MONTHYEARL-15-150, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-05-27027 May 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI ML15280A0742015-10-0909 October 2015 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI L-15-325, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-11-0606 November 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI ML15320A4132015-11-24024 November 2015 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI L-15-371, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-12-21021 December 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI L-16-058, Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052016-02-24024 February 2016 Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Supplement ML16099A0112016-03-0303 March 2016 NRR E-mail Capture - Draft 3rd Round PRA RAIs - Beaver Valley Units 1 & 2 - NFPA-805 LAR (CAC Nos. MF3301 & MF3302) Project stage: Draft RAI ML16084A8442016-03-30030 March 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI ML16089A0622016-03-30030 March 2016 Meeting to Discuss BVPS Draft PRA RAI - Slides Project stage: Request ML16071A1222016-04-0707 April 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI ML16105A0082016-04-25025 April 2016 March 30, 2016, Summary of Meeting with Firstenergy Nuclear Operating Company on Its Draft Probabilistic Risk Assessment RAI Related to Its License Amendment Request to Adopt NFPA Standard 805 Project stage: Draft RAI L-16-162, Response to Requests for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805, and Request to Change Implementation Schedule2016-05-12012 May 2016 Response to Requests for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805, and Request to Change Implementation Schedule Project stage: Response to RAI ML16158A0022016-06-0101 June 2016 NRR E-mail Capture - Beaver Valley, Units 1 & 2 - Update on NFPA 805 (CAC Nos. MF3301 & MF3302) Project stage: Other ML16333A0162016-12-0202 December 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI L-17-024, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052017-01-30030 January 2017 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI L-17-197, Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052017-06-23023 June 2017 Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Supplement ML17220A2342017-08-0808 August 2017 E-mail Regarding Request for Additional Information for NFPA 805 License Amendment Request Project stage: RAI ML17313A6422017-11-0909 November 2017 Transmittal of Draft Safety Evaluation for Proposed Amendments Transition to NFPA 805 (CAC Nos. MF3301 and MF3302; EPID L-2013-LLF-0001) Project stage: Draft Approval ML17335A0962017-11-27027 November 2017 NRR E-mail Capture - Beaver Valley: NFPA 805 LAR: License Condition: Fire Protection Program Changes That Have More than Minimal Risk Impact (CAC Nos. MF3301 and MF3302; EPID L-2013-LLF-0001) Project stage: Other ML18058A9422017-12-11011 December 2017 NFPA 805 Amendment Application Transition License Condition Project stage: Other ML17291A0812018-01-22022 January 2018 Issuance of Amendments Transition to NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants (CAC Nos. MF3301 and MF3302; EPID L-2013-LLF-0001) Project stage: Approval ML18058B0722018-02-23023 February 2018 BVPS NFPA 805 License Amendment Change Requested, and Other SE Comments Project stage: Other ML18059A7982018-02-26026 February 2018 BVPS NFPA 805 License Amendment Change Requested, and Other SE Comments Project stage: Other ML18058A9852018-02-27027 February 2018 BVPS-1 License Condition Page Project stage: Other ML18058A9532018-02-27027 February 2018 Comments on BVPS SE Project stage: Other ML18065A4032018-04-0505 April 2018 Correction of Errors in Safety Evaluation Associated with License Amendment Nos. 301 and 190 Project stage: Approval ML18099A2322018-04-18018 April 2018 Correction of an Error in the Renewed Facility Operating License No. DPR-66 Associated with License Amendment No. 301 CAC No. MF3301; EPID L-2013-LLF-0001) Project stage: Other 2016-06-01
[Table View] |
|
---|
Category:Letter type:L
