Insp Repts 50-445/75-10 & 50-446/75-10 on 750716-18. Noncompliance Noted:During Concrete Placement of Unit 1 Containment Bldg,Base Mat Procedures Not Followed & Addl Water Added to Concrete W/O Approval.Related Info Encl
ML20137F569
Person / Time
Site: Comanche Peak  
Issue date: 08/07/1975
From: Crossman W, Stewart R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION IV)
To:
Shared Package
ML17198A292 List: ... further results
References
FOIA-85-59 50-445-75-10, 50-446-75-10, NUDOCS 8512020054
Download: ML20137F569 (118)


Text

{{#Wiki_filter:. , ,. , . , . - ' U. S. NUCLEAR REGULATORY COMMISSION 0FFICE OF INSPECTION AND ENTORCEMEhT .

REGION IV

!

l IE Inspection Report No. 50-445/75-10 Docket No. 50-445 ' , 50-446/75-10 50-446

Applicant: Texas Utilities Generating Company Categcry A 2 ! 2001 Bryan Tower l Dallas, Texas 75201 I 'Fccility: Comanche Peak Steam Electric Station Units 1 & 2 l Location: Glen Rose, Texas ! Type of Licensee: W, PWR, 1161 HW(e) l Type -of Inspection: Routine, Unannounced .

Dates of Inspection: July 16-18, 1975 ' Dates of Previous Inspection: June 24-27, 1975 Principal Inspector: ." a m /[ 87Y . R.'C. Stewa D eactor Inspector Ijate i . Accompanying Inspector: None R; viewed By: M 8N[F ~ r;;; n W. A. Crossman, Senior Reactor Inspector Date , 8512O20054 851106 PDR FOIA GARDE 05-59 PDR , e sh m-..a.m.e-mam-- e e.

r ., - --- --,,,-- -,, - - ---,- ,,n ---.- ---,--- ,- -- T--

. - . . I -

- - ., ., - -2-SUMMARY OF FINDINGS I.

Enforcement Action A.

Items of Noncompliance , 1.

Violations None 2.

Infractions a.

Lack of Adherence to Procedure' Requirements ' Concrete Placement - , Contrary to the 10 CFR 50, Appendix B, Criterion V:

During concrete placement of che Unit 1 containment building base mar, procedural requirements were not adhered to.

Complete consolidation of concrete was . not achieved between two adjacent concrete lif ts result-ing in a concrete vertical " cold-joint". The matter was identified by the licensee. -(DETAILS, paragrapt 3) b.

Lack of Adherence to Procedure Requirements - Cone'.' 2 Transit Mix Contrary to the 10 CFR 50, Appendix B, Criterion V: During concrete placement,of the Unit 1 containment building base mar, pour batch tickets indicate additional , water was added to the concrete in the transit six trucks without the approval of the designated R. W. Hunt Company inspector. This matter.was identified by the licensee.

(DETAILS, paragraph 4) 3.

Deficiencies - . None . B.

Deviations None II.

Licensee Action on Previously Identified Enforcement Matters None III.' New Unresolved Items

None (continued)

. l . -.. - - -. ..- .. . - - - - -... - .

- . , , ,

-

. ,, . .. - -2-SUMMARY OF FINDINGS 1.

Enforcement Action A.

Items'of Noncompliance

1.

Violations None 2.

Infractions , a.

Lack of Adherence to Procedure ~ Requirements ' Concrete Placement , Contrary to the 10 CFR 50, Appendix B, Criterion V: During concrete placement of the Unit 1 containment building base mar, procedural requirements were not . adhered to.

Complete consolidation of concrete was . _ not achieved between twc adjacent concrete lifts result- ' ing in a concrete vertical " cold-joint". The matter was

identified by the licensee.

(DETAILS, paragraph 3) ' b.

Lack of Adherence to Procedure Requirements - Concrete Transit Mix contrary to the 10 CFR 50, Appendix B, Criterion V: During concrete placement, of the Unit I contain=mit building base mat; pour batch tickets indicate additional water was added to the concrete in the transit six . trucks without the approval of the designated R. W. Hunt Company inspector. This matter was identified by the licensee.

(DETAILS, paragraph 4) 3.

Deficiencies - ' . None . B.

Deviations None ' II.

Licenses Action on Previously Identified Enforcement Matters None III.

New Unresolved Items , ' ' None (continued) - .

_., ..-. - - .- . - - _ _.

. . . . - . .. , ' .. "

IV. * Status of Previously Reported Unresolved Items A.

IE Bulletin Status 1.

75-05 Hydraulic Shock and Sway Suppressors The licensee's response, dated 6/11/75, indicates a hydraulic . shock suppressor supplier has not been selected for the Comanche Peak Station.

. This matter remains unresolved.

, 2.

75-06 Westinnhouse Type OT-2 Control Switche2

. The licenses responded 7/15/75.

This matter is considered closed.

' .' B. CDR-H00507F4 - Reactor Buildina'Over-Excavation . The licensee is continuing geological mapping of the area. A final report is to be submitted when corrective measures are finalised.

This item remains unresolved.

V.

Desian Chagfi . None . VI.

Unusual' Occurrences - . None ' VII.

Other Sinnificant Items None . VIII.

Manaaement Interview on July 18, at the conclusion of the inspection, a meeting was held with the following licensee representatives in attendance ! Texas Utilities Services. Inc. (TUSI)

C. H. Gatchell, Resident Manager F. M. Milaa Site QA Supervisor . . . (continued) . e . . - -. - -..... - - - - - -. -

- . . . - .. , >

-3- ' IV.

Status of Previously Reported Unresolved Items-A.

IE Bulletin Status 1.

75-05 Hydraulic Shock and Sway Suppressors The licensee's response, dated 6/11/75, indicates a hydraulic shock suppressor supplier has not been selected for tha Comanche Peak Station.

. This matter remains unresolved.

2.

75-06 Westinghouse Type OT-2 control Switches

. The licensee responded 7/15/75.

This matter is considered closed.

  • B.

CDR-H00507F4 - Reactor Building Over-Excavation _, The licensee is continuing geological mapping of the area. A final report is to be submitted when corrective measures are finalized.

This item remains unresolved.

V.

Desian Changes None VI.

Unusual Occurrences . None . VII.

Other Significant Items None VIII.

Management Interview On July 18, at the conclusion of the inspection, a meeting was held with the following licensee representatives in attendance: Texas Utilities Services. Inc. (TUSI) C. H. Catchell, Resident Manager P. M. Milan, Site QA Supervisor . (continued) i ,

e . - -. - - -.. _ -.. -.

. - . . [~

' .- - .

4_ - Brown & Root. Inc. (B&R) H. C. Dodd Project Manager C. E. Bonin, Assistant Project Manager P. L. Bussolini, Project QA Manager ' . D. L. Hansford, QC Engineer, Civil

-W. E. Childress, Jr., Project Engineer Gibbs & Hill (G&H) J. J. ;4oorhead, Resident Engineer R. V. Fleck, QA Supervisor J. V.' Hawkins, QA Representative ' . The inspection findings, as contained in the Summary and Details Sections of the report, were discussed.

, - .

. . . .. ' , . . (continued)

! - -, a . - .., _ _ _ - - _...,.. .-.

-, . _.. - - . - - -. -., -. - . - - . _ . ., .,. - 4,. , _.

, -5-

DETAILS - i . i P~rsons Contacted i' Texas Utilities Services. Inc.'(TUSI) i C. H. Gatchell, Resident Manager 'P. M. Milas, Site QA Supervisor , Brown & Root. Inc. (B&R) , L. A. Ashley, Construction Manager , H. C. Dodd, Project Manager - C. E. Bonin, Assistant Project Manager ! P. L. Bussolini, Project QA Manager ' D. L. Hansford, QC Engineer (Civil) , -B. G. Banks, Concrete Superinton' dent-R. E. Morris, Batch Plant Superintendent l ~ 'G. H. Fisher, QC Inspector Gibbs & Hill (G&H) - l J. V. Hawkins, Site QA Representative R. V. Fleck, QA Supervisor ,.. ' . R. W. Hunt Co.- . ' B. Kinkade, Lead Level II Inspector

. '

Report of Subjects Inspected I i

1.

Scope of Inspection

The inspection was limited to the follow-on review of the licensee's QA/QC program implementation applicable to the concrete placement for i

the reactor building containment base mat.

2.

Plant Progress i The overall plant construction progress is reported as 5.0% complete.. , During.this inspection the first mass concrete pour for the Unit 1 containment building base sat was completed. The pour was completed , , from elevation 769'-2" through 781'-2".

Construction activities in ' other areas of the site appeared to be progressing as scheduled.

t ! i . !s. . ! (continued) < . ) .- fai

. < , I . i - _. -. _,_ _ _ -, _.__. _ _ _ _-.. _ - _ __ _._ ...... ..... ..... . . _ _ _, _ _ _ _. - _ _ _

- -


-

- .. - - .. . - - _ - - - -. _.

-. . . . - . p. 7. : l.[

t - , -6-i 3.

Unit 1 Containment Building Structure - Concrete Base Hat Concrete placement from elevation 769'-2" through elevation 781'-2" of the containment base mat commenced at 4:00 a.m. on 7/16.and was

complete at 12:30 a.m. 7/17. Approximately 2300 cubic yards were , placed.

. .

1 Concrete placement was made utilizing two 3 cu. yd buckets / cranes, one conveyor unit, and one concrete pump unit at four locations around the containment building. Concrete was transported from the batch plant via 10 cu. yds. transit mix trucks, approximately 0.5 miles.

The inspector observed the concrete placement activities-throughout . the day. During the placement of the lower lift pours, the inspector ' . ' noted that in certain areas the concrete lifts were exceeding the .. prescribed 1.5 foot height maximum.

In addition, the time interruption } between adjacent lif ts appeared to be at the point of exceeding the t prescribed 70% of the time of initial concrete set.

i . ' ' These~ matters were brought to the attention of the cognizant TUSI representatives and corrective measures were initiated. The B&R concrete superintendent provided additional supervisory personnel at ' - the four areas of placement which appeared to rectify the IE inspector's areas of concern during the~ remaining periods of observa- , tion.

j '

On 7/17, during the IE inspector's review of QA/QC documentation ! relative to the completed concrete pour, the inspector was informed .,

that during the concrete placement of the last concrete lift (approx-

,

imately 779'-2" to 781'-2") a radial area 60-80 feet in length on

! the west side of the base mat, was suspect of a vertical " cold joint"

r

between adjacent lifts. The matter was identified by the B&R QC F inspector and recorded in the B&R Deficiency and Disposition Report

, (DDR) No. C-45, dated 7/17/75. The surface area of the apparent " cold joint" was visually examined by the IE inspector and photographed.

  • The photographs are currently on file in the NRC Region IV office

files.

! ' On 7/24, the IE inspector was informed by telephone at the NRC Region l.

IV offices that on 7/23 selective areas of the suspected " cold joint" ' were chipped out and examined. The examination revealed that the lack , i of complete consolidation of concrete was not achieved between two I ~ . adjacent 1ifts in the area of the west side of the bottom of the

reactor vessel cavity. Preliminary investigations indicate that a ' , radial section of 60-80 feet in length and 4-12 inches deep is i , involved. The affected area is currently being removed by chip hammers. The licensee representative further stated that a full

report will be provided in accordance with 10 CFR 50.55(e).

, , . (continued) i ,

. . i T e + - - w-w m, -- ,. e_...n.

--. T .-t.*-t--- eeg--~em9g.- g.1 --re m-e-t-%..,,..-e -- -, - -w,g, -w.g..-. w..,&,. .,,.--.+-we< --,-.s.

w. _.cg-. , c.,m,- --.s , m -- 7._,------~,,naw-a.--,+-rw .--.-w .,m,,,.,.y-~m ,

. _ _ _ _ _________ ____ __ ____ _ _ _ _ _ _ . m__ .__.

. ' '

.. '\\ I - '. 7- - i . Contrary to 10 CFR Part 50, Appendix B, Criterion V: Concrete placement activities were not fully accomplished in accordance with G6H specification No. 2323-SS-9, Section 8.4.g. Revision 1, 3/19/75, and B&R procedure CCP-11. " Concrete Placement", paragraph 4.3.4, l Revision 0, dated 3/31/75, in that the time between placement of ' adjacent concrete layers during placement of the last lift of the containment building base mat pour on 7/16/75 exceeded the prescribed j 70% of the time of initial concrete set. The time delay resulted in a lack of complete consolidation of concrete in a vertical section of the top 4-12 inches of concrete and extends 60-80 feet in length.

- This infraction was identified by the licensee and had the potential for causing or contributing to an occurrence related to health and safety.

- This matter will be reviewed by the IE inspector during the next site visit.

l t 4.

Unit 1 - Concrete Placement'- Records' Review .. During the inspection the IE inspector reviewed the QA/QC documentation records of the pre / post concrete placement activities relative to the , Unit 1 containment building base mat.

' ' , Documents reviewed included: B&R."Rainforcing Steel & Embedded Item ' ' Placement Checklist", dated 7/16/75; B&R " Concrete Pour Card", dated 7/16/75; and B&R " Concrete Placement Checklist", dated 7/16/75. There ^ were no items of noncompliance observed.

In addition to the above, the R. W. Hunt Co. records were reviewed.

During the review of records and discussions held with the cognizant licensee QA/QC representatives the IE inspector was informed that during , a B&R QA surveillance check of the B&R transit six batch tickets, six

transit six loads had water added without approved supervision and ' signature of the testing laboratory representative.

In discussing this-matter.with the licensee representatives the IE inspector was provided a copy of the DDR Report No. C-46, dated 7/18/75.

In addition, batch ' tickets were identified as 0579, 1982, 1980, 2084, 2085, and 2105.

It was observed that the maximum water added in each case did not exceed 10 gallons. The inspector was informed that an independent check will

be made of each batch ticket against the batch plant computer print-j- outs. The print-out indicates the allowable water that can be added to a particular batch without exceeding the water /coment ratio.

Contrary to the 10 CFR 50, Appendix B, Criterion V: During the a concrete placement for the Unit 1 containment building. base mat water was added to transit mixer trucks on six different occasions without . the approval, or signature, of the cognizant testing laboratory repre- . sentative. This activity was not in full accordance with the-B&R . ' procedure CCP-10. "Ccacrete Batch Plant Operations", paragraph 4.10.5.6, + Revision 1 dated 4/21/75.

(continued) ' +

. -. -. -. . -- ..- .. O - mir + -, ,m.s-Ma --,w _r----. ,..__.--,,,,3y , - ---., ..- s_.

,,-,-,r --gw- ,-

,,,- - ---- -- gy-

s ,

.' e > ,, , .. -8- . . This infraction was identified by the licensee and had the potential for causing or contributing to an occurrence related to health and safety.

' This matter will be reviewed by the IE inspector during the next site ' visit.

.

. I e t

e

4 s . e k .

A

b

a

- +M ms mee eg ee s e e=a .ec.

,e.. . ..m.e pop v.,.....,m ,, g ,, , ,,,, ,, _ _, , _ _.. -. .

i ~ .. M" g &ownCTRoot inc.

' ' QUA1.lTY ASSUR ANCE DEPARTVENT -- _, 7,",*"' , , .a s.o.

DEFICIENCY & C4SPOSITION REPORT I.1 COM ANCHE PE AK STE AM ELECTRIC STATION DOC UM E N T VIOL ATE C' R E v. No.

CP-0AP-17.1

  • a at.

5.2.1 < Error corrections on the following documents are not in accordance with the above outlined procedure.

Calibration Record Cards L-100, L-131, L-163, L-164, L-167,i-159, L-210, L-211, L-215, L-217 and L-224.

U L-l T'l b lbc /

I 'Q/A QUALITY ASSURANCE g i QA RECORD , , \\ \\ ntt.DbA...Q.Q . L-REitnTic:a '=m =-. C ...... _ j 3E II{' ' 'i["-

' Comanche Peak SIEn Elee. S_ta - RE PORTED ev: - i[ O ATE: OVED B DATE: George H. Fisher 10/3/75 AkPdef [Y bussoI~.u: /o-6-75 DISPOSITION RESPQNSE-REWORK @ REPAIR Q SCRAP Q USE AS IS Q OTHER Q g g All corrections have been initialed and dated as required.

e< $;: y f) l ll } O n g ASSIONkO TO.

[ DATE: SU TTED BY-DAT

B. K. Kinkade lof3/75 \\ /j)Mtw a X4 wh M u N Or W / eE'R SA 5.'W 73 ku'Sf' h,fl 'fh " " * }l'1 73 -

RESeONSs c/ v y ! All personnel have been instructed when making %;: g ghu ec nts a to line out error, initial and date.

tuu . ! copy

I l/ l Y / - ASSIGN E O TO.

B. K. Kinkade 10/3/75( h DATE: S ITTED BY: OAT / '6 r tv U /> /b 'M6 CLOSE OUT iTo be completed by Quality Assurance Department 5 h " 4ATIS37 m u n't " W g g %/'gg coee.c1,ve.c1,om: , g pE,.C.E NC CLOSE O t;"gryy/, era ^;'r.7s-:;fgq g,s n ^l';..,7 - " " * " ' * - ' /YONg was 'we k.'# b r c,. 3-gg 4 _ - - - - ~..a g % B&R QA. HOUSTON

tb so-173 2- - e&R OAS TE O Tus' o^ 04 u ^5

i TUSI O A St TF h NSSS SUPPLIE a O ~ b ~~ CP.O A bi. ' Mtlf . R.e tE4 s E D"FoR D ESiC'N R E"' EW . fV L) . ' s* ' _,e . , COVER SHEET .

  • '

' ~ ' , STRUCTURAL CALCUIATIONS ' //f x

JOB: 2M9A )( - , 3 (sAB-l0lC) CALCUIATION SET NUMBER: st A B s. f M M ~~ 'FL. R., E L. B L o # ' -G DESCRIPTION! . . , ,.... ORIGINAL ISSUE:

- - Sheet Numbers Included:- ~1 , ' ' ' 4M4 . N Design Reviewer-- Date: fl 24 7b , + / Date:

ff - ' Job Engineer -

'. REVISIONS: - , Sheet- ~ Numbers Sheet Sheet Sigs ture Signature ROvision Superceded ""^a"s Murba- ' Design Reviewer Job Engineer "

  • Numbur Or Deleted Added
Mi b

Date Date GEE RER C0tivat 3 H. 2p j lWy.

- By pa i.t ns o nce . ., 2-3/6bA-P C6'r Aer. coJcx s a..s p GY P4 SAC Off/C6" . t ,l ,.~.,: .y -

. \\ ' FCH BS'-s9 . , L_.

J . ... O, , .

[.. Y .... . ..... .,.. ~.... .. _.. . . _. - .... -. /, J*, *...Q........ s .,... .s a, .. +,, ,.,.,,.,.. s ,.= -..y..... . - - . .., to . g.Q. p ..._-..\\ =_ .. ...,... .... 4.,

,. s

  • -

s a

  • ; %. %. -

g , _ y , , .,s... ../.. -.. a..:. w,2 7.+ w r.

.... -

. ;.... a'

. ., - .-a :. c. y ~.:.~ + ~ +. - ' - >. - r *.z.

, o . p- , . ys , . n ..

  • ..

. *[. . .y. ;. ].. q,,..., ..p ;. c.. I.,.

  • + 6 1,,r"],. _.

,l ~,e . ~.. . '.; < k, r't e,. n "'

r.

> , , . .u.-,.... ... e..,'. t'. Y :. ud).0. 7 }. *; s, 5 s ' D -....p .... 'i n... - * ,,... .. 3 :.%hk:.* %:.;. 3' i

. :. '.4

' ~.; . . ......y-1m. p.a.- .m .. ... p. p. -,, s ,',.n ..... . ... .e,.,.a.

. .m , '* -: A : +3 gs- - 'rs".

_. p. *y'- ~.

.- *

_ <g3

r. m.

. . 9.,, .w , .

. -

.,. -.

.s s.... m3.c> ... . ~.r s...-m.s . u..e..v'.. ..... ., . .., .a ,. . c > -r . v 4..,.,.. w eno....n..... . .e , n - - u.

. -,, ., , * * .. TITLE /drwer/cA-2>come NF.O 2 ~ '1- .. . ... . y,. - - ' - ~ t.t - . - ' $.. . ~.. '.. . . , ......

.:. . n.. % -- _.. . a ~,.. , .....m.

-.... -,..~. ... . . 305 NO,. //.2.M3-96.. ~L .i . + .... - m J.

.s...6~.~.

._...

. .

,.+...,

. .. e ..n - ... .. -.. ~. - , . m.

. ..., . .. .: .: .., r - e.. . ,., .. . .. .. . .. . .. ~ . .,.,.v. : y g v.....N...i :4:.n:s.a.w.,. .-- CRIC...N, O. 40Mwr, sgr$ . t,.: . . .- -

_ x.

. - , ....~.a.~..,.... . ... . ... ....,.... ... . . . ~. - _,..,. .e.

.., -. -- ... . n..~ . w.,.. n. . .u.

.,.. .. . n,.,. -:. PREPAREDBY 8 A.S....... - - -- - . 5 _- ... -~.> ~. -.. _- -,.,.._y"."..<.... .,_ . .. . .m . .., a :.. ~....n e...n..,,..~.m.... ~ r.& . g . -.. ..n

. ,. n.. _s.w .x, em ~ . . ...s u.., ..vu c - --. . . ..,,, -.. DESIGtt REVIEW PROCEDUREL /... .:..~ . . ~..-...._-..~..~...~.4 ,,. .. -. -.. ~. .-. ... -- STRUCTulum Cill;CKLIST - CALCULATIOt!St.

. . <... y %. >.., T 5s . .. . . .~ . .. :~ ~ ?. :. . ... a '...:.7, ..

< x -+

a.:: . .... ~. ' - ' :: .; .7.:.,

,
q

. .. ITEMr. S [ g.a,.u,m.v.: w.r..z..~:. p..p.7.3 p..-.. m.

4 w.y.23:.x.

.;. ". . u . . + M.x..m@ 'c. .. w.>. ... . ~. -

. n.,. m..

- 'MOfc CONSIDERATION .[l@V$$"8 ' ~ ' m.,,.,pw.,.ww.,,Lw(.S ' '. . .. ' n..,.. :. &.:y. An..,.,sf .*s, k.?he.w.r i".

.. - : .x. ... : s r. x, w w w a.,.........e.... . -. ~ .. .... m, y....... .-.,. .m .w z e. 4an ** war. ;,,..... r$.e ........ - . ...n,. . '. 2 s >%.,oo+ y v.s n.wa nn.,..- v f..t; s, + e s;., -em. s.. *.n. $... ......- ., .w.3 m e.n'Iv.. . e, ' >.-.m,. ., .,., ..p ..s,s.. .._+.:o. ne...... r,....~_..o,..m.,.;_-.,.-. . _., . s :. .o.

. u ~e . ., ...,.. . n.r s, s... -a .e... ? , .. .._...... _. . . .... USNRC " Current Events-Powcr-Reactors" ~~7 '"- '~~ - -"7"*:"'""-~C

~ ~ n
':~M.t. u r m. a M.M a;.-r w w.en.-=

- c.

cnd.,Operatin5 E. xpericnce records,.u.~ . . I %_.. d=M. W~. v ' ' / ~Tj;;.3 v- - - - - > - - * l s M".

J.c m G.sc r' have been considered, where applicabIs', .. . .. e W 4.p dh .. m. e.c_..d d '. y - (Ref. Job. E.ngr.T - .; a ww@ +NC

W

  1. w...

,,. ~. _,-.... %.y ... . - . + -.., l,. 4 '. , - . .. .2s ... +. ,

. sy..; y > . ^:~ - . .......A. w '.s ~ . , ...- ...... . _,,, , ,. . ,. . . - . _, e. c c.,......--.s... . ....- . - .. . .~ . . Scopercovers aII 2.ntended. worke no,

c ;.c.slg~., 1.x.~.c...m..- .a M.,.~ W,..e..h. . u., a,. n.. interface gaps, noioverlaps (Ref.;.. ".s,.. v. :.n.. .,.,. n..+..,. -. g. g. 2,.. g 4'q g g. m ... .. l =...~.g .,7 '

Project GuiGa.F .... = *c: * :.. a....A.,,O.~...~.m.,~.._.._..

=+ 4. P M.,.,-.n.c.,. > .- ,. w _k.

... .-. r,.%. - .. w.

-. m'. . . '..... '.,. + - ., -...+;- , m..

a -. . _.. g, t.

  • ,.

. ,. em.Ss.c .-. .~..~ .. - -..~ -. . , ....,..,.. +.+t~..-. . . ,.. . ..... * . p,. ss,g sta6g.h _. * * 4 ' ;g- -p.,,,,.3,, ... . - , y e ..... g,,

  • ..-

. . [&' &).hfr.. h..., .( M.'1$ w.

Assumpt2.ons are Irsted, clearly,-defs,.,j '.nccI t -.. ~ ~.. 4,,,, g

- .: e .. . ... s . c...- t.- . . -. -.. ~.t. 7*.~r.

. cind reasonabIc- ... ....- u.. :... f ..,.4 -

. .- . .., . ' . - < ,,.... .,...;.3 . .

. ~. . .. p w -w,.,.rs w . ,. r ~ ...m . - =.

..m x,
x w. a:a.

.. . w..+ E +.... w . s,. . cl. n w: ~ R ferences, includintf other calculations ..... .. ~.. -f.- . ' . _...." i 1.i.... '.., - v.' , M., - - and sources / nrc listcck & t . .. w,., w w...e, s x ., e.rwz . ...,. . e,.. .

  1. .
~ ^

. s.t + k. $ "*- 5.Y f. v ' %. c.*. ". me', D : ".* .a.A. .^ ...~.,. e'. . .. :. !. * l,. S ' -.- . .. . - v ~ n.a v . n . : % - fccto . solution.

- -

.

. .. . s . ...... ..... ... . - ._ . . . . - C:nforms. to seccificationi.

~~ ' . .. ' *

[ ' , . . . . ' . . Loads arc corroct (Hc C ; PSAR)' (includ-- ? . ,. - . in7 Env2 ronnuustal, Cbnua dorationc) ~ -

,.

-. . .. ~ . .._. n

  • ..,

e

, -

. ,.f.

. .N . k -,%, M- - , TIID. 8W4 ag ,,,,,

  • .

, % k "$ .W .

...r ... - % /

, . ._ . "f"

. -.. _. _

f . ........ ... - - - - - <.. o o.,@y..

- . . - . ~ . .

      • -4.,. s.

- J,. . ,.s:. .... . _ ... ". w..,, Q, _y....' . /., m

. . - .. -q. , ... g* .'[ . 6,, g. p '....."g.. ,j;. ' i., . . ..,.. gf f !.*Q *p 'Q.'..yg.

' .'*..b. /.. ;s..., C... ; _ n.,... ;. ; ;,. w. :...., ','.;, s. c...,. 5 ;

e.e .. >,.. 9..

J

. :....,. s .w c.

. a , ..s.. w ,,. 7. 3.m9,f., s .e . . . .A.

a.

_.

-.... ;.. a.4, .. . .,...c.,,. .,. . ...s . ,,...... . .. -,_7 ye,. f, -~. . .. .. .' ~. . ... . . ._.

1 g ' p., ,.,. e , . . ., %. , s..: s,,. ..;*,,.. -

. -e., ,_..- . - ... s, y -. .. ,,. i...,.r- .y.,.m-, .- .s -,,;. . _ r.,

-

,.c-4.- -..- .s.n,,,; e&'f_ ,,.:.a., ...,... . ,. .. - ..- , .m. s. .,.. ., ;...:.,.. . ...

  • T1TIR Afryssvac orws4 */G2/'&y2

. ~ '. "'-' '$j

'* 7

  • ~

" . . . . f.w...,. u t.m;,h;.;. ~-s .. /./ 24Mo& .

' ~ '

;.. _.,. p...,,. _

m.

... ,...... 2.,.., ... ....

  • 305.NO.

. L '., : ?.:T. ' :W.

' "'~' ^ . .... . . . -[ . qom.

vt yM: ....-.-.,..~...._t.

CALC'. NO maK.-me -Se r '5 - 1,., "S.

,. - -- . . . '... ~.'--'.--r.

. - .... m.m.._.un.,,,.,.. - ,o.4 %..., -. . f . . q.-.. - , . . n., :.... _

y my

.. - ~ . . d'C V.'hb .PREPAR.ED BY 8 M ~ --

. h w - + -:...._ c. --

... . ... F. ~~.. - m.<:.m..m.,,., , ... w.m.s.e a 3.5 c '..e,.,:.. % l .... . . . . .. ...... -,, ,. ' - DESIGN REifIEtt PROCEDURII. ._.. . -.. _..e.. ., , ... ,. -.. m -er- -e - - O.M!.~~.N,.m.M.,@.. i ". STRUC.TURAL CI!ECKLIST - CALCULATIONS.

... :.. . ' .*

  • -

- - - x n ,

.... ~:. -

.a.:. u m H

... . :. a., w .. . .. - . ..... -.,.-,.. m .: w. ; n. n. m. + v.. g..e . ...,.. .r.. n.,.w. e. ,1 n, ,. . .... , ' ~. t : CONSIDERATION * '..f 3,Q gff, . .-

. r.- ITEM' i " ..m.. .... .6 . -w....... .. . ... - ... . , a.y n.. ~:.,.;:. mr.M., - .. m.;w u. 1.. > t.- v -. - ; v v...s f.;, g L.. r.4. em s :. - - .. . .. o . v - r g m.

n.r. . - .,c 4 3.dge-1 > , . . , , , ..v. y.. ~., ;.u.w aff , Deflections ' and. dispI... ..3 acementst are: - 5 'I..$%,e,.; ; $,P ' @ -; g ;. E '.; p ;:G $gg. q d. .- l..- . . .. .. m.

. M t_.+.. V E. '. _W.O W. &.. _Q U W O M...,.. _& : v7 L

suitable and reasonable (Interface 4 _- . .. _. _ ..... - - . ... -. . . w.r ..,..a.. n n.

,s.

. ..__.._.~____:._. _.

. wit.h other disciplines)....~_,.. .. ,. -..,.. . . ......... .. ~. ., ,. . ,, _ _ _. . . . . ..... . .. .u z.,. p:w w . . ,,, ~4,*;,.. g.m - ., _,..... - .. _. _ __ ~-- . -....... .. _...... ,.. .. ,y, et n ,.s ,.s .. ..-. MQ t' C ~C [d".".' *0 &..,? O,..illT.%w.~ Compatible with equipment inf'ormation, ~ M .. < ~. I -,c ... - (Loads, Dimensions). -. m- ....., _,. :.. y,u.~4 n.,o -,...3 ~ .o. - -m e. .... . ... m.,. e w:.. r, r..

.

, . . ,...~ ... ,s,,.,4.,. .. v. x -. a.u..y e.

. .. -. .. . .n :.,... u. E.g..

. n.: . :. . .. .

_ .. . x.,:. .~ . ,,..e.

g' ; :.u 7 %.,W'M.M.M...f.;W.:;& Description of materials incl,udcds.

. r... p. >. . . .. C.M,... , . - ....... > ". "m,u> n @mo"u.;*e.r..*..,e"t.3, [.s". 3,.. #,..,L.*:. w' n '* M. .....o..... _ g.- % ~.,. a +.g'".. M.+. ~~ M

  • -'

' (RcE PSA10 ) ..s. .

. .,..,..ww%.. . . - . +.r,. . m.

..= m, . m.

,e s.... s m .- .., . -. .......-.. . . , .. n..,,..,, N,,, + w..g. 7,p g,,7 g n . .. ..,.,............. .a r,.%.g,, c %~ . .. -

T.'6.Pfg@c.p,- Compatible withe soils capability 3 - L, % py V. N...j - .- . '^ 4. m.& _ n n .r4 (Ref PSAR and Soils ReportL. y .. -a u a i . - g .y _-. . m

... . .

.,, _. -

. , ~ N a gT.m. ^ r . . - Cbmpatible with reInted drawine.rs..' . .. a... a....., e m. w.

3.. . . , . . ,. ,. i.+.3 '. ". c .r.g.N.n'.. "',% +y P, - n- ' ... ...... a c.

.* u.

.. ....; . . m.i. . . .m...-- .e.

.,y. . s.e , m.p.. ., + m... ;.,. .,s,.~.p ..> . , . . . . _ m a. v.. a.. '. Na r.

- e a, w ', . ~. 2.. n.. a.. h. q.,. u..e ~ Conforms to PSAR -

<... =.>.. ; * c l v.:...- . . v. ~ n.... w. .- > . . . + .w ~ . .. -. ,. .. u.

. , .-. .. .... , .. u,s., s ss , g,.+.e a r. np.

. - m.,,.g w... a.. + m m a 4.u.- : p.., .- .. .. s. -./ .% .

p.w , n,. , Specific references to,codest and, stan;' . .. o., 4 -r . -, ...-,m.

.. g.s.

.. ! - p,f //.- D e<G.' dards are included and, conforms.thorntoa - ' '~

c.d.. (H3C. PSAR and Prtrject. Guide) ' ' - < , .. n. ~. . .. . . .. . . . .u-p . s . . .. . . .. . . .... - ..

w.

. ...._.

Conforms.to. Struct. ural Design! Criteriu ..~ . . 9,-- %.. r.. '- ' - ^ - - - - . y .. -. r

,

. ......- cr.

. . . - . , .. . .InterNce with other disciplines has. been.' . '. 'C.

' '- " g ! (.[' ' accompl'ished- [ / ~ - ' , . . Wlb, - - , . -' l - .., - c. ;. ' .M.

i-AdditionnI. for' Computerized Calculations: . >.. !3

l g [. , - ,

' Proper Comput t:r Prentrinis.(Imr PSAP) }ha= ucci,annrooca ror.. e.-

. - m.. . . -. . wgM - ..-; s.

. ., -- . . .: . .' ' . < ' $5 - w.

'

. ,$

. - Q- ._.

% ' ;. . ..; . . :s k: , _ - . . . ,_ .. ..,.. e..-. e_a

- .. - . .... s.

. .. . . ... %,... T M.

.. ... - n . . . m 4*.M,i. w,*,d. '. * i . .... f ;, : i..... e . ,- .- ..a.. i ,. - . - - .u.

~ n , <.... - . .. > .,. ,. ..,. .. . ,..- x.

s

  • .

t , _.

- -

  • .'...,.e.

, e l .. M.u g' t ~ _....... ..,. . ...... .-, .. , . _.

.,. .-,.. .,. . e.y. . . , . ..

. >s ,... - . A y;. . - ,.,,4. s,c . s .. . _. - . . .. ,y .a .; . -.. -..#. .3 , . ., ...- ?,S. 'E ~TITLEi Gwat/cra D.

    • /~ G. 2 (, & g

. . ..,. ~~ L.,,.__ ., . s.

. . , .3........ . , f . .. , .. . . . 1. ^. .C-. p- .- ' .. . - j . ..... - .//23Z5-WO Yacio NO.

n.. . M ~ -..: . . . . C . ..- _..r. c. ... ... ~ 3- .y.-.. .. . . s.. , ~. -%1^P-- NO .4#s-/M. <=7-::t h1 . .- . - -.... '... ..... ' ' - .. .- - - . . ....... ..- . ~

...

. > . PARED BY JPPS. - -..... ....w . ,. . g i..:. .. n.. w ~..,, -... .~. .., . ..,,,,...... _.. . .. _.. _.. .,... ~...,..m.n.. .. .. - ,., .,, - -..-: .. .. ... . , .... :. .? i.

.s.-

s.~7,- A>. . w.

.... .s - - . .;.. ...... .. .. ~..... - ...... . , .. o s.. c.. ~ .m.s .. . , . . - - ~ + .., ~ . '. '.... -.. '*~ DESIGN REVIEW PROCEDURE: . . - -....... -..,., ~ - '-" . . ~. .. _ ,,.. STRUCTURAr. CHECKLIS.T - CALCULATIONS .' ~ ' - , ; . . . '.,.. g,# . . . a ,s . .... ..... , _ ....., ,. .... . ,. .. .,:.,x.p m.

. . ... 3. : qu.. . y.

- ,..n .- ..:. ,, .,, . . -, ... x.,,8 ....a ,".R~1.. VN . '.. CONSIDERATIOt3.

. i > !, 2.'. ITEff - ,u<,. . e..... .r . n.

-. ,- n...n.

..m., w w.w:n..g.e

.. : . y: .,..s. w....m. a.. .. p. u.

..n ...- ... . m. as...n..n.u,.e.....>,y.. . p.. ~ . ~ .. . i .. ' " 9. '~.b.1-9.'..d.t._95.m.

.. -.D2ta Input, Assumpt ons and Model. are -

. 12.stedy defined and are satis actory . ,. . ., .., . ... ... ... ~.-.,...~.. - .u m m.~ ,.. _..,....3...,_2.~.a..- ... -.. -,,.. - - ..%. <.. ....~ . . Interpretatiors of Output is included . .. .. . .-. .- . . . ..fg .. 3.;w. y:v -fu - - c -.. . . . v.

. ,. > s

.. -. ~. - + - . -Check resuIts for reasonabIcness;- . ' ' '.~,.,. -@. c. ' - . v .. .2. a 2 s...... w,_. .. . ' Preferably verified, by a simplified ~..,....,.. . ..., ...... .. ,~.,.m.

. .... 3 e..,f. 3 ....... ~~ . .paraIIeI check (Ref. p.mARh. 3.,;_ = .. ,,. ~ . , ,;.., ; -. ,. . ....__s.

... . :. .s..:.;;j g

..,

. . .y .

- .,. . . . - s.

, . . ^ - .. a.. :.. u.

. ... ........ -

.
.

.. - - ^ ~ :: ~".4 " *" ff '"~- .... ~. -... - Properly indexed and"fiIcd > n P .v> bv+ . .-

.y = -,..e...

. ~

.c - . .....r.

. v . . . . ~ . . .. 2: . . . ... . , ., .. . . , . .-

...

.. , , , . . . . . .-,. . .. - n4.. , n.- .q. :.. _ .n ....,.. . . . . . +. m, . .. ... . . . ,. Nster Desigrr reviewers signature confirms that desic)rr reviewer.,... f.' ~ . - _ has co'nsidered each item.on. the checklist.

. ,.

- *

- , , ..g .. .. r. t.. '. . . .. _ .- . .- ..... +. reviewer"s completiore ' . . f'. - - Signifies designt .. .,. , .

s.r..;.. n =~,; & w.'.

OB review; ..',,..~'.a,=..c,y A., - . - . e . . ...s . . . >. - e.

. _.. c . m.r .. n .4 - ' rm ... -. -.' ' ^ ^.

1

.. ejsf.mlwt .G1..

  • .

. ;. - .y.

< y.i.

v.

, . < , . {. ~ '

  • ^

' ~ . NAi Not ApgIicable ... . ..- , . % - . .

,

. - . .. -

,> . . _ - ,. .... , . ,. . , - .. . . . _ g.

- i - - - 2.

.. , _.,... s.

, . - - . - . 4. s . .. c.

. . . .% , . f.

. ~ w g .Q '.y . ._ ' - . . . - _ _ . . .. . . . .

. . r . . . F-722n., in-7(i ~ ' . , . . .

. __ . . .. -. --. _ .. ,, * r c *,;;,p.......(.' .J. 2,.. c.e ;.'t.

.. . g.~ i.. . .. . , . ' u(e. v. e, . . - I

.,( *

, - -- .,m..... w : w. w ..,.... <..-.es* ' 'm.

      • .r
  • * ~.. ' _ * * *. * ~ ~ *. *. " ' * *.

sibbs a t-rr.rr rnc.... ~ : e.~c ~ m_w.'. .t .. s 1..., ., + ..,,

="*=.. ,' *. ' ' " I .. ,./ ,

  • ~*e.a.-

.==8';,..,...y 8 -

. .. y .- . .- ... m.

.... _ .. ... _ _ ... ... . m. m . __ . _ sy - .r.

.. m. w,m. -..s w r. y. c. .. - - - - . . . . -.. _ .m . - 3,y.

m.. ..m.

.y. y agf s.r1 gg gg, g..ggv e.

. .. - pyggy yggag - 7- . ~ ,

. ... ,.y.,.,. ,. f l,y.. .. .n

. n w
,.

-w,,.s.

.-. ;. n,, n.-_.. vi3nn., ..,q,y ~, , . o .. ..,:e s c. m,. ry.pp c,,; y i..,, ys.2,m,,w.... ,,; , 3 ~r....

.. - .. , Tt.

MINIMUM' WEB REINFORCEMENT W- *M R._ __ . m .._ .,,1.. n. (AC L 316-70.: It-t A 5.9%, A-5lO)k.L +Er .* - "W:= ' -

. -.w.

... .. - .. . . .

  1. - -.

-4- .4 -.$a.

,. *...-,.a.. w.-- ... /g.,, .- .. . ~,x. :.w s..t.c..v,., m,.. n,.e.a.:.;~.x.w f.s :, y,S..n,n,.~c.rw s.w...,%, $,,..w c .. . .., .~. ; n..,%,..g+ , ~ . .~. ., = n.n.

sn ~ ..,-,. m;3,,.c.e,t, n~:m.. s:m. ;;.%, L , - m.e. .~.w.;; n,,, o n p,. ,,a..,n.

u.. __ . . .. .s . - - s.

.. _.. ~y ...,. h,.g.

.,.. . ,., t r e.s.s.,.. ... , .gr 'V.. g ~.**. w..w.s, ms; ~,. s,w e.

.. g .. u -s -- I ._ n.a . m.n.

n. _.. ~.. n n.

. -.- - , _ 2. a,,$[ !. 4,.,0 0 0.,..p 3 g _ y,= w y, . r.. ~ . .. m, ra. .. .~ wm &, m..gg.%,3 ..... . .sr .5-gN.. f,,W.". ' "*[J. )i d, f ? A. ".,(z o _ s o c o c e st* "Ai, <.w.hm g _ %.* @' gw'., j.".g,;i[*,, fQ, h. $* %.- [ N ~. ' ' %b.. i / ' ,...L 'i' *"7' f. ~, g ' ' ---2 Ay. b 4d. a - t.-- 8 d. 6-46- . . + ... w 4.=

re w,,

s.m.. - ~ _ -- = - - - .,. =. .... g w~e,- - . - c a w +: q, a w.s M...... - 4..= Eri=ECUVE. DEPTR wg , . ,.- = = =. _ ._.- . . .s.. . . . ~.. p.. ...

.. u :. ,n -. g. w: w......,. y. w.,., . .. v.~ e.v *,.+bc_.r%.%w rVM;#W.-., M,.W., ~.26.. - . .m..w .x ~ .,, e. a xtren a~Wc .t,+,%j,. m.f,+

  • .y y.6M,p'.y....

- - .. g fT::%.ee @ W W

w- 'g.

- e ' ..,.O.,.,.......7.w.

, % n-%

~..e..., . M y e.,:- f-~ m %- w w:, p- + ' me.-.>m ,w m.w.

n m , .m sx r mmm.a.

. .o y.e w vg4 w.

e n.s - v-m - -- * - ~ ~. " OJ " ~ ~ -- -M* ' JJ **/ ~**.*:* ' l * * l *... e s ,,..-.,.s ..: i,. ..6'. cm . ~.A. c c.r t wCOt,-3';U...ssv.. Aufsat+ Cotf" 2E."

in n. Est.owTab..eVu Oe.r..V -. -... ... i.

. ..,. . ~. . . - . .~ a.&..VA.t.tJ..E ttiC.OLG/JSEVAt.UE IMCOLh..-. V D . . e. tri R. E G.I O N. - (. D. lE E -- ... .- ... -.. . -... . . S., tM REGIOtt. (b),i L6 04:: VAL.ljsIt4 cot 7 t135THE FOt.LOWtMs:n.

. a : ;,, : ;. m,.,..,s. ;.;; x,. : M.a, y%.~:wwp.a.~..m,. 3p' 3..%g.u:.o.m.g ,ph... - . n :-p w,. ~.... . ..._..~.u- . , g.

.. . .. .m~.. .~ > ' 6.. g )g p 4 j, g a fd, f,s =e up =gg. -..s.78t!. p rb'M.% /.g-OR.11 E..,,; q.g..,.er. ...l- > ~n. c m%c3 y p. p.4' <f,.:: m;p n v& : a.:.w m.,m.~ a.w :.w<: n.mme.- - . ". 4.. ..J - a..a..:,- r -: m.

, - =.7_.WES REIMF. iti,R.EGtG_t4 (af.... L_WES fREMMIN l%EstOM (bM,_ _.p,- . . , _ . - . - . ~. _ _ . _,. .

i3 - . c _

, .. 9- ' i 5 ig, : -..,ipD.

. ..- . . . .. -

..

M

. BEAM ~E Nf lSMEAK WJiiduidQgg. 3'riEAR

' ' ~ CAPACI.T't" j=g.g,=O2 b ' CAPk2rY SPAcitsy

STIE

. . g - b k. 7 p

.. PSIF ?S g 5-L.,..-

-irastY. x m 1;m.n p _ .p - . ' 2.

3_ .4.

s s -

t .. . .. tex 24. ~ * 4 @L t.G , SEG.E. IOT

  • 4 & 5

'52s.S ' c.04 M W., 'rr 6 412.5 O'.GSin Q ' 14w28

  • *

't 'It FGer.5 IEM- - , igx 32

  • te it :25E.5
54 r A P G

~5 76.5 G.Oa7& 6 - L [8xSs u pyma. CS ;255 5-m tO57. W Wi Sc ' 2331W %.O.Or85W.- . 20x40' m' O IE f93.G ' fsn ~ - > >f 127G.S' e O.O t6F ~ F - - 21<44 rr r IS T ST.0-20" n-tv tO 235.5 0 012T ' ' E 24=46 e i*'18.i82.0 '2e?

  • ~ 5 10 -

226.5 0.O r t t b i ' 27x54 't v 15 r S S.5' e4! r IP r" rE '200.5 0.006T . ' ' ' ~ O'.OO74 r : k 30'x60 P ' V.

I6G C' 24: - ~ r e t2 I SS.0- ' 33xGG ift e le I $7.0.- 24'

  • r iE

!.&/.G O.0007' ' -

  • ?F 1F I'82.0 0.00G2'

.3G#72 tr tr 12 *I82.0 24> - 39x78 P P

17 5.0-

  • 24-
  • * IE E78 G O.0057

. f 3 0.0$ O.0071-L . 42x84 P r

I a 0.0 et rF S

t ! 45c_0 mr

1 8 5.5 l 24.?

  • - L 9

. [Sc;o & o'.OCGG -

- 4ScG tr * S T 6 2.G

Il 15 3 E 87.Q~ G.O O M i i

. _. - - --- - -. = . = V _ . . ca. ,.. ~- ,3 .

.,..

. s. o,...m.. m . . .. .

, - . . . ,,,,, ~. - TH E ' FIRST T#O sTIRRtlEt t=froid EACR surroRT ARE To BECf.OSED'TtC.U_ , r .a.

. . . . - = . . ' - - , - ' . _ _ _ _ _ _ _ _ _ _ _ _. ,' g "k ' 4 c.

'Q g .-g g8 ) _ _ _ _. _... _ _ _ _. _ _ _ _. _.

_

z_ _.: _ -. _. _ _. _ _ _ __ . . . .- _..,. .. _.. .... <,.. . , ,, ,,,, ',,. w.

-.- " ... .. . . .

%5';&' l;';.. k,. W W.

n.

Gibbs 8 Hill.Tnw, , 9.,.~,

  • ,,.

'.se . .., ~.. . ,. . , 4!M G,,, a

  • ~

~ k[. m -ec.* Mg.o..~%. . -. t .. . e.'.,.........T..z.. .. .

  1. .

p.,.euuc.us. co~st aucroas, u.

- . ... .

.. . 1,4 &.

Neam YO8HE .,. .., - ., % :<.w : - _-. s., 2.:.

.u...., :e.w ' n

- ~.an + : n.. ' . _,,, m.m. _. p,g-L.

ewe, *. ..s..p.

. ~ ~. -. ~. v,,r o;. ;~.:.u . m~ . ., ,. .~ ._.. ,.m.

... .. .._.

,..., ..., %. - 2, ; . . m rg).....ga.g. B. d.3.....E.. ' 8.1.d...3...G....' -..".. u 'o 'as "~*- --- "-- #*'" ' .m, , , .... ., w : .u..,


v -:: m..........

....... - .. ,,.c . v. .. ... ., - . . .... - .. . :. , . . .. . .. =. ... .. . -.,. ~..,..... . --. w.,,,,, ... s, cr . -- .- ... .,. _ .. ,.... ..s <w~...-2, . ...... .,s.

.. .,.. .. , a~.~,m....w.2..,.r.-.-,..-

,c. ;. -,

, fg u. 4,, . + -- -~c.

,s ....... , ...- c ,%f.. -w.~,. m.,m + .m . 7.,,, ., -, 7.~ .,_. + -. _ _..~.. . .., . ....,,;,,e,.~,.......m.e.,.. ,.,,.. ,y . , _ . . g ;,g. y.~ .q,,..- . w..o w 3.. w.3.,. ......_... .. .. .. u... .:,q,....<_,.v,.,. .. #. m..- -.c....y.

.y, 4..,, . ... . . . . . - . .. s.._. -. .... -. . .... - .. .,,,, .. ..:.. s...s.....m . . .... .....,.,, _e88'" d fhk h (. I t e ' .

"

  • O

'* '

, . . , .,... _.,._ _. . ..,-es..

  • ,..

,,,..=.4- . *+ s *J p.4%WrM.-*U ~ f. 6 ** *, h.y pd,*N -We? fg.e' * "<e.a ,? %.3,rar,3... '.,.geggs.6 4',. ,-..ae*, . ? *~ - A.h,s s. 9+' /l . gg'w.., arjes;.4 aw-e - v.e 4

.pg.j. f 3-

+ * - + * * ee r* r t..,

  • 3 - 86 1 * '.

. 4.l - A ** a ., .,.*<e,,e..s,., A .e e w 1.

. *, *. , .,s . .,, +-.= w..+....me..s.a # .. ,,., u w.v e e y_ m.=g.4. ' aae em.a. e wps i.e . g=& e,% eeve. ge-ae **sgr.

.wA, pe g-wi e.

. d. ..s .= u , y s...., s...eM @as4..e, w 4 py., g _ ,,Ae,., rap '3.

,a , '* * s A. As e.. .= a + p i. y,. s qts,ww * n y en. .a e ,. r., e, s -Ve soy n, J.,.e y,, -e...rt.= W ..s.

? t ;. *.,,, =. .C.M Qmg,'s:ll*,%.:.;. '*~.,,:.:~.,.,. .a~ .L*M.. Ja;;5 !.'L' TJ 'C.:.J.~7 T w s... %,'. n.4 :::G*. ' ;. L.r. & i, + . s.** e.w s.e.. ?ce e-e.

6.i, w.m pp.g;,ryd.j.4rge.t.u epeannesg,.p.,m peamW*e, Jg arh, *;* e.l0. < *4e dse,.'*.gy.ar.su./t.86,4.> 4.ap.eJm.t.'a-uV,,,., " .ng. 6ee* eses.n Ase.rt..e,rsm.e.w m.

^^ , ,,,, ...:=._.--- e . w. - ...-. r-- -.,,. . - * p . % ___.

_

  • n

. ...

. . .,. . . ,..,.. . m f

.>s.

a 3.

. . ;..... r ... ~. a.

.# R-. N (. .. l

. -

" ..-s,.-....,..

,. -;..- ..c cMdo k W RtM' ! f2' i!NV StA S' ' " L. Er=r=..c0 ! - -' - &-muccess a e.P ' T-W - eA * - CK-W MN p cfad $_~,*..El** M~s [.E E~i.i ).o[w..'.' '.'Z., h' 1',s , @*

. G a...a" *.. a* d ' p e e. eda . . m . .... .. _..... _ ',. .. .. . ,. -. . k q .. _..- ........ -.... r...._._.

.....~.a.

..e.. -. . e .. - _ . ..., .e >... * *

a 5 ..# . ., ..,-e .. ...-..sm,... e-e.

r .n.. -.c ..^.... w -'t... > e v.s%=,..anem - .. V, '..@ NY.5 IjQ 7

  • ' U rip.[4 *n

"ga*. 'b't. J '.#7 h.E.. * f G.*V'. * b *,k.7*";* .fh4 '{l n .,. [... /* 7 p' J JIl '(, a.f* '5.*.d.e .y .,.<....-..,..'s.- i .. , . ~. -~ _.

. ...c.

....,.. _. . G5.., .,,. ' -. 42.2 G. g..-,-.... h.

S.

.g .......i ... F.,s.a,,,.,,- y. cw..,.. . *.,p-_ ... > <r ,.,. -..,.-.. -

.g .u,.. [. .,.

g -. - . ... ... .-. ... - . .- . 3.g. . i.. z.

. ,.., M - *.4 g.. L.,.. , A s ,..%.%k8,... u 4.

.,.,..

  • r -+e. ist *

.,. . s.... eJ ~ te.s b . ,m... g i.* *** e.eA y ' f eP** **-,'g- ...%.

.. r * * * - f g y A"- 4 4 a*

A % "*-%* e g - $.h> -. a. 5 W (' # 5 2 d%' AT~.}i.

' ".:,n;TJ.J T.Ei

    • * *

, . t,,. > .e %.. a,. .. a .a.

m....... a.4... *. , ~ .===.- . . .. . N ' - s . ._...v.

g' _,.i",,,';,*4,,.*.#. p,. .a-g +-.: - .. g.

s. a.

. . .... g "

  • ,.

" *.

  • g"-

,

~ ', , M'5. ' **' * g.

-

. . ~, - - ' *,.,.. b,,,. w # ... s. '.. t A.. *.,** ; *g .. - ,, ., , .. _ . ....~.e , s u.. , .. . . .s

....m.. ... , . , . t m ..h.# . . . .~ ..,.

  • g

..o%.. ,- [ l*%"* ( '.",' $ [." d b C'***j".im's*** ps.J;*. .

  • .%-*
  • *

. -e - 'N**""',.*.*/w " $/* ;.*"" <. P. d', '.1 l '**k' P)d*; *Ws *V '<~ '% ' w'** . +. - ~ .. . 1' * - c y ' s , [--.,. -~,. rs .h***.",'...s, L . 9. ~ $..

.

,m.- ..., - [ '."*s.

  • /

[ '*7*9* g, $' E*/ .

  • ' g'...'. y

'# -" * * ". * ' " * h8 , L".6J i't * p.

g'gt '[. Er sP.'i"%.3P seN.I6, C , J., C, I.* p. I 1 * f d. # J 3r' *NM. ' [.s A.> ' -1 <*. .a 5.

p- .. * l.

. =- a gg - g g.s ..-,,.... ..7.. fv,

6 , ., . . .. _ .,. g . a g y i., ' ,e . . .c a . , _,. e e ,. _ ,. - _,. # . .v. 3. r. s. -.,..,,m-m..,, w , p.%,,+e, %.,.,,... r ~' - * >-~ *. * - - - ".: m, . . i .. p g y,. . ;, gj ge,. g,g. - , - ,.s., _.

, .s,,. . - . a 'e & . . m.

...-- -.. c.

. i . .. ..,...m..o,.- . ,. .. -. >,...,...., , .c.... ,. .- . - _.

, .. m .

,

- c v.

, . M1. b { q (/. 'e s-M -. . gg.j M 'a*$h.h.

, g

a.

lm~ a..... m.,. m .s_.

.. .... _r . .. , .. g /."',. ., ;. - s=. Lw-,. :.v '..-<*. 4 '.... - , .. s., . s ,, .... ~ . *~ .s u m 's

  • >

., e .x 4 . < ....-.s..y.

... u,. e ,T y . . _ . .- .... gz . r.m.o> .- 0Q%- . l2 . - >. a s. y.- . a , . .. +. - ([,../ >. :

;t r..

- < g -,... .. s _ po a,.....9 ot ' y - , ... -. . , , a,, . w.

z . .. u -

.24... ??.o' : ' ' GEE ' I.,*. 7 F 8'_' : - -I'*T. _ " Ln ;.. :#.& ' e.

, . . . .m.

. t . y....*. v. c...,.. s. e >... V.,........ _.

. ... ., . ... ...1 m..,,.. t.A.c<.gg t'vc < .x .; . og. s.... . v.

. s . w..,.... . J.

. gy.72.. <% e w .

v,.

p..~ s,o4g.g ge-y ..1 ..~

w m.p.s. . , c. *

-,

-,7 l.

. u , , , < .. . . <.. . - - , . . , .

  • & @ T *c Iff-T*

, d L

^ %.cr t.oS . ' , , ,. ~. . . .- , . . . . So '22,c bit' Mt h %,.- d..h , ' . , ... . . . , , , l g

St.

g.o 1.15s 46 $8% 150G . , . .. i , ss sr.o ins.

  • 9 T "c 17i.7 t

<*- - . .

-

- . . h.h w ' kh C Sh MG k -

.

.. ' . . ,%

' + %g. + S

s b ' Ma, ~ M.O l.6 ' b% Y c E@ ' , .. t , e

  • .

> . - ,, m ,. .... ., . , , < .'.. d'..v.?. e v . - .v .- '* /Zoon = o*. 0033,.(ef w S m c w G 12.)

- ,.- - - . e, (G 5Aser.s ows $3 - f

I . .. , .$f,

. , . . .-.. ...

gg. I

hY&iW@Ndb.M.( Y,'44'"~Nh.. Nii$FM4mm.m.s _., _ -Y, : -.;-. Gg .

_.

h k.. f,... "~ M N h '- m. s,;,w w. 4 ,.:.a m ~---.-. ne 9 k5.2P M f W .

- - . - +... V: -- -, r.:: My'% ' u.s.

c
.<,s

=:- '

  1. / *

Y - Q.% " v *. N/,;c -._ . w

  • ':r.;. -

M '*<.,*.~ y **,~ % m.., 2 '- M. a;. u p ...

  • O;.

. . % , .1Q.I,, 'mh. ~ i.h:$. s ;.,. - '

    • 'Y N [?"T L erbbe cHist.Inc-

%- '

- - L s.u

f.:J. ~ s. ~ ~ w w ~ ~ . .. J,. J ' ~ N'h ~~l.

' - ..: k MDeYomm . . ..;4 . Q~ [of8%* g.E* C 7 .S.e . t ^ ' ~~ E fmW

.e.....'. f.

' . k ii k %.* + .......T Cwd/Aseed sp..M.J..-e A A..,, ~.N.1 U... @...O.. %......... nos.nweds w n.... & % n Wv, . .-.%. ,.,. . ,. [ ' - .;,y.- .:,. ~.. - amu.ae...T..'. U I.... M..:....; M.."- D......-e.... .... . . . '..._....%"' . ..%. -a ,_e . _ [W.,. ;...,,,,. 4 %. m,.,. a., w;. . .% ,: ~ c .- - .r

  • -

. ~ - . ! .s Q ' y ? R J f.3 '.w; r* s.,g ;?. .

