MONTHYEARL-15-150, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-05-27027 May 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI ML15280A0742015-10-0909 October 2015 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI L-15-325, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-11-0606 November 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI ML15320A4132015-11-24024 November 2015 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI L-15-371, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052015-12-21021 December 2015 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI L-16-058, Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052016-02-24024 February 2016 Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Supplement ML16099A0112016-03-0303 March 2016 NRR E-mail Capture - Draft 3rd Round PRA RAIs - Beaver Valley Units 1 & 2 - NFPA-805 LAR (CAC Nos. MF3301 & MF3302) Project stage: Draft RAI ML16084A8442016-03-30030 March 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI ML16089A0622016-03-30030 March 2016 Meeting to Discuss BVPS Draft PRA RAI - Slides Project stage: Request ML16071A1222016-04-0707 April 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI ML16105A0082016-04-25025 April 2016 March 30, 2016, Summary of Meeting with Firstenergy Nuclear Operating Company on Its Draft Probabilistic Risk Assessment RAI Related to Its License Amendment Request to Adopt NFPA Standard 805 Project stage: Draft RAI L-16-162, Response to Requests for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805, and Request to Change Implementation Schedule2016-05-12012 May 2016 Response to Requests for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805, and Request to Change Implementation Schedule Project stage: Response to RAI ML16158A0022016-06-0101 June 2016 NRR E-mail Capture - Beaver Valley, Units 1 & 2 - Update on NFPA 805 (CAC Nos. MF3301 & MF3302) Project stage: Other L-16-186, Bearer Valley, Units 1 and 2, Davis-Besse, Unit 1, and Perry, Unit 1 - Supplement to Submittal of Information Pertaining to Foreign Ownership, Control, or Influence2016-07-0101 July 2016 Bearer Valley, Units 1 and 2, Davis-Besse, Unit 1, and Perry, Unit 1 - Supplement to Submittal of Information Pertaining to Foreign Ownership, Control, or Influence Project stage: Request ML16333A0162016-12-0202 December 2016 Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: RAI L-17-024, Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052017-01-30030 January 2017 Response to Request for Additional Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Response to RAI L-17-029, Technical Specification Bases Update Status, Rev. 322017-04-21021 April 2017 Technical Specification Bases Update Status, Rev. 32 Project stage: Request L-17-197, Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 8052017-06-23023 June 2017 Response to Request for Additional Information and Supplemental Information Regarding License Amendment Request to Adopt National Fire Protection Association Standard 805 Project stage: Supplement ML17220A2342017-08-0808 August 2017 E-mail Regarding Request for Additional Information for NFPA 805 License Amendment Request Project stage: RAI ML17313A6422017-11-0909 November 2017 Transmittal of Draft Safety Evaluation for Proposed Amendments Transition to NFPA 805 (CAC Nos. MF3301 and MF3302; EPID L-2013-LLF-0001) Project stage: Draft Approval ML17335A0962017-11-27027 November 2017 NRR E-mail Capture - Beaver Valley: NFPA 805 LAR: License Condition: Fire Protection Program Changes That Have More than Minimal Risk Impact (CAC Nos. MF3301 and MF3302; EPID L-2013-LLF-0001) Project stage: Approval ML18058A9422017-12-11011 December 2017 NFPA 805 Amendment Application Transition License Condition Project stage: Other ML17291A0812018-01-22022 January 2018 Issuance of Amendments Transition to NFPA 805, Performance-Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants (CAC Nos. MF3301 and MF3302; EPID L-2013-LLF-0001) Project stage: Approval L-19-113, Rev. 9 to ODCM: Radiological Environmental Monitoring Program2018-01-22022 January 2018 Rev. 9 to ODCM: Radiological Environmental Monitoring Program Project stage: Request ML18058B0722018-02-23023 February 2018 BVPS NFPA 805 License Amendment Change Requested, and Other SE Comments Project stage: Other ML18059A7982018-02-26026 February 2018 BVPS NFPA 805 License Amendment Change Requested, and Other SE Comments Project stage: Other ML18058A9852018-02-27027 February 2018 BVPS-1 License Condition Page Project stage: Other ML18058A9532018-02-27027 February 2018 Comments on BVPS SE Project stage: Other ML18065A4032018-04-0505 April 2018 Correction of Errors in Safety Evaluation Associated with License Amendment Nos. 301 and 190 Project stage: Approval ML18099A2322018-04-18018 April 2018 Correction of an Error in the Renewed Facility Operating License No. DPR-66 Associated with License Amendment No. 301 CAC No. MF3301; EPID L-2013-LLF-0001) Project stage: Other 2016-07-01
[Table View] |
Text
1 NRR-PMDAPEm Resource From:
Lamb, Taylor Sent:
Wednesday, June 01, 2016 3:50 PM To:
Lentz, Thomas A. (Licensing) (talentz@firstenergycorp.com)
Cc:
Lashley, Phil H. (phlashley@firstenergycorp.com)
Subject:
Beaver Valley, Units 1 & 2 - Update on NFPA 805 (CAC Nos. MF3301 & MF3302)
Mr. Lentz, It has been identified that there are currently no further requests for additional information (RAIs) regarding the 12/23/2013 license amendment request that would adopt the National Fire Protection Association Standard 805, Performance Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants.
