Finding | |
|---|---|
| Title | Inadequate Alternative Post-Fire Safe Shutdown Procedure |
| Description | The team identified a finding of very low safety significance, involving a non-cited violation of Indian Point Unit 3 Facility Operating License Condition 2.H, for failure to implement and maintain in effect all provisions of the approved Fire Protection Program. Specifically, Entergy did not have an adequate post-fire operating procedure for its alternative shutdown capability to ensure that post-fire SSD equipment was isolated from the effects of fire in Appendix R,Section III.G.3, fire areas. Entergy entered this issue into its corrective action program and revised its operating procedures prior to the end of this inspection. This finding was more than minor because it was similar to Example 3.k of NRC IMC 0612, Appendix E, Examples of Minor Issues, and was associated with the Protection Against External Factors (e.g., Fire) attribute of the Mitigating Systems Cornerstone and affected the objective to ensure the reliability and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). The team performed a Phase 3 SDP analysis, in accordance with NRC IMC 0609, Appendix F, Fire Protection SDP. This finding affected the post-fire SSD category, and screened to very low safety significance. The team determined that this issue was of very low safety significance because of the low frequency of a fire, a negligible chance of control room evacuation, and the low chance of core damage associated with those fire areas where a fire could damage the charging system and make it unavailable. This finding did not have a cross-cutting aspect because it was a legacy issue and was considered to not be indicative of current licensee performance. |
| Site: | Indian Point |
|---|---|
| Report | IR 05000286/2014011 Section 4OA5 |
| Date counted | Mar 31, 2015 (2015Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | |
| Inspectors (proximate) | J Patel J Richmond J Rogge W Schmidt |
| Violation of: | License Condition - Fire Protection License Condition |
| INPO aspect | |
| ' | |
Finding - Indian Point - IR 05000286/2014011 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Indian Point) @ 2015Q1
Self-Identified List (Indian Point)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||