MONTHYEARL-23-267, Submittal of Discharge Monitoring Report (Npdes), Permit No. PA00256152023-12-18018 December 2023 Submittal of Discharge Monitoring Report (Npdes), Permit No. PA0025615 L-23-229, Request for Additional Information Regarding the Spring 2023 Generic Letter 95-05 Voltage-Based Alternate Repair Criteria and Steam Generator F-Star Reports2023-11-29029 November 2023 Request for Additional Information Regarding the Spring 2023 Generic Letter 95-05 Voltage-Based Alternate Repair Criteria and Steam Generator F-Star Reports L-23-247, Discharge Monitoring Report (NPDES) Permit No. PA00256152023-11-17017 November 2023 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-23-227, Discharge Monitoring Report (NPDES) Permit No. PA0025615 for Third Quarter 20232023-10-20020 October 2023 Discharge Monitoring Report (NPDES) Permit No. PA0025615 for Third Quarter 2023 L-23-208, Submittal of Discharge Monitoring Report Cnpdes), Permit No. PA00256152023-09-14014 September 2023 Submittal of Discharge Monitoring Report Cnpdes), Permit No. PA0025615 L-23-167, Twenty-Third Refueling Outage Inservice Inspection Summary Report2023-09-13013 September 2023 Twenty-Third Refueling Outage Inservice Inspection Summary Report L-23-205, Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments2023-09-12012 September 2023 Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments L-23-172, Quality Assurance Program Manual2023-08-31031 August 2023 Quality Assurance Program Manual L-23-188, Energy Harbor Nuclear Corp., Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments2023-08-0707 August 2023 Energy Harbor Nuclear Corp., Supplement to Application for Order Consenting to Transfer of Licenses and Conforming License Amendments L-23-179, Submittal of Discharge Monitoring Report, (NPDES) Permit No. PA00256152023-07-18018 July 2023 Submittal of Discharge Monitoring Report, (NPDES) Permit No. PA0025615 L-23-165, Discharge Monitoring Report (NPDES) Permit No. PA00256152023-06-26026 June 2023 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-23-139, Response to Request for Additional Information Regarding Fall 2022 180-Day Steam Generator Tube Inspection Report2023-06-13013 June 2023 Response to Request for Additional Information Regarding Fall 2022 180-Day Steam Generator Tube Inspection Report L-23-055, Submittal of the Updated Final Safety Analysis Report, Revision 342023-05-23023 May 2023 Submittal of the Updated Final Safety Analysis Report, Revision 34 L-23-065, Annual Financial Report2023-05-22022 May 2023 Annual Financial Report L-23-137, Discharge Monitoring Report (NPDES) Permit No. PA00256152023-05-18018 May 2023 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-23-125, Cycle 24 Core Operating Limits Report2023-05-17017 May 2023 Cycle 24 Core Operating Limits Report L-23-132, Response to NRC Regulatory Issue Summary 2023-01 Preparation and Scheduling of Operator Licensing Examinations2023-05-10010 May 2023 Response to NRC Regulatory Issue Summary 2023-01 Preparation and Scheduling of Operator Licensing Examinations L-23-129, Response to Request for Additional Information for 10 CFR 50.55a Request 2-TYP-4-RV-06 for Alternative Repair Methods for Reactor Pressure Vessel Head Penetrations2023-05-0505 May 2023 Response to Request for Additional Information for 10 CFR 50.55a Request 2-TYP-4-RV-06 for Alternative Repair Methods for Reactor Pressure Vessel Head Penetrations L-23-115, Submittal of 2022 Annual Radioactive Effluent Release Report, 2022 Annual Radiological Environmental Operating Report, and 2022 Annual Environmental Operating Report (Non-Radiological2023-04-27027 April 2023 Submittal of 2022 Annual Radioactive Effluent Release Report, 2022 Annual Radiological Environmental Operating Report, and 2022 Annual Environmental Operating Report (Non-Radiological L-23-126, Discharge Monitoring Report (Npdes), Permit No. PA00256152023-04-22022 April 2023 Discharge Monitoring Report (Npdes), Permit No. PA0025615 L-23-053, 2022 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models2023-04-14014 April 2023 2022 Annual 10 CFR 50.46 Report of Changes to or Errors in Emergency Core Cooling System Evaluation Models L-23-061, Submittal of the Decommissioning Funding Status Reports2023-03-31031 March 2023 Submittal of the Decommissioning Funding Status Reports L-23-058, 180-Day Steam Generator Tube Inspection Report2023-03-27027 March 2023 180-Day Steam Generator Tube Inspection Report L-23-066, Annual Notification of Property Insurance Coverage2023-03-21021 March 2023 Annual Notification of Property Insurance Coverage L-23-036, Report of Facility Changes, Tests and Experiments2023-03-13013 March 2023 Report of Facility Changes, Tests and Experiments L-23-086, Response to Request for Additional Information for Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair2023-03-0404 March 2023 Response to Request for Additional Information for Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair L-23-087, Supplement to Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair (L-2023-LLA-0027)2023-03-0404 March 2023 Supplement to Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair (L-2023-LLA-0027) L-23-073, Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair2023-03-0101 March 2023 Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair L-23-016, Twenty-Eighth Refueling Outage Inservice Inspection Summary Report2023-02-21021 February 2023 Twenty-Eighth Refueling Outage Inservice Inspection Summary Report L-23-064, Discharge Monitoring Report, (NPDES) Permit No. PA00256152023-02-21021 February 2023 Discharge Monitoring Report, (NPDES) Permit No. PA0025615 L-23-057, Energy Harbor Nuclear Corp Retrospective Premium Guarantee2023-02-20020 February 2023 Energy Harbor Nuclear Corp Retrospective Premium Guarantee L-22-193, Request for Exemption from Specific Provisions in 10 CFR 50 Appendix H2023-02-14014 February 2023 Request for Exemption from Specific Provisions in 10 CFR 50 Appendix H L-22-286, Supplement to Request for an Amendment to Consolidate Fuel Decay Time Technical Specifications in a New Limiting Condition for Operation Titled Decay Time2023-02-14014 February 2023 Supplement to Request for an Amendment to Consolidate Fuel Decay Time Technical Specifications in a New Limiting Condition for Operation Titled Decay Time L-23-032, Discharge Monitoring Report (NPDES) Permit No. PA0025615 for Second Half of 20222023-01-23023 January 2023 Discharge Monitoring Report (NPDES) Permit No. PA0025615 for Second Half of 2022 L-22-281, Discharge Monitoring Report (NPDES) Permit No. PA00256152022-12-16016 December 2022 Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-22-246, Response to Request for Additional Information Regarding a Request to Consolidate Fuel Decay Time Technical Specifications to New LCO2022-12-0707 December 2022 Response to Request for Additional Information Regarding a Request to Consolidate Fuel Decay Time Technical Specifications to New LCO L-22-217, Submittal of Discharge Monitoring Report (NPDES) Permit No. PA00256152022-11-21021 November 2022 Submittal of Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-22-226, Emergency Preparedness Plan2022-11-0404 November 2022 Emergency Preparedness Plan L-22-222, Cycle 29-1 Core Operating Limits Report2022-10-31031 October 2022 Cycle 29-1 Core Operating Limits Report L-22-228, Independent Spent Fuel Storage Installation Changes, Tests, and Experiments2022-10-26026 October 2022 Independent Spent Fuel Storage Installation Changes, Tests, and Experiments L-22-200, Response to Request for Additional Information Regarding a 180-Day Steam Generator Tube Inspection Report Fall 2021 Refueling Outage2022-10-21021 October 2022 Response to Request for Additional Information Regarding a 180-Day Steam Generator Tube Inspection Report Fall 2021 Refueling Outage L-22-232, Withdrawal of a License Amendment Request Associated with Fire Protection Program Changes2022-10-21021 October 2022 Withdrawal of a License Amendment Request Associated with Fire Protection Program Changes L-22-238, Submittal of Discharge Monitoring Report (NPDES) Permit No. PA00256152022-10-20020 October 2022 Submittal of Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-22-227, Revised August 2022 Outfall 003 & 004 NPDES Discharge Monitoring Report (Dmr), Revised Daily Effluent Monitoring Report Forms for Outfalls 003 & 004 and Corrective Action Letter from Eurofins2022-10-0303 October 2022 Revised August 2022 Outfall 003 & 004 NPDES Discharge Monitoring Report (Dmr), Revised Daily Effluent Monitoring Report Forms for Outfalls 003 & 004 and Corrective Action Letter from Eurofins L-22-219, Submittal of Discharge Monitoring Report (NPDES) Permit No. PA00256152022-09-26026 September 2022 Submittal of Discharge Monitoring Report (NPDES) Permit No. PA0025615 L-22-204, Submittal of Evacuation Time Estimates2022-09-0707 September 2022 Submittal of Evacuation Time Estimates L-22-137, Request for Fire Protection Program Changes2022-09-0606 September 2022 Request for Fire Protection Program Changes L-21-238, License Amendment Request for Addition of Analytical Methodology to the Core Operating Limits Report for a Full Spectrum Loss of Coolant Accident2022-08-31031 August 2022 License Amendment Request for Addition of Analytical Methodology to the Core Operating Limits Report for a Full Spectrum Loss of Coolant Accident L-22-188, Response to Request for Additional Information Regarding Steam Generator Inspection Report- Fall 2021 Refueling Outage2022-08-22022 August 2022 Response to Request for Additional Information Regarding Steam Generator Inspection Report- Fall 2021 Refueling Outage L-22-191, Spent Fuel Storage Cask Registration2022-08-17017 August 2022 Spent Fuel Storage Cask Registration 2023-09-14
