|
---|
Category:License-Monthly Operating Report
MONTHYEARML0517204222005-06-13013 June 2005 May 2005 Monthly Operating Report for Braidwood Station Units 1 & 2 ML0513902882005-05-13013 May 2005 April 2005 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0511201952005-04-15015 April 2005 March 2005 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0508105832005-03-14014 March 2005 February 2005 Monthly Operating Report for Braidwood, Units 1 & 2 ML0505405672005-02-14014 February 2005 January 2005 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0502601972005-01-14014 January 2005 December 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0435802392004-12-14014 December 2004 November 2004 Monthly Operating Report Braidwood Station Units 1 and 2 ML0432804062004-11-12012 November 2004 October 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0429903872004-10-14014 October 2004 September 2004 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0426600472004-09-13013 September 2004 August 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0423702802004-08-13013 August 2004 July 2004 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0420303442004-07-13013 July 2004 June 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0417406942004-06-11011 June 2004 May 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0414502852004-05-13013 May 2004 April 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0411203522004-04-13013 April 2004 March 2004 Monthly Operating Report for Braidwood, Units 1 & 2 ML0411703002004-03-12012 March 2004 February 2004 Monthly Operating Report for Braidwood, Units 1 and 2 ML0404905272004-02-12012 February 2004 January 2004 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0402107402004-01-13013 January 2004 December 2003 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0402107412004-01-13013 January 2004 December 2003 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0335702042003-12-15015 December 2003 November 2003 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0332903592003-11-12012 November 2003 October 2003 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0329405892003-10-10010 October 2003 September 2003 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0326709902003-09-12012 September 2003 August 2003 Monthly Operating Report for Braidwood, Units 1 & 2 ML0323302572003-08-14014 August 2003 July 2003 Monthly Operating Report for Braidwood Station ML0321103932003-07-14014 July 2003 June 2003 Monthly Operating Report for Braidwood, Units 1 & 2 ML0317003802003-06-11011 June 2003 May 2003 Monthly Operating Report for Braidwood Station Units 1 & 2 ML0313507492003-05-0909 May 2003 April 2003 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0311301112003-04-11011 April 2003 March 2003 Monthly Operating Report for Braidwood Units 1 & 2 ML0307902852003-03-12012 March 2003 February 2003 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0305501252003-02-12012 February 2003 January 2003 Monthly Operating Report for Braidwood Units 1 & 2 ML0302703502003-01-14014 January 2003 December 2002 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0236000342002-12-13013 December 2002 November 2002 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0232602872002-11-14014 November 2002 October 2002 Monthly Operating Report for Braidwood Units 1 & 2 ML0229605412002-10-14014 October 2002 September 2002 Monthly Operating Report for Braidwood Station, Units 1 and 2 ML0226804842002-09-13013 September 2002 August 2002 Monthly Operating Report for Braidwood Units 1 & 2 ML0224802712002-08-12012 August 2002 July 2002 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0220500632002-07-12012 July 2002 June 2002 Monthly Operating Report for Braidwood Units 1 & 2 ML0217000942002-06-12012 June 2002 May 2002 Monthly Operating Report for Braidwood Units 1 & 2 ML0215002292002-05-13013 May 2002 April 2002 Monthly Operating Report for Braidwood Station Units 1 and 2 ML0211903762002-04-12012 April 2002 March 2002 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0208007562002-03-13013 March 2002 February 2002 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0207106322002-02-12012 February 2002 January 2002 Monthly Operating Report for Braidwood Station, Units 1 & 2 ML0204300142002-01-11011 January 2002 December 2001 Monthly Operating Report for Braidwood Station, Units 1 & 2 2005-06-13
[Table view] |
Text
Exelinm Exelon Generation Company, LLC www.exeloncorp.com Nuclear Braidwood Station 35100 South Rt 53, Suite 84 Braceville, IL60407-9619 Tel. 815-458-2801 January 11, 2002 BW020002 U. S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D. C. 20555-0001 Braidwood Station, Units I and 2 Facility Operating License Nos. NPF-72 and NPF-77 NRC Docket Nos. STN 50-456 and STN 50-457
Subject:
Monthly Operating Report In accordance with Technical Specification 5.6.4, "Monthly Operating Reports," we are submitting the Monthly Operating Report for Braidwood Station, Units 1 and 2. This report covers the period of December 1, 2001 to December 31, 2001.
