+00 4.080E-01 CE-144 4.290E+04 1.790E+04 0.000E+00 1.060E+04 0.000E+00 1.450E+07 0.000E+00 2.300E+03 PR-143 1.890E+01 7.600E+00 0.000E+00 4.390E+00 0.000E+00 8.300E+04 0.000E+00 9.390E-01 PR-144 7.050E-55 2.930E-55 0.000E+00 1.650E-55 0.000E+00 1.010E-61 0.000E+00 3.580E-56 ND-147 1.130E+01 1.310E+01 0.000E+00 7.630E+00 0.000E+00 6.270E+04 0.000E+00 7.810E-01 W-187 7.820E+02 6.530E+02 0.000E+00 0.000E+00 0.000E+00 2.140E+05 0.000E+00 2.280E+02 NP-239 4.410E-01 4.330E-02 0.000E+00 1.350E-01 0.000E+00 8.890E+03 0.000E+00 2.390E-02 Appendix G Ri Adult Goat Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 3.250E+02 3.250E+02 3.250E+02 3.250E+02 3.250E+02 0.000E+00 3.250E+02 C-14 2.410E+08 4.830E+07 4.830E+07 4.830E+07 4.830E+07 4.830E+07 0.000E+00 4.830E+07 NA-24 1.360E-03 1.360E-03 1.360E-03 1.360E-03 1.360E-03 1.360E-03 0.000E+00 1.360E-03 P-32 4.660E+09 2.900E+08 0.000E+00 0.000E+00 0.000E+00 5.240E+08 0.000E+00 1.800E+08 CR-51 0.000E+00 0.000E+00 4.210E+03 1.550E+03 9.350E+03 1.770E+06 0.000E+00 7.050E+03 MN-54 0.000E+00 9.180E+06 0.000E+00 2.730E+06 0.000E+00 2.810E+07 0.000E+00 1.750E+06 MN-56 0.000E+00 1.320E-53 0.000E+00 1.680E-53 0.000E+00 4.220E-52 0.000E+00 2.350E-54 FE-55 2.930E+08 2.030E+08 0.000E+00 0.000E+00 1.130E+08 1.160E+08 0.000E+00 4.720E+07 FE-59 2.660E+08 6.240E+08 0.000E+00 0.000E+00 1.740E+08 2.080E+09 0.000E+00 2.390E+08 CO-58 0.000E+00 1.820E+07 0.000E+00 0.000E+00 0.000E+00 3.690E+08 0.000E+00 4.090E+07 CO-60 0.000E+00 7.520E+07 0.000E+00 0.000E+00 0.000E+00 1.410E+09 0.000E+00 1.660E+08 NI-63 1.890E+10 1.310E+09 0.000E+00 0.000E+00 0.000E+00 2.730E+08 0.000E+00 6.330E+08 NI-65 2.250E-52 2.920E-53 0.000E+00 0.000E+00 0.000E+00 7.400E-52 0.000E+00 1.330E-53 CU-64 0.000E+00 2.710E-07 0.000E+00 6.830E-07 0.000E+00 2.310E-05 0.000E+00 1.270E-07 ZN-65 3.560E+08 1.130E+09 0.000E+00 7.570E+08 0.000E+00 7.130E+08 0.000E+00 5.120E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.650E-57 0.000E+00 6.000E-57 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 4.870E+08 0.000E+00 0.000E+00 0.000E+00 9.600E+07 0.000E+00 2.270E+08 RB-88 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-89 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-89 3.020E+08 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.840E+07 0.000E+00 8.660E+06 SR-90 1.240E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.590E+08 0.000E+00 3.050E+09 SR-91 1.520E-10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.240E-10 0.000E+00 6.140E-12 Appendix G Ri Adult Cow Meat - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.180E-49 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.340E-48 0.000E+00 5.100E-51 Y-90 1.080E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.140E+06 0.000E+00 2.890E+00 Y-91 1.130E+06 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.230E+08 0.000E+00 3.030E+04 Y-91M 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 Y-92 1.520E-39 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.660E-35 0.000E+00 4.430E-41 Y-93 4.690E-12 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.490E-07 0.000E+00 1.300E-13 ZR-95 1.870E+06 6.010E+05 0.000E+00 9.420E+05 0.000E+00 1.900E+09 0.000E+00 4.070E+05 ZR-97 2.070E-05 4.170E-06 0.000E+00 6.300E-06 0.000E+00 1.290E+00 0.000E+00 1.910E-06 NB-95 2.300E+06 1.280E+06 0.000E+00 1.260E+06 0.000E+00 7.760E+09 0.000E+00 6.870E+05 MO-99 0.000E+00 1.000E+05 0.000E+00 2.260E+05 0.000E+00 2.320E+05 0.000E+00 1.900E+04 TC-99M 4.450E-21 1.260E-20 0.000E+00 1.910E-19 6.150E-21 7.430E-18 0.000E+00 1.600E-19 TC-101 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RU-103 1.050E+08 0.000E+00 0.000E+00 4.010E+08 0.000E+00 1.230E+10 0.000E+00 4.530E+07 RU-105 5.780E-28 0.000E+00 0.000E+00 7.460E-27 0.000E+00 3.530E-25 0.000E+00 2.280E-28 RU-106 2.800E+09 0.000E+00 0.000E+00 5.400E+09 0.000E+00 1.810E+11 0.000E+00 3.540E+08 AG-110M 6.680E+06 6.180E+06 0.000E+00 1.220E+07 0.000E+00 2.520E+09 0.000E+00 3.670E+06 TE-125M 3.590E+08 1.300E+08 1.080E+08 1.460E+09 0.000E+00 1.430E+09 0.000E+00 4.810E+07 TE-127 2.120E-10 7.610E-11 1.570E-10 8.640E-10 0.000E+00 1.670E-08 0.000E+00 4.590E-11 TE-127M 1.120E+09 3.990E+08 2.850E+08 4.530E+09 0.000E+00 3.740E+09 0.000E+00 1.360E+08 TE-129 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 TE-129M 1.130E+09 4.230E+08 3.900E+08 4.730E+09 0.000E+00 5.710E+09 0.000E+00 1.790E+08 TE-131 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 TE-131M 4.510E+02 2.210E+02 3.490E+02 2.230E+03 0.000E+00 2.190E+04 0.000E+00 1.840E+02 TE-132 1.420E+06 9.180E+05 1.010E+06 8.840E+06 0.000E+00 4.340E+07 0.000E+00 8.620E+05 I-130 2.110E-06 6.220E-06 5.270E-04 9.700E-06 0.000E+00 5.350E-06 0.000E+00 2.450E-06 Appendix G Ri Adult Cow Meat - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.070E+07 1.540E+07 5.030E+09 2.630E+07 0.000E+00 4.050E+06 0.000E+00 8.800E+06 I-132 6.970E-59 1.860E-58 6.530E-57 2.970E-58 0.000E+00 3.500E-59 0.000E+00 6.530E-59 I-133 3.650E-01 6.350E-01 9.340E+01 1.110E+00 0.000E+00 5.710E-01 0.000E+00 1.940E-01 I-134 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 I-135 4.420E-17 1.160E-16 7.640E-15 1.860E-16 0.000E+00 1.310E-16 0.000E+00 4.270E-17 CS-134 6.580E+08 1.560E+09 0.000E+00 5.060E+08 1.680E+08 2.740E+07 0.000E+00 1.280E+09 CS-136 1.210E+07 4.760E+07 0.000E+00 2.650E+07 3.630E+06 5.410E+06 0.000E+00 3.420E+07 CS-137 8.720E+08 1.190E+09 0.000E+00 4.050E+08 1.350E+08 2.310E+07 0.000E+00 7.810E+08 CS-138 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-139 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-140 2.870E+07 3.610E+04 0.000E+00 1.230E+04 2.070E+04 5.920E+07 0.000E+00 1.880E+06 BA-141 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-142 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 LA-140 3.710E-02 1.870E-02 0.000E+00 0.000E+00 0.000E+00 1.370E+03 0.000E+00 4.940E-03 LA-142 3.470E-92 1.580E-92 0.000E+00 0.000E+00 0.000E+00 1.150E-88 0.000E+00 3.940E-93 CE-141 1.400E+04 9.500E+03 0.000E+00 4.410E+03 0.000E+00 3.630E+07 0.000E+00 1.080E+03 CE-143 2.010E-02 1.480E+01 0.000E+00 6.530E-03 0.000E+00 5.550E+02 0.000E+00 1.640E-03 CE-144 1.460E+06 6.090E+05 0.000E+00 3.610E+05 0.000E+00 4.930E+08 0.000E+00 7.830E+04 PR-143 2.100E+04 8.410E+03 0.000E+00 4.850E+03 0.000E+00 9.180E+07 0.000E+00 1.040E+03 PR-144 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 ND-147 7.070E+03 8.170E+03 0.000E+00 4.780E+03 0.000E+00 3.920E+07 0.000E+00 4.890E+02 W-187 2.070E-02 1.730E-02 0.000E+00 0.000E+00 0.000E+00 5.660E+00 0.000E+00 6.040E-03 NP-239 2.590E-01 2.550E-02 0.000E+00 7.950E-02 0.000E+00 5.230E+03 0.000E+00 1.400E-02 Appendix G Ri Adult Cow Meat - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.260E+03 2.260E+03 2.260E+03 2.260E+03 2.260E+03 0.000E+00 2.260E+03 C-14 2.280E+08 4.550E+07 4.550E+07 4.550E+07 4.550E+07 4.550E+07 0.000E+00 4.550E+07 NA-24 2.690E+05 2.690E+05 2.690E+05 2.690E+05 2.690E+05 2.690E+05 0.000E+00 2.690E+05 P-32 1.400E+09 8.730E+07 0.000E+00 0.000E+00 0.000E+00 1.580E+08 0.000E+00 5.430E+07 CR-51 0.000E+00 0.000E+00 2.780E+04 1.020E+04 6.160E+04 1.170E+07 0.000E+00 4.640E+04 MN-54 0.000E+00 3.130E+08 0.000E+00 9.310E+07 0.000E+00 9.590E+08 0.000E+00 5.970E+07 MN-56 0.000E+00 1.580E+01 0.000E+00 2.000E+01 0.000E+00 5.040E+02 0.000E+00 2.800E+00 FE-55 2.100E+08 1.450E+08 0.000E+00 0.000E+00 8.080E+07 8.310E+07 0.000E+00 3.380E+07 FE-59 1.260E+08 2.960E+08 0.000E+00 0.000E+00 8.280E+07 9.880E+08 0.000E+00 1.140E+08 CO-58 0.000E+00 3.070E+07 0.000E+00 0.000E+00 0.000E+00 6.230E+08 0.000E+00 6.890E+07 CO-60 0.000E+00 1.670E+08 0.000E+00 0.000E+00 0.000E+00 3.140E+09 0.000E+00 3.690E+08 NI-63 1.040E+10 7.210E+08 0.000E+00 0.000E+00 0.000E+00 1.500E+08 0.000E+00 3.490E+08 NI-65 6.150E+01 7.990E+00 0.000E+00 0.000E+00 0.000E+00 2.030E+02 0.000E+00 3.640E+00 CU-64 0.000E+00 9.200E+03 0.000E+00 2.320E+04 0.000E+00 7.840E+05 0.000E+00 4.320E+03 ZN-65 3.170E+08 1.010E+09 0.000E+00 6.750E+08 0.000E+00 6.360E+08 0.000E+00 4.560E+08 ZN-69 5.490E-06 1.050E-05 0.000E+00 6.830E-06 0.000E+00 1.580E-06 0.000E+00 7.310E-07 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.470E+00 0.000E+00 3.110E+00 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.940E-16 0.000E+00 2.480E-11 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.190E+08 0.000E+00 0.000E+00 0.000E+00 4.330E+07 0.000E+00 1.020E+08 RB-88 0.000E+00 3.430E-22 0.000E+00 0.000E+00 0.000E+00 4.740E-33 0.000E+00 1.820E-22 RB-89 0.000E+00 3.890E-26 0.000E+00 0.000E+00 0.000E+00 2.260E-39 0.000E+00 2.730E-26 SR-89 9.970E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.600E+09 0.000E+00 2.860E+08 SR-90 6.050E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.750E+10 0.000E+00 1.480E+11 SR-91 3.050E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.450E+06 0.000E+00 1.230E+04 Appendix G Ri Adult Vegetation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 4.270E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.450E+03 0.000E+00 1.850E+01 Y-90 1.330E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.410E+08 0.000E+00 3.570E+02 Y-91 5.110E+06 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.810E+09 0.000E+00 1.370E+05 Y-91M 5.220E-09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.530E-08 0.000E+00 2.020E-10 Y-92 9.150E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.600E+04 0.000E+00 2.680E-02 Y-93 1.700E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.380E+06 0.000E+00 4.680E+00 ZR-95 1.170E+06 3.770E+05 0.000E+00 5.910E+05 0.000E+00 1.190E+09 0.000E+00 2.550E+05 ZR-97 3.370E+02 6.810E+01 0.000E+00 1.030E+02 0.000E+00 2.110E+07 0.000E+00 3.110E+01 NB-95 1.420E+05 7.920E+04 0.000E+00 7.830E+04 0.000E+00 4.810E+08 0.000E+00 4.260E+04 MO-99 0.000E+00 6.150E+06 0.000E+00 1.390E+07 0.000E+00 1.430E+07 0.000E+00 1.170E+06 TC-99M 3.100E+00 8.770E+00 0.000E+00 1.330E+02 4.300E+00 5.190E+03 0.000E+00 1.120E+02 TC-101 8.220E-31 1.180E-30 0.000E+00 2.130E-29 6.050E-31 3.560E-42 0.000E+00 1.160E-29 RU-103 4.770E+06 0.000E+00 0.000E+00 1.820E+07 0.000E+00 5.570E+08 0.000E+00 2.060E+06 RU-105 5.390E+01 0.000E+00 0.000E+00 6.960E+02 0.000E+00 3.290E+04 0.000E+00 2.130E+01 RU-106 1.930E+08 0.000E+00 0.000E+00 3.720E+08 0.000E+00 1.250E+10 0.000E+00 2.440E+07 AG-110M 1.050E+07 9.750E+06 0.000E+00 1.920E+07 0.000E+00 3.980E+09 0.000E+00 5.790E+06 TE-125M 9.660E+07 3.500E+07 2.900E+07 3.930E+08 0.000E+00 3.860E+08 0.000E+00 1.290E+07 TE-127 5.660E+03 2.030E+03 4.190E+03 2.310E+04 0.000E+00 4.470E+05 0.000E+00 1.220E+03 TE-127M 3.490E+08 1.250E+08 8.920E+07 1.420E+09 0.000E+00 1.170E+09 0.000E+00 4.260E+07 TE-129 7.630E-04 2.870E-04 5.850E-04 3.210E-03 0.000E+00 5.760E-04 0.000E+00 1.860E-04 TE-129M 2.510E+08 9.380E+07 8.630E+07 1.050E+09 0.000E+00 1.270E+09 0.000E+00 3.980E+07 TE-131 1.500E-15 6.270E-16 1.230E-15 6.570E-15 0.000E+00 2.130E-16 0.000E+00 4.740E-16 TE-131M 9.120E+05 4.460E+05 7.060E+05 4.520E+06 0.000E+00 4.430E+07 0.000E+00 3.720E+05 TE-132 4.300E+06 2.780E+06 3.070E+06 2.680E+07 0.000E+00 1.320E+08 0.000E+00 2.610E+06 I-130 3.920E+05 1.160E+06 9.810E+07 1.810E+06 0.000E+00 9.960E+05 0.000E+00 4.570E+05 Appendix G Ri Adult Vegetation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 8.080E+07 1.160E+08 3.790E+10 1.980E+08 0.000E+00 3.050E+07 0.000E+00 6.620E+07 I-132 5.760E+01 1.540E+02 5.390E+03 2.450E+02 0.000E+00 2.890E+01 0.000E+00 5.390E+01 I-133 2.090E+06 3.630E+06 5.330E+08 6.330E+06 0.000E+00 3.260E+06 0.000E+00 1.110E+06 I-134 9.650E-05 2.620E-04 4.540E-03 4.170E-04 0.000E+00 2.290E-07 0.000E+00 9.380E-05 I-135 3.900E+04 1.020E+05 6.730E+06 1.640E+05 0.000E+00 1.150E+05 0.000E+00 3.770E+04 CS-134 4.670E+09 1.110E+10 0.000E+00 3.590E+09 1.190E+09 1.940E+08 0.000E+00 9.080E+09 CS-136 4.270E+07 1.680E+08 0.000E+00 9.380E+07 1.290E+07 1.910E+07 0.000E+00 1.210E+08 CS-137 6.360E+09 8.700E+09 0.000E+00 2.950E+09 9.810E+08 1.680E+08 0.000E+00 5.700E+09 CS-138 3.920E-11 7.730E-11 0.000E+00 5.680E-11 5.610E-12 3.300E-16 0.000E+00 3.830E-11 BA-139 2.860E-02 2.030E-05 0.000E+00 1.900E-05 1.150E-05 5.060E-02 0.000E+00 8.360E-04 BA-140 1.280E+08 1.610E+05 0.000E+00 5.490E+04 9.240E+04 2.650E+08 0.000E+00 8.420E+06 BA-141 1.150E-21 8.700E-25 0.000E+00 8.090E-25 4.940E-25 5.430E-31 0.000E+00 3.890E-23 BA-142 5.960E-39 6.120E-42 0.000E+00 5.170E-42 3.470E-42 8.390E-57 0.000E+00 3.750E-40 LA-140 1.980E+03 9.970E+02 0.000E+00 0.000E+00 0.000E+00 7.320E+07 0.000E+00 2.630E+02 LA-142 2.020E-04 9.190E-05 0.000E+00 0.000E+00 0.000E+00 6.710E-01 0.000E+00 2.290E-05 CE-141 1.970E+05 1.330E+05 0.000E+00 6.190E+04 0.000E+00 5.100E+08 0.000E+00 1.510E+04 CE-143 9.980E+02 7.380E+05 0.000E+00 3.250E+02 0.000E+00 2.760E+07 0.000E+00 8.160E+01 CE-144 3.290E+07 1.380E+07 0.000E+00 8.160E+06 0.000E+00 1.110E+10 0.000E+00 1.770E+06 PR-143 6.260E+04 2.510E+04 0.000E+00 1.450E+04 0.000E+00 2.740E+08 0.000E+00 3.100E+03 PR-144 3.090E-26 1.280E-26 0.000E+00 7.230E-27 0.000E+00 4.440E-33 0.000E+00 1.570E-27 ND-147 3.330E+04 3.850E+04 0.000E+00 2.250E+04 0.000E+00 1.850E+08 0.000E+00 2.310E+03 W-187 3.800E+04 3.180E+04 0.000E+00 0.000E+00 0.000E+00 1.040E+07 0.000E+00 1.110E+04 NP-239 1.430E+03 1.400E+02 0.000E+00 4.380E+02 0.000E+00 2.880E+07 0.000E+00 7.740E+01 Appendix G Ri Adult Vegetation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Inhalation (INHL) Units:
mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.260E+03 1.260E+03 1.260E+03 1.260E+03 1.260E+03 0.000E+00 1.260E+03 C-14 1.820E+04 3.410E+03 3.410E+03 3.410E+03 3.410E+03 3.410E+03 0.000E+00 3.410E+03 NA-24 1.020E+04 1.020E+04 1.020E+04 1.020E+04 1.020E+04 1.020E+04 0.000E+00 1.020E+04 P-32 1.320E+06 7.710E+04 0.000E+00 0.000E+00 0.000E+00 8.640E+04 0.000E+00 5.010E+04 CR-51 0.000E+00 0.000E+00 5.950E+01 2.280E+01 1.440E+04 3.320E+03 0.000E+00 1.000E+02 MN-54 0.000E+00 3.960E+04 0.000E+00 9.840E+03 1.400E+06 7.740E+04 0.000E+00 6.300E+03 MN-56 0.000E+00 1.240E+00 0.000E+00 1.300E+00 9.440E+03 2.020E+04 0.000E+00 1.830E-01 FE-55 2.460E+04 1.700E+04 0.000E+00 0.000E+00 7.210E+04 6.030E+03 0.000E+00 3.940E+03 FE-59 1.180E+04 2.780E+04 0.000E+00 0.000E+00 1.020E+06 1.880E+05 0.000E+00 1.060E+04 CO-58 0.000E+00 1.580E+03 0.000E+00 0.000E+00 9.280E+05 1.060E+05 0.000E+00 2.070E+03 CO-60 0.000E+00 1.150E+04 0.000E+00 0.000E+00 5.970E+06 2.850E+05 0.000E+00 1.480E+04 NI-63 4.320E+05 3.140E+04 0.000E+00 0.000E+00 1.780E+05 1.340E+04 0.000E+00 1.450E+04 NI-65 1.540E+00 2.100E-01 0.000E+00 0.000E+00 5.600E+03 1.230E+04 0.000E+00 9.120E-02 CU-64 0.000E+00 1.460E+00 0.000E+00 4.620E+00 6.780E+03 4.900E+04 0.000E+00 6.150E-01 ZN-65 3.240E+04 1.030E+05 0.000E+00 6.900E+04 8.640E+05 5.340E+04 0.000E+00 4.660E+04 ZN-69 3.380E-02 6.510E-02 0.000E+00 4.220E-02 9.200E+02 1.630E+01 0.000E+00 4.520E-03 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.320E+02 0.000E+00 2.410E+02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.640E-03 0.000E+00 3.130E+02 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.280E+01 RB-86 0.000E+00 1.350E+05 0.000E+00 0.000E+00 0.000E+00 1.660E+04 0.000E+00 5.900E+04 RB-88 0.000E+00 3.870E+02 0.000E+00 0.000E+00 0.000E+00 3.340E-09 0.000E+00 1.930E+02 RB-89 0.000E+00 2.560E+02 0.000E+00 0.000E+00 0.000E+00 9.280E-12 0.000E+00 1.700E+02 SR-89 3.040E+05 0.000E+00 0.000E+00 0.000E+00 1.400E+06 3.500E+05 0.000E+00 8.720E+03 SR-90 9.920E+07 0.000E+00 0.000E+00 0.000E+00 9.600E+06 7.220E+05 0.000E+00 6.100E+06 SR-91 6.190E+01 0.000E+00 0.000E+00 0.000E+00 3.650E+04 1.910E+05 0.000E+00 2.500E+00 Appendix G Ri Adult Inhalation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Inhalation (INHL) Units:
mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 6.740E+00 0.000E+00 0.000E+00 0.000E+00 1.650E+04 4.300E+04 0.000E+00 2.910E-01 Y-90 2.090E+03 0.000E+00 0.000E+00 0.000E+00 1.700E+05 5.060E+05 0.000E+00 5.610E+01 Y-91 4.620E+05 0.000E+00 0.000E+00 0.000E+00 1.700E+06 3.850E+05 0.000E+00 1.240E+04 Y-91M 2.610E-01 0.000E+00 0.000E+00 0.000E+00 1.920E+03 1.330E+00 0.000E+00 1.020E-02 Y-92 1.030E+01 0.000E+00 0.000E+00 0.000E+00 1.570E+04 7.350E+04 0.000E+00 3.020E-01 Y-93 9.440E+01 0.000E+00 0.000E+00 0.000E+00 4.850E+04 4.220E+05 0.000E+00 2.610E+00 ZR-95 1.070E+05 3.440E+04 0.000E+00 5.420E+04 1.770E+06 1.500E+05 0.000E+00 2.330E+04 ZR-97 9.680E+01 1.960E+01 0.000E+00 2.970E+01 7.870E+04 5.230E+05 0.000E+00 9.040E+00 NB-95 1.410E+04 7.820E+03 0.000E+00 7.740E+03 5.050E+05 1.040E+05 0.000E+00 4.210E+03 MO-99 0.000E+00 1.210E+02 0.000E+00 2.910E+02 9.120E+04 2.480E+05 0.000E+00 2.300E+01 TC-99M 1.030E-03 2.910E-03 0.000E+00 4.420E-02 7.640E+02 4.160E+03 0.000E+00 3.700E-02 TC-101 4.180E-05 6.020E-05 0.000E+00 1.080E-03 3.990E+02 1.090E-11 0.000E+00 5.900E-04 RU-103 1.530E+03 0.000E+00 0.000E+00 5.830E+03 5.050E+05 1.100E+05 0.000E+00 6.580E+02 RU-105 7.900E-01 0.000E+00 0.000E+00 1.020E+00 1.100E+04 4.820E+04 0.000E+00 3.110E-01 RU-106 6.910E+04 0.000E+00 0.000E+00 1.340E+05 9.360E+06 9.120E+05 0.000E+00 8.720E+03 AG-110M 1.080E+04 1.000E+04 0.000E+00 1.970E+04 4.630E+06 3.020E+05 0.000E+00 5.940E+03 TE-125M 3.420E+03 1.580E+03 1.050E+03 1.240E+04 3.140E+05 7.060E+04 0.000E+00 4.670E+02 TE-127 1.400E+00 6.420E-01 1.060E+00 5.100E+00 6.510E+03 5.740E+04 0.000E+00 3.100E-01 TE-127M 1.260E+04 5.770E+03 3.290E+03 4.580E+04 9.600E+05 1.500E+05 0.000E+00 1.570E+03 TE-129 4.980E-02 2.390E-02 3.900E-02 1.870E-01 1.940E+03 1.570E+02 0.000E+00 1.240E-02 TE-129M 9.760E+03 4.670E+03 3.440E+03 3.660E+04 1.160E+06 3.830E+05 0.000E+00 1.580E+03 TE-131 1.110E-02 5.950E-03 9.360E-03 4.370E-02 1.390E+03 1.840E+01 0.000E+00 3.590E-03 TE-131M 6.990E+01 4.360E+01 5.500E+01 3.090E+02 1.460E+05 5.560E+05 0.000E+00 2.900E+01 TE-132 2.600E+02 2.150E+02 1.900E+02 1.460E+03 2.880E+05 5.100E+05 0.000E+00 1.620E+02 I-130 4.580E+03 1.340E+04 1.140E+06 2.090E+04 0.000E+00 7.690E+03 0.000E+00 5.280E+03 Appendix G Ri Adult Inhalation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Inhalation (INHL) Units:
mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 2.520E+04 3.580E+04 1.190E+07 6.130E+04 0.000E+00 6.280E+03 0.000E+00 2.050E+04 I-132 1.160E+03 3.260E+03 1.140E+05 5.180E+03 0.000E+00 4.060E+02 0.000E+00 1.160E+03 I-133 8.640E+03 1.480E+04 2.150E+06 2.580E+04 0.000E+00 8.880E+03 0.000E+00 4.520E+03 I-134 6.440E+02 1.730E+03 2.980E+04 2.750E+03 0.000E+00 1.010E+00 0.000E+00 6.150E+02 I-135 2.680E+03 6.980E+03 4.480E+05 1.110E+04 0.000E+00 5.250E+03 0.000E+00 2.570E+03 CS-134 3.730E+05 8.480E+05 0.000E+00 2.870E+05 9.760E+04 1.040E+04 0.000E+00 7.280E+05 CS-136 3.900E+04 1.460E+05 0.000E+00 8.560E+04 1.200E+04 1.170E+04 0.000E+00 1.100E+05 CS-137 4.780E+05 6.210E+05 0.000E+00 2.220E+05 7.520E+04 8.400E+03 0.000E+00 4.280E+05 CS-138 3.310E+02 6.210E+02 0.000E+00 4.800E+02 4.860E+01 1.860E-03 0.000E+00 3.240E+02 BA-139 9.360E-01 6.660E-04 0.000E+00 6.220E-04 3.760E+03 8.960E+02 0.000E+00 2.740E-02 BA-140 3.900E+04 4.900E+01 0.000E+00 1.670E+01 1.270E+06 2.180E+05 0.000E+00 2.570E+03 BA-141 1.000E-01 7.530E-05 0.000E+00 7.000E-05 1.940E+03 1.160E-07 0.000E+00 3.360E-03 BA-142 2.630E-02 2.700E-05 0.000E+00 2.290E-05 1.190E+03 1.570E-16 0.000E+00 1.660E-03 LA-140 3.440E+02 1.740E+02 0.000E+00 0.000E+00 1.360E+05 4.580E+05 0.000E+00 4.580E+01 LA-142 6.830E-01 3.100E-01 0.000E+00 0.000E+00 6.330E+03 2.110E+03 0.000E+00 7.720E-02 CE-141 1.990E+04 1.350E+04 0.000E+00 6.260E+03 3.620E+05 1.200E+05 0.000E+00 1.530E+03 CE-143 1.860E+02 1.380E+02 0.000E+00 6.080E+01 7.980E+04 2.260E+05 0.000E+00 1.530E+01 CE-144 3.430E+06 1.430E+06 0.000E+00 8.480E+05 7.780E+06 8.160E+05 0.000E+00 1.840E+05 PR-143 9.360E+03 3.750E+03 0.000E+00 2.160E+03 2.810E+05 2.000E+05 0.000E+00 4.640E+02 PR-144 3.010E-02 1.250E-02 0.000E+00 7.050E-03 1.020E+03 2.150E-08 0.000E+00 1.530E-03 ND-147 5.270E+03 6.100E+03 0.000E+00 3.560E+03 2.210E+05 1.730E+05 0.000E+00 3.650E+02 W-187 8.480E+00 7.080E+00 0.000E+00 0.000E+00 2.900E+04 1.550E+05 0.000E+00 2.480E+00 NP-239 2.300E+02 2.260E+01 0.000E+00 7.000E+01 3.760E+04 1.190E+05 0.000E+00 1.240E+01 Appendix G Ri Adult Inhalation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.390E+07 1.190E+07 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 5.510E+06 4.660E+06 MN-54 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.630E+09 1.390E+09 MN-56 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 1.070E+06 9.020E+05 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 3.210E+08 2.730E+08 CO-58 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 4.440E+08 3.790E+08 CO-60 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.530E+10 2.150E+10 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 3.450E+05 2.970E+05 CU-64 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.880E+05 6.070E+05 ZN-65 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 8.590E+08 7.470E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 7.080E+03 4.870E+03 BR-84 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.360E+05 2.030E+05 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 1.030E+07 8.990E+06 RB-88 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.780E+04 3.310E+04 RB-89 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.480E+05 1.230E+05 SR-89 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.510E+04 2.160E+04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.510E+06 2.150E+06 Appendix G Ri Adult Ground Plane Deposition - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 8.630E+05 7.770E+05 Y-90 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 5.310E+03 4.490E+03 Y-91 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.210E+06 1.070E+06 Y-91M 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.160E+05 1.000E+05 Y-92 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 2.140E+05 1.800E+05 Y-93 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 2.510E+05 1.830E+05 ZR-95 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.840E+08 2.450E+08 ZR-97 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 3.440E+06 2.960E+06 NB-95 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.610E+08 1.370E+08 MO-99 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 4.630E+06 3.990E+06 TC-99M 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 2.110E+05 1.840E+05 TC-101 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.260E+04 2.040E+04 RU-103 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.260E+08 1.080E+08 RU-105 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 7.210E+05 6.360E+05 RU-106 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 5.070E+08 4.220E+08 AG-110M 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 4.010E+09 3.440E+09 TE-125M 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 2.130E+06 1.550E+06 TE-127 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 3.280E+03 2.980E+03 TE-127M 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 1.080E+05 9.160E+04 TE-129 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 3.100E+04 2.620E+04 TE-129M 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 2.310E+07 1.980E+07 TE-131 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 3.450E+07 2.920E+04 TE-131M 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 9.460E+06 8.030E+06 TE-132 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.980E+06 4.230E+06 I-130 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 6.690E+06 5.510E+06 Appendix G Ri Adult Ground Plane Deposition - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX G Ri Adult Dose Factors for use in the Gaseous Dose Calculations Agegroup: ADULT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 2.090E+07 1.720E+07 I-132 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.470E+06 1.250E+06 I-133 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.980E+06 2.450E+06 I-134 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 5.300E+05 4.470E+05 I-135 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.950E+06 2.530E+06 CS-134 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 8.000E+09 6.860E+09 CS-136 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.710E+08 1.510E+08 CS-137 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.200E+10 1.030E+10 CS-138 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 4.100E+05 3.590E+05 BA-139 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.190E+05 1.060E+05 BA-140 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.350E+07 2.050E+07 BA-141 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.750E+04 4.170E+04 BA-142 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 5.110E+04 4.490E+04 LA-140 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 2.180E+07 1.920E+07 LA-142 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 9.120E+05 7.600E+05 CE-141 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.540E+07 1.370E+07 CE-143 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.630E+06 2.310E+06 CE-144 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 8.040E+07 6.950E+07 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 2.110E+03 1.830E+03 ND-147 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 1.010E+07 8.390E+06 W-187 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.730E+06 2.350E+06 NP-239 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.980E+06 1.710E+06 Appendix G Ri Adult Ground Plane Deposition - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 9.940E+02 9.940E+02 9.940E+02 9.940E+02 9.940E+02 0.000E+00 9.940E+02 C-14 4.860E+08 9.720E+07 9.720E+07 9.720E+07 9.720E+07 9.720E+07 0.000E+00 9.720E+07 NA-24 4.260E+06 4.260E+06 4.260E+06 4.260E+06 4.260E+06 4.260E+06 0.000E+00 4.260E+06 P-32 3.150E+10 1.950E+09 0.000E+00 0.000E+00 0.000E+00 2.650E+09 0.000E+00 1.220E+09 CR-51 0.000E+00 0.000E+00 2.770E+04 1.090E+04 7.130E+04 8.390E+06 0.000E+00 4.990E+04 MN-54 0.000E+00 1.400E+07 0.000E+00 4.180E+06 0.000E+00 2.870E+07 0.000E+00 2.780E+06 MN-56 0.000E+00 7.250E-03 0.000E+00 9.180E-03 0.000E+00 4.770E-01 0.000E+00 1.290E-03 FE-55 4.450E+07 3.160E+07 0.000E+00 0.000E+00 2.000E+07 1.370E+07 0.000E+00 7.360E+06 FE-59 5.180E+07 1.210E+08 0.000E+00 0.000E+00 3.810E+07 2.860E+08 0.000E+00 4.670E+07 CO-58 0.000E+00 7.940E+06 0.000E+00 0.000E+00 0.000E+00 1.090E+08 0.000E+00 1.830E+07 CO-60 0.000E+00 2.780E+07 0.000E+00 0.000E+00 0.000E+00 3.620E+08 0.000E+00 6.260E+07 NI-63 1.180E+10 8.350E+08 0.000E+00 0.000E+00 0.000E+00 1.330E+08 0.000E+00 4.010E+08 NI-65 6.770E-01 8.650E-02 0.000E+00 0.000E+00 0.000E+00 4.690E+00 0.000E+00 3.940E-02 CU-64 0.000E+00 4.250E+04 0.000E+00 1.070E+05 0.000E+00 3.290E+06 0.000E+00 2.000E+04 ZN-65 2.110E+09 7.320E+09 0.000E+00 4.680E+09 0.000E+00 3.100E+09 0.000E+00 3.410E+09 ZN-69 3.850E-12 7.330E-12 0.000E+00 4.790E-12 0.000E+00 1.350E-11 0.000E+00 5.130E-13 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.790E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.880E-23 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 4.730E+09 0.000E+00 0.000E+00 0.000E+00 7.000E+08 0.000E+00 2.220E+09 RB-88 0.000E+00 3.890E-45 0.000E+00 0.000E+00 0.000E+00 3.330E-52 0.000E+00 2.070E-45 RB-89 0.000E+00 7.660E-53 0.000E+00 0.000E+00 0.000E+00 1.170E-61 0.000E+00 5.420E-53 SR-89 2.670E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.190E+08 0.000E+00 7.660E+07 SR-90 6.610E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.860E+09 0.000E+00 1.630E+10 SR-91 5.310E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.410E+05 0.000E+00 2.110E+03 Appendix H Ri Teen Cow Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 8.940E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.280E+01 0.000E+00 3.810E-02 Y-90 1.300E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.070E+06 0.000E+00 3.510E+00 Y-91 1.580E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.480E+06 0.000E+00 4.240E+02 Y-91M 1.090E-19 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.170E-18 0.000E+00 4.180E-21 Y-92 1.030E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.830E+00 0.000E+00 2.980E-06 Y-93 4.120E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.260E+04 0.000E+00 1.130E-02 ZR-95 1.650E+03 5.200E+02 0.000E+00 7.650E+02 0.000E+00 1.200E+06 0.000E+00 3.580E+02 ZR-97 7.880E-01 1.560E-01 0.000E+00 2.370E-01 0.000E+00 4.220E+04 0.000E+00 7.190E-02 NB-95 1.410E+05 7.810E+04 0.000E+00 7.570E+04 0.000E+00 3.340E+08 0.000E+00 4.300E+04 MO-99 0.000E+00 4.470E+07 0.000E+00 1.020E+08 0.000E+00 8.010E+07 0.000E+00 8.530E+06 TC-99M 5.760E+00 1.610E+01 0.000E+00 2.390E+02 8.920E+00 1.050E+04 0.000E+00 2.080E+02 TC-101 4.740E-60 6.750E-60 0.000E+00 1.220E-58 4.110E-60 1.150E-66 0.000E+00 6.630E-59 RU-103 1.810E+03 0.000E+00 0.000E+00 6.380E+03 0.000E+00 1.510E+05 0.000E+00 7.740E+02 RU-105 1.560E-03 0.000E+00 0.000E+00 1.970E-02 0.000E+00 1.260E+00 0.000E+00 6.070E-04 RU-106 3.750E+04 0.000E+00 0.000E+00 7.240E+04 0.000E+00 1.800E+06 0.000E+00 4.730E+03 AG-110M 9.630E+07 9.110E+07 0.000E+00 1.740E+08 0.000E+00 2.560E+10 0.000E+00 5.540E+07 TE-125M 3.000E+07 1.080E+07 8.390E+06 0.000E+00 0.000E+00 8.860E+07 0.000E+00 4.020E+06 TE-127 1.210E+03 4.290E+02 8.350E+02 4.900E+03 0.000E+00 9.340E+04 0.000E+00 2.600E+02 TE-127M 8.440E+07 2.990E+07 2.010E+07 3.420E+08 0.000E+00 2.100E+08 0.000E+00 1.000E+07 TE-129 5.200E-10 1.940E-10 3.720E-10 2.180E-09 0.000E+00 2.840E-09 0.000E+00 1.270E-10 TE-129M 1.100E+08 4.090E+07 3.550E+07 4.610E+08 0.000E+00 4.130E+08 0.000E+00 1.740E+07 TE-131 6.580E-33 2.710E-33 5.070E-33 2.880E-32 0.000E+00 5.400E-34 0.000E+00 2.060E-33 TE-131M 6.570E+05 3.150E+05 4.740E+05 3.290E+06 0.000E+00 2.530E+07 0.000E+00 2.630E+05 TE-132 4.290E+06 2.720E+06 2.870E+06 2.610E+07 0.000E+00 8.610E+07 0.000E+00 2.560E+06 I-130 7.380E+05 2.140E+06 1.740E+08 3.290E+06 0.000E+00 1.640E+06 0.000E+00 8.530E+05 Appendix H Ri Teen Cow Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 5.370E+08 7.520E+08 2.190E+11 1.290E+09 0.000E+00 1.490E+08 0.000E+00 4.040E+08 I-132 2.910E-01 7.620E-01 2.570E+01 1.200E+00 0.000E+00 3.320E-01 0.000E+00 2.740E-01 I-133 7.070E+06 1.200E+07 1.670E+09 2.100E+07 0.000E+00 9.070E+06 0.000E+00 3.660E+06 I-134 3.580E-12 9.500E-12 1.580E-10 1.500E-11 0.000E+00 1.250E-13 0.000E+00 3.410E-12 I-135 2.280E+04 5.870E+04 3.780E+06 9.270E+04 0.000E+00 6.510E+04 0.000E+00 2.180E+04 CS-134 9.820E+09 2.310E+10 0.000E+00 7.340E+09 2.800E+09 2.870E+08 0.000E+00 1.070E+10 CS-136 4.480E+08 1.760E+09 0.000E+00 9.600E+08 1.510E+08 1.420E+08 0.000E+00 1.180E+09 CS-137 1.340E+10 1.780E+10 0.000E+00 6.060E+09 2.350E+09 2.530E+08 0.000E+00 6.200E+09 CS-138 1.640E-23 3.150E-23 0.000E+00 2.330E-23 2.710E-24 1.430E-26 0.000E+00 1.580E-23 BA-139 8.170E-08 5.750E-11 0.000E+00 5.420E-11 3.960E-11 7.290E-07 0.000E+00 2.380E-09 BA-140 4.850E+07 5.950E+04 0.000E+00 2.020E+04 4.000E+04 7.480E+07 0.000E+00 3.130E+06 BA-141 7.520E-46 5.620E-49 0.000E+00 5.210E-49 3.850E-49 1.600E-51 0.000E+00 2.510E-47 BA-142 4.790E-80 4.790E-83 0.000E+00 4.050E-83 3.190E-83 1.470E-91 0.000E+00 2.950E-81 LA-140 8.100E+00 3.980E+00 0.000E+00 0.000E+00 0.000E+00 2.290E+05 0.000E+00 1.060E+00 LA-142 3.360E-11 1.490E-11 0.000E+00 0.000E+00 0.000E+00 4.540E-07 0.000E+00 3.710E-12 CE-141 8.880E+03 5.930E+03 0.000E+00 2.790E+03 0.000E+00 1.700E+07 0.000E+00 6.810E+02 CE-143 7.640E+01 5.560E+04 0.000E+00 2.490E+01 0.000E+00 1.670E+06 0.000E+00 6.210E+00 CE-144 6.580E+05 2.720E+05 0.000E+00 1.630E+05 0.000E+00 1.660E+08 0.000E+00 3.540E+04 PR-143 2.900E+02 1.160E+02 0.000E+00 6.730E+01 0.000E+00 9.540E+05 0.000E+00 1.440E+01 PR-144 1.080E-53 4.430E-54 0.000E+00 2.540E-54 0.000E+00 1.190E-56 0.000E+00 5.490E-55 ND-147 1.810E+02 1.970E+02 0.000E+00 1.160E+02 0.000E+00 7.110E+05 0.000E+00 1.180E+01 W-187 1.190E+04 9.710E+03 0.000E+00 0.000E+00 0.000E+00 2.630E+06 0.000E+00 3.400E+03 NP-239 7.010E+00 6.610E-01 0.000E+00 2.070E+00 0.000E+00 1.060E+05 