Information Notice 1990-40, Results of NRC-Sponsored Testing of Motor-Operated Valves

From kanterella
(Redirected from Information Notice 1990-40)
Jump to navigation Jump to search
Results of NRC-Sponsored Testing of Motor-Operated Valves
ML031140045
Person / Time
Site: Beaver Valley, Millstone, Hatch, Monticello, Calvert Cliffs, Dresden, Davis Besse, Peach Bottom, Browns Ferry, Salem, Oconee, Mcguire, Nine Mile Point, Palisades, Palo Verde, Perry, Indian Point, Fermi, Kewaunee, Catawba, Harris, Wolf Creek, Saint Lucie, Point Beach, Oyster Creek, Watts Bar, Hope Creek, Grand Gulf, Cooper, Sequoyah, Byron, Pilgrim, Arkansas Nuclear, Braidwood, Susquehanna, Summer, Prairie Island, Columbia, Seabrook, Brunswick, Surry, Limerick, North Anna, Turkey Point, River Bend, Vermont Yankee, Crystal River, Haddam Neck, Ginna, Diablo Canyon, Callaway, Vogtle, Waterford, Duane Arnold, Farley, Robinson, Clinton, South Texas, San Onofre, Cook, Comanche Peak, Yankee Rowe, Maine Yankee, Quad Cities, Humboldt Bay, La Crosse, Big Rock Point, Rancho Seco, Zion, Midland, Bellefonte, Fort Calhoun, FitzPatrick, McGuire, LaSalle, Fort Saint Vrain, Shoreham, Satsop, Trojan, Atlantic Nuclear Power Plant, Crane  Entergy icon.png
Issue date: 06/05/1990
From: Rossi C
Office of Nuclear Reactor Regulation
To:
References
IN-90-040, NUDOCS 9005290270
Download: ML031140045 (9)


It9

UNITED STATES

NUCLEAR REGULATORY COMMISSION

OFFICE OF NUCLEAR REACTOR REGULATION

WASHINGTON, D.C.

20555

June 5, 1990

NRC INFORMATION NOTICE NO. 90-40:

RESULTS OF NRC-SPONSORED TESTING

OF MOTOR-OPERATED VALVES

Addressees

All holders of operating licenses or construction permits for nuclear power

reactors.

Purpose

This information notice is intended to provide addressees with specific infor- mation regarding the results of recent NRC-sponsored testing of motor-operated

valves (MOVs) which was discussed at a public meeting on April 18, 1990. It is

expected that recipients will review the information for applicability to their

facilities and consider actions, as appropriate, to avoid problems with

safety-related MOVs.

However,.suggestions contained in this information notice

do not constitute NRC requirements; therefore, no specific action or written

response is required.

Background

The NRC Office of Nuclear Regulatory Research (RES) has been sponsoring an MOV

testing program in support of the resolution of Generic Safety Issue 87 (GI-87),-"Failure of HPCI Steam Line Without Isolation." The initial scope of

GI-87 involved the evaluation of the capability of certain motor-operated

flexible wedge gate containment isolation valves to mitigate the loss of

reactor coolant inventory in the event of a pipe break outside of the contain- ment building at boiling-water-reactor (BWR) plants. The particular MOVs

involved in the GI-87 program were those in the turbine steam supply lines for

the high pressure coolant injection (HPCI)

and reactor core isolation cooling

(RCIC) systems, and in the supply line to the reactor water cleanup (RWCU)

system.

The MOV research is applicable to the programs established by licensees in

response to Generic Letter 89-10, "Safety-Related Motor-Operated Valve Testing

and Surveillance." In that generic letter, the staff recommended that

licensees and construction permit holders establish a program to provide for

the testing, inspection, and maintenance of safety-related MOVs and certain

other MOVs in safety-related systems.

The purpose of this program is to

provide assurance that the MOVs will function when subjected to design-basis

differential pressure and flow conditions.

As part of the generic letter

program, the staff recommended that licensees and permit holders test the MOVs

  • /

9005290270 Z 9 E

'I

'

IN 90-40

June 5, 1990 within the program in situ under design-basis conditions, where practicable.

The schedule in the generic letter requested that the description of the MNOV

program be available within about a year of issuance of the generic letter and

that the initial test program be completed in approximately five years.

As a

followup to the initial program, the staff recommended that the MOV switch

settings and, thus, operability of the MOVs be reverified periodically.

Although the generic letter has a five-year schedule for completing the initial

program, the staff indicated at the public workshops held to discuss the

generic letter that the NRC regulations require that licensees act to resolve

operability problems with specific MOVs when the problems are identified.

As

part of its review of the research results, the staff will consider the need to

accelerate a portion or all of the Generic Letter 89-10 program for particular

MOVs or systems.

In Generic Letter 89-10, the staff acknowledges that in situ testing of some

MOVs within the generic letter program under design-basis conditions will not

be practicable.

At the generic letter workshops, the staff discussed several

possible alternatives if such testing is not practicable, as well as potential

problems and limitations associated with those alternatives.

For instances in

which testing of an MOV in situ under design-basis conditions is not practica- ble and the licensee cannot currently justify the use of an alternative to

design-basis testing in situ, the staff has recommended the use of a "two- stage" approach:

the licensee would set the MOV operating switches by means of

the best data available and then would work to obtain applicable test data as

soon as possible.

The staff believes that applicable test data can be obtained

within the five-year schedule.

For the initial setting of the MOV switches

under the two-stage approach, the test results obtained through the.NRC

research may constitute some of the best data available for the tested valves

under a variety of fluid conditions.

Description of Circumstances

The MOV testing program for GI-87 has been conducted in two phases by the Idaho

National Engineering Laboratory (INEL).

Phase I was performed in 1988 at the

Wyle Laboratory facility in Huntsville, Alabama.

The most significant tests in

that phase consisted of opening and closing two 6-inch flexible wedge gate

valves (manufactured by Anchor/Darling and Velan) under high differential

pressure and high-temperature water conditions. The valves in Phase I of the

research program were considered typical of those used for containment isola- tion in the supply line to the RWCU system.

The results of the tested valves

were discussed at a public meeting on February 1, 1989, and are documented in

NUREG/CR-5406, "BWR Reactor Water Cleanup System Flexible Wedge Gate Isolation

Valve Qualification and High Energy Flow Interruption Test."

Phase II of the MOV test program was performed in 1989 at the Kraftwerk Union

facility in the Federal Republic of Germany.

This phase consisted of opening

and closing three 6-inch flexible wedge gate valves (Anchor/Darling, Velan, and

Walworth) and three 10-inch flexible wedge gate valves (Anchor/Darling, Powell, and Velan) against normal and blowdown (design-basis) flow conditions.

The

Phase II 6-inch and 10-inch valves were considered typical of those used for

containment isolation in the supply line to the RWCU system and the turbine

IN 90-40

June 5, 1990 steam supply line of theAPCI systems, respectively. *'On

December 26, 1989, the

NRC staff issued Information Notice 89-88, "Recent NRC-Sponsored Testing of

Motor-Operated Valves," which alerted addressees to the tests and provided some

preliminary results.

On April 18, 1990, the NRC staff held a public meeting to

discuss-the results of Phase II of the MOV testing program.

The test data are

available in printed form in the NRC Public Document Room (Accession No.

9005170154).

Magnetic tapes of the test data are available through the INEL

Office of Technology Transfer.

The overall objectives of the MOV test program included the determination of

the force required to close the tested valves under various operating and

design-basis fluid conditions through the measurement of stem thrust.

Other

program objectives were the determination of opening thrust requirements for

the tested valves under different fluid conditions; evaluation of valve closure

force components (such as disc friction and packing drag); measurement of the

effects of temperature, pressure, and valve design on valve opening and closing

loads; and evaluation of the valve thrust equation commonly used in the

industry.-

The tests for each MOV included cold leakage, cold and hot cycling, opening and

closing under normal flow, closure under design-basis, and partial opening and

closing under high differential pressure and flow conditions.