,p,m.. % h( .~..: .-q: -- . . .- w.

  • ' **w ~.,;,,,,~.;~, **~,= 0*M..Q ~'*,*m+- c ; Q M.. N eQ*'** *..[.h. k --- h
. m E gg- %
.gm- ;,...o.. c,e:.s 3

. -- _ _j - ( N ... . ' * Q m

.4

.- ~. . . .. m.

- .q,,- t '*6td [ Q g, w -'**.*Ln~.'." . s . . eww _mN,. 4. y w..=s.2Q '~.n +; ~ -.... 'h~*MQ,*,,- - .. .. e.

L .

- ~.. . - _. h %ug. ,z - c .. . '. , .. .~.,...w,r.,"~~',dC.. . ** . .,... % Y W W%e' g I b .% ""e , _ GCQ@A9f

  1. "d w

9h8' g.

, gg -. . . - N

.

2[ ~ 85e 4.4, ..,. CM St,.htb6 M D

  • ..

... '**( ~ N. gg, .,- v[f "%$D. %, ..$$tSMIC" C.CALOS ' .. :. ! ' - "* , ^' .

  1. =

'y.

% - -M. -_ -96 > ~ . . "q ~ ., R.:. ; n,.. / -

  • ..

f f**l$5, Y$$!'$vN.*CNU.7..,;<* O sk.Z ~ D, :ht A* r ['he* AI.._ I ?.* Uw ' %t m ~;

n..

..:

  • -w

.y v M q.e.u.w.

,

b ..

  1. s-h ' '

h j==:. p:%e.o.k;bw;r%y. A_g,..fs. % L ' 7, 3:ng,.. . 'e .. . Nan @%w - sg.

::~,;. g ~ f s-..-

, . .

. ~. ~,.

.~.

GDiu.4n ~.n*,.. e ~. -,m,.. -- .'** $ Mi W m.O2 .

- ~. - ~; e - , . m % ,

~. 7, ct +

".- . ... -

._ w. m.

. .g.....

.gg,,,e , - . ... _. aw..;;,.c. %. w. _.. , h, p', ....@._.. g x-w. .u, m s.e g.mw. % .~5 .,m e. m__. M i m._M( ff > . .- . I Ms.w.a.. m h..~ Wm = ,[[*," -

., %) - d

i ? ' bec & sE?bh Q M... '

. ,, i,' '. ]

  • T*.g g 7,,

L^ k MQW...;. mpw.

'. g.. 4.._.

N o E~ b, 5 $ t.'1 ,: .v.

. I 7'"f ps',.c, '

  • $$2.l.ht':p.;mg.g y q Q.4 g n,,W,;. w...,._&*R. f. Q.p~.g.

. . ' %yk - wr-. w.n ' s,s 4 . " .

... . $- . gn , - -.'.'..; * * * Q.. ::.. ' ' ; ;. y,,. 1,* _q.,... . . . - . .

  • ..,

n . ~.. . ., -

_

- , :.T * 'v s..:* * :~ w.c:.l.',L,,fg*,, ;, ' .

~;

- ...t,. . .r,;n _ - ', .. . - . '*""m%, __ i - .. -- ' l ~~ . ,_ -c _ .

.. ..

~ < + ' .. . b,..,..

.

~..-. / , -.. ... - .

  • "

er r % ..,, .. . - P m . Y . y .. . . & ,l ,... . -. ' ~ , 2..w.u,.... _ -, . . g. o.i.* *if*QQ e +., ~. . . ... A.w;; 'y Q. ;f;%N,g.-[-,.,. e .. ~~

Q Q v i.<* %_ .. _ _ w.

' i ;C'Z.f' f.. m.*pij*^ Q .. - m.m gg> Wwm, . - .

. . m~ ._.

..

- ,

.s,..

  • -

v.wr~., w,% f.

y -. .. ' _.,,. ... x,r 2. v , . . , ' * - .._ . ,, .~y

  • _

3, < - , & % nK >;

.6 ., .*

,,.y.

-

- '. ., - ~ - ".., ---

g, ~ - s u i ?,Y* - , . '...

'

  • .-..

.'4(. ..

,, . ~ m.e A, 1*?.p - ,3.c y , '* ~ - , ., .,.

  • .

, .. ' . - ^ " w.W.J..'7 * - ,, . -. ' .. '. _ . .

  • /, -
  • W',.

".{ - ',,. y ..s..... - .. .. - by ' .,

. - (, y .s[ %g .... "/ .- f . T .,,, - '. - ' ' * a.;._ .. ' , a , . .J.., x.m,.. %%. ~%' 3 ., '- . Q, ';. ; :t.

- , . ?. ; ..~~ r.' .W ~' * * N'+ 7)% ;- ' '.i' F - . L.f.t - ' ppfQ ...... .

'; . . - . , . h g%$.,- g?.,$h[$6.. . V.

. , .. % >i . r; ~ %y . - , . -.- . , . ,

. ..< .. . . . . .-.. < . - - - , ._ ..,. J.

- . L.

e.

%* - --- -- . - - - - . -- - - -- - - ~ - -

. _. _ _.... . .... _. . _. _. _ _ _ _ - _. . ..+.. w.- - . . . .. -.x.. .y . . . m.,. a.......,,.>.n.

. . - .,. x..,, .... , . .

..... n.. ~..., n...-.,~.....~..>.._s

... ~..4.

.. - a .. ~ -... w. m..w .. ~ n......... .. ~..,.,.,. - .

.e.. w....y .... ........,s.- ..-.r . ...s m.....,.; . ..m - q.. >..g ,. .. - r.

. ~.. w a..,.. ... ? n., ..v...... m..a w~.o....., m.m- . .-. ,.. ,u ~ .

.

-.- . r. . . - e..i, w. ~.. n.

. .ww r.. -.. e.

' n. e - . m., c.*.... ;. L ---.. s w ...: " ' '...3 ' m.p.....:.. . : ;Gibbs & Hi!fJne.

' E ".% Z.,.7 '..o..S... 2 . L . - . . n ' - ~ c.i.m..C M L. K M.. . sw. mms.otsmas.cowaucoas - - . ,.... New Yome.. . .... '.t n s.

C - , . ., ,., ., .. . - ,. _.

.... .. . .-.. ....... - .. o..., &. n.%..,u,. . . t... g.b. :....v. 4 ,.s. m,,.g g g %,, .. .- a . .. .. Cair d/Apped. BP.. ...WwM4 T.

sg. -. - M.~

. w.

.- g .-...-p,e r q .. -* , ' {...AL W Med M M... E M T... ... M. %... ..- M D W h** N -**************

..... m., ._ .. ...., u . _.,.. ,s... -.. - %.. s.. -.. ~ .u . e-a.~,+.~.--..,.-u w v,, . *.o w. 4-., e.~,. -~... w - -. . .--n ~....o.w.~,., . ,,.,. w..m.n.vg.

.n.

. ~ o y. n ve,w,,ww..m..ws & c.. -&wu... w.,w nrn,.4..emp.

. m.% p,'ig ,,. y : g ge p,.Sq 'qyyy9,;< w=... g.ge:.g 3,,.e4 g W. w-eg d.pIpc...

_..... <

t . ..a .a xa .- . .e . m.

' bl.4 ?C M.,M. M. l.p.M.O' N. W. d A Q.M.W.- u.p r 3 -S S.C 5 S %.....c.l.6,d, k *.C.*.t? W A..l W M...~!.$,.5,' t c ,.w..._...%.. .9..y th.

c.w... ~*.'- -, w b s.s w-h > '.*g: w.r. e~ , i.... .... :,. .,. a.4.s.

' a.re.+.-.+.,..a... .. t +=v A" ..,.,.. ~ ~. _,, e.. ~,,..., ~v.e v ;.x p,.- ,n.

+.m.~_m_ - we,:w+= r~-w.wwr.~ v .Yf. k..:'.6,L. W . .. ' ,m ,h, ~ . . ,s.

y .. .., . . .- ., --- a- .. . ~ .w r -- m. r, nJ mer.. n,%r.

. - cw?w

.n, c..m - . .. .. ..n.

. '.m,,.% s . .. .s., . ~. ~. -., ~., n., ....;.n , m,,.. ..w.r.v m.

......s + v. a ... .,........ w..,- e, m., ~ . .- . .. ,.,.. . . _ -... . .. . .

. y.--,.. ~. m

,. - . .... -..... u r.....f,,[.. vv.e 7 &g ( g g an g e M t M M h y.ye . ~ .g . ... s .. - .>.r.m N. A v a. _.,...x ... . .- a.,,~, .. - m.a... m.v=ev +e, ~ w e.a.

~ ~..,..s. ~ o - .. - . " .. ' y,M. ' ? ' QeECT.I OF Cobh""**.Q MC"- W@@.,.. , .... < *-, =: .. :..a.-.a.... _..., s.. ?..~....,._-....n..n..... '. . .6, 4.,.- y..<;M.. *.A. :. <,4:Q.-@p @*r -pt. ;"*g'47Jpq. > @;4.. *1gT.gp> .-.._...,.....a....... .m s.. ..s.

-.,-.. m,. _. :. :,.. L ,. . >. n... . -,., . . .. .e....- .- . ,- o .. .,. - -.. .~ .. .s ,. m .. -Qc.

. .

~....

. o. w:a w.s . . - n,. cu . 1.L-pin.. v.

+. w... . 2.u.w.S rf. W" v.9.< 3aA.h.rc.p+.pyt.r;.&,. w. m m.:. e m, % W w m+ m. e m r.M.f.s,. +. M.s, &..... m.&. m M s.e.f% y &.. n , -. n; :,@ ..,. . - t-fw:u e A.-. ,w *'v. vy

. ge r.t,* < . m., - 3 ~ . W.. w,...m..q .o ,-;.,,,

,. .v.. A. css.

n...q.h w wn.. ..3 . .w m+%qpnweyty;nerva;.m .s.u: ::w.4 g-wyg,w. g.w4.-v..w .=. hm..,. A:u r.n. L.u. :.=h.c. ~... i.=.~a:..r . .. ,,, l. c-m.p . .. ~, w? :-*..s w . w -. ~- . . -. - 4... r.

c."

m,,.. . .:.u

-.c +. v

,- . ~..... r ,e m..

1. n.~e.~ ~ s ~ w..- em a. % -.., _

- - - - + ~ - ..- w *.voeu.n . m _. . . ..w-... .> ~ ~ ~ w u.

. . , . .- ... . . .,. , ~ - r ,, .. .. ,. ~.. .... .n.

,.. ~,.. w e _ -- _ y= _ . _ -. _._ :. y-

-.

. .r---- .. .__ , - 7.,,O. ...t:.h+,M.c F (.C;:!!4'd.MW.Wr.dPffM.ti.hW.'.*.Mf6.5,YET&/EMM-M.Wcid43ddsh . . . . =, _ _- =.- -........

  1. .,-

m..... f'** f _ _. - m w

,.x e. ___,=.,..e. e. ~ ~. y. .a..,....... . ._1., ,,,.. s..m_ - ~. . ., t . - . ...... .. a a r. w..w m g.c a,,e g + 3,., m.s.,7. w,.e. y m e g.+. p g. w.,,, m.v.- e..,n. ' Jc.e t. p. A g y m...t.w, v.+.;,.e. 5,9j g .eprn M.a;,cg# w f.... ,a,a., W,. w.b., ".y w 1_ . . . .,, .n . y..y..3 g.q.. ' > .a ..w <.. s .. .. w 4... a.

.. 3.

i.

.c . .% 4.e. 7 4., m2 ..v.y e..,%..,w.# .".**v.'. y*.,ww. '. M .%.'* ws ym.

..~- .c q.4@v.

~v-

..

g.. - r . -*, ~ LE

- t.

. . .%4% g A .n~. - w,w.. . a.a..e w w e. + s.~. t.

, . .sz >.. . .s

,

..~....t 1 ' g..a,,., a..,..a. 2.s. >...x. : ~,.,.,~. .,.. 1w 1...r.-. s -

  • s % v..v. > ~. ~~m. w A.. ~4 ip.%...

< s w.

,,.~. .. . ..... .2:.k y.. .n bl..& m A....+.3-n.ya w M e*, y.'.:, e L y ~*W v w Y.*:w.: 9.g ". + %.d n y.r%v .... A. n:.,, r . . v.:.: , . < .,. . v 4y e.

e {,; y,.{._* ayo + *=w.e v.* *; ,.g * O *. *Jm8%, - s ., ,* Q, W,Q g.'g.k.b * p @p { n ;.a. hw. ;a eN.

-~ t,W-Q.7l.v 4.?.L*, :ig * .7.".w,Q.,Qg-eyt y y w (*g y * ',l Q .,,g g-34=.4 @ -.*t.any ' pr. -s;*rgrv.^:n.w':.'"e-:W.hsw oh, won: i ..

., 4; ~m.... = e,sp.xor....s. e O m.. e .m,.,.. w w., . o , e.3 gy.g ,# ..o..,.,4.,m, a,s .. - .. >

w w. w.

+ ... . (A ' he. 4 ..p.

,.,4 p.%.pg 4g.

e9.

.... ..p.

. .. 4m ,4 , - j q..,.., m f;,. *' OW9 st: m* LK yW * ~ -

m .e, n.ss;&yu.

m vr t :-. . ,+..a, gr ..w .w. m i. :: s~ m..Lu,.m sw. p. a:v:.:.i.,.4.'.4.u;r,.u w,:Q.;am.

. s. .p _ __ ___ ___ gg.,..... .- w..,.m gw> r :,y... '.p.

... y.

.. . .. .. - ~... e.3. e .. . -.. ..- +c... e- ., =. _ _ _ _ ,,.-s~~. ... - -~~ .ve ~- ~ ~ . t.. w. pre.w , gf.Pe 6, 1 rW<.W W +-@,,a 4. W,,a* ? =* *tw=*f"* )

, i.. x.df, Ah,t..p u.. o, _, , . w.~,. .%.% 4 M. @ b W -iv 6. Q.nr M W.:.;,t.w n.Ai p,e,.,. c.

'a: m.fA.s.

. .t. w. . .% . .., .....w.~. %..., s.. < . e.,e e . .~..~.as.,....o.: ,,. v-a.. .

....e,..- _.,., w - a. , ..., ir f.

w. t,.,,,f... ..,.-.m . ...,...- .w ,. . . ,. w.

. a - >..~:.. -,. +.:.. ..e a w.. ..j - %

s +

k. - w * ~(r2W.

. m. p".

- - . u ". +.. e. ; s.,., : ?" c %.m 4 .93 e.p).y.37 n A:

.*. v. * ~. ' y y

' "" .. s. r p y..V.,q ,. .

.-

-

.g ~ a. - - ,. . _, 6. a w w a a .r.. ... b. Q,.. ; a, j ' =~a. 4.nr.ygpu.m..eQ4 p.ye;. pag. ~_ ...,.w., 3,N g.,., S@. >. %.

g- , . 43 & S. 1 - 4v,c.uk

4..,p.s g#%

.e . , ... -, g.

m,, a,, i. %.. , ~.g e

,.4

'g q;'" %2.' f. (Nh. 3. I Es.' *" h L ' '.4 % W+. NO8".**- , . . .U O&

  • .

..i. % .4.- - + g w. M,--. g w. Q,#. a +- o, %, Q '. ..e.. w.f. r, p- .v. ..n g a 4 +. r,.. ~.,a n - - ,.. . -.... is,.o - .. . u

,,. f,. c. g v * .g ,

  • -

. M& y,sb y t &,..ceMr 4. ('.;Q Jt;4; M.n +...y;; % n W.h s.

.,.m.

.+*,. ~ y ; .., ;,t s p %. ;.- d.c @ f f.% g.,.2 e, ... .f t >. ~. .. y:3..c. -.,,a,.,w 4.

. m.

P..u.. r~~.....1,. . .,<*,.,. .._.,. - - ,, . .,..... . .- ... L.a c ' ~.J, _. -w.,,.. y ..., O.C . ~.

.s.

w
..v..'-

. m a.. ~ . L.

' , ..-t y. ,- . ~,.m..n.~, .. V., :.....Z, ~.. ~ ,w + - - ~.n ~ m..h.. - . ... . .w.~- -+s .s M.,., _. - .. w-.,4 ; w n. mm. + , -- -- ...ny: . . 4.I e d.k." Ye9 k'E 'NA?.TN'$n.Q7.'UQO C '

    • tej-i,.',"* * '.l*?. 38,.m *4.;%hr h+M%.{.b"N...:*/ 9.' '.. D. n3 D WM.$@

q.. .i,.

'A - L ,.4 w:., y m,. ,,. . - y m.. .- e, w.. .. v p.

. c .p-O.'t. - . -

' . w. ~.. : ,L ,e ? w -,. .,. . ,,. .y . . s -- - ,4r a . . - , . . . L.

- . ..~..t.

......- , .,. ..w,. >... . ,cs , - . ... OL .i... ,c J...e , g..,. . , ..s ; .g.. - ..,, v . a., .. u w., ,. . ~ < -. a n '. A.. , - ' -m .. .y. n.

.. n.

.< < r .~ . . ' <. , c..I r -.. s W ? .. -, ? ,, .,,. ;.,.:.,-- , s ,A.

.s ,..,4-c.

. ,. .- , *.. , - < . . .,.. ' < r - , u.,- .. ,.

. s.

+ . a ;.- - .. . , p,-2.

- , ...4 . . .s-, s. .r.. , % - - - - -... . . -. .a-.+.- - /" < Ney . ~ . u 30. sh 4cp GQ) - r ' '.. r.

3o - T.o .. . .- r.

..,. e, _.

.m

q ... ~d.

PrsupueNcy W. tc: ' ". . ,n 3... . ... . v . - . . . .. , .,. .., .- +., - %. . s 3, - y.

.._ b.j;. .A* ,

_. ._, ,, .., , n, 2 w

a , . . - - . . , . . ~. - -- .s e < ~ s.

, -.. _- , . . . .. .. a s . - . .

... . ... os* .. ,,. , 4.,.

  • ,

, . ... .... - . -..,., . , .. .... - F - p.w _

--

~

-.:..y 0, . . . . .-- _, v. ' .g.

- . . . .. . . . ..c. r + , m s 6 * i _. w -

, + . *. ,.,- - .,sA - a . y ..

  • < *;

, > , ' $ g . ">.,.^y '. '.. , - =,. ' v.

.~ , - . . >... .. .g ... s .-*.*p

4. -

, 6-4' . i ..3 _,_

_.. --- - -. , , .s'.. - .. - s , . .- '* ' .- l , -

  • .

t

, L gissg g gifr:ynei [ , .yh T ,,,,,;.% gte g r 4.F.. c LB.g~r.35 ;. < ~ u.

' .f... . y o... ...4......... .-s.o s-s.cos=crom . a .. - - ~ ,. w... c.,._c...w. m_ om.. ..... . - c a nu m u~an..u...,.,.o. n. . .u, z.

... .. , ....~ ~ e .a ..,.v:..-:.-. . ~.- .... - - .. ..r . cwuw.wr........ ; -

. .. ... .. El BI - .. u.a m G m.a...A..,L.,G.fg-.a..g......n.y..... s; r.p6. k.ri.G...,J M.. ' '. % ' .x. :. ~. - .. -, .,,s .,.. ,.., n .. - .u~.,......a........... . . ....... ~.. y.

. ... . . ...,,.:. e3 . ..7.s p.. . ....,,s-4.. ... , . .: - $ -, .. .. ~. . . .... . ~.~.~',c..ag:,. ,. -' & . . v e

.

.:... ..,..i.

4, .. .[,. ,,. . ,. ... .4 %

$. ,. , hf $$ Y . . . -. _ , - .w. . *.,.a .

  • .

~ p-t . ..... -... ...a .. '. u e.n.2 -- .

. .. . - . a .

I . ... ... ', ' ... 's,,1.

....t.

. s.

m.

)ff CIE. D,d . $. l IIP.. - ** L, s i,i.e ;gf.*'.'.m.. M "" a ....;-ea.... v...-r,*i.j .... . , .* CSP.. g m -,. - --..... - _._.3.._ .- ._......,r ., < . <,,. , sy.

.-.....vs - ....... _ , .*r -.7......._..,...~.,._1..esv . ~..,... . _-,..r.._.. ... ,.,,..., . . ~....,,. . . }7 ch e gamer,tG,..... .. x 4.

., ~..,.. . c.,; . y.w .s.e... . ..a .. - . ~..... .- . . . 9.'.... a . SygML . e.v, y.z.4 ::c L., . .. fanR,. .-..m.,,.. ... .. . .. ..z.n.w., v.,~. .:..... .e .~. - -, n.

. - :.,. n.

- ww ..e - -:.__.__.

. x -, u.

a ..,.n . u.n m; .. d..f L'T[z.% w.TAY, ~.

  • e M 9 >..~.. w wMG. e-

-- y.- ~ m.,... .

. , .nfernen [. k A es .s s=4 ..p.ae ne* .M.- ., a .. s . w.

. <. w.a .A e e. . . ~ a

, 1 s t . ,. ., . , .. ..u .a.

. .,... . ,.. ..... .,...,,. ..:. n.s.... . a.. . ~. .,..: . ...... ... - i,~,

- ,,.. .a.~. . .~.~,..... . . ...t.... ~....... . . .

. t c,%g.

7.2.
: y,.- q e v?...b. am.;.u. w i, p; m,.,.n.; e ;.n = m..:.:g....:

J. wy r... . .. . ... . . .- er: - a.

~. > , , , . c... a . - .,. =, . ..... - ....m . % z.

. . .. . - ~ e.: 1 *t J q.~ -&... ~.,,. A-t * s.2:

  • ga.,

...M. ->:r.

.. m.

...~s m,, ,'., a..::. 9c 7. e ', m Z.,: :-% v. ~:n,]. ~ c n.:l~;y. Y L .

. T. ~. r -s A v g . .. . > 2.r-m;g,.m ',-. r. ~ %..:~.h.u:4.:. s; . ,..

.. m.w ..

~..- ~ - . .

. .Q, . ,w_,,,.g.g ;t. 3 fp p,y y Q .....~_.~.._~..'.,.,a.

  • , %..

p... P q .m... %

  • .a

.... . .<yy y.

.

, g:s.

., 3.y. ..,,.... x.. . s ,.. .._n . =,.~..- _.. _ _..... . . . . .. _ _ _ . .. ...~. . - ~. .. ~.. ...... -... . .. - .. . ,.m._~,..~..-__~,g.,,.... .. ......... .~, . ... . u.tryg-. . _. m _._ .. . . ..., . . _ ... ~,, -.. - ~., - ... _. ..... _. _.. _ _ ... to n c o.

_ 4.- .. ........ . , . ,....m..n.... _ ... -.. ~. ~.._~....,m m. . ~,..... . - . . ..- . . . ~. , .,... . - -..- .. s... , .x . _..-...=.,:.-

.;...

.-.-p.5 W.p. = _ ., = ... . .. . . . . .e m ... ..n.,. m. w v.,v. w m,..e,v. m m.. m;carwxw.:,w.sn:. p y~.; m,;w. ;v.w,.,. m,.m.y:.er..~ s.

..

...... . .. -. a.y,. ;..-, v...,e... s... ...~... ~. . ..,.... =.. s.,~..e..,r._..... . . , ..s .... . ., - .m -.. .,. _ .. t t.;.. .., m_ . w..., ~,......... . ~,,- 7a. rc. ~ g. s _ g.,3,n. 9,, j. ,w, < . .. v.

. . . .s.

., 7.. . 9 y.7.s . , - ; -.' , w.. s,..s, m,. .. :...x Q. {. :q.. _ u..,,. v-s ~.; :. p.- + - ..

.

..b

.s . .,n e,. y..m :. e. -;. -

  • s.

. Na p. - 2- . . ,.3

  • *.

.. y =..p. r w. s. ..s.

... .' '.,._."'z,.'.

. .

. - .. .~ .wr ,y. v ....:,. 's-1;.y s.3.

) % s.. ....e.

-..,...... t..'m..,d,..-(r ;.: ' N.

g ' .....,~..'...>:,.'..~...: :.~. %. ..m+....._......, .:*.. t.. .; ,, . ~ _. %_ y,.... e.;w., - 7. : <g a.~,3..,. 4 .s . .. . ,... .~. a.x,m..- gs,, .... .... .:. .c m.... . wn...:a.m.~n npm.w.v.,n .- - -....u.,.m.,,-~.. .. g,. . e ...c.. . ..... . e . v . .. 3 4., u,,...: :. u.: a z. w.a. +. ~ 2.,. .. . .. =.....;. u.

, a... . g . y>>; &...,. ... . - ~W- . 3. t * p.

.,.- a. yy. w ., ,,.2 p,9 . - . o, g _, ... ...... .. g.: :. ;d.:...:.a.~...,.w.-.u.. a....w.w . p.;. u n .e.. - w.-,. 8 a: lW.-yg p.p.p.s:..t >~i.

p. r:.. 3.. J.r.,%.,,.k, O..a*3,.giy O. J. E - p.A.m.p, j,M- -,. r... J .. ,% ,.# Y g.,

. w. 0.T. A - - %. - - , h.:4 ....... s.,f.v.

.. 4.s. -

. - v.

. . .- ... y ..,., ... ~ . _..... . ..,,,.. -...a . . - , , 5_., c r. .... _.

. . ..., .. ,. . , .- -.. 44'n . -

. - . - . s . . .y . . s.,.9p...c.... 'J sb. H:N, 0.~.W,- .. ... V4., S t 6'T.f.: r.% (_ - c .....c .. .: . ,.s .;.. , -. .... .. _ - " ., ~ t4Cr#E.af 71 J.Z J.' i M,11 '. ras. Ceb Es * STAMOAADE.... .. . , - .e ' .. g ' 3 ' g.. . ~ . , , ' - ~

.

, - !SPECWICAMOMJ NTETHCOSt 'ht,M W

  • *

- ' rf"D.r_ C~.E % t3 6 ' . .. - ' ' . ,. . .., -.,.., _a.

,as m t%fic1ano oEsto., - . .. .... - _ .. . ... -m - .. ,., ~ ~ a.

... . h . . .. . ~ .f d C ( f. d ;' M 7.:.$ d' %~.C M

    • ' d ecaccrAnre g

. 9.f..'.t." 7tyE-V - r c- - - - 39^ yrm-sEcriosu 3 2. 4 /1 ' _.

y G.sf : J.'t 7-4 -7 'n p c A g' L,' ' ' i - - r% 3CM.y. F.7 3-s = reW".f. . .... e. ' a . . .. . . ... .. bG - - U L. ' Z.. _... .. . . ' ' ' 2Gmpc2cG AG#1~ . M ...,. . ~., .,. - ... . ., . ... s

- s.ll A a t2.Q et. a W_.

,, .e _.,. T ?.'W, . .,. . ba17.'".

. 'tk 7- $l - .. ,~ .. > 9-9-e, I 7.x d, &qh - p o.ccI. O.ca % -

nN _, - b di n_. cz.tp.

- .... 1 ' ' .:. . ..... . , , . ,s.

. -

h W ... % , p , E - . . . . ... ' ' %. J.

,. S.

,- *. k+ ,

$ S" $ .. - . . .. . . ' .,. "

g . . . , _ _ .,... -.~ : . ~. - ,,, .t

._-_ _ _

c.

. , , . ....v... .. .. n.

... -. ,...... ~. . , . ..... . 4. p.- o., . . . -. -.,, ,... _..~.. , w. ,e, .../ ,w . _.

... ., ..dr.-6.,e.c a. ,,.....,......aw..p.

,...n..*A.

  • .

w.

.,.. w. -. .. ...p r w$... . -, .. .. . .

  • ~

-.r

.

.+ . . - ~ . K.. :[.. o.j...j.4. 7.4.... '

y Gibbe SHillinc:.

' ' f, * ru e %%-).qLG-. , .s W.- W 1.. .: - - ENGNEERS DESIGNERS CONSTRUCTORS c.- ,ia'. - -. ' ' ~u - m.~_ ....... . : - . +.v... u.w.. . ......- , . a.rr- .. . . , . . , ~-., ... . . ,. m,. _ - ~ z..gs.g.ga..g; ..- n ,. ww. gas.... ma.g. um.m.. .,. .=, .- w .~. . .. .i ...p..c. /.n...D... A.....[.7..a. 7... cmm.m. n. &v... ,,...D a u........:............ _ . .- - . - - . .. ~...,. ~. ,... ~., - ..... _...,.. _.. .. ,,. . .,., - -. m.

.... s ...... . _ ._ m..n.

. . . ...-. . ~. - . . .. . ....~m..,,.....-. .. REE,mCca l CS..,.SA 6 - t ot C.. .,_ . . - - _... -.. -. _. _. ... .- , ~ ~. - + F.

- + . .....e_...... ...... .. ~4.w.. s u -. 3. T.RM.. a.F.) e.,a-gg.f... ... 3&.... _.,a h + >.&.

  • _..

- .. ... R... :' ' ' . V

z Y!. 1, D.G,.r.i x. 6;l M. +

- . . , .. , , g,...~. ,. ~..m,.7.. -. ...m... , , a v.;. - #. n., m .,, .r.~... m w... :,,. .. - . .- ~. ~..... yw.

. n...;.,, e. - .a .. ..... , . a 2 y (m,. /... _ . . - . . .._..., _..._.._.. .m.

. .. . _. . . . i .,, ... 7,..~, . ...--.m ..~.- . . -.. - :.w,.. ... . g,,w g. ~.. ...,m - ~. gy ,

+ ~. ~.w ~- ..~ ,%..w.- 4.. Q.r.. ~.-y4,.. y.

-.. ... y yf. q.. , ..,,.s ~.. , . . . @,-.cg C C g -f, M.) C [ Q,= cz. $ 7 [yJ.k,r ... r, b.

. . . n-M. .; _... ~ '., '. - - . ... . ,y;s.: n.,.m [.x v.

..y....+ ...,. .a.g.w/'.; p..g7 s ry s M W~:. (.m.n--P.w3.., m. a. J ' vi

.y c.m

. :. g... ~> ~ ~ w n y.w.

4 + aa. _ n c . c. - '.y .m v . g.~ .c 2 s u , _,.. - -rg y w: 4t yt-.*-;<%, n q n.

.r w3- +.wp 7 -' Q :. .u.' m lH;,.s.y+ . .. ~.

.a s.

yyjQ.Q.lfi:f...h,. {l> $ f &,.?. O f. & &.,. h.. l{:ft...-.,.& @ S (70 $, & &... &.. "Q } h.. .,

~ _. ........s~.... .,,..4-.,%e.,e..~...%u o m.~a i,. e.....u.-....c- ._ ...,. -,. ... .. .... ..a-...%, . .. . u..- .w %. , ,.4..s ...,.,.,., . ...s.,.. . . -. -. e -- . . .~r.

... ..,o .....vr-.. .,, c..,.,.. .- .. ~.,., - _.

.-. .u....s.

..v ,.p..< ,. n.

. o 4,.. .i. .. . .. . .~ .s,,,....,.m.~...., ... ..~#.%.- .#- '- $_MCh.., %~.-[$*Mt?bgh,* Q N.M,TApt hh O\\k'.T M

    • ,"

'u-o u .- . .. ..- . -,... .. -. ..,- -- - ~. - - - - LM1 N ld.A/T4 .- . , - f- .

,,, ,'y'. '.. ' ' ~ ~ ',, , .. . tGub. ! Csent.burnMcGed h" %eL~ '

? 2 cuWvtcp - . .. . .% .D C -.Db - O ..l . '. , @ ( a ../*,... .' . ... s . ' . * ~ .,. o..r , e',.' " ~ *- . &. W,-.,6....,; m? '.,...*...... ~, o. -. w.e..,,w..% _.. ., . _.. ... y.,.4,m.. ;,.. L e.~.. c,...' 1,'. :~,..-~,,.a.,..,., ...,.,r..u<y.. .- +v .:. 7.,,,.

.

.. % . ...... *. <

. .3. 4,. e*. *.a.-. w,,m' 4 r-**.. .% .. .. .%...e - ,, $... y' 4.g. a ^ l' N.s.o p.,,,.{.,..., %,e..,- u.,4,y.. ~. % e.m; . < .. , m. _ %.g,,-ks. m,., e.

,., *,,'..e.a+.... .. % y . -, 4, ..., ...,9..* e ..s.9,.. - . - -. . . *-.. i 'y.

- . ',. . . .8...-wm,,', . ,8 . 3.,' "f 4.,g, y' t y.. *.. .%,'..g.

. - r...... e c '. m.

,... g.x..fg,,t,,.... '

> , .. . -.,.. s.

- -.,. . . i .... .. -.. . I b,".a *M E, .. - a.. . -+. c,ar'J * g.1 %,.e. 4A %"[tg'd'7 M" '%M,d".s.",.p dp*, M '. 6.~ 9 ".' f ax.%.Y.' s #D * ** . p A44, b S.. * a.

. . ** U % ..*.*I.4 De * * . ags.

s . e j.. ,.3p,M v 2....... ' - k".h*Ib,s88 I . t . ..

/4y y$&

s..%.

p ,.6, r 4,.... , .- .p e , . -. ,,. w.3 g y., j ..** , Ie ,. M.4,.....%e%.... -.,===.. =.,. . 's -

g N, 4e ..w.,-. ,.. -.,..,.., -.s. w.. . r, .. l

... ...... \\ een,pe.f es se v ye-..e %. ,.J.wws e sk.te f eemew gus A= (nr 'N' s.sd g - e.(3 VO R.. :.) h ( .>.4..$. 4.' M' ' ' '.. ?...? - e r., . s. 4.+ - . ~, + .e~ e .p.,qo w.af,_ ny ' bC.T l O N ~.. ' - . - - ,v . g g...a.-.*

" J e..,,.,. . .. . - . - . ,, -.. %..m p.. . u.a- -a,g,.,..., .. M-** e.a p h . .i.,-, .,g ,g ,, , .($ ge .egp m.=. -.. a.....=w,. . w. y ...e,'.- ,-- ..* . - > . r... ... < -. v

w.a, O,e.

. >......3 y . -. - , -

. w.,ta .

.5 ., s,.A v.

w +. x"p %.(q.W2..p.g.~w w.

..s==*s x.. % %.w - u - .. .m a m c v... - -.1 -.-o W.n.,y5 ~ q w/ 'e.5 e.g", . . + aw ...e,<.e <a. - .m , _ i.. 3 - e 3.

r >* ,. , .n.

l

  • M

~

4f.4,. %... a *,.e..'+

q,., ap..a,..., t, . s.

, . - . 4 t - ,, . - % -, *. .m'

  • 3.,a,-_..%-

.. ., e e . .e-.-.. n.. a . . '.4 M..@ 4 p- ' T,g*. .. 97 M '. 6..i.* be,pi.

p %.5p S'h, % gaps.p&.iiggdb'

  • Sb -e.M X. @.,g y,
  • . qs
  • .e % 9'W

-..,4h

    • ".*.=h

" sM%ds.

'M dh4 W* e s.a.

9... w-.y., - g ... -, a. 7 (. . . . ~ .. . ..- .. .. - .y(,, j.. . ' - .h

  1. .

--C'.y'

" - ?. .. y..; ; 'c .,. _.

4 (.4 A e .4 .,, , ,y,s.w.w 42, r, - rs.,: -j... ....,. ; .. . *,,g... s... . .... -. .., < . . m , . , . % ..., . .., m~.',, ' ,g.. ,.. -. '.,.,.., e...e.e.,s.....**.. e.

.. .. ', 4,' J . .,. + *. -. g -. . ... =, .. .,,a... .. e s. a.,. ... ~.... .s.

. _.. . .Ng.. ap,

.b ^3k

N u.b.%.aC h"$ .

    • ae.4e+ t "y"-=N.

.

  • '

$k .n.

44'- J% ** u. **"gh * f*.c.. *e, s Pe. T"'in '* I f va". 8, g

  1. .8

. '. 3 c. g,g"l.A.W.\\. g* .M.." ,i.'.,,.4 . arj f ' $8 -, .*

,. ** 9'D"a* [: *. *8-J'".O%r f *% As '4s'.4,'" ' t 4."d 2 J

8 yj . g ). - stc ' p . s p - _g a . ~..:.n,.,u':. g m s m ":,.s;.c. n.~. .,.s w w w s m w.s 6.m.63 4., - - w w.& , - w c; .. . . ; v... i,:...... .~.,-9 s >. . . .. n.

=

.s ... W.,*+., .* ,.),,. s a

y pt- . " . .k %

T ' 'o . ey , , 3.- y* y . g , S . I e _ 4.

. =*

  • -

,. '

y -

. . . _. .. . - , .,.., _.~; _ ! s , .,,. .s .,, ,.. .. .. ,. ,,.... ...-

  1. .

,, .J -

.,

. a = e p '". . ,

t + s e e O - . . y b

9 . d* . . s . ) = . f t . , e %

    • '*

b S

,

., .) . . a.. . .-

  • -..

'*

% , I. . g 6.

.. , e + % f. g = } - h'

m c.n. 9 &.l9.'.C.

': L, L... M7..7!t... Gibbe 8 Hill. inc.

yjg, <==r 5. msau. =~5=as - .e E. oi..Sa4

. c.c,...6.(....... - New YO8est h C & H Job No. T. 4 7 3..b .. ..... Chk*d/Apped. By.g.... us.qu..s.t.../.4.,c..... &. 4-3, Cn..........S.'.L..e..b. e.%...S. t G..r.J Ej..M'- G.. i............l.. . .<. o..n.

.m - ~ ; ......... .

. . . &.*v1 ?. A-te el f.

_ $ O.c o'b'b scc 2. n rQ s 0 07 Ofl

- . , at 2.

  • 7 6 $ % %. (.o.90 Ch

' - - - T CoM cW pop, ggh-pl,. . , v.oueW < 2./fE a./C - s.

i l . ' s t '2'7 p : O.b 6> l & -lQ.

. ., - ~ . r10e44.es <~. .- .. IfD ' l*b 4 0 8 1 5 (J 5' .a. s 5 6 N l+/[3,g " ' ' . s , oc . 4 s. c. w 0,4,)q_ n 1. - e +i. ~ ~ ~ . . - -. n._ . ., s - a w.,...~.. . .. -~ .. ~ -.... n.:. T.12 0 4 3 b' - t >. [n.. - . - _.. ... .. _... _,.... $. . ' rt$qz S (q. :.66 4 19 (D- & = O.V44-b = ia2W< -h - .t,. - . - . . . ~- - . . . ~ '

  • ~f 0 [5 t?>

{C 9b f, QS & . , .

g e, f.pa.

.

  • . / -.

. *, - - A

  • .=.7

> .94 . g . .T- . .8 .9 (Y. $.$$.. . .h.

. g,,. '...... y., g . .,... .,.. -.& :.... - ,g - .. . .. . s .. ~., '.. -..Y Z , l' ' Y $lh & $$t90 0 ~ [ h . -

  • O

. . -. ~. - , .... -. , % =... a.- ' ' N' ed $ gd T. O f C W R. G o4 G A tje4 f % I e t b 7 a n X_...,:.. ". ' '. ~. . ' ' ' . . ~. _ . _, ,. ;y 9 3.: y ~ ,_L - _ ~. Qq,, -. >.-. . -- - - -

m v.

. ,

v, .w... = w,v.. y x. a.~ 7..- :. . . v,

a.

. .., ., ' ' ' [ '

OO % ' ; , %,l . ' g , . .,, , - - - a - n g, m . .- p//l1}l - .W %. L :- 'LG74515' W g.

e.g,t,g,"l* .,gr5*'/. ~ / / . / . /...p..'.w.--. - 12_a n...,. .-. . ., ,

,D. Q.) r.,. '...,. . 'e, ' * W.: * . r \\ . ' ~ .

... e.

.w.-.. .;.- ~~, y%. . ] <*f ', 0.s [ s t ,,n .,i - e z ..

. u . , ..q,., }. tyg* ]- %u_.

..A Qw ....., T G , _. , ...,. m.

.% "

  • ;J';; l c:. i $ $h*

. ........ .a. e .t .... . . ..,. ~ r. 4 811 [,I~ 7 ~":D 'T * *.[ 'f.h5\\..he '~ *N N " ,:_' " ' ' ' "

Q ',

- ~ *,

  • .

., . . =.. . ' ' Y),g.

o.3 f 6a t h, g l f g .. a~ . ,.. , . y u, e n,,.2., s.,S . ~.. + . - .~ , , ~. - U ... p,;.1 - J9, 00.h.q\\'100 b..... ' "_ Yst c .,. .. ... y -. / - s .. .~ , _

  • 9

. * - p p 4- -4.$ %** e S. S Y'*,p=*4[.>*.9' 4'E. [.- wm.ip-'

  • 'e/.*W

% " e,.**eb*

  1. '

) ,,,,,

_ $ Q.

s, ,, n. ~., - . .

- .., , ,, _ ,,. . c.sg.m.,, . . , -~- .. + ..s .. s ;. y s

.

--. : ,. s -

  • .<-.

I - - S~ ., . . e, s.

) Q Ql r..

  1. I~ r

' . .... .t" ~... -. .- - -. , . ~.. . - . .. . ~ . .... -. . , ..S . O e .==se.

.. a,. O.

N -- t ' Gibbs S HiH,1nc.

O m ec~s.'. W = lR W ^ a m p.. &.:. @.'7l .. ~ -,. . yy

y .. .. - , ; , '. e.,.- A.:------- _ ,,,,,,,. . . . m . as.u.m..@.9A... - - ' r a m.,--------- n..d..a. s..s..w....... k... m.....---- St %.321.?d. g, gg oZ.(.,.. -4..Ti.ll-- --.. ~.... , . .. - .. . . . 4,

    • ,

g

. - ,, , .,. - v] - . ' f-4 .. .

i i ~ .a 'l

l* c TA , A1{ &, f,.

  • -

d-P. -, ' .~ ?J~ ' . , e . , " ar] L/ " ,1 e , .~..,,t . ne-er p .. g . l ., - .. .,,.... .,

. - ..+m.. o ,.y , sJ , - ..,,,.~.4&

.

. .

  • . -

~g " $.. . r%*

,

, ^ $fMsr. d.D*8st h.g,'I O _ ,. f . E.,. * . - ,.c.. .

,,. -

. V.*. ,.< .

. .. *, ,,,,, , . * N,. . J., M =.= _=$ ** ~ '. . - ._ -. ,, ,.,.,, __ . , - w:, ;;,g.., mp.~i y n ~~. - .~. :

  • ;M, i !k k:%c.

...f 2, l 2.b.

~ i,.n.

.. M r- .... w.. ' M . . ::L . t**.b c

  • ?

%ra .FI*f,** .-. % y O. S..W & S *' W *'% R 2tch, M'W..W2: % *&*M kfkW-M &-t'W>~.s W . ' g. - :.,.,, _,;. g -g -- > - -. P. ' % T** * *f'*e".~5 * C

  • %

. -~J~ ,n 4 " \\Y ' ? N .J h.W,w,'76 9/,.S k..L...*'.'.e.S.D, C +. ' T ' .. 3 O.. 1% or JO,. a.> .M.u. i.3.--+ C'w.'. '".f.^.!.,M, _a h* /J.', L. - - ~. "* ' g g.- ic e.' w. m .. - - .* .Q~, : _ _ +*\\.. g 3. s.np::v. ~ $.:..g.3;,v.

p.n.

. . . . .~ . n- . b / % M'.:.,. e M6.g,5 . .w.- .. ~... i;re %. g....pi+Je s* M W 4 % '3.>i U. I % d W Q M if ph c %.y '. 4 - W qk W m...- . u.. t

r n:# -:n u.....s.

e.,p., + q' r. m ww;.%. t n.

s r + m.v. t

...<..

+ '. ~ < -. ~ .> . .a.

~ _. e. & >.'i',, w. %. " -, , t,..- . . 's 4. 4 ;*h . yn g

  • g.y

&.3 4,.k ;.,. s ).,4. c. 4.->..+: .,.w, ves ..

.; +...,. w .. ,,.. . . ~.. < s-s -

. e :n.- w v.e#. S.*= *. ;; w.v,.. m.,i.n. g.

v,,w.,.... .... .. ,,. ' D-e (.$ e.gPh'

  • h8
  • e eb P' 1P

'f (;p4 . M' ** + C.d r,e.'qr *.Q 4,5 /l- *S' 4y 44

%.. -k

    • 4.,

.**...rs,,

  • -

.,d .g hp:-u->.'-. -~-g - %,a4;..%+ # y..

n n.ps.- m.. m. p..gw we'.,%.@ ? t'.p

' *" q L*9 e, p - w,,.,.. ..,..s 1* ,,, ? b -Y S N b .:, l* j hh-{l;,hhh,s.m&,.,&. c5#,? %WQ:$_l? I.O w.ag. m..y ,.-.cw m.n w -. , . T'h...'.f[

.. X Q D D. ~.. r...,... ~, . _.,... a; , -- -. e.

.o.

w..

s,. a.. %..;<.,.,:....m.. . .. - .,J,. u.w...y..y.

,... , . . . r . y w .... < 3.sM. %. - e er a .,c ,, p A; ~p2:~.-,4*s. m,4 ) -y.:a;9. My d.v.. ez Q~, f,'...; y n. = W..:.g-.tq.'.

-'w .r e M dw*. g. ; M... ~...,

- .., :- ,. d e gg***'t., &.-4; -. r.. - ..,... ; o.- . . .

pyt ,- .m +:w.c,g n 9 w - ., M W vr.:W.u. - ^. . .~ - ... -. T M @.- -.

,+

.~ p-g -?..&:,r. ;.w- - m.tw < m: wm e.4,wm, - -n m c n u w n;,m. a.,.p. m:~. v.

.s.

cw-w- . ..c. - w . ~..:.. 1t t,.$n.

...M. 1,g.f. e, . mcw-gyr- ..s q . n '.. m. w'f.dy%c,..p.- a.;;t., q.anr w'- 4:tm w. g C,.,,.p.:,','~;- &mr. m . ft :p*o vm t W.. - * W e*; m t v:'p. mm- ~ - ;.a.w tn :.A.k.. & n .. Tr.hyp, " 4~x4 u.wg.. +3;z,.+M;g.yJ..'.v.~.14.. . .. .m.Qg%." E..%m.v.. s.,,.c J - .a,- - .,.

.e

^ ~ ".M.'.c.." -- .,.. + at , , . ':. 'G}..9

w

. . - .w **

..]

';%
:.d.tm. J

%,,r ,7,.,. -'. L., e. p- ., s' ". f

-r : e: =*

c m% 2.. N ' W..c.#,. pn. w- ;.. ~ -v

g . . .

A, -.c.sw i

.. ... ge w.a :g e.

. &,, --. .u c~ -*=m.-==-,

. :: 4.e, m s n., . - -.. - . s.

. _, . %.y.,y,7%, %,yW...), %QC:y.Q. ? : s.', "%.,.M s:,** <;yl.[.,e .%.,w.,4. ph.. e.+ :, :<.r,a,. A.r.....~..= m...M.p,,'..,.a,.,. .,. ;.,.- . a,,.i.~sp.. <,... p *Q weq,c,.. a.{. u.; w,g +,. ,...s.. . ... , 3.. r.

.,y o..,,.

m...., .c.

- n.n ~,.m,,.,.a,.. .. . . w ;w' ;.s - ,w . . -.. .fj?gt, . w ....,4. 410e c. .. .a.r% g./g,v . .a.g.

w.wp:.,.sp - -=..e.- I.,. c...e. 4.~ 4 +. ', w.

vk %,e=. ~C . e..u... 2swww y:in. ih ;f:..'$w$. -- 2.m ~n n"M;..-e h..M -... p. .v4 g8* jfW ,ug I M aru.Q.snw:cm ve* * .., -4gM.wov7g wtWa'c.. .w ' A F -:4,w M <*v* . Pa-

  1. a/* @ 4 % F - M y ?." y..S -MMwrN%GD x marKMDh6e.4@.uM.tC.7 firma GM..

.n . .. @4@DN2W'WN"a' MfvM_'F/@'@M**!E-diKTWWi&#gppy _. -._ _ - - - . -WSD. wpm *yy% ..-._ _~._ u.

e = =.sas.e,e anseq>euww.).-e=enlg 43.gb.g mp.png au CsesG.. - -.~ -~ a ", - - _=.--L-'.. ' - - _ _ _ ~ _ ... 899b.uB@me e.muk ambu 1he.*9tt sWm=*= e.easukescut.. Pf"#9sM.hg GP-7)et.. u S.S.%

  1. ee,,

_ _ -*;tejwpgesaansmeM.47 - ~ te teDe _- e#MOid'Ist F.bue.ht.phDed. 49 e.gbe* qs.r.W.pw1.is..Wi,e.,.h4IA.4m9 teel ***&tampque and w m.- f-T *eult - - - e - , ~ ~ J ,"t e*I'P-

  • h.**["

. -4 . 7%.,.J[WN.b..O.

'E.

ON.

@N., . .M., u._. __ M

  • k

.# .. ^*** p.augGWsC;b. .3'N,inc op..,. e . . f.* q - % , : gM-.7 .'n, c,M.t. - . A..,.. , -. V

  1. w 4A*+r-* Q =ene L

' ~ QM'#ac.s.;*w p W *%@g@4 '%.., A. - - M^.'"~-=- , ' . w w .W .. - M.,$ F ' hp%. t, 'f,' .'. *A.. %+ w*. s d t sie.~. g1re.~ ,3 wsAc,+. t - w .,A,&,i.~e ,.u ,,y hM[.."y,g.g.j,W.w. W 4aQ0 M W JM4 M,e,he 7:% s.M G'^.W,,. +m.

'T a . W 'J2: - -..f *f g.g%p,.,Q,.,.nr% rw -* w g - . ? , ..t e - sm.L.,g pgM.f p e . . . Mi ~ ~ yl...M d.'hdv i wp M.4 4 wm:=.=:m ws:n.:w=~.w.:xs.&..m..w; :m.=* e w....~:-:.~.a. =-= w N.m@.. gd.w tm sm% d;. v. ~w, -~ '.agw.m$p. ).m,~. *.yeam&y~4t.,N g4. y'r.;;g*f,'~ m... - ne,yyn, r_wge y.&p+:;wm-r,;wa.

. y.w= y . ,m. _ r.r ~ r.,.9 y E..h . ". ' W W %,v s

., WMA ..cw.? p.u.w...m,, %,,.-m.

. %gg.

M*pS /. W 8T D J* M 8.T Dn.iO*f b.['7'cedM* T d ? @ D " N 2*T % F4 "$'*O. D N **I'@I.I$ U N N , . m ev e . x... m.

-- - _... --. _ _ _ -- _.._.

. . s,.wo-~w. yw.w.v,u.o.4.,.,u.g. pag l:c,9spygry %,,3; :gy ;.:.;;;:ypyyn..2-<,wg y.,,., ,.a.

mm._c . ;.emQy :_c.ym,nwgw,m wy,.,Q'*T.Uni g.,.n..,. TOf[.@,* w.nw =.-,. ip,t yw.. a..,..m . ~ . I' D [."Md.

NNbb. k NNb ..- . m.

. e y.m.

.. n ,m . m.,

. YNEN3M5bN i _i.

m.m %. . ..;.s N %, - m ,

m.m

- ... .w.

. M T ' k'.m m[h.wm m.rk,.y w*5 .eu,a,,bt.Nw ~.r#~kk.).$,,. . .,. k -.,,.#. ww.e.

  • * * *

, , f .' ~,,,.-# ._ b% k d - . kh Nbkh . h ~ ' h . ., w e, m.y..- m m m w. m.a n x m w. w _ .== mumm ~.mu -e v..w..s. --. m w.

- .w z -- _ w- _ w-. --- ; m _;. C y,w',.v.~ w.,s, -m e < m m m c.u.:...m- -w* c. r.:._.._.=w m -w.,eemm.

e e.

, %ww-c.

.na-wa - r.w .~, y 3.- w ., &.gh.wmCW MN'%.,.anM.hy;.,k"AW*%,.u:ws:d4W.yphyW.g- %@7,M&pbut:m,T.%M;w, RgeS.Wa?p.ry'.N g;gpt i:: n T:S M W n.e-9: Y-. 3%%y2ct:M*t.#w*:;p%: % 4 ql C M.Q.M."M;X.: . %.z:

.u M;A.w h @ M M 3,:s %

y% iOC.12'

%uA.w ~MVrWM.g.g.T:1614 ;t,@:r.:dsa ca.,:,.t.14,..mww%mW:nt"mT**cer.mm-*see8AwwC % 5. c Wemqce r.s;> Q ;m 4 :r*.!#* W rM:tsNAW' ech W e* M W cS M m.< p V6 6 * rv e a @ i.y n man,;: .c.mm. vg.c va u.-9.w.3,;g.2,,4,. a.4s W,.a m w.sp.

,Df.M,**~4NZ .M"'$**MMNTMN'U*DM.MMMYMS$ v.e - - wnt,bw w v>m...~.c.y,;.,c,,w._,.,( re t~ym4px.m, mc.f.,.?eu&/.:m,.;,.w; wor %; MM*4 MN w. < M. m_,, a...w~. y,; n rn %.b % v r + W 'aa.W.

r ~ m ;a & # s. %,w aw - W s.% tsk :~ N ' '.'.., 5 s#~.<..e . ,> ; u., a % W- ^*rs:gd;,- +...,,r*vM1w.x >1-wwv< 4,w, 4 www:x =Q v,m- ..-. s . p- ., .y %m&r~siv-1 L.a,

.s e . m e.~ w. w - v w,w.w m g / s.g:;@ q a s a..w _w df.a A2.f. 9. d ; r., W. k, m o&tw ~w.e.. ~s e v *-vm w O@.s*-AWf..-' ",r2,"'FM.W+eteaf 9-*P7f i.'W3 terr e T*W".

  • WtP"},,,-

.g mt T.~ t Y'TWrrr'oWWm:- ,-

y . aNW.Y.w. n % wsm, w er+ww .w, . na,a, p e w w +-Jr%%r.knst ew *.m .ea..:3.v y.

=.ve aves sw wWM8 ?v , w n.+, swar,yr .. -/s s-N_. e m a - . a- . - ........ w .. - . _ .. .

~ n.. : .. - . .. .. , . -... ...... &..n.

e.

.. m . n~. -

c-u,

. . . Q....:...?.:M:2..[ Gibbe B Hill. Inc. *: '. .' O.sm:.c.a..$.d&lCl,G - ,.. ., '

.

3g-.:. M A . r.

ap' .INGINELP.S.DESIGNf%$. CONSTWCTORS., ite

., , r " -' Sheet S4. p...C[. ..T n'- .. cmc C F ** * -@- * * * * * * * * * * .T e

New trosse . - - \\ .o-o ,4..r.... ... . -. n a m.i, u..Q..Q. Q........

.e -* - o - r , m.4. 05. l....h.. ).X..H M... ~f.. 4.!!.> 1."M.......$..J M...>.&.. 45..t.G..Q _m - i _ .. ' ...-- .- ................

y

. . . ... .. .r - ~

s

, - . . ..,., - . ..;, , l , ,1-GL4 @ LL. bt0-r,l* 6th. % 94 4 G h M. ~ ' . s . , ..p.

. ' .,. g., .. {,#Y ff % $&h4 (' flNl& " , n. a:v.. . I $~:.e

';- . , -

  • ,

,.

e y

2;;g.. a ..... ;. y.. m.

r&. >, . I.

  1. t.

' .

'

. . . ' . . e. -: n w , yh[ . . . .., ' . ,. b ., $.,, .

    • E
y

. s.

s.

,. . - . , . . .. ~.:.n. m.,g.:..g3. ;.y.#, ,c,

- . ,...s.,. y.

- . *..., g jy.

. - . . .,.er; ~.";... _ yy,J.

., s_ < . 8: et %..=. s: . g.

z,;.,.,,, - ( ; . .. = ~r ' . y , . ~. a..~. ... ~ ... --+A.. . . . (.. w.

'c., c,.y *f.y g . -e.-4 g* p

t, 8, ,,'-,g, v,. .

-

.ei=,ir .c e ...,. , r s p.

j

  • , -

.v..,. . g ., .,, . .%- . . .. s*.se .. . , - e,... s. . .w #.,,,., m,..,,.p.s.., ... -$. w*; <... . - o -. .y,.,,.. - . . .f.

,. L.. .. ... . C ov4 C I (. d h $ d g: s. e, M - S M,.;,g.,. #. w.;, g. :.s g . .. hNh-hM' , M[Yh25N. M 5 W.c ,y.5a..s M.4.,j,.7 w o .,, w.we. 6. e w.. ., gNIy...m:u..s.a.,...a qs, ww% m.

.> n..- c =. p n..w

m . -w ~ .. <. ,

, c . Mkk'If ' M,4 G A 4 &sCd G.J*J, - e 2 0 # N % j. h k k Y f-M i$ ?/3 k }. 9 Y M : k.' gy$., y&vW::m,.:_.sk%it.f.g,+,.:. i,q@ + ps.%M*.W h.,yp,. , . 9A y y; ;. a w.

rr,,.?, p.M' y m. o. % M,..: w.n,,, - w , ,a.w:i.,e :,.. :,. :,, ... .. . .e,.. _.

.. h . : .,q.

. e., f ;.,.,..,.... ~. -. ., ve. w.%... .., ... . s.~..u,,.r 3 ~. .. s.Sy.. - g.

. ', - ;. .: .,.,.a;. se .n n.,s k 7.p'.,,pa .. n .

m..., ;. w 9...ax. y -. y 9 ;,,,4.se..,,..: p :s w ; m..,w..w.,,, .. . .n.

... a.9; .-.y..

a f.ue y

.y,... * %.., :.. s .a m4 s . . 3,,.,.Q,& Qg3 y3'.p.g,yg.:4. syyrg..g c.+ , ( . q, p. Q: ~=. - ' - g A ;; x*y c.y 3 ? y s4 3

y , g,.o n

4-ye p. vow
..n.w:$1 r a:. w - M m.

e :. y :. ~, ~. m. w

.

. ,. m.

a ~ g%r.:.*:ry#ys.* Wy. @,@ 9. 9.S.% 4,eM494.pf-> .-- - w %.:. p.+ %,., w g q w..g g..N j s.r w y 4 4i.,q q N %.;; g q .. u @. ac-- p w f , .g,ex A m m/.,e.%, A. T nsp.w,as.

,s,, n. v;;,..t.,e, r,, g,p%

s. 4 g...,. %. -.<.

J m,p..p-- . i .. m.., ~

- - 2- .:,.. a.c(r.a e,,w ~ .,.,.m,, . ..w.+ ... + +

c nm

lb:' 'f :W %* *i9 ,3,...cf. *. e.J.. psg.