0.000E+00 3.670E-01 Appendix H Ri Teen Cow Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.030E+03 2.030E+03 2.030E+03 2.030E+03 2.030E+03 0.000E+00 2.030E+03 C-14 4.860E+08 9.720E+07 9.720E+07 9.720E+07 9.720E+07 9.720E+07 0.000E+00 9.720E+07 NA-24 5.110E+05 5.110E+05 5.110E+05 5.110E+05 5.110E+05 5.110E+05 0.000E+00 5.110E+05 P-32 3.780E+10 2.340E+09 0.000E+00 0.000E+00 0.000E+00 3.180E+09 0.000E+00 1.470E+09 CR-51 0.000E+00 0.000E+00 3.330E+03 1.310E+03 8.550E+03 1.010E+06 0.000E+00 5.990E+03 MN-54 0.000E+00 1.680E+06 0.000E+00 5.020E+05 0.000E+00 3.450E+06 0.000E+00 3.340E+05 MN-56 0.000E+00 8.700E-04 0.000E+00 1.100E-03 0.000E+00 5.730E-02 0.000E+00 1.550E-04 FE-55 5.790E+05 4.110E+05 0.000E+00 0.000E+00 2.600E+05 1.780E+05 0.000E+00 9.570E+04 FE-59 6.740E+05 1.570E+06 0.000E+00 0.000E+00 4.960E+05 3.720E+06 0.000E+00 6.070E+05 CO-58 0.000E+00 9.520E+05 0.000E+00 0.000E+00 0.000E+00 1.310E+07 0.000E+00 2.190E+06 CO-60 0.000E+00 3.340E+06 0.000E+00 0.000E+00 0.000E+00 4.350E+07 0.000E+00 7.520E+06 NI-63 1.420E+09 1.000E+08 0.000E+00 0.000E+00 0.000E+00 1.590E+07 0.000E+00 4.810E+07 NI-65 8.120E-02 1.040E-02 0.000E+00 0.000E+00 0.000E+00 5.630E-01 0.000E+00 4.730E-03 CU-64 0.000E+00 4.730E+03 0.000E+00 1.200E+04 0.000E+00 3.670E+05 0.000E+00 2.230E+03 ZN-65 2.530E+08 8.780E+08 0.000E+00 5.620E+08 0.000E+00 3.720E+08 0.000E+00 4.100E+08 ZN-69 4.620E-13 8.800E-13 0.000E+00 5.750E-13 0.000E+00 1.620E-12 0.000E+00 6.160E-14 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.150E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.450E-24 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 5.670E+08 0.000E+00 0.000E+00 0.000E+00 8.400E+07 0.000E+00 2.670E+08 RB-88 0.000E+00 4.670E-46 0.000E+00 0.000E+00 0.000E+00 4.000E-53 0.000E+00 2.490E-46 RB-89 0.000E+00 9.190E-54 0.000E+00 0.000E+00 0.000E+00 1.410E-62 0.000E+00 6.500E-54 SR-89 5.620E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.690E+08 0.000E+00 1.610E+08 SR-90 1.390E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.900E+09 0.000E+00 3.430E+10 SR-91 1.120E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.060E+05 0.000E+00 4.440E+03 Appendix H Ri Teen Goat Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.880E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.780E+01 0.000E+00 8.000E-02 Y-90 1.560E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.290E+05 0.000E+00 4.210E-01 Y-91 1.900E+03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.770E+05 0.000E+00 5.080E+01 Y-91M 1.310E-20 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.200E-19 0.000E+00 5.020E-22 Y-92 1.240E-05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.390E-01 0.000E+00 3.580E-07 Y-93 4.940E-02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.510E+03 0.000E+00 1.360E-03 ZR-95 1.980E+02 6.250E+01 0.000E+00 9.180E+01 0.000E+00 1.440E+05 0.000E+00 4.300E+01 ZR-97 9.460E-02 1.870E-02 0.000E+00 2.840E-02 0.000E+00 5.070E+03 0.000E+00 8.620E-03 NB-95 1.690E+04 9.370E+03 0.000E+00 9.080E+03 0.000E+00 4.010E+07 0.000E+00 5.160E+03 MO-99 0.000E+00 5.370E+06 0.000E+00 1.230E+07 0.000E+00 9.610E+06 0.000E+00 1.020E+06 TC-99M 6.910E-01 1.930E+00 0.000E+00 2.870E+01 1.070E+00 1.270E+03 0.000E+00 2.500E+01 TC-101 5.690E-61 8.100E-61 0.000E+00 1.460E-59 4.930E-61 1.380E-67 0.000E+00 7.950E-60 RU-103 2.170E+02 0.000E+00 0.000E+00 7.660E+02 0.000E+00 1.810E+04 0.000E+00 9.290E+01 RU-105 1.880E-04 0.000E+00 0.000E+00 2.370E-03 0.000E+00 1.520E-01 0.000E+00 7.290E-05 RU-106 4.500E+03 0.000E+00 0.000E+00 8.680E+03 0.000E+00 2.160E+05 0.000E+00 5.670E+02 AG-110M 1.160E+07 1.090E+07 0.000E+00 2.080E+07 0.000E+00 3.070E+09 0.000E+00 6.650E+06 TE-125M 3.600E+06 1.300E+06 1.010E+06 0.000E+00 0.000E+00 1.060E+07 0.000E+00 4.820E+05 TE-127 1.450E+02 5.150E+01 1.000E+02 5.880E+02 0.000E+00 1.120E+04 0.000E+00 3.120E+01 TE-127M 1.010E+07 3.590E+06 2.410E+06 4.100E+07 0.000E+00 2.520E+07 0.000E+00 1.200E+06 TE-129 6.240E-11 2.330E-11 4.460E-11 2.620E-10 0.000E+00 3.410E-10 0.000E+00 1.520E-11 TE-129M 1.320E+07 4.900E+06 4.260E+06 5.530E+07 0.000E+00 4.960E+07 0.000E+00 2.090E+06 TE-131 7.900E-34 3.260E-34 6.090E-34 3.450E-33 0.000E+00 6.480E-35 0.000E+00 2.470E-34 TE-131M 7.880E+04 3.780E+04 5.690E+04 3.940E+05 0.000E+00 3.030E+06 0.000E+00 3.150E+04 TE-132 5.150E+05 3.260E+05 3.440E+05 3.130E+06 0.000E+00 1.030E+07 0.000E+00 3.070E+05 I-130 8.860E+05 2.560E+06 2.090E+08 3.950E+06 0.000E+00 1.970E+06 0.000E+00 1.020E+06 Appendix H Ri Teen Goat Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 6.450E+08 9.030E+08 2.630E+11 1.550E+09 0.000E+00 1.790E+08 0.000E+00 4.850E+08 I-132 3.500E-01 9.150E-01 3.080E+01 1.440E+00 0.000E+00 3.980E-01 0.000E+00 3.280E-01 I-133 8.480E+06 1.440E+07 2.010E+09 2.520E+07 0.000E+00 1.090E+07 0.000E+00 4.390E+06 I-134 4.300E-12 1.140E-11 1.900E-10 1.800E-11 0.000E+00 1.500E-13 0.000E+00 4.090E-12 I-135 2.740E+04 7.040E+04 4.530E+06 1.110E+05 0.000E+00 7.810E+04 0.000E+00 2.610E+04 CS-134 2.940E+10 6.930E+10 0.000E+00 2.200E+10 8.410E+09 8.620E+08 0.000E+00 3.220E+10 CS-136 1.340E+09 5.290E+09 0.000E+00 2.880E+09 4.540E+08 4.260E+08 0.000E+00 3.550E+09 CS-137 4.020E+10 5.340E+10 0.000E+00 1.820E+10 7.060E+09 7.600E+08 0.000E+00 1.860E+10 CS-138 4.920E-23 9.450E-23 0.000E+00 6.980E-23 8.120E-24 4.290E-26 0.000E+00 4.730E-23 BA-139 9.800E-09 6.900E-12 0.000E+00 6.500E-12 4.750E-12 8.750E-08 0.000E+00 2.860E-10 BA-140 5.820E+06 7.130E+03 0.000E+00 2.420E+03 4.800E+03 8.980E+06 0.000E+00 3.750E+05 BA-141 9.030E-47 6.740E-50 0.000E+00 6.260E-50 4.610E-50 1.920E-52 0.000E+00 3.010E-48 BA-142 5.750E-81 5.750E-84 0.000E+00 4.860E-84 3.820E-84 1.760E-92 0.000E+00 3.540E-82 LA-140 9.720E-01 4.780E-01 0.000E+00 0.000E+00 0.000E+00 2.740E+04 0.000E+00 1.270E-01 LA-142 4.030E-12 1.790E-12 0.000E+00 0.000E+00 0.000E+00 5.440E-08 0.000E+00 4.450E-13 CE-141 1.070E+03 7.120E+02 0.000E+00 3.350E+02 0.000E+00 2.040E+06 0.000E+00 8.170E+01 CE-143 9.170E+00 6.670E+03 0.000E+00 2.990E+00 0.000E+00 2.000E+05 0.000E+00 7.450E-01 CE-144 7.900E+04 3.270E+04 0.000E+00 1.950E+04 0.000E+00 1.990E+07 0.000E+00 4.240E+03 PR-143 3.480E+01 1.390E+01 0.000E+00 8.080E+00 0.000E+00 1.150E+05 0.000E+00 1.730E+00 PR-144 1.300E-54 5.320E-55 0.000E+00 3.050E-55 0.000E+00 1.430E-57 0.000E+00 6.590E-56 ND-147 2.170E+01 2.360E+01 0.000E+00 1.390E+01 0.000E+00 8.530E+04 0.000E+00 1.420E+00 W-187 1.430E+03 1.170E+03 0.000E+00 0.000E+00 0.000E+00 3.150E+05 0.000E+00 4.080E+02 NP-239 8.410E-01 7.930E-02 0.000E+00 2.490E-01 0.000E+00 1.280E+04 0.000E+00 4.410E-02 Appendix H Ri Teen Goat Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.940E+02 1.940E+02 1.940E+02 1.940E+02 1.940E+02 0.000E+00 1.940E+02 C-14 2.040E+08 4.080E+07 4.080E+07 4.080E+07 4.080E+07 4.080E+07 0.000E+00 4.080E+07 NA-24 1.080E-03 1.080E-03 1.080E-03 1.080E-03 1.080E-03 1.080E-03 0.000E+00 1.080E-03 P-32 3.930E+09 2.440E+08 0.000E+00 0.000E+00 0.000E+00 3.310E+08 0.000E+00 1.530E+08 CR-51 0.000E+00 0.000E+00 3.130E+03 1.240E+03 8.050E+03 9.470E+05 0.000E+00 5.640E+03 MN-54 0.000E+00 7.000E+06 0.000E+00 2.090E+06 0.000E+00 1.440E+07 0.000E+00 1.390E+06 MN-56 0.000E+00 1.070E-53 0.000E+00 1.360E-53 0.000E+00 7.070E-52 0.000E+00 1.910E-54 FE-55 2.380E+08 1.690E+08 0.000E+00 0.000E+00 1.070E+08 7.310E+07 0.000E+00 3.940E+07 FE-59 2.120E+08 4.950E+08 0.000E+00 0.000E+00 1.560E+08 1.170E+09 0.000E+00 1.910E+08 CO-58 0.000E+00 1.410E+07 0.000E+00 0.000E+00 0.000E+00 1.940E+08 0.000E+00 3.240E+07 CO-60 0.000E+00 5.830E+07 0.000E+00 0.000E+00 0.000E+00 7.600E+08 0.000E+00 1.310E+08 NI-63 1.520E+10 1.070E+09 0.000E+00 0.000E+00 0.000E+00 1.710E+08 0.000E+00 5.150E+08 NI-65 1.880E-52 2.410E-53 0.000E+00 0.000E+00 0.000E+00 1.300E-51 0.000E+00 1.100E-53 CU-64 0.000E+00 2.210E-07 0.000E+00 5.600E-07 0.000E+00 1.720E-05 0.000E+00 1.040E-07 ZN-65 2.500E+08 8.690E+08 0.000E+00 5.560E+08 0.000E+00 3.680E+08 0.000E+00 4.050E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.070E-57 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 4.070E+08 0.000E+00 0.000E+00 0.000E+00 6.020E+07 0.000E+00 1.910E+08 RB-88 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-89 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-89 2.550E+08 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.030E+07 0.000E+00 7.290E+06 SR-90 8.050E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.260E+08 0.000E+00 1.990E+09 SR-91 1.280E-10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.800E-10 0.000E+00 5.090E-12 Appendix H Ri Teen Cow Meat - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 9.880E-50 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.520E-48 0.000E+00 4.210E-51 Y-90 9.060E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.470E+05 0.000E+00 2.440E+00 Y-91 9.540E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.910E+08 0.000E+00 2.560E+04 Y-91M 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 Y-92 1.280E-39 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.520E-35 0.000E+00 3.710E-41 Y-93 3.960E-12 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.210E-07 0.000E+00 1.090E-13 ZR-95 1.500E+06 4.730E+05 0.000E+00 6.950E+05 0.000E+00 1.090E+09 0.000E+00 3.250E+05 ZR-97 1.720E-05 3.410E-06 0.000E+00 5.170E-06 0.000E+00 9.230E-01 0.000E+00 1.570E-06 NB-95 1.790E+06 9.950E+05 0.000E+00 9.650E+05 0.000E+00 4.260E+09 0.000E+00 5.480E+05 MO-99 0.000E+00 8.270E+04 0.000E+00 1.890E+05 0.000E+00 1.480E+05 0.000E+00 1.580E+04 TC-99M 3.530E-21 9.850E-21 0.000E+00 1.470E-19 5.470E-21 6.470E-18 0.000E+00 1.280E-19 TC-101 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RU-103 8.570E+07 0.000E+00 0.000E+00 3.020E+08 0.000E+00 7.160E+09 0.000E+00 3.660E+07 RU-105 4.830E-28 0.000E+00 0.000E+00 6.090E-27 0.000E+00 3.900E-25 0.000E+00 1.880E-28 RU-106 2.360E+09 0.000E+00 0.000E+00 4.550E+09 0.000E+00 1.130E+11 0.000E+00 2.970E+08 AG-110M 5.060E+06 4.790E+06 0.000E+00 9.130E+06 0.000E+00 1.340E+09 0.000E+00 2.910E+06 TE-125M 3.030E+08 1.090E+08 8.470E+07 0.000E+00 0.000E+00 8.940E+08 0.000E+00 4.050E+07 TE-127 1.800E-10 6.380E-11 1.240E-10 7.290E-10 0.000E+00 1.390E-08 0.000E+00 3.870E-11 TE-127M 9.410E+08 3.340E+08 2.240E+08 3.820E+09 0.000E+00 2.350E+09 0.000E+00 1.120E+08 TE-129 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 TE-129M 9.500E+08 3.530E+08 3.070E+08 3.970E+09 0.000E+00 3.570E+09 0.000E+00 1.500E+08 TE-131 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 TE-131M 3.760E+02 1.800E+02 2.710E+02 1.880E+03 0.000E+00 1.450E+04 0.000E+00 1.500E+02 TE-132 1.160E+06 7.360E+05 7.750E+05 7.060E+06 0.000E+00 2.330E+07 0.000E+00 6.920E+05 I-130 1.700E-06 4.910E-06 4.000E-04 7.560E-06 0.000E+00 3.770E-06 0.000E+00 1.960E-06 Appendix H Ri Teen Cow Meat - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 8.920E+06 1.250E+07 3.650E+09 2.150E+07 0.000E+00 2.470E+06 0.000E+00 6.710E+06 I-132 5.660E-59 1.480E-58 4.990E-57 2.330E-58 0.000E+00 6.450E-59 0.000E+00 5.320E-59 I-133 3.050E-01 5.180E-01 7.230E+01 9.090E-01 0.000E+00 3.920E-01 0.000E+00 1.580E-01 I-134 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 I-135 3.600E-17 9.260E-17 5.960E-15 1.460E-16 0.000E+00 1.030E-16 0.000E+00 3.430E-17 CS-134 5.230E+08 1.230E+09 0.000E+00 3.910E+08 1.490E+08 1.530E+07 0.000E+00 5.710E+08 CS-136 9.400E+06 3.700E+07 0.000E+00 2.010E+07 3.170E+06 2.980E+06 0.000E+00 2.480E+07 CS-137 7.240E+08 9.630E+08 0.000E+00 3.280E+08 1.270E+08 1.370E+07 0.000E+00 3.360E+08 CS-138 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-139 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-140 2.380E+07 2.910E+04 0.000E+00 9.870E+03 1.960E+04 3.660E+07 0.000E+00 1.530E+06 BA-141 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-142 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 LA-140 3.050E-02 1.500E-02 0.000E+00 0.000E+00 0.000E+00 8.610E+02 0.000E+00 3.990E-03 LA-142 2.870E-92 1.280E-92 0.000E+00 0.000E+00 0.000E+00 3.880E-88 0.000E+00 3.180E-93 CE-141 1.180E+04 7.870E+03 0.000E+00 3.710E+03 0.000E+00 2.250E+07 0.000E+00 9.040E+02 CE-143 1.690E-02 1.230E+01 0.000E+00 5.510E-03 0.000E+00 3.690E+02 0.000E+00 1.370E-03 CE-144 1.230E+06 5.080E+05 0.000E+00 3.040E+05 0.000E+00 3.090E+08 0.000E+00 6.600E+04 PR-143 1.760E+04 7.040E+03 0.000E+00 4.090E+03 0.000E+00 5.800E+07 0.000E+00 8.780E+02 PR-144 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 ND-147 6.230E+03 6.770E+03 0.000E+00 3.980E+03 0.000E+00 2.440E+07 0.000E+00 4.060E+02 W-187 1.730E-02 1.410E-02 0.000E+00 0.000E+00 0.000E+00 3.820E+00 0.000E+00 4.940E-03 NP-239 2.260E-01 2.140E-02 0.000E+00 6.700E-02 0.000E+00 3.440E+03 0.000E+00 1.190E-02 Appendix H Ri Teen Cow Meat - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.590E+03 2.590E+03 2.590E+03 2.590E+03 2.590E+03 0.000E+00 2.590E+03 C-14 3.690E+08 7.380E+07 7.380E+07 7.380E+07 7.380E+07 7.380E+07 0.000E+00 7.380E+07 NA-24 2.390E+05 2.390E+05 2.390E+05 2.390E+05 2.390E+05 2.390E+05 0.000E+00 2.390E+05 P-32 1.610E+09 9.970E+07 0.000E+00 0.000E+00 0.000E+00 1.350E+08 0.000E+00 6.240E+07 CR-51 0.000E+00 0.000E+00 3.430E+04 1.350E+04 8.810E+04 1.040E+07 0.000E+00 6.170E+04 MN-54 0.000E+00 4.540E+08 0.000E+00 1.360E+08 0.000E+00 9.320E+08 0.000E+00 9.010E+07 MN-56 0.000E+00 1.420E+01 0.000E+00 1.800E+01 0.000E+00 9.360E+02 0.000E+00 2.530E+00 FE-55 3.260E+08 2.310E+08 0.000E+00 0.000E+00 1.470E+08 1.000E+08 0.000E+00 5.390E+07 FE-59 1.790E+08 4.190E+08 0.000E+00 0.000E+00 1.320E+08 9.900E+08 0.000E+00 1.620E+08 CO-58 0.000E+00 4.360E+07 0.000E+00 0.000E+00 0.000E+00 6.010E+08 0.000E+00 1.000E+08 CO-60 0.000E+00 2.490E+08 0.000E+00 0.000E+00 0.000E+00 3.240E+09 0.000E+00 5.600E+08 NI-63 1.610E+10 1.130E+09 0.000E+00 0.000E+00 0.000E+00 1.810E+08 0.000E+00 5.450E+08 NI-65 5.720E+01 7.310E+00 0.000E+00 0.000E+00 0.000E+00 3.970E+02 0.000E+00 3.330E+00 CU-64 0.000E+00 8.340E+03 0.000E+00 2.110E+04 0.000E+00 6.470E+05 0.000E+00 3.920E+03 ZN-65 4.240E+08 1.470E+09 0.000E+00 9.420E+08 0.000E+00 6.230E+08 0.000E+00 6.870E+08 ZN-69 5.140E-06 9.800E-06 0.000E+00 6.400E-06 0.000E+00 1.810E-05 0.000E+00 6.860E-07 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.910E+00 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.250E-11 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.740E+08 0.000E+00 0.000E+00 0.000E+00 4.050E+07 0.000E+00 1.290E+08 RB-88 0.000E+00 3.170E-22 0.000E+00 0.000E+00 0.000E+00 2.720E-29 0.000E+00 1.690E-22 RB-89 0.000E+00 3.500E-26 0.000E+00 0.000E+00 0.000E+00 5.360E-35 0.000E+00 2.470E-26 SR-89 1.510E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.800E+09 0.000E+00 4.340E+08 SR-90 7.510E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.110E+10 0.000E+00 1.850E+11 SR-91 2.850E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.290E+06 0.000E+00 1.130E+04 Appendix H Ri Teen Vegetation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 3.970E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.010E+04 0.000E+00 1.690E+01 Y-90 1.240E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.020E+08 0.000E+00 3.350E+02 Y-91 7.840E+06 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.210E+09 0.000E+00 2.100E+05 Y-91M 4.860E-09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.290E-07 0.000E+00 1.860E-10 Y-92 8.600E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.360E+04 0.000E+00 2.490E-02 Y-93 1.590E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.860E+06 0.000E+00 4.360E+00 ZR-95 1.720E+06 5.430E+05 0.000E+00 7.980E+05 0.000E+00 1.250E+09 0.000E+00 3.730E+05 ZR-97 3.120E+02 6.180E+01 0.000E+00 9.370E+01 0.000E+00 1.670E+07 0.000E+00 2.850E+01 NB-95 1.920E+05 1.070E+05 0.000E+00 1.030E+05 0.000E+00 4.560E+08 0.000E+00 5.870E+04 MO-99 0.000E+00 5.650E+06 0.000E+00 1.290E+07 0.000E+00 1.010E+07 0.000E+00 1.080E+06 TC-99M 2.740E+00 7.630E+00 0.000E+00 1.140E+02 4.240E+00 5.010E+03 0.000E+00 9.890E+01 TC-101 7.640E-31 1.090E-30 0.000E+00 1.970E-29 6.620E-31 1.860E-37 