Finding | |
---|---|
Title | Inadequate Fire Barrier Analysis |
Description | The team identified a finding of very low safety significance, involving a non-cited violation of Indian Point Unit 3 Facility Operating License Condition 2.H, for failure to implement and maintain in effect all provisions of the approved Fire Protection Program. Specifically, Entergy evaluated a new fire barrier and determined that it provided adequate separation between redundant SSD trains within the same fire area, but the barrier did not satisfy regulatory requirements, and was not included in the barrier surveillance program. Entergy performed a more detailed barrier evaluation prior to the end of this inspection and created a new fire area using the guidance in Generic Letter 86-10, Implementation of Fire Protection Requirements. Entergy entered this issue into its corrective action program and re-evaluated the barrier prior to the end of this inspection to verify its adequacy to withstand the hazards in the area, revised the combustible control program for adjacent areas, and added it to the barrier surveillance program. This finding was more than minor because, if left uncorrected, it could have become a more significant safety issue because combustible loading or barrier integrity may not have been adequately maintained in the future, and was associated with the Protection Against External Factors (e.g., Fire) attribute of the Mitigating Systems Cornerstone and affected the objective to ensure the reliability and capability of systems that respond to initiating events to prevent undesirable consequences (i.e., core damage). The team performed a Phase 1 SDP screening, in accordance with NRC Inspection Manual Chapter 0609, Appendix F, Fire Protection SDP. This finding affected the post-fire SSD category, and screened to very low safety significance. The team determined that it did not affect the ability to reach and maintain a stable plant condition within the first 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of a fire event because the fire barrier was not degraded during the inspection period and no postulated fires were identified that could breach the new fire barrier. This finding had a cross-cutting aspect in the area of Human Performance, Design Margins. |
Site: | Indian Point ![]() |
---|---|
Report | IR 05000286/2014011 Section 4OA5 |
Date counted | Mar 31, 2015 (2015Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | |
Inspectors (proximate) | J Patel J Richmond J Rogge W Schmidt |
Violation of: | License Condition - Fire Protection License Condition |
CCA | H.6, Design Margins |
INPO aspect | WP.2 |
' | |
Finding - Indian Point - IR 05000286/2014011 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Indian Point) @ 2015Q1
Self-Identified List (Indian Point)
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||