[Table view] Category:Response to Request for Additional Information (RAI)
MONTHYEARL-23-229, Request for Additional Information Regarding the Spring 2023 Generic Letter 95-05 Voltage-Based Alternate Repair Criteria and Steam Generator F-Star Reports2023-11-29029 November 2023 Request for Additional Information Regarding the Spring 2023 Generic Letter 95-05 Voltage-Based Alternate Repair Criteria and Steam Generator F-Star Reports L-23-139, Response to Request for Additional Information Regarding Fall 2022 180-Day Steam Generator Tube Inspection Report2023-06-13013 June 2023 Response to Request for Additional Information Regarding Fall 2022 180-Day Steam Generator Tube Inspection Report L-23-129, Response to Request for Additional Information for 10 CFR 50.55a Request 2-TYP-4-RV-06 for Alternative Repair Methods for Reactor Pressure Vessel Head Penetrations2023-05-0505 May 2023 Response to Request for Additional Information for 10 CFR 50.55a Request 2-TYP-4-RV-06 for Alternative Repair Methods for Reactor Pressure Vessel Head Penetrations L-23-086, Response to Request for Additional Information for Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair2023-03-0404 March 2023 Response to Request for Additional Information for Emergency License Amendment Request for Technical Specification 3.5.2 Regarding One-Time Action for Valve Leak Repair L-22-246, Response to Request for Additional Information Regarding a Request to Consolidate Fuel Decay Time Technical Specifications to New LCO2022-12-0707 December 2022 Response to Request for Additional Information Regarding a Request to Consolidate Fuel Decay Time Technical Specifications to New LCO L-22-200, Response to Request for Additional Information Regarding a 180-Day Steam Generator Tube Inspection Report Fall 2021 Refueling Outage2022-10-21021 October 2022 Response to Request for Additional Information Regarding a 180-Day Steam Generator Tube Inspection Report Fall 2021 Refueling Outage L-22-188, Response to Request for Additional Information Regarding Steam Generator Inspection Report- Fall 2021 Refueling Outage2022-08-22022 August 2022 Response to Request for Additional Information Regarding Steam Generator Inspection Report- Fall 2021 Refueling Outage ML22094A1152022-04-0404 April 2022 Response to a Request for Additional Information Regarding a Revision to Technical Specification 3.3.5, Loss of Power (LOP) Diesel Generator (DG) Start and Bus Separation Instrumentation (EPID No. L-202 L-22-079, Response to NRC Regulatory Issue Summary 2022-01, Preparation and Scheduling of Operator Licensing Examinations2022-03-16016 March 2022 Response to NRC Regulatory Issue Summary 2022-01, Preparation and Scheduling of Operator Licensing Examinations ML21147A1462021-05-27027 May 2021 Response to Request for Additional Information Regarding Generic Letter 2004-02 ML21132A2422021-05-12012 May 2021 Response to Request for Additional Information Regarding Steam Generator Tube Sleeve License Amendment Request L-21-106, Response to Request for Additional Information Regarding Amendment Request to Update Analytical Methods Used to Develop Reactor Coolant System Pressure and Temperature Limits2021-04-22022 April 2021 Response to Request for Additional Information Regarding Amendment Request to Update Analytical Methods Used to Develop Reactor Coolant System Pressure and Temperature Limits ML21055A8862021-02-24024 February 2021 Response to Request for Additional Information Regarding Steam Generator Inspection 180-Day Report ML21048A0822021-02-16016 February 2021 Response to Request for Additional Information Regarding Steam Generator Tube Sleeve License Amendment Request L-21-030, Response to Request for Additional Information Regarding an Amendment to Incorporate the Applicable Standard Technical Specification 5.2.2, Unit Staff, Into the Facility Technical Specifications (EPID L-20202021-01-27027 January 2021 Response to Request for Additional Information Regarding an Amendment to Incorporate the Applicable Standard Technical Specification 5.2.2, Unit Staff, Into the Facility Technical Specifications (EPID L-2020 L-20-277, Response to Request for Additional Information Regarding Steam Generator Tube Sleeve License Amendment Request2021-01-22022 January 2021 Response to Request for Additional Information Regarding Steam Generator Tube Sleeve License Amendment Request L-20-293, Response Correction to a Request for Additional Information Regarding License Amendment Request to Modify Technical Specifications 3.4.162020-11-30030 November 2020 Response Correction to a Request for Additional Information Regarding License Amendment Request to Modify Technical Specifications 3.4.16 L-20-162, Supplemental Response to NRC Generic Letter 2004-022020-11-30030 November 2020 Supplemental Response to NRC Generic Letter 2004-02 L-20-276, Response to Request for Additional Information Regarding Steam Generator Inspection Report2020-10-30030 October 2020 Response to Request for Additional Information Regarding Steam Generator Inspection Report L-20-161, Response to Request for Additional Information Regarding License Amendment Request to Modify Technical Specifications 3.4.16, RCS Specific Activity, 3.7.13 Secondary Specific Activity, 5.5.7, Ventilation Filter .2020-06-0909 June 2020 Response to Request for Additional Information Regarding License Amendment Request to Modify Technical Specifications 3.4.16, RCS Specific Activity, 3.7.13 Secondary Specific Activity, 5.5.7, Ventilation Filter . L-20-155, Response to Request for Additional Information Regarding Request for Exemptions to Certain Periodic Training Requirements for Security Personnel (Epids L-2020-LLE-0026 to -0040)2020-05-0606 May 2020 Response to Request for Additional Information Regarding Request for Exemptions to Certain Periodic Training Requirements for Security Personnel (Epids L-2020-LLE-0026 to -0040) L-20-097, Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Modify Technical Specifications 3.4.16, RCS Specific Activity, 3.7.13 Secondary Specific Activity,.2020-04-14014 April 2020 Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Modify Technical Specifications 3.4.16, RCS Specific Activity, 3.7.13 Secondary Specific Activity,. L-20-125, Response to Request for Additional Information Regarding 10 CFR 50.55a Request Number SRR-1, Rev. 0, Snubber Testing2020-04-0303 April 2020 Response to Request for Additional Information Regarding 10 CFR 50.55a Request Number SRR-1, Rev. 0, Snubber Testing L-19-182, Response to RAI Regarding an Application for Order Consenting to Transfer of License2019-08-0202 August 2019 Response to RAI Regarding an Application for Order Consenting to Transfer of License L-18-209, Response to Request for Additional Information Regarding Steam Generator Technical Specification License Amendment Request2018-10-28028 October 2018 Response to Request for Additional Information Regarding Steam Generator Technical Specification License Amendment Request L-18-121, Response to Request for Supplemental Information Regarding Generic Letter 2016-01 Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools.2018-05-25025 May 2018 Response to Request for Supplemental Information Regarding Generic Letter 2016-01 Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools. L-18-125, Response to Follow-up Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement IEPID-L-2017-l-LE-0019 (CAC Nos.000976/05000334/-L-2017-LLE-0019 MG0010, 000976/05000334/L-2017-LLE-0019 MG0011,000976/02018-05-0202 May 2018 Response to Follow-up Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement IEPID-L-2017-l-LE-0019 (CAC Nos.000976/05000334/-L-2017-LLE-0019 MG0010, 000976/05000334/L-2017-LLE-0019 MG0011,000976/0 ML18099A1232018-04-0606 April 2018 Response to Request for Additional Information Regarding Request to Modify Rtpts Values L-18-061, Units. 1 & 2, Davis-Besse, and Perry, Response to Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement2018-03-16016 March 2018 Units. 