'.. . ., . .5 w ~ i' f - x % r~ % h '7.M D gs d y1,G N A." d.6/6it'fN ..W @ ?,9 $,[',%-t

  • '%'% *Mi :.Nhl-TU* f"/
  1. ' If$ 2 G

' bd,d, h *,.!, n.. J,.. J -

p.. ..e.edw..x..ww 9%%"V ' % ' - W * --7 4'A

3-. , " w w:% m tw _. a.. .ir.:*c...e*=ggg*s n .. M ~~ n v c-x.,,,s a.),.py.,..,.,..6 ~. r,s=% g,.. ~,,.y, .. ;.,..,,.. . p..'.n.g,.~:w.w_< r u. n..r L,... .-..,~,s.~-.a -,., c . p.... - ~ ~.ef.<j.

g w . e.

. m wm' won...,s~v.. n..? 3.

. .e.e. g @.,,thg Q p' y,;..,4 my4,y;.wa4g .- yjg ... .m j -- . s.. ..%.x m, b, w . n p.

, .. m ?.,.. E A, ; m u r c., .e . y ..#.,, m ,.g .p.

. m,. e ,,, , . -4 .,p; ~ , yhe'.%s,3 9.. T,..Y&M, :.#

.,., s., ?'2.,.M..,.;:

.p.;ym g gfg y,ag.% Mg,g.q 9,q g . W. 58I*, es . % yr:.; ~m -

-d , ..+ c:n.m.., e p% n@.4.:;: %% 'cEK* * 4; r' Q - , . -. e.. 5.

aan .;..c.s.

. . ww m.& , n...s,,.. yM

        • "***8w,

. rn., ca p'S- . Js-M'J,, . --

e.

. .. ,. o - ' T '"t*'y @* P1. . .

    • 'N;A'1"".'M. 9 A * M '.?'
    • M " '

T' . . %... J.:., uJg.7h..,3),M..:,'Jf7 'Q.Y* ? ".*d p. Q *r p m ]$.,i.et,' 7. M *..;,;.A-Q a{**"~ %.. $ "' '7,."4 .:***'- ' 7n.. t.w,'p-,. &h..m..,$3dsPsas , X g e .., w.

.

, u.,,.,. w.v...," N...,,w . , .... < ..,... A,*i. . ,. ..w.

% )m. e., 4n.. . a . S , -* yg e.[ . A :. se..a* ,. ,.m n, g. %g,73,.:;g.'M.~. y'9* ts#1.% gh=4*-te .. *yg ..y,1.T W,Feu 8"DWf6*J [.*'QdM~ Gtf9;9(*43; *[, !t g.st.Q ./.(.c...r #. ;s..e..d.

9* P* .,3.c,mm, +.~ m - -.. v, t.. . :.N + 4 + ,

.g.

sw.gy .w , ,.. -, a y; e

q@t -lgaghg e *T*%'gu.n..T , Y=.m3ee%@e 9r4:,W. .nsV.M*a'faeQ;.W.LL@u 2,ailU 2 i'M,.pmME..&s '. .. i sm. e< h.sc .. ....n,.. ,,'.. W ' '," T f' h8!'! s --'q:~~ K M 'G.L ' * M M*r ' im M .i Y . ..... ' h,.'* 4,u".*.:. d k i h."

,, z_ = - -[u. - --. hfh*. 'Y.

. 4*[ #%N: / f d i-m.

- > __.__=.a.. ., _., .-r .. m -. -, w===+.e.-g ce _ _ es.

. e. 4 a.s...,.. u.sn . ,.n _. - -. __ -._;__--- a n.._ c. .. 4ht ye*'P" et.W e.e.a r.%eqP 2 9b4-pr.am.:p.4 = =.* * #..n~...-w... 4. g. :::p3 y,qt,th 8. m.p W m gget, -(*3

gy g gfeggeb _.M M.F.O W-MW.

f gg ...p.+.g* ., s.-F

' : - - -n w _;,, e n_ : p =. ~,. w..- w -- :. : - - - - ^ . a.m.s.;m.,..v.,f * AMf;, rap WA*d ~~ .. - - ,.,. ' __ m M.,,.s., c.' w8 M.T M. ~ M.4-w Mt p,Q pW;.p: u &..w i.v.g*w: f.at e.e'.i.*# W,.g'* *,w s.. - r io -- T . e,. g.v w3 ,g .~ i-r m.

y ~2: ?: y a,4 y j.w My D,,J.':%.._., $,.df. '.,. d.,.J ;J sur. T' E _ f.*' g-i.' . m. Q y"Y f"' af. c<.u'. " N.,' ' %. ,. - - - .& .. - +G. *?.'% y % - r.5 *= ,, o . ..... - . 9-3 s.y. _,. ~. S.g, n..,. c. a.m 1, y',.t*ct:-/ ::c'.d,t,b:_ g.

.. . , p.c.9t ',. gg; ;r t.6 ,. 7 q.c;n.c,.;;-@~'44my MIp. ;:'flrlli;7. A:- s . m " M J. " c:l:WC';n .@,N.

c 'en ,3.,.. . 5jg e w w. TL.%r ~.. :,U.

M..;:, M.. w m,,t'r?e%.g. w d. & u p 4,..q,q.-1,pr.%n . s w ;.w.,4,s.w*;XW4,,,.,a:'.h;r,..,

g .S . 3.. " - H.W.m,M,.:g ww..r : .. -

,. w,

m.:. . .m ~ m?mm u <.n :... & g.._ .f,...j w%' ' ' Wr.~C;3+,.+ y.m u, ~.wp m.w+,..+m.g:v ,- .... - ... u. < -

2-Q" siefibi@W " = k%s-w

..... J .p.

%msenC2: " = -

' n _.

N d _N..,.tN,p?, _y-'4 Q-.EtyV.e;M w m=

m;wh.n.,m r:,-.* w%enii-- w w - we m.

- ..: ,f.

r Q:.>< w s mo.sy WL. 9 % '.exW+ %. ......:..:~w.v4.m.p&.. V..M%: %,.m+,.,.W _ _ TM . . =. -t e - w.e

-.... w q .:^ ^ g;=_zr ' af. pm-M xb y g y u:nOMM a.

+ . n.-- b . Mn.n.w.,$Nm.nM..v N-$dS5 ,.. ,. p.EtiW.Er,J ~um u m w.

, a .. vO.uMw,#.F?.~w.m.

e- ,w .#w v -- .se.+.~m m m..:m af}}$*:e.;D S> . .

eanwennon tm-. C ~ w :~w -~ -- -- ~.N e. '.ews-r . _.~ % .~.~.4 Nw.* .f.*n .m,=m.rpwi n . .-._.m . . wy".4 q.r,n^ n ' ymy .,c.,. -.,yy,n,,=-.. c ".,,.76p..;v'q,-; s.p -n.$: - -,. e .a D.

~^ . s.a

  • e..c. %' naw e

% e se.n.;"> ev. p.=.-;e= r: +.*a s n.s. ++w. 4 % .-=~.5 e y, t.n., .r.

j

t g

.. - wy,g t 9 4W ***$ ,,.. ; 4 ..*. m.. %... 3.e. -a',e c.

. r.- - - t -.- y_ W., .w~. -~, .4 .. ._27 y, m,;;.a.a -- .)x'R..M n.,,p., k..,,,A '.'* r,e > %n . ,.. . ..i &. - ,.~.

  • u.

%W?Q.sG*...., ~ . ...4' +.,r.,,. ?. =;~. m, -..., w..., n,sn,.w.R.... M

-;.

.a.W

"

y ww.s.s 'y

. c,%u... A.

y . a. x.

. .u;:x: w. m. u .

,. .m on . - w-w w.ve+-* W.* x.

,.

. Wr*?*"yp'<i,egjuespump;2: surgj4, sMp-A r.63*M.:it.*ry;p%ftfi%:==4,at+t-@f.x, .~-@..,4,,[.5s(,hn-twjdfad-fLEfa'.g&m).Rr@d*dwA rff.dP.

-F-M C='C:!W. M W w G~ w.~W~Q M $3 d r .. - n -m.+ . .. n n.,'. s a nw-@. TUM i**?"4N.*.P

  • Fh5M%.WNvMW

.. ~ MW "y. h e%uR m @W@% % e n s'd'.

  • D

. 2i ' m < m 3vWhe e;wnwkw4@nh * rw.., .. . t . sp wy% ~ .-%. w g&@.. p &. n % w%p..v. m: 9 +w ' p m % w ~ d.. m w'.m<. p w p w y% $ w &>2.k W h e y... ' u w -n -

  • n

~ .p

.:... n.;we ? q:'tWN...:%.;g t.v

,W W.:-

  • ~

-sn r,i wn..mov,~b:&..r.. *.rm.W : cyWtM. ~ &. w .n.s.= 9.%.% %. s &. _- r m n :- .< N,s w %.t. 3, ' k.

v w w ::;3.v. n.. . ,. . . -... .. .. - s .~ -........,. -- .. . i m - - - - - - . - --.g .r. - - - - --- t v ~'

ye = y-e ' 9. ' ... ~.- - .. s w w w r x y e a w.s y g: g tf %, . g . . .... ........ . , v.... } . W ' '~ " 6 , Q.4. %. h. . , h.. . C{i.

",. s .

~ ... , , l c.,, r.... b.. Gibbs 8 Hill. frac, ' - '~ . - . . .. v.

.. ... - - 3 4.m.c.a.Sd&}.?: namuns.onstanens..consmerons - - . . . ww ww- > m.

... icn. M*d/Apped.SF. *. g.. . , . - ' . ' ' ' ~1 sa,.c.0. S..t.p..o.x.

,. ...a..Q. (;,. :.......K. 1. k. J...E. b...B..I.o..L.G..... . a .3 .

M M J.b No.

. . ? .. . . ,....q, w. =.:......, . . . g . , .. O d's* M 6 C par.g.

. . b, " ' .

...,. - " . - . , _... ~~ ?' f, . .. ... .-.. ~! ,, f i h f.

  • ,*

.,,,...I** [- . . ... ;,. A c.

l%.O '1.5.l. 9p w., ;; ? ). 7 Ll]f,. A,o;. . ,. ', : : .q,y ' . i . r ~ r[ ~ J,.Q ., '.** . p , , -.. .n.

+ -, 4.,. ,. - .-.. .

,, E3f 7-I'.* &

' . . .,M,. ,, j/ N (,,.I-' , l ,. g .? - - y-c '.., &, L.

Q :. * - ~. ;. ~ -* < _ .. s, .. .yo 4 j..,>~....,.y .. ...... .. . , 4:i +, . ;.;..;.., d y,,;,,,,,p.p g ::._*Rs;g g ; s.,- s. g.%,. = . . w.?. - . e u.. .. g / _.v - - . . ... . '. * -w ..

.

. < ' 3-e: ,. t, ; py m.

., f . .v-, %.e. -~ m., W.' hi a ', v.1, ;w~~p= Nc;,.U *.- i~.G '. dt.W@Q.MlMv,',.f.C.$','. h.4 -C, w, _ ;..,, *.,, a+9.9,i.k, t4w e, - m. '4

..4 ,p A m. q m ;,.g.;w...g.,y.,, ,, ,w w.9,,4,,, - w e. n w.4...%m,,.9", m.z,_ a. Q, m..., w3..,s.pe,... m. a es.y w s.

- w <. - p[.: r, ' m, .n.,, cxS ~. . mw

d,. . ... .,.m.,. -?** f. g, g '. r- ..~c,,,. J., 3 'Qd.gle *y!gyb %.gQ ;.'$Q sf, g f }'* r' * * ,

    • W* *y *o* p. *(* gs -*
  • ,. - * * -

'

  • J. 9' 'f.

.* ... ' '4 ~ '*' . g )

/& 3l ~ .,

  • -

?.. ;BT &y . s%It; QQ~ ['k,n ~. y'.. . * '~A.l A;W4 %'Qs' k.Vray+r.,& :4Q; :s '. '.

,.,.m

. s: c..r.. / :t;,. :. . v.s . ,,,,,, ,,,

-W y

p',/ ,;"gw9, 4.MJ .p.M:,Q < : :..w.m.m .,g ei. z,'g, 4,Q, ;, g.,. . q.u cymx.:. ~ . 4? Q d,=.p.e G,6pyA +, ,, ... ,e e%,w.y ;g>r .m,. .

. :,.;;.; w

. n 4,. . n n r...... . g 4'. .. gqg 3.p. e .4,.-

  1. .

. a.

. %, m .o,wx Q /.* " ' : :.'-P ~~ '.4. Wy ?:'.:; m; a'.L,.6.,9,. d.i".%y 4M,, w...A.V3f, % rM..& y NCP 'r .y_ N L'; L4 '..' .. + y+p. n. ?...-. . vnc ?..,,v.:.. s -w ... w v.

.%3 y+ 9.',A p.j; u.!w 6.. n.

.. w;.i.,,.p.e,QrA,n,jwg.,j,, wly,.,, g,, A.,.1,y.5.M r. q%ml,y.m.cxp%q y,..a ,,g 9. :g y 3.J.e s. 4 -. f ., . ~., - .. . u.

y . _;_ ,. ;....g.. ;

. 3.,;..g7

... w.3 y; n. m,. ..,... x , a.

N.w. f . ..w ,.a,n. m.;,, ( ,,,.w. 1_., e..o,.' ^. 4,. 4,..( j g. ..... .... . . .. m j~.., ...s.

, . -- ..s....' h,,,, b,,. < 3y.

q.. , (....b. .... m' .j . . g ...w.% .a.

. . .,. ,...,*.$,5a.....m. jf.,?,.,,, j-),, gg,q ,,, . g.. g., - a yg .

.... ., a,g.p. a" y%;; .,.g,,,. '.y.f *, - .g j-a /... ,g .,, jf.

.. - prM, gn

h gh . g '-apay y g [- $ht'*[.'mi ~.p'} j'y , * ' __ '., *p ?g-J.

..j'.j,;'*e y p* '44. _ g m qfM.......rW.q % g.,,,M,,,.,, g,p.'y@y . b . . .g r .. $n.' C

.n..

M,.yi.hp N4 %.yja.4 M....,W.g.,' e + %.n;,* w -u g . p_ 3, u-L,,.., m. _.,.<. ..g,, m.. s,..~ >. .. . ~. -.ig .1-r . .,,g.-. .~ o.g%, \\ p*2 3 ;p gM s ,y, - - _fs <,_...&. .,y -.. .,.r,. _.... ... . _...u.._...,

. .#4g.

W*Wf**d htg*

yp=F9+=sy.

Jy rv4.gf*'57.*Q*.- . .

  • (N" {2ow..q.y y.g,,.#p

.. f 7.% 7+_ *, a A.

s,[n,. g; ., F 2 q,..w.: y c^. i G. %m%',3.A %,e kg n,.._w,. a...%,y a y.O % g;pt: . p,w,pt.m. 9:. m:4g @* o.o: z.

p Y n,% :<%. X,,,g %,tl;. x &. &..W:

r,Cfa.,b.s., Q,

.'my,&,....,.Q :..~...f..ga', '. ~ :4h.. , ,,,,,y,..'ga# v h.

' .u..k

N o.. g, v.n;.,, _; 9 y -- q:, mm. q7ee,,., v,.,,,.y....,. %. ~;,,,,.. q.,g....e y*. ;- y,, u *.. D.,. + p.e .,.-

. ,. -: le*;lp,. %. .. s .m..s,,t r @,,, & * .';m.. m u.., f,,;.+3.,. g...A :-.~ - ., .e(, L=. gww. Ase h .... ., .%.,..,.,.p'. .. 4.w,$.m.g;.s.n. 3.a.,y.,% ,,.t 3q gf,q,g,e,g .,%,..,. s.. m,,c,. w,.,,.. ...., .,. ,. d p f q;y v%.. e.,. e4 y' , . j,. - o

6.

e., i.e,itafs... 4.

.,3 p3,., %gp '. P .M g. f ; G,e, *4 ,* .. j g.% p.,g., q, e g .? .,., . ' M.9 4

    • g jty e

p sM.., .. r.+ . l.

..g. ; y .u;s, ,.g,,4 . ,, ., . ,, w.

. u._ .. . .Se9 #g.

w m ., - _ ,. p.

m s,n..gw. p.,,. e. +.e w p3.m., ,.s,n,3,+.3. o... ~,. . ,n.

.s v.sp p w,r.. ~,.. m 2-; -., . u, r. .: . ,,..,? .>

3,u,: . , .., %.r... w. w,.;.., .e .,,w...,,, y. ~%p .,wa m er ym., , - %,. %.$:w7 y$:.-a. n-v .. - - m ov .p p p

+, _ . .pg,. , .' y;,:4 e , . x W.,,.4 3..

  • w h

ff Y l fe h '. Y" ' $ e.' ..e y

. e x@w w;.;. _.~.. , -- n;;,@:,i Q:y.x,:,agg? TTW-Qymem c-?=.c>M--~~xw

    • g'g } y y,[ W YeyQ:

?Df. ~*'.Ml y'*. *Y V.%t ~'*P'*'" Q [ .dM;'?'* Q' !f:ff, Q @ Q K. 1[ & j,.y g y k ,, ,, f m,, m, '.*4 3 h,,em,.ur,._ . u-% ,2... s-

-

_..~4mm....m,_,,r .--,... c., _4.,. .,> . ._ .,. . - 4. 7' m,. s ' 9 5. o.,-, 1s.

- ~ o , __. _.,,ii a.n i, >ew,. .e ,.:__--- _ _ . . . _- ..- , . %. f7?'ea t*Ty mum'em 4me~s:.".,M VD:*,... O p._P ?J " 'N :9 fre*3-po,T='"wWa**<*gGg,," -- . . g*fyp ** r4d-g ' ' 'gg73 h-*>.-~ r

J.++4 s.4 m 2'ffw e >,,;

W'W;;.? +..?,-

  • '

g$ k4,,;;,,M..,. W.y% ).g.% - c.- D ri,c .o y c.;_ - J..-v>(.g,p:s~y..9...f- . u,- x.

y-c

  • y*

> F .* W,ss -,Q_ .N 'St; p r.

a;;4

_ w;w rewN ".'*; w.,va' m.4 p q *c, p .,.=,=gg;>g.g,c..r..p..- .

  • . - - - -

s,._ , , ,,... - - j@.1. dr .Q.. e g., .,,q.g+~ T.,;ik' %;yg2;;~.wg:-t;3 cm., 4 fg, y.,~.y r4 p.~ 'M >,..,ip*c x ..3 -, c Jg *

n
. :-,.,

. &. ~.: 3 - } n {., s. rtu, L.h ,. m ~ e, ah w. @y 2,.; v,,;.;w,,.; . -4;. gg > L.*W>W- ~ 4 r.

. m.~ :;%.~>.:'.:,.. :. ..

t :N w'M.Et;~wtn_ _ _.

c.

.e . ~~ t.hG %...;.S..p* y vlW.~. ww. MH.

m ..-?.,. y:, %, ? r,:;g.a: ?Et1,%%% 4AMh V., s. . .h...*,.u.

. . . A.. .w . .as&#. rif, ____ _ _ _ _ _ _ _ _ n_ _,._, _. _ 1_ _ _.. .=in.&,_ y a. m.3,w~pr. m ;.-gea.... wig.,c g,*p #.j m 4. . . c . cet r

... _ _ . .__ , .c.m,..;L,oen..q,aL.v., % s.Rp.. p c. w.WM.Le,,,en ww &W"m.,sE;g nvw;: u-mem.w.,-y n. erd 33 D. m.w,:-: :;W n-uw , s i L 9 E'Pw* rm~~ -'*"Mx-M" C, e.,;e.,y. - "p= u m v%mt.qrep e m s.m y,L --2 - i ~.

  • We..%

r - m,g -mmw .

c o .s.w ,. p- .. , MWWWMANWd'.'. $Oh&i' *

.
..
.

. 3WW - l ._, _,, -. > ,,,. v _ w.s.'at4 %.t m.x.u.y:.: mw.,mi.. gV]Lg,p#T. W.}.;.;nd.9.k.+.. _.. 4..., m.,.. _ ... g I .. W' * f l c. %.,o. qu u,. e=;.e..$..,.r-A,w MT,Jfs,Jf P Q.aiig.Q M., _.

.Jk.W'IC 6 t'.%M ',J-g%.* '**,,c %h *0 * a F.e

  • $

.y

-4:4A. A r, .. .. v :,.,.M: 4.5 * %. ' r $. V - i

) u.

. w,..z %.sw:ms .m,9e,.; a.2. d. ~% m. m,+ s 4 s d,.et2. m.. s . ,m .m.m.

.. w.w:,s < - b .. y,s;pgw.

37,,m.,,w ey3: 3..::.m*L,.c_.pn=:,n: = =. --. ggy _ + 4 -my e m e p o w sp. w.:..e. q:..y.- . c n.,- .~ 3,. ~

  • t ~..n. =.

- _ r w ar w .. - .- _Q m > ,u:*%ng

%-.. n, n: . , J '< w

. . yC '? ' ~)()og.f..r w.ea, Nda....,.. + mwo..,'Aa_c.ec. br. ms.'.ew.. u,.pg/ e,,, '.5 ' .( w _. -. m.xWx.N3' %,w._a. 4{",e ,,#',,g'. "' > = * ' = w= % dp,

  • 3
  • @*'i'.~4$*I.*.k

., , . -2 , ., u.s ..>- ., ~.. .. .,... . g,:A,4,n,;fg 4 _ ; -r ' u 4e.Q..u ava% . . .. .. p... . r W x.;. g aifw,.* _..,,.4 % g .I,9&rve ie +' g eq Q *g y lg'g*f Q g 4.r. : g 4n r4s., . n e,., * 4 _- ,y )* g.; 4,g,,.y .k*pA.)]M*fs $ **;'*- ,- n mt-9 . Ca R W.% tL*/l~~y,.. a *.'; @@STRW.~&.. ;. e* d[*s '

w e . l ,,

  1. RsLy>,4,,e.%

4 44 s.tw.

n.W.

~C K4riW v5 .g w,;gw.a w 4-w.g%hW/d***91Ntm.%-.' ~ %.*,, Q .-yMio.wsw.ww>w.wy;q,3,4,3,h.4 as .s. _.,, 3.

< - pe,,ggg ,,,c,.,4 .w.r ;;w m,.g.. c- - ;scr%& %epfe CvC.g'r. J.r C: . T ~ w tNnt.3 wwpnum>.'.k.w...y' w"ll,sm W ** w*:*Q k.g *M.,,. e W= m ,

-. ^m - $$.A,'a%.yb.. ;% .w - m%.4. ?,:tN, M..v..m.~ m-n p..n;M.xiM '. 4$ :..: .S-M V . n i .,tf, es + ~.. .n. y.

w s w.

n. %e Q,,-.:}.AMkgc~ yM m. y%wr,n.4......,..,...- ; ;'-- ~ Q' :~ W,x;3, . .,g?. :,b e:s.w : .: % w...w wa , ~te. & -*.<, m. o x..: % vp*. _ - .. _.-- r.< &g-s 5.. - '. . g y: tth;~;ne.r . W .

V an~

,e .-- =Q..pp.we . i% <p.' W.x W U.V,. e' - ,.w.

%,n-v c* ' - ;, 'd. s wa.r::.gK.>, ;. ;;q- -q:pf*.g;C,: [ a w - .- ' '~- ' .g 6-- = . DUi 't . '$ Y O sea.**4%c

~ ~ - n . . -

,
: ' *-' - ~ :

- - - '~ % i

. , , . . -.. _.-.-.-. .- - - ... . . ,&$ k %1%.21.. sibbe s Hirunor.

4m m., e.S./.W.M.'.V e.... . u,,.....S.. P......._ w womun.usas.cw.swcwn. - f..... ~ - .., . . = = 4d5W Toft 9L ...w w w,... . ... .. ,. . o.u m.. e... n...a.... . Q. &..S. l.A..Q..x. '....&..L..%...s.....$.. U....b. 4..Q..gL.. &... c....$. d e..m.w.. S.... 0. 9..U....'........ ^ . . ... . . - , ~ ~ ' ' ' ~ ~ 51h.' hmF.

' ~ - . .

..

. ' ' ~ . acog3x 11 mo.5 r,. A 4 2 Fj . f 'I' 'Q1t $ 2. W.T f & g,c.h W ' ' L' .w.

. - .. s., . " . . . , , - , . L..m w,

  • *

. _ ' M NM. ... .o, , ~.. , [ '.

. - ... . , -

.,

i ,v.% ! - .. e :. - N ]{ *I M.. ~~". h e'* d, n.. b e..,.u.' y [, e K 4.c a. - (2f p _ g - - *- ' . . . $,,.4.%.p..,:;@.% S.&W WW,Hs....,. - %V.:M., *.4. n..,@ - -. 6 7 .4.. . ces..n,.,.u...v. _ a.... r.n.. 4,.Lw.p, %w~.g.. /. wmmWe.Ww,_a Q., . D.b.nw.pw.

~ - m...,:ry....... m... w' r, .s m.. n w .u .w.-~.._,... . . . .... . -.w.,... -. , ~. . . ' '. e. usa.' - " .a 87+ * =* > e**h. - e* v .- %* s ..

  1. emcw h t.m. e r -

.. . .. e ,p.. ' ' * e.-a ... T%*Y.&..O'l'- -.-*e-. Pe - - , !".h.** y * - - Y ': \\ m7 Y]'~',.'.**..* . . .;G f..}... *'k *?;ll' f....k..,C.[.f.R.*.i '.'...,O.

~.A ' ? Y.* c.l ,

' ,. '.., ' ' -h . ... - s . ..g 4. s - ,p , s,,; 3,..,.. #. .,. .

. .. m ... 3 bg*f 5 ,sg ,.,. * g. gg,4,,, ,,9 .i., ' feOA,WIM !)fb.p.' - , .

., <.. $I.b. M M &., M MI 8. AN. e,.A k,.n.g.,. Q(s;. [ h.' * g y.,,,; _ ., g , ..s- . . . nw.

- { g -[=9*$.Me[+ gey.Q4 4 der.y **W3 # -*,w,.-s,. m q..m p.,.e.4. w % ' '

    • t,- gms..

"ar**w &.. J '* h * a, 4 app. g.,s.+.e ac d.

-*,=,..q.'pa#=.* . ;... e .,g y, ys, .. .. ie? c. 41,y., - e (het-h.o. - ., or4%w.n 3 I,- +. 4.b.9.... )...~ -r ~. .. y-)w.m ; y,3 .e. :. v - s.., t - . , .?* .,,. Wg.i% ."-.sh P==w*aaaet.. r cf - . .g.n' c w.m'=-: m'a tv m - - ' 4 * m, p=. . .eu-.,'.. ." k a*?' **. +==- P"at.i.

N mamed 6*# w M'-~M.'.%*ssta sitba*MW,. Mare-F emia e '.; - a . ,.. . ' v - ns.- o < d.

6 4 %* W.:J,Q A D eu P W W Se M. W.m r*;M.Je%.p.WQ.?

  • M.b....';v,u.','
  • i-i's 3.;.f,F. *.%..

. y 'mOe Og e cg'*? "~

  • e;

'

. -,.q, y yq.; p.Q.c.'e j.4.. ~;112 v.. n( . .T s'.w -. . ak,Jtk% r.. <.w...,4 s,.so e sw w *J L.aa. re...x.. e,.... v ew.e , - M* 4 e,4 . sA ..

Qa s..~,s..

  1. %

d,.. s. w.. - *,,

.

4t-., ..,.c . M.. sd. .- a .t ~. mp %r.b,. I/y#f Q %,.p., ..

  • *y@.dert b '*/ -

.

/ fc%.g.qqxg's 'e Li-d-O m e,# z._M w . 49-;= es, o.s.

M.Qcy:.W,~. n : . m. % hs.

. . ,

- ~ wqW?v.ma f4WW@M_ - -.n

9..~.4 4 **%...4V..p4-MWf 8-f,W,W;4%.,>f.NG fWW@w-6 --

T.. a;.e. : M 2.- . -. ~ . n,., w.'c.j. Q b..m{J;i.QL5% lin&Q.p%,,$$n&,.,. . ,,V 'dl.a...c - n . .. .. .Qy.fl.g)1.y j

".#" O.sp.g.mu..:. h.s Q

m,. ,.n&:.:. 5,1 $%,&; u - g.

w. s. 'm,. ;.y,4,, e.:. p.,p~,,.,;p,.w... 4,. m;; e..s, y. A.yWs p,,p,4p.~. :%..r,m,.u%eg. vpw ppa e.p,yy:.4, .,,3. m yf.m 7 ; . , n .. v.,. 4.,n g.m. ~ myn,.1g.%. m.. ..:4 y.

.., ,.,.3 . .,. 4. 3 . ..e..w . .& . ,.#. 84 , m y.

~.d.lI,_e'..,% =.c. W +u,9,c . ,,%,. g., 3. u .*S.N.g,....a s. 9.u 7.5 3ww2 ,. 4...m,, , c... . n... . _ . .s % , -... .. , . ... ,.E..>_..s.wn.. .ew A.<.,. y- .. - . .%,-.y,

  • .se.

s g.,.o '.'.-.mj y'Mv. !"; '- u *~, W % ' ' ' W,%,,'r.h *'Q.eM,gy.,p..fl'4Q ,..e,r.7.t/ "%'V/m. i- '.g.

= . 4, .... ..e e pm %, m.

u.

g W%w.g.

+ , . .m .W p,..'.21 ,.

Q T?my,,. M % 2..*d.3.%~i. W:6 iv%i.,+.C M A e.G s. k su a, s - -- - ...... . n w.i .< .. u 3... U..m$g../ W. W..,? !>_tr ,,.,?" *7. r.+. . P. M.d, d.y 71..',.1 _

x.

ys.,' ar.Am - m . s s ._~ .m , . . . . % #d .. .. , 8,*

,geha +.M'.# y-.47,.e*'. M m., Q*d eri NJ.D .v -.d y e,4.b...., ,

mm.p.,,,vge,..% ,- g ,e

a .t ,y

  • , -

e.

s 4y-ww.p .q.

-.. . m m. ,. - %. 3e M m. m+.v.~.., m g.v W, -- .w u - . . M; Q.

%- w d &..-s-ps.~ n m. 4 ; 2.,.C,6- %.oo N "* y% .' ~.rg*. }g AI.Tg1,. <.. w.

,.., . r, c. ' ,.. %. , , e W.2 M e w : :.: ,l f;> e.cs . .. rumeq.;~&~.?? 2 j{,4.g costQ w;mm. xv A D6D.~,t.x1p* n~ n.v.hkgem;;,sby+,htkw,. < s n nc gg-4 v.,a. n. v.m ' - ;y w- - m-+.a w-o.-.e-n v +. .u 4.~ ..

. : - . - w c ~ .w. --

_...

- s.w.. s,.- _, - - - _ " J' . ? >,c.': ; u w

.st m. r c,.. w = um w.m -

~ w,

==.. - w, ,.4 l e e

, ,e' f '*.

e

  • *

AW - f

,

,.

- w_- .= _ . - o.,. , %.*. ,. 4 . ~.,,,,, -. - - . n-. --. _ w,.,4.

. % J '. "3=..ppep,.Fmshh a.see t.* r.., g.get. g %%.s ",dep *iras ei.,tW.,.s t -. g en ' hWp .g.a*3,H.g,M, . w, - ee" ggWw.y.ypse6 perA,4s gea p. p a.1 g'We. pses=.4'g ge.ge b.

dW M A-e..aa,. = Y?.,.c.

. s .wwy,%_1mn ne&...l. W"** Y_.*YY.5__m^ ?*._Y. a p5 .f.

N,h. 7...N.D.

W... T5~g $.v.m .v d:.c. w w-t,. -? w% eon p~f.

.- YY. y. Y A.*~ ,) ] .e

  • '

m e 'Y ..,1

.. ut -- . -,,, w . e m= e v W n w s JNw, : ,. g3 wuW:pu.M.e W p he* b i.W Am+@ w%y:

pa 3<.g,.g4 a;g e.* w p :p,wf.. w e.a:rer;. w-,, ggw 7 e . g * % g A v. g.w. m, w p:,<, y., g. g. a g.. f 6 w p p'mv._npgymw sp 4w d.i.1 W~ w p % sr W -

% g e.

. eg.

2.

w. r +.. 3 ,.n;A,;.. v -.. y.; . w - - , <s,w q,.. e q v.e - < ryu -w-cc = ..c g et :,wna,qg,s.p.n. n.:

ccerm.g.-
: A rM+ *$W=w%.* 1h::.w y J

. A2,. M r .. ........ gw%.. , - . y.Mhef'.h.. >. ;,

ry .y .v.- r -. 7. w. -f rg g-- *,g .se es.w .- w:;+... ,m.n.e.n.. 8' yY.. .e &*y.

vlL)R.g L.M*kaf.4 5.e%&&.*Q.hb'W.kc 'l'G'34W,'yy Q..,

Q ea.

, a.

sr

...

M_.w,.,;;.:x.n =, - ga g; - .- . w.

..,. m m.hr.w.ns s.n.s,, a s,o.m s n. m,,;,n.,.., n.- . ,ms.m r.

.

w-w ._ : -_;m a m

  • 2"D
  • Wi*

7,3[N.a%NM N 6I[d.7dkWi)ND'Y.Z*NNY.E5MD'NDE* N.IMN%YMMiNhD N %c:n-u., ap c x,po. w;. mth%.w%. &x,, u.smp@ep> m.,gwwww= p,en%. gno.

W.

- .m.n .n .w. s sx..,.. A.w.e.

.n ~m. s Mw., &e :% as. w e, n.a.

. .w - .+ . m .<

s .s.m n w.v . % Jr.R'29 Am.d e S,d.*~@s.At&s,',s'.&M. g b4W... 2 g.M. _~. pf +9R. *354 vim *4_ ei,*.E M, . .. p a.- _ n4%_Qp4Y$3' __.- .w y.

. s . _ ts p; %;' ; ,7 p (p 9 o[.a.: - g -. - _-a, - . _.. _. pi. sg..A. g / % i.

t..e.

_ ip,s.r d.1 pw. 4..;,. r,..,k7' , i.

. K.g. g, d; - - gEj.

c.

s ogs wt *.q ,A q*t . r.

ww .-- w p,*,-.'..% +t L.4 n.aW....a e . ~

_ lt

. -a - . 7 .M ..a , - e .% A r anu.+:*==w - a,*efS.t.P $a.

s' W.-

.

.;,,n g. =vt.

4;.s y * .tae.* Akht N.n%,n%.g.w.,.......tt..sv 3.

.D*.N %g., v m^n. n..n m.m..m -sWt.

+.d.

o.

- dM v.

p ms m. .....a s.w-Lw.9 mn... qs.w.wrt. g < pwo.,r. e.,.c 4.6%rS:NWs.$$dow.dds%.2C*2:.&yhg%g~d%g, n n % 41 W. ^W O

.hgii

. h f'. W M.

. MiMl ..g.aw.ms.p ecev.we-mim9 rima,s.qvmys waw.mm n, e, Am.m.m.-.+ m n ~... . .w.,4, .q.w = m,- _ - 1a + -- _....~ = =. r.- w =. n.. s ~ --. m . ~. ~ v ,m.] [ ') ' F,.. u% v...w.~.~. - ~,~..,. -. .e n m.% *. w.

-e.,,em.,.A.

g ' .m

0, ?...s . g M~h..

    • z

'*b* 4* , ' * d,. ; g; .. ,. ' n"y"h.9 * =88#* ~& e-$

  • l*

%'* 'y ?.h +& m..M d"%..N.<. t.j'R*$,. ' hh,J*.~~ph(,*-C'!&$.m y.dN '#* j v y r t..u .a,".

h0%r 9lp .f . e. ev> w.- ....' ' ' "j.. ,,WWr . w- $ C \\;; x m.,s.T y '?.,.w:n'l ?..c,...cm,.W. -. . m%w.W6.mM&Mww,...&n.q.M E' '

  • .

'M*dRQ CZ'p.

-

' t%ver Q tM Mo b,. 4.pe%.%..pM.:.< ;pW'M-& ave %ei+V9t*./y'"lrQvMSwuMGMWlJWMHNC9Wr??$% Tit = r , q. s ar,q.9.. y p. e %.mw yggg__,.,.g,g3..3..pc.agngegg.u.e. e w%,1. wu c .e . .

  • t

. y$C6f,W t t;%+r.%$,1tWae@M7"QU*@es(4yr.It57 %F=. .;. .w wm.%. *. m....,,. - ..,,, bY}-*f**fWt?,*/pfea.*.f2O T; 'N4 gg4.g Myn*@w','*gy.

.b $ .Ml9EMQ

d h h $.c.% &. w. Y. Y.c. x W., h N. e,. m$iY.! h+ u+. m w$. &.~9,Y ~r $h hk,...E.Yh%*,,*p.. ~.. , Y W N a \\ [J~F.*y.. ,.w. n. m.w

  • N+. <. g..,..~...., '9<.*MJfM.*4'*.

.,y*. , . r - + rw1~ psp e ,.m*Q MLkNM Y: c N.w^4 4 - r.

.- - - . ..,,,, Q.

- v%,_'.d, w*W.*}N*W,{.p i,:f%. ;*: & N'N.*?> e G Y -. '. . . .,u, . v.

" #*[dC gp"'

  • s'

'

  • .

r.,gg ggJ,a*'> mw.A. %; . i aa be%*. x+w+ .;d -- se ,, m - ' 20 N v* Y?i T. te = = - - . Y. t ..i. . ~ v ~. n? ck.f *w ?* " &* $y~WP..Y.dW., ' . s . . . .- q.

-- f.. d.n. 2;.1.%.?k... ' Gibbs 8 Hissinc.. - m.. c.s.R6A.61.4 . . ._.

.. .. _ - -

'INGIN EE R$. D ESIG N E RS. CONSTiUCTORS c), % .... y.... . . . v.

- . a m.m. m...n....p... . - - . . o m 4..y... .. . . .. m %4.D.S.\\ p..O.x... 4>j,.y Sp...b... 6..d.....&..f o. C..'... c.i. i>...es, m .S. 4...1 1.... *...... . % . . .... . ..... j ' endt M b.

. beg s. SA..G A A SA.4.n.

- . .. '

c . .... . $< MW W.

. .: m... . T g.

o.s% Y.t:f.

- - ,.. - s , v , - . . 4 . .u. ,, ,..4 ...e..,. . .... .g .g _ r do. f -

  • .,e

.

  • M g

, , .... w.

. . ,*(..,,*"' ," .

  1. ,'*.*

[.* .,, - s. e* l*p Q ,6y a . -

% " i " 3., - 4** . [ k N-h[,jj.[. - - {;- * ? '. , _ = '. ... e , _ , . . .

.. _..

, f.y. '( - ,, f.e..-..;., .. ,.e i... ..

. .s.

g., ,, . 7, r sur %. ' r.

g-. >.- 4.a M. 4 < . ~.

,<

.+.s , y )1 =5 Caghg Dj.$; s..a[.] Alf b #'%'a U :r'O' N.# b " '#*#'D y k i

  1. "" J S '

"""'*W - 2% ' : %.. plw'?.. M. yn.;4m y',;,-7.ge""r.o;t a.h' rj n w..

r.;E-W

.c ) g - . e . #.. n - 4 v , ZWw.

. . . t.c. N.. M.m ..r . u.'?. m..,:.,;.:;.r.. -

  • v w gW
  • ,

- p,ff,, *Z,4.*b: ' ;4. t ~' ' * * p:xt.s .. 1* ..:;. '~ . ~ ,, .~ . .. . ...,..m ...! v,. -. ~, ',.. ._ . . ~. .,, %.N. r.y;.%.Y...'%,.iW' :. *. T:f?'Y3. 'Qi. '>;c-N *C '1^" *:, ** '. Y '. 4.

..... . C: - .4, m-, . .... -. ..p<...' w,0 6 w;&v.m 1., c,i .. . . ty ump +

W.c/3 0..mpw.p,:..s,...c.-

.p3

.x..;~ 5 o . ., mc .- . - ; . , #. w. w : 3 t,. m - - . ; . . u.. , n ',.,h *m.m(.,->,.,.77. n..- ? ; +4.7..~.a* w -

  • * -

N#~ . . (. .

. - ' ' ,, +,,. .. v -.- .n M e m=ym w a w.3.. %.. - w % : n. p:,f.t,:: m m.;.s. m :.#y:,..r .,. o-~.s:mr w, w.0 a.=. * .

u.n

, w .1 e.. ww % e.. - -, O.. c . NOfM4'4,4. s -i. s. m,,, s 6. o -d M or- *. Map.aQa.ca./M.v,' bas **.C.I.oM.5,CMM. k-Ei.'.de.#- p. As. w f .

a b k.

M. w.g...r,e/ M,,W.&, %4 r,; 4 e v'@ * *N..!+ * b~ ', ?". +. r. ' . ic/f',... Pr A t %, ;% - ..o.. . , ' ~,. ., . p.f.C,..e - , .* s- ' w, . -. '. ",.. .s ' a,

, *

' n.

s ,-p.a .m e.,......I...- v . ,.,,........ 4.T/*,: . E p..' o .y.. # 4 JJ DV.i,u?"#@ Wfi s.. pf g T,.,7.'k... . -- , ,f A.ji)A ' = - '7).f-S ..w.4.w.p&.M.Q%g@?'. '%'4.% O.qMst.k gm.

.g4*p..? * ,p?.i ~ b.,a. - P - s qn 3. p..,. .. g r.ii. @.-@.,, ++9>*:+ ws i W ~ h, %;" u %. kPf w a &.M*.M..M s Q*Q4 m..v

>

f kmar,in .F ~7)4n x w e,5 -m.~. u. &..n *., r.., * 4 w..w...:,..=. gag Naw-f L..

.. .@.V.

. LV,,.8. . .... ... .(".rj nt L, --- q-' - ',4,,J* W ;v g. A..../*4.w'e' >r y N .l. e' - ... - . ..- v.

h <,wc.w. a *mw'4ta;t*gg.peah w.*Wi:ay-**.7 @g n

  • *.

.".8. I r., w

...... . "- . ., g p=r:~t* m m w.3=4 [r' n. n.;;-a -.. r w .. .g

'S e.e.Q.,g..; f,.:rg,f,,;..;]w;i,^-;,1,q.c,.aw.4en ::n.:

st.w;.'n

  • g+t+ e,x3*;y< v7 - -

y a i.

.,. -.,, es w =p.. s w%w..u.Q f . %.wi5...h,w ... y m ,..c.m.e...M.a.);q~.,4.;.p %u.

o ' -..g.4.

m., 5.m. 2.v.. % - .. S.s ~t ." , ., e..* /... . n. 4.,.r..; m.

,. . a .. S . . . n.- v,. - ....w.e, . 4.,.. J.

. A * ^.* Mw '$ ' ;;f**i y y;f'*in- + at. *w.* bb.

.~.%,W.} %ye'\\ V:q A,ts%!M.4,;2 M*;T.*w'NT ? e %:U.c=g:n 'Cr V

  • ** W" 3.J,.'s V%; b..

..,- , . %,.%. n J.nh.rw..~..:.n.**wc*..c..,.,...n.P,.h n t . c :.C." * !.... . c . .. &. -. .s ... /... J.s.. ..3t or.

.+ Tar .

ar- ' w* q-

  1. 4.e*%

sye = -+ "p.;p' e * O.g.f, y K

k..

  • -. rt

. * * . . e*** a.* p."g,, c.4,f.p, ' . ~ , g -*.h " [. $ ! d (

. ~ ..?. E .d. m #w a' 4* 'N c .V e m.m ~.y.~,m% a,,le - mc.e.% % :a Q ff, 4 x. $' p.f,.' y..,,. 5.e 4. w.m. w% o M,W,,'W a.,, ;"**f$y,%+lt.:rkh,]. % pg.y w$*), / o '.5 . w,.,J *.%C W.

- . m,,'jeg a.*4 - W.*H ~ g~%. A.

y 6,,,.'. a.. w N,,6. g ~.t... ...., o. e.

A .e,..%. J.. %. :.-% , . + f .

  • ~,bi

....[.,. 9,4 - s.

,. .. - , d&%m*!F '. sCW:?,%Yv Xss,ayWnf., A:etry.' M 2 ;;.% '. ?NW,m M.i,w.G4=.A 'L.

e( W/m_-M- ,. %. _ q y; = _ - gnpc.:peww T cp ye...guq ::'::t;&s-i;%W.tyt.p>'3,c_ma,4.rt;MWr*:*P*E'^@, a. P64MO w .t T

  • -

de w..- a D.*CCS A .W,-m ~. _..... g.. 6 bife'_. p _V,. _+ w - . W M I'9t'M a., ; i.;; _.a. cm./,...._....[5c.._.* - . . _.

. _ .. ..- - s -, ir dr a'.'+f- * 'a4 K %. **.( h 48*@ St M Attf.) Q W 4Ff'* - ".%.r 8'0G'4P S 1'a'eW"W%*8'edP* . ^ - . '% ea A.. e% er.

.rba./ 44e gf4. 48 9..pe..(.eD.S.A )s% 3.

  1. .e,*d w..

.i s? .~., P,r--"ar ::"m* aaw'M. J. t.t. !.?.2 M,..m. _ 2.2. s.* ip~':.?.r. n, W*.,tcwe a.z.%. ~ A,F'i%, sa^ Artre-f?t gWr.. A C.f#. n',' m"**'** " *+ t.- .

-

    • '

. n.

a sc.Mq,r a m, f .c f %

_... -. . . < T,Y

~ &y,.p*,.+ u'.-- - q y-M GC4*b kA % jd g 5 Mf, e l. W sw+%aN

  • p.---

+ . fi: e w}g% g.y ..N e.* *.si..v.g. m : ' a me s cc-4,5 0 w.f=is&;*g y t W.ng.% 7 % ** &i G... a~% _; & ~QQrZJr],r[.& g.$1..weemgwhe),wwW.afca e -

p , : n. m '* > w. m.:.; x : =. a. =. e ?. M f.' d. 4.* ' M ' N @ m.& ... . U..,7.Mv.n n.vr - g m.w m.my.m*Y .w

w...s..

ty f;.

.;<q; g' ans ~~~ ~; a:,- h.,.m.;,, ~ v,w w: ~ . ,J'_.d.. 6.Ranarevede swa. ewet am=e*+rm.e:*e.s. _4 Ek..~.fr k.

4.W- _, a D .Z ,:.6 #:%,c.vi ..,.,4 % 4.m. c_.Wir_.

'" J ... . . w. s .- . e m _... _..,,~ .~h.m.<e. - ",. ~- n ' '~Q4v%speseMw.r{ o, .r g*;.,; - _,. -.

  • .esymorep

.s.... _....,, -_ . seewesis uns ing g1Ms

  • <=e-o-s

.- emw.anmeuws:Tr@~.wcer.wwJ.sa'*-5%+ aW *Wa..:., r.co c.. >w.m: ma n:~:~ k fh. M~yp=cwwmma O~W2.gu,dn. 4,.'wu.,._i aW ~ ~J M pi ar?s,sW,$.%.p;..-.m en &.S..m.M@ey4+4aW@r'.M_&.4 p. cr 9, *,,. - -~- +~ getir.*Mep Tggies w e .ev4.,; *am yM w x.. n ~. m, .,. , _.. . mm%c. af %. e.:. ..,.... ~ .r , n.

. oep. n n&.w'*7 .s - . w k y.Q,*%. g i f.., _ _ Q t %, % p W.:.s H w m q yy n.,ay&M'.t*,@ _.

-- , - k.W v ' 4.

.J > .,, n g.pm.y,as .se

  • %..c.e

(_ .e ?

  • a.:

_ _ . . .. .- -'a<.,...%..-..,4.,. ,,. 3 M .Ag,. .r . ~ . &. N.w -.,, ?.A.<.%,.g. t* ni ~.y A$.$r.w,,E;M.,.*,, '.. _. ^ .. -. ~ r. a 4.7"y7:= U N. ~ N,v.,$ W's.96',0C?.*. $. &.v.5 D ]s~k. $~*.$,. f' V +.* %%...p . m ,, 7 w

.

. c

p%.w.4.

y .p.. ~.g re g,v _c.,-c.e eye es..,y@y/..g, M M Mk4? <. ~. w.

M'.r'td/s.fWesDriPhy : . <,... u..% y m. p.. m.. a g. 9,g ia G M I A* d ek.

e ,

.. -. - %j egs-Miw@%4M."lt 4h , . :.e. s.- m.

e.

d'j.'tM/d=r.

av.w.so m.,,,.u.m{ g.Det'.-[ g fg M, t m. w s,eman W~ws.sne.w ous n yemise w s . m--+ ; e> w w p ~., w m.r,.s..er w.z_c_c . ~..,, -, s. e.~.,r ,4.,p,m. m.

. v,. . ~.:~, ccc-- -

.. m .a . .%. J.v,, e..c e.m

  • he. %.g %g",. "y...

m.. .s, ~ .. % .,ve e% '.:.~;(=".*.i.$ Q,.7

  • /S_ $ [gy.$.~4 (D'.ww. '.

. .

.. .- , ^ ^ i?. ,i ' s

  • ' 3gA y qgp ? e. t '

IJ5$M'COh4M..

  • ..a..t.

., . M.M M fiy M.s,n rcrea g o.- , g s.>w.g nw .,t.

- , c. .

,.g,. k.m.y . .y ,.3a . v.

,,

., ... OM.' 4.6.4 'f+ W..<.i o.,.n, D.fdst di2.=2.2DiUM,.

  • f4 M'44 L bg,,2is ' d. @, @4'_:

.. ~, .w-r n w+ -r r - .wac~rmwm- *~w:1.wnwnsv.vnu.w:.vCWtentcriswckii.d.&R ^;~t.W.m=~,h*.aste:w7 'M?tw! ~ -

. M*.c"* Wym4WC474.hiq@d.r%5FAC;vgvfUMh#@A. t;3)%sim Agarpsewyesutd*ew ewe %.e- - 'E. dry.W nemrs..rf.e%q s #I,%.6 vy?_qd,+ u.eweg.mv.Cq.m::4%...< M u.. e sr *- c.,. W ww a.i p4 if,q 4M4 44.mi <&.4%=iG ~ ~vwe: tar.Wh %,renvtW.g+.w,/m%.agerrr.}n: A%WW.w, wr f.s. . r.

y-4g'+hw:::;;r;;c.g - r:..q:e'; *y/s..>O'%,n.,,,...' L 4f.yA,.Jf,Q* A.Y G'..k &.<tk% w* 9.rax C f*g.W ff.N/cW r.Frw>esertte M:,r , e $:*;* a6 s-M %%.h.W.%:awM'.%. ,. Q Q u,;ta+rf Qo g. n ++erv.h,r %w-W. 8.+4. - %.%.,.i g+, i,rk. v .m:. w r.n.yg w e,:W.w.y..* 3<p-W'gn.<< g.Ma4w%m.m% m . W%%w e,.N * ;n.go.L c . .4 k 5_.h,r,.e

..m..u. y: .r agA n. %, m,o m,w.,.. m ...y 'W> :WMr.;54#ds *W ' .n * rW-- Tr...M+%s

wr* yet - c e.u % .v.pm* e . 49 %m M r *p: *e.ws>.-*=.<u . .tr.. :,% n,.;y;.e.r.p.c s y+: 4 w. m-r-

w gafw.. M...c.,;.m.,,rp.*m o:m%cAn rg y.=y,;n g ;.m,. .Q~ 2_ ;

~ z t

=. .: m&.;p men.:;. # x.*. p.v.ga

w w MW ~ww; y _ - 4... g - . ., ,a - . e.

,. .- . . . .,.,..ai.

- -- Mw ,. _ _ _..,

. ss........_..__... . . . .. , .., . . .. - ... . M.rm c.<.G Ab.-@ %......$4.'.'h.h.4.b...... Gibbs 8 Hill,1nc.

~ .. f v . c <. w.,... 6. P i~cmm.s.mc~ms.co~swas ' - m.. p....a. RI.

- N w Yonx, ........

w w =... @.... TO..S..I./wy..... h.Q..c.......S.L. 4. 6... 4.1.. S...o.@.. C.. gg m.m.TtU..A.... %Tewecl C. M d; n k....................... '

. .. . ~

Q 'd , [M th, h[M.

Nd.

M .N N b-

  • 4

.

  • *

.d""", "* h .- , .

. ..- , ,. . . . , - 4.;- - g g t..,~; 1- - . . g... . _.,.,.... . , - o.- - , . . ~, .[. " . o.. e.

,,. g_ y, ,".. *

' ..

i . * ,y.

, i

,. " , . $* s e {ppy , e.. .$ * 3 - . - . $. - > 1., ~' %.3 g c,. _ s , i /.. % -. 3 s "

  • -.. *

g . .., 10).J .D.*24,fld .,:.. .,. ' ~ . . . . s - w . d.. L _': . .,.. . . ..., - , ... .. . _ v,.1' .. . s.w i w.,..c. ~....../ . ". ;,.. < . .. M w.

, - ,. '.. -,, .

  • W. TM [ h f.q,.sp'

g*p*.,.g,ye, s.q

g

. g., .,_r,

  1. j. f.,.I,

,, ~ y, e.

' $. , s

, . v' - ["*p'. .r.

p.y.., a. M.,. a .w,.-- . g... +g{N.a..ap~. 4_p,e, v4, qc.i.

w.?$9m;gpy.yg,tp g,. W,y,,, , A .W

.. .,. ;. _,.g, m, ; %,,,.g.. , Q*;*t.

.W .

g

- w << e ,.. ,.,. s,, w,.~ p 2,,..g ,a..s,. . m.

.,.m.p,,gs, n..w., ,,. v,7.. w s... *~.,.c*~.- ..a . ... a e.,.,,,.. m.:...,-,sg m. e,..- .,;seen. ns.m.s,,,,s,. ... A

p g . ... q w .,.,.,.,..n w,,. c %Ar,/w., +me...,...w ~ ..a.r-. D ....- 77 "-* * * j, 7.', g, 4,..g e s.. su*"!* .. x,- ,...m n p. s... u .c., .ss v# ('- ..

  • f a

, (,,} '* rff eg. A',. - 1 * ;*

..' ',' y,7,

,'

  • {

{ '* * s T , _, .q,,.. - %,,,...x%, r ._,,..,~.....s.....,p..,.m.

.~ . o . pgg,1 .,. .., ~. J. : ' @ w i;h.%.n 9 p.y & Q :.cw.,.y. 4 m m % % h.a.s>,n. 4 4 e q%%+ . s.u +N.g e.a,y%gs[.Mg.W i, p,, : * ; <

4 -

. . ,c+ '.p.7 Ww%,. $M *"*' '.f* d--N # *. m , . T: .. - - ',.c.

A% . .. _.& ..e

...,-,

.. a.c _... . . . .e m.

. n,. , ,.. ' N J * bF T,E 'f kk 'Mbid **"+***f '"* N'* *TM *** * --

  • 4-

. $Qhea

g 2,s.g M %geg."W h m O.m." q u. n..,v.N,F g"y,

A g m. p= -... '.. i ; 7,. , ...o,.Mg 3 g e,7g.o.sy qw c, . p .m.

3 ( ,p.: . , e, p.. a. %.,.s ., .. .~7..~ p. m.,,,, h ;, x.c. %w.,3e.w A %.#:~..%.%.v w. m,.. g, . ...r . - . w, w, m *.... ys x r.; .~ 4. g.

.a uw . . +....,.-.-s. n..u. -.. ;,.. s. 4.,.. y. m.,w.w. &n.yy :. ;., .m;y.

., - y;w.2.;.; y... y. . = ,

%...~-. p.n.,m...,.,.m g:.. Q,..Gh,-. ,a -,...n gs pm,,>..s.. .mn...,. ~ .v.,.,... s.y:. .a, . .w

. s., y.., A v.,v. u.

+. ...... .r . , ~. . .., . s.m,.4,,,. ..a o :. -e n..s,.. .v ,....h... - * , . 1g J., .. -.ar v % .*O.q , al U *M..,,.y.p 40.-#swi o..,o . % . .....r . ~~.p}g. g '.. R g3 . Q. y. g.l .. - F4 * I.. ?. O l7',,, .=,e . w.g u y, y 4 ; p 'q y'p q.. -v:> * y'i j* * .w,r -.'.S .. . _.

w.w.,s.g w;pw,wmmw.. .. ' 4d EM.,* me % w.s%'".*-_- ' _ ~...... %....s,..p:.#, g y 3 g.. . x . g e w r( _.,~. g,., s y.. - s2.,.a. g ,..f ,,.. y;4,9 -_ .. .,,3 ,., y,.,, p . ~ ,s.

g,g * . p g,.. .4 . ... j9, i . .. (*d * M. 'd. es a.s.q ".g /y.m g g . g N,.ana @eed . -- - '- -shn.st63.+.a 1st V4F i g

  • 93 tve a..

L a.gm --

r7 M - -- ) 4ab., M.Q,-tj e. eyW p pm.

g gar p. .gg3eyge.gs,;e.cee%ee p y eg yens.p+;aab* f'}*-det.'*rf""#'.' 7, 'fM%Q.s4 Y.V '. - '. J f~.r~.A,Y s -. Y$a.T "..,.... ? R.c 'W'*X5 W'?',-, '$. Ww ?* $0 $$ A i h X g.s ?.~,,.h..C &..,t.,,N_ a'D ~* Y . .... . - . n - ~.... .. S M.

.m.

. w 5.e.

. ,.7 .~w,...A

  1. ,m,

. e.,. u.

-. *. 3 u. %.,r ee %,% a.- .. . .., ty

c.pg* -.

  • _QQQ e

.q

  • su

.u. =g a,,,,

r,
W s,.~.

. %.

.;n
* y w.g,

z.m

  • e gnie.=.

. . .'.~.V W.. 2a.. - f. - o v +sen r>>e=neee wer%., ms.m.me..~.L;a.,,%.pf a y;;;.n.l$'%%..n * - wwwa '

  • m.s a ~k s,m 7..Q.p.s m.t e...-

...a,. . - ,. .. -ta . eat ua m

w. ': s v.

. .%. . . y,.g,k.pm y 'ew g7y ag.,, 4 . ;;.4g f mm p 4 y.~:,..,; D&k.pfg.t,,4 y.m.,,.% p 3 ' '.~,' m. %., 2... L og,*. < c. L (39, - 3.;.,;,QyQ, 'iR. 2.p,WE,3,.:wM;;.C;,c,:%...

-" w. w.a.W',A &.D. &,...,., %.., e,r w e ',, w. w w .~.c -m... g.w JmnWn.< g'.~ M,,p.ge mar.0f.% +.. ncT%'9M @g. , .e . .- ,;,;3p y.i.'d.,,1,h * 4. s , w,>d.% g.D,.?:%t. }&W.,, gp4,,U,g,4op 0e

Lg' ; ag bgw edge, ,,4

4 e, " bd ^ 4. ;i(,%. w.. c -- ..a.

g .s.,M-nc* w.- sWs ~ e;:*.f w Y @- % * W !< w. w?ww.n v.ye t un;at-ru. n ci ? -.. ; g...: r . .... m - Q' ~,

s

.. .,,. V --@mg, 'Jep,Arg.1, Ie wn, sw ~.. ~.vc.