Although the

tested valves were intended to be typical of those used for containment isola- tion in the HPCI and RWCU systems of BWR plants, the results of the tests

should be considered in terms of their applicability to all MOVs in nuclear

power plants. A detailed analysis of the test data should be available in July

1990.

Nevertheless, the NRC staff has begun to develop conclusions from the

test data as a result of its review of the data and the discussions at the

April 18, 1990, public meeting.

Several preliminary conclusions are discussed

below:

1.

Regardless of fluid conditions (i.e., steam, slightly subcooled water, or

cold water), the tested valves required more thrust for opening and

closing under various differential pressure and flow conditions than would

have been predicted from standard industry calculations and typical

friction factors.

Thus, a potential exists for the underestimation of

thrust requirements for valves in applications, and under fluid condi- tions, other than those of the valves involved in the NRC research.

For

the conduct of the tests, the motor operators for the valves were sized, and the torque switches were set,Ain an effort to ensure that each valve

would fully stroke without regard to the thrust requirements predicted by

the commonly used valve thrust equation.

(Despite this effort, one valve

failed to close completely during a'blowdown test.) To provide an indica- tion of the accuracy of the valve thrust equation, the thrust predicted by

that equation for valve friction factors of both 0.3 and 0.5 was calculat- ed during each test.

Table 1 provides a summary of the blowdown tests and

the minimum required thrust to close the tested valves.

The table also

indicates whether the valve thrust equation would have bounded the thrust

requirement if valve friction factors of 0.3 or 0.5 had been used.

IN 90-40

June 5, 1990 2.

Some of the tested valves sustained considerable internal damage during

the blowdown tests.

The occurrence of internal damage can cause the

thrust required to operate a valve to exceed the thrust requirements

predicted by the valve thrust equation.

Such valves were referred to as

"unpredictable" in the test program and included the 6-inch Anchor/Darling

valve and the 10-inch Anchor/Darling, Powell, and Velan valves.

In some

instances, this increase in required thrust can be considerable and might

exceed the capability of the motor or operator.

Thrust requirements to

close unpredictable valves under design-basis loads cannot be accurately

determined without testing the valves (either individually or as proto- types) under those conditions.

3. The research program revealed that the testing of a valve under static or

low flow conditions cannot always be used to accurately predict the

behavior of the valve under design-basis conditions by extrapolation.

For

example, the valves that were damaged during blowdown tests operated

normally under less severe flow tests.

Thus, low-flow tests might not

identify a valve that requires significantly more thrust than predicted by

the valve thrust equation (i.e., a valve that is unpredictable).

4.

During opening of the valves, the maximum required thrust did not always

occur at unseating.

Rather, in certain instances, it occurred much later

during the valve stroke.

At nuclear plants, the staff has found that

torque switches for MOVs are sometimes bypassed only during the initial

portion of the opening stroke on the assumption that the thrust required

to unseat the valve would be the maximum thrust for the full stroke.

Thus, the research results raise a concern that the torque switches in

some MOVs at nuclear plants might not be bypassed for a sufficient period

of time during the opening stroke.

5.

For certain tests, the valve was closed from a partially open position.

This partial stroking of the valve failed to predict the thrust require- ments and to identify nonpredictable performance that were found during

closure of the valve from a full open position.

For example, during

certain blowdown tests, valve damage began to occur before the valve was

half closed.

The accumulated damage over the full stroke influences the

thrust required to close the valve.

6. The research program revealed that measurements of torque, thrust, and

motor operating data were needed to completely characterize MOV perfor- mance.

For example, the measurement of torque or thrust alone cannot

identify problems in the conversion of torque to thrust (i.e., abnormally

large stem factors).

Such problems can cause the thrust measured at

normal or static conditions to be misleading as compared to the thrust

that actually would be available under design-basis conditions.

The

measurement of motor operating characteristics allows the adequacy of the

motor to be determined.

7. The research program revealed that reliable information can be obtained

from diagnostic analysis of MOVs only when operating data are collected by

trained personnel using accurate and calibrated equipment.

The MOV data

must then be evaluated by individuals experienced in the performance of

MOV diagnostic analysis.

IN 90-40

June 5, 1990 The staff is continuing its review of the results of the MOV research.

