I" hSSE TEXAS UTILITIES GENERATING CO.
REVIS!
PAGE N
CPSES QI-QP-ll.0-7 0
7-12-78 1 of 6
[.
M L //- 7g STRUCTURAL STEEL ERECTION PREPARED BY:
h AND BOLTED CONNECTION
/'
DATE INSPECTION 7!//!7S APPROVEDBY:d hV U
!$ ATE
1.0 REFERENCES
1-A Specification 2323-SS-16B, " Structural Steel - Category I" l-B Specification 2323-SS-9, " Concrete" 1-C Construction Procedure 35-1195-CEI-21, " Requisitioning Safety Related Miscellaneous Steel Items for Heat Traceability Pur-poses"
(*,' 9. k;'k 2.0 CENERAL
/7 Ni}h A*.
hj 2.1 PURPOSE AND SCQPE r., 'y,
% K'h To outline th
,ods "e M by QC Inspectors for verification that structural ' isl is ected and bolted in acc c
with Reference 1- ' l}
3.0 INSTRUCTION 3.1 INSPECTION REQUIR 3.1.1 Base Plates and Bearing Plates Acceptance criteria for the setting of base and bearing plates:
a.
Base and bearing plates set to proper grade, leveled, supported and aligned.
b.
Wedges and shims cut off flush with plates.
c.
Entire undersurface of all plates grounted in accordance with Reference 1-B.
e.q? ' S, 1
}
U t UI' B512O20327 851106 PDR FOIA GARDE 8 5-59 PDR TUCCO QA
[
i I"
8 TEXAS UTILITIES GENERATING CO.
REVISION PAGE N
O CPSES i D
, QI-QP-11. 0-7 0
7-12-78 2 of 6
(
3.1.2 Structural Framing Acceptance criteria for structural framing items:
a.
Framing shall be properly aligned, leveled and plumb prior to any field connections.
b.
Members in completed frames true-to-line and free from bends, twists and open joints.
c.
All joint surfaces including those adjacent to bolt heads, nuts or washers free of scale except tight mill scale.
3.1.3 Bolt Holes Acceptance criteria for bolt holes:
Holes cut, drilled or punched at right angles to surf ace a.
of the' metal.
b.
Holes not enlarged by burning.
Holes cleanly cut without torn or ragged edges.
c.
d.
Outside burrs ground smooth.
3.1.4 Bolts Acceptance criteria for bolts:
a.
Bolts are 7/8" diameter (unless otherwise noted),
b.
Bolts rest squarely against metal or washer unless bevel p
washer is utilized.
c.
Bolts are A-325 or A-490 (unless otherwise noted on Engineer-ing drawings).
d.
Bolts flush with or project past face of nut when completely installed.
O
' v TUGco QA l
l
TEXAS UTILITIES GENERATING CO.
I"f REVISION PAGE
/~'N CPSES
\\~-
QI-QP-i l. 0-7 0
7-12-78 3 of 6 3.2 METHODS OF T,IGHTENING BOLTS The QC Inspector shall verify one of the two acceptable methods for tightening bolts.
3.2.1 Turn-Of-Nut Method a.
Bolts are brought to a snug tight condition.
b.
Parts of the joint are brought into good contact with each other.
c.
Final nut rotation is in accordance with Table in Figure 1.
d.
Bolts may be reused only with approval of the Engineer.
When required nut rotation has been attained, end of bolt e.
marked with Nissen marker.
f.
Inspect a minimum of 10% of the bolts, but not less than eg two bolts in each connection, selected at random.
3.2.2 Calibrated Wrench Method If this method is used, the wrenches will be set according a.
to a table provided by the Civil QC Supervisor.
b.
Wrenches calibrated once each working day for each bolt diameter being installed.
Recalibrate wrenches if significant change is noted in c.
surface condition of bolts, nuts or washers.
d.
" Touch-up" previously tightened bolts which may have been loosened by tightening subsequent bolts.
e.
Inspect a minimum of 10% of the bolts, but not less than two bolts in each connection, selected at random.
3.3 GALVANIZING The QC Inspector shall verify that galvanizing is not used for
~
structural steel installed in the containment, or encased in concrete without Engineering approval.
v TUGC0 QA l
... -, ~. -,.
3-
f I"b I
f4 b
TEXAS UTILITIES GENERATING CO.
REVISION PAGE
'8 CPSES
[d QI-QP-11. 0-7 0
7-12-78 4 of 6 3.4 IIEAT TRACEABILITY Verify that heat traceability is maintained in accordance with Reference 1-C.
3.5 DOCUMENTATION The QC Inspector shall verify on the Inspection Report (Figure 2) that requirements of this instruction have been met and submit it to the QC Documentation Supervisor.
(~.
LJ o
I
[)
i v
l
)
-- TUGC0 QA 1
I
i a
INS Im ff8 TEXAS UTILITIES GENERATING CO.
REVISION PAGE
/
CPSES 1
(
/
lI-QP-11.0-7 0
7-12-78 5 of 6 FIGURE 1 Ficure 1 a
NUT ROTATI0?i FR0" SNUG TIGHT CONDITION l
Disposition of Outer Faces of Bolted Parts One face normal to E:lt length bolt axis and other Both faces sicped (as measured frcr face sloped not not more than 1:20 underside of head Both faces more than 1:20 from normal to to extreme end of normal to (bevel washers not bolt axis (bevel point) bolt axis used) washers not used)
I
~'
a to and includ-ing 4 diareters 1/3 turn 1/2 turn 2/3 turn
- .tr 4 ciameters but not exceed-ing 8 dianeters 1/2 turn 2/3 turn 5/6 turn.
Over 8 dianeters Out r:t exceed b
- ng 12 dianeters 2/3 turn 5/6 turn 1 turn
' ut rotation is relative to bolt, regardless of the element (nut or bolt) being turned.
For bolts igstalled by 1/2 turn and less, the tolerance should be plus or minus 30 ; for bolts igstalled by 2/3 turn and more, the tolerance should be plus or minus 45 biio research woric has been performed by the Council to establish the turn-of-nut procedure when bolt lengths exceed 12 diameters. Therefore, tqe required rotation cust be detemined by actual tests in a suitable
{
')
ension device simulating the actual conditions.
' ~;
TUGCO QA
\\
1
INSTRUCTION ISSUE TEXAS UTILITIES GENERATING C0s REVISICtd PAGE NtfGER DATE CPSES
~.s
( ))
QI-QP-i l. 0-7 0
7-12-78 6 of 6 FIGURE 2 COMANCHE Max STEAM ELECTRIC S T ATION s-tre c.
INSPEC TION REPORT I%
l
. r t. C i o.p f cg
= T.4 ge ws a.0
- r&IEhe / 5tagrw s OtiiGhafoe a
?
4 W?%
.4
(.
Os g
C i4 e45*tC T 3 af tfl04 5
T@e g
... u <,.