.

,,;...x.
x__

_u '. ~. 5~ ., .ae.

,, v%'e .: <. .c dren, ar.n.

,, - me8b es* - " ^ _ -

  1. 8+

'4 . w..- J,,._ . = a.

4 +.au , _ - h Q.7 (h Q Q -DIM k %,%.p. ~'k % W 'D*T 91; E ~_,_'O'.' , _ '. _

q,.4 m..._~. . m,..~ _. e. 2. s.._ -. s... -. _ _.. - 2.- ~,mm.- _m, _-._.. x =r _ ,._ s,. = - . _.. _... _ . - ,... - -- .- - - y%,4.5QQQV ELZWWe5sM&Wa1%R$Qwy~. w'F+&-QYQM.

_ m.

y

,

~..n m ^ ' ,P M..w.

-. .. %@~. @yO'W EC-QWQM'"=gy ~. .... . . k ..<Qwep -m& f n A'L W v (3.s'.m.Q, m.%,AV.Y*{ @.w g;:r@ w.t< W,.4 Dr. 4 C= b=,* d *: w# n,.ih c M.4.. 7 A t p.. W g9 v.

y a u e n,~ 9 - .... - W.4M,%.y? $ r AyW.mn.=m.m.=w d.e%D,a;Ms.u,eh*:.c.Mg3Q=: n.trM* .

q=

. =- x=;.a.

....ww t.z= = m .: .>v m x-n .

.:w-~~,,mp v..re -w:,s.

n.o .r.-- -w, a.~. m.- + m.- ~;'c,e. g 5.v.r...MG , ..., Q. %)4 ". - ' g. 4.-seMD45.-1 @ y, M.*.GWWW % ~ Q.

~ ' * fLt+;f floccW-4-4 g<

  • ao m e - -....

. g ersgshtT _ p.f,,,.t - --e . m / L.. A. .__.

  • Ds
-- 7 _ _,',,.--, --- em68 * *nr + + ;. *^

g s.-.y..~m.a.M.. m.-,.. - +.sf.f*v-td.h.(dN ggwas..,sAmpde'w.r.w-* ;Ww-- e ~~e - -% J Mat:mmp ~/.r.7,e. r ;-r ' . m p e, W.*****,+s.e,. ed m~-w.@.a a -..y. - . ,,,

    • &

. * ' .***4i-1.nN M.5

    • /

-

  • e*%.'.* % --
4 am da9a a[sar - w' +,. -

.. . a. m*ma., av)wx.wpj%' Am..%p. "',,f99.; ~... ..r.u.[z& 2.1'.LGW"4pd /J1:2-w -s , gr wa. w e* Si,J4. a. mrw

F s ' ;.f. 8 gw,Woky+. ;pl am q Pe4 5- ..h - i s s_er ,/=

c % .$ . g. g 5,y g*. 3.n.

.. s .u.5, y.. . e... ~MkMMy-[NNh YM*N NY EM - .. ~ ,j h.(, ...,,.. k.c tri@ e., ,,s (...k.,.h...e...* tY

    • E ; I

- g u-~ ,.- . ~ ~ ,m he.

~ ' A.

' . h *. . e _ _.... _. m.._. w. e...E *. ~.wm. ' " ~, -% . 98.**- w m.

. ~.. -.. - . - en 7 * d" ..(* s .. .. - ., - .b w.** sv p= o.oew.e.-.. .1 ' 7"-r,... +,PMan VApoow=:.Jr4%. W e.

vm

  • r my j

. . ,s, eg.q,g M.ge a ., ee. 4 * .a ' f.

, .s

C < < A. s; J. E.,mpe.n., f,/-N. e e.e. n..ef.-vi.*,. k,,en*^

.,#. .., e p,s.., Ch * c,.%w eersg.N*. pey t mW ' s t 6 * '@ er@.,.rJ **w. g.,. e 7.

=e.i-- .as e 4 6.e4.pt. e' g. 6.p# 3 .#. 4.. * * ' ' *. 4;

+'4

  • ..0

. - ' *

.r 4 et d y, p.2.'D vs.. r,. a q..J.r.%..A. g 4 g *s*. ie,m..~~.. 3.s. 1.; ' e < ;.'.m.., . ...awM" O w* a.

...,gpe.. . % 6'

-.*..

  1. .c. -

wy ...,.. 4... gk g g [e v.$g,+g.' .C 4 %". =i.

o.

-. @y

  • ed O n'

, .e. b pgede.. e. g O..,y h.,.h,$ @ g [. -ee4 Jg 'Nm x ..%#.

  • .

.. +.n.e-v. d. w: g(,,*.. " a

  1. .

- ,. "e.# 4. 4.l4,WW,

. .-@.4 M&g a ee

,.. 3. 4.n.e 4. e4 .-#, h e.. ,,.- es %~.,gn,y (n,,.. -{geg.e,.p.4,p%,,ge 4 4.r. y f AL.=W%n.n.. u,spf**#.4rd**W p.e=d.\\= =. - u ..

. .v, - .- e ps. u*. e . ,q u.e.w, m.--., 'lW 9 A P M*U' W W ??. -n5WVM7tfr3'hC*t*p4'earg'T"nTa'veNG75M"Mr91F W ch@5. w =C Fmc' W.y

  • '

W . ~ w ' m;.y y=L*ZwWm.y!g G :t,:da +..g!L qg...;k:ngMk% s Q.*.G'%r;.t .;Ly%y.Qu:p'v % ". ,. 42.has e a.-. -. A -

..u% % re..ow w.... f-r e 2 . y,,5,&rz m S m ~e w amenw:en - 54,pmnnmnw e - g e .%q. M -wem. n-n mw h awc.>4 q w.,.. m_eW5>e. 9 g %g g s; e.m m s %r W. ,W de....,-L %w.;.; w:,..< g...' ed~%4

.. - ,s r- - - ...

.+m. &. w.x. d..,.e..m m:.~n%,*t'*.'. t-**m N ' t.,.},e... :sq. gg n ..,. -. ow . 4-m&.y~w-tv .s'=-y*- .x-s y4Qt W,/'Wt.\\n*M?. Mfg, ~.M.

,w- ,~ .,, n + y. .s , . < wW'r*A W PM V**"W. Mr.4.m.4.P*Ja*yf ".:.E**M'-/ f*$** ? ,. .. e., .m.. m. n., m.w.,. ' #' 'QB %.. JJ

W m. a, s...w.. u. m. -....n.m_.,w. ;. - a.2.m.'wn. r ~.v -- ~.4en o n .s n . G ,. - m n . . . r . ,. m :.v.-~ . . ... . w.+ . .- .. - -...

.n.. - . , . .. . _........ _ ... _ , , 9% Z2d.29.~...1 sibbs s Hiri.inc.

m.c 5M..mm- . 4 IB

  • x

. E NGpsEEES. DESIGh tT4. CONSTIUCTO'.5 - sh-st m......ot.

. '.. -

.. - -.. c. w ay..... ........ . ww w= . .C & H Job No.T..S.25 4... Chk'd/Apped.Sy..T. U..M.. ' s > . ... . , . s m.n R. O..G.i..j.&... Q.Q...G.2..$Jr.A3...G..L...b..W.....fo., m.t.w..rs . ..................... .... . .... ' ~ -- - , .., . Q,4f. N.,.GJ.

.h A A 8 k Gh &~ ' . -. . . kor.

c.o DL. M G QRfHQh % . - n . p', '.

. 9 _ % ['.4s.

- 'me e- ' Q J , ,. , , .

'

  1. *

- T)>S6 _ - - . - - - '-' , %4 ' G....o _ . - pQ ** _ - .- ' A J .. s S fe rJ - # 5,-0, r - . . / - m .,iy v.a. - . , . . > w

. ... . 4-a.,., g ,

...,

  • .:...

s.

..L . . ,, ....s' em. , , , . :,2 g.avr.~ c.J.64. - v.;a9..p t ;y,4..~.,.:.:._-yy,d y,..,.,.,, -- @ v.y e,.w....Q - e., 4 Q r. p.;. w 3. e.

. - - t,, , - .. ...a . ...ws ..._m... . .m. ce... r., . e.. u,c.4.. 3 -. ..- _. p.: ..r.<, - . <, ..g g r. ...m...s.~....,.,...,~,.,,, m.

. . .. ,.. ,..... _.

y.,. ., .... . - . _. s., ., ... -., ,.. ,. m y.

. , . 1,: 4.u .

. . ..... , !x~ ~.: ~7 *.,.. .3).L.s.

2'Z., C.CL. s 4.MP - 'e ,.,-. ty ..,+ a.>. m.y.,y. e.. +. ..s. &...w.

..,.

.. n.

,- D.D2.$ W d -

  • ,- :~ % Q' M,b d j :7 '

- p

. . .Q gg .. .,. x _

    • W W -

f Q4 g* CLC. 4 &.e *~0."$0 '** * *

~ ' *i ' ? W ~ '"~ ~ ~#N , . m.9,j.. %.3;.. n.

  1. N.15 *@,

- e.~v e. r...qc;;. c- : m -p-~ . p+ , . + ~x . .r - - _ m._ ..; . .. .,.de m,, e

  1. ,.4 m. w..., ~,.

,., <. ...r..,.,.._.3% , .,,L ,,,w,.y.;.e. v % pg,,a .M e y.,. .v ' . . ..f s.te.. %... f,. n *;. : 4 *./ },k sw @. m v,j.~-r...,,_~4 G 4l

(1.h, '.'. ' K ; c.

>.~.sc .s v,. w.,... >d*,i,; Ctg,.e,* M u v*.; . , . - ~ .t* ~ - '~ - w,. y<r -.-. . -4.

w, ..~.,2v...,- . ~ - .s,.., .. s., ....w.,.c,.., ~..,a m . -.. r ., _ . . s . z.y m ep.m * mM. %. . . - . y - m m.: _,-

._,vs.m,,v.s

. ~ .... .... ... .o . . .,... - n.

s,.3.y... v, . na . a , ..... ... WM p..m v.wam..d p % @s-s.-3xpi.;s.y..v..pg'.% x. s t.. . . y.~..M a.y.x.w.

. . p.' r W %.:.;i ' - w,y.:. 8 . .e c J.2.- w j.t._ M.. -1 8 84 @,-. ~._ + mm,4,4.ae.:/ u.,w.c.",~ -. 4~'~-e . - . -. . g. y... ',. e2.

- ' . n g,.. . s& . ..'a.

., _~. .,,.~Z--

.' < ~. _.., . emy-w-. *.~wnsmem m.d.,. W.w.+y +...MM5s N*.M M' I'.aw ~ipii..-.WU..,.+ k.i.3 . - r. e. cm.,w, s.

/ S.

L.m. A:i,g - - , - ' - ' w.2. n <%.,:, 4. J.~..... ,. & y n m p a, - . g-e.

.+.e uenw..v.. +. . =~ p'a-m i.. & :; m.m..*- r.nu . . M.e$A,*,%.n @ % C. A.s4. B.,..u. p.. g~ er

.A

. -.-. . +e .. +.. ~. a a,.w.,. c. n 1..c~.%..a...,s - me J .c.gs.%..,y,~ ...,. -. - y.s... s. > .. s.

< ;. . v. g .s - .- ... . .....,. s.m.#... s.

~.m,.,, +>w.o= is - r.. s ,.. . .a .. ..r.

. m 3. - .... .we u...~ ow ..

,3 a x -; s e...
-

. . v... a - ,, . . m r . m. r..., L.. u,. ,.. u ;..o - - .t- ..' -4.. '., ', : ;_,- W,t.;.t es.t. m,..,o,,, +..,.,., a. w x. a.......g;.y a.~t.,, p. n..g .

  1. ,,

..: . ,. . .-,.g.

.. .,o . . ?. w W.4. % . . K. w 11 .. .C . . .va . . , s. A TLT.*zsa. C q.,.*7., *. '. "....A..' .C . N.e M.V _Q ? %.N., . s.,<. n A.t.,a.w- @ @e r A,.. , c p... .....,.v.3.. w ....., ..

.

.*.s,g, y a,w ,% w.

...,. e ;-w, - . - ,e ee. A .N *3. e. * w w,w** ese-W.,.7.q.e.m p ; <g,. m,eg,s %,C . y.hy.e.t wp4 ey me,,.m a .g. ve.#.. :.... -._ p'. est ,

. .K.,'.v v.-v. we _,.v.y.3.q.* - a -

  • .%

- .. .y.

- my..,,,.; %s.

~ A, w, .n.. g.

. 4g., 3.. w %w.

n.3.. <.. c p.- , y +.. m,.,.. ,. m.u e.. m .,e._ ~. -.. - L. 5 c"*.. <.,.4 r9 7;I.,.. 4,htA.m.9W. -..,.. s % 1.

., u . ., ... cg.th:tesh,t rmrt Turg. .. - . - w.Wt.d;.M f. '_.

. . v.

. +. c 1..m e +~,.. c g e.,a. >.vu..e m.. vA e_s_w. " -_.a.m_. e_ -,.,.. . -.- m_ sw x_ _--_: - , .. _ ._ , . . . - _

  • bW$ Q~.h?W &. Ejh ygM.:W. % ' W & 5 $.%" @ W W G *? % C.?"C & V

-' f y E*8$;G'M%T.*$kWW".". 'M t .. c - ..... e.. 1- __ :_ - m.

.. _ w-a _ _ _ ... -3.~ g g.,r. ~ y-_,. - _..,, ~ .. _ - _n.m,_ere... ..s, -. . .- -- - MW, L d.m,u, p~ ~... e.m.w :.e.,,, m,,y me %r g~p _ _ _ __ :_ _ __ .a ~ ,,n.,, ...,,w y w,ww.=.m.-. .;u_ r.

,.,. .. - g 9 3.$.,. m : w ,..r m. m,. < w , ;, ,2. ~2 m .r., . ..- me y en'aiset ems .gJ.. . o

w.. e..w h cE.

a..., w&, % n y

, .c - ' ... nh..a 3.,.4e w 2 -w

, - 1 4 y.,.3c.5 x m.p... % <.w 3 g f..r A..:'. , %Mee md.m g .r-

. ...g u . . Cw ;y = wqD ~gsm.Wem; :.~ L%C? v?. a~ '.., i ' ~

  • .: :,

,* .m. M., 1.x - e xv.~.w.;r,.n. _ M. cy, ~^d. ; .y-~ ,h..x ux g*;M;,h.n QcG;M 2.*;; ;7Q ng;;d,. m.W.'mp w. f.2,wi,ccm%.L. 'm.g,:.~; ?:: -

  • -.a

.;..,-...,.,.: v ..,,. r.

am.; t!>. 3 A.o..?m;r.: 14. g:.: . . ,:ctX. ;a g.:-:' m: -;?-w DD..: g.me.4.y--Qq L " -.., ~ ~" - sv n ; T..;,. - ~;-

e. w.e.m ,..%,cp ~..g u, w w.,.; < ge w mww v.,m.. -. x.z. - a.%,v. _ p ~ .g . 3;. sy .

., . ~ J;.e, s. - a.. . ...m ,w.

. s..

m. m-.. _ - -. .yeo ,. w+%. ., yr - . . a __. w sw,.va ~ m._.

-- %,,w- _ m.m.

Mr m,.,.x ;.. y..n n r. w _ _ _ _ _ _ _ %. ~_...# s. m..._ m..n . - . . . . . wm --. _ sng. ? ttatW A,.tWamrytt . _ m _ ..m _ c:rapn%d w,wst rs+M.,3 pwup.,oew,5 ep,ivywAwev'%y;* s,r46. m.w r... awca,,:. ' e r c-ww #,M/atwanMgW.., - rtmae W 3 m *.7 M *.P,' h c W -. .y a ' a ,y .=;.=-., f.m.s .n _ . _ - -. . - ~ - . . a.. <. - - gy .u .-. m.n..w n.g @:- +. w.. u c. c 1, u n rs.,,,k; 3~..3 _ ..... n

. . .__. _ - - -. _ yW ge.4thtWy.

, p wca.w rerrg. ppm._ _a_ ypmespMu. yW e_ tW4.,. m.

.. .....a.e.

~. - ..,,. ...., .m r.. s -._ _ _,,.. % m.

_ 1.

.,,o ... ; c,2,,y.-w >,. a.

_n ..c 'lA&+.r -. w.% _ _. 4.'.,, # 'WY %'l.. -J.,.[ @.,. nr. 6..4 .Ww;V'm, m.. y' W,, r..w..,. _ n. %.h.*.M,, .. %*.9...t: h - m p K.... - ,,v.., nm. +..' ~ m... @9., s.~...m%- ,,. r . w, a e.

w ..,. k ith M v 6 4,i.c " % A W.

. < -w m , % m' ' m, ~. m.~ ., z.. n. y g.w.

Y %P. ..vuriA % %.s .,,...... .c.AM, ~ : 1, > % W% . T.- ? ' hghbQ jd.s hhgDerd, .ar.@. 1^ ?W .,siep v. ear.n...N. ydy*.w. :. . (/ a sA.a .-. _= - ... -- , ww.

=- . _ m,. ^ s, t.,. . ,, y _, w., w .u..,o,. . +1

m.,..n ,. ,m .e. m. e.,,..~ w w . ,n...,=, . u s %.a s n..m e ,r.w m. n.

., -n . ... c. m,;.;. .r.~... w o.....,..s.~ ne.v... .s,~.... 4 n..,a- - w . ~.. .. ,-.s + . : ;. .-.n.. w.

...... . m - . -. _s...:..,...._....c., . <.m.. , ww.,.. . . -.. . w<+.:.,. y .. .-. s.

.w.. ,. s . . w.

m w... x... .s,..n . .w,. ~.. t p...a..., /..c.... . .i.. .ns.u,m.~. W- * ... f n %.. - g.. .. s, ~.. .. _~. . r - . . .s . -... w - c . w . -: .- g . m,.s w ..

..

- .- ..ax%.m.n mw .O u d.

r n m .v:- - grG.e k . J., 1 mg, pang &Q_Answ.syyy ggpyreny..r: rm .,,,. 4. brre.

v ~g gy , . .r;;t.;.q R,Jd .., .,O p/Am*Mn-r t.vMr.w.eg;;. g.,m;.EC: y sera.,. A*h 3 W:;&C/.go.:.4 x.M;:s;;:M, pett.'pA:n gg @, we.w,G; ,7..i . %.s.. < k M xm.. g g.

, .s

, e.c ve 4% / * av.e, v y Ase,va neh%rw.%e4.t.- masur c su.W.

. O.

.a , . g Q -se. W.r e :fg e. s.c wrw y g t h - gg*m.

<y v .v.N i8&:e@i;g.,..>

d
: -- A. OS

.,,b AAkt ' y@kN. hArni m Mr.$, g,p*gt.d.r W.$. A*?.*.* 1.C.gs.

g ;r..::q;g.w w ' %..g . 4.,. y s ..,.. e... a..... . to, R,- P. w. 4s.-. . ..- A..a. s.%. ..b"' W.>a ;w i M p - n.,.' 3 P.'.#. vN. m. ~. .M - A,.,e A. W :" W W.4.. -.

.s . n.

.ue -.+- c w t w. m % -~<. m...v < - . -4 --,.c.,-~..~ , w m www vm:- yW. e m1mw ~4 a. c m pfev. y r-~. ..w ~w> %.-mt m.

.-s .u - -. ,e * , PyM.h,e9.. A.-wyna : , w - -j.., p?v*.v.M m-me* c g4.f.C _ f~ce,.c f -. , w~m*;s.%.%.N.m?r n~e.e/e9 n ..w. w y V.' &p 7 w %r %. W :.v. ~ wv y o e-m-t m W me< w s v -. c..~1 ...Q. m'- . K... h. y W : y * s.v,.. ,.... n .-< p

r.

.... ..c - . -... -..... .. , _ _

, - ..~ ,. , - '. f.s,.s J.%.*. y. >.I...... &lbb8 S $*$l$$,$13C, - m u.e c se $...f. pp. m... [.. . .; e. '

rs 4 .

.,... , ,

  1. ..Ct.

M*>- .

  • -c41: 57.....h *.h

. S NGINEf RS.USIGNERS.CONSTJ:UCTORS

  • =th.4

- - ..... ww vom o w w.37..Y. R 4..,;, m m 'Z s.2. s..e....- . . .. ... E : ' .....l.o...G..'..... w n, .... ......L.....6 M...CJ.A*3.....C.L.. a.

, .T.O.S..I... f..u.n.. .................. ..... . .

-- . , . - -' ", , f10dkkf . r fl.

%/ j.

d).n.

c/526 6. 4 ** .kI E j, .. '

.:::

, s::

-

- ,r o . 't.

. .. ~. " ', ' r% y " y c.'2.

_ Q f 6 14.S * k - - % - ~% -.' ~ . . .r o - .u. - - ,; m, - .- ,. ~

  • g-;',. ;

. * r

V ' %

  1. "

- - eL s 9 9r.7 M.

. , s c*

Qt.. . . . . .,. -... ,

,.. 2.

+ . ..- - - . r.

. - 4-*- A. 3 e.

,. g.

4.. ,' q - *, A & $ .-.1 . -. -. .% .. % ' , g,,7g.= . * . er. # * 'd

  • a sev4 ;

O. @ 'e k.M*,hh, 7th - .y,',- ) f h. 4t*-AA D h.eg4 A -t h ey os*W.*Ni.

MV$h"*lle, [, ',' ; i ;f MJjd.%.1. M.p; '*

e < w't , e ... n..+ s.-.... m. 4..,.f,. w, e# n, . ;g.w.,g. ;.wm;.. m... c. g;-. g ..e.,.mm. %, w... 3.%. .g..;;. w w . . .

- h m.a s Esewta e.yyg-peq m ,r.c.. .* ,.*y., ~s.- -t.. m.

... .., ..., > As - ~.a., s m s ay y c ~.. & - - ,

g sw @

.m* em e v.

es . . <~,,,, r e. p..'.2 e.m + y g,,, ;, g,- J= ,,*......pf ; f> ) n

d wuam r, ,..4 . v.

m ny3;fr g y,p x,,er'p ; 3-.3 y;**- -'

Me.'av Js 8 ') -

m p q'I " ' ( @ Nh ', * '. P

  • 4~

' %-

N- [A a J M.*. M.Em v & Y y ,s . ~ w,h m. y w";-r4 x. m y.gn:,y. w w a.2 %. 4: .e s. -. ;. ~ - .. . g en .m, .s . g# . m. p - n -, - -. t

~. *. a r ,..

N N O . =

e,, f pp d.

.,,., . ...y-.o g ,,,,g, . *., *^ . .a.x.

m.. o.y.,.. y > m,w..e.e.M.g., p $wg.g 4g.g,&a#4;m-QA p M M,% $n. n... - eann '

, . p . rma x'.. ~ 4,c

/, - pm M%o - hW 4.A4.M4W. e#5.he*,b.h s'Mk aus/r.JdA sd.s m.w e+ hr.. s.n 4.*/ w.W.4 r s b h.: e - <v .

.w.: w ie;.%ew.

. ev; -nu , -. - ..: :y.. >. s w., ". '.. <' $$.a w oD fo G 22.wtD Q c c.*]A %,n s W *& s.Q s $g;m y! M... . . . - $k W,C., . L. ' .c.%.mm. 2.a W m.- e-M W a,. ... ,,. ..,.g....... .. v.

. - ,mt.. . si ^..t.

. ..~. t s a w 3. e: r..,x ~. ~ v. r,'m a,.4em'e. +. . .. .. w. ltw < e ;e-w.p.* : wo~~%cym-* %'. - v- .... v' s.

pJ

  1. 7.

.- f -,

/,y.., t ax t. W,..a.a,Ad.a r.A.s.:<,u.4 Q bc R /.e.g.sgiggs,V/'i,g"'.C .9g a.,.Ed..j 3vm "':"%.y,y.p ~~t.., q rm;s w,.3.; _-m;mm,5 t4.>.6,, v.c..i,u.v ~.n.2-.~ -wr ;~ '. .. n,.g.~%. .~./. ~~ ~~ .: r. :-- :~'. r-u.ww.t :~ ~s .1+ y pe.>,M, & w : -.. W .,,.% G N.

? g; 4;.; ..r m. ..,n.Res ,. --gh..y. w,44pa.g .. A p.. ;.a,. a.

.n,,. m.,y. v er + 'Ide@.- FTCC2.72--9 W M. b r&_'S.*.__b..,.,,.,,W.m.w._ mew., S.v.m .,.,.,.,. we_@ e r.q ,

.. Ja.i.~w.. M,. 7 i S - m . _ _.

. i g enas.

l7,,Wh ... ,..~..~..s..~,e.~9's.e,,..%. . L._.

. . u w,,. , w .ye o g-s.

- . e p %.a vg. tv.s

., ~.cyte ht wo. ~,.,~%.r -m 't,% q.J > %,y m

,., . ,m.

, s ' ' m Ap e.e g n a.,e aA +,,

  • ~ n e e. y 4.

,,e----, . p.j,misme%.e , g

  • i'**"d".7,6.%, @.4s N *fa % fh u r:p g.he'ans d"m'.'

. s.s ,

7".* 7 % $# c.7... ..- M 6 2 C. -. * *. !.. *'<' '*w.e a'f $ whe Ek *. S N Y.d. D J..a.

,aedp.eggg'T.$g, . - 7I ' N* N ','.me *. 4 * -

      1. ',

- s' . %.es** ' ..M. t. %g *-.,*. W. y. y."..'%.e..'s.

.y.

  • '?

" * ' ..w s.

+? -.> .. ~4

  • e, J F p**.*4 *.. w..

g-yee i.ypt .p., w.

Q=$ 6. _.* g ..ag - , . . ;L.*;a, :.t. 4;.L. t*: ..,...f.. 9,. j.gf..g3 ; M.:..W.g _ ' yo',%.gq'..;.u.4. W,,,kg n f,4..Q.,.% l ? > : n~ 'r ? ' ~ Q %., $. < p44n, [.

, .c e gs..,.,..r . L . jd,.., = ,,. a.s <., ., ..,.#. 4.g.

a,_- m.,,,.,ea... , . a.1 .; f,1. g. . _, , e,..... v ~.- 4. r., s..w.,a , y9 p.p ..-4.,.., ..., w 9 4 w.J;.,,T,m., Jf f3,%., ,p ,.m... , -%,,.m.

t.-..& , W M ; M g& a wb., w.3 _m u.... ,. a.y.am.. , p -. s.. n..~#.. ; ;w w :.% ,.m~.2-wv .. . w.

,+w e,. ~ dT#4w.W,, Wv.~m...e. . w? 4 9-y - www > . ..; - . . g.

s.,. y . ..a a s . ' .#.- . u %

5 6.M / jim'My Mh'X5:

  1. e.1.Eg9@&c.:.i,p;;;s.c,,;4;g,;;.,;g;,;;p * ~,- ara,W.y % % *N ~~_m.e he-we y.w_'+y.s - am r >--y1:g4,;

9ta Q,e.Rf 't, '_ S . g ff, W,=.g,-7g-*T m t e. r y.

= s _ q-M*yW2MQ4'eWyescg"'.,M'@ M:%4.Ms;:af,g;rg.,p., pop gnglp,; T*;y,ygg*g(q:gg,pW . - - _, a _ _ - _ = w.

=. -_ -- = -

- _ u-_ - - _ ss - s.a 9.ed,n a. maw.

_ a. ww - _ _-resear_ __ u. __ v _ -_ __ tue.aree.ea.eseewee --see.

,ae- .aws e.aes av - - _ -- ,.. _ _ .e out.*aa.eaahWowe enk.a - _,, _ _- - _m w t v.m wsw no.e yr*9.' 9 %.orh4 W es*** W. dew.,.- - _- T._ r- .- __ _S'."_----- . T_ee C -^ " - _., - D ,WY... n.... # .Y.Y_ ?.,b. r.$..W...a,r'u.$Y.Y.

^ C~ 92 4 s..W_, q~. .a n f.,W~bt*, ma.m.W,rt.a.5:.Y.

Wn W ^ r ^~ ME# ^~ %. .,,s -_r ._4._, Qg'.- ~ --,-

a.,.- ~v g. cam' ', .v.,, g&'. QjN f..... %...-.M. g, scar.8mM.t.. y..g.. 96.s,5. m).' % :s f..+?* &. 7., i nt. Q.' h.r.g. % ,,f h. e. g 4, . . .,a .y, g w . r* ev Vet.w p ,. .A w+re

-, =. . _ _ _ .% v .f.,. m v w 3 b'.W@.Mf.n.,&.e$v$.'Y, N'l.f * .mh c... t ry.. &..g*"A'o@WW w&* $* > y..Rj.. LM * ,,, d M& %'We% % ., wp

  • tty,

7u 4.6 mm

w. r$- -

n... b IPCf!M * *v-'-~**RMWF.?LW"2'$..h.

-[...fM,WipQk.IJ?,W.$...'. 6. W / MM*4Md'.M ' i' / .i.e.u:g 3;e.. ;-P.t. ; r :.,.r :q.n.~;.m-e :;n. n,.ca.::;.:f;;* v.

.qh g.c.:st.::p.t ::rm.y.M..',d.lR w ; _ a- -. -

  • '** *il* 4" M**f 8.C'.*kAa w.fcg4 9*M* ppm *{*= Y't.t.e *f,f7*.if.p]td*g ka$g %

a'o* - gf % h("f.' ../ **N ~**M'*

r ' 8.=;e Way n"g, u.a e;, - , ,w-m ut.u ce.. -. a.. n 4. wg. n. p c %m;..q 3*m o.wiQ.&,. _w g.1 %,a.,s .,y.4g g.- N 4... r 2c. WQA

n.w.~

...,n.

w % u. a. M+.... +... f,.. n~ . a .. .. c.. -.<.. w g-.,.,, 9 ma.m .yy-op g o y.

. an .r m, -% s.m.swa.o.wg.-., x n.

. tw v _ _o_ y c ~ _t z y., h.DIgD[.M MMM Y hh, .[tygN hsNr.h - . ____.,__m .....,,... _ _ _ _ _ __ _.. _ _ _ _ _. _ __ _ . _. _ .h.h .( - - - ~..- DT[.,,Y [[Y. v'YeSN-8.M 7.*

  1. DN7M

'*S*eM*ll~M. qa* yg7.s;*A+RW-"wcm% a mqm,.mv. u wi w$sML* test"Mi@Vg"' e WQMtmi'd9tr**G_"i/ _ r.4. ~PDa'? +- ec. :.3 rsm.- .w.

. 4m, . , .. . ., ,,,,,cc.ggwg.,,

_, - W - L um oe._ ,,, _. o.,. . .e.,. _, e 7,.%.....u.

,. -.,_ y - - %., ab - ( , ... >rn%~.,%.- h

.n w [ ,,J:.m..-+b- - n..-. a..-..-n-_.,,. .. n- . -. = ~. - - ' . Y) . Y . h $ . n. -...a.,, n -. - - -m..... 4 , - .- - - - v...,,., . ~ m..v w w., ,,r -,.c. n-e4.4 y.t m.. . ~-, ..,.... w_ ... ... e.. . -m.

1w _ - : _ - - r -%-

- .I- .> - - - .:.w, %,n... , .f.

, ..- T . .. ...m. m.g2w.,, e.m c.r _- ,. w __ .- w i,., ww: 4. m..,pww.,,.. -.~._.n.m;gtws e - y.:, n.;. .. ,. .s.

- . . wm ., , m e.s. .n... w . .wn, t.,, ...e. e :~..... w n,... _. m,t. . .. m _ z. 4 4. NW,.&my::'G.&e...a.&.g3w~'C%2M%%,,W:;5ity;Ms.Mb'M%@y$$p?MCq;;d.k.%::%M,9c.

w .t <.u r.

.. .s .. w.m.%p~. ~.: m. 7 ... .... _.. - ._

.= 1-Hw' m
% y m Www M&.k.y.: M O:%.%,

. .

WnM & N T Wf W W M *5M M WJM M 12'5B m e W W W h hi-R $'DNentowy.n, W._.; aE J ww.=wp.s ys wa V, i+aa mm:.W. tor 41 Lor %,u ##C;;c 4= SAM.e.M.aqa,n.w,.dii ;W.^M.$.v Mmr%F,*ps.4%+%ew.am':W . w$q - fMc 2.m.ae pc%Es: JMWW 't au:n. amu,,y.ss,%a.4:a:k:4,u.

p ba;.. VA &s:* elvi$. h r W c m m y >*W s:Mv.z***AnMcMNm rewittWmd.5%4WWm-mMmc:Mrsower.e.

S

  • W W M Y M ' M..i 6 t P ?., q.exe,.,* : m.o.,.?%,-M.a^ttM,. o.Wx.?. z.,f.MM.s.; d'Mi@?f2 *

' 2$3'.hW.m. m,,4 uW.

M m,.'. '. 5W 9 7. M f.

-'.%% V.w ~'\\*.[fs.pt.m'..;;*P.~.dy ' &.t*n% ,.ma ~.cnn',A AN.

,e a. ~ 3:vt.4-W h %:.C ~m. % % m:..e.g..; nYt.ty=-t=* J= ** ?m.ve. paw;w%*y:r-w=. >,# a.Q* yw--,m -=='u ., .s.e e pe.-=%..e.e" - m n m:..%e * -.

._ zw,; ~ w. gw arm. g +m - e

  1. *m nw

.t M % h g .g - v v = ws.w % m ,- c, -.p p.i.e.w,M p+ re.y,m a+t ewsery;W.-..vm 7eb;n-A:.4 m.x.q c.u,4 hlb.,. . v.r.s ww- .u. m s .. v w Mv,_.W + ~- ,p:. n wean

  • ,hea

.n.w p.aeress noa n - . .m %..,.. g. 4...w m_..y,g.. cerm.,,. g.g.;g,w, s..u.m....,s.w.9yg w m...eA.. .... ... .., - ,.,.... ... .. .,, - . -. ...... __= ~.. _.

. . .. . . . . N ~. :.y:.&...%.hj.....l.

Gibbs 8 HilUnc, a., c.a. M.

~? Y s w x. W.on.. Q.% . .. & m,.....k S:.... '

  • mD m s.*s m '

mwyou.

'.%.- cwo,,,4.3,..T..it... c.s n s.m..T..B..W....... - . . , 3.w.]l. ).s..t...... @....m.. S.t D. G.. s..S. I %... 4..L.

b...' D. 6.. u. ws,. w..................... s - ... . . . .. ..

)

- , , . ' -

.y

.. .. . , . SLA B Mna..GM 4 GA44A.

b,.-

~ , . . l - .

.. ':r.., . k. 4,l.I.$,. _ g.

v._ .. , . .

., .,. , , . .. , A .

d, {. g . g ,Y 1 gJ

u as. . - , . - , %a . v . - - t > r . s 84.4 .,. . . . ', . ,e . , , - bs6 - .t.. ".e.

~ .

..

s ,..- -..,.., y , fp4 - ,..% ., si.>W x. .,1)

  • 1% ~ C,f.Q,'[.~:. _ ;+.9; &m ~p.y

.--- s N.

. )-.. ] --) . 1 - p. ~.g 9,,s s.w]a - a w - .y.

- 1 ... ... , <t-v:, s..... t.-'., u+%.n,. u. mw,.-. w. s.

v.

. n . ~ ~..... m,.. g.. m.

- s.. w, :~.. ?g

  • J5 ; *

...% , -,. c... e .I .h., , - %....- c.

w.3 .,- . ... ,,, ..... c ;..... , ... - ... .n . .3

. 7'

  • 5

' ' . 78. *, ' - ' ',,. ' . .e , . cv... J -

    • }

.4'l ., a.J J.T* **{ #: , . ..,. . ' , i = = - - - - as ~... i .... - py;jM.u.

- ~ . D. 895,k M. 4, .g Q' :< $ - e,@.g'. M 4rw 7;p - p y,(1d.fiJG M.w. a 'f g. -4.o,. + . , - '*.h ' '5 ~,' P l- -". *

' . ', M. :. Q O.;,. 7... - > p , n.

, r,n...m . 'w...g,:; w,, n ..NA-e,o hA.+.y,s-- Ax.~- er-.= U 4.e.-. p.e. ^ ;.~.s e. 4 w.~> .v e., - d.. s e -...,.w .....-, * ,~.;.~. 33. j,g,,. y,a ,7;{g. .g .{ W h.

h,; * * - g.( p,], h. 4 g - -

(- J[.p.

+*.Q$'r * > ~.4 <.uar ,... + .... . ~, . -. -.- - -. -J,a

  • '

.e ,. .g,, q

N % -h '

h..e

[e g e.

.6 gg gg g g g ay s e,g ,p QW p..q y g{p 4g g p ,.6 j l ,, 9., , p . : v.v > - a.ci,w Y,,.a,L. q A L.i. *'.. ;.wg'.~.-a.i.m..,* v.:.

s g. ' ' r..
  • ..

.,o,&),4.. e %. i: y..,,, ,, - z ( %..- e . m < (e s.m,_. n._A,...., _. 4.,.,, = s.~?.:. - u (d h ' t p, p . er' ~h,J.,;. --, ~ . . -. ,...._...s m_% ' !"- ~. kp. s.k4, . .*.i....<<.. .. .[ _v '. 4 Y. N,., 't d...... ..s._ .. , .. . , ~ . .

..,.t.

.... . ../imi1 . %D ? 6.a t

. f; F."J -t.e' 1.

d.g./ 4m,7. ; -ry. Ar" 4 b. h % t:W M yr.jfp q}p A W.e p W g Se.# c.e t e_ ..#4r.ew.QQ=* A*. ' -. . c... Nk . ., ' - %w;c..VF ' % a.weswe.a.4.s&@W" WW9)?d.c.:.4em=y ( --4 a.;.. y:p.y; l.a y -..,,,~,. -......a...m.,. >,3,m.,.am.s,~% ;.i mm--. Q w u., 4 u s,.w u w.:.4 u~,. ,. . m._ .., . - . . m p ~. =. ~ -.~ *, a., r w.J. . , .h,@g.e;n.; 4 n$gsa.gy w w q g {;;g. 9m.3w y.%_ q w.7, m maq a.a. g r,.4, w m,.m m~w,. s 5 _ . .-+ ~ 3'" 3 3 ( W ;pe g.a.ar.4. :. :.4',a.c,y2. t s E.* p ".,4 g y :g %. w.;. q p g, q :y;p. Q. 9: n .2.m.gw ir.o.g.m, a p c A.3,4.. A.

m . m. y s.

.y fx & M;g,;. . m 4.*,u . mw..,., ,w.c, ;g 4.

D.;,:s:,;;g;y 8.

' h.ac.5.f CD a..,--i~.W -$,u c.,.v n. ?.v,..w..n.w. n,.in n,.,: e. w. % ~ A'

p.

. s.

,.a.

k .,*.w.- u .~ ...... ..

,.e

. %. . p...,s v A. - y 9. ;: '- v,.4s.,.~.d-w s. g%...J,.1..w ;;%. _d ;gw' k m.

._v;.s. x.... . .. . . ~,. . . J, :.~e . .. . r.1 '. - c V 4m.,y%

.-cA.vA - ~ e v.. % % <.Ty; C$

3 g -,.:w C./ -- . '. '..... M 4] 9. ..,.n f.

x,..-- . > - . c N..",.:..;.q. pj b,, r 4,w .t - 4 - .- - . W.

W.qw 1.s.4 ** w,v-t q P &

67.WO..M..,.We *

. c. L.. - mw/ F. he..- .sm,. ye,Lt.M, wc. meg,wno.3..,. w w. w.$ _.i m 9y.m,>,N.m%4> ' N,.a 4.. . . ~,: ,.. W.

s.

. , p.

. t nv < m- .,. - + -. . -,,.tv y[.. .

3,.+z. e&f. .e Am, s,y.~ +. L n p e..-...., -. .e t ~,%. .e y c; - q dw u,,..poc m -r :.y, . m.

g.. ,% e Qmn e.t %.q,,s.,9,. g%Q--u -~ef.'m %. Dcp p : 4n. w*de +)yung'G/ J:w: ki a s g,, 6 f m,,es..,nj. &.-.t n -. w. p.- - -k. -

M..'ad.sn' * :'_.W)h g M, $ [. u n. 2 w L . a e-. , $r@K*@gm.m.gh; e % y - . -d d k~/"% - . .m.

s 1rtiit'.jf,P'{.Y';U.l4dM. e, ' a - $~ e Z d 2*i % . .- - n.n_ _. n_g . n; . . ' _ _ _ _ _ ,..... _.. 9 y - - - - - - _,, ,,. .m _.. . r4* dysr.gr;gJs y.jd,,, d % g, g.w p x =;;, g g g g.k M i p w s w g =y g m m m.

..

- -.

_ -_ _. _ . s= ,.= ... - - _. - - -.- -- is..-_.

.uen - _- - ~ - _r g.,4 ,.%.e.. ,m w $.v.. -. +- ne - -. .- .u.

- .,u,. ^ ^..,, - _-,__----s**..g*

O, [g - -9 e _., _. S,P I'p.Wbd4$.mw ~ v m w.~.-- e *My W M h.. *. J.=. - ^ ' , , -~ _

w ~an.-

$. 'y'M.

mou <%e. m.rx w e.rt .s.w.~. u wd MWY D<.m+4 g r - -. ~hya@i.. gm.v. s4M , y.;ww,u.g.a.Mm,v6;M.bom%e,.J ' c-

  • 'W Whe hN

.-'T , gT%g.M..v.m 7 --. n.m%y."pw'mTaW.Wg.

. gruder== 7 C@w w .~ h. gas.

y* .,~,,Ww, e a n -. ~

.s. m. g w % 1,w. w.4.x. m n. W.r M. d 'in.s * %.a.y[gy.w.3...c::p.w X Q M a y V 7qgn y. v. W,

.

.6%

4.wk..v..m.w. u - - -a.- w n,.- y . m.

~. x m.u,. yhn.- mpr . y ~m - x.- - - :...a. gy=;.y-~ x- _, /. = = n : u.n.. ,; .: ,. : :v m.tv

,

u; r..= . . 3 7. o. 9..uwo,.s.$..... a *L'* Win PWer *'fut**ps -WM.,.+n. C **~~,i *"4.%., ,.u..: G* %% ". *.- . a" -.s., sw%,. &.q *. *:: 'f.(e+(.m. s%.n, * 4< s c Wa t '. " ~ ~ - h - - ~.q. ;4%.m sq,,,1 % - e.

. ~y ._..r.

o o p+.e.- w,.a. ,.4 s m c t.

-.y d w . y .m .y. 4.. es s.&- sna . . - As vp g,., ms.a.. . ar.y....v ,, ' m .: m w., y ., a.

- W _ [_4 f.i: "_"" * * '. "Y

  • I T * f_

f[ d 4 N _5 VI d M* F O

  • *

? ""' - I

  • '

_ . sew.wwer:.o.w:nm-*ymwr m.mmw.une mexswmwramwnnww w.y= T'.". WWi**"8_ g"A"[@p***y y A j'*rpG{ g@Q^5@T*WfM]**W?*"*fa'*Q

    • 9

,-,.,o-e, v % s,,.s.g.

g y,%3.,c%,w.m %.,, %.ws.,,.. c m .,..,., # e. _.; w. ' . .-

- g . g " MA G' _ _ "*1 b . p n.... q. %, we.. n., e :.pw. m,, wem.+. ~., +. m, ;-w, w.~ x ? m -.m . n u ,. .,.-. b, ? M D M, N. k M M M... ~ ?N?id.c.e.~%,*5... .YdW89T. =IS,9_Q7CW/Yt*/.126.i'W- ~..v wu. a %. e.e.

.-,_.A m.~A. r.g : % a. .a.,. ' w,. -u m r .. - - n-

w.

n.

,,r v.m aq.p x y,... n.

.m - .. dM3argg.*[th ' O* Y.N*Y:41.d2M:~. ma. p.',,; p p gW teL9maNp=y.. -NbM*MdMdMobekhereM**tt%Nh!N4.M,[p mmag[asd ' . >. g.

+ . e, .n MN,W.

'ti/N*MM'esthkM?. ' " ' g y :_ ; meus.nw: =3mssgr.A.s.>.nyncp mam, w.a entwy'nym,asswom,ay.w -~7 -w.u.w.na.

mcw e @.w . -- _._..:_a -

w.,w , - - x=- .. t --ep s.r pe.m mw-

= =.<.

e**********'=ar=6*=e****w=**We.**=*4*****=*at=**va*t==***

=r.

  • er.1*.-*.a.w-m.r=;/ A *=* w a

.*W .s> J'. '

+eva eem wee.

w. e~,r n. e t r+-* # "Ts.n V. - a*h

..% %%,. rri,m. a, 4,%, vey-u. g-,t..a+ w y. e.ves se q' W' M' ' "aQ'?""Us'-"'R'T*! &** ?C"5'W'~t%W a%.ae.-**v; *"'-et.v' rem.h.as.w= a. g "w'2RM"'C + .~-*'Q ~ V-s ,.,,,..M... "*; W' 'i'b' *** ...,."3L. W ' 1 *

' ~ ** . 1,..I.%~,7.,% % V.t.-l'c :'Y..,. ' _.M_.

"2'*

y s M,v.9.e. n.,..'t,'ih.s.1 w. S.Cs.M_.~.. 6",'*6eW'. &..'2./.s J.4..A';"'?. . - - - * * 'M .=. $.. . A^ - - [,.. - p s aN7 P.' * pWY ,, ~ } 7 '8U AaM " fp 'V'I6. lp 4%T-G'. 4F Md[ T ..w se. /- - - . 1 p._..,. g p.. a,. m. J A.4.- W,., ec_-. It . , .n .. M_W.d.2.e M. g. tw4_.y%.M___ _ ~ -- 4- . . _c A.._,,. w m__ _b *.. Wye < Wh_ e-M. _.,. i h .ts

-. _.. .. __ _ _ .. C _ _. em,.. . _ _.,. - -._ n Mg .* M*l4d85T M *T4 $ UV'T W d ,-'S %2 t7#.' h T WM '.Q*'.. . n . .,,,

  • .

. N . t e ? a a, w.emoam.rua.%9 ; amur,.:v.:sw.n.a.e.w eg= i.e-s.%.wwW " c.e.:

9.h ' 7'YCA% y.21*4*1@4W'f%*d"/W"" ?#M?'WW~&@d'*%*WWW80C#W4??4M.*NE84*W'4A*#cN.*'U*h % V M rgy.oJ+a;.w du.es.e.c ^ W-. e.

' " " v., M... t.u:%,3.M-.(q,.- - w n.1 5.. .. m - s.,,r#. e.

.n Was.so , wig,.i % * s.g .,.l' % w. m.-w.,a &= %%. f,.r.r.w.

3 p.r,,, M.i@.. ,r+4-e -- . g['G +. s m..%g. e - dw.y.w,.g' 4 2 m..t.,.,,, %... -..,.v - . - ien . w .- - w%, t.%. p.,.

  1. -

. - & y9 & ' c.v a., ..r.

.. 4 e n3 N'p?$(hyy.t: m,' ?p W .. .c e v.

Y t.W . .y we. m Y ?. rwc ,7.nere m.'m t&':" era,:MW.h ry,~,, g *ifyt%)$(-[4,4w.:* x t.n. v-cWM.A. h,,. <.r

Yh W** N

  1. YN
  • O

, .f YRU '% M d W . sM #f

  • -

-

- we g-u:*- . . Wr m: -&...e.etcy**e-rv*=:wr?.h m;.*e WW.-%u.w.u..%g.vwyrw,-W,-- o e.. e. W v o.....r w w t.. A.

.rce-w W o -- - * a. g - p e y.

w m. m,;.-# w:rR..- w e._r.

~ y ... e...... q._..... ~... . . ..s , , _. ~ - ...

_ >= . - . . . . Kd6.:M..' W,.g....T:J:.1.%..... Gibbe 8; Hill.Jrsc:" ~ . g m.. c.s.

$ ' M,...h.d. ... . M..&.3%

  • *5.m55*5.*5 - 5 5

< .

==

c'. c-m. E.V. 2 z%.. .v ow..,. - , . .. ..... , , m.a..O..S..I.. }. w....c> &.L.. %...... $.L. p.h. 24.S..I.M........ u.o-n,.' m..$....Q.1.1.l.......... T m.

. .... -]. - - . . . . $Lhb.

SG54 % 6A 4,' GMA. 4 Lalo'- 4 ~ ..

' E, 6 SYdh . . . , e % '. " . -Q . & '. . -A .. . _ . $ E I O C.a h $ & *,$ h E W. $. 12,,

~

.. ... .. ,,.. -. ... . .. . < . . - - + . , . ' ' ph [ .Q.

.. $.. s .s = . , . 3.n - .. % , _ . . . . - -

&. > . p

  • a. *.

m.

,:2 %. 1. T... . .p . f,% F - . .. . 4.. . ar - *..,,.. , ...

. ' < '., .. ,.4 L " 7g.g,'.,7.y

.p .., - ,. < - a*. g .. - . ,,;.,,., ~ a, y,. j- , ETY*M,WF, 7 l g 6' t./* Ji,,- k~5.. , %sys**** ; Q g

,,..M...g. h,M' p .. e., m.,.%. b.Ag. 4..r l , t - g, 3_.p ur"u. A. s.sp.i... . c,o..A.., ,

  1. .. v.

,u. t... p.,. m.A,.. .m - . .- e :.m.,. s.

.,.,u Q n.

.#... -.r.

.o '.9 f. r;, ,a..<... w .. w - . l e .. J..r. z.

wy-+ .n -m e.s q . e-(u.s..7,,yf;**r: .r, s w.-.r, sa y. Q : .& ..y : t ~ r * ~ ' ~ *a V. q UM.3 j., - m < -. ,, . + a..dA ' .. M D g y 3 g,7,., y, [,.;,% ,y,. g.1*~g.w.t W.. 9. ; ;w.,;. +y.3 ;, 7., en.

s. ; 5. f.. * ,... * > 2: sw.

.p.27 4.. @. g li.g 4, .N k..b , J Wh L. al .M

,.,, - 7. '- e...c. m.:- . ; # ' 8 d4 8, A - ? c.

.,, ~:. ., 43..k s wt..,... e . 4.+:. A - - . y

  • .. 53.*

_.,,.,, -,,.. <o. n ' m.i.,,. & s Q. y,, ,;o."..,-4.

.;. .,aM. f..g.' h 4,

C w;.... . m

-

.. .1 a t ,..., /.%.a,-;v.;.,v, w; f:5b., ..a - ,n.;@ :.:u.~ v g ' ...w.c.

. ,.s.

m, p . . pg }g..~,.. n. w.,.e.a.

. .t.

. u..:. ' .c ~ .,.... r.n, : u..,..,, w,.- w .c ... .. . ~ g..r , .. A4.c -. s...-. . .4;.,:. p.:.; ' - ..d.

, .l..,w 4 m :, - w y"m c w as. , ?... p.% s -. . _..... + c v:..m.

... -:. .- ... _ ..- - - '.4,6se % " w..y me*. "w ej .*A ..aO 4ea4seyg -4... @.j, fe.s.

w ..n.._ m. -?.,...... '.. _..... .,.., - r . - *}; : -* * y. py z 3y.3.

, g,,4 4., ,

f. i., J *n

. - r *.. - -

<>% ,. ..., .. .....a,,..... _ . , . . ., .,..l...

,_ .,. ~... . . o T ' *-sk.

.

.,. svg;;;dgep.n.ko e 3V&uff pp &. - ', 3 o ~ a.mw .. s.. .,.., . ~, .. - -< ,..p.

..f .s* ta.

' .:v. y..J.y,w;- - k %.,*b p f ; - o. M p K'r > * x*....f. r ;,.. .: c _ f . . r.

. Q +sy:: *, xyp%Q-QW ; qs*c*:b%m ~2: n " ye . .% ip,4: 4, - .....< ; w.; 6 :w : q :. y, O*=A ~. . a.

. MT E.UU 7.*D, _ w.A 9. ~ '.* - M k K b sra d 4.

lf-t' Mb-Q- ' 4.no .gaw M ~ 4 ~ t.w ' -...E-4.[ AMW'd.: .,%.@. . ..-.....-,.6 .,.;. 4.M dbN.<et.a.M*M.Whyer=.t. w:c ptsyw. eve.g ' - N ' g!;'.5,'N A.shNY hM h Y ',, 'd.',h AL.:s.y" a i d.yf.p,cy p.e7.= g y,..--.- y.

.P%ese.*q s y v..;,w a m t * g qm. 1 eq 2.. cywf+w A>s.w.,r..w%p:w;W :mt,L w:s s:ce rey.e a+- e %<.w.:.2.

w,.. -.m.t.M,....A.n%. :..._.

. $ .a.~S O~. p '.w.w w ?_e ~.w.n.w 8: . . a _ " : L., s ;, -. R dB .n

  • .a.

. , x, u. m..2.m _% '..

. m

~.g.,p P.c.n;;u'*?.*. T.g. m.... _,_ 3, m., _ ~... _ %... W2, ~,g ta., e.

. .,. l* r> Y t W : g. r... 2_Y!*- ..xyml C':'t,"m%WP,mq;'b.... ,,,. s;; + W c'~ ~^rr~~;~ ~ ~*

    • '

.T a.

. u.womer. ~. 3 w.;,b a.u-Asw .}; Ac,e..a . m. 4.

,m,rc. s.w, _.. go., # (4 . - m.. ,,.._ :. c* %.. : . -m ,a s m...-y.

~ - . * * m .r.

    • Q *l-W y&,,..arv. solW W,o,kt

- .m.

e ,4s.y G M V.f'%'***l'M @ Yhh.&#* g.1t' Q ~f. vs,R.., f'~.,'.7, ' * .t k 'L i:"N. t.* ,u,.,.n; V'%.*, f %g *.. ;. * '. " r.

..,,,... o.g u.,.,. 4,d.x.,.y % C f '

9.

. -

A -fs wc.n ;.11,... M.rg~s.,a. me.s.w %v. W,.w.eewg.pof.,%q.... u.... p..,,g.g v, w &ut.h,M.%.%..wAw.,

.,.w.e s;*. vews g ., m p, .. . h;. ...e.,..u.. . - w ,_

m..m - ..jc.%.4.,.,. ... ,3 ...

$.gM. a.

..., . ,, er e .e .es . *.~.. %. 7 + a v n$1RXGb'MgWi2.g%QQ{g% 4h;;y,linTQM,*?TtF:M ~; c?MW%*n'@.*.%...w, . ,y

g A N M.___,h',sT',4* %*'b.#*. @ '. 4 *.; M l.9 ^ $.* d N ' %4.L w+....s> s -- w u.,..e., th.MG' *.*.%h*,WF.%.s.,

^*i,W*$M*AGr"'d,Trb.d*YJdMT-N.. .)Pt " s 3.m:y e-y_. g y n d m.,wrm_o:,s, _ospecem _4 3_.p,;Q f _' _m. __ e,,_ e.n.e n _ ___y .ar _ ~ .a q- . . - - * ug u _ * gg.g - _.__,_ g __ _ _ _ , _ _ , _ __. + . 5 h$Y'&?Sl*."DR**5$5WNY.N:Wk$YE*&'. YOW k h W&. Y W WNeh? W.%?. w$ $ W .,,,,g :.. m. g E.%.;., ~w s n w %;.n . _. u.a.: ;... .... .....

. :.

, y -- _ _ e.~*. . _., ,gggm _ _,.- r_ m.. . .. - gp.g.g g . - - ae - _ .. - ..... .., ~ _.. +. p.,. c, n - ~ ~. w -?:. m~.d. r.41.r,y: r w. 4 : % . ;;;6,v.n:f. -.s.z.. = - %., m.anx: k y wd__ a m .- ,ca ~ ..-. .m..-,.

n c.1 %=9 & O y $ j 12 W @ Q M E $ ' " 'l -- . n..,.- . ,4 raae.keee.nfuaw.wrm..t.~. caps

ec

>G;. h +tw

.s x

MN.s.; yp:n@*pu :..+M,e =&,d.r6 , wmos s.wdes . c-. _.

aes. M%7Prw.* *eMMy* T

1 Y'* w3DDDP'N@ Q 4, 1.y%$

  • %. W's.

.'9$ r.WJ.

gdWMM5:w&d,hi,p %.

WKhewe h e$s: m u g& &.. : M & t. m .3 e

  • .

3 j %:.u. m. W.W.W. M A.bSn 4%N2.26.u, p, . y M w ^ M.DW 7"'r ' T?'-'r~"n V Ww: :.-:,.u.v.= wr=w.~. :=.=%' 4.,,Q(Q Q yQ'y;kac*4 * w A'b46 w= .wr**y Y. n- = r.:=.. ::.:.:.m.

' 1'y nmM rC;~ts**** W 'ev'*"w:* %p.

c~;;?. *.,~'v.* p ~. 4.*M*%* ~* '. Q Q[' * ' '.4 d y w w.6c.+ia, "'e=se.

A*4 ?*y7QF A; *;7 **. ? ' *-' Q * f gg f..,.h,w.e l .;i 'Q l $r; & *r _

..

.**c.

A... < t s . m..._ m... h..,,m, ,.m.. a % td k a'-- ,. w.. e..... m _ ., - - , _ ,._ _ _ _

W.. u-a -.

p m f.su'.'.TMM*=*Ca*. **@C* * **.WQ#'**W.***$e'US*;*TTi% '5"I,T.Way,*tSMjT{*I**fl$*'W9%PElg4j$f%*,M.rjphur. Pk8%f*3*KWh*l,'ge es.gg - j

acme ffis@sA..a.reswe W * - .*6,.sq w W . i.mJ g8'8'.f.,.p.sr' ass w/ Gr!2.. - a m..r

g/* '"' Nt.i"C%p,Q*W n=Ja. 4, p@rWW;_, pilir*We#wMyasWf$. _ nW ' are gf e.d..%

s w.4a.m.we. h. e..e.

f.,e.,m.

m 7. w e ;s yn a.v3 m_ ,.4_._m,,. m * ar.- . c. m., n.

.. - >. W n., .

    • f8 h_.1

) f.YY N ?'**h***'** _fYYW Q

Y?

  • *?NW*
?.Y

. 5 ma WrWYN e , w. ~ x .a n~ ,. e-w ;-.,. - n.... . g.. w n. n,...v.

...n...c.. .. - ..w . g*. w.- Wo h V.E%. E'=C .. .. iW'h w,... m. m.4'h.Y,%,,.q.o.,w... T

m'.%,..,. w. _f. 4&. &. w.N ' " K6d'$9&t@IeBr N d" gz.. . MMMaisNM.WEM'"W f- -- et4% . ~. $. ~.,r...e.........b '.. .

gn I,. o..s.w.. . r -e-aw-fa .esT w ,v- ..n - ,. ,. - m i. q%2NEdlMt%'MW[ $$N..'Q'.J C ' 'i * q *,...t m .. ., . , 4.- a l e 7. y,@.g%h.n.1MN".m.. % "p~ %,iin a w yl',' W p q w eg.p,,q.bc.n.w.aratv M[ f ,,,'..-..a.

~ n ,. , , . -ensnesaw:nuwo p pr.. Iv

?., $m$&. m., x e 9,m cmew e aa.e. e.r.,no.,y. mv.e.se v4. ; _w,.we. <t.

.,.'u.A ^ -. a._^ -_ _ uneo mm _.

- - .m - _ - - - _ : w ee. ,s'._.,_w w.q._35%. w %,, - ,,en am.

see _ ggw , s.wm .e.e. r e . ...,4 pp .

  • *j. g 9,7..m. s : m.

.r..A,e w y ~e..;* y, s,v s. _ y,%...==. ~a n r= < .q, c .., _m. v. t r w.n,...,w.. n.n. j .u . ',..s.h - %,,.,.:. s... Q,. - D ..w . ne : w. n. v .qyy:., ;ne s.. -q'..w . n,%g ~. q .; ..e.... .. . .,. w y pp% 9.. w a .n . .t.

,==n ,,.. - - l $ hh $ n v*..Y E.b-L.* h.

.? f N.-$ $, ."hd ~ s . .Y & 5 ?$,5$$ $ 5 k.

. n-n. mmwnum m m m m m m.t2.., & =,.v.m.%e'9=hym.k.wm Jan %e.me%ue,-s..ce.ayM.'~ - - - - ui .m"w.co.ir7.y4 e-om.py.&i;.a-cao r.:.u.. i 4m.

wt-mcA:S = .%. w .wm u-z.

a. % .o.

. < www%w&,:a.f.-~isi.c,s.&W..- y.%4 enmm-. . w.sp s. s- . -G ww.m.,; ze - J~. y. W~ >#,,E,,:. p.. w c. d. ? 8 g.+.,: m. % g *' O A.7k..2.., %'? m w.. h.. W.

. +.%. ka n .e s;W w.p.. W... . .. . - . g . .. , [Q

),. a 4.5phb[.e .' D k Ogh . 4 Wh.w.C..'! h . ...,.._:. , e .; ; i. *. .. - n{$fNh*;MN5f.

. nn ~. - - - . ~ ~.. -. l.. h.h.m.... Q.*h. $ W W . -..$** : Y'N.'.A \\ W G,..:.. Nfh * 'N

,_ .s. w,.7 m.,,,."g e.,-3, w y p. 7 m.. - . ., . %. y. m, ..y.,3 . c . ,.,. ~ . .,,. . _., .. ,; . ., _..,, . -- ,. ,. .

- -- - g y ..... . .. . , f . - .c .;;

  • .

. fr G , . .,, :

n y.

- - ,G-4. " O-a's

m ,

[ .. -h.

c;dt w.

,...., .-.....' e> r u . y.

-w, :

e-au.

$ ~ Y %. f.'h [ ', o - f . 3-An " * ' ' ' uJ ' Ih ,. O,,4-gj

'

{ i O % s v.i, /.*> n%J, , e -- . y- ... w we w.

< w 0 Dqp < ., -4 'a*a ..y .w ., , ^w~-. -w o g,o j~ Ls p V w~ . p,.. Q# g +,Y fg g &k.. e-4 . *s. :.,.

r.. , b j. Q y, f.g'. .:~.. . f g& p' L-g>. o.

.e. ' ~ * - . . ]g ,. ^~41%-3,g- .

}Y ye' - O ~ fIp& .o.t O ~- ~-

  1. p ~
  2. q g

. ?. W -f.

llf@.,u p& , . h + ' Mt. /n., % .i., .o. p _ n.,..<.,.. , 4.He.ni y. M.

, . a . , , m.g .. .... 7.,. . 1,g,2 C.7 - ~. v. 'b, : n

.sf6.w~;m,%:gr-w.tsy & -

. t.

. .. . w ,) .

*.- ::.

- p.. - - - -

- . 2.z..- , 2.,. ,. c.v..,....

.; c.

-. n . '~."*.;..,.-.,.?..% -. ".g,. Q... , .

.

- . % /,$' '*l 4 $..rl\\ ,s p r._%.s 7 '. W;. N.

~. ~ ' *- '? ' p. p g. s.,, w. < a.-.. ~. ~ ~. .n e m,

,

4;>.9 '., h,A.y. -~,.-.,,. A. v b,n. -++= - -.- .g~ . . .. .. d - ;..t .% ? 3 Q - N,f & j ... m...y n..A w.n.. . .

p, s

. -: s . . m ? Y,p. x.e./.-:- w.n. uY S.'ti. Y W. l . , Ek f S { ~ qo

- * L. && t.L,. m,.

.i . y c. a. w w m%. . *sy 4.9 m,,g3 9.yye,-m m.

.., f..a. r 4 c... m.+.m + m.a.a

  • c,....... -

, , ,. ... a.. e... %. gT__. L:w. W q . =g..+g.y.e....c- -.w;..n / ,.sm...e,3,,.y .. . 91.c :.. /la.e.j n s q.

.. . . .,, .; .@ , p..r.3m -. gg.

s. :.... . ,. f., g,.yg7,w, . n. M v.'.;s c Q.*g.Y.

.,.g ;peerw.p,,.,.C..at+ 3gpmen.t u g ..-. , ' 401 .- 4 . uc uer . a p ? g

c.. W _.w s1G.,.

%, ,. M.

W.

. 2.- g.,,,... c .u.. . om .,. m. m.

. .. m . .. ~ , - . g ,.4 7.,. pg.. ga .w.w.w:-- - 2 5;72..'$y .e.y 7,7;.y e:n.,.w.s.W h-,... ,, > g ,, y - -,.,.,. '.1 l..O A

, w w,r.w p.m,,.y GJ.a.

__^: d .. ;: B ;.7,e G *.'*3 4 %.A.J

%. 4. - - _ . , a w . . . ' * f.-....~.,-M"I.w.?- s - y u.,4%,. W, : k+i.W...a,&.k%,N~:.',*Mi,,G. k.'. iM%.h '. @: .: : ..t.

.,/ . ,e,. ,o ,e.a .: se - ,- . - ~ - - O.

% O m "'.m.. &. yp,h n:(h,.

. a,e s. - - *E.h. _a. >.s g> m+,,n,n,. g.J;- :a ex.r b9, "T-C.?':* *s.* c.;;, . u,. : -

  • =%gpmi

...:eo.... - ,.,. s,. g w.m. m.

v., rn ' * *t c_ j %. e-e M ., - - .,..- t.

v*,."ll.f*f.. .f,.Yy ,WS?,,t@t*42qq,flp;, .W 3, -t;G.W c. **.. - e : _s;u.,., z..s.. 4.., g r . - %,_)*) 4 W.

.. . _ 4. p 2.. y-. .. . v,~w m p,,.. g ,, -.-. 1.r- . .mm .,., _ _ +. - _ .,afemp;-m iv g y c:. w g y # : -.:... , . ,,.... _.. 4... .., g. p,. q y w y g r g,.g w . me,.yw . . eq~ a _ .= a.m . m- = - ,. . m-3 ,4.=p y s_-...m .- . ~, _.__ _ _- _.

.n.-m,,

,wa.,.<

o.

_- , m p,,e f ag-. __ _ ,-, .ea.

_ _ .. , . .a- . d ~ ,...,~.~... - , 4..a a.. m .r 4,.. w. .

- -
    • w

-

  • -,4's **--;c-W r

r,f.r. y- -.p:,, m., f~.

  • * $g.-

.aM ireau ,=yer v,,e#,n ...... w.c=- <st.sryg-*.'.. - %':- ., cr.r.. '~ .i.

"- -r4a; p.v/. .1 g-Wgli ,.m. ':5

  • WW*%*w.g

- - . ?63.ya%.L.-"..i r.' ^ , A n JC,aw.

, g:..s . t, M.u :~%,t.%.U".L. + '; . w .'.a . - .. . . ~ C.

n, .v., :* w .4. g. : .' ayw+ '.~ : - o.,c.x;m ny ~ &,.97 t

. p. g n.

s , c.:..~.. .,:.u-.n l W'.s.o.

. m:%,. gp w g.c:.a~; m n :._.,.m w _mn.. p y e p%;,.y;;yw2.yy,.,ca:n?. % w: , - ,,4 n

-,

, su:y . p.n +- 3.w

  • ~

?,., .- ,, w.-Q -

.g.w w.

n,..r: A: d.m:.&~o-u=2e m.

y.

q. :
i
w:pa. - -

.; .e.

,m.-

x.= z,. m.... - : .,, y *m.s.~ x.., 7 m-r.1.,. . . -A . .: . .. .,e mem.x t.;. s-x- - . . Q :r;; y:.. - - .x * ~ p

s .g c~,: e . - . .. _ ,. , r, g,.v &o.. g 6;.5% 4 2. w.,

  • p,, a :,gM'.3e. &

,,

  • .. m w.".'g

.. M J. - er%, c*..,t..g ' y a.

< , , . .. ~_ ,s.

...

e.cs.esm#eWa...---%. . y'n . wer c., we..,.N..Q4r k esp.eew.ky,,, .,.y .g.e,., ..., ,.,...,.. .. , . myt,. - _ c-a . -- %:_-- - - .. r

  • -

48.,c, gA+t*v,glgfg.*Nury.4*yygar.g,,g;Wus-poQc'.p.,;T+,,W, v ** p. v.l*.p*j,.e~ Q M g:+ e : . . ,". .,. p 4 %. q. 9..., ma...,.,r b.-...o...:- ;/.,- , . <.., ..-Q. _ w.- a.,9

  1. c.m.A. m sp.6%. 9.~r-+=py;e <eedh-+ #

, e . a , .,nQ .w - - - --: -y m. m,n.r - - - ,:; w L& n s.

_ m.

- As .g.w. ;f y;..*... -?q- ,.,J .u,1

a v, .

r.

- .a..w..;..,u.n,. &, g - m a4.y &.._,y, g- : a m a m..~.s.

w,.nA. a.,.t - .a u. n.._., : - y.- --- ,. ..,s . .w 1.s.

s.. ,,,y.~,..

ae; s,q*C , p #. .. ,.p.es s&.- . 3.. .q a s".. ... M. J # sp =.,o.

..<,.i ,. R,y$YMe *Mg. Ja M..T...,e.". MP d : # d 'd '. .g. I-me. 4GW'.g %=y=.,, %. h i.

. .4JE.

. .

I. M.*.m,...,j id.5.f2f.py. Ms3.n.. d.=* g w.

earew .r.+ m.

. . v 3r s - N,... . :,, ., WW.

. - .*

..

A ' ; n@ ' vc.

F Kd.7L fd# . e gpe$ Lue r~sw.a.., Mw s x,a. w...s,.w-. _.. .s.

se . . . . Q n ,,.,.a.

. .. - .,._aa.

m..,,. . .:a.-ye.. a.,, gn ... p* /;? - ,; .w ,_ .# .. .%..; % .r ..a,.w.,.: [. ~ '. s.. ' ?;, y :;;-**:: :* y.

' =.,.; .s.- ' ..w. %...g, ..', e, M ;" -[ - ~, , ' [ h L'., v.

' .. m'd" m m, g,.T g g ie;;8 N Q;*$a.t *,C **,. g g *'F- .. ' -^ ~_ C';A*;;t,.;y. 4AM..' w J., E , e J. : u.s..v.m m.s x -.:

  • Ya."* b'$ *.,k.?.Y4h. ?e 'Y

- # ',a.. n;l, h,,,'.

. ~ .,

  • *

O -- _ _ _ _ .., _ pg , ~ w

  • -

.F = .O k W

rm., c.a. 5'M -!8.

l , o ... 7..'F. 7.%.... Gibbs S Hil1. Inc. ' . j18,,,,,,,,g ' g'G.

~

^ / c .,.....@.. 6..... '

    • $auns.oisa s.w~s-s

,, - v- , . G & H Joh No..- r'25., A -

1./2 ~ Chk d/Apped. Dr.T..*I.g .......; rL. 4 ...s....u.....s..t b..r o'.6.... Ref. Dws./5p.s. No....s. o. 1..o...". .) Sesbiest..T.o. s i...n..o..x......s.... G.

t .. - t.D ..... .f. . . . / -:. a.- < , .. .. , q St. A6 66fel. f4 - G4 d,.rto n. n c f 1 A. _ . . ^ ~ '.:.2 g'4 -- S u.

pSw 6 El.

' ' ' ' 4.

3,.. L,pfp S.

. . -.1 Z,c, w/ ' - - - - f - .,.. :. . ... .,.. -. .. a_. m.m. ~~ - j rg - . , ._ . Wy.g o. tut.S.,yQ, .,

., - n :..

.. ... .. gy., ,,/ .k, S Q i.

, o.q. *10 - c:,. - . se..h b: f 4 4 R.y... .. m.

. ~y ,.,.g.gg,. @. . +...-:.',m ' ~ n.

,v , ' - .- . ,_.. -. . - ... . _.

,' j '~ . . ~: ;;..;; y;.g.- , , s .

r r a

. o.1t.5 x LL e i n.t - , , .. ... _. - ~Yn.L n ~ - -

.u ac.

. -.7.. ,- - -... ,., _ _ #.%.... . ' { g ' C. { ll g ; l 44. ' ' ' ' " ' _ .-. ,. f c

%'

/. _ ' _'Z, , .,h Yq 6'(.f(Th 1.'7 (s.1) 6.6 ' .

= . ; .c , ik.,4 . . ,. . rMor4& RET.

. -bi . .; .. _.. . . ..,... ., s - .

..,,,,,., / g.

eg ' .*

,....__:f*lhf:~ , ,rQ,g. 0. 'M.6 _ (.!I) g Q. 7% . .., - . i - -~ . . .. . -.,:. ;, . 0. tv. G 0 g. _.. 3 .,,.,.. __ - g s o. i ~ .,.,,,..,..,,,, .,,, ,. - - -. s T. V% l'It-L, ,... ~~ -... IO & G.';"$ f 3 7. @jg, i,.h/, .] . r/fg - , ,, , ~ . ...:..-

. . S Ger4 F0K C6 RAG.r41" ~ .- . +... :. a - ... /. d s it,1.6 10 8 h t<2."

' ~ '. .. -L-o . ...s 0 :', l'C't.xtt&ob ', et f ~ y, o,ogqf q oja,f*'[.~fj., . ..

4 6 el 2.

(# 4.) Q o.syZ.

, - s J ' ' ./ .c frS : o.00$3 x t'l < r o.S = 0. h'2. 0% C $ E. n6 G. h 7" 4 & (kr o.4T9) ~ 4%?. R s,.a e.

. ^ , / ! $ e b " 4"< h (kce.l+79) oco.as sLxlo.Se 0. 4'2. l .O S E

' o r t .i. m.

. .,f. 4 0 m h.

a ... ~. , - . - ' ' ~'- CH cn fc2 S d 6 A rt.

= . R s . s J < ' } aw _ S. 5 5,t.

pr: c saa o. ie - s . . o. a.3, in ics / s a . . f .

t_.~.~. .._&.,.. #gA'l.? ). T '.. s4Q. . W ' ,a .- - ? .-,.. ^n w.g* &., 7 g 7L . ..wk . ' .: & . &R,,:= 9,,-%.,r..,.. ?'.-- l k+ g.---, . -Gibbe 8HillInc:. ~: - . -,; . * ? - . _ _ ;._ . +M , j . * Cele 5y.'...V.. s,t. g..... . ENGINEEMS. OESIGh(KS. CONSTKtJCTOMs.

w.' -.;,tr-, -. -. .. m.

.,;.,

. w._.

- gy@... , -gO .p ^,MytpgdgCg_pa sEg a g.f.;g%R.w d c % < =L I kLY.. " % m . S. m%, -


.

. x.

' . ~,., n.v.. _..

  • * ' '

. ....... ~ :. ,. . ~ a 'a.. u. ~ .~ . '... - .,,,,-.'*' * ?,T,. *;*,*,:.;:'.' '.,, ". ' " ".A' ; ,,W."'.'*'. "" %. ., ) /* ' ]_ . ,, ..,, y, -... a< 4/s9, 4 ste.=e ,.J-i.-~-4,- .,. , -

.."'t-g _

-

  • 4. -..

m . 81 < x J4-u' k.. 2 7A , $,sA.y55_. wt{.% v.. m m -~m-" - ~ - - ~ .. -%- m._ .m . - .- ' - - -, {h k -*'.u.'... m'...- c7 ,, 9 y j.%,g%,yrr,.... g, #, m -. . 4.g.:..a ., _ - - ,. , a p ' ' ', J 2a..,,, W ' O " . k.g'M... 7.:. [ - , %_5 s - ~- - .. .. ~. +,..~..y u..pw.e %w::-.wy a... .. . ,. .:.' v.,2 :,, ;si n.:. w..- ' 3::9.h. " n.

. -p-greg y.M=gg.y- _,w .._ . ' ,.. ^ l age,, m M,.._ , " --..,.,,.*-1 - ~. - - ' -..v.-.~.-- . _ _ _ _ _. _ <

- -o .. fm.,. ' -- '*g~" __

  • , ~. *T"#[ ' J/,. A -_.

--#

  • _,, ~ ' ' *

' 4 J - W'*wi.' -{.-[[r F ..."**,[r,,.g'.",T [.. 'Y _ 6 Fy 6, ,g'g(**f*; kh* c.,*." -,

. [h- / d N an. ( .[ " 5

ed . :%w . .-=.e-. m' ".-.---y.~.. f . . -..,. .p

  • .. <. -

, .-..,.,.4 , y.me y . w:.w w n.w w., m m ~.~- + sm m % m m y;,e s.

,=u + ., Y

  • h. %* $!~dfY O'

?s'e?W-s e Ch ' - ' "n e >.n,

  • - ~ ' r -

5%mYY,

  • 5.k

' .b'=. h.. i.YL an ' %2.! O x h mt -**Y , ['.-M.D" "..a$ S T*.3 * *** '^. h a 46.e --- ,<.sa.,.p.

mm 4 we g.

e - u - y c.

-.. ~,.c,r W 3,s.

,=.,h,, _w--.. N.. i . 7ynwa*,~... .g y. .n - .... , - -

e , , . , [

  • ~7

' '# . 4 # ' ',, h ,lO.'* .h ..

].

4, -

.s t ...,.;.... . ;., _ _. .s ~ _.2..... ..:,. : j.

. r, . ::... %,.. ' }','! y(' 7.1,)l.L.. ' ' * * . ' '. ' * * $*,'. 7 ** *.* J ".2 7.* 2 *J ~. * *.. . Cg "'" * i : " * # t . 7....p.m.y..L,%.,...g.'r y.. g ...,'.. ...'dMis - ? m A,.m.Cc.

-- ,,.,,. . CP tWE , . y %, p4

m . r,.-r'- mc. y,,h .- m- % ;. sn,?.r.p;.y'

  • w : 7 '.,w> a w.q g,a..M

..., .. . . <. ~ w.,.. .m . .sy;3 :. me3 mv . y - .- -x , p p..b 00$ & : ... - .--6 - .,-.-r ' 3..r,,we[.,remmancam. To123 Ar**irv'c# e.,.m 4.- _ L.."-- . jct!rtrWsomet.'*t a.M h *v. w A ,a w-.t Q. k C** * g'ppQ..*L. e'.'.'..e d..P..i C"'P'6 V d.

    1. ' **

~ ~. a -.. _ _ _.. %,, ?.*w[ v. - a m - w- -m - ( - ..h w..,.< w 4*m' 4_._f_s,*+#mJ_ ' : _

- -..

.# ,,,,,,,.,,,, _ ._ ene _. _ _t. Ma_lM. aipM. _, _ww-wr.~m* **- a s.a.m.. **w wenaev* *aw-==-** *.- =e -. * * -er = e. c -.* * ^.8=%==**. gy g g { v., s.'. _ 4 - ' **' f~ ; 5**' '-. >. -- =-

. _ _ _ _ _.,,,,,,,,.,,,,,,,,,,,,,,,_ . _ _ ____ _..,,,,,,,, .. .S*- '-' - ',[;'"% -- - _-- , _ -4 -- .y ;-- -- ;}w {;- -

- _+e.

- - c.;P'i; ,. <a ,, nm - -- __ - _ - - - .fV.* ^^^1 ME . g.

,gh -

.,.

-- t '* .,, a . w%m m_ mo., +& -. ,v -la x,2ewc.Y;-; a.

W,x%,5 *OA jf.

._ a QEx. , n,- - _ _ _ - -. a AN j p ,..,& G;ZCiM,~1 @ g*$a %n, @:3 sug g 9-p ': m m A,,%.% W YO3 %':.Y ., w.,' lM WI.M.'I@i"W ":3X4 %4** @ 6e

y,w - u ___z m -- -.m.,, s _.m.

,M.. -Q.mm_g4A [ air * 4 7. D,[ [ '". J,. ?. h jf f.~* w.[lle cm m.m 2.'.fs','/,,.' K '.. d. p . u.,, v,;. m., ,..... ...,_..,,.m . .. -r ._ c w.'c,. A g_ c r --2. m[% p ,c.,. _...a, ; m. ,a.,;,,, ..,2,,,,,.,, - ~-. ..,,........ . . ' .. k I, h,, .[,,.i [ *' ~ , g $=.7 - _ g.ae,e u.;:1.x v -'.' w, w=w= m.w. nc.

. y 3 qn.;~.Q. 7,T~~. v.=~~ f... =.v,- [= gp n m.. ..;.,.* 3. ' +. ' ; ?.. . , . . . ~~:r.. $qs f.&. . '. ' _

. --.Qy ; y ;;,: = r~., y

-,

. + :,~ r '.:. =, ,,. ";. - .:,1:m p.c. <vy Rs..wm!~ o. u", ~.- .,,j c g.. ~. mmw -= , , s.

pa,; --. y.m p,.. . ,.. ,.a.a . r .

. ., s.. p.% c-.n., ,, ,,,p e . . ..- / . < -. . ..y , .... -. ,: .4 _ . ' n . ....L

~s"

' - g * 4 sg, ///,,, *,, [J," g h$ h,, *.,.gg , i ge.

. c - ,d;.. '*****'"T**'N# V@~T ~$ @s[' ' f. f. hp..g[ **.?""C~~4 w,. m. n. 1 1. i, -... . w... m m..,,. v v.s. u.... w... .. , . -.. . y.. 4.. n. - :. - - . - z -.,m r ~ - m:.a. w, u.

,.

-h ed,r,,.. g. Q ~ _.4 M .. .. ~~:-7.- - ,, . ,s . ;g. - - - 1 :.2 :. z ~ ~ w ::f y,,,. - c i- . ~ e,z-. - .f. g< ' + - %.. Y,1,{, A }, { y,'.,4 y. @ s,. ,~ ,,( y ],., g i' .g '4- , _. I f,.. y ~,,,T,,, ' "L"4,, . - -m -. ,,,.,%..u.,.,. ., .o% ,m.

,,,,. . .".%'"', .,. *. - T 1 . ~.t 19, C. ~ 4, g',t. ?".y' -s"'. . -. ' ,;;g..y ,,...._.,.,.;...t.,c... ...- ..> ..q, ....g,. . r.h-o e.

a-A ., 4.., 3.,.,.,,, . 4gpg( . ,, . f.

  • %.w.,,

, -. 3.- * v.

s w .; - s. - mg ,. . , .- - ._.saa-g g,,, c,,;, , ,g.,. . _ y

s . ,_ I " ' ^- f2., ; .,.se j. e. . q,,. .,. .m v *.

'

.Q w l., ;.. ;; %, t./fL % a O. d.-. },},. -] ry y y~. -m = ..a.. . --. ., .., , f .';* ;.*..*,.~ '..'.:c..g - . '-v,". g i.f, a - ,,,,,4 1.

c , m.w.y.www:. *g...1. ;. 5 .e*h.,'..."':...~, .,.\\.,,....n ..;.*' l .,4 %, y y e

,;. _.y,, , ... - m.

p.

- r.7

a L.
.w:M

., %y..a a.s. %, w a c p: i ;~ p.:,.,,,. .. s c.... .: . -, ,.

..

r.

.,

-

,.1; .;z. ,.., ; sv > r . I s- - i .. g l'. .v..... . .s.

. s ....,g.; -- (f(hf jf

" ...'3 - h*' !* ^S** p -. Y e a.

. .:, ' ~ ' ^^ c e.

y' ' ' " ' AM, _ i .,,.,-A, - '. ~ g ~ , . e s p

z

,

- - .u - ", . _ .. - C 3 1 -. S :,',>, D .. . h..e 11,,,' .,. - A . _. ' . ' - .....

gy ,.

,M,.,n..g- .., ....-...- - s- 0 ", e. s i.

,. . i p g.. .. , Y f ,w-N - +f D' ~ lT OCYC;" sQ " Rrn - ~

. . u s.: az /m.

. . . / m . e- _ a.

.,c s w- ,. m.

y . .. - . <,.9 . -., ,,., < g - .. . " ~^ D fC C. C ky tr. C Q.

. . h,4-Y . - % P. Ra,,w.

.- - - . . _ x.

T 0 52 #$G ffs . = >

l~y.x
.

~. . . we.

, .*. - en ~ d.d h 3CI( d { g gg7 b

a ,

} k @@ fo #!. SM A.7,.. _

( ' ~ ' <.3

g y" s; - ~ - c.u. a.o., g p,..& y m % . % D&* _ _ m.

. . , - a . , . . - . y n .- . _.

-.,. . a.... g,,..._ .a... ..... ~ s...; m.........~.,.,.. ....,,..,.... .s. m.....,.. ~........ ...,...... .

' .. " .- ' ' ..c., w h. . .

u.

p;. ;,,,[ ._.. .c.. , y.

, . . .v

. ,

.

4 &&. ... _ - - -_; .+...#.~ . _ _. - ~. . . A L . %...%.drh.. = -.~ ,.2" ',.. Q !. 2 '; ~ ig, (rsC'- . Of - .T,._l'" ** " f. ~ ' '<' . _... , r, . . i t . . M...1..y..... ~... y-bp e3,consWgas.

...,, ...m pp:g;*,,q.

_.,,,, , _

.

w.. ,; . iMG*ggs,ctycs .,,,. < r= - - ..,.. '. 4. ".fh...C-A-..1 atf, &.%.4 -. s L N.~.E * J... ;- ., . . . .,, ... ... W MfM .__ -o j,.

== - n.-. i.

- 2.. g.....c.~...~-:n..m . . giga top _..,: . -(e.

, nr.w. u. t, .. . w ~..- a.. .. . . - ......, ?a.o*+1se ., . ,, %Q&M,u&m.+:% & - % w..- e.c -. D* * -l7 ?&W_. &, W,r;W.&. 'g i',.$?", $.gM'_#~~,,r;:;.~ c a.~w..w $., v.",v, 8nT..S,.. w - g, ~ ~ ..- -: x, ~ ^Y f ,, ' ', _,.

. f.

U.h . .. .. _. g . f...L' ., . -:. " wp,. ,, p,p.. 3..t,p G,. . ..__m _ .._, \\ . m % e + -, w,, .......,m

- -

o, . % _.~~ #. "7 4.~. $r p.

..v.

- .a s _ _ ,...~.. e,,..-.;c ~--T f !' g ,.- . -.. .~, s. . - . A.. c .,o

e

. - . - --

-m . _ _ _ .st- . Q lyi'. O :,4 o.g._ _ a.e L.. y. w.- w..-- y - w...m.

- .... _.... n . - < + - . gp.t} - . . - -- - - . ..... .

m ,., ..~..m.u # 4.u %. w. ~ y,,s. K.

a ...,e.. ,.. . .=- -- ---. ~. s n. m.

.d.._w_am.- .- .4 .. %. . .. m p ' "" ., . - Q - ~. s -~n. 'f.,e - o'- . .*

  • "

' ' '

' .' "' -t--- w' way, - m,- m g. _.... v' ' " " " . mm/ ua_m Lh,- - -' _T 'u .- -- . -. - + E 1 'r'a dM MIS r. 4.x.,.. -- - - ~ ,u.. . . .'~ . .

  • ,. '

' f,,*. '. .,:.. *l*: a" w..~. M .en ,,. ..... 9}'.m.

- m 'L. m. A'

h, k ..J J*" h t.':. "[" *".'.*.l;;.C "' 8'."..'.

.-..~. .c. n..... .,. ..

  • "';****

en . ..,. I -/..~. I,QSN'*., "* ' , ~ _ 7* .. /T .ef.*'g M a'?":.,*gh*2 7."v.

  • *

...v ,..~;ptr' t-2 6 'p-W'- n f ct.C.

.. n m. m m, n w- "'..,, .~.c' -- a .., ..w.y)

  • d' '" %K**..Q JR's'$h ) t ',i $ *;g.z.9 ;. l.... >. y

._

J.,.

.' ......w h

v g, m...... "...,~~,', 5 *u. %. t .,-.a..',.,,->?' . - 3.<* e,. g* f a.

L.y ,.<a,' .;; - nEn e, ' ,. n.A :. r -,s ' },:', y >., . 94,- .,#s L% _. _ , i - v:k.e.

-s . . e .g.a.,2,#.+Tv61:*g; "7 M_ m &.n~w t e=:. %, W<mV~r*Mrt*Wr.tv,W.5.. :n..M W< *.t.'n:'afe v. r. ga., , W e t-

. m n.-.e..~.-.r..~u w. n.a, ~ - w v.. m. s.. .~.y-. .- n .a.- n .. . .. . _b.. esp *'d * - .w e-e.v..< pen a n + 3 $.e r e,ess.,ys .e

  • .

r-- .w . ,w-a - ._ g h h,eaveav.* '".= *.* * * -==-*- m-'-*~ p #2 $... "g" -Q.gh.* #A .^ _ :-" ' L Ame* _ f--,-([ . _. _ _. . -- -- -- _- iL

    • r*.p=*=*-*-aa.***.5.****==-***-an'**"

p.ypas F .. ~~ c.

_

+. -. n o.s . ~ hniMlidsNMace.r..c.a.5N_ - --[ - n$_* (,'/.~E.fca}.,., ~jC.,,. 1*E' T,,"l i 3 r [> e , w.. p, s. ~.+. . ,. 7,...g -a-~y ig'"l'=,m. w.v.r.n.uw.:n. :.w,..,s.-[lM gw. w f'.e: ta w....~::.:c,.,C-ya ~ nx ~ ~ - - - d - . ~ -., ...,...,..,j,.#%.,.s,..f.. .. 6f,,, . s z.

- ' 4 ,.e,.c .,.. , , .-..,., L.

. m ._. ._..a . .. ,,...-m ... .. - - s.C AW ' FE._,, '*

  • ME

.f' h.

Z.

, 'smh Y'x:%9 i. .%y J, .h*' E

','Td, w,..,. \\ .g' - , g gm J p. , j%, ._ ,;,,934 ,.,, ,.,, .ty .e ......w...,,,%c... ...'? * - ' . s.., l~. ..... $.; g*,.. ,,,m,.4.,s,..... a.. .. . .

  • ' '

A* '.**,N.-:. ?- ' 3 * i "',

?'

' ." u a,-. ' ~ -.' i ' ~

  • ~.f 1 W=~.7:*.Q= y=*y~.'; y ;rWL g Q.ww',#m...'.

.~.~'~,,. e +J,. C1.*'. - ed 7..- .-.. ~ s- ~ .. .. '.;-:;q % >;::t n y ~'.2*.r:;m.q-)

^-

4: .h. ~ - . . '. b N b [- .

s. w. w a;..s+. a r L-[. n.s. n..u,s.;s n$~w. 'a an

. - *h '"h E - 'N. I. '.y- ,,I,, ?. -f ' p- =- - -, - ..c 7,. ~.. -. .m,o m,g.,,,...m wa.u . ,wu. u., 3,e,.. _..,w +::s.w;a.

- >- . -. > a .. + . f 7' $_ ',~. A a.or - - ,,., -,,,,,._ . - m ,;,..q:i. J..t f.1 .,m,,,.. ., ,.., .., , ,., .. , . 1.

g' ~ f..J..J 1% % i - g}* d: . s' W a.'. ~. i ~ i -. y l,:l. \\,. \\. . 7..,. ~~5W'SYWY"- : m. ~.,, r.. a.u. m, +, ;.. y9,"e.q;* O'O Q ' GS **~'W""~' ,,,. ., m.. a - .

.2 n -.. -. . v.

<t,. . g..s.

r . . ,. ;e: w ya :;<. cr.

.a 'A .

  • * *

""'"

  • .=

. l ,.,I #,,'4, J.. - _ .

- , .5'+;*~~**- m, {d

  • ,5

, gl.

- }

  • 1P,
  • ',

, --. [ q s..t c, 5.qs hes.s,g, ,, y S, . ; .s* t.y a:,;,. ,, .l ' - -

  • -

,,g',arari.m,N ' . p *..,.,. ; j... '

.

!. _ ' ;,_ ,

- e, ]..

  1. [ ? e

-

~* I

1 L * g:. s g;. m

.v v... *. - ... :..#.. l.,.. ..'.? e s.

. , QT.-@)

  1. ~*

. /J.%* D%* e-N e ..r .. ,~..,1"k,,,n. e, w ., a .,J.~% . g

h

%

. w - g y.

...e<.- .r.,.. .c.u . . ,.

., -.. n .....-,'@n f( G..9)4

T.* - - :.. - .-.-~ ~ . a.s - 'y,. .., ..,.,.e- . - . A ". bok ' ? ~.... w _ ,,f

  1. e

~ ' O . , ..; ,- i a r q.*: % .s V

.

. . e V, w 2. &,.m' v... :,4..A.. #~ . ~. ' ~ ~ ) .m., 6 y - <: , . s?F " "[ * - ' : '. n.: ;.

..c., 3.e: - ~.r.m.,n s ..e..fllt gA W, #"*

?C

- - l l L t *d.,..L.&:.. - ,.u. 's,, w? M.3 .:. N 't.

.

  • * ^

s e.

< , (rZ.t4).~. S. +,.'..n.,: ~ '

.~: '

-- .c

.. . s..e ~ .. . a.... ~ eves.c m.ws, w sr4.:p,.s. a r *u.. g, . -- ,... Ly p tF (QYh .,, < i - .. ' . - '.,.,.? * r ', - ~'" 7. -.. r/}y,,. =>nr - j (* @ J , . yf.

' . g,g y . , ,,, $;t' l2' - g

  • t

<.. - . ' % ',.._ L.y Q.

-" ./ 's es

W '~~ ' ' 0q . ,, N.

'*' W : - ~ ~ m -- r% L <,,. :. -- -y *. e5. 7 p.m. w4 d)' L

, p.s. w. c .g r - . , .. ....... ) c

, -,. ,, 'Y, bYhh - N.,.

  1. *

' ' * -A. c + & M.Y \\

~' ~ ' .%g.p...m.%m ~ - . " -

n.

.,

% - pc, e'.j yQ ... - ~._ . m . ~ , w$Qf&.y.g;?' L ^ a &n [' . , e

  • e

. .. Q . / Qo 7-9:w

, , co er (y .. . w $s nw~.s, M.&- Mgf[ . y '" J c'* - += - O a \\- ^W ', . q,,, s'b v- ~ -s - ~ - I i . - m . ^ ,) __ pf0h

] a %s -

  • ",

.

      • *

yh.

g l(W. _ ..... , py a - ye -. 4.s g.# ~ .. . . ,, \\' ~ ' % -.. er - ... _ _ _ - _. -

. o.

...?&. ; 7.'t...... Gibbe 8 Hill. Inc, nu., c. $if.?. ?.*.G.

i "i.a... *.. B.. 6. ' ' ' s.,- >. JP'. o. Q f

    • ~m5 ot5"'5 wa5=*5

- ...,...........g... Reic42 "" c. had a#nme. mu.e.... - m ........ x v. s.s... '.. h.x....%.'.w..e.u.s...s.. s. w : ci.*..... o.n.

....s.- e 1. ! !........... . . ~ ' Cons / roc l Ion len.d l 4l' LA 6.

(b& TrJ.

Kts. LA

  • C' GA-10 upfrom El. 8Io'-G j

~ 'a 24'- o* CW Q ' "^^ * 2 1 '- O -, / na t.7 d-l 9 fc.9s { k-d'.-i o" st A6 + t." F ewesd.

g qz/3 93 x /E+/ 7?' . U" - ~ j.'sa p 17 = l'85 * . . . _ . -

LOAbs.

yo p m El.82rC ? coac. st.as o. e s,. s. ds = o. sts 'Y.c -,=f,got/7L-/l'9hl %- Pe ar sa . ,0.015 ., U o P, P a c, < si.cc. coaD.

=s.oso / =I 7x d 'E ,.c' . ' 0 GG O up=.f 95tl'02 ~ L.L.

= 0'L'%:s' . q_. 97 rstF gy,29<21l10 N G A

  1. !/

da.[t. O. GGx t, 4 7 8 Y = /28 1.

j G V,, _ e.r.au _ t. 4 - " < L'

, S (7.b)f.7 (t 4) = tv s'7 Vu

. noa~c h 9 ",' " M D.t c o..' 14), #1 G. bj' v wa - %. c, - o. t (, 4 f, 14 4 '" V b _- ' ~ ' -- a,. w \\.to u a- - . bH.: '$ G.b)g 7 N'HhC l & & & 'Y ' I o 2Grafc2cs McraS h 4 s,. 7 a. 44.o / 6,IA ' ___ r4 4 _, s6 5 se,10 0 0 b5 l fc.c.oot'G(o.ocsb , _3 p d ?- 01 < (44.0)'l- . - A s : o. oos3 tn%.O s t!"il, b Q f(, y92$( &&rstGN G r4P. s2 ea.

I' ( ^ Y' Oss A G. 6 74' b (1 A R.

o.cos % s2x % <1.% caca i=c e sw e d Qun ka w 10 Q_Reic.. 7iS - g, 27 6 _ 4, ps: c eq7 c.g ,, o.as, ear,

pMa
a ~. m...w +.m.v. a_w.s,: ~. _m.., y m,..., :. n.

?. ;.,.. ...ww. n w.g. n~.u...,. ..s.s., :.m.s - +.: . e . ., . .... .a.

. ., . . a.. - g., . u. - s. -. . f.m.w,,,al. ~..f,. *. (....,_.. o... g.

.. . . 4. ' q..:.y..;Go;bbs 8 HM,. inc. --w. s e. ws;,m~e.y <, x - - m - - &:.y "..j. g - .x .~ r.

.., - ..:~ . b,..su-. ... ..... . ...... ... n. w.

. A.u. rw <,,c a e.< 4.....,.7 H..e..a . .u - , .-. w~t -.;, 1.g s,.,.'.' EGEET.S. D E SIGNE RS. CONSThuCTO'.5,.... u..,. _. _.... w n, g... o.. f, ; e -.,~,f , - .: i ~ 1T . .... _.. . ~, e.

. .. ..-..._.. %. . .. ... . +_% . w,,,.. .. .., 7.v .n%.%. w.. % . r % 4 s...#. g a s as,.... gQ,.y., R ( &,. w.~. m . ... ...m....e ;:14sv4.

v.4

r /. 5..

- ..... ~ s ~ s.~ c w w e,*.or.....l...:. . '? u % f@ ms no........... - ~ m, It 'Lt b w ....,.n.e.o. a se.a.n . T.. e m..._y.w a w w _ . m.,..,..<m.....S..l...h. m. : go pG.. C..t A..&...G.C.. s..,w-, C...%. c . -uw. ~ i; -

- -

- N . ..un:.. . . ...m..v as, ~. . ~,..... q a..ps.e w. y .e, .e - f,.e..,... . . .-. ... .. . .... . ...... .s.., w.

...,....._.

. .. . ...W.

. . pe.,'...>wr..,,,,..#.,...W.. ..., ~s.. :m,n.m,r,o..,v. . _ ... - ,. :. ;./ .w.

..c ..,~.....,. ,u.rs.

..s s."* . .m.

.. .. . m.

.. . .. - . ~...,.. . v.,..,. +a... w . . w w,,,:. .--g* Ass...,...w %.... x.,.u.s 4,,:.. v. c<.. ; m, .'...*;,ga.4 % ..% v. w.m w - i.

  • u*geg. w.w... s.

., - ..% ...,.. sc

  1. .....%.

....... ... -w.

. ,... ,..a . . n .,4 .-u.

.m.

..

4pq.p.pasw ..s neA 4e-es: at-r.4egy eph a049en..gr.Q 9 m. %eaymp.sgee . 8.

p ygm.43. E gegJy Ap=tg J.n, gha.m., e.s1ued.es3 1.eg hym #t q,e . , 4.*. g (d e.-/O;,,g M,* g*Gyk g $ s s, sv. sp Mac.' * '. &.l. h, h.m . Cgh; j M.4.w; ipe/+Q;tse ft

v. - u.

a e , m m.

. n.n.w.s..o.c. r.

.c. ; am;c. m 7' sy .c.s i,,. c.; .. . M.~*lt'*f?l****1 .,; .... ...,.....,M., .....; ...,, s.. n.

.. ....,, . ,,..,v.. . W'??tW ?%*e.'w,&; ~~lk. n.,.>.. W. 'f?'* *R?****U: . g,W**5$^ Y.W****V.myr{wQWW m.. e_ sw.n.'C,M'N(;;*.'& ?.'* **'-W"*. *** **"** **g" ** " W'g* ',," * *:

r,c . %.M,m 9 m.,m.. ..... y geg. g ee m.,

.... w..v . u :. :,... ,- - , ..... . w,y.. - -c % f M.

h f _. ~_ p . ,.f..m %. #---n.._ .A.

g., . y ., .8.% * &@ufQtf(b , g]fe - '.. _ Q .__.- -:- _; . _ _. ~. hgtp-[w4AP), . . o.

Nebe% .. v ;. w. '.% 4* *C W'*if*MI

Af.[ f ..h.,. k $ I 6 %#4f*W J .g . .. n ~. w,a c.,...g. .,% r .* ** W; W=dWM.d *cW,*M,.f.o an**endeof*=h*d'er.a,,.m.,.,..p,g..., s.pg4,,m.3fej seal ; 7,..>, m., m.,. ... - .. . r~ ,. e ~ , ' '."* **.aajM.,*e*.n'e-M; h*.*W,s g f*W.=*m.

sjtud ,eep .Ji g p.a ,ipty __.,;,w.,,,, i . r m

k** *6r*.a t,W.ea as %% =-v m.*,W*.h ***Wi.thw %.,

'?> m* **.*W r r-r(poh.* ,. - -n.r4, r y9 - m c . g . c 'L.** ' M.G.e.U.'.:'s.' :cW': in.*.'f W.S.-1,P/P.M M,.M,um".S7s.,* ' *C5 r.~cid,*h,2A '%.b,;g'f4G'M4.g'Avi'M M'T.*hW.LO* P** ~*

ex,.e n.w.,,,sma .we.ew,oun.** evw s=.s w,v " v ee./N44.g.nn.as.*e -. sm,,+/'*.".useia.ynung. y&6,,es..e. s.4 e :ar._-,w.,e m p,,.".;gg' ",.:m;.p g.;v - - . '. 24- - ~ - v.

,, u y au.,m.w.

. 7.. y,.,y. :.,.. ~ g, c.. g - sm .... pc..,,.m,.,.,. n..,r+....,p ,,y-.. A.;y. %. s.. ,- .. g,

(L.

.. - - -

we.e.*.7u..q

.y s..-.+ %< + .

~. A. _,>.,u.

u. m.... m..,s.... , -. .u . .

... n u..,.w. 2.: n.._ L.t..w. s y s m._.,._,4 ;.,

_a.,-.s..,.w;.a &.. _,.p.: ,:a,; n.,.w. _ p*7.ua. ~ g.... m....-.y , u..m;..~.y....4..

.~... .g. .e.

.. . ..m .w.s.,* . .......,.. .y.m # ... .,.,., .... b. 7 p.L >

%.

.: %,.... ' h,,.. ... e er.t.,4 - ..-. e y- .. - .. ... . - a..u,.. % U. M." i e Q J QdIst@... ~.....- h.. ,, *. k h 4p,.. . s p vv.. se y. 4.- 3. wyc;(.w:,w.,.x.,v.s *j., OS 19([hd=$b a - - . r-

Cve" [ ..;w N(*,,. . & ',

  • J atto g,'

. s.m.w d, . e,;o. p.:. hm

  • - - y..w..Ls.. m,ea y, v.s......% m
w,.Jhw.m%+,m..
.a%.rm..Jpm, w.m.%.va.4 (f.,w.f m

.. re,r,. ,a~;; n,,w - e g ' W vSw.W .fe...x .~ vee .% qfma - 4, .. - - m pws w

  1. t-vk d.elt.E pt.O...-.-_-..__....._....m','.1-

.. qw'S.7C.W...l?e m.e e k..~J. @.Ti M 4 ~. dC*M80.!9eJam2 p:f" ' ' ', -_ M ..M_LJ.

/

_ ... - _.. - _:d.

-- -- -sum E _ -. _ _ _- - ..., Ja.***-_ t ,= =#. em.

e=== m weemas e r n_.

- _- .__r - .,w=w -- _. _ -. _ _- - - _,... M4@.3M,., J ,.- .. g y-

g ;

-', ..< pe ew pe e .me V _ - WJ '#."Ata@*.,*.MG-Nid.: .'.b Nf d,$ M Q

  1. 4 k h '.D'?[' M d w nam =. s [Cr$M"A+1dNC-4M w.

~ ~. wmm~n.w.m www.mn,s.p';i m?qt:.$yn; u%chWp*ffp. - g 2.~ y.(!w ..etn~*g*+W'JiW5.Me*"*Pg.y w 3, ge m.... ~.. q: %,.,. %.., .. 4...,..v.,. a. _.:.'. Q.y %.,w w % y, g 1 n ~ z , w%. 5% an,w. m m.m,. .~ .w . g-g . - .w . . w.

- .m e.~3.

  1. . A-2 hw %. ate.-<.: - %s *m m. y

. u.

w.,.3.= a . %, s., s s u .w e .w.w eI.'".4g .,m 3fm %.~e t, m. o.y. w...... g.

w c.

e v 4,+ ... - . gW, t..e ...,.e.... w. w w., e..p.. u g c w . -.,. ;.N.xw. :rr.. w~ ;.",e 'ga..G.. WN*c..;.gd. m w......... . %.. - ,y p g. r.,.?., y p. m.%m %. '%gi.%b. w.tr . . .e.. m.y w - , - ,c .. . . ~- n.,w.w m ~. % m.+T.*. yhM..s.,.yL.yC. c.,e m.w:.(i.,Qp,5;;'%'o.g.&. ghk; L'hytL% ,r..*. a==. f.%.,.,, e,. *.' .*M

  • v*

. & p. W.4

w w w..u.- n w ... ., -w o,..w

n

- .- - .& . ,_ w*.M li'.'

  • n ?.

y,.d.

_ : ~ y e~; M s m a s-

  • -;

. E. p ,..., r A . a,.w e.se e .v.

... m - MW y' v't Q,L~. n----, - Nj' y%.". 7%^'p~4Wg"Qi,Ci,,L- . , %~..-= ' m&- TJ.,QM:g:. <y.....T

- - - GJ"5L.,.]n&.fR'U.qi%{t.'t.e,,,_

  • Q*

- -,. C

' . g + -ai o.

.L. a.~.,.m.....O,; C.r.,

--W-an.,, :e. e* en.p.. ' Awtzav+. e:ine m.~a.

. .ww ..... ~,.. L.. t.m,,J-m,4 tea.: **-s9. d 48*"q.oso ar.c. mo...

n w wm.

m > s.

... - ,* - x e ___x.p.e ,

-

--m.^ - . v 184TW.

% y=3*96#

. p s.* 6 c.e.

.. e w fT r.e - p= p.N.,,.% +/Lr ... _9..n..,.g-. f gL.g e IAe y.u; f .=*g # Q..,+.:- %. t,.w...g..,.$...,=M...r.. , . my-l ,r g-W . m..u . .,..... .. <~,. s. . . .. c.JP

.. .~ .- - -. ,. -. m~ery. L,-C.g %~ N.

W E ,,.*

L'- ~$, hfd"' ~ '"';' ,~ .c n ...m.8- %n,.T...r n".W1',*~m~ e. - m,.,.,. 4..m.... :t %.n...,b. m .sw&,...w.w~. AAm1..

  • - Wi*.,-d.e4.** 5 y.*.Ms,.*'

-.

. r, e /.. s?e.s-*.4 , *. , n.,. --.:. u,. w a.... r - . -- e'.. e s s e.u.4......-..=s.

. -. .%e ... 4.a,. s.

. A... -..

.,m . . $ h.

. e.s +. *4e.vve4= 6 .e y.y - gyu.:[L t.F g gg y ma .s

. m -- . . .w,s.%. =w A. y.s.s..sr,x.%. m,p,.p.g.; g.gm opg* : ~.yyc g.; ~ :x .ea - ; .c ..r.. g h.

. 4.,v.sm -- m w,. a . -. . w-3.

w -= . +. . . W * @he a Wr, a==ava b*;*e= d'3',4***.e y* ee.sweroWen.wAnse,sieA.yes =wvp4t@"N f MW M Ws,,,,m.;. a.y h,g,4. Qh_, (page. NE' e . Q.k[d$hMkm b h *. k k h S ir.- M r b*hMNd EbM..f ,.m..:_n ~ ~ e mm.m.m s w.n w c w.#.v 4.,..w.sr-e 2%is~ m w...v.- m

* tvQg.gA.< ?.. yv%m,...w;,.mpM,REMTM.isG% w !@W

. e...,..w. m. e m .w.

.... . . p m..:. M,n m :,y m.e @Q. p.v-m.c.cmemw s.Ww%m 3. &mv % v

M.5&M'.Q'.

WW, W 4*a+J- ' . v.

m..g.. w m m.,w n6 ~- m.,m. ~ * w-w. ~ m.-> v.

<yw.g .w~ . +0-V me % - n,

.O. %; w...L.. a.,,...,.,.,, n,. w:..; ~. e,. m. e.

.

  • ~.,-

~.. s n.d s.

e

-

e,. a. m ..- - A.% c. =*O WW *.

        • Y

. ' * ^ * M'4 ' .s.

-e ~w -.s,.a.M.

4..we..e. p.o.. -.. *.' =* . . ,n.

,a.

. 1 u.

' es a ~- ...r.

y 9'*%+&W. 4.a;'*'. -r,t*~f.W*%HMnt- - - - -O N , ..=. S ' r*. ye^.* $.* W . o *\\ b, 'Ss < 19 a..m ..t 4.s.%.u - m.c.:. U.

.c .

. hW-.*m.** -J -

- -. >. = * eso sa.- 4.

.-p.

,e mh.Q..y,*5.[2p',..5 WWM._sm.2D5-s ' S.+5 W.rn &.g %. %. .7 ~s ww ve y+r w., m,. w N s& g M.,,~ f' r m'rgjy..,,.,.. hn '~.... m, o.., e e.g. t* ne,- s hN . 4.M.&,; e p.Qf K,aL.^^ ' W' ' . 3 -- -... 6-< - m.j4 +. -. y. =y. T8.

D4 _ m. f *.n*s,m.*u.:. ... m'p, w.e. m ., ...e n , j . ** ..... + .. _,w.

,f t. '. '. e'.,,, - n c e . - * ' *.:. ,p'.~ sa ..- ~ e.

,\\

' '3 $.W

,

b 'n--*4~~ 7 f#

  • .

[*'l*** ') .. rls'.' - 1r %

    • I*

" * ' e,

' # ad A' ' -.-x &. Q.i "a".C.j*& p'W"'" 4 's .. sa. ' #

.' '.?... g ' Q."_'W..' - ,e

  • ..

2-S,

. . - g ', k ~.4 ga - * - r .

  • '

~

.

,,....r. vu . ., ...c + .x y :. . n, ... ., ..... i, 5.. f' '.. h: f

~~ C

  • -

.. w. m... m.. r.p........ -..'%Jt,t 9.eM m 't:

. , ,. . .,. ,. ~%.e 5.g..; -%.,,. m,. w.m ... w'. . ~., su .m.- ..e.;,..,...~,. . ....q... . + w...s ., . - u -. -NE .~. ..... ' . g. c - ,.... -.. ... . y,. M *' .y.>. <p*S= 8% i."T .g , 'Y kk 4... - ., . 't M ~., ". N ..p.. y Y. 2)NIIUY.in.r..... ~ M),,. c. y-. e*~s.m m.m . v.

. m. u. +'.o.Q'.y! s.O@S v.

. '

4M $$lgG[ECE'svf&p ". ...s***A . c n.

  • ..rYo ~t',T$~.',l =a&:ls'

. u~ .- .., ~,.. . .. .+ . w.n .. ~. . s ? f,,.S. *. ..._1 ... $ . . . '.. g. '.> ;~ e s-Q* .* O ,. ... a' ? - ., " L - }n

^ o, .'g'y} q g.

.e.

... .s m.m. - ,, ...+.... .. - a.

z...

- Q t .

, ~ .. y.. _.~.. ;j %.%,g;., .w;,, -e.g- .. .. ~. mm ,. , , ., . . .; .. , .,, -., s % ... p,,,,.

.g,%,,,,.,,.,%. ;w,-, y,., ;,g.,.;, a

- n ,.,,. . g,. 4.,. G,, . . .a 4

r y, . .,.g.

. ... - -- . ., >.. ,. y. - a.,..:... .~or.

...A .e ., ' . ' 3'& . * ...y.. ,t , , a.. r , ; g _.. - . ' d,,. Q.,. 4. ' ; i [*, .,.,/%ea.1i } 4 *- 4. > <e' 3 ' L . -l*$ ' 4*- M * + - , ,,,..

  • - b d-l' #k. k.i

~30 ..T.h.*. '.C DNbNC, -.,q . ( QM C,,fC.

FO Z' * pg '* ,,n -.

.. A u p. w; h ;,kr'Q e~i %x &. -.,. ,+ m.....Q Lyy,*.e.)<.w &y n e

g-

.. v - g.

_ .e y ... , ,.... ., ... y 2R b l " G; Q:.; a N > 5 1*k.E.h;fN K.

s '~e.,. (}ff g.,. N.'l

  • lf'

- ,- Uk f..a.f.C U, '3' ' ( . l ' 7;. f' ' '. 7 M N D. A. G..., 4.... ~... 2..,W-. % ' .- ',_ y . -, U

.,.-..7....-.;..,. .4. ;~ .- [ - -D [' D ..

{ g % Q dd4 .

._.

..g g ...,, j e.

.. , w#AM,u _ J ' ?. m.,.

s . ~.. . m . h:

. f.

. j.' '?. *. \\W _.

.;. mp p;n.

,.,, _. .

.4 w$,y . e 2:;.sily%w%CCs& m m.g n y ;;4k.W 10.%m 4 m g$$o'b$h.DW. n g$ E _ % W.G. M % D ": M id. M' 8 6- , . , , - - - - - - - _., _ _ -_ , .. -.,

s.k.i U... 7:S:.&.;..~x.,. 3.... Gibbs 8 Hill. Inc:.

  • - L: m c. A b*.'-WI Q

-

.. Nm 5f M. 9 5 " 5 " 5 " o %,Q. n.:. ~,+.a.~ +..-sa-. SE...De$.M.M..?.M. N..:?.gmm..g.g:nu.;m,.c.. A .. 0q ~mm .- . ~ q.m::. g..: s.,s: . ~ . .. . M, ,a...n 4., .

-~w x w.m......;Mi.

nt-- bio.G.

ak...:y.m._J.?."..%"q: .a. w, . w.g.3 -... .. :,..: w . .. ..... ..;sakw.- . 7. -.. 5

.e. wcw m *r-

.a a. .:- -., :n..:n., - . .

< y.g~..

..n..._.m. TGS.. %..; ., m,..-. ~..n,..-e s w., n m a.,;.e.r..y: n.c, w o u,.. w. n n,......C.Y!..!.!. J...:.. w...........W....... t.n G.

.S..t

............. w. o-es,.. u.. ..... -.- r . .. ...... .. .au.r...mw4.m m, b.y m e ny - 4 y.v..a +:.. q.

+yyg.a w r, x.,.:,y...; y e

w.w. p., m.?.*. 9.,..c.

.., g,...,,...~, ~,...,._ w,sep g#.. .,1 .. a. :.5.m,, ,.....-..,,..,.<,..,,er,..v,. ..... w...a .. . t,. .J s ...,.1.2 y .....i....,.. . g ... _. ..#. . .,. s, ............ .% ..,..,. c%. ..,, .gf,. w... o ,,r. , .. .- .. .... .co ... . .. q.

.-. f.,,c.~ . ... . - ~m.

~ ' Qgyp./. Of M, '

h.<~M,M @

..w a e.

.. ' kg(.,.. '.'f.. . '. . - w.. s. w 7 w, a =. [g..=)Q, Q,(...,... ... .

,., ' ~,

s. .. A.

. x, w., _ ,,, . .... s. * w,=, : .m., e.t.wQcg.~ ca .. u..u.

o. .- . -,. y.

_ '* ;R. 0 +ms.eseyr:ewsa,.mw ycu.eae,s,wjiw.w gr.;.w.yx en.+sn.a.m,:q%,y}.*;*M*q . .,s.w o ' ?.s ?- a.s- -, _.w .. m y r.. y { g:. .j - r * J %* Ai,y &**yy y Qsf.frg M Q.

me s. 4 +, v p.

.:s - y f ......n ,. - ~; .x ........ .o.~-..a - u..g . . .w.

. g.i v., g.- w n m,,, n.

... .. y.~.,. , a.

.a :. v,- ,.. + N'th.;'4 W W 5 %.".,4.cG k.r w.._ ....,,.......-,.s ,., u ).u, G&.. y.M.M,,pr.e;v.k.,'3'.%,:,L..' M.u. :,k',WW.li.:.c.#.#y %.,%,.w h*4 s m.j, . Cs%Q.

  • :WG.:., %ck. 'h..,,,.'.

W

  1. -

- . a

  • ,ew mna,

.---..a.*-- --M -. -, %.

o ,. h h*..,.. ~., ....._.....u..*.g m,g@r nW.4.*.G wnj.k @-Q u *A.%".%.%s.w. ; O$:,w-p ., s.. ..,

. ".";s'6^ M. W s, &. m - ( 7 Q* g y# 4 g7.yy.