FENOC can proceed with the integrated analysis as addressed in Probabilistic Risk Assessment RAI Nos. 3 and 19. The NRC staff will expect a response within 120 days from the date of this email (6/1/2016).
Thank you, Taylor A Lamb Project Manager U.S. Nuclear Regulatory Commission NRR/DORL/LPLI-2 MS: OWFN-8B1A Phone: 301-415-7128
Hearing Identifier:
NRR_PMDA Email Number:
2884 Mail Envelope Properties (Taylor.Lamb@nrc.gov20160601154900)
Subject:
Beaver Valley, Units 1 & 2 - Update on NFPA 805 (CAC Nos. MF3301 &
MF3302)
Sent Date:
6/1/2016 3:49:46 PM Received Date:
6/1/2016 3:49:00 PM From:
Lamb, Taylor Created By:
Taylor.Lamb@nrc.gov Recipients:
"Lashley, Phil H. (phlashley@firstenergycorp.com)" <phlashley@firstenergycorp.com>
Tracking Status: None "Lentz, Thomas A. (Licensing) (talentz@firstenergycorp.com)" <talentz@firstenergycorp.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 693 6/1/2016 3:49:00 PM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received:
1 NRR-PMDAPEm Resource From:
Lamb, Taylor Sent:
Wednesday, June 01, 2016 3:50 PM To:
Lentz, Thomas A. (Licensing) (talentz@firstenergycorp.com)
Cc:
Lashley, Phil H. (phlashley@firstenergycorp.com)
Subject:
Beaver Valley, Units 1 & 2 - Update on NFPA 805 (CAC Nos. MF3301 & MF3302)
Mr. Lentz, It has been identified that there are currently no further requests for additional information (RAIs) regarding the 12/23/2013 license amendment request that would adopt the National Fire Protection Association Standard 805, Performance Based Standard for Fire Protection for Light Water Reactor Electric Generating Plants.
FENOC can proceed with the integrated analysis as addressed in Probabilistic Risk Assessment RAI Nos. 3 and 19. The NRC staff will expect a response within 120 days from the date of this email (6/1/2016).
Thank you, Taylor A Lamb Project Manager U.S. Nuclear Regulatory Commission NRR/DORL/LPLI-2 MS: OWFN-8B1A Phone: 301-415-7128
Hearing Identifier:
NRR_PMDA Email Number:
2884 Mail Envelope Properties (Taylor.Lamb@nrc.gov20160601154900)
Subject:
Beaver Valley, Units 1 & 2 - Update on NFPA 805 (CAC Nos. MF3301 &
MF3302)
Sent Date:
6/1/2016 3:49:46 PM Received Date:
6/1/2016 3:49:00 PM From:
Lamb, Taylor Created By:
Taylor.Lamb@nrc.gov Recipients:
"Lashley, Phil H. (phlashley@firstenergycorp.com)" <phlashley@firstenergycorp.com>
Tracking Status: None "Lentz, Thomas A. (Licensing) (talentz@firstenergycorp.com)" <talentz@firstenergycorp.com>
Tracking Status: None Post Office:
Files Size Date & Time MESSAGE 693 6/1/2016 3:49:00 PM Options Priority:
Standard Return Notification:
No Reply Requested:
No Sensitivity:
Normal Expiration Date:
Recipients Received: