2CAN029602, Discusses Leakage Detection Sys Consistent W/Recommendations of Reg Guide 1.45

From kanterella
Jump to navigation Jump to search

Discusses Leakage Detection Sys Consistent W/Recommendations of Reg Guide 1.45
ML20100P447
Person / Time
Site: Arkansas Nuclear Entergy icon.png
Issue date: 02/29/1996
From: Mims D
ENTERGY OPERATIONS, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
RTR-REGGD-01.045, RTR-REGGD-1.045 2CAN029602, 2CAN29602, TAC-M90610, NUDOCS 9603110195
Download: ML20100P447 (2)


Text

_

b

, coi o og. oooc.

.i 8 'NTERGY E uusa m Relalle Afl 72301

/ Ici 501853-5000 l

l February 29,1996 2CAN029602 U. S. Nuclear Regulatory Commission Document Control Desk Mail Station PI-137 I Washington, DC 20555

Subject:

Arkansas ' Nuclear One - Unit 2 Docket No. 50-368

+ License No. NPF-6 I' ANO-2 Reactor Coolant System Leak Detection Additional Information - TAC No. M90610 Gentlemen: ,

By letter dated September 16, 1994 (2CAN099402), Entergy Operations provided information which demonstrated that the Arkansas Nuclear One, Unit 2 (ANO-2) leakage, detection systems are consistent with the recommendations of Regulatory Guide 1.45. The Staff did not agree with conclusions regarding the capability and sensitivity of the containment sump level instmmentation as it related to detecting a one gallon per minute (gpm) reactor i coolant pressure boundary leak in one hour. )

During the most recent refueling outage, additional points were added to the plant computer monitoring system which included sump level. A rate-of-change algorithm which calculates sump level increase once per minute was also installed on the plant computer monitoring I system. When a sump level increase equivalent to one gpm is detected, an alarm is generated l on the plant computer monitoring system. This alarm will assist the operator in detecting a i one gpm sump level increase within one hour and will be available when the plant computer l monitoring system is operable.

Should you have any questions, please contact me.

0700W

\

9603110195 960229 PDR P

ADOCK 05000360 pon

)i y i l

.t ,

d .. . U. S.FRC February 29,1996 2CAN029602 Page 2 l

Very truly yours,

<h Yl

  • Dwight C. Mims Director, Nuclear Safety DCM/nbm l

cc: Mr. Leonard 1 Callan Regional Administrator

U. S. Nuclear Regulatory Commission Region IV 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-8064 l NRC Senior Resident Inspector Arkansas Nuclear One l P.O. Box 310 London, AR 72847 Mr. George Kalman NRR Project Manager Region IV/ANO-1 & 2 l U. S. Nuclear Regulatory Commission NRR Mail Stop 13-H-3 One White Flint North 11555 Rockville Pike Rockville, MD 20852 Mr. Bill LeFave '

l U. S. Nuclear Regulatory Commission One White Flint North 11555 Rockville Pike Rockville, MD 20852 l

4

)