1 & 2, Davis-Besse, and Perry, Response to Request for Additional Information Regarding Exemption Request for a Physical Barrier Requirement L-17-375, Response to Request for Additional Information Regarding Request 1-TYP-4-BA-01 to Extend the Inservice Inspection Interval for Certain Reactor Vessel Welds2018-01-0505 January 2018 Response to Request for Additional Information Regarding Request 1-TYP-4-BA-01 to Extend the Inservice Inspection Interval for Certain Reactor Vessel Welds L-17-372, Response to Request for Additional Information Regarding Request to Use ASME Code Case N-513-4 (EPID 000976/05000334/L-2017-LLR-0088,000976/05000346/L-2017-LLR-0088, 000976/05000412/L-2017-LLR-0088, and 000976/05000440/L-2017-LLR-0088)2017-12-23023 December 2017 Response to Request for Additional Information Regarding Request to Use ASME Code Case N-513-4 (EPID 000976/05000334/L-2017-LLR-0088,000976/05000346/L-2017-LLR-0088, 000976/05000412/L-2017-LLR-0088, and 000976/05000440/L-2017-LLR-0088) L-17-296, Response to Request for Additional Information Re Request to Revise the Emergency Plan2017-09-20020 September 2017 Response to Request for Additional Information Re Request to Revise the Emergency Plan L-17-197, Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052017-06-23023 June 2017 Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 L-17-104, Response to Request for Additional Information Regarding a Request to Revise the Emergency Plan2017-05-20020 May 2017 Response to Request for Additional Information Regarding a Request to Revise the Emergency Plan ML17213A0172017-05-11011 May 2017 Enclosure B: Beaver Valley, Unit 2, Seismic Probabilistic Risk Assessment in Response to 50.54(0 Letter with Regard to NTTF 2.1 ML17213A0162017-05-11011 May 2017 Enclosure a: Beaver Valley, Units 1, Seismic Probabilistic Risk Assessment in Response to 50.54(f) Letter with Regard to NTTF 2.1 L-17-053, Response to Request for Additional Information Regarding 10 CFR 50.55a Request Numbers PR6 and PR72017-02-22022 February 2017 Response to Request for Additional Information Regarding 10 CFR 50.55a Request Numbers PR6 and PR7 L-17-024, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052017-01-30030 January 2017 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 L-16-299, Response to Generic Letter 2016-01. Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools2016-10-31031 October 2016 Response to Generic Letter 2016-01. Monitoring of Neutron-Absorbing Materials in Spent Fuel Pools L-16-212, Response to Request for Additional Information Regarding 2015 Steam Generator Inspection Reports2016-07-14014 July 2016 Response to Request for Additional Information Regarding 2015 Steam Generator Inspection Reports L-16-162, Response to Requests for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805, and Request to Change Implementation Schedule2016-05-12012 May 2016 Response to Requests for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805, and Request to Change Implementation Schedule L-16-085, Request for Additional Information Response Related to Modification of Technical Specification 5.3.1, Unit Staff Qualifications.2016-03-22022 March 2016 Request for Additional Information Response Related to Modification of Technical Specification 5.3.1, Unit Staff Qualifications. ML16063A2882016-03-0202 March 2016 Response to NRC Request for Additional Information, Per 10 CFR 50.54(f) Regarding the Flooding Aspects of Recommendation 2.1 of the Near-Term Task Force (NTTF) Review of Insights from the Fukushima Dai-ichi Accident L-16-058, Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052016-02-24024 February 2016 Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 L-15-371, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-12-21021 December 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 L-15-303, Response to Request for Additional Information Regarding Submittal of Reactor Vessel Internals Aging Management Program2015-11-0606 November 2015 Response to Request for Additional Information Regarding Submittal of Reactor Vessel Internals Aging Management Program L-15-325, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-11-0606 November 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 L-15-261, Response to Request for Additional Information Regarding Submittal of Reactor Vessel Internals Aging Management Program2015-08-26026 August 2015 Response to Request for Additional Information Regarding Submittal of Reactor Vessel Internals Aging Management Program L-15-202, Response to Request for Additional Information on Expedited Seismic Evaluation Process (ESEP) Reports and Seismic Hazard and Screening Reports Submitted, Per 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term..2015-06-29029 June 2015 Response to Request for Additional Information on Expedited Seismic Evaluation Process (ESEP) Reports and Seismic Hazard and Screening Reports Submitted, Per 10 CFR 50.54(f) Regarding Recommendation 2.1 of the Near-Term.. L-15-188, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-06-26026 June 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 2023-06-13
[Table view] |
Text
FENOC' Beaver Valley Power Station P.O. Box 4 RrstEnergy Nuclear Operating Company Shippingport, PA 15077 Marty L. Richey 724-682-5234 Site Vice President Fax: 724-643-8069 January 30, 2017 L-17-024 ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001
SUBJECT:
Beaver Valley Power Station, Unit Nos. 1 and 2 Docket No. 50-334, License No. DPR-66 Docket No. 50-412, License No. NPF-73 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 (CAC Nos. MF3301 and MF3302)
By letter dated December 23, 2013 (Accession No. ML14002A086), as supplemented by letters dated February 14, 2014; April 27, 2015; May 27, 2015; June 26, 2015; November 6, 2015; December 21, 2015; February 24, 2016; and May 12, 2016 (Accession Nos. ML14051A499, ML15118A484, ML15147A372, ML15177A110, ML15313A306, ML15356A136, ML16055A160, and ML16133A340 respectively),
FirstEnergy Nuclear Operating Company (FENOC) submitted a license amendment request to change the Beaver Valley Power Station, Unit Nos. 1 and 2, fire protection program to one based on the National Fire Protection Association (NFPA) Standard 805, "Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants," 2001 Edition.
By letter dated December 2, 2016 (Accession No. ML16333A016), the Nuclear Regulatory Commission (NRC) requested additional information to complete its review.
The FENOC response to the request for information is attached.
Remaining information that the NRC needs to complete its review is planned to be submitted by June 28, 2017. This includes the responses to probabilistic risk assessment requests 3 and 19 in the NRC letter dated March 4, 2015 (Accession No. ML15049A507), as well as updates to the license amendment request attachments K, M, and S.
Beaver Valley Power Station, Unit Nos. 1 and 2 L-17-024 Page 2 There are no regulatory commitments included in this submittal. If there are any questions or if additional information is required , please contact Mr. Thomas A. Lentz, Manager - Fleet Licensing, at (330) 315-6810.
I declare under penalty of perjury that the foregoing is true and correct. Executed on January 3v , 2017.
Sincerely,
-~1t> - ~
Marty L. Rich~y
\
Attachment:
Response to December 2, 2016 Request for Additional Information cc: NRC Region I Administrator NRC Resident Inspector NRC Project Manager Director BRP/DEP Site BRP/DEP Representative
Attachment L-17-024 Response to December 2, 2016 Request for Additional Information Page 1 of 3 The NRC staff's request for additional information (RAI) is provided in bold text followed by the FENOC response.
Probabilistic Risk Assessment (PRA) Request for Additional Information 27, "Very Early Warning Fire Detection System (VEWFDS) Credit" Section 2.4.3.3 of NFPA 805 states that the probabilistic safety analysis (also referred to as PRA} approach, methods, and data shall be acceptable to the authority having jurisdiction, which is the NRC. Section 2.4.4.1 of NFPA 805 further states that the change in public health risk arising from transition from the current fire protection program to an NFPA 805-based program, and all future plant changes to the program, shall be acceptable to the NRC.
Regulatory Guide (RG) 1.174, Revision 2, "An Approach for Using Probabilistic Risk Assessment in Risk-Informed Decisions on Plant-Specific Changes to the Licensing Basis" (ADAMS Accession No. ML100910006), provides quantitative guidelines on core damage frequency (CDF), large early release frequency (LERF}, and identifies acceptable changes to these frequencies that result from proposed changes to the plant's licensing basis and describes a general framework to determine the acceptability of risk-informed changes. The NRC statrs review of the information in the license amendment request identified additional information that is needed to fully characterize the risk estimates.
New guidance on the credit taken for VEWFDS is available in NUREG-2180, "Determining the Effectiveness, Limitations, and Operator Response for Very Early Warning Fire Detection Systems in Nuclear Facilities, (DELORES-VEWFIRE)," of which the final (pre-publication} version is available at ADAMS Accession Nos.
ML 16286AOOO and ML16286A002. The methodology in NUREG-2180 is acceptable to the NRC because it is currently the best available guidance. By letter dated July 1, 2016 (ADAMS Accession No. ML16167A444), the guidance provided in Frequently Asked Question 08-0046, "Closure of National Fire Protection Association 805 Frequently Asked Question 08-0046, 'Incipient Fire Detection Systems'," dated November 23, 2009 (ADAMS Accession No. ML093220426}, has been retired, and alternative approaches for staff evaluation are necessary.
Explain how credit (e.g., approach, methods, data, and assumptions) taken in the fire PRA (FPRA) for the proposed VEWFDS is consistent with the guidance in NUREG-2180 or bounds the risk results (i.e., CDF, LERF, change in CDF, and change in LERF) that would be obtained, had the guidance in NUREG-2180 been applied. If
Attachment L-17-024 Page 2 of 3 credit taken for VEWFDS in the FPRA is not consistent with or bounded by NUREG-2180, provide:
- a. The risk results (i.e., CDF, LERF, change in CDF, and change in LERF): (1) without credit for VEWFDS that would be obtained had the guidance in NUREG-2180 been applied or (2) that would be obtained had an alternative method been used, along with a description and justification for the alternative method. Development and use of an alternative proposal may extend the time required to complete the review. The new risk results can be generated from a sensitivity study type evaluation insofar as formal incorporation of the new method into the PRA model of record is not required.
- b. Explain how the total risk and increase in risk are consistent with the guidelines in RG 1.174.
Response
Credit in the fire PRA for the VEWFDS at Beaver Valley Power Station Unit No. 1 (BVPS-1) and Beaver Valley Power Station Unit No. 2 (BVPS-2) has been re-evaluated and is consistent with the new guidance in NUREG-2180. The fire event trees have been updated in accordance with Section 6.4 of NUREG-2180 with the appropriate parameter inputs used from Appendix F.
The VEWFDS was fully operational as of February 2016 for BVPS-1 and August 2016 for BVPS-2. The VEWFDS design requirements, system installation, acceptance testing, inspection and maintenance, training, and alarm response procedure were presented in the response to fire protection engineering (FPE) RAI 15 (Accession Nos. ML15118A484 and ML15147A372). Fire PRA credit taken for the VEWFDS in accordance with the previously-approved frequently asked question 08-0046 was explained in the response to PRA RAI 12 (Accession No. ML15177A110). The VEWFDS is credited for reducing the probability of fires that may propagate from cabinets in which the systems are installed, and not for reducing damage within the source cabinets, or for area-wide detection.
Particularly, the VEWFDS high-sensitivity cloud chamber detection system is currently installed in select low-voltage cabinets (cabinets containing equipment with an operating voltage less than 250 volts) in the process rack rooms in BVPS-1 and BVPS-2 (fire compartments 1-CR-4 and 2-CB-1, respectively), as well as the west communications room in BVPS-2 (fire compartment 2-CB-6). As part of the change in VEWFDS fire PRA credit from FAQ 08-0046 to NUREG-2180, only one item in the license amendment request Attachment S, Table S-2 will be changed. Item BV1-2854 will not relocate the computer inverter to fire compartment 1-MG-1 . The existing inverter in 1-CR-4 will be replaced with a new inverter, and the VEWFDS will be connected to it in the future. The inverter will contain nominal 480 volt components. Therefore, it is designated a power cabinet, and fire PRA credit will be taken in accordance with NUREG-2180. An updated description for item BV1-2854 in Table S-2 will be provided in a future submittal.
Attachment L-17-024 Page 3 of 3 VEWFDS alarms are displayed in the main control rooms on the annunciator systems, and the first instruction step of the response procedures requires an operator with fire watch qualifications to respond to the affected fire compartment. A continuous fire watch remains until the alarm is cleared.
The calculated probability of non-suppression for damage outside of cabinets the VEWFDS monitors in the fire PRA has been re-evaluated and is consistent with the methods, data, and assumptions in NUREG-2180. The updated results will be included with the response to PRA RAI 03 and 19.