Insp Rept 50-261/86-03 on 860201-03.No Violation or Deviation Noted.Major Areas Inspected:Loss of Offsite Power Witnessing
ML14175B359
Person / Time
Site: Robinson 
Issue date: 02/28/1986
From: Jape F, Vandyne K
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML14175B358 List:
References
50-261-86-03, 50-261-86-3, NUDOCS 8603110192
Download: ML14175B359 (3)


Text

p REG(

UNITED STATES

NUCLEAR REGULATORY COMMISSION Al

REGION II

101 MARIETTA STREET, )

ATLANTA, GEORGIA 30303 Report No.:

50-261/86-03 Licensee:

Carolina Power and Light Company P. 0. Box 1551 Raleigh, NC 27602 Docket No.:

50-261 License No.:

DPR-23 Facility Name: H. B. Robinson Inspection Conducted:

Fe ry 1-3, 1986 Inspec or:

'//

I K. W. VanDyne Date Signed Approved by:_

F. Jape, Section Chief V

Date Signed Test Programs Section, Engineering Branch Division of Reactor Safety SUMMARY Scope:

This routine, unannounced inspection involved 18 inspector-hours on site in-the areas of loss of offsite power test witnessin Results:

No violations or deviations were identifie O3110192 86W0332 PDR A DOCK 05000261 0PR

B REPORT DETAILS 1. Persons Contacted Licensee Employees

  • G. Honma, Senior Specialist, Regulatory Compliance
  • F. Lowery, Manager, Operations R. Moore, Shift Foreman, Operations
  • R. Smith, Acting Plant Manager
  • J. Sturdauant, Technician, Regulatory Compliance Other licensee employees contacted included engineers, technicians, operators, and office personne NRC Resident Inspector
  • H. E. Krug, Senior Resident Inspector
  • Attended exit interview 2. Exit Interview The inspection scope and findings were summarized on February 3, 1986, with those persons indicated in paragraph 1 above. The inspector described the areas inspected and discussed in detail the inspection finding No dis senting comments were received from the license The licensee did not identify as proprietary any of the materials provided to or reviewed by the inspector during this inspectio. Licensee Action on Previous Enforcement Matters This subject was not addressed in the inspectio. Unresolved Items Unresolved items were not identified during the inspectio. Loss of Offsite Power Test Witnessing (70316)

The inspector witnessed Operations Surveillance Testing (OST)

on February 1-2, 1986. The testing consisted of the following:

-

OST-162, Emergency Diesel Generator Auto Start on Loss of Power and Safety Injection - Emergency Diesel Trips Defea OST-163, Safety Injection Tes Because these two tests have common prerequisites, they were performed in series beginning with the safety injection tes To ensure the adequacy of the testing, the following items were reviewed and observed:

a. Satisfactory completion of the procedures would fulfill the require ments of Technical Specifications 3.1.1.3.c.2, 4.5.1.1, 4.5.1.2, 4.6.1.2, 4.6.4, 4.15.2.b, Table 3.5-3 Item N.a, Table 4.1-1 Item No. 32.a, Table 4.1-3 Item 5, and Table 4.8-1 Item b. Testing was conducted in accordance with approved procedure c. Latest revision of the test procedure was available and in use by testing personne Required test equipment was calibrated and in servic e. Test prerequisites were me f. Minimum crew requirements were met and test personnel were properly briefe Data were collected for final analysi h. Test results indicated preliminary acceptance criteria were met or properly documente No violations or deviations were identified in the areas inspected.