If you have any questions regarding this letter, please contact Ms. Amy Ferko, Regulatory Assurance Manager, at (815) 417-2699.
Respectfully, G. K. Schwartz Plant Manager Braidwood Station Attachment cc: Regional Administrator- NRC Region III NRC Senior Resident Inspector- Braidwood Station
ATTACHMENT BRAIDWOOD STATION UNITS 1 AND 2 MONTHLY OPERATING REPORT EXELON GENERATION COMPANY, LLC FACILITY OPERATING LICENSE NOS. NPF-72 AND NPF-77 NRC DOCKET NOS. STN 50-456 AND STN 50-457
A. OPERATING DATA REPORT Docket No: 50-456 Unit: Braidwood 1 Date: 01/09/2002 Completed by: Don Hildebrant Telephone: (815)417-2173 REPORTING PERIOD: December 2001
- 1) Design Electrical Rating (MWe Net) 1187
- 2) Maximum Dependable Capacity (MWe Net) 1168 Month Year To Date Cumulative
- 3) Hours Reactor Critical (Hours) 744.0 8,287.7 97,744.5
- 4) Hours Generator on Line (Hours) 744.0 8,247.6 96,782.8
- 5) Unit Reserve Shutdown Hours (Hours) 0.0 0.0 0.0
- 6) Net Electrical Energy (Mwh) 911,644 9,557,872 102,485,180
B. UNIT SHUTDOWNS Docket No.: 50 - 456 Unit: Braidwood 1 Date: 01/09/2002 Completed by: Don Hildebrant Telephone: (815)417-2173 REPORT PERIOD: December 2001 No. Date Type Duration Reason Method Cause and Corrective Actions Hours and Comments
SUMMARY
Unit performed normally at full load for the entire month.
TYPE REASON METHOD F - Forced A - Equipment Failure (explain) 1 - Manual S - Scheduled B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / Licensee Examination 5 - Other (explain)
F -Administrative G - Operator Error (explain)
H - Other (explain)
C. SAFETY / RELIEF VALVE OPERATIONS Docket No.: 50-456 Unit: Braidwood 1 Date: 01/09/2002 Completed by: Don Hildebrant Telephone: (815)417-2173 Valves No. & Type Plant Date Actuated Actuation Condition Description of Event None
A. OPERATING DATA REPORT Docket No: 50-457 Unit: Braidwood 2 Date: 01/09/2002 Completed by: Don Hildebrant Telephone: (815)417-2173 REPORTING PERIOD: December 2001
- 1) Design Electrical Rating (Mwe Net) 1155
- 2) Maximum Dependable Capacity (Mwe Net) 1122 Month Year To Date Cumulative
- 3) Hours Reactor Critical (Hours) 744.0 8,497.2 101,858.4
- 4) Hours Generator on Line (Hours) 744.0 8,481.3 101,347.7
- 5) Unit Reserve Shutdown Hours (Hours) 0.0 0.0 0.0
- 6) Net Electrical Energy (Mwh) 867,023 9,647,858 107,757,151
B. UNIT SHUTDOWNS Docket No.: 50 - 457 Unit: Braidwood 2 Date: 01/09/2002 Completed by: Don Hildebrant Telephone: (815)417-2173 REPORT PERIOD: December 2001 No. Date Type Duration Reason Method Cause and Corrective Actions and Comments Hours none
SUMMARY
Unit performed normally at full load for the entire month.
TYPE REASON METHOD F - Forced A - Equipment Failure (explain) 1 - Manual S - Scheduled B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / Licensee Examination 5 - Other (explain)
F - Administrative G - Operator Error (explain)
H - Other (explain)
C. SAFETY / RELIEF VALVE OPERATIONS Docket No.: 50 - 457 Unit: Braidwood 2 Date: 01/09/2002 Completed by: Don Hildebrant Telephone: (815)417-2173 Valves No. & Type Plant Date Actuated Actuation Condition Description of Event None