From

this review, the staff may prepare additional information notices that discuss

the staff's conclusions regarding the research.

If an immediate safety problem

is identified, the staff will initiate regulatory action to ensure the MOVs

will perform their safety functions.

This information notice requires

you have any questions about the

of the technical contacts listed

no specific action or written response. If

information in this notice, please contact one

below or the appropriate NRR project manager.

ar es .

s i, Vrco

Division of Operational Events Assessment

Office of Nuclear Reactor Regulation

Technical Contacts:

Thomas G. Scarbrough, NRR

(301) 492-0916 la

Richard J. Kiessel, NRR

(301) 492-1154 Attachments:

1. Table 1 - GI-87 Research Results for Blowdown Tests

2. List of Recently Issued NRC Information Notices

.

Attachment 1

IN 90-40

June 5, 1990 TABLE 1

GI-87 RESEARCH RESULTS FOR BLOWDOWN TESTS

Manufacturer

SIX-INCH VALVES

Anchor/Darling

(Phase 1)

D/P (psi)

990

T (OF)

524 Fluid

Hot water

Required

Thrust (lbs)

20,000

NOTES

(1)(2)

(1)(2)(3)

Anchor/Darling

(Phase 2)

900

520

Hot water

>23,000

Velan (Phase 1)

Velan (Phase 2)

990

950

1040

750

600

1000

1300

524

520

550

<100

540

470

520

Hot water

Hot water

Steam

Cold water

Hot water

Hot water

Hot water

15,000

14,000

14,000

13,000

9,000

14,000

16,000

(4)

(2)

(4)

(2)

(2)

(2)

(4)

Walworth

TEN-INCH VALVES

Anchor/Darling

Powell

920

1100

1300

750

800

1040

520

550

570

510

525

550

Hot water

Hot water

Hot water

Steam

Steam

Steam

9,000

12,000

15,000

29,000

28,000

29,000

(4)(5)(6)

(4)(5)(6)

(4)(5)(6)

(1)(2)

(1)(4)

(1)(4)

Velan

990

1400

1100

550

590

560

Steam

Steam

Steam

33,000

40,000

36,000

(1)(2)

(1)(2)

(1)(2)

NOTES:

1.

Valve damage during stroke could result in higher thrust requirements than

predicted by the valve thrust equation.

(These valves are referred to as

"unpredictable").

2.

The valve thrust equation with valve friction factors of either 0.3 or 0.5 did not bound the required thrust in the blowdown test.

3.

The torque switch tripped before full valve closure.

4.

The valve thrust equation with a valve friction factor of 0.3 did not

bound the required thrust in the blowdown test, but the equation did bound

the required thrust if a valve friction factor of 0.5 was used.

5. This valve had a removable guide which deformed during the blowdown test.

6.

In determining whether the MOV can accommodate the required thrust to

close the valve, the weak link among the motor, operator, and valve must

be identified.

For the Walworth valve, this is especially important

because stems with relatively small diameters are typically used in these

valves.

Attachment 2

IN 90-40

June 5, 1990 LIST OF RECENTLY ISSUED

NRC INFORMATION NOTICES

Information

Date of

Notice No.

Subject

Issuance

Issued to

90-39

90-38

90-37

90-36

90-35 Recent Problems With Service 6/1/90

Water Systems

Requirements for Processing

5/29/90

Financial Assurance Submittals

for Decommissioning

Sheared Pinion Gear-to-Shaft 5/24/90

Keys in Limitorque Motor

Actuators

Apparent Falsification of

5/24/90

State of Connecticut

Weight Certificates

Transportation of Type A

5/24/90

Quantities of Non-Fissile

Radioactive Materials

Response to False Siren

5/10/90

Activations

Sources of Unexpected

5/9/90

Occupational Radiation

Exposures at Spent Fuel

Pools

Surface Crack and Subsurface 5/3/90

Indications in the Weld of

A Reactor Vessel Head

Update on Waste Form and

5/4/90

High Integrity Container

Topical Report Review

Status, Identification

of Problems with Cement

Solidification, and

Reporting of Waste Mishaps

All holders of OLs

or CPs for nuclear

power reactors.