0.000E+00 1.070E-29 RU-103 6.820E+06 0.000E+00 0.000E+00 2.400E+07 0.000E+00 5.700E+08 0.000E+00 2.920E+06 RU-105 5.000E+01 0.000E+00 0.000E+00 6.310E+02 0.000E+00 4.040E+04 0.000E+00 1.940E+01 RU-106 3.100E+08 0.000E+00 0.000E+00 5.970E+08 0.000E+00 1.480E+10 0.000E+00 3.900E+07 AG-110M 1.520E+07 1.430E+07 0.000E+00 2.740E+07 0.000E+00 4.030E+09 0.000E+00 8.720E+06 TE-125M 1.480E+08 5.340E+07 4.140E+07 0.000E+00 0.000E+00 4.370E+08 0.000E+00 1.980E+07 TE-127 5.330E+03 1.890E+03 3.680E+03 2.160E+04 0.000E+00 4.120E+05 0.000E+00 1.150E+03 TE-127M 5.510E+08 1.960E+08 1.310E+08 2.240E+09 0.000E+00 1.370E+09 0.000E+00 6.560E+07 TE-129 7.140E-04 2.660E-04 5.100E-04 3.000E-03 0.000E+00 3.910E-03 0.000E+00 1.740E-04 TE-129M 3.620E+08 1.340E+08 1.170E+08 1.510E+09 0.000E+00 1.360E+09 0.000E+00 5.730E+07 TE-131 1.390E-15 5.750E-16 1.070E-15 6.100E-15 0.000E+00 1.140E-16 0.000E+00 4.360E-16 TE-131M 8.440E+05 4.050E+05 6.090E+05 4.220E+06 0.000E+00 3.250E+07 0.000E+00 3.380E+05 TE-132 3.910E+06 2.470E+06 2.610E+06 2.370E+07 0.000E+00 7.840E+07 0.000E+00 2.330E+06 I-130 3.510E+05 1.010E+06 8.280E+07 1.560E+06 0.000E+00 7.800E+05 0.000E+00 4.050E+05 Appendix H Ri Teen Vegetation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 7.690E+07 1.080E+08 3.140E+10 1.850E+08 0.000E+00 2.130E+07 0.000E+00 5.780E+07 I-132 5.190E+01 1.360E+02 4.580E+03 2.140E+02 0.000E+00 5.920E+01 0.000E+00 4.880E+01 I-133 1.940E+06 3.290E+06 4.590E+08 5.760E+06 0.000E+00 2.490E+06 0.000E+00 1.000E+06 I-134 8.720E-05 2.310E-04 3.850E-03 3.640E-04 0.000E+00 3.050E-06 0.000E+00 8.310E-05 I-135 3.520E+04 9.070E+04 5.830E+06 1.430E+05 0.000E+00 1.000E+05 0.000E+00 3.360E+04 CS-134 7.100E+09 1.670E+10 0.000E+00 5.310E+09 2.030E+09 2.080E+08 0.000E+00 7.750E+09 CS-136 4.370E+07 1.720E+08 0.000E+00 9.370E+07 1.480E+07 1.380E+07 0.000E+00 1.160E+08 CS-137 1.010E+10 1.350E+10 0.000E+00 4.590E+09 1.780E+09 1.920E+08 0.000E+00 4.690E+09 CS-138 3.610E-11 6.940E-11 0.000E+00 5.120E-11 5.960E-12 3.150E-14 0.000E+00 3.470E-11 BA-139 2.690E-02 1.890E-05 0.000E+00 1.780E-05 1.300E-05 2.400E-01 0.000E+00 7.830E-04 BA-140 1.380E+08 1.690E+05 0.000E+00 5.740E+04 1.140E+05 2.130E+08 0.000E+00 8.900E+06 BA-141 1.080E-21 8.040E-25 0.000E+00 7.460E-25 5.500E-25 2.290E-27 0.000E+00 3.590E-23 BA-142 5.490E-39 5.490E-42 0.000E+00 4.640E-42 3.650E-42 1.680E-50 0.000E+00 3.380E-40 LA-140 1.810E+03 8.880E+02 0.000E+00 0.000E+00 0.000E+00 5.100E+07 0.000E+00 2.360E+02 LA-142 1.850E-04 8.240E-05 0.000E+00 0.000E+00 0.000E+00 2.510E+00 0.000E+00 2.050E-05 CE-141 2.830E+05 1.890E+05 0.000E+00 8.890E+04 0.000E+00 5.400E+08 0.000E+00 2.170E+04 CE-143 9.330E+02 6.790E+05 0.000E+00 3.040E+02 0.000E+00 2.040E+07 0.000E+00 7.580E+01 CE-144 5.270E+07 2.180E+07 0.000E+00 1.300E+07 0.000E+00 1.330E+10 0.000E+00 2.830E+06 PR-143 7.000E+04 2.800E+04 0.000E+00 1.630E+04 0.000E+00 2.300E+08 0.000E+00 3.490E+03 PR-144 2.900E-26 1.190E-26 0.000E+00 6.800E-27 0.000E+00 3.190E-29 0.000E+00 1.470E-27 ND-147 3.620E+04 3.940E+04 0.000E+00 2.310E+04 0.000E+00 1.420E+08 0.000E+00 2.360E+03 W-187 3.540E+04 2.880E+04 0.000E+00 0.000E+00 0.000E+00 7.800E+06 0.000E+00 1.010E+04 NP-239 1.390E+03 1.310E+02 0.000E+00 4.100E+02 0.000E+00 2.100E+07 0.000E+00 7.260E+01 Appendix H Ri Teen Vegetation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.270E+03 1.270E+03 1.270E+03 1.270E+03 1.270E+03 0.000E+00 1.270E+03 C-14 2.600E+04 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 0.000E+00 4.870E+03 NA-24 1.380E+04 1.380E+04 1.380E+04 1.380E+04 1.380E+04 1.380E+04 0.000E+00 1.380E+04 P-32 1.890E+06 1.100E+05 0.000E+00 0.000E+00 0.000E+00 9.280E+04 0.000E+00 7.160E+04 CR-51 0.000E+00 0.000E+00 7.500E+01 3.070E+01 2.100E+04 3.000E+03 0.000E+00 1.350E+02 MN-54 0.000E+00 5.110E+04 0.000E+00 1.270E+04 1.980E+06 6.680E+04 0.000E+00 8.400E+03 MN-56 0.000E+00 1.700E+00 0.000E+00 1.790E+00 1.520E+04 5.740E+04 0.000E+00 2.520E-01 FE-55 3.340E+04 2.380E+04 0.000E+00 0.000E+00 1.240E+05 6.390E+03 0.000E+00 5.540E+03 FE-59 1.590E+04 3.700E+04 0.000E+00 0.000E+00 1.530E+06 1.780E+05 0.000E+00 1.430E+04 CO-58 0.000E+00 2.070E+03 0.000E+00 0.000E+00 1.340E+06 9.520E+04 0.000E+00 2.780E+03 CO-60 0.000E+00 1.510E+04 0.000E+00 0.000E+00 8.720E+06 2.590E+05 0.000E+00 1.980E+04 NI-63 5.800E+05 4.340E+04 0.000E+00 0.000E+00 3.070E+05 1.420E+04 0.000E+00 1.980E+04 NI-65 2.180E+00 2.930E-01 0.000E+00 0.000E+00 9.360E+03 3.670E+04 0.000E+00 1.270E-01 CU-64 0.000E+00 2.030E+00 0.000E+00 6.410E+00 1.110E+04 6.140E+04 0.000E+00 8.480E-01 ZN-65 3.860E+04 1.340E+05 0.000E+00 8.640E+04 1.240E+06 4.660E+04 0.000E+00 6.240E+04 ZN-69 4.830E-02 9.200E-02 0.000E+00 6.020E-02 1.580E+03 2.850E+02 0.000E+00 6.460E-03 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.440E+02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.330E+02 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.830E+01 RB-86 0.000E+00 1.900E+05 0.000E+00 0.000E+00 0.000E+00 1.770E+04 0.000E+00 8.400E+04 RB-88 0.000E+00 5.460E+02 0.000E+00 0.000E+00 0.000E+00 2.920E-05 0.000E+00 2.720E+02 RB-89 0.000E+00 3.520E+02 0.000E+00 0.000E+00 0.000E+00 3.380E-07 0.000E+00 2.330E+02 SR-89 4.340E+05 0.000E+00 0.000E+00 0.000E+00 2.420E+06 3.710E+05 0.000E+00 1.250E+04 SR-90 1.080E+08 0.000E+00 0.000E+00 0.000E+00 1.650E+07 7.650E+05 0.000E+00 6.680E+06 SR-91 8.800E+01 0.000E+00 0.000E+00 0.000E+00 6.070E+04 2.590E+05 0.000E+00 3.510E+00 Appendix H Ri Teen Inhalation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 9.520E+00 0.000E+00 0.000E+00 0.000E+00 2.740E+04 1.190E+05 0.000E+00 4.060E-01 Y-90 2.980E+03 0.000E+00 0.000E+00 0.000E+00 2.930E+05 5.590E+05 0.000E+00 8.000E+01 Y-91 6.610E+05 0.000E+00 0.000E+00 0.000E+00 2.940E+06 4.090E+05 0.000E+00 1.770E+04 Y-91M 3.700E-01 0.000E+00 0.000E+00 0.000E+00 3.200E+03 3.020E+01 0.000E+00 1.420E-02 Y-92 1.470E+01 0.000E+00 0.000E+00 0.000E+00 2.680E+04 1.650E+05 0.000E+00 4.290E-01 Y-93 1.350E+02 0.000E+00 0.000E+00 0.000E+00 8.320E+04 5.790E+05 0.000E+00 3.720E+00 ZR-95 1.460E+05 4.580E+04 0.000E+00 6.740E+04 2.690E+06 1.490E+05 0.000E+00 3.150E+04 ZR-97 1.380E+02 2.720E+01 0.000E+00 4.120E+01 1.300E+05 6.300E+05 0.000E+00 1.260E+01 NB-95 1.860E+04 1.030E+04 0.000E+00 1.000E+04 7.510E+05 9.680E+04 0.000E+00 5.660E+03 MO-99 0.000E+00 1.690E+02 0.000E+00 4.110E+02 1.540E+05 2.690E+05 0.000E+00 3.220E+01 TC-99M 1.380E-03 3.860E-03 0.000E+00 5.760E-02 1.150E+03 6.130E+03 0.000E+00 4.990E-02 TC-101 5.920E-05 8.400E-05 0.000E+00 1.520E-03 6.670E+02 8.720E-07 0.000E+00 8.240E-04 RU-103 2.100E+03 0.000E+00 0.000E+00 7.430E+03 7.830E+05 1.090E+05 0.000E+00 8.960E+02 RU-105 1.120E+00 0.000E+00 0.000E+00 1.410E+00 1.820E+04 9.040E+04 0.000E+00 4.340E-01 RU-106 9.840E+04 0.000E+00 0.000E+00 1.900E+05 1.610E+07 9.600E+05 0.000E+00 1.240E+04 AG-110M 1.380E+04 1.310E+04 0.000E+00 2.500E+04 6.750E+06 2.730E+05 0.000E+00 7.990E+03 TE-125M 4.880E+03 2.240E+03 1.400E+03 0.000E+00 5.360E+05 7.500E+04 0.000E+00 6.670E+02 TE-127 2.010E+00 9.120E-01 1.420E+00 7.280E+00 1.120E+04 8.080E+04 0.000E+00 4.420E-01 TE-127M 1.800E+04 8.160E+03 4.380E+03 6.540E+04 1.660E+06 1.590E+05 0.000E+00 2.180E+03 TE-129 7.100E-02 3.380E-02 5.180E-02 2.660E-01 3.300E+03 1.620E+03 0.000E+00 1.760E-02 TE-129M 1.390E+04 6.580E+03 4.580E+03 5.190E+04 1.980E+06 4.050E+05 0.000E+00 2.250E+03 TE-131 1.580E-02 8.320E-03 1.240E-02 6.180E-02 2.340E+03 1.510E+01 0.000E+00 5.040E-03 TE-131M 9.840E+01 6.010E+01 7.250E+01 4.390E+02 2.380E+05 6.210E+05 0.000E+00 4.020E+01 TE-132 3.600E+02 2.900E+02 2.460E+02 1.950E+03 4.490E+05 4.630E+05 0.000E+00 2.190E+02 I-130 6.240E+03 1.790E+04 1.490E+06 2.750E+04 0.000E+00 9.120E+03 0.000E+00 7.170E+03 Appendix H Ri Teen Inhalation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.540E+04 4.910E+04 1.460E+07 8.400E+04 0.000E+00 6.490E+03 0.000E+00 2.640E+04 I-132 1.590E+03 4.380E+03 1.510E+05 6.920E+03 0.000E+00 1.270E+03 0.000E+00 1.580E+03 I-133 1.220E+04 2.050E+04 2.920E+06 3.590E+04 0.000E+00 1.030E+04 0.000E+00 6.220E+03 I-134 8.880E+02 2.320E+03 3.950E+04 3.660E+03 0.000E+00 2.040E+01 0.000E+00 8.400E+02 I-135 3.700E+03 9.440E+03 6.210E+05 1.490E+04 0.000E+00 6.950E+03 0.000E+00 3.490E+03 CS-134 5.020E+05 1.130E+06 0.000E+00 3.750E+05 1.460E+05 9.760E+03 0.000E+00 5.490E+05 CS-136 5.150E+04 1.940E+05 0.000E+00 1.100E+05 1.780E+04 1.090E+04 0.000E+00 1.370E+05 CS-137 6.700E+05 8.480E+05 0.000E+00 3.040E+05 1.210E+05 8.480E+03 0.000E+00 3.110E+05 CS-138 4.660E+02 8.560E+02 0.000E+00 6.620E+02 7.870E+01 2.700E-01 0.000E+00 4.460E+02 BA-139 1.340E+00 9.440E-04 0.000E+00 8.880E-04 6.460E+03 6.450E+03 0.000E+00 3.900E-02 BA-140 5.470E+04 6.700E+01 0.000E+00 2.280E+01 2.030E+06 2.290E+05 0.000E+00 3.520E+03 BA-141 1.420E-01 1.060E-04 0.000E+00 9.840E-05 3.290E+03 7.460E-04 0.000E+00 4.740E-03 BA-142 3.700E-02 3.700E-05 0.000E+00 3.140E-05 1.910E+03 4.790E-10 0.000E+00 2.270E-03 LA-140 4.790E+02 2.360E+02 0.000E+00 0.000E+00 2.140E+05 4.870E+05 0.000E+00 6.260E+01 LA-142 9.600E-01 4.250E-01 0.000E+00 0.000E+00 1.020E+04 1.200E+04 0.000E+00 1.060E-01 CE-141 2.840E+04 1.900E+04 0.000E+00 8.880E+03 6.140E+05 1.260E+05 0.000E+00 2.170E+03 CE-143 2.660E+02 1.940E+02 0.000E+00 8.640E+01 1.300E+05 2.550E+05 0.000E+00 2.160E+01 CE-144 4.890E+06 2.020E+06 0.000E+00 1.210E+06 1.340E+07 8.640E+05 0.000E+00 2.620E+05 PR-143 1.340E+04 5.310E+03 0.000E+00 3.090E+03 4.830E+05 2.140E+05 0.000E+00 6.620E+02 PR-144 4.300E-02 1.760E-02 0.000E+00 1.010E-02 1.750E+03 2.350E-04 0.000E+00 2.180E-03 ND-147 7.860E+03 8.560E+03 0.000E+00 5.020E+03 3.720E+05 1.820E+05 0.000E+00 5.130E+02 W-187 1.200E+01 9.760E+00 0.000E+00 0.000E+00 4.740E+04 1.770E+05 0.000E+00 3.430E+00 NP-239 3.380E+02 3.190E+01 0.000E+00 1.000E+02 6.490E+04 1.320E+05 0.000E+00 1.770E+01 Appendix H Ri Teen Inhalation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.390E+07 1.190E+07 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 5.510E+06 4.660E+06 MN-54 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.630E+09 1.390E+09 MN-56 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 1.070E+06 9.020E+05 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 3.210E+08 2.730E+08 CO-58 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 4.440E+08 3.790E+08 CO-60 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.530E+10 2.150E+10 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 3.450E+05 2.970E+05 CU-64 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.880E+05 6.070E+05 ZN-65 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 8.590E+08 7.470E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 7.080E+03 4.870E+03 BR-84 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.360E+05 2.030E+05 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 1.030E+07 8.990E+06 RB-88 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.780E+04 3.310E+04 RB-89 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.480E+05 1.230E+05 SR-89 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.510E+04 2.160E+04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.510E+06 2.150E+06 Appendix H Ri Teen Ground Plane Deposition - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 8.630E+05 7.770E+05 Y-90 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 5.310E+03 4.490E+03 Y-91 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.210E+06 1.070E+06 Y-91M 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.160E+05 1.000E+05 Y-92 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 2.140E+05 1.800E+05 Y-93 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 2.510E+05 1.830E+05 ZR-95 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.840E+08 2.450E+08 ZR-97 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 3.440E+06 2.960E+06 NB-95 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.610E+08 1.370E+08 MO-99 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 4.630E+06 3.990E+06 TC-99M 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 2.110E+05 1.840E+05 TC-101 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.260E+04 2.040E+04 RU-103 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.260E+08 1.080E+08 RU-105 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 7.210E+05 6.360E+05 RU-106 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 5.070E+08 4.220E+08 AG-110M 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 4.010E+09 3.440E+09 TE-125M 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 2.130E+06 1.550E+06 TE-127 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 3.280E+03 2.980E+03 TE-127M 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 1.080E+05 9.160E+04 TE-129 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 3.100E+04 2.620E+04 TE-129M 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 2.310E+07 1.980E+07 TE-131 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 3.450E+07 2.920E+04 TE-131M 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 9.460E+06 8.030E+06 TE-132 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.980E+06 4.230E+06 I-130 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 6.690E+06 5.510E+06 Appendix H Ri Teen Ground Plane Deposition - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX H Ri Teen Dose Factors for use in the Gaseous Dose Calculations Agegroup: TEEN Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 2.090E+07 1.720E+07 I-132 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.470E+06 1.250E+06 I-133 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.980E+06 2.450E+06 I-134 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 5.300E+05 4.470E+05 I-135 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.950E+06 2.530E+06 CS-134 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 8.000E+09 6.860E+09 CS-136 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.710E+08 1.510E+08 CS-137 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.200E+10 1.030E+10 CS-138 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 4.100E+05 3.590E+05 BA-139 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.190E+05 1.060E+05 BA-140 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.350E+07 2.050E+07 BA-141 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.750E+04 4.170E+04 BA-142 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 5.110E+04 4.490E+04 LA-140 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 2.180E+07 1.920E+07 LA-142 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 9.120E+05 7.600E+05 CE-141 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.540E+07 1.370E+07 CE-143 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.630E+06 2.310E+06 CE-144 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 8.040E+07 6.950E+07 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 2.110E+03 1.830E+03 ND-147 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 1.010E+07 8.390E+06 W-187 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.730E+06 2.350E+06 NP-239 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.980E+06 1.710E+06 Appendix H Ri Teen Ground Plane Deposition - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.570E+03 1.570E+03 1.570E+03 1.570E+03 1.570E+03 0.000E+00 1.570E+03 C-14 1.190E+09 2.390E+08 2.390E+08 2.390E+08 2.390E+08 2.390E+08 0.000E+00 2.390E+08 NA-24 8.850E+06 8.850E+06 8.850E+06 8.850E+06 8.850E+06 8.850E+06 0.000E+00 8.850E+06 P-32 7.780E+10 3.640E+09 0.000E+00 0.000E+00 0.000E+00 2.150E+09 0.000E+00 3.000E+09 CR-51 0.000E+00 0.000E+00 5.650E+04 1.540E+04 1.030E+05 5.400E+06 0.000E+00 1.020E+05 MN-54 0.000E+00 2.100E+07 0.000E+00 5.880E+06 0.000E+00 1.760E+07 0.000E+00 5.590E+06 MN-56 0.000E+00 1.260E-02 0.000E+00 1.530E-02 0.000E+00 1.830E+00 0.000E+00 2.860E-03 FE-55 1.120E+08 5.930E+07 0.000E+00 0.000E+00 3.350E+07 1.100E+07 0.000E+00 1.840E+07 FE-59 1.200E+08 1.950E+08 0.000E+00 0.000E+00 5.640E+07 2.030E+08 0.000E+00 9.690E+07 CO-58 0.000E+00 1.210E+07 0.000E+00 0.000E+00 0.000E+00 7.070E+07 0.000E+00 3.710E+07 CO-60 0.000E+00 4.320E+07 0.000E+00 0.000E+00 0.000E+00 2.390E+08 0.000E+00 1.270E+08 NI-63 2.960E+10 1.590E+09 0.000E+00 0.000E+00 0.000E+00 1.070E+08 0.000E+00 1.010E+09 NI-65 1.660E+00 1.560E-01 0.000E+00 0.000E+00 0.000E+00 1.910E+01 0.000E+00 9.100E-02 CU-64 0.000E+00 7.460E+04 0.000E+00 1.800E+05 0.000E+00 3.500E+06 0.000E+00 4.510E+04 ZN-65 4.130E+09 1.100E+10 0.000E+00 6.940E+09 0.000E+00 1.930E+09 0.000E+00 6.850E+09 ZN-69 9.460E-12 1.370E-11 0.000E+00 8.300E-12 0.000E+00 8.620E-10 0.000E+00 1.260E-12 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.400E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.510E-23 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 8.770E+09 0.000E+00 0.000E+00 0.000E+00 5.640E+08 0.000E+00 5.390E+09 RB-88 0.000E+00 7.160E-45 0.000E+00 0.000E+00 0.000E+00 3.510E-46 0.000E+00 4.970E-45 RB-89 0.000E+00 1.340E-52 0.000E+00 0.000E+00 0.000E+00 1.170E-54 0.000E+00 1.190E-52 SR-89 6.620E+09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.560E+08 0.000E+00 1.890E+08 SR-90 1.120E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.510E+09 0.000E+00 2.830E+10 SR-91 1.300E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.880E+05 0.000E+00 4.920E+03 Appendix I Ri Child Cow Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 2.180E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.130E+01 0.000E+00 8.750E-02 Y-90 3.220E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.170E+05 0.000E+00 8.620E+00 Y-91 3.900E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.200E+06 0.000E+00 1.040E+03 Y-91M 2.670E-19 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.240E-16 0.000E+00 9.730E-21 Y-92 2.530E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.310E+00 0.000E+00 7.240E-06 Y-93 1.010E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.510E+04 0.000E+00 2.780E-02 ZR-95 3.830E+03 8.420E+02 0.000E+00 1.210E+03 0.000E+00 8.790E+05 0.000E+00 7.500E+02 ZR-97 1.920E+00 2.770E-01 0.000E+00 3.980E-01 0.000E+00 4.200E+04 0.000E+00 1.640E-01 NB-95 3.180E+05 1.240E+05 0.000E+00 1.160E+05 0.000E+00 2.290E+08 0.000E+00 8.840E+04 MO-99 0.000E+00 8.140E+07 0.000E+00 1.740E+08 0.000E+00 6.730E+07 0.000E+00 2.010E+07 TC-99M 1.320E+01 2.590E+01 0.000E+00 3.760E+02 1.320E+01 1.470E+04 0.000E+00 4.290E+02 TC-101 1.160E-59 1.220E-59 0.000E+00 2.080E-58 6.440E-60 3.870E-59 0.000E+00 1.540E-58 RU-103 4.280E+03 0.000E+00 0.000E+00 1.080E+04 0.000E+00 1.110E+05 0.000E+00 1.650E+03 RU-105 3.820E-03 0.000E+00 0.000E+00 3.360E-02 0.000E+00 2.490E+00 0.000E+00 1.390E-03 RU-106 9.240E+04 0.000E+00 0.000E+00 1.250E+05 0.000E+00 1.440E+06 0.000E+00 1.150E+04 AG-110M 2.090E+08 1.410E+08 0.000E+00 2.630E+08 0.000E+00 1.680E+10 0.000E+00 1.130E+08 TE-125M 7.380E+07 2.000E+07 2.070E+07 0.000E+00 0.000E+00 7.120E+07 0.000E+00 9.840E+06 TE-127 2.980E+03 8.020E+02 2.060E+03 8.470E+03 0.000E+00 1.160E+05 0.000E+00 6.380E+02 TE-127M 2.080E+08 5.600E+07 4.970E+07 5.930E+08 0.000E+00 1.680E+08 0.000E+00 2.470E+07 TE-129 1.280E-09 3.580E-10 9.160E-10 3.750E-09 0.000E+00 7.990E-08 0.000E+00 3.050E-10 TE-129M 2.710E+08 7.580E+07 8.750E+07 7.970E+08 0.000E+00 3.310E+08 0.000E+00 4.210E+07 TE-131 1.620E-32 4.920E-33 1.240E-32 4.890E-32 0.000E+00 8.490E-32 0.000E+00 4.810E-33 TE-131M 1.600E+06 5.530E+05 1.140E+06 5.350E+06 0.000E+00 2.240E+07 0.000E+00 5.890E+05 TE-132 1.020E+07 4.530E+06 6.600E+06 4.210E+07 0.000E+00 4.570E+07 0.000E+00 5.480E+06 I-130 1.730E+06 3.490E+06 3.840E+08 5.220E+06 0.000E+00 1.630E+06 0.000E+00 1.800E+06 Appendix I Ri Child Cow Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.300E+09 1.310E+09 4.330E+11 2.150E+09 0.000E+00 1.170E+08 0.000E+00 7.450E+08 I-132 6.890E-01 1.270E+00 5.870E+01 1.940E+00 0.000E+00 1.490E+00 0.000E+00 5.820E-01 I-133 1.720E+07 2.120E+07 3.940E+09 3.540E+07 0.000E+00 8.560E+06 0.000E+00 8.030E+06 I-134 8.480E-12 1.570E-11 3.620E-10 2.410E-11 0.000E+00 1.040E-11 0.000E+00 7.250E-12 I-135 5.400E+04 9.720E+04 8.610E+06 1.490E+05 0.000E+00 7.400E+04 0.000E+00 4.600E+04 CS-134 2.260E+10 3.720E+10 0.000E+00 1.150E+10 4.130E+09 2.000E+08 0.000E+00 7.840E+09 CS-136 1.010E+09 2.780E+09 0.000E+00 1.480E+09 2.210E+08 9.770E+07 0.000E+00 1.800E+09 CS-137 3.220E+10 3.090E+10 0.000E+00 1.010E+10 3.620E+09 1.930E+08 0.000E+00 4.550E+09 CS-138 3.980E-23 5.530E-23 0.000E+00 3.890E-23 4.190E-24 2.550E-23 0.000E+00 3.510E-23 BA-139 2.010E-07 1.070E-10 0.000E+00 9.360E-11 6.300E-11 1.160E-05 0.000E+00 5.820E-09 BA-140 1.170E+08 1.030E+05 0.000E+00 3.340E+04 6.120E+04 5.930E+07 0.000E+00 6.840E+06 BA-141 1.850E-45 1.040E-48 0.000E+00 8.960E-49 6.090E-48 1.050E-45 0.000E+00 6.020E-47 BA-142 1.150E-79 8.310E-83 0.000E+00 6.720E-83 4.890E-83 1.510E-81 0.000E+00 6.450E-81 LA-140 1.940E+01 6.780E+00 0.000E+00 0.000E+00 0.000E+00 1.890E+05 0.000E+00 2.290E+00 LA-142 8.100E-11 2.580E-11 0.000E+00 0.000E+00 0.000E+00 5.120E-06 0.000E+00 8.090E-12 CE-141 2.190E+04 1.090E+04 0.000E+00 4.780E+03 0.000E+00 1.360E+07 0.000E+00 1.620E+03 CE-143 1.870E+02 1.020E+05 0.000E+00 4.260E+01 0.000E+00 1.490E+06 0.000E+00 1.470E+01 CE-144 1.620E+06 5.090E+05 0.000E+00 2.820E+05 0.000E+00 1.330E+08 0.000E+00 8.660E+04 PR-143 7.180E+02 2.160E+02 0.000E+00 1.170E+02 0.000E+00 7.750E+05 0.000E+00 3.560E+01 PR-144 2.680E-53 8.290E-54 0.000E+00 4.380E-54 0.000E+00 1.780E-50 0.000E+00 1.350E-54 ND-147 4.450E+02 3.600E+02 0.000E+00 1.980E+02 0.000E+00 5.700E+05 0.000E+00 2.790E+01 W-187 2.890E+04 1.710E+04 0.000E+00 0.000E+00 0.000E+00 2.400E+06 0.000E+00 7.670E+03 NP-239 1.720E+01 1.240E+00 0.000E+00 3.580E+00 0.000E+00 9.170E+04 0.000E+00 8.710E-01 Appendix I Ri Child Cow Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 3.200E+03 3.200E+03 3.200E+03 3.200E+03 3.200E+03 0.000E+00 3.200E+03 C-14 1.190E+09 2.390E+08 2.390E+08 2.390E+08 2.390E+08 2.390E+08 0.000E+00 2.390E+08 NA-24 1.060E+06 1.060E+06 1.060E+06 1.060E+06 1.060E+06 1.060E+06 0.000E+00 1.060E+06 P-32 9.330E+10 4.370E+09 0.000E+00 0.000E+00 0.000E+00 2.580E+09 0.000E+00 3.600E+09 CR-51 0.000E+00 0.000E+00 6.780E+03 1.850E+03 1.240E+04 6.480E+05 0.000E+00 1.220E+04 MN-54 0.000E+00 2.520E+06 0.000E+00 7.060E+05 0.000E+00 2.110E+06 0.000E+00 6.700E+05 MN-56 0.000E+00 1.520E-03 0.000E+00 1.840E-03 0.000E+00 2.200E-01 0.000E+00 3.430E-04 FE-55 1.450E+06 7.710E+05 0.000E+00 0.000E+00 4.360E+05 1.430E+05 0.000E+00 2.390E+05 FE-59 1.560E+06 2.530E+06 0.000E+00 0.000E+00 7.330E+05 2.630E+06 0.000E+00 1.260E+06 CO-58 0.000E+00 1.450E+06 0.000E+00 0.000E+00 0.000E+00 8.490E+06 0.000E+00 4.450E+06 CO-60 0.000E+00 5.180E+06 0.000E+00 0.000E+00 0.000E+00 2.870E+07 0.000E+00 1.530E+07 NI-63 3.560E+09 1.900E+08 0.000E+00 0.000E+00 0.000E+00 1.280E+07 0.000E+00 1.210E+08 NI-65 1.990E-01 1.870E-02 0.000E+00 0.000E+00 0.000E+00 2.290E+00 0.000E+00 1.090E-02 CU-64 0.000E+00 8.320E+03 0.000E+00 2.010E+04 0.000E+00 3.900E+05 0.000E+00 5.020E+03 ZN-65 4.960E+08 1.320E+09 0.000E+00 8.330E+08 0.000E+00 2.320E+08 0.000E+00 8.220E+08 ZN-69 1.140E-12 1.640E-12 0.000E+00 9.960E-13 0.000E+00 1.030E-10 0.000E+00 1.520E-13 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.280E-02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 7.820E-24 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 1.050E+09 0.000E+00 0.000E+00 0.000E+00 6.770E+07 0.000E+00 6.470E+08 RB-88 0.000E+00 8.590E-46 0.000E+00 0.000E+00 0.000E+00 4.210E-47 0.000E+00 5.970E-46 RB-89 0.000E+00 1.610E-53 0.000E+00 0.000E+00 0.000E+00 1.410E-55 0.000E+00 1.430E-53 SR-89 1.390E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.380E+08 0.000E+00 3.970E+08 SR-90 2.350E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.160E+09 0.000E+00 5.950E+10 SR-91 2.740E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.040E+05 0.000E+00 1.030E+04 Appendix I Ri Child Goat Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 4.580E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.680E+01 0.000E+00 1.840E-01 Y-90 3.870E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.100E+05 0.000E+00 1.030E+00 Y-91 4.680E+03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.240E+05 0.000E+00 1.250E+02 Y-91M 3.210E-20 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.280E-17 0.000E+00 1.170E-21 Y-92 3.040E-05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 8.770E-01 0.000E+00 8.690E-07 Y-93 1.210E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.810E+03 0.000E+00 3.330E-03 ZR-95 4.600E+02 1.010E+02 0.000E+00 1.450E+02 0.000E+00 1.050E+05 0.000E+00 9.000E+01 ZR-97 2.300E-01 3.330E-02 0.000E+00 4.780E-02 0.000E+00 5.040E+03 0.000E+00 1.960E-02 NB-95 3.810E+04 1.490E+04 0.000E+00 1.400E+04 0.000E+00 2.750E+07 0.000E+00 1.060E+04 MO-99 0.000E+00 9.760E+06 0.000E+00 2.090E+07 0.000E+00 8.080E+06 0.000E+00 2.420E+06 TC-99M 1.590E+00 3.110E+00 0.000E+00 4.520E+01 1.580E+00 1.770E+03 0.000E+00 5.150E+01 TC-101 1.400E-60 1.460E-60 0.000E+00 2.490E-59 7.720E-61 4.640E-60 0.000E+00 1.850E-59 RU-103 5.140E+02 0.000E+00 0.000E+00 1.290E+03 0.000E+00 1.330E+04 0.000E+00 1.980E+02 RU-105 4.580E-04 0.000E+00 0.000E+00 4.030E-03 0.000E+00 2.990E-01 0.000E+00 1.660E-04 RU-106 1.110E+04 0.000E+00 0.000E+00 1.500E+04 0.000E+00 1.720E+05 0.000E+00 1.380E+03 AG-110M 2.510E+07 1.690E+07 0.000E+00 3.150E+07 0.000E+00 2.010E+09 0.000E+00 1.350E+07 TE-125M 8.850E+06 2.400E+06 2.480E+06 0.000E+00 0.000E+00 8.540E+06 0.000E+00 1.180E+06 TE-127 3.570E+02 9.630E+01 2.470E+02 1.020E+03 0.000E+00 1.390E+04 0.000E+00 7.660E+01 TE-127M 2.500E+07 6.720E+06 5.970E+06 7.120E+07 0.000E+00 2.020E+07 0.000E+00 2.960E+06 TE-129 1.540E-10 4.300E-11 1.100E-10 4.510E-10 0.000E+00 9.590E-09 0.000E+00 3.660E-11 TE-129M 3.260E+07 9.090E+06 1.050E+07 9.560E+07 0.000E+00 3.970E+07 0.000E+00 5.060E+06 TE-131 1.940E-33 5.910E-34 1.480E-33 5.860E-33 0.000E+00 1.020E-32 0.000E+00 5.770E-34 TE-131M 1.920E+05 6.640E+04 1.360E+05 6.420E+05 0.000E+00 2.690E+06 0.000E+00 7.060E+04 TE-132 1.230E+06 5.440E+05 7.920E+05 5.050E+06 0.000E+00 5.480E+06 0.000E+00 6.570E+05 I-130 2.070E+06 4.190E+06 4.610E+08 6.260E+06 0.000E+00 1.960E+06 0.000E+00 2.160E+06 Appendix I Ri Child Goat Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.560E+09 1.570E+09 5.200E+11 2.580E+09 0.000E+00 1.400E+08 0.000E+00 8.940E+08 I-132 8.270E-01 1.520E+00 7.050E+01 2.330E+00 0.000E+00 1.790E+00 0.000E+00 6.990E-01 I-133 2.060E+07 2.550E+07 4.730E+09 4.250E+07 0.000E+00 1.030E+07 0.000E+00 9.640E+06 I-134 1.020E-11 1.890E-11 4.350E-10 2.890E-11 0.000E+00 1.250E-11 0.000E+00 8.700E-12 I-135 6.480E+04 1.170E+05 1.030E+07 1.790E+05 0.000E+00 8.880E+04 0.000E+00 5.520E+04 CS-134 6.790E+10 1.110E+11 0.000E+00 3.450E+10 1.240E+10 6.010E+08 0.000E+00 2.350E+10 CS-136 3.030E+09 8.340E+09 0.000E+00 4.440E+09 6.630E+08 2.930E+08 0.000E+00 5.400E+09 CS-137 9.670E+10 9.260E+10 0.000E+00 3.020E+10 1.090E+10 5.800E+08 0.000E+00 1.370E+10 CS-138 1.190E-22 1.660E-22 0.000E+00 1.170E-22 1.260E-23 7.640E-23 0.000E+00 1.050E-22 BA-139 2.410E-08 1.290E-11 0.000E+00 1.120E-11 7.560E-12 1.390E-06 0.000E+00 6.980E-10 BA-140 1.410E+07 1.230E+04 0.000E+00 4.010E+03 7.340E+03 7.120E+06 0.000E+00 8.200E+05 BA-141 2.220E-46 1.240E-49 0.000E+00 1.080E-49 7.300E-49 1.270E-46 0.000E+00 7.230E-48 BA-142 1.390E-80 9.970E-84 0.000E+00 8.070E-84 5.870E-84 1.810E-82 0.000E+00 7.740E-82 LA-140 2.330E+00 8.140E-01 0.000E+00 0.000E+00 0.000E+00 2.270E+04 0.000E+00 2.740E-01 LA-142 9.730E-12 3.100E-12 0.000E+00 0.000E+00 0.000E+00 6.140E-07 0.000E+00 9.710E-13 CE-141 2.620E+03 1.310E+03 0.000E+00 5.740E+02 0.000E+00 1.630E+06 0.000E+00 1.940E+02 CE-143 2.250E+01 1.220E+04 0.000E+00 5.120E+00 0.000E+00 1.790E+05 0.000E+00 1.770E+00 CE-144 1.950E+05 6.110E+04 0.000E+00 3.380E+04 0.000E+00 1.590E+07 0.000E+00 1.040E+04 PR-143 8.620E+01 2.590E+01 0.000E+00 1.400E+01 0.000E+00 9.300E+04 0.000E+00 4.280E+00 PR-144 3.220E-54 9.950E-55 0.000E+00 5.260E-55 0.000E+00 2.140E-51 0.000E+00 1.620E-55 ND-147 5.330E+01 4.320E+01 0.000E+00 2.370E+01 0.000E+00 6.850E+04 0.000E+00 3.350E+00 W-187 3.470E+03 2.050E+03 0.000E+00 0.000E+00 0.000E+00 2.880E+05 0.000E+00 9.210E+02 NP-239 2.070E+00 1.490E-01 0.000E+00 4.300E-01 0.000E+00 1.100E+04 0.000E+00 1.040E-01 Appendix I Ri Child Goat Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.340E+02 2.340E+02 2.340E+02 2.340E+02 2.340E+02 0.000E+00 2.340E+02 C-14 3.830E+08 7.670E+07 7.670E+07 7.670E+07 7.670E+07 7.670E+07 0.000E+00 7.670E+07 NA-24 1.720E-03 1.720E-03 1.720E-03 1.720E-03 1.720E-03 1.720E-03 0.000E+00 1.720E-03 P-32 7.420E+09 3.470E+08 0.000E+00 0.000E+00 0.000E+00 2.050E+08 0.000E+00 2.860E+08 CR-51 0.000E+00 0.000E+00 4.880E+03 1.330E+03 8.910E+03 4.660E+05 0.000E+00 8.790E+03 MN-54 0.000E+00 8.010E+06 0.000E+00 2.250E+06 0.000E+00 6.720E+06 0.000E+00 2.130E+06 MN-56 0.000E+00 1.430E-53 0.000E+00 1.730E-53 0.000E+00 2.070E-51 0.000E+00 3.230E-54 FE-55 4.570E+08 2.420E+08 0.000E+00 0.000E+00 1.370E+08 4.490E+07 0.000E+00 7.510E+07 FE-59 3.760E+08 6.090E+08 0.000E+00 0.000E+00 1.770E+08 6.340E+08 0.000E+00 3.030E+08 CO-58 0.000E+00 1.640E+07 0.000E+00 0.000E+00 0.000E+00 9.580E+07 0.000E+00 5.020E+07 CO-60 0.000E+00 6.930E+07 0.000E+00 0.000E+00 0.000E+00 3.840E+08 0.000E+00 2.040E+08 NI-63 2.910E+10 1.560E+09 0.000E+00 0.000E+00 0.000E+00 1.050E+08 0.000E+00 9.910E+08 NI-65 3.520E-52 3.310E-53 0.000E+00 0.000E+00 0.000E+00 4.060E-51 0.000E+00 1.930E-53 CU-64 0.000E+00 2.970E-07 0.000E+00 7.180E-07 0.000E+00 1.390E-05 0.000E+00 1.800E-07 ZN-65 3.750E+08 1.000E+09 0.000E+00 6.300E+08 0.000E+00 1.760E+08 0.000E+00 6.220E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.520E-57 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 5.770E+08 0.000E+00 0.000E+00 0.000E+00 3.710E+07 0.000E+00 3.550E+08 RB-88 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-89 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-89 4.820E+08 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.870E+07 0.000E+00 1.380E+07 SR-90 1.040E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.400E+08 0.000E+00 2.640E+09 SR-91 2.400E-10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.300E-10 0.000E+00 9.050E-12 Appendix I Ri Child Cow Meat - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.850E-49 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.490E-48 0.000E+00 7.400E-51 Y-90 1.710E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.880E+05 0.000E+00 4.590E+00 Y-91 1.800E+06 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.400E+08 0.000E+00 4.820E+04 Y-91M 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 Y-92 2.410E-39 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.960E-35 0.000E+00 6.890E-41 Y-93 7.440E-12 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.110E-07 0.000E+00 2.040E-13 ZR-95 2.660E+06 5.850E+05 0.000E+00 8.380E+05 0.000E+00 6.110E+08 0.000E+00 5.210E+05 ZR-97 3.200E-05 4.630E-06 0.000E+00 6.650E-06 0.000E+00 7.010E-01 0.000E+00 2.730E-06 NB-95 3.100E+06 1.210E+06 0.000E+00 1.130E+06 0.000E+00 2.230E+09 0.000E+00 8.620E+05 MO-99 0.000E+00 1.150E+05 0.000E+00 2.460E+05 0.000E+00 9.510E+04 0.000E+00 2.840E+04 TC-99M 6.190E-21 1.210E-20 0.000E+00 1.760E-19 6.160E-21 6.910E-18 0.000E+00 2.010E-19 TC-101 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RU-103 1.550E+08 0.000E+00 0.000E+00 3.900E+08 0.000E+00 4.010E+09 0.000E+00 5.960E+07 RU-105 9.020E-28 0.000E+00 0.000E+00 7.930E-27 0.000E+00 5.890E-25 0.000E+00 3.270E-28 RU-106 4.440E+09 0.000E+00 0.000E+00 5.990E+09 0.000E+00 6.900E+10 0.000E+00 5.540E+08 AG-110M 8.390E+06 5.670E+06 0.000E+00 1.060E+07 0.000E+00 6.740E+08 0.000E+00 4.530E+06 TE-125M 5.690E+08 1.540E+08 1.600E+08 0.000E+00 0.000E+00 5.490E+08 0.000E+00 7.590E+07 TE-127 3.380E-10 9.120E-11 2.340E-10 9.630E-10 0.000E+00 1.320E-08 0.000E+00 7.260E-11 TE-127M 1.770E+09 4.780E+08 4.240E+08 5.060E+09 0.000E+00 1.440E+09 0.000E+00 2.110E+08 TE-129 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 TE-129M 1.790E+09 5.000E+08 5.770E+08 5.260E+09 0.000E+00 2.180E+09 0.000E+00 2.780E+08 TE-131 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 TE-131M 7.000E+02 2.420E+02 4.980E+02 2.340E+03 0.000E+00 9.820E+03 0.000E+00 2.580E+02 TE-132 2.120E+06 9.380E+05 1.370E+06 8.710E+06 0.000E+00 9.450E+06 0.000E+00 1.130E+06 I-130 3.030E-06 6.130E-06 6.750E-04 9.160E-06 0.000E+00 2.870E-06 0.000E+00 3.160E-06 Appendix I Ri Child Cow Meat - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Grs/Cow/Meat (CMEAT) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.650E+07 1.660E+07 5.500E+09 2.730E+07 0.000E+00 1.480E+06 0.000E+00 9.460E+06 I-132 1.020E-58 1.880E-58 8.730E-57 2.880E-58 0.000E+00 2.210E-58 0.000E+00 8.650E-59 I-133 5.670E-01 7.020E-01 1.300E+02 1.170E+00 0.000E+00 2.830E-01 0.000E+00 2.660E-01 I-134 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 I-135 6.510E-17 1.170E-16 1.040E-14 1.800E-16 0.000E+00 8.930E-17 0.000E+00 5.550E-17 CS-134 9.220E+08 1.510E+09 0.000E+00 4.690E+08 1.680E+08 8.160E+06 0.000E+00 3.190E+08 CS-136 1.620E+07 4.460E+07 0.000E+00 2.370E+07 3.540E+06 1.570E+06 0.000E+00 2.880E+07 CS-137 1.330E+09 1.280E+09 0.000E+00 4.160E+08 1.500E+08 7.990E+06 0.000E+00 1.880E+08 CS-138 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-139 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-140 4.380E+07 3.840E+04 0.000E+00 1.250E+04 2.290E+04 2.220E+07 0.000E+00 2.560E+06 BA-141 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BA-142 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 LA-140 5.590E-02 1.950E-02 0.000E+00 0.000E+00 0.000E+00 5.440E+02 0.000E+00 6.580E-03 LA-142 5.300E-92 1.690E-92 0.000E+00 0.000E+00 0.000E+00 3.350E-87 0.000E+00 5.290E-93 CE-141 2.220E+04 1.110E+04 0.000E+00 4.850E+03 0.000E+00 1.380E+07 0.000E+00 1.640E+03 CE-143 3.170E-02 1.720E+01 0.000E+00 7.210E-03 0.000E+00 2.520E+02 0.000E+00 2.490E-03 CE-144 2.320E+06 7.260E+05 0.000E+00 4.020E+05 0.000E+00 1.890E+08 0.000E+00 1.240E+05 PR-143 3.340E+04 1.000E+04 0.000E+00 5.430E+03 0.000E+00 3.600E+07 0.000E+00 1.660E+03 PR-144 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 ND-147 1.170E+04 9.470E+03 0.000E+00 5.190E+03 0.000E+00 1.500E+07 0.000E+00 7.330E+02 W-187 3.210E-02 1.900E-02 0.000E+00 0.000E+00 0.000E+00 2.670E+00 0.000E+00 8.530E-03 NP-239 4.260E-01 3.060E-02 0.000E+00 8.850E-02 0.000E+00 2.260E+03 0.000E+00 2.150E-02 Appendix I Ri Child Cow Meat - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 4.010E+03 4.010E+03 4.010E+03 4.010E+03 4.010E+03 0.000E+00 4.010E+03 C-14 8.890E+08 1.780E+08 1.780E+08 1.780E+08 1.780E+08 1.780E+08 0.000E+00 1.780E+08 NA-24 3.730E+05 3.730E+05 3.730E+05 3.730E+05 3.730E+05 3.730E+05 0.000E+00 3.730E+05 P-32 3.370E+09 1.580E+08 0.000E+00 0.000E+00 0.000E+00 9.310E+07 0.000E+00 1.300E+08 CR-51 0.000E+00 0.000E+00 6.500E+04 1.780E+04 1.190E+05 6.210E+06 0.000E+00 1.170E+05 MN-54 0.000E+00 6.650E+08 0.000E+00 1.860E+08 0.000E+00 5.580E+08 0.000E+00 1.770E+08 MN-56 0.000E+00 1.860E+01 0.000E+00 2.250E+01 0.000E+00 2.700E+03 0.000E+00 4.200E+00 FE-55 8.010E+08 4.250E+08 0.000E+00 0.000E+00 2.400E+08 7.870E+07 0.000E+00 1.320E+08 FE-59 3.980E+08 6.430E+08 0.000E+00 0.000E+00 1.860E+08 6.700E+08 0.000E+00 3.200E+08 CO-58 0.000E+00 6.440E+07 0.000E+00 0.000E+00 0.000E+00 3.760E+08 0.000E+00 1.970E+08 CO-60 0.000E+00 3.780E+08 0.000E+00 0.000E+00 0.000E+00 2.100E+09 0.000E+00 1.120E+09 NI-63 3.950E+10 2.110E+09 0.000E+00 0.000E+00 0.000E+00 1.420E+08 0.000E+00 1.340E+09 NI-65 1.050E+02 9.890E+00 0.000E+00 0.000E+00 0.000E+00 1.210E+03 0.000E+00 5.770E+00 CU-64 0.000E+00 1.100E+04 0.000E+00 2.660E+04 0.000E+00 5.160E+05 0.000E+00 6.640E+03 ZN-65 8.130E+08 2.160E+09 0.000E+00 1.360E+09 0.000E+00 3.800E+08 0.000E+00 1.350E+09 ZN-69 9.490E-06 1.370E-05 0.000E+00 8.320E-06 0.000E+00 8.640E-04 0.000E+00 1.270E-06 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.370E+00 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.820E-11 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 4.520E+08 0.000E+00 0.000E+00 0.000E+00 2.910E+07 0.000E+00 2.780E+08 RB-88 0.000E+00 4.380E-22 0.000E+00 0.000E+00 0.000E+00 2.150E-23 0.000E+00 3.040E-22 RB-89 0.000E+00 4.610E-26 0.000E+00 0.000E+00 0.000E+00 4.020E-28 0.000E+00 4.090E-26 SR-89 3.600E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.390E+09 0.000E+00 1.030E+09 SR-90 1.240E+12 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.670E+10 0.000E+00 3.150E+11 SR-91 5.240E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.160E+06 0.000E+00 1.980E+04 Appendix I Ri Child Vegetation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 7.280E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.380E+04 0.000E+00 2.920E+01 Y-90 2.310E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.570E+07 0.000E+00 6.180E+02 Y-91 1.860E+07 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.480E+09 0.000E+00 4.990E+05 Y-91M 8.910E-09 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.740E-05 0.000E+00 3.240E-10 Y-92 1.580E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.580E+04 0.000E+00 4.530E-02 Y-93 2.930E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.370E+06 0.000E+00 8.040E+00 ZR-95 3.860E+06 8.480E+05 0.000E+00 1.210E+06 0.000E+00 8.850E+08 0.000E+00 7.550E+05 ZR-97 5.700E+02 8.240E+01 0.000E+00 1.180E+02 0.000E+00 1.250E+07 0.000E+00 4.860E+01 NB-95 4.110E+05 1.600E+05 0.000E+00 1.500E+05 0.000E+00 2.960E+08 0.000E+00 1.140E+05 MO-99 0.000E+00 7.710E+06 0.000E+00 1.650E+07 0.000E+00 6.380E+06 0.000E+00 1.910E+06 TC-99M 4.710E+00 9.230E+00 0.000E+00 1.340E+02 4.690E+00 5.260E+03 0.000E+00 1.530E+02 TC-101 1.410E-30 1.470E-30 0.000E+00 2.510E-29 7.780E-31 4.680E-30 0.000E+00 1.870E-29 RU-103 1.530E+07 0.000E+00 0.000E+00 3.860E+07 0.000E+00 3.970E+08 0.000E+00 5.900E+06 RU-105 9.160E+01 0.000E+00 0.000E+00 8.050E+02 0.000E+00 5.980E+04 0.000E+00 3.320E+01 RU-106 7.450E+08 0.000E+00 0.000E+00 1.010E+09 0.000E+00 1.160E+10 0.000E+00 9.300E+07 AG-110M 3.210E+07 2.170E+07 0.000E+00 4.040E+07 0.000E+00 2.580E+09 0.000E+00 1.730E+07 TE-125M 3.510E+08 9.500E+07 9.840E+07 0.000E+00 0.000E+00 3.380E+08 0.000E+00 4.670E+07 TE-127 9.850E+03 2.650E+03 6.810E+03 2.800E+04 0.000E+00 3.850E+05 0.000E+00 2.110E+03 TE-127M 1.320E+09 3.560E+08 3.160E+08 3.770E+09 0.000E+00 1.070E+09 0.000E+00 1.570E+08 TE-129 1.320E-03 3.690E-04 9.430E-04 3.870E-03 0.000E+00 8.230E-02 0.000E+00 3.140E-04 TE-129M 8.410E+08 2.350E+08 2.710E+08 2.470E+09 0.000E+00 1.030E+09 0.000E+00 1.310E+08 TE-131 2.570E-15 7.830E-16 1.960E-15 7.770E-15 0.000E+00 1.350E-14 0.000E+00 7.640E-16 TE-131M 1.540E+06 5.330E+05 1.100E+06 5.160E+06 0.000E+00 2.160E+07 0.000E+00 5.680E+05 TE-132 7.000E+06 3.100E+06 4.510E+06 2.880E+07 0.000E+00 3.120E+07 0.000E+00 3.740E+06 I-130 6.160E+05 1.240E+06 1.370E+08 1.860E+06 0.000E+00 5.820E+05 0.000E+00 6.410E+05 Appendix I Ri Child Vegetation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Vegetation (VEG) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.430E+08 1.440E+08 4.750E+10 2.360E+08 0.000E+00 1.280E+07 0.000E+00 8.170E+07 I-132 9.220E+01 1.690E+02 7.860E+03 2.590E+02 0.000E+00 1.990E+02 0.000E+00 7.790E+01 I-133 3.530E+06 4.370E+06 8.110E+08 7.280E+06 0.000E+00 1.760E+06 0.000E+00 1.650E+06 I-134 1.550E-04 2.880E-04 6.620E-03 4.400E-04 0.000E+00 1.910E-04 0.000E+00 1.320E-04 I-135 6.260E+04 1.130E+05 9.970E+06 1.730E+05 0.000E+00 8.580E+04 0.000E+00 5.330E+04 CS-134 1.600E+10 2.630E+10 0.000E+00 8.150E+09 2.930E+09 1.420E+08 0.000E+00 5.550E+09 CS-136 8.240E+07 2.270E+08 0.000E+00 1.210E+08 1.800E+07 7.960E+06 0.000E+00 1.470E+08 CS-137 2.390E+10 2.290E+10 0.000E+00 7.460E+09 2.680E+09 1.430E+08 0.000E+00 3.380E+09 CS-138 6.570E-11 9.130E-11 0.000E+00 6.430E-11 6.920E-12 4.210E-11 0.000E+00 5.790E-11 BA-139 4.950E-02 2.640E-05 0.000E+00 2.310E-05 1.560E-05 2.860E+00 0.000E+00 1.440E-03 BA-140 2.770E+08 2.420E+05 0.000E+00 7.890E+04 1.450E+05 1.400E+08 0.000E+00 1.610E+07 BA-141 1.990E-21 1.110E-24 0.000E+00 9.620E-25 6.530E-24 1.130E-21 0.000E+00 6.460E-23 BA-142 9.930E-39 7.150E-42 0.000E+00 5.780E-42 4.200E-42 1.300E-40 0.000E+00 5.540E-40 LA-140 3.250E+03 1.130E+03 0.000E+00 0.000E+00 0.000E+00 3.160E+07 0.000E+00 3.820E+02 LA-142 3.360E-04 1.070E-04 0.000E+00 0.000E+00 0.000E+00 2.120E+01 0.000E+00 3.350E-05 CE-141 6.560E+05 3.270E+05 0.000E+00 1.430E+05 0.000E+00 4.080E+08 0.000E+00 4.860E+04 CE-143 1.720E+03 9.310E+05 0.000E+00 3.910E+02 0.000E+00 1.360E+07 0.000E+00 1.350E+02 CE-144 1.270E+08 3.980E+07 0.000E+00 2.210E+07 0.000E+00 1.040E+10 0.000E+00 6.780E+06 PR-143 1.460E+05 4.370E+04 0.000E+00 2.370E+04 0.000E+00 1.570E+08 0.000E+00 7.230E+03 PR-144 5.380E-26 1.660E-26 0.000E+00 8.800E-27 0.000E+00 3.580E-23 0.000E+00 2.710E-27 ND-147 7.150E+04 5.790E+04 0.000E+00 3.180E+04 0.000E+00 9.170E+07 0.000E+00 4.480E+03 W-187 6.430E+04 3.810E+04 0.000E+00 0.000E+00 0.000E+00 5.350E+06 0.000E+00 1.710E+04 NP-239 2.560E+03 1.840E+02 0.000E+00 5.310E+02 0.000E+00 1.360E+07 0.000E+00 1.290E+02 Appendix I Ri Child Vegetation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 1.120E+03 1.120E+03 1.120E+03 1.120E+03 1.120E+03 0.000E+00 1.120E+03 C-14 3.590E+04 6.730E+03 6.730E+03 6.730E+03 6.730E+03 6.730E+03 0.000E+00 6.730E+03 NA-24 1.610E+04 1.610E+04 1.610E+04 1.610E+04 1.610E+04 1.610E+04 0.000E+00 1.610E+04 P-32 2.600E+06 1.140E+05 0.000E+00 0.000E+00 0.000E+00 4.220E+04 0.000E+00 9.880E+04 CR-51 0.000E+00 0.000E+00 8.550E+01 2.430E+01 1.700E+04 1.080E+03 0.000E+00 1.540E+02 MN-54 0.000E+00 4.290E+04 0.000E+00 1.000E+04 1.580E+06 2.290E+04 0.000E+00 9.510E+03 MN-56 0.000E+00 1.660E+00 0.000E+00 1.670E+00 1.310E+04 1.230E+05 0.000E+00 3.120E-01 FE-55 4.740E+04 2.520E+04 0.000E+00 0.000E+00 1.110E+05 2.870E+03 0.000E+00 7.770E+03 FE-59 2.070E+04 3.340E+04 0.000E+00 0.000E+00 1.270E+06 7.070E+04 0.000E+00 1.670E+04 CO-58 0.000E+00 1.770E+03 0.000E+00 0.000E+00 1.110E+06 3.440E+04 0.000E+00 3.160E+03 CO-60 0.000E+00 1.310E+04 0.000E+00 0.000E+00 7.070E+06 9.620E+04 0.000E+00 2.260E+04 NI-63 8.210E+05 4.620E+04 0.000E+00 0.000E+00 2.750E+05 6.330E+03 0.000E+00 2.800E+04 NI-65 2.990E+00 2.960E-01 0.000E+00 0.000E+00 8.180E+03 8.400E+04 0.000E+00 1.640E-01 CU-64 0.000E+00 1.990E+00 0.000E+00 6.030E+00 9.580E+03 3.670E+04 0.000E+00 1.070E+00 ZN-65 4.260E+04 1.130E+05 0.000E+00 7.140E+04 9.950E+05 1.630E+04 0.000E+00 7.030E+04 ZN-69 6.700E-02 9.660E-02 0.000E+00 5.850E-02 1.420E+03 1.020E+04 0.000E+00 8.920E-03 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.740E+02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.480E+02 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.530E+01 RB-86 0.000E+00 1.980E+05 0.000E+00 0.000E+00 0.000E+00 7.990E+03 0.000E+00 1.140E+05 RB-88 0.000E+00 5.620E+02 0.000E+00 0.000E+00 0.000E+00 1.720E+01 0.000E+00 3.660E+02 RB-89 0.000E+00 3.450E+02 0.000E+00 0.000E+00 0.000E+00 1.890E+00 0.000E+00 2.900E+02 SR-89 5.990E+05 0.000E+00 0.000E+00 0.000E+00 2.160E+06 1.670E+05 0.000E+00 1.720E+04 SR-90 1.010E+08 0.000E+00 0.000E+00 0.000E+00 1.480E+07 3.430E+05 0.000E+00 6.440E+06 SR-91 1.210E+02 0.000E+00 0.000E+00 0.000E+00 5.330E+04 1.740E+05 0.000E+00 4.590E+00 Appendix I Ri Child Inhalation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.310E+01 0.000E+00 0.000E+00 0.000E+00 2.400E+04 2.420E+05 0.000E+00 5.250E-01 Y-90 4.110E+03 0.000E+00 0.000E+00 0.000E+00 2.620E+05 2.680E+05 0.000E+00 1.110E+02 Y-91 9.140E+05 0.000E+00 0.000E+00 0.000E+00 2.630E+06 1.840E+05 0.000E+00 2.440E+04 Y-91M 5.070E-01 0.000E+00 0.000E+00 0.000E+00 2.810E+03 1.720E+03 0.000E+00 1.840E-02 Y-92 2.030E+01 0.000E+00 0.000E+00 0.000E+00 2.390E+04 2.390E+05 0.000E+00 5.810E-01 Y-93 1.860E+02 0.000E+00 0.000E+00 0.000E+00 7.440E+04 3.880E+05 0.000E+00 5.110E+00 ZR-95 1.900E+05 4.180E+04 0.000E+00 5.960E+04 2.230E+06 6.110E+04 0.000E+00 3.700E+04 ZR-97 1.880E+02 2.720E+01 0.000E+00 3.880E+01 1.130E+05 3.510E+05 0.000E+00 1.600E+01 NB-95 2.350E+04 9.180E+03 0.000E+00 8.620E+03 6.140E+05 3.700E+04 0.000E+00 6.550E+03 MO-99 0.000E+00 1.720E+02 0.000E+00 3.920E+02 1.350E+05 1.270E+05 0.000E+00 4.260E+01 TC-99M 1.780E-03 3.480E-03 0.000E+00 5.070E-02 9.510E+02 4.810E+03 0.000E+00 5.770E-02 TC-101 8.100E-05 8.510E-05 0.000E+00 1.450E-03 5.850E+02 1.630E+01 0.000E+00 1.080E-03 RU-103 2.790E+03 0.000E+00 0.000E+00 7.030E+03 6.620E+05 4.480E+04 0.000E+00 1.070E+03 RU-105 1.530E+00 0.000E+00 0.000E+00 1.340E+00 1.590E+04 9.950E+04 0.000E+00 5.550E-01 RU-106 1.360E+05 0.000E+00 0.000E+00 1.840E+05 1.430E+07 4.290E+05 0.000E+00 1.690E+04 AG-110M 1.690E+04 1.140E+04 0.000E+00 2.120E+04 5.480E+06 1.000E+05 0.000E+00 9.140E+03 TE-125M 6.730E+03 2.330E+03 1.920E+03 0.000E+00 4.770E+05 3.380E+04 0.000E+00 9.140E+02 TE-127 2.770E+00 9.510E-01 1.960E+00 7.070E+00 1.000E+04 5.620E+04 0.000E+00 6.100E-01 TE-127M 2.490E+04 8.550E+03 6.070E+03 6.360E+04 1.480E+06 7.140E+04 0.000E+00 3.020E+03 TE-129 9.770E-02 3.500E-02 7.140E-02 2.570E-01 2.930E+03 2.550E+04 0.000E+00 2.380E-02 TE-129M 1.920E+04 6.840E+03 6.330E+03 5.030E+04 1.760E+06 1.820E+05 0.000E+00 3.040E+03 TE-131 2.170E-02 8.440E-03 1.700E-02 5.880E-02 2.050E+03 1.330E+03 0.000E+00 6.590E-03 TE-131M 1.340E+02 5.920E+01 9.770E+01 4.000E+02 2.060E+05 3.080E+05 0.000E+00 5.070E+01 TE-132 4.810E+02 2.720E+02 3.170E+02 1.770E+03 3.770E+05 1.380E+05 0.000E+00 2.630E+02 I-130 8.180E+03 1.640E+04 1.850E+06 2.450E+04 0.000E+00 5.110E+03 0.000E+00 8.440E+03 Appendix I Ri Child Inhalation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 4.810E+04 4.810E+04 1.620E+07 7.880E+04 0.000E+00 2.840E+03 0.000E+00 2.730E+04 I-132 2.120E+03 4.070E+03 1.940E+05 6.250E+03 0.000E+00 3.200E+03 0.000E+00 1.880E+03 I-133 1.660E+04 2.030E+04 3.850E+06 3.380E+04 0.000E+00 5.480E+03 0.000E+00 7.700E+03 I-134 1.170E+03 2.160E+03 5.070E+04 3.300E+03 0.000E+00 9.550E+02 0.000E+00 9.950E+02 I-135 4.920E+03 8.730E+03 7.920E+05 1.340E+04 0.000E+00 4.440E+03 0.000E+00 4.140E+03 CS-134 6.510E+05 1.010E+06 0.000E+00 3.300E+05 1.210E+05 3.850E+03 0.000E+00 2.250E+05 CS-136 6.510E+04 1.710E+05 0.000E+00 9.550E+04 1.450E+04 4.180E+03 0.000E+00 1.160E+05 CS-137 9.060E+05 8.250E+05 0.000E+00 2.820E+05 1.040E+05 3.620E+03 0.000E+00 1.280E+05 CS-138 6.330E+02 8.400E+02 0.000E+00 6.220E+02 6.810E+01 2.700E+02 0.000E+00 5.550E+02 BA-139 1.840E+00 9.840E-04 0.000E+00 8.620E-04 5.770E+03 5.770E+04 0.000E+00 5.360E-02 BA-140 7.400E+04 6.480E+01 0.000E+00 2.110E+01 1.740E+06 1.020E+05 0.000E+00 4.330E+03 BA-141 1.960E-01 1.090E-04 0.000E+00 9.470E-05 2.920E+03 2.750E+02 0.000E+00 6.360E-03 BA-142 5.000E-02 3.600E-05 0.000E+00 2.910E-05 1.640E+03 2.740E+00 0.000E+00 2.790E-03 LA-140 6.440E+02 2.250E+02 0.000E+00 0.000E+00 1.830E+05 2.260E+05 0.000E+00 7.550E+01 LA-142 1.300E+00 4.110E-01 0.000E+00 0.000E+00 8.700E+03 7.580E+04 0.000E+00 1.290E-01 CE-141 3.920E+04 1.950E+04 0.000E+00 8.550E+03 5.440E+05 5.660E+04 0.000E+00 2.900E+03 CE-143 3.660E+02 1.990E+02 0.000E+00 8.360E+01 1.150E+05 1.270E+05 0.000E+00 2.870E+01 CE-144 6.770E+06 2.120E+06 0.000E+00 1.170E+06 1.200E+07 3.880E+05 0.000E+00 3.610E+05 PR-143 1.850E+04 5.550E+03 0.000E+00 3.000E+03 4.330E+05 9.730E+04 0.000E+00 9.140E+02 PR-144 5.960E-02 1.850E-02 0.000E+00 9.770E-03 1.570E+03 1.970E+02 0.000E+00 3.000E-03 ND-147 1.080E+04 8.730E+03 0.000E+00 4.810E+03 3.280E+05 8.210E+04 0.000E+00 6.810E+02 W-187 1.630E+01 9.660E+00 0.000E+00 0.000E+00 4.110E+04 9.100E+04 0.000E+00 4.330E+00 NP-239 4.660E+02 3.340E+01 0.000E+00 9.730E+01 5.810E+04 6.400E+04 0.000E+00 2.350E+01 Appendix I Ri Child Inhalation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.390E+07 1.190E+07 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 5.510E+06 4.660E+06 MN-54 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.630E+09 1.390E+09 MN-56 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 1.070E+06 9.020E+05 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 3.210E+08 2.730E+08 CO-58 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 4.440E+08 3.790E+08 CO-60 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.530E+10 2.150E+10 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 3.450E+05 2.970E+05 CU-64 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.880E+05 6.070E+05 ZN-65 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 8.590E+08 7.470E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 7.080E+03 4.870E+03 BR-84 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.360E+05 2.030E+05 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 1.030E+07 8.990E+06 RB-88 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.780E+04 3.310E+04 RB-89 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.480E+05 1.230E+05 SR-89 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.510E+04 2.160E+04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.510E+06 2.150E+06 Appendix I Ri Child Ground Plane Deposition - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 8.630E+05 7.770E+05 Y-90 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 5.310E+03 4.490E+03 Y-91 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.210E+06 1.070E+06 Y-91M 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.160E+05 1.000E+05 Y-92 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 2.140E+05 1.800E+05 Y-93 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 2.510E+05 1.830E+05 ZR-95 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.840E+08 2.450E+08 ZR-97 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 3.440E+06 2.960E+06 NB-95 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.610E+08 1.370E+08 MO-99 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 4.630E+06 3.990E+06 TC-99M 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 2.110E+05 1.840E+05 TC-101 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.260E+04 2.040E+04 RU-103 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.260E+08 1.080E+08 RU-105 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 7.210E+05 6.360E+05 RU-106 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 5.070E+08 4.220E+08 AG-110M 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 4.010E+09 3.440E+09 TE-125M 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 2.130E+06 1.550E+06 TE-127 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 3.280E+03 2.980E+03 TE-127M 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 1.080E+05 9.160E+04 TE-129 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 3.100E+04 2.620E+04 TE-129M 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 2.310E+07 1.980E+07 TE-131 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 3.450E+07 2.920E+04 TE-131M 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 9.460E+06 8.030E+06 TE-132 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.980E+06 4.230E+06 I-130 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 6.690E+06 5.510E+06 Appendix I Ri Child Ground Plane Deposition - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX I Ri Child Dose Factors for use in the Gaseous Dose Calculations Agegroup: CHILD Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 2.090E+07 1.720E+07 I-132 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.470E+06 1.250E+06 I-133 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.980E+06 2.450E+06 I-134 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 5.300E+05 4.470E+05 I-135 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.950E+06 2.530E+06 CS-134 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 8.000E+09 6.860E+09 CS-136 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.710E+08 1.510E+08 CS-137 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.200E+10 1.030E+10 CS-138 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 4.100E+05 3.590E+05 BA-139 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.190E+05 1.060E+05 BA-140 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.350E+07 2.050E+07 BA-141 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.750E+04 4.170E+04 BA-142 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 5.110E+04 4.490E+04 LA-140 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 2.180E+07 1.920E+07 LA-142 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 9.120E+05 7.600E+05 CE-141 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.540E+07 1.370E+07 CE-143 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.630E+06 2.310E+06 CE-144 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 8.040E+07 6.950E+07 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 2.110E+03 1.830E+03 ND-147 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 1.010E+07 8.390E+06 W-187 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.730E+06 2.350E+06 NP-239 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.980E+06 1.710E+06 Appendix I Ri Child Ground Plane Deposition - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 2.380E+03 2.380E+03 2.380E+03 2.380E+03 2.380E+03 0.000E+00 2.380E+03 C-14 2.340E+09 5.000E+08 5.000E+08 5.000E+08 5.000E+08 5.000E+08 0.000E+00 5.000E+08 NA-24 1.540E+07 1.540E+07 1.540E+07 1.540E+07 1.540E+07 1.540E+07 0.000E+00 1.540E+07 P-32 1.600E+11 9.430E+09 0.000E+00 0.000E+00 0.000E+00 2.170E+09 0.000E+00 6.210E+09 CR-51 0.000E+00 0.000E+00 1.050E+05 2.300E+04 2.050E+05 4.700E+06 0.000E+00 1.610E+05 MN-54 0.000E+00 3.900E+07 0.000E+00 8.640E+06 0.000E+00 1.430E+07 0.000E+00 8.840E+06 MN-56 0.000E+00 3.100E-02 0.000E+00 2.660E-02 0.000E+00 2.810E+00 0.000E+00 5.340E-03 FE-55 1.350E+08 8.730E+07 0.000E+00 0.000E+00 4.270E+07 1.110E+07 0.000E+00 2.330E+07 FE-59 2.240E+08 3.920E+08 0.000E+00 0.000E+00 1.160E+08 1.870E+08 0.000E+00 1.540E+08 CO-58 0.000E+00 2.420E+07 0.000E+00 0.000E+00 0.000E+00 6.040E+07 0.000E+00 6.050E+07 CO-60 0.000E+00 8.820E+07 0.000E+00 0.000E+00 0.000E+00 2.100E+08 0.000E+00 2.080E+08 NI-63 3.490E+10 2.160E+09 0.000E+00 0.000E+00 0.000E+00 1.070E+08 0.000E+00 1.210E+09 NI-65 3.510E+00 3.970E-01 0.000E+00 0.000E+00 0.000E+00 3.020E+01 0.000E+00 1.800E-01 CU-64 0.000E+00 1.850E+05 0.000E+00 3.140E+05 0.000E+00 3.810E+06 0.000E+00 8.590E+04 ZN-65 5.550E+09 1.900E+10 0.000E+00 9.230E+09 0.000E+00 1.610E+10 0.000E+00 8.780E+09 ZN-69 2.020E-11 3.630E-11 0.000E+00 1.510E-11 0.000E+00 2.960E-09 0.000E+00 2.700E-12 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.340E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.260E-22 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.230E+10 0.000E+00 0.000E+00 0.000E+00 5.690E+08 0.000E+00 1.100E+10 RB-88 0.000E+00 1.880E-44 0.000E+00 0.000E+00 0.000E+00 1.830E-44 0.000E+00 1.030E-44 RB-89 0.000E+00 3.290E-52 0.000E+00 0.000E+00 0.000E+00 1.120E-52 0.000E+00 2.260E-52 SR-89 1.260E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.590E+08 0.000E+00 3.610E+08 SR-90 1.220E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.520E+09 0.000E+00 3.100E+10 SR-91 2.720E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.220E+05 0.000E+00 9.830E+03 Appendix J Ri Infant Cow Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 4.640E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.000E+01 0.000E+00 1.720E-01 Y-90 6.810E+02 0.000E+00 0.000E+00 0.000E+00 0.000E+00 9.410E+05 0.000E+00 1.830E+01 Y-91 7.330E+04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.250E+06 0.000E+00 1.950E+03 Y-91M 5.670E-19 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.890E-15 0.000E+00 1.930E-20 Y-92 5.380E-04 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.030E+01 0.000E+00 1.510E-05 Y-93 2.160E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.700E+04 0.000E+00 5.870E-02 ZR-95 6.800E+03 1.660E+03 0.000E+00 1.790E+03 0.000E+00 8.260E+05 0.000E+00 1.180E+03 ZR-97 4.060E+00 6.970E-01 0.000E+00 7.030E-01 0.000E+00 4.450E+04 0.000E+00 3.180E-01 NB-95 5.930E+05 2.440E+05 0.000E+00 1.750E+05 0.000E+00 2.060E+08 0.000E+00 1.410E+05 MO-99 0.000E+00 2.080E+08 0.000E+00 3.110E+08 0.000E+00 6.850E+07 0.000E+00 4.060E+07 TC-99M 2.750E+01 5.670E+01 0.000E+00 6.100E+02 2.960E+01 1.650E+04 0.000E+00 7.300E+02 TC-101 2.470E-59 3.110E-59 0.000E+00 3.700E-58 1.700E-59 5.280E-57 0.000E+00 3.080E-58 RU-103 8.670E+03 0.000E+00 0.000E+00 1.800E+04 0.000E+00 1.050E+05 0.000E+00 2.900E+03 RU-105 8.050E-03 0.000E+00 0.000E+00 5.920E-02 0.000E+00 3.200E+00 0.000E+00 2.710E-03 RU-106 1.900E+05 0.000E+00 0.000E+00 2.250E+05 0.000E+00 1.440E+06 0.000E+00 2.380E+04 AG-110M 3.860E+08 2.820E+08 0.000E+00 4.030E+08 0.000E+00 1.460E+10 0.000E+00 1.860E+08 TE-125M 1.510E+08 5.040E+07 5.070E+07 0.000E+00 0.000E+00 7.180E+07 0.000E+00 2.040E+07 TE-127 6.320E+03 2.120E+03 5.140E+03 1.540E+04 0.000E+00 1.330E+05 0.000E+00 1.360E+03 TE-127M 4.210E+08 1.400E+08 1.220E+08 1.040E+09 0.000E+00 1.700E+08 0.000E+00 5.100E+07 TE-129 2.720E-09 9.380E-10 2.280E-09 6.770E-09 0.000E+00 2.170E-07 0.000E+00 6.350E-10 TE-129M 5.570E+08 1.910E+08 2.140E+08 1.390E+09 0.000E+00 3.330E+08 0.000E+00 8.580E+07 TE-131 3.430E-32 1.270E-32 3.060E-32 8.760E-32 0.000E+00 1.380E-30 0.000E+00 9.610E-33 TE-131M 3.380E+06 1.360E+06 2.750E+06 9.350E+06 0.000E+00 2.290E+07 0.000E+00 1.120E+06 TE-132 2.110E+07 1.040E+07 1.540E+07 6.530E+07 0.000E+00 3.870E+07 0.000E+00 9.750E+06 I-130 3.550E+06 7.810E+06 8.750E+08 8.580E+06 0.000E+00 1.670E+06 0.000E+00 3.130E+06 Appendix J Ri Infant Cow Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Grs/Cow/Milk (CMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 2.720E+09 3.200E+09 1.050E+12 3.740E+09 0.000E+00 1.140E+08 0.000E+00 1.410E+09 I-132 1.430E+00 2.900E+00 1.360E+02 3.240E+00 0.000E+00 2.350E+00 0.000E+00 1.030E+00 I-133 3.630E+07 5.280E+07 9.600E+09 6.210E+07 0.000E+00 8.930E+06 0.000E+00 1.550E+07 I-134 1.760E-11 3.600E-11 8.400E-10 4.030E-11 0.000E+00 3.720E-11 0.000E+00 1.280E-11 I-135 1.120E+05 2.230E+05 2.000E+07 2.490E+05 0.000E+00 8.080E+04 0.000E+00 8.140E+04 CS-134 3.650E+10 6.800E+10 0.000E+00 1.750E+10 7.180E+09 1.850E+08 0.000E+00 6.870E+09 CS-136 1.980E+09 5.810E+09 0.000E+00 2.320E+09 4.740E+08 8.820E+07 0.000E+00 2.170E+09 CS-137 5.150E+10 6.020E+10 0.000E+00 1.620E+10 6.550E+09 1.880E+08 0.000E+00 4.270E+09 CS-138 8.390E-23 1.360E-22 0.000E+00 6.800E-23 1.060E-23 2.180E-22 0.000E+00 6.610E-23 BA-139 4.270E-07 2.830E-10 0.000E+00 1.700E-10 1.720E-10 2.710E-05 0.000E+00 1.240E-08 BA-140 2.410E+08 2.410E+05 0.000E+00 5.720E+04 1.480E+05 5.920E+07 0.000E+00 1.240E+07 BA-141 3.930E-45 2.690E-48 0.000E+00 1.620E-48 1.640E-48 4.800E-44 0.000E+00 1.240E-46 BA-142 2.430E-79 2.020E-82 0.000E+00 1.160E-82 1.220E-82 1.000E-78 0.000E+00 1.200E-80 LA-140 4.050E+01 1.600E+01 0.000E+00 0.000E+00 0.000E+00 1.880E+05 0.000E+00 4.110E+00 LA-142 1.700E-10 6.250E-11 0.000E+00 0.000E+00 0.000E+00 1.060E-05 0.000E+00 1.500E-11 CE-141 4.340E+04 2.640E+04 0.000E+00 8.150E+03 0.000E+00 1.370E+07 0.000E+00 3.110E+03 CE-143 3.970E+02 2.630E+05 0.000E+00 7.670E+01 0.000E+00 1.540E+06 0.000E+00 3.000E+01 CE-144 2.330E+06 9.520E+05 0.000E+00 3.850E+05 0.000E+00 1.330E+08 0.000E+00 1.300E+05 PR-143 1.490E+03 5.550E+02 0.000E+00 2.060E+02 0.000E+00 7.840E+05 0.000E+00 7.360E+01 PR-144 5.690E-53 2.200E-53 0.000E+00 7.980E-54 0.000E+00 1.020E-48 0.000E+00 2.870E-54 ND-147 8.810E+02 9.050E+02 0.000E+00 3.490E+02 0.000E+00 5.740E+05 0.000E+00 5.550E+01 W-187 6.080E+04 4.230E+04 0.000E+00 0.000E+00 0.000E+00 2.480E+06 0.000E+00 1.460E+04 NP-239 3.650E+01 3.260E+00 0.000E+00 6.510E+00 0.000E+00 9.430E+04 0.000E+00 1.840E+00 Appendix J Ri Infant Cow Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 4.860E+03 4.860E+03 4.860E+03 4.860E+03 4.860E+03 0.000E+00 4.860E+03 C-14 2.340E+09 5.000E+08 5.000E+08 5.000E+08 5.000E+08 5.000E+08 0.000E+00 5.000E+08 NA-24 1.850E+06 1.850E+06 1.850E+06 1.850E+06 1.850E+06 1.850E+06 0.000E+00 1.850E+06 P-32 1.920E+11 1.130E+10 0.000E+00 0.000E+00 0.000E+00 2.600E+09 0.000E+00 7.460E+09 CR-51 0.000E+00 0.000E+00 1.260E+04 2.760E+03 2.460E+04 5.640E+05 0.000E+00 1.940E+04 MN-54 0.000E+00 4.680E+06 0.000E+00 1.040E+06 0.000E+00 1.720E+06 0.000E+00 1.060E+06 MN-56 0.000E+00 3.720E-03 0.000E+00 3.190E-03 0.000E+00 3.380E-01 0.000E+00 6.410E-04 FE-55 1.760E+06 1.130E+06 0.000E+00 0.000E+00 5.550E+05 1.440E+05 0.000E+00 3.030E+05 FE-59 2.920E+06 5.100E+06 0.000E+00 0.000E+00 1.510E+06 2.430E+06 0.000E+00 2.010E+06 CO-58 0.000E+00 2.910E+06 0.000E+00 0.000E+00 0.000E+00 7.250E+06 0.000E+00 7.260E+06 CO-60 0.000E+00 1.060E+07 0.000E+00 0.000E+00 0.000E+00 2.520E+07 0.000E+00 2.500E+07 NI-63 4.190E+09 2.590E+08 0.000E+00 0.000E+00 0.000E+00 1.290E+07 0.000E+00 1.450E+08 NI-65 4.210E-01 4.760E-02 0.000E+00 0.000E+00 0.000E+00 3.620E+00 0.000E+00 2.170E-02 CU-64 0.000E+00 2.070E+04 0.000E+00 3.500E+04 0.000E+00 4.240E+05 0.000E+00 9.570E+03 ZN-65 6.660E+08 2.280E+09 0.000E+00 1.110E+09 0.000E+00 1.930E+09 0.000E+00 1.050E+09 ZN-69 2.420E-12 4.360E-12 0.000E+00 1.810E-12 0.000E+00 3.550E-10 0.000E+00 3.240E-13 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.120E-01 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.510E-23 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 0.000E+00 2.670E+09 0.000E+00 0.000E+00 0.000E+00 6.830E+07 0.000E+00 1.320E+09 RB-88 0.000E+00 2.250E-45 0.000E+00 0.000E+00 0.000E+00 2.190E-45 0.000E+00 1.230E-45 RB-89 0.000E+00 3.940E-53 0.000E+00 0.000E+00 0.000E+00 1.340E-53 0.000E+00 2.720E-53 SR-89 2.640E+10 0.000E+00 0.000E+00 0.000E+00 0.000E+00 5.430E+08 0.000E+00 7.580E+08 SR-90 2.550E+11 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.190E+09 0.000E+00 6.500E+10 SR-91 5.700E+05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.750E+05 0.000E+00 2.060E+04 Appendix J Ri Infant Goat Milk - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 9.750E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.050E+02 0.000E+00 3.620E-01 Y-90 8.170E+01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.130E+05 0.000E+00 2.190E+00 Y-91 8.790E+03 0.000E+00 0.000E+00 0.000E+00 0.000E+00 6.300E+05 0.000E+00 2.340E+02 Y-91M 6.810E-20 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.270E-16 0.000E+00 2.320E-21 Y-92 6.450E-05 0.000E+00 0.000E+00 0.000E+00 0.000E+00 1.230E+00 0.000E+00 1.810E-06 Y-93 2.590E-01 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.040E+03 0.000E+00 7.050E-03 ZR-95 8.170E+02 1.990E+02 0.000E+00 2.140E+02 0.000E+00 9.910E+04 0.000E+00 1.410E+02 ZR-97 4.870E-01 8.360E-02 0.000E+00 8.430E-02 0.000E+00 5.340E+03 0.000E+00 3.820E-02 NB-95 7.120E+04 2.930E+04 0.000E+00 2.100E+04 0.000E+00 2.480E+07 0.000E+00 1.700E+04 MO-99 0.000E+00 2.500E+07 0.000E+00 3.730E+07 0.000E+00 8.220E+06 0.000E+00 4.870E+06 TC-99M 3.300E+00 6.800E+00 0.000E+00 7.320E+01 3.550E+00 1.970E+03 0.000E+00 8.760E+01 TC-101 2.960E-60 3.730E-60 0.000E+00 4.440E-59 2.030E-60 6.340E-58 0.000E+00 3.690E-59 RU-103 1.040E+03 0.000E+00 0.000E+00 2.170E+03 0.000E+00 1.270E+04 0.000E+00 3.480E+02 RU-105 9.660E-04 0.000E+00 0.000E+00 7.110E-03 0.000E+00 3.840E-01 0.000E+00 3.250E-04 RU-106 2.280E+04 0.000E+00 0.000E+00 2.700E+04 0.000E+00 1.730E+05 0.000E+00 2.850E+03 AG-110M 4.630E+07 3.380E+07 0.000E+00 4.830E+07 0.000E+00 1.750E+09 0.000E+00 2.240E+07 TE-125M 1.810E+07 6.050E+06 6.090E+06 0.000E+00 0.000E+00 8.620E+06 0.000E+00 2.450E+06 TE-127 7.580E+02 2.540E+02 6.170E+02 1.850E+03 0.000E+00 1.590E+04 0.000E+00 1.630E+02 TE-127M 5.050E+07 1.680E+07 1.460E+07 1.240E+08 0.000E+00 2.040E+07 0.000E+00 6.120E+06 TE-129 3.260E-10 1.130E-10 2.740E-10 8.130E-10 0.000E+00 2.610E-08 0.000E+00 7.620E-11 TE-129M 6.690E+07 2.290E+07 2.570E+07 1.670E+08 0.000E+00 3.990E+07 0.000E+00 1.030E+07 TE-131 4.110E-33 1.520E-33 3.670E-33 1.050E-32 0.000E+00 1.660E-31 0.000E+00 1.150E-33 TE-131M 4.050E+05 1.630E+05 3.310E+05 1.120E+06 0.000E+00 2.750E+06 0.000E+00 1.350E+05 TE-132 2.530E+06 1.250E+06 1.850E+06 7.840E+06 0.000E+00 4.640E+06 0.000E+00 1.170E+06 I-130 4.260E+06 9.370E+06 1.050E+09 1.030E+07 0.000E+00 2.010E+06 0.000E+00 3.760E+06 Appendix J Ri Infant Goat Milk - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Grs/Goat/Milk (GMILK) Units: m2 *mrem/yr / µCi/sec; mrem/yr / µCi/m3 (H-3)
Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.260E+09 3.850E+09 1.260E+12 4.490E+09 0.000E+00 1.370E+08 0.000E+00 1.690E+09 I-132 1.720E+00 3.480E+00 1.630E+02 3.890E+00 0.000E+00 2.820E+00 0.000E+00 1.240E+00 I-133 4.350E+07 6.340E+07 1.150E+10 7.450E+07 0.000E+00 1.070E+07 0.000E+00 1.860E+07 I-134 2.110E-11 4.320E-11 1.010E-09 4.830E-11 0.000E+00 4.470E-11 0.000E+00 1.540E-11 I-135 1.350E+05 2.680E+05 2.400E+07 2.990E+05 0.000E+00 9.700E+04 0.000E+00 9.770E+04 CS-134 1.090E+11 2.040E+11 0.000E+00 5.250E+10 2.150E+10 5.540E+08 0.000E+00 2.060E+10 CS-136 5.930E+09 1.740E+10 0.000E+00 6.950E+09 1.420E+09 2.650E+08 0.000E+00 6.510E+09 CS-137 1.540E+11 1.810E+11 0.000E+00 4.850E+10 1.960E+10 5.650E+08 0.000E+00 1.280E+10 CS-138 2.520E-22 4.090E-22 0.000E+00 2.040E-22 3.190E-23 6.540E-22 0.000E+00 1.980E-22 BA-139 5.130E-08 3.400E-11 0.000E+00 2.040E-11 2.060E-11 3.250E-06 0.000E+00 1.480E-09 BA-140 2.890E+07 2.890E+04 0.000E+00 6.870E+03 1.780E+04 7.100E+06 0.000E+00 1.490E+06 BA-141 4.720E-46 3.230E-49 0.000E+00 1.940E-49 1.960E-49 5.760E-45 0.000E+00 1.490E-47 BA-142 2.920E-80 2.430E-83 0.000E+00 1.400E-83 1.470E-83 1.200E-79 0.000E+00 1.440E-81 LA-140 4.860E+00 1.920E+00 0.000E+00 0.000E+00 0.000E+00 2.250E+04 0.000E+00 4.930E-01 LA-142 2.040E-11 7.500E-12 0.000E+00 0.000E+00 0.000E+00 1.270E-06 0.000E+00 1.790E-12 CE-141 5.200E+03 3.170E+03 0.000E+00 9.790E+02 0.000E+00 1.640E+06 0.000E+00 3.740E+02 CE-143 4.760E+01 3.160E+04 0.000E+00 9.200E+00 0.000E+00 1.840E+05 0.000E+00 3.600E+00 CE-144 2.790E+05 1.140E+05 0.000E+00 4.620E+04 0.000E+00 1.600E+07 0.000E+00 1.560E+04 PR-143 1.780E+02 6.670E+01 0.000E+00 2.480E+01 0.000E+00 9.410E+04 0.000E+00 8.840E+00 PR-144 6.830E-54 2.640E-54 0.000E+00 9.570E-55 0.000E+00 1.230E-49 0.000E+00 3.440E-55 ND-147 1.060E+02 1.090E+02 0.000E+00 4.190E+01 0.000E+00 6.880E+04 0.000E+00 6.650E+00 W-187 7.300E+03 5.070E+03 0.000E+00 0.000E+00 0.000E+00 2.980E+05 0.000E+00 1.750E+03 NP-239 4.380E+00 3.910E-01 0.000E+00 7.810E-01 0.000E+00 1.130E+04 0.000E+00 2.210E-01 Appendix J Ri Infant Goat Milk - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 6.470E+02 6.470E+02 6.470E+02 6.470E+02 6.470E+02 0.000E+00 6.470E+02 C-14 2.650E+04 5.310E+03 5.310E+03 5.310E+03 5.310E+03 5.310E+03 0.000E+00 5.310E+03 NA-24 1.060E+04 1.060E+04 1.060E+04 1.060E+04 1.060E+04 1.060E+04 0.000E+00 1.060E+04 P-32 2.030E+06 1.120E+05 0.000E+00 0.000E+00 0.000E+00 1.610E+04 0.000E+00 7.740E+04 CR-51 0.000E+00 0.000E+00 5.750E+01 1.320E+01 1.280E+04 3.570E+02 0.000E+00 8.950E+01 MN-54 0.000E+00 2.530E+04 0.000E+00 4.980E+03 1.000E+06 7.060E+03 0.000E+00 4.980E+03 MN-56 0.000E+00 1.540E+00 0.000E+00 1.100E+00 1.250E+04 7.170E+04 0.000E+00 2.210E-01 FE-55 1.970E+04 1.170E+04 0.000E+00 0.000E+00 8.690E+04 1.090E+03 0.000E+00 3.330E+03 FE-59 1.360E+04 2.350E+04 0.000E+00 0.000E+00 1.010E+06 2.480E+04 0.000E+00 9.480E+03 CO-58 0.000E+00 1.220E+03 0.000E+00 0.000E+00 7.770E+05 1.110E+04 0.000E+00 1.820E+03 CO-60 0.000E+00 8.020E+03 0.000E+00 0.000E+00 4.510E+06 3.190E+04 0.000E+00 1.180E+04 NI-63 3.390E+05 2.040E+04 0.000E+00 0.000E+00 2.090E+05 2.420E+03 0.000E+00 1.160E+04 NI-65 2.390E+00 2.840E-01 0.000E+00 0.000E+00 8.120E+03 5.010E+04 0.000E+00 1.230E-01 CU-64 0.000E+00 1.880E+00 0.000E+00 3.980E+00 9.300E+03 1.500E+04 0.000E+00 7.740E-01 ZN-65 1.930E+04 6.260E+04 0.000E+00 3.250E+04 6.470E+05 5.140E+04 0.000E+00 3.110E+04 ZN-69 5.390E-02 9.670E-02 0.000E+00 4.020E-02 1.470E+03 1.320E+04 0.000E+00 7.180E-03 BR-83 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 3.810E+02 BR-84 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 4.000E+02 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 2.040E+01 RB-86 0.000E+00 1.900E+05 0.000E+00 0.000E+00 0.000E+00 3.040E+03 0.000E+00 8.820E+04 RB-88 0.000E+00 5.570E+02 0.000E+00 0.000E+00 0.000E+00 3.390E+02 0.000E+00 2.870E+02 RB-89 0.000E+00 3.210E+02 0.000E+00 0.000E+00 0.000E+00 6.820E+01 0.000E+00 2.060E+02 SR-89 3.980E+05 0.000E+00 0.000E+00 0.000E+00 2.030E+06 6.400E+04 0.000E+00 1.140E+04 SR-90 4.090E+07 0.000E+00 0.000E+00 0.000E+00 1.120E+07 1.310E+05 0.000E+00 2.590E+06 SR-91 9.560E+01 0.000E+00 0.000E+00 0.000E+00 5.260E+04 7.340E+04 0.000E+00 3.460E+00 Appendix J Ri Infant Inhalation - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 1.050E+01 0.000E+00 0.000E+00 0.000E+00 2.380E+04 1.400E+05 0.000E+00 3.910E-01 Y-90 3.290E+03 0.000E+00 0.000E+00 0.000E+00 2.690E+05 1.040E+05 0.000E+00 8.820E+01 Y-91 5.880E+05 0.000E+00 0.000E+00 0.000E+00 2.450E+06 7.030E+04 0.000E+00 1.570E+04 Y-91M 4.070E-01 0.000E+00 0.000E+00 0.000E+00 2.790E+03 2.350E+03 0.000E+00 1.390E-02 Y-92 1.640E+01 0.000E+00 0.000E+00 0.000E+00 2.450E+04 1.270E+05 0.000E+00 4.610E-01 Y-93 1.500E+02 0.000E+00 0.000E+00 0.000E+00 7.640E+04 1.670E+05 0.000E+00 4.070E+00 ZR-95 1.150E+05 2.790E+04 0.000E+00 3.110E+04 1.750E+06 2.170E+04 0.000E+00 2.030E+04 ZR-97 1.500E+02 2.560E+01 0.000E+00 2.590E+01 1.100E+05 1.400E+05 0.000E+00 1.170E+01 NB-95 1.570E+04 6.430E+03 0.000E+00 4.720E+03 4.790E+05 1.270E+04 0.000E+00 3.780E+03 MO-99 0.000E+00 1.650E+02 0.000E+00 2.650E+02 1.350E+05 4.870E+04 0.000E+00 3.230E+01 TC-99M 1.400E-03 2.880E-03 0.000E+00 3.110E-02 8.110E+02 2.030E+03 0.000E+00 3.720E-02 TC-101 6.510E-05 8.230E-05 0.000E+00 9.790E-04 5.840E+02 8.440E+02 0.000E+00 8.120E-04 RU-103 2.020E+03 0.000E+00 0.000E+00 4.240E+03 5.520E+05 1.610E+04 0.000E+00 6.790E+02 RU-105 1.220E+00 0.000E+00 0.000E+00 8.990E-01 1.570E+04 4.840E+04 0.000E+00 4.100E-01 RU-106 8.680E+04 0.000E+00 0.000E+00 1.070E+05 1.160E+07 1.640E+05 0.000E+00 1.090E+04 AG-110M 9.980E+03 7.220E+03 0.000E+00 1.090E+04 3.670E+06 3.300E+04 0.000E+00 5.000E+03 TE-125M 4.760E+03 1.990E+03 1.620E+03 0.000E+00 4.470E+05 1.290E+04 0.000E+00 6.580E+02 TE-127 2.230E+00 9.530E-01 1.850E+00 4.860E+00 1.030E+04 2.440E+04 0.000E+00 4.890E-01 TE-127M 1.670E+04 6.900E+03 4.870E+03 3.750E+04 1.310E+06 2.730E+04 0.000E+00 2.070E+03 TE-129 7.880E-02 3.470E-02 6.750E-02 1.750E-01 3.000E+03 2.630E+04 0.000E+00 1.880E-02 TE-129M 1.410E+04 6.090E+03 5.470E+03 3.180E+04 1.680E+06 6.900E+04 0.000E+00 2.230E+03 TE-131 1.740E-02 8.220E-03 1.580E-02 3.990E-02 2.060E+03 8.220E+03 0.000E+00 5.000E-03 TE-131M 1.070E+02 5.500E+01 8.930E+01 2.650E+02 1.990E+05 1.190E+05 0.000E+00 3.630E+01 TE-132 3.720E+02 2.370E+02 2.790E+02 1.030E+03 3.400E+05 4.410E+04 0.000E+00 1.760E+02 I-130 6.360E+03 1.390E+04 1.600E+06 1.530E+04 0.000E+00 1.990E+03 0.000E+00 5.570E+03 Appendix J Ri Infant Inhalation - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Inhalation (INHL) Units: mrem/yr / µCi/m3 Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 3.790E+04 4.440E+04 1.480E+07 5.180E+04 0.000E+00 1.060E+03 0.000E+00 1.960E+04 I-132 1.690E+03 3.540E+03 1.690E+05 3.950E+03 0.000E+00 1.900E+03 0.000E+00 1.260E+03 I-133 1.320E+04 1.920E+04 3.560E+06 2.240E+04 0.000E+00 2.160E+03 0.000E+00 5.600E+03 I-134 9.210E+02 1.880E+03 4.450E+04 2.090E+03 0.000E+00 1.290E+03 0.000E+00 6.650E+02 I-135 3.860E+03 7.600E+03 6.960E+05 8.470E+03 0.000E+00 1.830E+03 0.000E+00 2.770E+03 CS-134 3.960E+05 7.030E+05 0.000E+00 1.900E+05 7.970E+04 1.330E+03 0.000E+00 7.450E+04 CS-136 4.830E+04 1.350E+05 0.000E+00 5.640E+04 1.180E+04 1.430E+03 0.000E+00 5.290E+04 CS-137 5.490E+05 6.120E+05 0.000E+00 1.720E+05 7.130E+04 1.330E+03 0.000E+00 4.550E+04 CS-138 5.050E+02 7.810E+02 0.000E+00 4.100E+02 6.540E+01 8.760E+02 0.000E+00 3.980E+02 BA-139 1.480E+00 9.840E-04 0.000E+00 5.920E-04 5.950E+03 5.100E+04 0.000E+00 4.300E-02 BA-140 5.600E+04 5.600E+01 0.000E+00 1.340E+01 1.600E+06 3.840E+04 0.000E+00 2.900E+03 BA-141 1.570E-01 1.080E-04 0.000E+00 6.500E-05 2.970E+03 4.750E+03 0.000E+00 4.970E-03 BA-142 3.980E-02 3.300E-05 0.000E+00 1.900E-05 1.550E+03 6.930E+02 0.000E+00 1.960E-03 LA-140 5.050E+02 2.000E+02 0.000E+00 0.000E+00 1.680E+05 8.480E+04 0.000E+00 5.150E+01 LA-142 1.030E+00 3.770E-01 0.000E+00 0.000E+00 8.220E+03 5.950E+04 0.000E+00 9.040E-02 CE-141 2.770E+04 1.670E+04 0.000E+00 5.250E+03 5.170E+05 2.160E+04 0.000E+00 1.990E+03 CE-143 2.930E+02 1.930E+02 0.000E+00 5.640E+01 1.160E+05 4.970E+04 0.000E+00 2.210E+01 CE-144 3.190E+06 1.210E+06 0.000E+00 5.380E+05 9.840E+06 1.480E+05 0.000E+00 1.760E+05 PR-143 1.400E+04 5.240E+03 0.000E+00 1.970E+03 4.330E+05 3.720E+04 0.000E+00 6.990E+02 PR-144 4.790E-02 1.850E-02 0.000E+00 6.720E-03 1.610E+03 4.280E+03 0.000E+00 2.410E-03 ND-147 7.940E+03 8.130E+03 0.000E+00 3.150E+03 3.220E+05 3.120E+04 0.000E+00 5.000E+02 W-187 1.300E+01 9.020E+00 0.000E+00 0.000E+00 3.960E+04 3.560E+04 0.000E+00 3.120E+00 NP-239 3.710E+02 3.320E+01 0.000E+00 6.620E+01 5.950E+04 2.490E+04 0.000E+00 1.880E+01 Appendix J Ri Infant Inhalation - Page 3 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body H-3 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 C-14 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NA-24 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.190E+07 1.390E+07 1.190E+07 P-32 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 CR-51 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 4.660E+06 5.510E+06 4.660E+06 MN-54 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.390E+09 1.630E+09 1.390E+09 MN-56 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 9.020E+05 1.070E+06 9.020E+05 FE-55 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 FE-59 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 2.730E+08 3.210E+08 2.730E+08 CO-58 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 3.790E+08 4.440E+08 3.790E+08 CO-60 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.150E+10 2.530E+10 2.150E+10 NI-63 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 NI-65 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 2.970E+05 3.450E+05 2.970E+05 CU-64 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.070E+05 6.880E+05 6.070E+05 ZN-65 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 7.470E+08 8.590E+08 7.470E+08 ZN-69 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 BR-83 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 4.870E+03 7.080E+03 4.870E+03 BR-84 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.030E+05 2.360E+05 2.030E+05 BR-85 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 RB-86 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 8.990E+06 1.030E+07 8.990E+06 RB-88 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.310E+04 3.780E+04 3.310E+04 RB-89 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.230E+05 1.480E+05 1.230E+05 SR-89 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.160E+04 2.510E+04 2.160E+04 SR-90 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 SR-91 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.150E+06 2.510E+06 2.150E+06 Appendix J Ri Infant Ground Plane Deposition - Page 1 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body SR-92 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 7.770E+05 8.630E+05 7.770E+05 Y-90 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 4.490E+03 5.310E+03 4.490E+03 Y-91 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.070E+06 1.210E+06 1.070E+06 Y-91M 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.000E+05 1.160E+05 1.000E+05 Y-92 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 1.800E+05 2.140E+05 1.800E+05 Y-93 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 1.830E+05 2.510E+05 1.830E+05 ZR-95 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.450E+08 2.840E+08 2.450E+08 ZR-97 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 2.960E+06 3.440E+06 2.960E+06 NB-95 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.370E+08 1.610E+08 1.370E+08 MO-99 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 3.990E+06 4.630E+06 3.990E+06 TC-99M 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 1.840E+05 2.110E+05 1.840E+05 TC-101 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.040E+04 2.260E+04 2.040E+04 RU-103 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.080E+08 1.260E+08 1.080E+08 RU-105 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 6.360E+05 7.210E+05 6.360E+05 RU-106 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 4.220E+08 5.070E+08 4.220E+08 AG-110M 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 3.440E+09 4.010E+09 3.440E+09 TE-125M 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 1.550E+06 2.130E+06 1.550E+06 TE-127 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 2.980E+03 3.280E+03 2.980E+03 TE-127M 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 9.160E+04 1.080E+05 9.160E+04 TE-129 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 2.620E+04 3.100E+04 2.620E+04 TE-129M 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 1.980E+07 2.310E+07 1.980E+07 TE-131 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 2.920E+04 3.450E+07 2.920E+04 TE-131M 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 8.030E+06 9.460E+06 8.030E+06 TE-132 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.230E+06 4.980E+06 4.230E+06 I-130 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 5.510E+06 6.690E+06 5.510E+06 Appendix J Ri Infant Ground Plane Deposition - Page 2 of 3
Oconee Nuclear Station January, 2004 Offsite Dose Calculation Manual (ODCM) Revision 44 APPENDIX J Ri Infant Dose Factors for use in the Gaseous Dose Calculations Agegroup: INFANT Pathway: Ground Plane Deposition (GPD) Units: m2 *mrem/yr / µCi/sec Nuclide Bone Liver Thyroid Kidney Lung Gilli Skin Total Body I-131 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 1.720E+07 2.090E+07 1.720E+07 I-132 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.250E+06 1.470E+06 1.250E+06 I-133 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.450E+06 2.980E+06 2.450E+06 I-134 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 4.470E+05 5.300E+05 4.470E+05 I-135 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.530E+06 2.950E+06 2.530E+06 CS-134 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 6.860E+09 8.000E+09 6.860E+09 CS-136 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.510E+08 1.710E+08 1.510E+08 CS-137 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.030E+10 1.200E+10 1.030E+10 CS-138 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 3.590E+05 4.100E+05 3.590E+05 BA-139 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.060E+05 1.190E+05 1.060E+05 BA-140 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.050E+07 2.350E+07 2.050E+07 BA-141 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.170E+04 4.750E+04 4.170E+04 BA-142 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 4.490E+04 5.110E+04 4.490E+04 LA-140 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 1.920E+07 2.180E+07 1.920E+07 LA-142 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 7.600E+05 9.120E+05 7.600E+05 CE-141 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.370E+07 1.540E+07 1.370E+07 CE-143 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.310E+06 2.630E+06 2.310E+06 CE-144 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 6.950E+07 8.040E+07 6.950E+07 PR-143 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 0.000E+00 PR-144 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 1.830E+03 2.110E+03 1.830E+03 ND-147 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 8.390E+06 1.010E+07 8.390E+06 W-187 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.350E+06 2.730E+06 2.350E+06 NP-239 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.710E+06 1.980E+06 1.710E+06 Appendix J Ri Infant Ground Plane Deposition - Page 3 of 3