Finding | |
---|---|
Title | Untimely Corrective Actions for Degraded Fire Protection Piping Results in Piping Break |
Description | The inspectors identified a self-revealing NCV of license condition 2.K. because Entergy did not take adequate corrective actions for degraded fire protection piping in the Unit 1 turbine building. This issue contributed to excessive leakage and failure of a 10-inch high-pressure fire protection spool piece. Depressurization and isolation of this leak resulted in loss of high-pressure fire water to Unit 2 until compensatory measures could be established after about two hours. Entergy entered this issue into their CAP as CR-IP2-2014-6668, repaired the piping section, and is prioritizing repairs to other sections of degraded piping. This finding is greater than minor because it adversely affected the Mitigating Systems cornerstone objective to ensure the availability and reliability of systems (fire protection system) that provide protection against external events (fire) when all the fire protection pumps were secured to isolate the failed piping. This finding was evaluated using IMC 0609, Appendix F, Fire Protection Significance Determination Process, question 1.4.7, Fire Water Supply. It was found to be of very low safety significance because at least 50 percent of the fire water capacity (5500 gpm) remained available when the leak occurred. The inspectors determined that this finding had a cross-cutting aspect in Problem Identification and Resolution, Resolution, because Entergy did not take effective corrective actions to address issues in a timely manner commensurate with their safety significance, resulting in the piping break [P.3]. |
Site: | Indian Point ![]() |
---|---|
Report | IR 05000247/2015001 Section 4OA2 |
Date counted | Mar 31, 2015 (2015Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | B Pinson G Newman J Furia J Stewart N Floyd S Chaudhary T Burns T Setzer A Burritt A Patel |
Violation of: | License Condition - Fire Protection License Condition |
CCA | P.3, Resolution |
INPO aspect | PI.3 |
' | |