All fuel facility

and materials

licensees.

All holders of OLs

or CPs for nuclear

power reactors.

All holders of OLs

or CPs for nuclear

power reactors, and

10 CFR 70 licensees.

All U.S. NRC licensees.

All holders of OLs

or CPs for nuclear

power reactors.

All holders of OLs

or CPs for nuclear

power reactors.

All holders of OLs

or CPs for nuclear

power reactors.

All holders of OLs

or CPs for nuclear

power reactors, fuel

cycle licenses, and

certain by-product

materials licenses.

90-34

90-33

90-32

90-31 OL = Operating License

CP = Construction Permit

IN 90-40

June 5, 1990

Page 5 of S

The staff is continuing its review of the results of the NOV research.

From

this review, the staff may prepare additional information notices that discuss

the staff's conclusions regarding the research. If an Immediate safety problem

is identified, the staff will initiate regulatory action to ensure the MDVs

will perform their safety functions.

This information notice requires no specific action or written response. If

you have any questions about the information in this notice, please contact one

of the technical contacts listed below or the appropriate NRR project manager.

Charles E. Rossi, Director

Division of Operational Events Assessment

Office of Nuclear Reactor Regulation

Technical Contacts:

Thomas G. Scarbrough, NRR

(301) 492-0916

Richard J. Kiessel, NRR

(301) 492-1154 Attachments:

1. Table 1 - GI-87 Research Results for Blowdown Tests

2. List of Recently Issued NRC Information Notices

Document

  • SEE PREVIOUS
  • EMEB:DET:NRR

TGScarbrough

05/25/90

Name: IN 90-40

CONCURRENCES

  • C/EMEB:DET:NRR*D/DET:NRR

LBMarsh

JERichardson

05/25/90

05/25/90

D/

  • OG :DOEA:NRR

RJKiessel

05/25/90

  • C/OGCB:DOEA:NRR

CHBerlinger

05/25/90

  • RPB:ADM

TechEd

05/25/90

IN 90-xx

June xx, 1990

Page 5 of

The staff is continuing its review of the results of the MOV research. From

this review, the staff might prepare additional Information notices that

discuss the staff's conclusions regarding the research. If an immediate

safety problem is identified, the staff will initiate regulatory action to

ensure the MOYs will perform their safety functions.

This information notice requires no specific action or written response. If

you have any questions about the information in this notice, please contact one

of the technical contacts listed below or the appropriate NRR project manager.

Charles E. Rossi, Director

Division of Operational Events Assessment

Office of Nuclear Reactor Regulation

Technical Contacts: Thomas G. Scarbrough, NRR

(301) 492-0916

Richard J. Kiessel, NRR

(301) 492-1154 Attachments:

1. Table 1 - GI-87 Research Results for Blowdown Tests

2. List of Recently Issued NRC Information Notices

Ao1-61 p1& M

--

,

--..

--

- ..-------

I,,,i-_ -

-=1 I.

.......

....

OFC

EMEB ,4T:

MC:EMEB:DET

D:DET:NR
0GCG:DOEA
TECH ED
C:

D

_____ :LX


_______-_-

_______

----

--

_ ------------

------s-

--.--

A

______

NAME :TGS'a' rough:LBMarsh

JERichardson:RJKiessel

ger

,


v---




DT

/5/0
/

90

5/ ./O
5/ zff7-9O
5/J?1',9O
/

DAE.........90.*./....0.

!

.9

.5>!.0...5fi9 ...........

.

..

..

..

..

..

..

. .

..

..

. ..

..

..

..

..

..

..

. ...

..

..

. .....................

. ..

..

..

..

..

..

..

..

..

..

..

..

..

OFC :D:DOEA:NRR :

NAME :CERossi

DATE :5/

/90

. . .

.

. .. .

. . .

.

. .

. .

. . . .

. . . . . .

.

.

..

. .

. . .

. . . . . . . . . . . . . . . . . .. .

.

.- .- . .- . -. . -. -. .

-. -. . -.

-.

.

-.

-

OFFICIAL RECORD COPY

Document Name: IN FOR DICK