. --.-.f',o -

  • p

- -

-. e . q- ~ ~ ' - - - - .c r wy. .v.. b' - .- w wp !_ = _ C W..,4 m.see.j)g.@ mye s'.ec me<v+ y q.- e '.. - <. - 0& L.., 91.,,%n _ m<*.e ~ r.* ndg(e. 3 p,y.%ste @ 6pf eg,q ys.,g.uy,sigsgr,e,.v,p.4ppp %. a. esp. W'.~.. . c.

s. v e n.pa-o w .. e ...... , +....., .. . et ae.

i._'~ . .s.w.-.m:ven.c.ss.nya = . e a ygspp? sgram_.. _ _,.-^.,, _ j,,e.

. s.. "1 0.p. g...es e r,._ p. o $ c. r ,. -. _ .,.. ~ %..W.',.;M::,,.*W D;W;'.:.Tr:9.M;Cc.*A~rs}%iWC.M.m Lhm.t.~.C,@.19 iciW.M,%.,;'sGW,%

  • . n M;', "..LX ; :.

. - s _ - rcr-tu% . w...,,+. v,y...___7-f 1;;._ S.,2,t;wa 4.:,,,w e... .-r w. %.o g% % . -_x - _ _.%... % m, .... yyq,i e..m...m....,e,,-.,..+y _ y ..,rr ... _ -...,. m..ma,yg_g +;gy 3pgg - . . . y.

..

7 'g. m cf.} y.y gjQ. );g .s:...f

,.p.j.-

,. g .y q ** w h k :'.i a,. s r.,. % n..,s M A._. t.,,._ga.%.,. L.: sa.;;.i_u it;.4 +vM b~ c... e >,:.: a : :. _;., :. WX4 T.4.aasf ^. w.,,...._,.....J... -... .._ - ...- .. _......... ,. , .... . .. . . . . n...._ ., .. . . ....... ..... ......,. m.. ........,. . . .. .v~ z :. ;. - &-$, n,,.%'.*5*tt's ?$. - : '~,n' Q: ..., & A&.3 55 O. kQ - .3 . .V .Y K &..gG'ff. ',...'w, l**%y' 9*p v. 6g.m" 'd. DN, Q+ (C.,&... x ~".: @ ..f f .f ,.3 ~. yggggp, m.aN.,93.. g-..- +,yg,g.w,gt,, 2. %..,, y,.,.c. q,, Q y c.,... f. _ m.,. &..gg g y.:.- -y2 ,n

. = &,,..;.~.,.. ~. %,y.

-=m gy _w -.; . -.r . . . [ . .,-..,,w .s - k

  • .

fh , C4, # D _... . ~.. ~ - N4 f3E&, " % . ..,+,-. ,.. , s % w w,A ...,....+ +._-, *, w .<,,...,.#*w,r=,.,.,,-- , ...w , .= m.

$ -.. r...h % ~ r.

-

. _ - - _ . -. _ __ .v e. N.*(** W.-- e-e v.m +.. f, FI',. _.-...

.
_ -

_ y _ =,. .. ,

e_ _ ... .;A. ; y.. c..c.. g.,.s,L - C % v,a.s.e W. <.:., ~E =..,s,.s U. p : --- - -g.- 4:'M' ll3"@ w yp4/m,+A.. -gLg ~. g. Q.

  • ..--

. . .-,w: -_2 cs . *. 4 ' sr, .; --. - . .. .,e, ..,~ s, w _, _, .g-p, /.A. . . 4, L - . . . w. w r + r.oot....:. 3. 9 t c.J*..,-_. v.. + p. A %_ - -. wew w,si. epr / m w..t .y y.

  • .ge.

.-,9,_,.:;

  • ;. - 2. : - -

-- . w., -

- -- - - - - - - _ r, m e,, sp,e. =,... a f . w.

. +.-j s " VihW5V,NT. &0,'Q .NsQ W C.,Y '). u* : . 's U.N $'. W. 4 & W W M,.u. e.IW A'.$. %. % %wn,k. h:.A % x. N.

.,- UX.*h*W%dA&,a W[[$)[% - c- ..#ndn-p.es &'. .a n4.Mv M.. .t d w .L g..&..vor.

re. - s . %. - ,c- ,. .., + +.

  1. .vlg*-m v.n smugs.rM b-s.noa r ne

.ee,6 sw

..,,m w. %,a.u, w w.

rtr a.a..*.m..yo%.,.p: % +,g.t %. %.w,,.f'. .o..amA:.+ L..,.e'sN1;+ , . e w u o.

q v.,,,v q-.p wa. 3.g.,. % g.,a,.+ w;., m a;.,.,a a.v,,.A.sg.w w; g-Sg", .e.

.e -4 . , %.., /. -e ss a e +w m 5 4 ,ps.q.Av.

..w. < w, T Ssa.4 ..,.L :.c.,i %W.9...C.+p:4. ; ~ *.4;Q;.x.~~'s'.cq *:a,Mm w& yl - -,u . .6 . y.

,,. a4.

.r ..a J.,'e. m,, - W t'..".. ). n> $ M.~ c..,a p. Q.; y.; 'w!..,y.% ;.,e< a. &.1m W-w.4.: %~.;~x. :.. ;; ya.:n.

,w.r.m.@ : . - . .

;

=% cT s W sN^ a .. .a ,. .,

  • v

..w.

.%w. w; M m 1" e .. - ..... . . u,. L v.,m,;,.1 <.Lm.m,uc %.. my.y ~-:w.~ c.n.Y w,%;w n . a . q* p O w' $..Q.L.. e3.a y %.k..A.,.,. u.,.. . .,. # e -

e..m..,.*'T ,~..\\. , .w e.

..-. .w.e,.,,...~, .a - - +..m..,.4 ...*- .. o r . ', m.%~m H ~**:.1 %. M,n:>. w m.s+ m. % & d,.,.z..w.M.w M%'==n.

g,2 >;l 9:$%.s.,w,c'.*,5' + L+ m;e'k.4ef%q*h ,.a.,* 8 -- g. p.1 y. :. ...y:

. N'%.r:.t, e., ^ ~- u,-m --

s

, s s en.~ ~ ~ u - v ...,.~.g *g g,'. 4 ' W. gy .. .- . -J-(. 9 w

r

. .* r ..,,. . ..yf* J,...g.- i . . .% M.~ % '- MG .M- % *.9^9-nf ,s'), m

.m , i. w st m : w '~. .:.v :.. w u " I ' u, 7 /, ;.. ' x'*.M. Y! *"'* 7'*/.iy**M~.'e * '*' * 84'**" *p,Q g. y. Q ~ *y". *g' -* *g*[..*3* ,. ,.,:- Qhu.4f 4.g/.N.-rQ3 5-MMk.$.'"*.'**T,, Mi . . ' g a.** w.,.. .,, - - - -- . b-w p . . .-... -. ,,f.. v.

"t.4*r%..iW,r TN.p_'.ntaa *.v. ass W,d_vd.ry:tPtht%... empbsTY# v=. -w =p*W.n. f. L~ -yW. c.. M/q g,..s.tmr.

. MVi t,,.., y.,...W, f 6.y-M.. 'M'.. "s K. g.. Y~ y,. - .C J . ~.4 .

>... ... m %..%* .. .s.... .. W ,mu.,. 15 > *%. T;. A,W.a. d.

. +

  1. cu.:g. t&=.9e*.ea.g. 3. a

... b,. .e. d..L,,.A.

, - .. m.

.w.7 s wq., L p~.w~- e,.q.r.

,sk~.eM :,.. ..

.;g ... s ~.... q 7.y+ g w. 4 .m,..4,- . . $ . t M.w . p-c:.W.,+ p g 4, .

...... ......,\\. . @ a .s .s. w,* s . e.. < .. < .- E... .& c+ . :. . -.., m. t' . -. .g<-

  • .

W .M y n.< '.A,r'.a @iA/iI* W 2 M :re'* ' 'Og ^ ' ') D. 16: y*s**.-*W 'M: '*ik'!p> '

  • g*.....

- , -. w t ' > .M** W frd * .- #, - m.'. :. w.,....%...~.,m m ~..t'G F!.4 6.

'A "ib*h -

    • 4m W.^

'#- rv- .*. ~ Q4M-usk +9.u.*$, T e-- e". v.c.v.a * g.,. f'.6 4 e**.t esi 4. A =w.4 iP -e, %.s. k&' e?. p* h...

  • W, M. k.. 6 - - '"**f.. :

r ' ..;. u,..- Q Q ~; (h$

..M v.s:. ~ . . h pr.M . . . '. ~2 , wh

    • n s

. y .. s

-- . e bs" v - O c...L-r<. , w.

w U.=eae

. wa+ 7.De %' :*d$.k s# N T**n.,. ..w@rQ .,a ...... ,un.

me n. " _H . a c *G,. e $.C.

h.' .

  • .:

. 'I h k 4.: a.'h , U [f _, $a,. - t m. C.&~. #,m %. m -.. _,,.m..,., %. ..... m,--m:..c.<. a.

, . z . , . .,.w,..

.-

,,;.

y.# v . . ., ',,- .. .,-,w- .. ., f.. m*M** ' (?.) . [h . . [

  • ~..

I , .y'i.T. ~ f '. ...

, ~, " . y,, ...... . n. &. x.. *. "....sa.r..

, e, e }:.s%, s.,....,q.,.,s.L,. +.,.~,.._ w, - -*n- ~ ....., ~ ~ . p~ <n.,s.:m, a.. : f. ~.. ..:.;.--...y.~......n,...-:n.w. r..: 3. +.mn.e.s . . ~ ~ - .w n..p ..,. .... > c . .s .~w w. M .w ... ~ e e 5,.- V@ '.$. NdedfRb,.1W.,.d *-.c}.2 J-Ard. ii@M,, k., Qgrv,=$ef GM.mm.h. m.5er5,nr$.. %! M1.4PtQ f,n.

Mk $ j . .......x m + . rpe - -.,u. m p m uV .w.Q s.o.u. 2 p ~ya4Lik.% y * 4*., .. y f'~~. ... -,, ,i ... .., 4:.: M.s.&,..s b. 'pgr.J,3. 2..W.m.,.,7.-

a

. .o.c v de- 'n -. r ..w,.. n. +.n. .. . ~., +* . .~s ,, . . ..o e s s-y.s - .%. s.t~ ., %4,a.;.ygM.w. Qf , um . yy. .. .,:. ,, ~ ::

-. y.' .:,.. g n . ...n.

. .,.,.- aQr , , , - ,. r.. .&.;.,.. r %..s.&.., n.e ~.. m /T.0 a., Ma,. Or . Cr R ~. +

-?

.. m.. 4 r,.>. . ,~.. a,. ~V.

~U N.ea* A M O',,.,se s.=.r N . n - ..~.5 '4[ * . *** *IP,. . N 4- "^"!. N O. QQt lt1 + h. 4(*6'*'// w 4 = ^ * * * . n.9 . { ' +w ,,.., .% (i w.

  • ..av e.F. e A -.

...

r

  • . fL *
  • e 4.4

'. 'ae *~-.. s..,c W T4.=; 6.e..t.- w.

. .- * '

  • s

,i . . sea,...,- y., . . p-g . cr/D O M ;. M , . IN7.,c t Gr 'h t't.oo o . i G.J. .w,p., w' **. .m, ,~ v e.p Aw.n

  • ' *

- ' ' .. ... ., .. -. ,d 3*.# ....-.~3 .. +.... @hb.,.. r - e.. -- - $pCf 'C. 'I .' 4 .; Ww"N.,..=. g%.'2 eT w.u;. a.

. N.

s Q.

M

e +-a m" e '. ,..

  • * y ? :n. - &n.:m 'y (*'4 +^' Qty *Me&. -.

c+ . , . ' %. 1

  • q. 7:..:. c.. ?..

, s. & %... en.h): .- .. s . -- .1.e,';r ' '~r.

.. ~> , . .7 -.*.7s . s .,..,.n... - be .- .. . , ~ &c C.co $911. w t&. 0, N& f,. &.[. 4"$ E$jf $ ' - . ' '. ~ , -

./

  • P-9.,

- 'b .# 'N.3 ..)-=

J...*W Nd

  • We [ 4'.
  • - *

. a T.- s ,m,, , * '

  • %

As p.

- &rke hidf.. . .

  • e., g

,{,b(

  • .

. 4. m'.A., dk Me * * ",ee

  • .

..r.

- , gN . " j ' / ~ +W

n . 9 ;~ ' * , A - L .. ,.( -J; C o $'O * VT. N t % Y 0 3 5,,{x. UGG; s& $5 $.(~<.h9$ ~ . A . u..,... ~....s.. .., .: ... e ~,.. j.~:.]~ u ~ '?-'--.* ),,.i..,.. s

  • rm';..'ey u f.y. w,,f*'.*

' _ _,, , %. A;> ', .n-m.

. g.

.,. n. ?, . ' ', . p s.3 e

i . ~ ., - .. n g q.;: x y_ , _ . CMCCIC FOL WM.

~,E 'Ah.* z / a ' %, 9, s,...~.. l.r ;,'.f *. 5.,.... M. w ~i %. ' ,- .**w \\ . . e. U.. A,.E 'y4 4 $..*.

em 4Ay

. T. ~?. .-v ,, ' ~... + .C.L,.'$C 2 b %xk % ,& g,;, & *?p. l= y f'y-L (L W'}'.:,y [.' O te,,#f.&s?'%Q.

', , .. ; %. &c." '. ,...,.. - .- w a . n .' - Ry ' _

,m h..

z
..

w . ..u.

, h. c..+ :.. ,,a.

, ... - $' k*k$hhkkhh,f$

  • '?

l *. ..,. n :a.Y.h.h,. ? h.

. f.. q. g h.. N -- - .

. - _ _ _.. _ _ _ ._._ .. - . c.. . :..,5.

. .. ..- ...-z.

, g.... 9 r..,. .,... ..,~..y.w -. w.....y

-..

. . . .,..

,...

n .... ~... .~a ~ a ~ ' .. ~.. +,,... ~ m-.E.~300.U!.G f 'Y-W 2.,., h.t-L Z ?.*-. J. W Gibbs 8 Hill Inc.

.

L .I,jfT.'+.u.7 '. g %.7.. ' --.h.d'M tummtns otsices. cossnucto.s.

W, 3.,,,,,T,og,g[.

. ...mv..._. s N,ew venia.. ;.. h...@.w.,ct m. u... q 'MS.J5. s....- v.u m #g.

.n.

.--...., - . ~ 2- ..w. - ._ .- --. .,, c ,.. .n .c ..,:-,. ...c c .:~ .:S~ w cw w n.e.er-- . ..,.n.~ w m..> ; ~.: G.

" "*-------~ --~= . W:@n w.z yQ$~.. g p--- g;- sg.@,-3lg,,W.u :m.n,m n.

  • t D=*ssee n --..,.... ; g cm.--.W---.. xz.x.

0 ;':, ". x. r. .. .. .-.


~~-----------

, ',")....s m.ae..... .. ._. m.. ~.,,.........+ ,.


.

.. -..,. . , , . ... ~. , ... . . ._.

....ex.. . .,.,.. .- -. ... ., ...,,.. -...,.... ..........~a.

....... .., . ., ... ..,.... ~.., . .n,~ n.

.. ..

. ,. - .n~.~.+..,. ~...a.

~..r... ~..... . .._.r.. _ . _ +.~.4 em n :..-$7.o.w .~..,.@G y....-M.:.-K b '....,~ C a.~cW,M. -., . ...o.~,_... ....,.. a.... ~.m, c...: .. . n.

n .-. <..~.,c.

... .,%. -.ur, = ~ h>. +.... .m-~~-. - .,. v? c L - - .a,gy;m. s.w ..w-. .2... v.,. m. " ; ' .,.q. ; y a,w s t. s... ..: -,. ... ,

  • ,.

. ;.L- ',,..

.. . .. *. z y - :',.,.s.

3.. <-a. c3 r~ t--e_.e,.?.e....u , . m-- - +- a n ...::~:c=w. r-m.e:;mv. hr w:.mw.,.a, e<.y.m.c...e.. -m w ~. p z-W.:~. a.

. 7. 6.. G v... x % .y._e;_ ... e.m s.m.. u:w

. . . e 7.,. _mev., * %... - ~ . - o.

- ... m m o . .. .._. w p.

~ u e.,.o,. ,. . ..,, . . . ~ .,._. . _ .._. -, - -. .~Y*pd -.,p ; ;- 4 M * w ~;,_,. n'. % % ;e u. ~- m-L . ,.y~. . .. . . t.. - . - p s.~. s.sey A.-r.sm:2.;er Snam )*H 2 'n,n.weerM %. ~.y-y s* ^;;i - -,. ~....... :.. .. . y...,. ~ m. m ~ w-n ~. wm.. $.,e d. c*~.. N t. h..y.. w.. p,m g w~,..,v... ~, - ~.<~ ~. ~. r~ -m n.u.w . ~. - .. ,.. .m ~- A '%Ci*r c M.73'D . '.X a d to n. y.bn,pf,.4 M Lf M ;",.20,,:6 ', . m m. f'.:l G:." .ne . .... ~ ... ..

. n.

,w w .. ..... - ., e.

- .s..,a &. .m,...,,.... .. .. ,.... . , . .g.

. .;w . - A.

. e . ..,.y.y,.g.,9.g.3,..,, 4 yG..,pg(. .. y y.

. .. ... .. n _ ,,. .g.

.,. 7 .+,3 ..; c-.. .... w.,. ._.1,s. m... p c.r . v. t._ 2 : w. w. o._..:. u.. v.m.v. s..,,....., ... - u - _ .:,,..,;,~... ..,.,v.~_.. , .... r_.__4.a... r. ~m,... . ,, ..... ~.,... ,,;....

.. , < .. . ~... _.... ....,. .. .. .v . .. ....,r3 ri. r,m -n~~w~r.uc. r ;& w c:G,Gr ; . ; .

~ <

t ru':f ~~.n fq . g... 'r..-q. 7. ;p m.,rrQ:M, v y:-

.... ; c. - , .. .j2,4.;r "u. %.s, us w.. o ;.. ~ % .. . .t .. ;..a w U."*orpK,mW;n.&.y%, f. w,.s.e.#.*.e*;,Mt* p m-W..,,9.. miW.+w15%?.14,'%,. ..G s&y f.;.r.M'.:~.m.%.y,v. a.c.. n ,.. - p ".. Er> p Q4.

. ..... ...... nu.A...,. ..3 .. Q"- *g y. ept',t*' ~@*~ g" ' h-'*' y % '4 _R_. w.w.,.. #.mdm /713. 47 ko""c>%: $. 6y'.. /.. /...u, ,.s. v m.%.. g m %. .

. Trs., qt.% y. w. w.a .dw+glf.d?c. n %v g

  • 4,

_o.

. r o..~be> - ~ M* - ~ a-y 6w <.g ,.. ...

-.. r.:::

... w ..n.

.:,.m,.-:.*. e. =. c o.w ewmevre t.a4 s e mm;s,*.epwo# =e ima.aw.,, w.ws.4. ev.Wo.. .e.w.

. . . . . . . . .. . . ag.. 4 . w m..- - - a.

u.,,o . w.. -- . _._ __,-n,. - _. m - m m- ~ w.. _ __ . ~. .. . . , w,.w - - - - - -. ..., a.Jrac=.. - . v

... _ - - -

-,,,,r.,wm..,.~ . _- ' '?.'&.T.,.Mrkbu.k..?' $ b 'O q lsv>d.t[E,bOJW W O* . %

bl.1t?s$.,;i%dC,l$.f.WK~t.dl, 5 %M:ii,;%%C :.;*, Vtd

. i.?.**%, .~...&.- h.J .;,- ..h..; h... d **"* M **** ^ - ' N n'n'rf4%. :..,.MM.r.. "..eqw c, M.;.a...s.+..n.p

X g,, BG'.-M---^ ^

.e ,,. a . . . M.VM'W.- W'P *0WWi" " 4 M'7 W*WiL5vdMM.~- w.Tlw..,L.d.y. p 2 i. 4. vg 3. 7.,4g'ML*.,.M'W MT.26. My',:. gf.% ym..f.

N g. ~j. w. Q.a...:....c..+. */ c.*-- e,.q,%-?*c..4. ~. m v. *t.,<. m ., . e: ; w.

.rw. 6 u ,.,4.

c.

.... %.n,

4 . s . w. m.w et.d* b -- M.% h.

.v ,. .M.W . o, %,:,wnw ..... C .., ~.., w.m.,,,r /pr..W,..._.

+ * m p y. 6,, %:.m p** Q.;.7 L.e: -. ~, ;..#.... s. g,s c w.,.. s m.... .ms. g we.43. h e. r p,., D, . ~ ,,(.., .; %. . -......c+e 4 cm .,

w.,v w, c_. wm... x..n, v.,te $ ", %%.% o&,v,.A :wM* s.'-* 7.f.'.-."f. M.%.h * W*-~f...,,,; et t.L.t z,,., TI t'V'.,... ,..,..,s ...;. .* .... .ws;u, <..w - -n.

. . - ~

m., sv.. . . ..v .- ,. ... m.. m... m. %,.:u,,. m.u s..ct e. .... e.

. .. a w; A, ~; % y.~:a y. ~,.' * g.. -. y m.,,. e ,. ..e~.... - .

  • -**

C

.

., - ?d.L.v, xM *.. - j** sp Q' ' *~. %,,,.. ~ urw.,gs. 4..mw w -,.o.p, e >. we. 4.p%,  ? 's,, t% ......,. % m' '., .*% e. m.p. -

.'..,.,..Z.wS, Q.T' "A w .M.,.,,

  • ,,.,,.~%..

4w my . -* .e . ,. -3 N '@ ; v...t-% a.

., .% .c ..%.s s .- .se...,..r.

.... e 7.. .-4...,.....m..s$,,,.... w A"*.'..%n - .. e.

~ #.v

%:r..4.,,,.s.I q v g *.. , n' .. e.4e.r s, g.

.. .... '.. ;:.,..ym e...a

- D ; g. C*37.t.hl*'.Y N.*N'"L"gns.is: ;;um-4 @SM.6;4a m * c. u..' t *.*

  • b'*v:$f \\***

.W Jo ~

ru.v ,r k.# U.-1 * * , '. S e+5 M 'e m: s :c"*##Y.' M.w..y A y h g'f*'* M J'{g'T""%3 ub.

N'*dD * *".^, \\ J'*JO 1.W* M**. .o..., 4* 79' H. ? -.u.': -='-e&:r'e.. . , '. & n.=m.. $k%W p , . ?.td W C: ,. ~:W . .~ _m y.~. wmy ._._--_: y. ~p ~.n..,. .u,. y.y n,. n.... -....- .p* w . C.. * e.... Q. g.' 4. m-n.*. - .. r .~ mr-- ,,,. .. . -, , .;.../ w . -%- . - Y.

? -v Au M.% *- A , m. %. m, 7%.m;;c.S.k. e *N - :m.r. @..wvx..lO g:o.r-[7.W . y.

- y . . -x, *;ee rigm.,7 . :c.., C..%, r5 >h_. _.

..n..a..s.v*. 4, m. M a. n -. - , . .., 2. s \\'. '.'.'~.a..,.....a.f m,ee. A d.. - y# n [. . $ -- - -.,. -.. f.

. 6. eJ

  • * *

. ~.i 6 = ifi I.'.. #. h*.i '.' %g -w..*s.a.4.'.l.h."~. er " [.,-...v.n'.e.d.,'c a ; f. e.

.. . M W me 3 y*

, s

'. .e i '. , d' k- . b) J e I e.

~y e. ;a. e[.f 4 7f.

., . . .. ~.. -. '.a w . ' ' . .-., , ,,.y: a.

,y- . a uw <,, .. -

~ '. -. - .A s. 4 + . .. _i k abP.O.3, 4. gS %

O .

.. gi.JW$

  • -h

.~ . g

.s.

,. a- / -. -. y w ,.g.

~. ~ ...w.. {.... *.e.. &,, k' F.

.c.

.... ,, e.%.,..y,.,. ., . ~3y. p,x 2, ,w.:s..ar. p.shv... w,. n ,o , s.,s.

.. \\., 3,. , .. . e . t.

o.

..

s.<r.- - 4 y. * * . , u.u c.,~,w q,y .w..o.r. . - . : .. m.us.3,.e..%,r.p.. f"'*[ O pt @, g,w. %.- .z ,.p -_ - & - u <.i'. 3^ q.

4...my.w. -. + .s.4 y _- _ w 7, ,~..y,, a.yM es h w ma._

  • y, a ' V Q.' -

. [,~,. A. . S. m.s. m...,,m.... ... , . . . ' . ....;,. ,

M.,47. f a - f.;., w$O W g *.xv m"-.] py.w. p3f' ;.A+.m a ygge g b

,- 7 L.;.".71; - J.? i.4, % s'dy, & ' m..pw.e.enn :.~.A,f. 4, W - ...a o* ,.ww.. v s. ;;., - . k& ;.- -e~ O' y . -- l'Y /- f .m.st:a . . _ - t * I ' M. y 3 ..,.. ~..... .y.

.,~... w.-. y....,a.., a.x..:. @ge-w n.,. m c,. w,m. Q.:. .. w. y.. .

,.w w.

x. - b.L.s...n,. e j 4 &. ~ , m-w ~- M *Abep N. O,,w, e my,.. ..... . -..-v'*-**W a w..u ewaveaw9.m +- o- -- . pg g; - e es'.' $. 3~.u r w*. h 4,.. . A*er. Pe*%j.ss Aw1 war.,ed . f'a'*'

4.**

  • . -..

U*g/ 2J,'.,/*' @r$. dr'm :.L2i' g h~.w ::K.Ed}%P 9%

  • e.*

' ry %. y - t' d *dD 'e J M.MQs=.d4 ,.6 % e.., g,./'6@3.s/E.:',sysC FM..'*n..' e i *. M Er.k+k N E b-- h}*N.w=ll:g'. . s .

+ .v /

.a,. e ..u.

= ;.. -

v 1.. - .,- g.

c n.. .,: --. u.,n ,. .: n W.*,,,.n. p.. -- ~- . .,....... j

... 4a,.\\..s,., a s s.. n ..,e . .. .%*.*=... . .. " .g p..,e p <, . s . ~ .~m r : H. s.. .i,**.? . .,,c- . -- .m.-4.. - - O-s:[.. . '. (., hlst. - bb b . r,. s ...g.

.. _ , 4 '. C.

- 4.' * [.

. u..

  • + -.^.

- , . ~. j 4.***.. v,- r '*' ~ :,.. .V.r ^s3, c', . "', ...~ . - ~ t.3

-.

  • .*a f

, 5:.* .* ....

.s w '.

@ "J'A. r.. e.s.

' - , u.: \\**. . f[ 6a,.**P e 4."b. ~w ...x.... ,.

., e .,. , 9*.'

4- ,.. 7-M ' s,. * *' - *. a.'. v . ' * *.

  • '*w'.".e,#"

era = kl h l h" 0 k'C &-tA M r.~ .

  • *..

- .v.

- .W ., q . i J . N

...$ %. k. 2,'E k. '. *:.~ ~ %. ? l'.Y'.~ ..

  • .,. '

'C . . ~. .

m

' , ,, ,,. ' % ; J *'v.

'..+.K ? -m s., n.%e. U...% . .,. w,x.

..,.... -.c....,... ., ,,.3.- % +w ,.., - , % 4.

m.- a.+,m.,.,.-.- " gf

  • .,. *

.9.,., _ . e.

,,

,, [.* .'[. -s..

  • '.

, g _ n,.,9... ,. . O,.,.,. a ..j-s.

y - t,-

.,- -g q g g.,..,, y, , -. w'- - , 7 -

.- ',. - -S:4m.

,;y.3,y g.

.,% g w.,p.a . -.4 4. <... u .i n w e.

...,; p. g,,. - ' '- d' , h.h l@'h7CF - a hflllr". ...m.... ;. ..( C' Ddh.

.. .

. + . n -.. ~ .,.,. ',..

  • I J

g.. W".00 f . N.f . n 3.,.gT * * ' *" ~' . M Ts* / 1,,sc @ y. q) % b 1. ' d' 'A.

'*' ) .. , .c.. ' ' ',.

^* . ,, ,.,.4.% - .e _ _ ;w ;. ? .. w, _.

.s a,. . .. - - ., ~~ .r.,.c. & 4 %.a..- .

. 9 u.,y. s.

.. , .,. -.y .. .. -(. - ' .ll: '8.##6 i .O I.

, d db

.f,/ , , ..y w

n.,. - A % ' s w 'm,. n..,., . ~. . . .,- -

  • - *....

'es.: * < *,. ... - . V . . ,,.w - . . . . .. E , . , , 1 g .. .,.. . ' C,N*. <*T 9 { &,m,,, k W .-, n.m"' e.' g O.OCU'* $, 64 L.T 4 L ... [ s?.. ; '.. _. ~ .... s...n m M*L. , .., ,. n o.

,.

s... .m ..,_.

, C . k.

.

' .. L... _f.- -' M[ c~. *.. ..J, " . . - - $ , "... &i 'x '.. .,. [: ?:W .. - %.. s. ' "-

- , o. d*n K.s!.' W...- ... _. O. ' ".! ' ' '; Q .s .... . f.D.N.Rd.JUrM.'.'7mNM NDtI k".'t[=h476.f*'

  1. 7 D.*F

'Nd hC)U pW b.. &#7,,7 -.' d K * N,,Q7h.ld5 - '

v. s
A y O t. y q

.. < ' . .

, ',.,or.....Q..'P.14... Gibbs B Hill. Inc.

rua, c.ai.WA&.-JM C 3,2 6,,,.... gK. o,.p, . 8.f.

... t'e~un o.soms. cas==s

. czi e,....... . N*.w Yomst asu> u..?.&. W... ew m,,,<..,... . s, >,.....T.Y E.-55.. kh.D.%.. Eh e.b.... 6L. 4.'.S.C' n.. o...n.... u....................... .. i - $L Ofb.

0&!I.

5Aa GA A, f A G.A. j ' CPAd - e t '- c," , L D A-D C.

D.L.

w T. of c-oos.oaa..Jinsk fbmPe '7 t, bso Ibe.

'. go ' ' w, c.1, s s o /d, e e, , o>o it C.S.

c.

o.I h "/d'. o.od. - yaarse , Psp a a g et a c- = o.oso a D. l'I. 6 y ' t c.

c5v . o. 1 "/o'. ' d,o.EiVo' " * #% ' . / 26hcfooetS.

'

% o~ L ,33 4.w

  • n i

.'

2. i.

Q.. D2 s,. I'26, D. 6v 5 5 0.%7 x 9 g '7 3R t.. l.b 3 Rg.T.C " % bc " e--(, e .. v. I J Lp.,,O.tx11.$ m f.S * * ey G lMW I ' E '^.w ? 't.

( Sa c. p (,.Q.G>)g I.7 (l.%), lO* O'

. Ecc 3 3f 140 rw r.

't.

('_ Ma a o.'Ls Q1.% es.ts a c.17,&.5x t.f u lo foc f) s*"{ * *l* a 84J.,. C.t(l'l 6)t.',. 3,I /e eo 3(,.6'7)./-17(6.I)g. '7t.&#'#, , /*[g ~ r s.

. Estar.

' Me v2 4, it coo 'z., 3 p. o.,os, , , 6st i s s O c.. s p. kSs 0.0039 x l'l x f 0.5 s O.49 Ott 4 (o Q Ic f 5 b. (0.5%

. O . . g .

__ _ ___ __ _ - _ _ _ _ _ _ _ _ _ - _ _ _ _ - _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - __ . .' ' ' '. ra C.e % Ab.-M.'f.

o. :.. k.%.1 %... Gibbs 8 Hill. Inc.

' 3l2C,,,,,,,,g,,,,,get

co, c,....P,(.,,,,,,, twinuas. oisic~m. w~ saws , f New Yonn C & H Job No.

.h.... . Chk'd/Apped. py.. ... Subjef t T.. O..s..i..A.o..x... 6..L. S..c.

.. S. c..h. o...... G.. t.. 6. ' 0..I..G. "....... f4e t. Dw g./ Spec. N o..................... .. . .

W i I \\

<w. u.a.

. ? n. u r u. s.

O Caece po? nier,L.

, /Va c - 'O s. % /C: <

0. g, 0.b9s Itu la b S . D' . t . um m I

. l u- . fet. W.

, > '. . [*, .. *. , $ e . f % . - __..-. - .. _ _ __ ,, ~~ . _ _. _. _ _ _

- - -. _ _. . _ _ _ - . - - ._ . , - - . , .- , , nu.. c.a.17 Aa..f.G.'.G o........&.. M.T.4.. Gibba 8 Hi!f. Inc.

3b7 ...W.. o,.@ 4 - . C...,....h.P....... =~uas on==5 c==cmas New Yonst .$. N.... Chk'd/Apped. By.Y.

.I.

C & H J.h No.. . ...... I VE h. M.x.. h.1: P.0:...G.A.S..... 6.L.. .+.'.o.'.c.~... n.. o...es, . u....................... e - . V .- Slab , bl4 hh _ VSA N Q. h.

$ / sfna,<y. o** , ' L04A9.

%. -7 I o w, erS *le' /uu.,d -lc)y -fhnY e 4 ?' ..A:h / ,. 2.'- o~ c.ac.

ci.. c. s 'la'. ' ,. . / O. OY lf %_- ft NI$$l Ce flfsetG (7 6t coa ~b.

O. 0 & Je c. 616 s LL O. 4 * /.cs'. ,c W. W~/c '

<

  1. ,

bl. Ac.T I O rJ f.

[

  1. -

- a; 6 * ',, ' % sL a,. t l..- ,,. t, e / / ,, - g.Sb.s5 7tG [Li_. . R R.

S R.u 9 $66x26 o . 7.- y s; )I-R :. h

.- ,,. - . . . , 1 p = o 1 < 9f, o.9 ' tu I , .u a < , s *S @7)f *5 (f S) * & $ somas Mp. sO.$b s t.% i " /. 5 5 21... e ,,o N Wig a Q' ) . t. (c .* .,,, -? L.., 7, .o %, 6 (9. )# 4 6 5), @ "'/, . R enaF.

V _.- < ce C8' ([p *

  1. .000 ( o,gg{

LI ,,, g bdt t e., x ( '41, )' . ec.,p.

a v' r 4,e o se c.,.

c. a. - ? [ N b [ 81 - 'l (b - %= ew p-rs: < t7 o.t.

. O.&5wI'l.<'t.1, / / - . .. . - - .

_... _.... _... _... _ . Y u.'... 'f:.4' 1.'...... Gibbe B Hill. Inc.

ru..c.d..$AA.-fp!.G.

' 7. ;2 3,,,,,,,,, y,',,. ,4 . ' bu.c,...@..6........ tamauas.ossicat 5. con 5=cmas NEW YORM G & H 3.b N.. ........ Chk'd/Apped. By.. ... ' sa,.....T..u..s..t..... p..>.x... B.L..v..G.... 8..,4... G.. c..t.. S. t.o... gi. '. n.. o...f ... u...S. o.1.. s. I............ .. .. .. . ..

s N v / - - - ,.. s~1 'vt us. saa.

ba.n s n.co.

t

S P4,4. 4C.',o'. G]aA

{T f L .l:

L.cAbg.

- I N '~ ' 'O.L.

CLAb C,%16ylc 6.75 N.

/, h a a 90 rf.

s C. t 6 n '?. x '7 : 0. G o

t+. s s, . L.L ' G..o 'Va o.tl. x IO c 12CACToorJ5.

- 29.t, 4.56 x G 66 6 * <2 G d L.L s Gx (S c kg 3 ( N h tl.7 b C)', 1 84 ' s 14046 6 r1.g,Ot.'%)(%.) c 't.9 Li '

' io

,

2. (T C-)g l's6 rd t. L ' , , IO TAa S C4 9%) t I 7 C.I'b5) = II 11." s.

- A 6tr4 f.

A4 Urbstooo s.Qbo f o,co 6L+, bel t 7 H w Q1 +.S)'t.

t ,. .L5 As.c. cog % w.w s,s.r " use c,.-, r s; S. (c.o op e CHr. c se fcut SHGott. 163 - - h Vu e T 4. '3, 4 9 6> % J,e _ l. % t< 48.e.( c ,1 . G)a : 'bb = ( G 9 7 l'z? O& Sx 4'fx4tr.s ' (. Y c s ISS~ %t.16b-15'5: I b' l <> si.x, 4% s w %.s s;.f;- > s Ib ni D Q. tA' o Jsc r c.

-


.--_.-m.-

_ _ _.. _ _.. _ _ _

- _ _ _.. _... _.............. _ . _ _ _ _ _... - _.... _ _ ._ ]';p...'.,7..%7......

e r b b e a H itt. trs c. ra...e.s.na..im G.

.. en,tr....k..f....... b[+ ENW EKS. DESiC.NERS. CO**STRUCTORS M s>>wt N s.

Os New Yosest . BIN., C & H J.b N.. ....... Chk'd/ App'd. By. ...I.9.k I.T. 4.9h... 6. L.9.6... d(*.7.....@.'.'.b.9.~.. .. o.../s,... N... b.y. !.l..........

T ' s 6,. ... bd.

ItNVG. k buGl. 354A 2' fe, D A.

l ' . spa e4 < sW c". v . ' . / D496.

'P. L. S t. 4 *b. o.L$5x T b. * o.hG> *b / - o. cef,.. ' beq vo. ifs I.$x b wr.4 L c.tS,Isac,."S , 9. 4 t-3., , 'b.71 '- l .

' ' L.L.

~0.1 *d . o.'S "4 RSRC.'TooaC.

? < u.

A3L.

, 3.7 2 >< *). 1. b e, ,z-0.6x 18 3.h"' - .L L e . 't $st . 3 (,'?}) g 1.'f l'ile b), 90. $, - y . dCMLMT.

u y d, '33,(_I6) 9 'h

h.L c c.

9" c.G 66)a. c. n % , A.u., e'<

J s , 'Aa e 3 (,,.9 5) g g.7 G r. 5), 80 0'"- - f.GIdf.

./ i ~ SooxitJoe ieo. [ c o.cos o M7v -- = _ () - b cl 1 & x ea:s)z- / - / i d s v % i e l = Q.l l )1 6 $ 4 8' f* f $ ce < ('2.11 {.' s k 5' t. o.oO%lo y _ b y % 1..$ C IIG C tl.

For?. CHsp2.. ... h, 9 0.Q '&a $17.x 9'z 6 I.'7< c.'Sx 32 5 e 5f ' r 7. s u z. - , ll] ( * W'J $' O ll.

&A 1

' ' O.b5 x tb s %7;S f.

/ / / . O fr r4d i 6" ec.

' v . i - - . , - -

- . '.,. :7. 9:2.'!.... Gibbo S HisI. Irro.

ra,,,,c.. 9 6 6 = J.a?.c ' ' - 3/3/ s u.. g oi. @ - . . emc,....&.6...... 5~c'~tmS o555~55 co~5=c=5 , . u.. v.- ' ci,6..u,,a..,.T. 4/.% aan2.u...T.3.7.?.f...

' .....T..U.S..l..A..u.s..... 6..'.D..G.

.....S.e...&..E..L.6.10...C............s...u.....S...o..~10........... . . . . . . - I GW6CK fo R CHGAR %tc 36L;,3 (b't5)x %.G,_g.q(3..Q,% s ,q,bb?* ,z it.

  • 4)a,

tab , 162 ps: 7 '2.o G 6 t: (s ktw c,[.dbr(') f 0. b G = S o %.6 x l:C.15hbb-: _o. 4 -, 0. co 69 C 00% pygth. . C.16s & Oe . . e o e s, Av h - 0. % Co. coa ca.C ' ' ([va %c) b lasines)<bo ' cA s.

Av ut [ c.H % 6 , e,. c. 0IVAk$ O. l 6 4 6'11.,, . U S 6.

a 4 c.$ G, C# s., S n E.

c i . .

  • .g

[

., d- . = $ . $

. . . - o w-w - ..-, w e- -,- - - - ++ m -, - -, - - - - - - - + >, - + - - , - - - - - - - - -,- ---


%

--

' I '* ' ..b.'....T.T..W...... Gibbs 8 Hill. Inc.

nu., C.<>.Sf6. lP!.C N.20 e..,, J u p f. oi S M c;i........%.P....... ' E a ua5o'5 - 5== = =5 ' Nauf Yosest y,~,, t Chk'd/A pped. By......... G & H Job No.

.... sai.. IW SJ..d.Q.<... h.h9.G.... k d. 6. h.L.. 4'.N.9."... n.i. o...es,... n.... f.. F.7.8.l........... ... ' / / - s s 64E Gorka Mr,.t. s A-4 A < p g. $. l ' . S?A L 2.c)' o* . LOADS.

'* 3L.

CL46 c.'b15x 1o.5 a 4 - IJel.C. L D.,0.e.5 < t x I &. G. 4 "- htA. c. l6< Q.5x 7 = M6 **

. - ' 7 ' 5 no, kl s b 4 x l 0.5 s. 5 ' L.L.

', - o. 4 >, i d. 6 , t.1 /, sm.s 4.15 ' gf 2OC'ft o a s.

  • Jr..z.i)

J P t c. l. - o.*.' .. ,L s%c- )? , , , '+' Stur,,.Q9 s '57x 13 kn5x 19

,

p },.~r./. *- , bl/4 y. 9 9 4 3c.3A.cloc.c.'- " f I o g%, q 9, tj,,tg gs. < < + ~ "' .,f ,.i a ' M i & W f "'- I &> W-c,- , ' L RW, 3 o.-3 '" L.Rsk,so.5

i S4 HA. S (.9't.H).r. l.7 Cic.6) < S36 ff G?

Ra ss, s q...u), s., (.so.s). 35q . Hor 4LM T.

r4 t st+,4x<G,IM6eI~o907'" (.- t

,. t Q(<"( 9)L, /7 t I '" - / r4 L t , b ' d , '6 (.9o t) + t.7 (It.t) < S obt l.

E &tdf.

, , Gt I f C.olS' [d 'L, _ 30 2 t x e t ce o ba 3 e x ( %.5)'L , bS. C.c I b v 3 c < b Lo 6 11. LI s . _ LMd It, e il 7 4 f.,, (i571'- . ..- -... ...

.. . e - ..~ ' ' '.. nu ea.StM.-ta:C U.'.t.?:.86 7.';t... Gibbe S Hill. Inc.

'j" ..

m w M.on.$.3 . c.i..,...k t.@.. 7... '

    • ca "a5 ou a 5 c = = oa5

,.. - c-u ..'...g: .. a, . 7.1.M b.. ' . .. TD.Sh N.5,.. S J.G,... X L A 6... M :..@.'.e.':fE.......<... w................'.... ' ai .. - . / .,.. $L. Pb I'7.

Cic w bLT SA.- Ge4-G*, G A-t+h. .. ~ . . ;.. .........SPM - A '-/. < . feoLUd :-lo Il'LIbnA ~ . / -* ' . .'~ .. .... .L Oh-D S.

': 3L.

o. rot.6 Wo'. . , . . ' o.fl. la'.. L.L - * ' .

..

.... .. . ~ ~ SNe4L ^ - . ' V p u,. o. 1'L 5,;I 4 I. f.i- ~') ~C e %.t e 0. G , I.k '- , , Vq S (t. 6)# 17 (,I.9),, 7. '? *. , eno,sar r4L o. 4.'t 6 (t4) , 4.t.f '*,; ' . .- , 8O dLg, 5 d (19) 3. 3 9 * io r4st. s. & Ot.4).y I.1(S 9) =. 8 9.b 26Mcae.snu T.

.

.. d <<- i.s. no.v' b.i<. l r4d 19.8.=st ooo Ibo [s.r.00 36 . (~ ^ , , ~ v b d 't.

ox. n (.so.5)1 As s o.co%n s'Ls no.S s p.44 D'{,, c)sG a s G. $ d' L' b (c.H1* E..a.

C.n oc.

f o R.

sp sn.a.. . .. ' h ' E . . O.C 6atl't*IO.6 - 'b g . . - . I.

. - -.. ..

.

.. _ _., _. _. _. _ __.. _..._. _ .__.. ......-... _.... _... -........ _. . .

-

,

..:..

.- , nu em KM. del.G o ..)Rs.h49.4.... . Gibbe B Hill. Inc.

l35 ...E!P'.ei. @ g n . - e.i.

... A.f,. 7.... '

  • ~ca'"as ot5=as co~5'auc'oa5

. = . . u n, 5.5. M.e... - - u, . ........ . , , ' 7.U.fJ..M.5.. th !.?.G....VM.4.... e1.. A ! R '- 9.~... n.. o...n ...................... . ~ ~ ~..'.... . SLas., o(G.

W Sa g G;. a / ._.

^ .f s t 4 '.-o'. /. .. _ . . ... . _ _.. _ _ _.. - __.

. .. . . ._.

.. ~' 't.' d t'a,eu.cm * y,a, e,i. / ketjlStj h 18"-fhiclE. a . , C k^ b t^ h.,. o. 3-tG '%' ./ - . , ~ %. o.'2.</d.

- . . Chc4R - .vbc c.s76, # 4,, 4. c."/ , s ~ %.a. : o. 9. x t 4 I.4"' L.

- Yq s b ('t G-).7-t.7 (l 4) = l c.%" l .r... . . M oMGaT.

' WlDus0.'b75(IH)a =74~ . . Io MLt s. O:.$r. (Ih) & *.) ' ~ ' e IO tdq, S (,7 4) y I.7 ($ $) s 9. b.b'" d

" ' 2e,aeoec.amea.r.

- . d,<.'t a 1 c' be 1%" / (~<- WI'l , Q b.b r I'l o00 ,. G 9 6 f.*O.ooII(,ocoss, ,/ .. ' b cl'L I'l x (JL) ?- , / / < - , f Q, h [' t, b ta Q, k $ * D.00%bnCQu'2fl,,5 o.$]lY 0$$,

{~p ' " , . c a u,e e.a. m a.

' qja I o !L , 46 js.

< ,< 7 0. w,.. 0.66ml'Lm#Lt

. v \\ . . e w -.ee- .......... ....

( ? s' ; * a : , , .

,
"'4,

'~ 'ou. 'R.T T*f:..... . Gibbe B Hill. Inc.

rm cs SA&t2.4 194, M. 84'g. . ca.,... 6 f,, naciaca s.msic~tas.co~sucmas " , ,,, , .- ' o. n 2..%tM.. ' o, uw.... : - .. 7,/ m.,..T.O.sh.4.. f.. Av.1 fri. KM.?'...F.h.?!R':.4."....... n.c o.asd. =~...... '.. . - ,, .. . . .. . S'- n o ci-es ... ber.

n.14 < aoeu of sA.

.... -.. -... . ~ ~ $PkJ* ts'-o' ~....:. .:. ~ ' .' r

~ .. .- ... . g7s- .

- L.cn s.

C. S "I '

L C

LD g.

c - b i c-ST 9hGE, 'I"ANK f: t7, 400 'Ibt? Sf 6 el'i 265soJ O ' i M.u,_f(1)bs6.sc'.- 't wa., 't14ao. 7 7 rie < , V 52.S / e.)

^ ' ' ' LL.. o.!l. */c'. ,W, o."<t -l, ' ') '. [h s - ' ' - = ' s*'d b6

swuz. . - VDLe 0.&5 *S/gp o.7tL7)q' s 't.tt..s t , , s., - , . ~ v'c c n 'J.fo S x s : '2. "' - - , 5 (L.s) + 6 (A 5) + s.1 ('t.), 4. b. S " Va t n104s'T . / ,- / (Y} q,.9, 0. 6 5 x I & 6, o.7t7 n '7 Go 4 x i5 - Sx so) 5 %I% 5 Io izie is%7 .-. .g l.*7 x o.7 * G = '6_ '3 = 1 'h,,, T.x 3 - l 4. x l.'b b"' - S t 9 (, + 3 c.. S &,,I. t 3,, s.

, . = 70. bs'**j Stulf*. O - (uT. d# A ic" . /Ys/ _ 7 0.f.r s'Z. coo # , 3G.C, f4.,,eot , ba t-s.1 = C.+)- ' / 45 s o.coes = sta49. l'78t #/, ()(6 I I 6. i d ' f t', 6 sw

' - . CHGc.x 10,2 S Hrafur.,d - / % < >. s c.3.s p: <. is7 o.u.

. - 0.65 x stw 94 - -... _ _.... _. -... _ _. _

... ....... .... . .. -... -. ..... .. .. . . ... -, . . --. . . - - 7..v ' ruu, em E/.M.-10!.C.

. ._ ' " ' ' ' a ..'.) R. 9s.T H.... Gibbs B Hill. Irsc.

j

. . '. - e .,....@.2..g.... ',. Sac'a55 5 o55'5a5' 5 "*5=*5 }/ 3f u W. oi.iS.. e. ~..... b. x.'.. EGVICNGCl N ***C /Vl?nch] .. ~ . u....cs..f... . . $ .T.u.m.3. c..e,i.a a...a g.S... c4..a m >. e :...........,,,..................... .- - lg ~.'. .... .. h Stab.

&&f".

5 A Co A S{ PS GA., . , . < Q ?. ?. [l.S?hde Il' G' / .... .g \\l & N}$'?h f, .. . '.. - , LOAD S.

' Pi ' h- 'ye = _ 3. I-. .q.yg ., es. o.see'%- . r LO T. oF coolr4G M4.T.22-P.JrAP, 'z.t,5Go It's. ' - - . Lal e.

L'I E G o , 7et fla'. *

~ ,. 5xio ay,r ' '# #I '*I *- L.L o. t ' >'y ) wls o.3- , I

RsWood s.

.. L B-G* 96f I'C Rt.

RA.

. 9gs o.16 M,of ' . -

aere: se ac.c sePC es , 6 gg.xst.G s 0.1l. b.517 15 ' Her & m o+ g cup . . os +r eres.L.o>cr< . ' AL. s s. p ** den. s 1.t* ' t.o+3,ps cio 2 r n,.,e

as (19 *asresD CP G y ,. L 44.x :.5 c hG< l '::> Cor)Slt'c)C!Ei L. R s.,,,o g E.

L. RA., 0. 51.g., L.c a d G o n dt W C f ' . Y ?=6(Ih).y$(9t)+.l.7(o.ot)*IS-4!G'4-L!Oi frift: Ef Old '-

- . = j.4to +).7L +1 * 9 Fc'

M or16.a f.

' . . <Z.

= 2*910~ / /'74 d9, og(,gg.5)t .e p.1I.h5,eb.5 g b.5 w t

  • 2 ' 9 1 * /' 6 # ' 6 Y 7 '

' T.

bef.

Yo UO"#- - S,,atfgto.t9a(39<t.

s '8 3 Raf i =. A s. D T"% < T (l * b't.# sn.5) i oad } rein GI O3I'0 L ? . '7

  • p

'a ()pg s t ac'J /t7f.+M , o, y-iue'b(.3.27)t Sho.89)4.f.7 Gis) 5 /e

7f

'

kerelF.

g, Wb = 83 l'75 =I'Sll , . $/ lW

  • P pf a lf x fl') '

d.t, he-b u n1ooo , s.;t.e - f, e.co$st - ye _ Wc t <t < q't.,g / as,s. oasts...s.o.rsby' xecoe efd' r O.

G.sc, - ' 0 6.92 )(l3. w 16 . os **..

  • E'i~W.

.*

.. . .

... _ _ _. _. _ . .,... _.....,..... _.._ . ...... _.... - --. . . g . - . ... -....,, . . .. . rm c KSA:!acC.

hl9 G. n..W. o,. 8. . o ..LP. 9..T.%..... Gibbe S Hill. Inc.

- .. c.,..,.... h. f..

womuns.usmes w~s"uam . c s u J.= u.."d. h.1h. k.

.P'....- v- . cw an,.w..v....o, ' .. ... .. , Eubs.et. T.U..S. ) ~........f.L) A.....%..k. D..G....S..L.A. b.... G..L.. C..I.$...G..' R.I. Dwg.

. . . W6'4.

26 MF.

, / Ott .eS e. Y' T 4 s.

- . m . _ e CDfu-c n<. f*o P, S99ceeR.. ' Yq. 16. Lf.,,. % 0 9% sf.:,f, FL. 9 ' ~ ' ' sq a. 86 netaso.6, Ill (S: C sT') 0K.

IT*4 0/4a / . . d . . g W h h.e ga _ gp . . . . . -. . b . . a. . . . D

. . .. an e .*. [ . . . . . - - - _ _.. -.. -.. .,,... _,. - _. - -, -- -

y.. ' ' vm.. c. %46.-Jot G ' a'.. :.t.G. i 9,1.'l.... Gibbe S Hill. Inc.

' ' ,j37 o,,,. 4sr'o,. g c.,c,....bA....... 5"'"5 o"*"5 co?S'mcr as ' ' ' - Naw Yones

  • ,,,,,,

..K;.. a s a s, n....'::...... . e,,,. w.,,. s.,,,,."C.QF.t.-R!.'H... b k?.9......k.' 1..G..bk.D.R'fdn.c.o-. ism.n~................... ' " 84.

4.'t 4 tro, BT &Gr. 4A 6A c' # A

% StM, tz.t '. c .c t s L.OADs.

' it. s-4. ': I . N . . )L.

St_gb.

o.s*75,hgq6, % o \\ , N 6ef.

, o.16 Tv t, o. Go

  • e e

- - N M 't e ff Lb s 0.'1 I n 1 0 s '7 l '* 4.1i U' ' A S.' n11 o. '7 x M s M 'l>.t.y 4,,.r L.l.. s de aif Au 2.3,j,44, ti.T l f, g p , - , e , . < .- - e ~ _ _ s-o l. s o-o, y: p no.a .. 2essas.

,, m., c.

S~uL, Lh RL n gif, p=7.I x g.$. Q, $, l t . , ~ 2.2 u.s e , RLt.. N= i o.5 s %I ~ eso.K b o 3 k.8) # t.7 %'f = T.5k'h a. c.

N.1 MoMEM.

r%..,$(1't)7.Ix% 's.5 i 1't-sx13 5). Io.S'_@='L4-t t# IQ n 239 % S fO _ . = %5 .t GS S7 = W*7 N '* 't set.s H)s.t k% <11< 'o G (%x114 -9.n so.5 (. L, a 4. 4 1.'t ' = hko. 89. 9 ,f 9 f,9 < < . % *S Nc7)+s.'7( &_ .t 6 * m.y es.> - l114. *l

  • *O OD

- f(co4f.

itr%t.a uAcos 1'wz.

f, o.co 55 er e., u t.

1.'s C 44 5) 2.

s oc.9 kse 6:oaQG>.1'tx4t.s = h9 0" ose6 #9 R 6 & * l ., .x n C. ? E -we rt p (c r ~. - a . . . . . .;. .. - s -... - . .., _,,.... -.

. ' o.'... l.4. t 9.'1.4..... Gibba S Hill. Inc.

nL., c.a. 5915.<fG.'.C . . ' 3 s e,,,,,,.p,,,, g, co......S..P......... ' = = "5= = "~ ~ 'es ' Naw Yona ge e w ..,(6 K.... a a n s.. n 7.M.5 n. : $ ......T.Q.s 1. e.V.4 :..Si P.G..... &. ~.f.. S. G'...@. '.9.': Id..... o..ss ..~.................... . C #Ec4 704. fif e44. ge: 1so aht

Va s QQb S u k'R4w44 '5 l.9w%'n 't4 5 i& . ,.z.

.s <t.%.6 (S k W G pc! ) (16, M Ihc. fs; <- . 's 0.b5=t.9=44.s 19et ' L X (c 4if G.0 2 80" o.

4va owt.

c r- . d . .+e,. me o W*an% b '%e a 5W f . . e s% bN .

. . e (M

, r s .. s L' . . . --m...

.- - - - - - - _ _ _ - -.. _. _ - - .... ..M - -- '. / .. ,. . nu,,,ea.S$.6.9l.C.

c......\\.n.t.% ?.'t.... Gibbe B Hill. inc.

';M s...W..g.. I - c.i......hl'........

  • * * a5 o*5 e ta5 a a5" = a5

' , v , C & H J.h M .. h... Cht d/Apped. Dy. ...

....T9.qt.-4H.=....B.4.D.?..... 4t:1.....G. 6.L...4:!?.4A.~......o..<s,.M..................... - . bd. b, 60:45 kr. 34. 4A .g 4 'iA. T N x . :- S/&4 a Q co'- d'. \\. 11oo a,151 *la' .

. 5 x 15., 5 - Lo405 H il D. L. n.7 ' SL#6., p.s15 a eQ a Wo \\ Hn.s.s..t % o.t&#1< Ib : 5.f' -e ' bd. s o. 6= 0..G. 4 : c G' 4'.75 ". 24: 64.sy,r 'Gq' 61 us y .. t.. L.

.r 2.3 T.o 6 o.t x AG e W'/,

,. o.tSt 4 G, I.t#' a . c::. 4 4 a.m ' / 14)! s 0. t x Q s i. t /. M5 q,

  1. s.g,$#"/,

N Q f..N ' I3 (.. T I.2 ) ) a . , - s , R.L p ' 14 OP LLdo, 6.o J. g - , 2g Acfsor.IS.

.. ( * , G,2 4.

k N 5 e 2Q'.;2 y C.'iZ,s b x 4 ' Ng., x fl.do.6e Nx IQ 4 % NLe 9 U.7 3Rp, a gg,y < it /p tc..G,kiatb.f..,.I=#9.G17.'t.G . z - 7f Y21.3 l* Y kg a %.(.to% &)f $ 1)t3 yi-

I c mr v.s.e u., C~-.- 1404 g oq T.

G [tGr 5)y k>< ITx D%5)<. c ce p W 8x %'5<4. Cob. N 'l %' \\ W13n, I cor.c) "- (scsJL 8oo R 8o Ms t, h(.US) p Is '94 x G 5 ISE ' ~ -x = p - st Io Ioo I z.<1 s

' e//w a &(~)%')l t I 7( !&q1) e IN $ 6' ' sos.'i (29.3 zo s 3.9 'E Eti4F.

son.1 aos2.

r4 C, it H R, & x I 1. c o o =%8 [=oM.

/ {,s bds 30^(,W.9)7-

E W/C v , , , AS, e.;- 77 ^ S o x W. 6 : % DCG

"'I f5'.b bd' , o. c oBt-l o.*) y oz _.

,,,. - - - -,, -, - - -. - -- --

. D,,.. J.E. !!. 7.4..... Gibbs B Hill. inc.

I rm c.S4hrtw.c: . . . , " $' $' Sh'** H 2.

. Cl.I

N;w Yonn ]; C:IrCr...

...*.... ci...,,..r. M... c a n 2.. N.. t.'.9.,?.t. , 'W Y Subt.et.},Q 5..l.*. l L. W.. &.L ).G.. b.M. 4.,Q. E.. L... h.t C.......... Fie l. Deg./5,.c. N...................... . .. . ./ - C K U.

FeR SHCnR.. (W"r w& t.3 29 0.5 766,8 6l5Z (~ Vs4. %Lt 3 (*Nrf),, 4M s.7 (N)x 44 C. tgs - It.

t rL ., 290 t t'Dg r., W.9 4% f t.. / 4.o C 6 [ fog (Sbc4V C [**k ) )

' S: S .6 ' ' ' o Oh5nSM'4 6 2 TG f oreq *o d's tas* /q e MK s II. j . ( fsom S6 d MOO } L-20 Y fPOV! tb.

fs - 1 - = -=s c., m - . ' S, 0 4"Ce wo %'7 ' . L%5*1to)so c. u s-og-S p.t: 'a, & p~ 'n- -

. ;5, -.;

TE e 't t.) G, C." *c.

44 r.c out, < .. ... .. L

e \\ g t . . . . . $ e '6 ,

. es

e y [O. ... 1. . (.. L.a . .. ..; .. . . ..

. . e

. . _. g.,

' c~. 7.

l.'?.... Gibbe'S Hill. Inc.

nu., c.e.N Ok*!.*!.?... <. . , I s.... d.M g - 3/4 - ..... - OM .. 2,,j.

ianas. oisio~i:.s.coasruuctoas p.

i "** va .- . -

a a n m u n. 3. 2. 3. /.... ..,. cwa , ......... 2!!d.V. K !...b.I.d.'..@. I. S.h......................... o

-/n 4.b n ' ' ea s-c,-s s - a,s m 5/g' dopy 2Ao f 2>dE f &a/k.m ? . a n as~ 3-s r~c --~ <a . b l . / $ f bdf f3; gQ JAevr /ssn .J1eies && c-95tSto 4}E dezg.

/. y v ee d . odG c 6 76% g4E j3j p " - 7%- 2% sed CAa m a A n c, 95232 ' d l-1 '

xy & OA E'

/,5 b.A.E.

* 3) 2. y w ew.

n s.rses2 vl a ~>w ' JJ O. 4 E.

A 5a A* /.o.of ., y .

D. 6. E,

2.

- - . d.d LJn u s A w 232s. Ms-it py 3-q hehi9.4e

o. s. m... -. _ z. 5 %...... e n - u dnuw

y Nr Y-S.' Vcr/ ' cs e - b ac Acd hc - - +. . I .

. .'

. - . -

.. . ,,

\\ ,#.. ,,. -

- as.....&R9.-15.

\\\\'9 elbbe e Hist,Inc.

8N .u se.. 15 M.

rua.ca.M".'!.*!.? - e.

....d'L..... f,j)*R ,. eaus u f.41.54... ' <~mauas. oism~<as. =~staumas , e. a .~......... ,,, , ,...TYhl..<T&.. h/dr.ae... warpo.. e. A.4. :9...... a...,.. . u..................... . i2' = = _ - e ' N 2- + + t D d 4 f q. 4Y " gp.w ws,a > ~

N r) e.cfi A - a f r/2 4 \\ll

42 _Y/ /$" e' . /S J t' Ac-ey 29 wA-O.s.'x gks gan.

s:e

U - s:db s //ss. 9~7a . ' awie p.sdt hll.

6/- A4.'b, /.N-C_f__. i 2 Sh a S/ffb ) fjpp /...:epe xi c! ' J ,. . W " e

E . 7.D ^ <0(b." T u b) % S h 5lD , nerfo'nu %,,/p = y n(4r' - ,.cos , U. sus = 'Ab s /. Pfg wane k ./so s.7s..gg ' s _ ^ f.LTi + 4464 29ib, dg/ ' - 2y 9.i>.,1 + .ep/.4/ -e.

- Bie '- 9 'O C' ( gg gr' h s R - vis . n.q.,4 " - ,,.,. asas u,.p.

mr/yi eis s *

n hldfW f"b% dal w h eacA & l' e w / . ._

.. ... . . .

h < * .,.' . . . nu., es?.A.4.. !?!.?.. . '.h,M..l.S.. Gibbe B Hill. inc.

3/4J m,... E,.g.04 ' 5~m~uas. oum~ias.co~staucrea .... ./.. I.. ..... a s n s.. 7A2."#k... New Yoast . '.... .r. 0.. 51.... A.o.'.c...F).l.d. 8 3. 8.. ..8.10.'....r, ... w..,... . ... ..... n.s.o-,.n m.n ..................... ..... O .. . _ l b . k$' 4. l b , I.W ' ' t ! ~ = ( 4.Ia a u, 0 2.2st , 77.<.' * ) h= w k' . iO /o . 5 S*

.. / N o

/tcoo-m-- _.

, a g w /No \\ dl e d' ', . os.s i na > so. 7s ::- i. s9 m' 9 Ace . t . a ' % /f, a' Q dS.)(a)(/o. 7S) /?c, %s 2t f = ' 4- (%-n) Ls y*4 As.

s, t. 9" 6 . ' . . M . . f

a

. ~a.-e ...% ,, s..__ --... M.M.~/0(.9.. '

;..,~.b..%<n.~T5 erbbe 8 HisI. Inc.

rm., c .

'

... g 5...... ~ ~u n qs;~;;.;;~ m - = s/44 _,,... E. O s.4 - . . , .. a. a a u s. f J. 0 A... , 2 ?.'.u d...i k c c e.... & a p a. w x d p t................................ ... ~ . h

. g . O ag /W y y - , n h a . f'?:6 " d e.a ( //,p,, - /2' By%7'l' 3. J.$ ri:e W' Ugy ~ (/8"+ c).is s.os} 2 921. /.o

Y' w= .3. / s x o. f. is / 4 '=- M L 32.5

, so f= Ao /2 P4. 75J' . 28, f = s zo ~ u . /2000 /zaco ( : oc ~5 % ks(hks.00%=a(,11).(l(.~16 ' - - ..au s 2 af ale f d'.k m r y er/ . . . 4 /2 x 72 - h a > this = /e.se ' /2.

. . O= /2 Ble . 76. W ' . g F5(/2)(/4.75) ' . _ _ Q= 2J' [ a t'J4co o = /td M . - , . .

.

  1. w*msm

- =+wed ---.,e , ,,,, _ __

. . - = = =. _.. _ . , . . . - _ _ _ _ . ^% . . . . 3.... e s s e w n.ir,a.

giy . - ..:...&.w~.7s.

~ ~ u ~ <,.- d ~~

l c...... 7.,'.... .c,,~d.C hkws.luer.e. 4ct.54f6 -.c.

~.. .........r ...... . ~., -

.( , lc- " ., 8# $' . /

/

tr 3a #l' . c.4. '"? e/s l . t ' or - sv,s 4 /3 *~/ ' cu s.

ic . $ 42.0

  • L*,

,

  1. l*

to N vaood . j kir.0044[l'L}(S.75

  • M /.

.1 - f .s,+ t6 af h+ d

!L L' ' 4. is A n ' - g ;.g . % .is x A - I .' . , - g <85(/2)VG. 75) . . , .lf A hh , f ' 0E & N m *l'~ " 9 P "' O' "' #

c c wfa r Purop ?.r'If Cja k are3", c ) Nole: bea rns. g,x t,,'ho /c d -

on anifary.

W "h ' .

, . y,,,Qllo ) acanalysis " ! a ha' ' ' ' a dela '

. mm

    • =g

7

- - - - - --

, - -, --,------w

. _ . . ,. , . o..Hp.t..M.%... erbbe a Hist. Inc.

nu.,c.99.4.-!.*'C. ENGIN EE RS. DESIG NE R S. CONSTR UCTO RS g[g(? h t No...... og C.le97............... New Yestu Chk'd/A, ped. 97 .W= G & H J ob N o.

...... .... g...d.,...E..j. gt.o..L c i dus ...,... I-d..u. x.. ' j3 ........................ ....o..,........................... ..... .. . slah bel r-A, e-A and eA, 44 (Pawltes checEBi Design Recener) . +,.. - -. - .; _ 4 sopporfing c.c. wafer Pump - _ .. . E uipman/ loae' suppor/ad 6, /W: sish = fooyn/r2. es n q .L. aa , u , ' 1 miis/? ! i, sin i i i a n . s Ass orna DL + LL c/is /rr'bvlad.

$ $ ' s s s % A-c' o b DL ' L L = '8 7s x 2 x t 7 gys + 3 4 Q $'

'# = / 2/S YY & , , \\ / f f / / if / { f / // / <' / I ///f/6' Refs c $ cA Trans/a/thn # //3 (lona'on) for dis /ribv/ad load h b> %=4 ' ca.ceQ) t/b - 2G//4 5 = i a ra s/a

. rni. oi = ' 042 rob. 'o61 'ose + i34 ,.oss p A 2'401 P R1 m.

o2e i+t+ 4o2.

0h n ' /3 4 Y'

4o2 . * 054 w *16 < 14 s x l' 2 is, 10 3 .. -.. ..2'402 . .. . 9nt = 'oo 4.

  • 0 9 & +'//7 p,

ot7 x 20 als s sl.'1is, a 3 K!// / + t + 3si % 8S1 - mib,

  • 0 2 e + *197 - 3 G S p,

/4x 1S v/4 sw /1/S,

  1. 20. G "l!

~ 2r/-l' 095 3'095 ~ ' r$l./_yn 057 + 'o 98 ' 244 p, ' UB G x Z G x /4' S * / 2/5' - /4* G *l' - 292a . . '. .5. L w "..i . 2 # y es _ .. . Mr, u:. g J/;j.

  • -

M I_i _ _. L-* %: ?__ _ ., Dod ' Vo Equipman/ Load t Grovi/r) - %.': - - r P = too *.l

  • 2 c ' ^b ~ to s'

A. - G' o # = io ' o . a v' ., - YL.+ a3 p '/0//4 042 w/0/i4 S os e >c $/1s+ 134 _6, Qi a1 p /77 .... . ..-... .. -.... .'S + G/2 G + ' 40 2 //p./. >/t + L24 .

' _ _ __ . - _ _ ~ _ -

.. ,. o.

..UPX.. /.t!E... erbbe a Hist. ina.

n u.. e. M.8,,/ q f,q.

e/47 .............g. e.4 <~m~uasmsm~ias wastaucwas co.................. "~ ewm,..., d4.O a 4 a s.. u.. '2:'p,23,A,,. @.. A.W.... ($1.0/s :.. R&...e !9. h.G.........................i......... '" __ i ~~;nis. ca 9 oo e e + i3x p, 134 os7e.p 2 69cz'xtoo,7 3 "/r . s 9 + 43,t 4 o1 i.e22 / e22 ' . .. _. _ .. . . -... -.. Klll 00+vto//45-o 9 6 x c/2$ +t/7p, og 2 2 * to o.,, y.a . l'27/ 'q2 + * 3 SI m)b '028 x /0//4'5+'l97v Gl2G 's & S " 3 001 y t o o., - /4 9 K/ ' p,

  • 92 +1'09s

'2 ' 0/5 'mIl ::

  • 059 x /0//d'5 t ' 098 x G/2 G ~ '241p.

'/79 x /00-lo 9 "I' - .q2 + '72 3 /*G 45 n2 9 e/- as //fe pain / Joad is aInta d,- ' No/e : No cortec/fon ts a/ Jhe odye of /he s/o.4.

mb toS+7.sc 17' G * f = 3 '.S + 7 ' 1 c la' Sl' - 25 5 "'b mif - 2o c - is - 36 6 tn,'/ -it a -it a.

Ear /4 uake Morner>/ &pufom en/. D ue./o

ors M= 2'5x 19 4 (4s+tz) = 2 so '" ' ~ /2 on shod cpan, assom e Jhrs M resi.s/cd by @+ 4) -le's/ab.

_.on.. lo g span, asso m a xld/A > ts'o M l ,/ n

  • t
  • -

- j .. i WA '- ^ M6 =. /yli n (s ei - a) n be - c %_ +;. st ' e . . 146, - g,9 y.g g.g Q _ g jet / ^ \\y- _ , , .,. , - m.= m ) o..e /VI= 35 c F G n 41 */i ~- - .. Ma,e . [, d= 18 - 34 In. = lG '75 '! F(sha'r/ Cpan) n bd2//1oooo ~ 12 x /6'7h//2 oo 0 2e .Ko= 42/'28 u /6*o p cas% ' ~fnY . __

  • A.

as s in < ta k ..,2

...-.=-.....-.=....... -- - --- . . -. ... . -.... .... - . ,. . . o....@.t../.9?.E... erbbe a Hist. Inc.

ra.. e..R4.8 -!?!.9.. S/48 a .Fw ~ main s. oism ~ia s. a~ s=== ......... oi. co.................. New YOSHL ews,,a.., c.... a..n.a.W o a n 2.. u.. 2. 3 2 3. A.... . . si., 0,.3.1 A. u.. s....B../.d. S....E./.. B..lo '.. G..................... a. i. o...es,. .. .. ... - . g.-

lE + Croch Confro/,

A ct //ctes 9. Is 2 ~;fe eit o

. ' ~

3 e s a (osact).

_ -... &

- P

a e'g I - . y..

' o.. b . ,t . '}. . p --. y.

- - p m.. cw T.

. ,.

.. .

.. _... _ _... .. .. _ - . _ _. _ _ _ _ _. _ _ _.... ~.,.. _ _ . n.... - . - . . nu., em.%0.@.~.N{ 9.. ' '

te!-X Gibbe B Hill. Inc.

.. p.

i >~uu.==~ia. =~muc= 3/g _,... g..g s.4 "- . ...... g 4 ..,u h.2 M.... - . . ..- , ... ' ~ R%?n.. Nl.. dme<m. {ee...M. M. e.?.1: ht2.A. ..................... - $ ... p.: q Zi1/0 * .darhi. ~.S-A f 6 f a m/ //.4fJ;4 \\ 8G O-ci' G * Y'S Y fh, f $)l* /a.eds t' ~ c/d*.1,Pic! W + c~ k o '~ " . .3,4 o bee m - .>. 4 s /a. 4 =. sc b < /x S - ' 6asr,. ./S 22es .W t j. g d, a e tt-4, - '

- . e < ges. 2 3 */ ' 2. t - i ~2 ' .'s,'.,,,<ixa i., " s.%.f,8gp[ a 43fi ..9pt;/// 'TS4/2f4 - 5: .e g 2.s c 2%e . - - g< , ', l

  • I l'2

/c. > e ia a" _y' s r' y g.so t y .g<y y.

. i u

  • 2 ) wU'

>0 i2f.E ~ ejah, Q dotjs

(.,hrIA(.y').=Zd2.h

i dya s.$ba s.9 5, . %,u. J,, t 9 2 = 4 '2 k fMd , d'# - so > - - 7.4) &4E" ,, g. p t' -t , ) g.i w '. 2 (3-20 2. (vo, -

.pe ' % .y< = 3,f [.37(kd(.; AI=[23.%Y.'- g .s1 - j ,.. i . b , 136 i.9 , -..ptr + p(p @ L 4 Ag,,,,g(iog.4E'5j .A.vr( 8:sg (,- urq+1c.&) - < ~92

p,ES = . , , . i bOfs3 .-c M C " Doc.

. h.

.. . ..- - . -. - - -

. . -

. _ - - - - ....,. . . . . S/60 ... M.9A4..W 6.*..&.&.TE.... eibbe a Hist. inc.

' nu.c.n o, pp.

c... d.f..... i~Tuas.otsio~< s.co~stauc'oas h1 a,, s,.. t. p.?.M.. . v.

.m ..,......... .,.. f.U.S. \\. A v.s.. S. idg..,..Cl. 8I.e. ':.9..................<,. ' . .. _.

OQ = I 9(t sh) = 4f y y M- ~ . -- kli prodwe s A.::. d as~d x 2.4 Ahm ' , c. 43 , w 'f Av" A u m n k.oh u La v+v, I oc.Jak n w% .A W m

= db" k, (sh,-?) .bg

  1. ' '

= W2.

% (. s) 3 (. s) 'z - &n3 ll 6 = .

>k Apia L',.. ' y) ~ ~. < . . 233 ,,.S toe ? '- AAX Nmk= (gRI 4 )$ + '5.ar$ + 4M = ' 'S T'# % bd - 4; vt 4 V! a~ 4c..gSf 't - 24 , Ro90 . .t ,. tjA '250 z~.oo-s-t0044 A du. A D(24)(4(..MT = %

ce cov U se ada @ A = <.+a 2 2 * N (a p y n- '

.,s Y=(ig.gli p

s.~qu-l,.z{ _, ne.eas A g ,, IJo^ ibo + 571 6-2.75

= o 19 0. ws,t[ 44_. a tg eve J4" g ( .8s(tf/4(.).

  • 4 O Au.k

. s , s. sa" ~ (g-v W - e a 4 P '1 e-c /lhyu c.vt.

' , v . . - - -. . -. -., -.. . -.. _ _.. _ - -

.. -, ' n~ e M.8-!.0!.?.. .

  • ..

L......ta..r.- esse e um:ina.

,...... df.7 g... - . $\\'r.gsgi;=~=, e/s/ ....(.. 084 ' ~=~ -- ...... e 0 6' [44./a<.dd.dmywy.Nng6.ho..o,. ~"..'."..'. '........hef... . ...ny y .............. e p ~ , l ' ' ji toc 6-i i

[ ' ~( -j-,','t-t t + t-

g ,I ca. %.m3 A.

y $ p .- +3

-

, ,y + + +-+

, IL $6'- 6 ' _ ( 'l i 8% il ' = 4fJf'.C 'L 9 c, <_ 4[E ' N.

. g from.centcfd N b G 2- ' ~' o J~ ier;6 a @_gdMiclC'eiFrien e d ' @ oh E'.._ _... u.4 - br,3- ' f.0 3 M 'O M -4D'-1,'ll& $ Fep

... @ b.B.G.

- bor.3 I o --%4 d E.1 Fgs ' +

.... / ^ .@dgg,p * 1.3D4 f.9(/D)v = 6. 3D + 03e - , O - h Oc.

D' l ('Z D)

O s - . OM m 4" a m M %N sc a. - - ,- i i,,,.

P~w a s '

\\ di NA * 15.fG.N q,,. i.9 A 1.SD *

, .M b hadj Se. o Ioc.d 4$4cd' M h I.

,, '

O @P' I '* b 3,Sb LGb sb: 43 F ^ . 46 6' ~ {. - - , . . . .- . .. . . -.. T

. - - - - - - . .. , . '.. . . . . . , , rm., ea.{548 - las ' ...d G * V W... Gibbe B Hill. Inc.

' o S/S2 ' . c.,,,, A.. =c inas.oisic~ias.co~sraucron ,,,,, ..... New Yones ...s.... 3.

s...l. e.....y...Ei.,.. s...t.o..L p.,.... ,,,. ,,,.,,.........,,,,,,,,,, ,/ q - . s......... e,,,. u s g.u....A..u..x.

c1 .. ... .. ..,,,,,,,, w . y . . . 4ir f A}e Jd' N '=c7" ' [ . g b as g) . zee. n. - 4A ' sz- - fu. m,/ ' ( d' / * 2N . /d f p ruy y,a, p.i ' - h (2 "ud meL F' Osn;b,..c#l' 8/* . Ihl h.l.454'i =. . .. _ _ . e

I s 1(dS 4.cns .n hshlS().ie.

'"~ F -! . gj . ' i! _ %as = 1A ug I. %.E,h ), 'z.9ghfg ,ll ' . O..t - ia ( C) 's.i.,(. 2). . g l'/ p,g r o = Cyl+.y b 12. 6 z,r. /K / "*b'W'h & '%.uu.e

, a-x. . w . ' (1 f h*.pd E g'. 4 Nf',, ' , N6 Quip - W MG 1 e -. 9 - =(& Qzasy ( s c G$)'f A c.4,',-) =,.,,#*g.7 ., xi ? krs.

l 'm.os 2 =.w-eseWS) [ W IM '3 ID:ooo og- ' , f, ew ,. 422 r

j .nssm n.y , , n~a . t-a <

32.

E'A'~ N-55'66 w0 - s eiogf '~

onsmnu e7 e l _ '" '

. ...J

-- - .. . - . ., . , , , rm..c.[.SA@:. . c L..19.-2D 6... Gibbs B Hill. Inc.

c.i..,... A~T Mas. oism~< as. c==c=s 3/53 o,.S.84 ' ... c,.., ... 8......tef %. Sid/'F "" ...o .t.525 A.. ... daw...ht. 9e.hQ.m...QI;.,.gg 4 .....s.. ........................ - . m .. v / /

. = c/eo r, spa n = 'E 'S % y 833 24<48 i.ir % Ws ' .c e4 g.,a c.i ' (% . f!= t..'s 1 5 + g v 2 4. /'u c s 4d5/.es '= /s./5 5,-S b ' 'b.L.

x w.

Ks-fp,,,;... is s<.os - - .. ' (i Mlto.a ' rgC'/ - ". !.L.

x.2 - = ," A.

gov e P - 16.8 .9: . fy ~ eA w mL~d w hq

om p p ' 9.s s'. 8 2 h a qs ^~ M,, - / Pr~ sye y 3h et W . , T - e p t_.c.. ' D / , , h

p.u.

- .k' GmQ. 4hxu..+ i, w O U-L p - i.4 be i.14. + M (.db 3

4 f, . - sgfhp pu ia,-a.

If,. = 2/+ 144 x 221#_ //d osRo'N ' rt.

2./ 2 no o 6 e - w.Le ~Q m % A la Le.w g s - s. Zb =. 4. 7 W y v. n. 4 b + 1.9 % a ' (k.

4 3 x 2't.'l%' , 2.4 5 ' /O

ro b.4 A., 2.43+ 990 - i133 F. tid (? 4,4 . k . lZ,oco ' - (=4 , ti I (.. oo u.

Q(.48 s '7

  • 9 g

h b W 4 dkgc, g

V: A.12 ('lg 4(. & L%..i51 g zz.n z.

n.

4/g.: t '51 o o o / (, o eJ e1. p ~6 5 y w .ss(s4)f4 Aby.f ^ 0.U dl(D hi " [] _ n s= to'

- .. _ __ - '.\\,, , nu.,ca.R .0!.4.. .... /@. o, lS 3'4.

N ..l.Q..5.~. Y.... Gibbs 8 IVill. Inc.' o . \\,,,,.. ET......'. cac=cas. oisic~cas'.Lstwcroas 3/r4 . ' waw von 7 C & H Job No.

h.

... w y. m.;* * * * * * * * *A.kj {..s.w..cw.y.fy{,g Chk'd/Apo'd.

... , ....z........................ ,. . .. ' h _ i 4' C '1 _ ~ t

'.

, . i . I - i a ' t + l'

4 , a dew.

GCg.r , . t Q - ~

  • j

- JAes + 33.54h-59 '

+ + + ' @ u,3h jg,7 h o . ! 10'-9" _ i o'-9" @ 5\\ab Osck = 18" t) ! fLd - = I bi A w/ & Q 0.dE i6;Arjv '

' c 6 D.6K 3.W- " 2.0l h

4 ~ . f; @ Ogqq,p 14 4D L l,9( 6 = 3. 5b 4 u s,q,,, .O L) gegi p - D+-8(.fD)='bL-U . V ir.c 'It d , a L m , ' .R ~$ % wu. - 4.uK2 ts

- . . ~ pu 4 d ur b ' - y WF.

(Ang eg c s.1,41 1.9 ( s'b 4.1.4(t.5xbx525),th) U'V'e t t i 4. ci (7 m - .c 4 . Psb i.sn - g 3. i4'h - s8.72 hs,A . 4. c.6 "" l*,'k - .- - , .. _., _.

- - .. ._ , , ,. , ,. . '. H ifl . _.. 2.q4B;j,of,q,, . ' o.... \\Q.~.*h O.% Gibbe B Rlif. Inc.

~ nu.. e.a.

3/'" ., sg ......... e - - . m.

...c.3. t.s A.. ....,.~.../r........a. 6gg ~~ u s. - ~ e. = ~ ~ ~ - . v.- . . y .. 19.m =. A n:...%.4g.....El.. &.a.%.%......... -, -. ..................... ... t . ,.. $ ' - a- . m . .t er . t 4.G s . c s 'l' (m to.sa - ukt 0,j"1 - 82yr2.

44. M W . Uu3 - i. 4bg l%, b. soo o,w.3%

i.4 g. i.9(.8 % e.42.b = i. io (l'

- . ..... .,0eguie . - tAs .. . , 'e K- \\t = (. c6+ t.io) 8 75'i -itk ' ,o no . F- _. 46 4 L = 35 osa.

= , eon A (b6 .cos(yNN(z 6 =.6 7 J/ '

Os e.d e8@9"T{3 A 1.os ).67 o4

. g, Y . Al h%5 h kgoet4-a 4 c h d % c.<_ d f- - W ( i.76) x 9 75 i 75 ".E - s.4I' ' r st . 4, s 4io _ e 4* 2 i20P o /c. - .65(iq (d) ... -_.

. .. -__ __ ... _ _. _ _. _

[,. ~ M E'M O - ... .. ' - > 's .gkfb lo lc . - . Gibbs S Hill. Inc.

' 3'ogg, , ,

~ '2 3 Z A , =oiwarns.otsicutas.consinucions - mw v.a.

4. M.

Za-n kNe L S /4-75 - 4DCI hux..hld' y d =A.i , q, e el 6 -^- /S. C. Mu k4.cnn . ._ - ~ e . . . .. . 1.

. G-LoAces [ SgE.

H oe.t - 3. n .44f-cel : N/** "I "" " #F # o NnM ""A UELT 3. s,1 gacye/c poddar hast.v.

2O - Aorie Scial 7En M * , y g,, Vext '2.

a fe r%E Y# S"n***N wi4f 4c y>sv <x's/ce/ " as n, azas W '" ' , - -.a x,,.~. s.i.i ,, w Y ~ (.ha.ryk) ANS l A. 2) f k er,/a g, ' >Casse ' " 'f M+tc en ndicon.. O - ra m,ie. g,,, a _,,,,.,,, g,.c-.,,, zaoa. -

  1. A'-

p,a,canv 9 e

?5ec we m .ir-Me prow y

    • " A /"W-y ci fa~c a,4e n for

& M f c a. / /wruts, de l Mfovb3 & & *lC M t<d$ & g&,/stil 0.p a t' s/Ada A s's&c - A&rf & Ma mp6o+ e s2'-4' i . E . . - . , . . ~ X , x . s ai'-4 " esi' 6" r.gN -) 7 tX k'.. R e.c.YCL E.

- " - \\ Botic Acto - ' H o t.'D u P l TAug.

i_ . -

  • h fe Wo w s p ThtA W 6/.TMk]'

18'do. > 1\\n (c' Y p . @k 2 4*-0 M ' s'... '* js' o"o.r.g 81O'-6"

810 %6, c f[ 53'- o' It - . + - - . U_PICg q 7*g ,p,.7j x ' hi. L . M P,P O R.T FidgED * t'**6 A R RG.T.

Ft. cop\\, ,7 9 0'-6" '- 2c. St.as 2

ric..a .f______.______._.

_ _ _ . - -. ._ ... _....

.. , . .

.Y..d?., &.7:3.. Gibbs B Hill. inc.

nu.. ca..M.4.'(? { P.. . ^

=~pauis===s. aer==r

. g g.7 ... g. o,.g.g c....,4.tr. g....4 , . v.- a s n s.,u.. C M. . ... ew r.........

2c. /.. 4d.....74...wr........E l i 8. 1.

o.....G..........i...u.............:......... - ..... ., ~.. ' ?A~ f ofd - /d}k6" y-9.

/- N ' \\ gg e ' ' , , >,

- /G,p@-rrf.1545/*

- - \\' , h AJ l} ff"d Y

%_.

' .sy/ ag ~ " s Arp fnd najaade farces 4 % Ma{g.rg,ypgyg ffff+i,Pg, Oc =/.425+ A9('24) . . h ! ./.S + ,. qf/ ~, 3 7t + V6 = 535 $' !' s Io- ,na p,p,,.g = . c,c /P x ~ y 4g*',,, f/M' To i.. ~. ' 52 '. . - . sgg. $, f_ zy.d . , uj= /;/6 + //(N(/k = / - - 91 +.72 = j'54 - U //o = ' he * W {2k *S k =$$ ff* O y . . A:cunic /3-o</8 t N \\ <' / ? c' =e. - P.~ nc C.

') 150 O~ f.hs.

o.34 y3 ' ~ A= un ce,.f q % g,g

., w

" , , \\O A f o )q 2, ,,,, , F= kgt w(z.gf.,. 4)V{ . ~ ,. ., _ n- ,,,, - _ _ _

-- -- - ..- - - -- . - - - .. .,. , .o tCh fe-Gibbe B Hill. Inc.

nu., c.a..W.$.*!.*!.4.. - .... 3/gg ,,,,,,. g.,. Q.c.4 e amuas.oesio~c=s.co~smcw.s L c,,,,,. ....., ,.. vo-o. n,.. 732 5 A.. < \\ a,.. ............ I _ u,,..T..O..S..t.... A..tu... b...d. g.......E..l. <...$ 1. o.....G...... . u....................... ' ' o ... ,. I' "** .//3lg yg ' 1 0 <- ,= _ '7 6 ' 6A-s:u.e - Me . cop.n_ = . e lpf /.3 =.00fj(/?h2h s ' ~82c<r' ^ - -- -- Osec) .5%em A ;a is.% z. '7

b '5 (L3-9M 8,)(' d ' 344 1? K

/ 'n. r. - - ., -*~~ 23 0 ci o ? MOQ ,$ /fG 'U = [. V e c u d5(Mf24) 8G { ' n - - . .. . I e" 2': Nc) Ebtor- 0, . ,,47 2:2 ^ d - f ! 4 = (i -vd Q s 9 'ik . . ey U c,o.coh, 2 9% s. ( -/z C,) / 2 . O Av 50 Q s mr

. C 'C' woc) 20 's .-ro ( / z) u4.t.

AfGD . e . - - sm e-v e, ew e=,

-- .- . .,. . . ...W.4..T.C.. arbbe e niti.ina.

r e ?.#.-!9!.c . . . . . c....27'..... 3/ff .....dC.o,.g.s.4 saatas. ois'c~<as. w~saua= ...,.$me.& .., ..t. 5.r. g A.. " " " ' " . c.

Tosi-Agx.. f61dg El B!o,'- G....................................'......a.

...i,-. ..................... ,............ .. Des / Ne lcf ol- /pery/c/.gs) ) sw s <- a su s,< s m /6

/sC/'-o' A/-- f82 '~ A - .r 28 4 sfc - " . d .z- . - /.fa $50 a i.9+Ed2s /8.

- 264:6' 7r Vo)#

. A-)) - z,3 7 e .z.

__ . , , _ _ _. g~ ~ f.x, . & c ~ %w a./ .- <n.o fa/

ou . - . J -

e.

. .-

f - . . - - - ,.. -. ,, -.-

. _ _ _ _ - _ _ . ... _ . _ I.

' l.,..,..

.. ....&.k2.4.

Gibbe 8 Hill. Inc, / c.....# /... .... i~canas asm~tas.c=5muc=5 3/60 rm.. c M.4ll..(?. .....g. B o.

c... =........ gg, . .., v._ . . ...... l.B..l.o '.. G............ o...<.. u a. w 1., u. 23. 7 (7 ,,,,,.. T. o. s.i.....A..u..o.....fh..i.d... E . ... . .................... f dcuc /cd &} caz2h4' a f'V":/S d

0 /.f'D,i),9/=y'a '~ 3, c : &,p5(.sp) ~ /. ir('s,q) =.S 29. O c.f g, /, /2)+ xffd)/) = 2.92h - /.s t / ' 7ys is eIrnod a- - q - d'8 O, U Sp(, rc pc n c.'- i ' l3 f.f" A/l--- I g . 2Of0..,;'- . u , A= tu./* (s. 55+ de)(s.s.42)' /ac #*' ' 'r' /00 - n sc.> . - ia.. - - - . ( . .

.A d' ' ~, / z ('ec,f ,.pm J200 u /2caoca ~ ' /00 ,2g $ "- 'l ~IS l ' a - A s = g b a.. & ci)(9.<.) i.'ss t z.

o= mc;; Proddec/ # '" l*]y} V = (8 8-+ x55)('/3.42 2& u e As rnos/ 0] //J c(f UPox ', . - ,y fc 9 ls r c /I m.e n beom = J f>b-4.J -::. J'(o 90a .,i77 a o, = /Et g, C&5X/2426) . Alu3^.>/2r.o~

@ ^'t'

. m .c. & aak 2.o m.n ' } [ : Av [u _, 2 ( (n c o c c h, / 9, C, WR N h / 8 , (zs.-d]sd (= ') (' 2)'

c . ks, ~ .

, .

,. ,.. '., . '.... L.ct.7.%... Gibbe S Hill. Inc, n w,e. s g s, t.o,t,,c.

o '" '"""5 D'5""5 C "5'aucreas ,,,,,,,, % d,Q,,,,,, c.i. 5,...I'?, PS...... - Dallas Chk'd/Apped. By. 4. 6...... G&HJ.bN..N.h I.

.......1x / R. R.6......l.4.E!....................... 4..o.s .. 2 n A..s.g z!2.. R ef.

Sh6 - f ol c

, Sheet 3/60 $$$' / Ae fl y d. = 1 0 4 in 1 l'>1 Cct cl1 dlrcc4fovl T 4 6.

e,c4ch t.oo. y / hs p ro vid c d. c * I o @, 8 " T48 (. e. I 9 in '1-/F1.

. / I4.o 4-in.2 " For 13'-6 wiidM Ae re.qd. = 15 5 C l.:4.)

' = A s pro vid ed : C l.9 ) (.13 5 3 - 1 C l.2.7) 2.4. Sa is .- n.s c zt ie' . Dc/voA (4 emg 7, g, 9, l I, I '2-4 IS cire, O. t<. ' ,, - -. .-.... . E-W R ein forceva cui- - / As reqd. -

(.l.c 4-) C 13 3 = I 3 62.

irt.1 AS pro V id ed = (l.9 ) C l S3 - 4. C I.2.7) 5 19.c 2., in.2 ' [J I3-D .n ' ' DC/pDA ifsmC I4 4 (5 cert o t<. ' .. sherw Ties Ho shewY Me2 cwe.

require d umd e.x Boric.' A cid Tew k,

  • '2-.

[Re.fe.Y shect 3/56 # s A 6 - fo l c ~7 . 1+e/m 5 # C:, cwe, c. N. g u s 6 %so m so o ' . q e.

3,) mu% B ecaW %, Col umvi Aehtf.

(f s/sy, s/'y f s ",o.)

R e.f.

sAs tol c.

eheef 3/G3 Ao rqd = 7 0 in.'2.

. -.. -

- - - .- . . -- .- . ...,. '., . . . .. . . - o....6:c.l.1.~.M... Gibbs S Hill. Inc.

nu. c.. 56(3.l.Q.l.G . N s.4ff....... '"**""5-555"'"5 c "5'""c' "5 c......[? A S...... Dallas . ci,,,,..... 5 8... a. u 2....232;3,,qgg .,.......T?.c /P E6...l.4 5.l............................. o...n..... 2.3 2.p. 7..g.o 7.12.

- I4 4-ails of * 11 lacems spl(cc.

loctv s's c ut, cassumu- +kc_, locw 4e loc.

ivi sff ec4)Uc. c'. R-l S

  • 11 locurs cure, t,0Ce ch%

/ / hs = S % l.56 = I 2 4 6 in.T 7 7.o in.

reqd.

. '. a. g , /

  • c N R 60-SA%

II9 Cl S h ett' I/9, IfSI,'/S1 n col u vnvi N o. '2. o e s / P vnu. : 2 Gs.s ' / 11350"A / Mg = , los4.o"lo / Mc - __._ ._._ _ .

/. J reice ree mv.d reg d.

l.oi 7, / r einforcem4eut prrov id.cd = <.2 4 4 y. / ,.%s provided, = C36'I ) 156 = 5 4 6 iw.* I ' . . o/, reirf.

= 6 4. G >c. t o o 2. 3 G s 48X46 D c/DD A if.eyn e to is o. k: . / ' .. . w eall Dewe ls t' Re.4.

'D w g. F, E. M. xD -232 3 - S-lo9 Gn'd 24A ' Pame.l

  • Gzal / 4

'G 1 3 s ' L Calc. 15 cole S AS-119 C3 8 sheet e/c /

As req d. = o.c o is*/ir).

For fle.xuyetI rein f

. .. -..... - _ ' ,. <. . ... . .;* a ..G.l.%.7.S.... Gibbe a HIII,Inc.

nu., e sA.s.. j.oI..c - ~.... % % f....... ' c.i.....S P.5....... '""'"5- '5 " "5 c "5'" " ": . Dallas ewe /A d..,.6. D... G & H J.h N.. .. . ...... P c t. p t?.6.,.I A s.(.......................,,,....,,_......................... HoweJec, rninim am reintorcews eu & is provided-Por +en pe.w4 ave, 4 shris kaycr.

c u 4-d o wa ls, cwe, e. p. ix %3 casc

e a 'q. ,, Dc,/DDA if ew & I, '2., & 4 4 - cure _, O /c-. D as a,w 2e via u s %,- : - fer.

s ee u ? cas .s n' 2/2cp 29nec d 2.5/, d Edb zowe Q, d - 85.c,8 x'/ (W'oisnssirmeh -

  1. genh = pg : M. 75 As pawceh =

c. as '$x x 9/:. : //:7CN*/s,i.v " , seurw n c e As = /i'.?2 - 3,,. - 2' 75<x 2:otI) . c ~ ' // 35 - / < u r.- /d fb iiv L :, Hy,' NotTH

P= Poi H  : 7. +'s MN - 30, C e s s x. = / 7 5 "roy l = (DP= 75, r/>z ? 2 2 (. o t<.

P - 7. S, -Afu ? 20fa, c'A;;' l - . Nu > Pfeee'c

. ... ..- - - . -..

. _ _... _. .... . .. _ _ _ _ - _. _ _..,... _... . - - - - . -- ..,.,q , . . . ',,,...(a./.z..7.Q... Gibbs a Hist. Inc.

ru,.. e. s.A.e..t.c {- c;

3[4,oD-Q**'"'""*"""

awan.sens. otso. ens. constaucions c.= or............... Dallas _ e,,,. n..,.4. @.... a w . 4.S.9-1 e s' ., .k:e.MW.$.Wim!744. C.?nmfM................ a-..n-. ~...... ~............... ' AMocerOURE To bar es.cP A PPRog/NA7E UN/-Axinz. syr5encrtch' DsAQ,gnM.* h Sritains5-6MasN St.;iMrm : I C= (ceW-c) p, z ~*~ . ' 4 rc.

e t s / l Asr l . . l j f <se= g (c-c ) - z { /l sz > r/, c-e-2/- 1s.

- e r

, -- g p._ ... - Na.

a = 2 f a c c sc.s 1 - - r _ . Eh 5%McK =koHgMT* g4 Af/OWs ' P - ~s % a _ ct.

c.t s c.

! a.uste ' 7s* = Gsi)(E)64sD g e.c-l .c ire,>fyfe.

s MN<s*#ff& U j q .1 O,$ 3 Esg at e = CesM')&)-4se) c { .2"F Ct. 4 C '

TMauc:(USftGkb.)

y -: e , r s: w iorn a P = c, e ca. - r - Pu f P M=(?s)(YZ-Ci)ksk'lt-Cn\\.*-(Cb("?b____ - __ . .. -- _ . .

....... ....... ... ...... _ _. .. _ _ l "bl&N a vts w e d'$ h y., m sy7 $ ' .. ,

-

- S h ts - lo I-c '

  • =

30.00, B= 1.00, COVER = 1.750 3/g g,_~ g . rY'= 60.00, FCP =-4.00, E= 29000

  • =

114, AS2 = .093 . . .

S PU MU PHI 6.4E-2-5.658398 92.149129

.9 6.2E-2-5.256438 97.541743 .9 6E-2-4.848050 103.020077 .9 5.8E-2-4.432602 108.592190 .9 5.6E-2-4.009377 114.267181 .9 5.4E-2-3.577556 120.055360 .9 '5.2E-2-3.136200 125.968463 .9 ~5E-2-2.684231 132.019896 .9 4.8E-2-2.220400 138.225054 .9 4.6E-2-1.743254 144.601692 . .9 4.4E-2-1.251094 151.170397 .9 4.2E-2 .741917 157.955178 .9 4E-2 .213350 164.'984194 .9 3.8E-2 5.280742E-2 168.088961 .899021 3.6E-2- .621159 173.630550 .888346 3.4E-2 1.204147 179.234881 .877119 3~.2E-2 1.804254 184.908554 .865246 3E-2 2.424399 190.656709 .852608 0.8E-2 3.068011 196.481577 .839058 6E-2 3.739121 202.380026 .824408 (Z.4E-2 4.442448 208.339377 .808412 L 2.2E-2 .5.183455 214.330177 .790748 2E-2 5.968306 220.293469 .770980 1.8E-2 6.803583 226.117761- .748508 1.6E-2 7.695375 231.596018 .722477 1.4E-2.

8.751468 239.201628 .7 1,2E-2 10.32661 256.409975 .7 1E-2 12.085064 273.773963 .7 8E-3 14.482955 295.358333 .7 ' 6E-3 17.946577 322.270617 .7-4E-3 23.389410 354.377243 .7 2E-3 33.34611 378.687421 .7

60.83441 222.183927 .7 -

6

' i - , ,.-r w - .w.

. -. ~. m, e.,.. - - <-.

... .. -. ..... -...... -.. . - _.. _. _.. - - -... -....... _......,. . - . f } '* hdEiS /C ' bad / 5WE=0* 3 g3

30.00, B= 1.00, COVER = 1.750 6 46 - lc l-C 7Y-= 60.00, FCP = 4.00, E= 29000 3/go F-D .093, AS2 = .114 Sci = 3- , ES PU MU PHI 6.6E-2-5.618954 62.554929 .9 6.4E-2-5.154956 68.768742 .9 6.2E-2-4.685089 75.061113 .9-4.208795 81.439204 .9 6E-2 . 5.8E-2-3.725441 87.911074 .9 5.6E-2-3.234310 94.485822 .9 5.4E-2-2~.734582 101~.173758 .9 5.2E-2-2.225320 107.986618 .9 - SE-2-1.705445 114.937809 .9 4.8E-2-1.173708 122.042724 .9 4.6E-2 .628656 129.319118 .9 4.4E-2-6.'858920E-2 136.787581 .9 4.2E-2 .503173 142.960532 .890583 4E-2 1.079844 148.935915 .879538 3.8E-2 1.335936 151.277004 .874540 3.6E-2 1.935287 157.397173 .862608 3.4E-2 2.544074 163.530751 .850123 3.2E-2 3.164210 169.680413 .836992 '3E-2 3.797904 175.846500 .823097 8E-2 4.447694 182.025310 .808290 .6E-2 5.116473 188.206290 .792382 2.4E-2 5.807484 194.367358 .775129 2.2E-2 6.524242 200.466986 .756207 - -2E-2 7.270287-206.430457 .735182 1.8E-2 8.048576 212.125352 .711452 1.6E-2 9.065132 222.346576 .7 1.4E-2 10.413452 237.868354 .7 1.2E-2 12.04063 255.780290 .7 1E-2 13.799084 273.162741 .7 - '8E-3 16.196975 294.772289 . 7-6E-3 19.660597 321.720941 .7 4E-3 25.103430 353.884717 .7 2E-3 35.03073 378.687315 .7

61.66643 233.720800 .7 i . , A C.Ti o N * A pproved by D E/C D-s -lo E%

- - .-.- .. . . .- . _.. _ --

.. ... - _.

..,... ! . . . .

o....0av:.AIK.

erbbe a ut:1. Inc.

r.u.. e.d.s fe. l9t_q _ ' ' 3/u ........... g 9 ' ~ ~ -.... - c--c- ..,.................. Chk d/Apprd. By...M...a..n. old G & H J.b N.. 2..B. 2.3..A... " " * * " " C ...... T..u..s..t...A. u..>.<...S...t d.. s.. 2.E..t..8. 1. o..'.. G...................,,, _._ . - . _....2.. . ... :B 4 8 - 3o x 6o supporhh9 Boric AcTet 'Tahb (Rarallel chech bf Design Revik,wj ...hi= l2' 25 x /0'3 4. - 127 W' .... w. l W2 15 (co-e e) is, i e/t d.

~ /2 n-n-nn.~ l (wg & A ' M= Vlo (L.*)rn + W2 L ln.

1'2 2 5 \\1 es , , , , , , - 127 x 12 25*x oS2 + / 4 xia:ci)2 "' 990 + /9 = foo 8 - - . W = l'2 >c 12 7 V G /2 + G a 400 & . o . ?

oo e.e I,s.

~~ II

._ - 2. < ..2_1 - Sw..... ' ', - , i_ ' _i.. s -. - ,. _ - -.. -.. .-,

.. l.. . ..,..., , 0.... ??G=%.. Gibbe 8 Hsil. Inc.

nu.. C.a.'.sq4,-),0l,q,, '

h ENGIN EE RS. OESIG NE RS. CO N ST R U CTO RS .h t N.. o,. C.1s Br..... ..... New - Yomst - C & H J.b N............. Chk'd/Aperd. Br...... . ,,.., 9.4.1.. 4.. h. n..W. :. Bio.b.9............. :... :........,.......".............. w

  • 6nt.&ob 1 -eA. cA km -/ d w hl/od-/ & L/c_

o.t.

o se co - ,P u '... p. 7 f - r 1 - du-p Lur. }c z5 , ., / e s , t ( / Usus +QQ , us m = /. 3 6 ( 4 ) n - z n b _ hag.- so v 'd. 63 2.15 + 2Sx5.ox./5 ' 3. 5 + i,66 - s.56 G, /6 7 - /Qad . ' u,o s = i n s a p h) , 'hes= 2(77$ s)% is a 't' % , f /W' j 7 75, . . . - = i.c. k /' Uhad= 2. 9 2 (I. l,) - A- (a l N' ~ _4 ~

u$"'t s

h/' sj_ [L 4 So ) = .e 7.7

7. 7s p Uu - /. 72. U = . s 4 esnaaL A d svu lk a d be.w w.- A* # b bI A l$* f

  • lb / S*E.$

~ $0Y i s-ux.. o~ .ap .8s (~g o) (58) . . - _.

- . . - . . .-. .;.......d.9-2-2C Gibbe S Hill, Inc.

5l$3 nu.. ca. M@. ~!. !.4.. ' - c........ 8..... . .... g o.. g a e s~=~ u as. msm ~ias. a~5= c== - ..... ~ ~ ' * * * eww w..,.....M+~ O aaus.u..?4.4M... , , Sub6 t @....s.i.....A.

6.........E..l 6. 1.0....G...............,....,.R.I.Dwg./Sp.s.N....................... .. Vd V = {S 6 - 2 5 4 ).r (/. 9.yi / 25o oh gg - a c \\ Vu d . A/u to.l 'fd,$ > /z.rs* . 72/ W /o /. 8 3. 5 - 7. 5 t'7 2/) /7Y - l' ')(?'O 7o'fa./ M = too e + 72 I nr = /729 WydyM^M%-3 / F, bd: aa < 5 7* ._ 2500)w L f.

_ // /2.000 ~ _ Ili 000 ' Hu

8.t l60

/ 729l8-l-2 /3

  • 1/c *= /* 7 ('20+ //)

- 225 p _. 4, y 4:- 3axC7x4//too ^ erra aem j/(5 6 /2 ., 7'O 'n' 1%v2cd - 90 ll NoviHcrL . _ ,.,, y . . . . .. _- - - __ .

. _... _ _ _ _. _.. _. _ _ _ _. _ _ _ _. . _ _.. ..,., ... - . ' . 2.Ab. M...t.. .. A.

% r, c f.../.q/,9,,, / Gibbs B HIII. Itse.

' ' ' e/64 .,,,,. gg,,.g g 4 .. .. ~ms...... co~muc1.. ,,,.., ( , r- . c. n.

......e,.. , w, yg(, _,,. t.sasA.. . ...1.u Mtc..,...kp ?. & e d u...................,.. ..................... Ly . i.5.'- 2 " - , _ . . ) D . , t ' i q'8 M Op I '. C.... dc.g oor-62..N5 G L/ '0 ' e/. eor fa,.r ' , ) .

- N

. 64y eqar h'x 4 +'7 * /.1.

c7 T . ' . , $" \\ h ' - .

( -f

-

p . 94" we$46" Dc_b +f<. m , e' r.44 -Io d

L ., Wl u. - 94" . C .

  1. '

rl' ',adu.d n o' i.es 'b,dg =f((i2n)q(i447g-

  • Q rocce. 4 %

h oe 3 eo.d k f_e.

/J2A.

%,, 1. 6 4 f < s.2.', n.c 4,veQJ %, C na9,&^, iw+t +& U.s,_ga : ' tsp.6%. l.8be.34.D 'HT '33 0va mk b -h+1h=FA Q =

. -..'9++h w_w., ,.

e m..--,g --e- ., n , - --

..... -...... - .. n -.. -.... - ... . _- . .

.<,..,

, _ gf nu.. c.<. S.#.~@(R.. o .~.lQ '%:~~lN.... Gibbs 8 Hill. Inc.

. ,,g,,gh,h ENGl ERS. DESIGNERS, CONSTRUCTORS %y Cal. Br..,. ...... ' Nsw YOdHC C & H J.,M. 2 5.2.3 4.. j .{C chk*d/A .3r......... .. p. s.. t... .o..x.

..d..a, a... E..t.,.. 8. 1 0.....s......... .., ......................... , s +. , . . . V ' r M g lO Q A M kw x - i

- a-45 11.'. L p.= 3 G ~ . . ,Up / -,, cabddf d= H ') . 'I h ' i , ~ e-J'; b'!/h.oao = /'- m( .u 6, /94 = Av. fp n = h3 Lo x 7]5

p U;0 e lc 4.p + 17L t / *4 Fag a j - g-D + 1'9 H90)'+'N v'h . %,$?$?)+ 21 2. u.j J ~.y 6-E-0 D 'a . +. y z + W. '7 f w= l'91 4 : 23 -- . e .q,go, g ( E f _4g;:p ^ t.f'/' gi "Il - . . 4g _ M= w /Q Q , 40 i%=3G F= b - , x 9// f, g, - p . /2000 $ m kC / O " O fr-(a dm Qg. }- . < - .1

  • [190 in) h._

. - - W-

., ..,u ..., V= (.G5 '.1%.ss) y. Af .c, S r . z.

t z.

M C M 4' C.'g af N'* G

= f- , s - K A:emo ve ble We// lcah !2 x I4 x 2 7 * 'IS = ll4 ' ^ / 4 o + /'q * * 2 b = 192 D (' , jr 4 9 + f.9 Fago' = on.:,iuw n ut~ - - -. ,

._%,,., m -- - T- - - - --r---

- . .- _.

_ _.. _ _ ,.. , . . as.. @!. 7.5...... Gibbe S Hill,Inc.

rua, e.a, S.M.~./?.l?.. ' ENGINEERS. DESIGNERS. CONSTRUCTORS h Cole B r............... N o..... m, ~ ~ " " " Chk'd/Apped. By.c..u...o. n da/ C & H Jeb No..a.s. 2.s..s.....

.,.e...To.s.t... A p.e.. Jh.i d s.>... E.I:..@ o.'...G.......,o,. o...,,,.e.......... _............. -r , sjab suppadihg Evapara/or Pac / cages.(Paranalchuk., % Des.Pxviewc1) .~'".s/ab 7hi%er.r - s'4 Floor Frh =2" - - b = 23' o _ _ _ _ _. / / / / / / / / / ?' / / t 's / / * / t ' ~ Ref: Trans/adbn d'//3 a ' } $

% > ' C.fCaA.,lonOon, Eng/s rus.

' " I t , i , 's i ~, h l- /4/23 = ci $ l f x IN R 3So ' k $lb = * '2/23 '08 7 / - , ~ s i a , / %) / mib, Qi$b+ Ol2 + a 3 b $ O2 y & p ' B/b+ h/2 + a4 0 #, $= 210 = , e s,,,,.,.,,,, c,,s

,,,,,,,,,, = 087 v'0G 2 4 *GIx /3 G *355 p.

' ' 087 + *Glo + t' O G S '272 Y 930 , - 5/ K/ft - l'702 Correc/ed Mib (b) = (8 h*) xst _ (10 2_4.S)<5j

. a'1 /61 , ~ %B G v 5/ , _ 47 Mt/t ' 25G p ,, - G oS x' 3 3 0, - 5 7 2 *l' Mil = /3G M'087 V 0 C2 x 'GI 'BSC /'7 G 2 / 76 2 correcled Mornenl Millbr)' - [d N -) #57'2. =~(22L fo'S ) 52'2 dz j 4g4 - 37 4 x 5 7'2, - 44'8 "'I ' 48+ 2.;lTo /a./ M= 44 3 + ai = 10 5 "lr l,- .

.w,-

- It - - - - --.d=- 4G 'l

t t.___ / V yt-p_*_. 3 - to = 4G" n., .... r2<44 /Q.,ooo= t' 9 4 ?~~~~~ ^

F= bd2//2.ooo - ,.. Eu = fos // 95. SV use k ok.. E~' ~~

As a *BS < l1 s 44//00 = l'7G is) providad n'/c @ e r.g e, s.w.

~~ S ci 90 ih*/). .. . .. . -- .. .. -.. - - - -. _ . _ _ _ _ _ _

- - . . ., . . . , o ..R..G. 7 b... elbbe B HIII,Inc.

3/g gm e.d.5.^.%..'R.*.C - m, W s,eo,....... c.... B. P.s/...... '

= = s. m =~ ~.c a m ucr

mu Chk'd/Aperd. W......... G & H J ob N........... ...o.c/.12p.o.:..W.2!.....g.qy;.p.............,,,. , _....................... ... (c. hum %, ' s Re imf.

required = l. 7G.in.2/Ff.

o me For 23'-o As= l.76 C2 3 3 4 4o. 4.8 i n.1 7..f 2. - To p

'2.- (So44e m bev>.f cure., cui-As pyo vided (2.6x i 2-2 ) C 1.'Z 7J = 41.17 in " 7 4o -58 - . s , v. '- . '. A c.c e. p FC d.

. A c. T t o N ~. A pproved b DE/cv - 1 o9 53 y ElCLEAR SAFm' 7tE!.ATED . ,,l ' s . . - . ..p..-. m -= +-eere-.- _q r.

_ . _.

_ .. _.. . - .._ ... - - - ,, ,, . . .........f... Gibbs B Hill. Inc.

nus, eae y1 'W 8-Iol C D .../..O - . og,hk,,, ENGINEERS. DESIGNERS. CONSTRUCTORS sheet No.

CelsBy.. . NewYm ..... .......z. m.4... ... 3frepfm.9.. 5+.,.mc.,e * * P. s u...n..,.. e p c, ."1 a e c~~~ - - $

  • .f

...... Re f. Dw g./S pes. No........,,,,,,,,,,,,,, .... . - . + + Qey agN = 8 'i+ tfpd -tsh " r @d as' @s\\c b %,ch.

(8 "

} . ' 3C/" ' h,U 1.5y mJ %Bs.

s..o8

y p[ed.o w l b mo(

C8E

h% i.o i Ose.

Le MA .

d = 1.4 1 * \\.9 % g. _.

" --)ap 25" x Il'4 kon m , e . ' '~'

- gb x (i.4 +19(t} g i.9- ).cibx.iff e ' x t m + q,, ((es)(n.zs , i. 58b +.oib ~, i,59 b ' - Vf C U L f .// '4 % , N - MN - e4 s p _ ' /33" = /. fDs Fh - 2.2h 2. 2 > *.2 (154 - 4 7a * ( Ogs,,gpsa i . < 2.

- ua y,.= t s9 (z m, 4s.* p 3* ?yk . _. _ _ _. _ _ _

..... -- -__ l

', > > ; , . , , o....b?.0..lE Gibbs S Hill. Inc.

nu., ca.$$!?.-l.0!.?...

' ENGINEERS. OES4NERS. CONSTRUCTORS hf ,,,,,,,, #,, g,f c.i..r.. M..... New Yostet L a a us u.C 3 X & b.. e w w.., .... .. 1. 05 i.. /.yx...B..ic.(.9 S..I...T.r.io '- G ~ n..o. < .nm..................... ... ............................ v hg,(, Og-QdnE I 't 4 5 ] ,; (' .3, a - ' / @ / }/ , l '%. / a.

O L o.. ,

b u~-t M Ue evs..e d@ /2" s/9 s dm e, 1.4b+i.9(4h . 'z.9 2 h l g,s od iso + .5. = foo * h%, gx u _.

//ea W s s Ugasp -- 4 %420 = 5 Is* Y t (4,t a. n - 540< sn ,-. _ ... W , h ie ' F -ML

G '- 2 " - { {.' j b _ i? i200o . (,-T G

, [= /5/ /O9 u-4< % =. . o'o 3 3 -- - Af . co is.wn>

i. o a J H = , a Q S 8 A g -=. x M sl'(; w a + c/ a(%./a-ca.

& m ~/ -. H v (i.no +.as)(gl'- %) #t s un Q 3.

/f 00 Q $b d /$$ ~'U W . e.

g - .ss<m a m& co y. _ _ __ -. - - - - - - - - - - - - - . - - - - - - - - - - - - -.

........ -... _.... _ _.

_.... _ _ _. _ _ _ . ....... -.. -. -.... .:.... - ,~. ld. E.'2[. G Gibbe 8 Hill. Inc.

rw, ca.?d@.'!.o!.9... ' gg9,,,,,,,.g,,,g4 . cmuns.oisic~eas.co~sraucroas .... ..... p .. , v.- ~.>?.8%,........d.v.e.,.f3 eg 8I o -G, u u .M23A.. w f c== y.

.t...< M s.r....t s xx...... ,s-. .....................

. /nn .

w/. 4'/ a ) 'f ,,f g v,,, 4 b .6 A rk.,6 p'. 54 "i z: p2* , -do,c s ) f a. s .P/A4 3 ' io' zi to- - '3 cp B7$ S-c' 93)" /b,g, s./s(./ q)e.ob(" dis), c so*/I'

f-psA - . .

  1. /'

dug .c.sd(i4 s. W J 9 - /.90 . 5) A4 . /.og de Q.

~ o86

s.og lurtf 2.ogtdeJ sSE ~ /oet.aG-} w A. o'=- s. f b u 7t' +/. 9 /*. ~ u.se c a . T -- y !9. (/. (+ /. 9') # i. s(41)( N . (d ' - "(W .}(%f 5.% - 7. 9 6'* 4 <.9 r + - q,. = i., c z) . s_q . ) N.- uM_ ( t. b.S h M,, - 99

to

  • 80 I-191 ( 796,54)(2t7 = N3 Mg PG 9)@

'N W %.P - a gmp-Wa M-39%+ % =29E'-E - ._ W bdf - 1.94; d d4" ' (-Ibo n.ceo . I p A. l.14 M e /of)d %, l.9 w -- . .

---w-_

==%e .....=.eemi-. - - .,.,

... -.. -_ -. =..... .... _ . .. _ _ . - . .,. . - . - . - _ a.

. .. . . o..e../&?~.??... Gibbe S Hill. Inc.

nue, C.aes.49.-g,9... E NGINEERS. D ESIGN ERS. CONSTRUCTORS Cole Dr... ..... sheet No.

Of. .. Nsw Yestet

Chk d/Apped.97 ........ C & H Job No..%.... ... NUW)ux < h/d,g.

El. S..to.'..n.................... Re f. D w g./Spes. No................... ' Subseet . .. r .. . . /O' _ - y .a ,. a f i ms g , 1, m i - (9 . ' I-l . . g.

2'/ O " ! = = k 9 +* N4 7 02( 80) M + 92 * Ib b\\ e as er , 2 S,5 sa u s = a - SG.S ..

\\/u. SG. 6 - ( 7.r v 14 4 L.((4{ - So.3 . . - 4- _ Sa 3 oo //3 < /Mg = (osj(iR4Tf) ' Am u sf dd ~ . m . -

. , . .9

kw . . e C.

t - . ..% .www.. - ..==-w--.me**--.. - * - -

..... -. -.. .. -. - _ _ _. . . , ., ' o.. 0. :.73-35.. erbbe a Hist.inc.

nu..eu.v!W..te!.9.. e........@T.... <~ai~uas. oisia~iase~s=a= 3n .....g,.g.# New Yonet I to g . us....c zaA.

, c. - .. .. I Y.. $ 6 f..... f6.C X / L 15..y..d. W.:. 4./.d g...I.'. II.9. 8,.< ....................... - 4/ b W , - ,m 9,, , , ' d. j2-2-so s - [ f = 4 (bio) = S G \\ ' r-v - 4)^X3l . md end k me.

S'he.aa dress - u 34 f Q= Uu _ T 4 50 8S m.

- ~ f4d f8sXS6Xio) QAsaa.ble + / 4 x fg = 262 x / G ~ fos ilis.f WBG cy _8a?, J sk - egp' . sa,

= &Ac asle ~ 7 c >.as/ i f.7 . ~ .58o6 f a C; cJ46 b - M e[6 ' f .g,3 g g' -75fC = 27 WJ W^ O

  1. h6

ga , 7i y*(pP ^y/"I'^^f

, . ctNeu.)able

/. L k. 75P

lGA.154 3C,ooo = 45 2o0 ob ' - ta 4v 4 bg PI. ' ' - -. - --

4MM ' h -- .w ^^ . sy..s............... Gibbe B Hill. Inc.

nu,, ca.SAS.- !?!R.. . . . c.i. r,.. d.... 4^L us..... o,.g.ef.

<~mau '5. msmatas. coas=c=5 J27'l .. . m. vo.

..w.r.

lo 1g a.,,,.....zarut.. - c... ,M.;d'. 4N.hi}d. a.ei%.'.6.':........,.......& a x.<.<.... , ........ _ t-# /K-A n/ s -4 / g-,1 / 2o' /;s~ wab' -f'-ts W z - L w.,.,- - f.'. w 2 e. d-=-4 ' 3 f4" wy w s, t& &A. 1-.4h M 74 t_. z.oog hs e' /.od, wd7-4 ' 20 'd 'r n, = f' dram f 'x d' + / 's./s - Ed'"I' if 4'/' 6/= A Yb </ 7 4 - = yfico) + vf(.z){ '+< y') - ' .. . 7.~ }6 f)4

2 o -Z <! = y M= d2 rys ( zz)*. >4u,f',25 /~ ~ =

-

_ M6 Ja'a

.

'

_s_gz 4s x f4' _ -7:- W c i.

,. /2000 ./L oao , p' - 14J, 5 = / 8 4- - .- , . '7*74 m .. o o s t- \\ .

  • 'l D r 000 f8 Y

.' M M

\\/u = (Il - B 5) '2.3'S = 17 G - c 1 TG 0 - -. q e p d /I'2.G.

' g- - [ i gg < 44 x 4 E j . . , . . e- <w ~ se.~ e m o me ae.oen e --s~ ., e em - w m o W-.

- .. .. ,' -.. . .. . ... .. . . ...

  • ; i,,.

. ., . e.e o.s.....I.D '.? 9.~..Y.. Gibbs 8 Hilf. InC.

n1m ced. Eb$.~!.YC#. ,

c.......6.......... mi~~s. msm ~ c a. =~ st-cto =

....... #.o,.t n 6 - . usw venic - .'J. t'. T... /c)- - G & H Job No.. .. Chk d/Apped. Dr.. ) ,..... A. e., c..t.. t..i c '.!."... C..h..e.c. k.. q.... .w =.J a..v.v.e.Q..o...' ...................

i ...... r.. ....... Of C^1 '- 4%~ l o A O / t.t dol = .2 'ha,-ll ./ ' ' . U 2 o o Ib l. @ - l 4" ci o Q i. Sty 1.1L l d = l. !, v 3 0 s ' O v :.<. > 42..o 3 ', o =

^t2.ti..lil?-

.

s..a .f. e icd,3 Q <Sil X 1 = .7f1, !./ f(.

. lm w y li <: Lc4 ,I, v I :.', A

L
,.

_ % . . Ln L.s.

O t. - u'a - * , y p g., / J '2 C 0 l[O 4 5'O . - T ' L t- '2 2 0 + 3 tro - Wo YI! , (.) u,, - I.4 x 2 6o + t. ) < 2.c o v =- l 2 2 't '*l{- L,.- w . $20 4 ~7L 4 . %{M fr.

- <, w . 9[ - 11. 1 I Ut - I wa 1y ~ . - - _ O- ' .v., - ,, .. ..

, -/

d-6" y2 . - -, - - - u V w a/ -. .. . / '( 4 2. " 10 v.. s - 3 :

  • .. ~i.

' - - - / .. tw u w.. t nsy . -~~" ' H ~ ~s- .w+m >m .m.

,4.e.e.,o,, .- _ _,,, _ _ , - , _,,

7* ; -- -- .. _... ....... _... .. _ _ _ _ _. .. - -.. , - . c:..... 2.13 52.4.. Gibbs S Hill. Inc.

ni..c .N.k.'/ N.C.

. s 4 .......e..,...a4.

c.,.., B.... n~ ~ ~ u ss + v u e~u a w"s ... Nsw YORK G & H Job No.. .. . Chk*d/Apped.

.. -i ) d51.0.n....k, M C e d.. T....h.( M. b.k W h m.i.o... esp...w..... ......... a L,* " *, \\ . . u. // n r : 2 5 - r-l - l (, 5 , 2/05 f 3hs 9 0-

g.. P N supe;mLE.

N tz: B> d. col. CA > D.4 R.s has bc e w d= 5t S n- y q.y g 3.g ./ in such c-wg ihca wo = , ' Locul wih can'c 40 DI' , 9 M- ,/ ' . - b eca rn. , Rcd rcM P-4 co.lculed(on5 for RPj/4.-4'o3 f i

F : c.. y U> - %2 L-j e/ > c FA g, <g ,) c - _, V e . A,rio i LoaA D;e....F'. T

  • i

- 5." C. D. C k 11 OOC 4d k hi7., ru.r.if h'M f f'!C C,, d4 . Lonc( a=D 4 L + TA + - 45*i33?.10- , , i A.2, q,, = w O, U 5 7 s 6 p2 w 2d+. !)f(i.4:r)',, ;f 444

a22 io Ia t '5 FA f l'

t.

' =109xEC['O:'l6G 5.

- h f,3 _ Ref ; R,c. Desi n gud.bk.

'* M o,.a xi41c : tt SS y ' cal'o" '"U F= if

44* [ 5.87 A c.1. P(us e. n e) Pg .. , Laa4io n 7%o ,z000 i cd Nd ofAPP-i.

( use 342 . ' ,. g Q w o n c d fo,' . Faf,,_ (up pa-). One e, A un.h, hcoat.a c.g/ */ re w e.e .e2 = ,, -- / eo le p . i i.

A.

. I x4 s L4146 4G 0 6 .

\\ 1 Ce~l '

.3 Lw.6IF (,'2.h .:.

5.

. $rd- * BI d' . 2 fC,, , B

f , '.&

.

. %-r+' a s 2 l.0 - 4-t-K

2 -

- - no aso "4 2ce-b';o c,~hAS. _ -

S r'-l,e': ; 6-

? e 4 44 - f 4 2'-

' t= - % b ^7 Posx. 6 145o K,. i c_sa 55' B~16 . ( t.67 Q, - k. $ & l} $ k Y ,~

Y bs , q-b ) $?83. s-+4 405 __ ,m o..u - -.,,r-_ ,

.._._.__....._..._...m -- _ ............._... ._ _ . ...._... '. . r,i, ,. a......?. ~.< 2 - ?k.

Gibbs S Hill. Inc.

rau.C.<,.S6.@..*!.0.lh ' . - ENGihEE RS. DESIGNE RS. CONSTRV.

h ] h Sheet No.

..Of... .. Cale Br.

. ..... NEw Yonn G & H Job Ho.

. ... Chk'd/Apped. By ....... R e f. Dw g./S pec. N o....................., Subseet...................................................... A < A,e '.- 8, g 42u cr' 9(fy t h . ):E ? 44@M

  1. I* o

c. sg z'?, = 44-6 f /3 (prov')- S.o D"

- - The e-Wea, e~d %\\\\ h u ctk%l - y S FA t AccomAg Lec a4 or of h,i,d ' d APP cMion - ' e bm one U dus-V4u Nu (d.-h) ~ Cod' 1641('44-24%.2'.5123o 14se. m - li n <, 1542 c s le4:' -

= a. be fo r e - 12 3 o 3ge K a n.; _2n %, 4s 4 2s 3.6 1 ~ Iq3o G7 y .->.4 y 8+6 1s4,=7 n W W4 9 v (, c.

4*5 f*e4 W.. t,,14 *" ,4, (emy.o y = 4-24'*..

= cc P 2.4 ' hs.cp h ' t ds..for Rpe Rasfrmnf R2 ' - . g b N6, vp % (o Xh-2 *i2.$ M -dCo '6 CcdC '.s - I' 'b To4al. M : l46 t 7 3 6 + G5 x h IGi! * resdi.lf_, Assurnin.g point of apPIhh e t ' b P c.

h\\ g e IGil - 12Clo C5 y 9'- ~ C. L) . W.g1 . g 5e M, jfhO -~ 4eo.6 do G 1t} E=

V 4 %, 012 9rk<12'fM

Ist i.oha 4 4 - 14 $ Pu '=.1-sue k l N ,

z'= e cs az F-S.6 1 (. 1600 tv - t%3 W 4ta m e.8 7 - . -o - e.

-me-, se we e, ~ ~, e.s - e- .

' ., _ _ _ _ - - - -- ~_....J . _......... - - _

l'

e, ,t ,. ?!.$.~!O!.4 Gibbe S Hill. Inc.

nn n C.d,.. ' Det,... . .... ENGmEERS. OES.GNERS. CONSTRUCTORS h ]h ... Of..g.. heet No.

Cole By.... . .... NEW YOmn Chk'd/Apped. By.. . C & H Job No.

. .. ........................................................... N.,.o...,,,...N............. ,,,,,,,, -. A.y (. M,3_ g3429 a. A #iro , W.N . 4'l[3 R %- 4 fox.64 L c. M t a 2.

. LGoo .ot A-Ssa >o t cs

_ S-RtM4

  • Q Moa A (env3(qe;)

. v

4*o2.

= 9. o ok g - T-Q - o" > s , F-4 alt use M o :- I 4 8 1 * Nos= Nu-N ( d-h.)

u ' l E g6 (44 - 24) _ Q.6,. 4 13 G S I4 81 4= 9-6-1 - .*, = 13G3 1 '2.

Uy - Qi '2%5672 Oy 44-l 4'iG - 1.s t.. tsc3 - ieo -e a A ,. 9es r . '

9 x c.o g 44 , k4> W o" 2a(pkd Y0 ksd.o v 5. = ^

+ = s 59 g 7* #5 I'- ( Qavis. 9,:a en - 3.,. ,. - - gg F5e P_ 104 4 sg t o)<. L - . -er ,~-. * . . g . p $s EC.

, e to i , .. . - ...7' . .n , - ' ' ' ' Q p. /c I T u- - c

2

,, - .- c ! - - c:l

? 1-O b S.a/ vd~ Q.7 ok o p,, I;,_ , . :s 1 ( , I !. (- ~ . .-

.,

.. * -- aw w m-e p -e = s -

.. - -. _ - ... ~ _. - . _ ., n c.a. f.8.A ~l.4 {.9.

' 4:.'..:. & A ?. 7 4.. Gibbe B Hill. Inc.

nu ' 3 n . m.M.. o,...S 4.

. ., c,..'.T C.. va~ ens.ois'c~us co~suuc=s c ... L asu3.s..@2S.6.... ~.. vo-ew m e..,....... ., -..........................................................o...<s,........................... . ... kmm Me de& sAedu n / . h.t.

l.4 ( l

s

/k/ SAeae -p_.L (/3.76 (t. ex.7 s. 2) " 7(e.e)(5.17)(,is)') gj i. 4 z Z .

= //4 6 awe +.>.,uc/Ade,z./ Y' fined $ BOO 4 ./ A do& 'l 2 2. 3 ' ec / hf 4/2*t.s / lA S 4 2 3 br l$ $f ~ dy Mae /by Amie +Aa s>uf' he AzJe . ca.

n , . p a,,~ 29 < a - . ey p.s.

_ _. _ _ .. . .

) W ,. ' , us eoo.

z>-s , (85)(29)(f5) 7 . q-g f Q asn.c w- - = t-<5-/q - 4 *e c ~~g g '^ i%od 3 *: ness n @ ca . //'r. krff?26 Q 7b'Lj

-a . .- , ff,, s . &5(c.o,0 ~ M c - , ,4, fpva& i)- (. 2o ). gc<'/w' elc . . L.

- ... . - -.. _... . -.. - _ _. _ - ,,

..... -. -... - _.L .s

* ; >,

b rm..cN.$.@. !.0!.9.

. . o .2.. .I...~l.4... . Gibbs S Hill. inc.

' - - u...... o...B A.. c.i..,.3;T..... ' 5"cattas ots'cata5 co"5=cteas c w a,,,...,....., j.

.. v... , a6us u............. . ... DES.% tJ.. w=..hm..Be..B.. f45.T6.6MT...... o...<>, . .17.ch y........... ' LeAbs E.L dn O'.6* u / U- b5 L 4 - U + 1.0 Foy R i. 2'b -

7.7 b 5 L.: Y' % gn 'x 'o -2 *A * F.- $$7 ; ' fy n b ' '

sla_ a .. h,,_ _ - _ d.a __i 644 0 =163 y < gg 4beo V c.+., a.

w i e ev o ,% o %- \\eH,,.'g - v., rw m.. a =,..y. i , , . . r.. d.& l @ b" r / l f IA c ( s.z b + 0) y, Ps.z(s.ih.i6.da)'+.(.=1 io f i i.'s* i .' .

,k.._ . _ _.l. o t.* /

- , . Y IG 195 Yodo 's I& J2/:1.$ .w,.4 - i 1L c'g t , . v ' p ~A__. 54. : L (c rnprec:lan) , - _- ' De w.,i.- . l(4\\, W)(M) =.f //. f i.. < - / - . I fc i- .- v' ' y . M

J.2 (.gs.%

' e n. z.

18 5 3 +13 41" 2-2-h: 2 G,-Ap.>. G.4E - . Pa 54.2

61 3 +d - k s C-@,o - f.f -f .

'i.s "

.i - _

.. _-

c...- i,, e, SI .g .. . ,, .. -t gao , o: , - _ .. . - /- ~ Z-F- b sf . .f 4 < Z- _f7 ~ ' u_33.3

2:

. -,12,50 ... g33 .- . .. u- .q:s.

mp =s-- (. . , ,. ..L. 3( Q :.65 .. G-m- . l' u - Re x ~.9 _IM C,. -= 1. 3 ~7 'S\\ 4'5DS , '),ST - - - .. ..- - ...... .. -. _ -. _.. -.

. ' .. -... I ,.. . .. d.(. ' ).0.J.%.. Gibbe S Hill, irsc.

rm., g N8k..@.I9, ' - , ENGINEERS. DE$iGNET.S. CONSTisuCTORS l SheetNe..... Of.. CelsBy.... ... ..... New Yomst G & H J ob No... Chk d/Apped. B ...... ....... . ....O...,,, ..,,,,,,,,,,,,,,,,,,,,,,, se.,e.

...................................................... m 4'30 5 M x,T 1-Q. g - ,4754oG

  1. 4_ g7..

4 5-A; - bl Pu.

- _ _ - A.c c Im .s ,2

l'S2 to on 1 y - LSO_ ' -

psr.J-

.1 W 54.2 _ . =..q a m fk 0- ,1 = ._ Len . s37. o 4'0 G-1, , $ _;s. g o m n , y.wci;d, dv ESS 5 '/ Q-3 N oux.

_ . Ck On-u@/ ~ - M ~- o . / -FA<O t

g. - s4.2

. ona.R.

%%t tb 3Li._ (os.e:v.m. -PL } rPL ' o

, [. c, - / ' - M= 54,2 //6.5 9 4. 9.'

< / -f*d M-94.9 + (ll. 9 z.

i n. s '* ' t-M r.

,/ F .97 / / .x .- I'. s - ! 'T.1 ( . ocu A b i - 1=W '  ? '" N'*/ - A q p h As .s. f 55-f rp e L ,'

- = ;,so - t; s . . C . %

. . - - - .. . .. . _ -. _

... - . ~. - - ~ ~. - - - - - - - - - -. - - - - - - -- --- .

_ _...... ut .:.. . ,, .. ,,..?k. 3 8. ~i.4.. e i b b e e n iir. I n o. rm..e.AAR.:!o!.E . . h,% % g, ,,,,, g, ENGINEERS. DESIGNE.S. CONST;.UCTORS Cale By... ....*** _ . v.- G & H Job No.

Chk'd/Apped. Sy.. ..... ...... . Sesbeest...................................................... Rel. Dwg./ Spec. N o....... J............., ... 10 F,b~- c,b. - 1. 2 b L) - 4L4-t = 2, :h + L + \\{ c / l (ht, e? f2% - . . 'C X D - f 6i. - "'- #72.

~ i Fv . f s , -- p V/ ~ h ~{. 1 f,.n / 1E

. L -.. - 9r-511 < s4p - ' . a ~ l. : ', - -.a c. 24 ' w.:.~ a:.;w . ' d sic.4 I f"

.

-l< b .$ - ( 2.4.-2-2 h lit.26 -7-I.Sh 2 0 & ~7.75 I%.676 . ' ~ I g , ( h g : (f.2D4 LM , h.2(2.17s.I's+.$5)~f~i) 11.67'Y .- 19.6 / '

g 01 G

\\ / / ~ r gV g.. n.7xm.57s, aeT.R MFA S 31eIel =3N f - ee

6 tgg '2.o(t 9.8)t20.7+ B B DIGS

n sw b5 ~ 16 sa . l- . I ( 'e Av-. I bi,h b a s ?_il.L / C y .5-51.i (.1) c. % / . z.n.t Ic6 S't?. , /.20.:- / & I,,39

  • ,

2-e ,r>u.:- W - . l'4 ll: /. 'I . . & Il d'- C < d-f - IM ' G 2 - yl - 7.sc*r 48 - 3-Pu e ' = 51 9 i IM qog , 4-F-6 D . 9f./ - s z.co o 5-Eq-R, e ' M 0.1 4 . - g.

, . . ... - - .. -.. _ . -.... - .-

. - _ _ _ _ _ _ _ _ _.. _. _ _..__._..._.._ _ _.

_ _ _ _ _ _ . ,,. _ _ _ _ _. _ '6 i 's s X , .,, D..e...?..b'.0.h.. 'Gibbe B Hill. Inc.

nue. c+.?b?'!9!.?.

3, ~ sn-iu.......onB.4... , cais3,... 2..... 5aciam otsiojt"-l,oa5'amoa5

h.... G & H Job No. 2...W".2.. 2 M.. l Chk*d/ App.d. By

Flet. Dws./Spe's.No...................... Subioet...................................................... ~ G ' Mek Ka {e 4 =.as r K'u U tx.: 1 uk '221 a.e 4,4 l.e q.

- . d% ctu 4.41 x. s 4., 7 4 os ' 7-M.

- , 4 32..

As ' bl 9d_ t ._ _ '20 8 = l-e6-6 5).9 __.42/-K3 8 [c u.- - M2i) n(so) = Gra du-fi

. . gos ' kuvLdxk k = S4'.'M - 80 d.

(

n. a s~., / es.e = . . . . . . . . . . l e - ' . / . . l . . we p-4 . - - - p, geyse em.. =rmee e.we a4 e== # w w-- e-.- -

.

. r ' ok.'.SA U.G.... Gibbs 8 Hill. Inc.

rm.. C.a. M.$.T !.W.@ ' , S &2" Sin.Ns......Of.a d.. _ ENGIN EERS. D ESIGN Ei.S. CONSTLUCTORS Cal. By.... ..... i Nsw Yomst Chk'd/Apprd. By G & H J.b N............. .... u...T.V.S.t... A : S.

%..e.t.p.L.Q.................. o.,. ..,,,......................... ... . _ kasfrciant R.,ss R.ef: xo-2323-Mea t-i Ceds. donc by (T. 8)

Q 64."

This is en col. line 24 ( bel. ween % ' ' G A 4 H A. @ El. Bl o'- G. f I , ' - f~ l.

/ ' . - / - M = 54 2 x (2 e3+i oo) = co e * , Assorne ihe lectcf achhg over = 2' o wrcle sica - ' Assumeeffective span U = D + l + Yr + l o Fects.

- - 14'-o as bepre.

3.

G ' 2 D + ' L +.Yr. / = M = (2'2 Dt L) b /10f ee.,t.L R.

. . _ I [0 = 20*f-hWiA'~ .. 'f ~ G 2(217 x.'15 t os) + 'fo = Totod Mu= toxz + coa = 248 * on 2 o 11 */' L = OSSlt Aussume.

Pu =. 54.2/q.=za.1 E com prescro n.

/ o 1.fc Ag = 1 x4x t2 x 22 = 10s c k-4 = 9 - 27 ilos G( 2) = es / / e = Mu 12 4 _. 4 s e'. s s" W~ 21 t ~ c.' = e.+ d - h/2 = 6 5 + 10 GS8 ' = / Mos = Po e' e.7' t x o s/z = 14l =. l s F= bel 2/,2,ooo . 434 - / Ku = Mus I47/ 4s 4 3 3o4 .= (. F / - MocliEeet Ku for 4 = es x.u = ao4< e/ as = ezz ou= 4 es / Mocil Ted G o = 4.es a esf. 9 = 4 oi ' -."'.' ' -.. = 11-3 i( /fe cc ProvBdt BBB =.I'20 id/l/h '47 / As=

, _.

- - , o 'np... s , - 1 .:i!$..L' ?.9.:.... Gibbs S Hill, Inc.

c.,,,,... t 3;;63 nu.,ca,. M ?~!. W \\ . . .......,,.g.4... inamuns. otsic~tas.co~sraucions ..., Nsw Yoast c. n.. um.... 3. A.. cwn, ... .... ...TV.H.. 4.'. B :. E.1.. B.I.o.'- S............................ ....<s,... u..................... , ,

  • /2

/ v Case c: Pu, :GTI (Tension) d M us = Mu/3-P u ( d / ). . . h/2 - . / G2 - 27'l xio/12 = E 9' 4 = i / Ko B9'4 = ' B1 4 0,0 = 4 4 4 ' - - , 484 / / / 4e +.so = 'so in f f,ce/f t,

, As as4 <ni

. . 4mez sxco . i . e ! -o-l

- . i . .

l t i . l , . di

.

1 -

. . . I . D -.e-eoo.-o o ,.a_ w,, + -. -e ..wma w.oone s.

- _ _ _ _ _ _ - _ _ _ _ _. _ _ _ _ _ _ _. - - - - - - -. . - _ _ _. _ __ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

. _

.o j .. ' . rm.,e J AB,,lo,1,q, g..,9.Lb).G..., _Gibbe S Hill. Inc.

**""$ o ' 5$"'" 5 ""5" "5 3 B 4 um..... 8.4 * * c-........T.. .. Hsw Yostt o.a, .. 7,R 9,s,A,, . m m,,a.

....... _... I.t3.i.. /..R :.. E,t;, @ ! g ',,,G,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, ,- . , . R.esfrcu'nt. Ei, Ra. 4 R.s - support. i ' A. B. Design Ref xo-es2s-M 412 (4+d) - ~. +- ' i.. Fv = 7 o K / Bolt.

- , El. 8to# c T 9 *4 h *'- [ f 77, e g,.o x,/ s olt,. " ' "' '"9 / " ' ' . Use i 2"4 A. B. i l l L 4 Length'c' of A. B. = I - u- , = ' / - ~ lAllowa.ble Tensile Force.

j , > .g . K m u aJ q = t 4 < l G x G e = 45 ed ihrea.cled a.rea.. t4k _ , u s .Tra.per.oiclaj cone.. surface _ '2 bo = 4 cJ. :. i G-2 - 14 > 4(Sc'C'")9 . < e 3-in . ' . A cI.

ti, l o.rg 4(.4d4)(i4) = t e o s

,

Shear Tak.en by conc.

icos = 'EiL o b

is faso x 12G = n 'Ty v.

4. V 4 8 (" Plale, . , bon = 45 * Assornfrig' Terisile Force, on i y . kS' Bearing Pressore en plafe =

34 .. IG -1 5 l . M = (6'l o x q'o /<t) 4: 24'8 L"

l - ' "I., = bel 2 {4. i.g} @ .415in3 , .. , , G G . i / / IC45 N.G. 24'S Go KSL- ).l'GxQ.Qw.SG h.

-.. ms \\ = - - .a 5 " x 5" l'4 Pled * ..TN 8eoen'ng Pr - 4s _ i e i 5 t.

g=(i eu a.s'%.)s= 3o . u - x b, 25 -i.s - / / .. 2,. (5 - l 5) x ( 25'2/g. 92 in3 - l SS (BG ' (N *'M*O'"9 0 "d Djf h*c*h K" [b = kg. = -. - . ..#___,. ...,,f oi,ae. .3 . __ _____-_

.c.a. e,..N./09/76 ',,, R.D~l ??..?. ' ca.: v~... R2 eibba e um. tnc.

- t.dr..... 2..o....... N esm~tas cmiws5 ( ;' ' no.

-.. Nm mn ' . c 6 n 2.s n.?.3. z..,h>. ew s,....e,.3.p3..... s - .. ca,.... S AEEGyft @.4.. %I. b.G.. EL, y.j.o.I.- f !'......,.,. o.u,,,. u....$ 1.~.Q G p.C... ' ... . ' REACTlotjE. AN b fioMDJTS. : 2ilY!U_ >' 1 %* lv.

0) _ urc.

__ ~2, / / 7;< 9, 2r L 9,, S,r i. r ;_, . --y; e - ,

L' 2 0- ./ ~

- -- ' 2,x gy, go 2.

9.2s' /. 2 x (9. 2.5)1 (9.?rf..= /4.-54- , x . f = /r.ro, e __ - / s.ro

, _ . (')e,= @Afs c n)- m.r =-ded ; gr.zr 7,7 c.

M,, p! x. Tr/R x ?.25 x2.4x(4,br)5 I E. ro < (0 25)2-(9 zgf y r IQ cx , ;x . ,,* S.* L II,Io i f, fo ' /f. ro . ,- " e " " '. V g _ % z.

c, . - I t_, . -- 7 +, 3 + ' + + x ( c. 2 t)p-- 2 4 x (n, sz c); =~n > _.

' Ylx + 2 x (9 2 C).- 4e x (4. G: s)*~+ 2 A x(A. c 1 c) x tr. co .-- l [ L 1-z 'M IOH = _l i 3 o. s.,. "-

{' - , ... 3., )g4 t0 i ' o - r ~r.v .x 9z%,?GW, L. g ' '" .. .f . % o ir.,,, (y-4., = 2. 3, 2. S ',; ' '. =(I.)x (3, o rx tr.ro) = 2.3,2e /

R

3 . (3,o or Air.so) x if. To : G o.16. ' E < M, = 6 c.16*j I*'Mg =( j , . I t. 4 4r. 7 55, 1.- 7 P. 5 Pg =K,7+ ? ?>. 2-9 = h7s < ; R., = 43,_3 3 e 2.s.23 = 74--te k ; , Ik $ H : Ht 41 + Go.16 =' I7G. S ' kj M c= Gh'l2 1'CD.lb= & 7 o l 74 21 13foo*5-i3o.s I90 4 'A . ];g f4: 2.. 2.. v., C 'i rA t s i I 6,o . /5 kg,,= 2. 3 9 f C, =(l'z) x(2.7.s'o xG.o) = A'. 3 4 . ' C ex e,. (g y (>.noxc.o) a.o = e.n, 3.. R., - c. u - 5 , IP03 W-5f C 500

' L a -. . .. .....

' ca. c,.TP.6......... i~~"5 =~"5 co~5="5 s[ ' '/ ( eon u.. W M..' - si..a ..... oi.......,

,,, v cw w. W.5..... . .,.....St.A 65..+. bas. f. EL.s ! d. @j "....gg. g.....'.... n... o.

s-.. 51 @R 6......... l (- . - ' " - ', . sq;::: p3.g. i p-2 +riise g:i:iuniti!:ililii .ly ' 4r. - --.. -. --l _ g.7.nTr: iF 6 t.c J .. g . iiii ij = yf; .

p-a g ;

. - t - . a : w.. i . v..... ' ' ,.'. -m.9 :"

- g.-inw --- .... - , r..,, e . {lt' .. c_i .

._.c q- -......

1,4 . Qy.{ nW c. i..q.h .

.,

. - j l

. .... n . , i ... . .,t.. .. ._ .

  • "

.

  1. ~

{ .. F j di l a,, .c :. ' f.. l

3 s

, , , .. I .' :..' i I$ dgl q[5

b ,' ' l -

t- .t.

r - , - yqpg.,_ph, l.,. ,,, c .-- !- i: ' , ,,., _ .. [s'.

.-:. , . N _ ,,g " wg.

_ _ _ _. __ - -.

i- .i

:

i,l' ~ ' - ' I #

)syg.r L3 I a p' i.

l

'~il I.l; l (M- . VIi ,

ll i 4..,=,f;;rj .l l, U l e ' -

. v., -. . ,

- -.. :l i .- .je g._ . _ _ ~ - .. .i ' .f._. -h i'. '. ' ] '- .... r

r

rh r - llb j \\ D i=~=~'

.;."c

.. < , r'1 !1 igt - ' "d I ~~ "

. [ l h '"' ' J l L.r'

r i L.

J ', ', i t -.8 .., . ....! g.; - ' f

  • =-+ - p-

_ _ _' _ ' ' '

. .,

.g , L , , ,.i -

i.,..

.m , .. , i .- . . . , p.. s .e i i .

i, . . . - o , -i . i.

%rq s , O t t

\\ . , , 3 g-j' j I, l 4$I 8;

j \\.\\ . 4 J !l' ! ( i I

l d I.

f ..I.i.l . ' ' 0., . I

. '. = a ! 3 g \\.<

3 .l.

, , , i .- i .q'. . s l \\'e~ " i i ni O, ' 1, fi.l f - .N ' ' i ' " - ' ' ' , . r t u i s.

. m - j[q' . . - Ipi ,c a~m , n. %.- ;,. , ., :m: .

.

r T ; '- 3-w].a.. I,jY$ i'" ~ g/r g .g~ 1 y .

, ' i s,/. . . . , M Y .I df). [- . g -$( j, ~~ g/ " "I ' P~ i. 3

n,

' ds_w ' g ,,/Mp9 ,. s i i u i, !..a i , ,...

x

- // - g s p,, - -

.,

- N ), !.;. (il i, 'n.

[d li o I". . < . y /--.,=.,w,_.

u.

< 3 '.. -- .: - . , , . --

.-

.. . , j.s,w ll . , /\\ l a.

. . , .@, . c.

' g ]- isE,..ti.

/ % 5- - s _.- , , - N ,.. , , - .. " [1I,N \\.s

I.

"i ' - W,),,.;. e.

!.J.......g t.

k:. g.n:p .!:. , ... - ~ . g..; p. . . s.

..... , , l . . ...,.,.,g, , .- ,-.,. _ - .. .. . ' s.f..<,,...se.

_ k r a.,

- .. . \\ , 18l

, , . m , . v.l :l wl '~e - -. ... . . . \\ ..A w' r - e.

. . - wi . .

o

a

l

. ' l.

/ 4- '. \\ . ' . , i i !: ce -- = =R u / ,. l.

. . ,L ),L.:...,

t

, . ., .. s.

j - - - - > .

n f 2,, 4'3 g , .. . i . >$ ' . . . \\ .. ai J ! l e e %p . ag ,/ ' p-. ,:h,- ! u, ' - *. - - i Qt et.

! ! A ! . A.--. <j.-

.i

J.

.y .

y -
y;;3m.a.g

.. , , , . , . ,,. -. . ..

- . . . , . --_----_-.____,,___..__m __ _, _ _ _. _ _ _ _, _ _ _, _, _ _, _

~ - - - __ _ f'e cm c,....M r- '...[ [ g r, / N W YOpu h" C & H J tb Ns. h.).... ( , cwd/Appes er L e iX./.e

5.1.RbQE..... s..i.....%s b.. Re:mf..J...L1$....El...t ).9.'...'.'.... m.

o...es,... m... .,, ' ', (C ' . - .. . , , . M - I '- lo " ( L-,,. e s h -Q

  • = PO M l b fo *

Pa d h b l'-'~ 'O y ICCdCd), 'i..* E, 4 = Efc Dcpih 40" / g[ EL- $ o(' - 4 " Ge.tm.

_ H E RT E Y tRRwoE AREA . . W D.L.

- Se.lf wt. o9 C.ow:.de. +- Finnh =..',30p i i

_:. - H. Pip i ng -=.. cHTo ' . _ _ _. - - - . - V' !! S] / /

/

l' x 3,' y$ X. IT = W/kog w;Qt-h , t ",1 k>oJ1 ust.: ' f l-* $. - - - - EoO fff % '. D' ' * . - -- 4h

- 'oadAIc buooov

O

'~ D EQ. L.

h t Dou.m H T. Ex. : // ( cw.* n,, e, JL eto.*vp.

R nos x-o"x o ' '" ~ i - Ftnf.e.<L Q)T = 2 <., ' l [ j

,., l.

p .: H.427*%(?.et1Yfto/q. ' 153 " ). ,

. k.

._ w & w f W}O ~ g - g M*% ,s..jM/ l - e t, N: to'-3 * f_ ~ v' [l W H n

bh - y' , CQnovt.

' t . >t lis'-fe'8(m >, b.I R,,.ud ) ( @*-> --.C it _'C3.

v

C \\ / . + re <

. l C.

' i

Cont.

  • , -

D f Q, b' [ .. t'. .....

" pJ h v4 .-p .. ., '- . ,

.

  • .

e __ g. % . .s' - .j; ' .

__ ._ - - _... -. -... . ...

.... . .. .... -- _ . t. .._. _ ...s.____._.L-_ _ .. .-.....;.. . ,_.

, _. _ _.. _ .- _., _ _ . _,. -. _,

Z 2 g; sn..i n.. 9... or. : ?. I " cue ur...fi """' " " # -" " "'s R 'a ' " w "85 . .sg.. ,u. n . . C & H Jab tia, b / '# chk'd/Appr!. By. ,- e . , , , G.

'....%.Isda...hw6,...E.t...% o.'..GJ :.. 3.4. m. o... -. a.. 5. /c.Q.6.0K... l - U . kh ' v'. . t o" / . M o t. - mo wit . 35 xQ.b.C) x - W x-er/fr . '

t 'a IW. ' ' m m,., m o _s.b__.= 2 a.5'yC -. 3.4 ft/fr w t ^- (p.c)' t/ / md,t,-ns.: om.b' F x t 2k x co.2ef /2.co re-Ag

ts.

p.s p y- .' J / M u.

= M':WI1 =

L xCho 5)z 4.s s x-w/g

- = l 3.

JL

V . . . . . . /V)v = 3 Cut.)'+ ~3 (.w/.t. ) t. 3 (._se.t.). + / 7 ( g ,0 -./ v / w.

/ /' F C,VrT) e 3 LM0 f- $ Cf a..co) + /q (4 5 s-) -

/ tl s. ' . A3,8 7 + 10.16 + 3 G.co 4, 7,7 9 J,, h h =

v.h

=. yg & 97 g p+ G ',.) ^ . . , -11 * f;f'e i f h p.i,.C' ? ( b = IA ", d M y 'E " / f " y- .y E' g ' n

. l, l bd hg :. 9 2.

7.

- . - - -- N /,- p o . , Kv.Thu[(: : W ' 9a : JW /. g.4 ,, h," p y0 ,\\Q ' - f: 6> l f

l - $st: 8bd: Loo 3 F) (l 1.).(2o.C} =. 8 6 ih . V y v - 03e * T e io % c.u ce) -+ f o. v o.s., ve 9[yr - - W y Y$ $ l / G' O f . .C . s.,y au,4-3 m:.e m. IT V **'***- c:ii .( F T.t c. u

. p-- - __ . _..

. ......v...==_.._... - - - - - - - -- _ _ -. _. .. . . . _.. _ .. . . . .. _ _ _ _ _ _ _ _. _, , _. _,,. _. _ _ _ _

co. e,..M.d e.... mtdotmas castactoas .l....or.,,.,

- no, . ,_ m - .c..m..4.a,d.D.... ./ c a n 2.. n.. M M8.

. -( s,..... SEGSUh@b,9, $$f,,,,,E.L :,8,1,Q,', @,",,,,,,,,,,,,, o...,3,.., u..,,5J.,g 5, p 5,,,,, ' l.) CHECK stab titJbER TRANSVERSAl. WALL.

2.) CHECX GLAB t/NDER PIER OF D.N. C; LelDNn H '/, O.

29' 3" - ,_ ' _ 4-- Auans 2'-o.5Ca.' Su fwol 1.,g r

n c-s eMc ed o-s64 as

.si.,p.(v n4uj.::;r.' l'sd lac a, aam,g &CCpek(Qb r.:.Jcp,r '.. f'" t,,,j g , ,,,, s _ _ s .., s? TT _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _. _ _ _, ' ' ' ~ P.l # 5 L A s + 2" fit]!:ll', ' ' l .- -g-~~--------------- -

'E ' ~ 5 L A S'- LL =. -0.209 %IF * / y i1 l - - ' i i : si v.. ._ - <>a a

l 'j +N

I W4LL WEi(~Ti' : 8.33 CV t E'? " d !,^ Fh . _ h- -

J.0,! ' t.

' 'wh . c %4 L i - a.'_4,3t43

t j. '/ IhL.-y 'i'J I

. , ' ' W V ' ' ~G ,fL $'.- 'h b .I d - l l

r l; _L@[sM

' ' }Qh.$. ,.- . ,.. . 12Ls2- , _ - . l.) CIlFCM LLAS UIVDER TPAC'EF. CAL MALL.

GLAS bL,(~) (Wp f 2 o*) f'# 'N' - c o' L . ,u , s.,_s - .. , W '. '~ * 5x(0.tsex 2xz.oc3 w.:7sx2)= 2. tzs %f T ' 3.%

  • i i"T =.e.t..'.,"s e

\\ u.= c.&so n,. ,l 1 a! ' t>L =7.717 at:r'

.

3 S LJ. S b L (s.) @ tn g cl-2 '- o *) l SLA6 bLt = 2. M n '+1 ' W. n 2 : :'.I .s i

3 * * S ~lH

    • m "lR '

LTS'h' 5x(0 ik2xI.e254 c.c15 x2) e 2.1oo& - m

i f 4.so s n' WALL bL (,)

, &jyyg/ 3x{p.tTox1>E.?M C.orox2.o)= 7 7.:7f ' / h C - am,,, et(,) ,,; ,. s w - - <.. w - . ._ - - - I J oa .- _ -- _ _.. h_o __ y' lo~lX{c.2 ec x '2.) :- r t'.CO,. y3 I/ ,,.. < .

  • 5:n /

6 o ',

. _,,. < . _. _.... _ _ _ _. . _ _ . , ,

~ ~ ~ c.,,.<.y..... t,.4 P.4.... '-f/ ') l c a2i a.. 0 7.3.6.

. p.

h,. ME.E.Ri&r%S..BkbS.

E.L :R!.o.'..4.d........... u. a.w, n. n,.. k)...o.G.9 5~...

... _ v 2.) CH ECK SLAS ONbER PIER OF b: u. vP,.L(ih Ric [a45u u.

2.'-o " U^t f W, ' e , (Su Josen CAT com h.s 593&-2.) pien. ij _

x , f4,4,. Pz WAu. = 0.Isox2.0 u.33 = s.c, = . \\f 'l .. l LL :- f.o. A " > 'l* *

' ' l 5.L4 o bt l = 2 MS VC u, s.' ' = <. 6.- /. ii o

<

L q^.; s' - (, (f' j & jaV' y ' - t 4.75' _3754 _ 7. o ' _ .tp s , < L .o m .-

~- , L f "A ts.so'- s.o ' < h a >e

-

~ . 21. SO 's _ lb,0 g.o%- / , V 3,0 C% ' h 2.T2 % " L .O R 'e L . y .. 3.0 css Ir.5+ /6.+r 0.75(3xA.7:+I2 7Y) + 5.0>-7.0*x (~~x8.5 4-1.0 ) IiL ? - - - - - - - = 3 a.15 y g. = 2-ts.s 3 t5.53 " (t) ?o_ 3.co. vsr.r + If.4 x - 7 shard 7:4 ?xtc.75) f 3.o x 8.5 x (2.5+ A.

f -

Is.51 ,.. ' Is.g > .- I')H =It ' Locnett'?+ 15.4 f.75"210.152- -f S.o > N r / te-95 ' E W. be - -- - - - - - - - =Qf.

II) g l2.oo U.rit.[g,,9 ,p, 9,, f,, _ _ _ _, _ _ _ _ _ _ g g 7,

rf f.7r 2 y,3,7 p g ,g y it Jr.rb e r.T L top'o=278k(.o = V. 3 4. / * U.) R.. n 2. \\ + k. /* = > L N gj.m'n.A c.w'"j ; f(:- P,3 + '\\; to

12.

, ,. R., = 29. 85 + s.t + = 5 e,17 N[g-) . C- - (.wi.@ i? + W ) +. I o r,. -, o l <Lo, 58 ' " D ESt M

z-r _!g._ i;d**, If, = B-7.-24 + f, 3 9 = -O r, fo

Mp,= B,34

~ 7g,jo sw ao 5 . - - - - -- g __ _ -_ _.. _.. _,.. .- . -... .. - - .. . . _- _ _ _.

_ _ .

c.u.....#..k.

.i rh~4ss== r .... 4... ........ New vait-( . ... . ' " * C & H Js,b No.

.... .. che.4/A,ere, nr..

'.C .........s&Ee.wMAs..eux.. M.. mo.. 6."..............,........ s1.- e.4.ox... .... - ' , C . Whi %. -)- 3 0 oS'/.[y_ _ ll t.qsa etu.lg , O - 'ML go R. V - _ tr.5o I_ 6.o ' _ ~ ' i ' , _,, - Y& 4 ns"- w.; z, O s -,, < s.n. I

t / r=24x2.7* /T.= I 27 I 292.s* )=1.ro7p4' fI ' .7f/ - 12.

s it* l1 ,.p , U 'Y %' l5o7 \\pn h Q Xg = IL ?o .--.-0nlL v c 0. 097L.

Xg& " (jr % G.o %b^. rI n I

o.u.fic.atsP l

~ b. r,

. %' r.s.t.s.

+L ~ # :2 l +e.9-e.s' - .%- +1?2 +l?M~<0 O o0 C w / m o., c.o , n,o g,, - - i _ A-% 5'* bEW n w. wor -%i ++Hi-M4 - - 12t.stl2 fig "' ti l ' * tyg ie- . ! R.EtOToRct:MOJT:(-@t a 44.- ei'p 2 o" tvM.) ; el x. 2cs ' ~' '

i su ass F = 2.qx 2E[l 2.ooo =l. e 6 3 K.g : 8+'A 5 /l.c 6. L49 417 T./3 4'0c 5 8813.

, j u -

O A-s = o.conx 2-9 <2 s f. ez.s3r!.
]USE. 4* 8 SAP.S,

,'t . VPL f8QQW -

. c!!ECK SHEAR ' . - 1t.s 1.s i l'; %y1 = %h&21 e. SA-) - (3.0 = T +'l +n ),'t / 25 = G l 4 ^z 5 ~ L es.g * -

v _.. .. _ _., A X 2.5 ) = a}3-f y'Q O I 2.S ' L. b ' (tf.- - (do S' s, w < U SE MEll R. Tl'ES : 4 f2 bn

l m . <. '1 "j ] 173 -12.6,)>; A 4 = sd,.: [ USj.6 lY /) . L.

_ .. . .. . ... .. ... . _,.,___.._ _ . -. -., _ _,.. _ _ _ _. _ _ _ __ _,.._, _..__.._ _ __.. _._ _ __,,. _ _.._,_... _ _,_. - -

co.e.....,.g,g,... m. sus 2a.u..a =sb o m s,. ,u....9..ci..... . . g),- ' " "* "*,3 33 4 .... ,,, _ . .- ca.w,.....n,JPk..... ' -- . ......E. w....A..P b.5.. 5..l. b..C,.... 212. 10 '.4."............. o...n,..u..N.I.~.M.P.5..... '=

W r~,.. - ,.,,,.., .. . .. - i.%- L iw.. RElldFoRCEMalT : (Mip 4*- [-o" f 'h g[ = % g / t

i c-( :: 2 3 " ; ^ . p = l2r 2.9/2oco' = 0,529 / i V,,= $/C~S29 = Y< l75 ;l TPJ/ r> : o coa 5 -+ A s = o,og 3: >< 12. x z3.:- 0,9 / gA ; ' ' . ( h.a (*2 9. ti'b '-

q;.L.,?jp " . y g,g * g g, s 't ;$ zr #

- -- un p,qbo,.., Y M \\s)y {($. ' (f'. h ,Y G

e ~ $ '~ ' . y\\'Q.: " ' e y_ r CHECK PjER :. ( b. htq. s Gc a b.2,J m A o.a./ 6 tp.) * . C km = 2 s' 5 cci'cacra ne^ 1.sa k x 2 s#4%,, tccu x..,, a,a),. ^ " ' ~ i s .t (*) vsR.ricAs. (seiu. sic) ReAc1iora % = IG. 43 *-', s , . (4) bor.it.o,JTa (.se/utic ).s;;eA,1 = ig.e4. K ; / H = !s sq.x 2.s = 47. i 'k 4 ^ }l8'7' io..r) 2.

  • EI.= (57006\\inooo*)n 19+l.Loca M(2 s x I.s3/I2.)

. 7 2. ' 9 K x ft,. , =I s.

m . P -- = ro,22A V b "O j p,J ll@. %sjw

c (2 x 2.sjz i' i \\h ( [ =.,j, 1 3. __ ocaso zza j F IG 4-3 T = d.o / L - q%J,(.y%'jub,./ . > .- # '

d I Me = 1.o x +7 3 " 4 i cle 14"3 f= 3oxiM/2.oco= c,4 OI K 4-7.1/o. 9 = 96j/ , useg.=0.o1

r,= o.ot x i+x 2a =.g.1,% i;, A.2 z = 2.1 a. s

=' 3 BAW 8 yog (Hitlimit ] y s.,e 4 M U h. % Y use 2.1 a.n.

) ons

.-.a ;+

, ' _. _ _..... _. _ _... ._ _ . _ _ _.. _.. _ -.. . .


a~---

- - . - -,, . _. ._ ._ _.

, _. _.,.. _. __ _ _, ,

on.04'R f./Xfe... Gibbe e Hist. snc.

. r,,.. =. r..~. k.-.. ; - - _ - _ . i . . 9... 7..... 21 /b . cme,.8.:Ms..... <" ~ua5 o*5aas a~5= mas N:w Y1 met J ,j . . C 4 H J.b Ns.

. . ..

. Chi d/Apped. 5y ...... , f- - .....To,s.l.sof.E.QUS,R$:@f,{,,8!9f,G,* :,..,C4.M, S.MB.,,,,, o... ,... u.,.h-o.691........... L , - UNbER. BoROM lal3 ECTioM TAMK 2 BORod INIEC. Tion RECIRCULAioN PUMP.

O g O ' h ' T w . 1t i.- al - g _ --S 2'Q' _ g,' 13'-o" "' e,{n , " = = , - , ,,,,, . y '" ,

.

  • %

l % . - .--- e - % . , @ ' Jt' - g .- - -- ,,.ka U.- _ r . 2'-l', S L A S v E'-l SLAE f , . . ~ 8FAs' e- - - ,, ,3.., _,.a l .

-- . i,, I

  • $

Q.L ' g '. ' f . .' +.. l ~Q.,, -. 9-

A, t '

I i f s t ystRV - t. ~a / I L__.

!c. \\

ve

. _ _.i.i g.-

'

4w l !' . !I 2'-2's S R ",' Q - %.. Q, m -- / , lL. _m B.j. y i

- , ' . _ _ _. - - -- __ _ _ _ _ _ _..____ _ _ , Q , , , _ . ia__ ~ _ - -. _ -. - _._ %, g l ! b I I l WT - air (sesjufsiwg sin (w kjecth, RuiwM% Pnp)' ' , I PAR.T. PLAN EL. 8 lo'-6" - i , 404 BCPJM IM.TECTiced TAN 8'. ! - LOAD (ese e 4 2.r '%d M * - @ bli(SLAB)nr 3 x (0.ISox 2. 5 t 2.08% + o,07.5~72.5) ' / = 2. 9 I .i bL2 3 x (0.lCox 0,80i x2.o x i G 7 ) = l. 2 l

/

,. M/g.; ' Q LL = l.7x (0.200 x 2.s) 0.EC = X/ ts<. W A.,/s k $YA & W'

  • zc4h K 4 or,/'a,yj7g d 22,

. , b

  • SS9 l

I ) b ne n.c ss.4 < p.185

I.ll , , [ o. f r N/t* I, - lh, A E 7.c I * n* L - _ A.oq r.78 l-A r.zs' l . . i+.. T ' ~l s c. c,, e4 A-A - ~ . r- ...____ _ _ _ _ _ _ _ _ _ _ _ _ _

'o .kl.M.l2 9..... Gibba S Mill. Ing j j),Qf rm..e.,%.%..l.q(A ' ' ,,,,,, j,,,,,,, 4,, . ', 'c.i..,.JP5......... Eac'~uams.c~ cas. w~ s== New Yomu c a us.... M M..$.. cww.s..r. .-

. 7.W)..G.G.. %4 9.... S.9 A. P.E.dM.. h. @. ' 9.'..t."....... o...e .. u.. 5 J.W.G.o K........ SLAS BETu)EEA1 5-5 4-5 $ Gs,D-5

. f SECAJsE~. OF SLock. OUTS t h! W/\\ LL off LINE c.s, THE SLA B S PAM S IM 7 d e LOM 6 E ST D I RECT tDA!. ' i'

__j M

- Q e '- . . &.h _' '

_ . _ _ __ ll . , f / ~ // / / / // /.' ! / / / ' ' /i/i i i /i'l /f h - , . . Y & ' ' EFFCcnVE l-lf,/ ,/ N/ uu sbru ~ , ' / ' ' , I .b / J l ' ! i { h , I ' . .. - 4. _ . . PLAAl 6 EL. SiO'-G " 2'-l"sLAs h ' ~ ' - . t 2." F ius s H . EFFECTIVE WebT4 . , ' 2s " - (i.5 + 1 + 1+.s ) = 2r " d, = l {' EFT; wioTH *- 2. t' t 2.4 * t 16' + 3 0 ' + 2. I '.' = ll4

  • 1,5 '

/ ' 3 ( z.o )(s.33 )(.,is ) - 7,417 k/s

il J w Att.

vt - . L8I i S 8 lac 4 PIER.

Lo AD 19 0014.

(_REF. 5.5 B-Il2.C 6HEET l/G4 tomur,4) - PIE R. LOAD 1S SMALL C o MPA 9 f O To u/A LL Lo tr) .. R E DllC.E E FFEC.T I t/E WiTO TN To Ac.< o ^'7. 7: o R- ' WAt.L~ o a t.y. . 55[' (-(- EFF. td'DTt+ = 21 + 2.4 + 2 i = G G = . . Y .

. _ __

..Ct.1... N IN S. 0E SWRS. CONSTRUCTORS // f sheet N;,... peleSr. 4......... NKw YXCY:. J ' , e f e a u.h um. S.'..5. 4.. . Chh.d/Apped. By...v0.s.

i

, .t.TV.t.t. 5:h.MLA :. 5.'.%..?.cHW...W...,lg 8 - p,,,,,,,,,,,,y ,,,,, ;s! 7,g,0 g,5 ,, E ' , ,,,,,,,,,

..

, ( ' R educ.s toAos To unit widr H OF .5 L A 6 va nt.t.

Ot= 7.497 f.353 r. f.g t -

'~ S t.A P2 Dt. : 3 (,328) * Iillo4 lt / fi l'

tt :. i.7 (, zoo) : o.340 E. / (+/ ] - tl. ?hd f ' 1.45 * 3 45 ~ ' / e, y n.

, '/ y y, 2 8 67 '/' . f CD ' s.or - '@ . / . i.

. / ' 17 48' / ' = ' - " ts.,s. ,, ., (2,867 X28.7c) + h.45)(L7.4$).[l.7-7 $3(D 48 . R=i tze.7s. , ' + (74s#5a )_ (23,e9,- 3(3;oo,)) = 44is u.

(.ts.7s )5 3'MUI 27[ [17 48 4 3(ii.t7)] . R =..g(e;e67)(2.sas)

4-(28.75) - . . +-?> ash >69) 6 oG +- 3(2.=,,6 9)[ t 48,% K ~ C . (1s.7 s f - - . . . e4 = @7 )(2.8 75P' y (7 45)6l.2.#17.4if .(7.4r)(23 6f)(5.c67, g* g i

(Z fr.75)' (E8 75*)a 12- - , C S C.1(,d18.~l5I.[ (7,4 5)'t1.17?67 4C) 4'[3.45)d3.f ## oD 2.16.60 k 4 82-(1%.7 s> ' (2.8 75)*-

- . . ..,,. ' - - . - e..gg.% '.241[f$l,,;.;l '. ~ ' vt C -@ - . - +. - - ... . --r0 , . - <. _ _ ~ .

. . . .... - - - -... . -. -... -. . ._ ..

.' kl.uh.4..... e i b b., e n ir1. 1 n =. i 5 f< ti.

ru t.ts@.:tofg.ch - ' ' . . - f .,,... 3...

. c.i.....dC.. d...b... i~m~u:uum~ u s. w~ ~u==s ' .... . / New Yostu e = - ..... W... .. m,...2.3.2.4.4.. . ... Ej. M..M.j?..1WW. P.W.W.. E.Ho.'- G.'.'....... , . .s.. op.q;......... .. ' F; (12 )(2 ; ) * ,44 f - ,,, , , , 12,000 2lt'&O 496 ()=.,olo'7 ' - Xg.:-

.

A4I A 2 70 M /p+ s t A<s -

_ vse 2. Layen &Es 0" 4.3=.3.'6 M - _ 3. I lo . ,012 5 4.0142.

[=(,!2.%2I) 6eoo . . . cdem s u e n e.

- . Edaw d+LLS bis r ai av TC toad ro - (ftEi: ! LA-Lo t4 bE 'S CoMC. Eh' sit. M4@BK )

. ' - RE PR.EhE MT Lc 4D 84 CEdTE R OF St.A-O - - // / / / / / / / ///) . . .e n-yL =o.sp t,, ws g g . . /- .. , L= 2.5.75' ' . , , G2c 9 % r.. ]. -l.504 x 2.9.95 x I4.s = Sums 1p tla L = ~1. 49 1x 2.&ns = 2.ss.c4k. V. WA L.L De c . To *r = 842.s2.w ' ' Lo A 0 cA a.e E3 si sp AtJ L. =. (,ly )(&42.5t) : 152.k./ g Lo A o b A P Rico 64 SP ArJ L = (,.62/ss.5z.)

(oi l i<- i e----- w i t<

=

. d

i ' ( . ' ' C 7h g 75 L - I - 4s

. q . i . ,. _,. -. .- _ .-_ - . _.... _ _ _ _ _ _, _ _.

.. . r <a..(c.f.1. 5.l.7.G.... Gibb.n 8 Hill. Inc, j gOf~ rulc$b.7.lRhF.

' -.,. 4..... 4... ".i. c,.JR E......... nac'au as. oisic~us. c= muc=s ' ' .- c , . Peew Yons 0 & H Job No.

.....1 chk d/Apped. Br.. .,T..

.,... T.u.M. 5:9.. %.M..2%!k..h D.I.%!.. k R c.':.4.".... ~. ..is.

.....S.I.-R6 0 K........ .. \\/* O'

. 24 k.

2 t. - g. 3 k.

- 1S.76 ) 14 5 / . - Gss ttoJs O / . 2. 4 . I t2_ Ic s ; 4,12.6 le-s r 6oob 4: m.

G sliL11.t ') ' ~ . . A4 (A> A L L Ato^Jcr s - s.

Cl+ec K B
EAw *criou o vs e._

. (3 '- l o uoa Q TCMPo R. A M Q P E'M IM Cr-n . ' -4, - . . q . > 7c . -.. ' 3'~ t o* h'/p u M C v'Al 4-LO4 0

  • ACTS

- , 0*""""" O; ~ ' ~ , . . .. - . . . . . .4 , . - . 44.e Oi , .] o,. , . m .

S.E 3' , - , -

M8 s.

' (= 20(L f ? : . T12- - I L,00 0 Ng: M :. gt/A f~::.003 3 / ~ , ,% 2-T4 t {A = 3.% 7J)' O' A =. 1.9 7,L 2-O s is E-- e t- . -

3 V:. 8 4 6 v.- / ' . . , Q %: PG .u1 4 les; >.I2 6 n s; ost

  • 4. t o e.

A v. 4 0 * ' = C5s%zzi)2.i 3 C. 4o)C6 o ) s - =. u1 vsc

  1. 4-e I2, O s. = (.176,126)C2 7 )

. 6 }}