Finding | |
|---|---|
| Title | Failure to account for elevated battery room temperature effects on battery service life. |
| Description | The team identified a finding of very low safety significance (Green) involving a non-cited violation of 10 CFR Part 50, Appendix B, Criterion XI, Test Control, because Entergy did not verify the adequacy of the safety-related battery test program. Specifically, Entergy did not adequately account for the effects of elevated temperature in the immediate vicinity of the No. 33 125 volts, direct current (Vdc) battery to ensure accurate and up-to-date determination of the batterys expected service life, in accordance with the vendor manual. After identification, Entergy entered this issue into the corrective action program and contacted the battery vendor for additional guidance. The performance deficiency was determined to be more than minor because it was associated with the design control attribute of the Mitigating Systems Cornerstone and adversely affected the cornerstone objective of ensuring the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. The team evaluated the finding in accordance with IMC 0609, Appendix A, The Significance Determination Process for Findings at Power, Exhibit 2 Mitigating Systems Screening Questions. The finding was determined to be of very low safety significance because it was a design deficiency confirmed not to result in a loss of operability. This finding was not assigned a cross-cutting aspect because it was a historical design issue not indicative of current performance. Specifically, the associated vendor technical manual guidance was not changed within the last 3 years and there was no recent operating experience that was directly applicable to the performance deficiency. |
| Site: | Indian Point |
|---|---|
| Report | IR 05000286/2015007 Section 1R21 |
| Date counted | Sep 30, 2015 (2015Q3) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.21 |
| Inspectors (proximate) | D Werkheiser G Nicely J Ayala J Brand J Schoppy M Orr M Yeminy P Krohn |
| Violation of: | 10 CFR 50 Appendix B Criterion XI |
| INPO aspect | |
| ' | |
Finding - Indian Point - IR 05000286/2015007 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Indian Point) @ 2015Q3
Self-Identified List (Indian Point)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||